Hard Rock Hotel Hvac Permit Set
Hard Rock Hotel Hvac Permit Set
HB
SHEET ABBREVIATION ABBREVIATED TERM ABBREVIATION ABBREVIATED TERM 1 ALL STANDARDS AND SPECIFICATIONS ESTABLISHED IN THE CONSTRUCTION DOCUMENTS OR AS EVIDENCED IN THE BUILDING
Harry
NUMBER SHEET TITLE (E) - EXISTING HWS - HOT WATER SUPPLY
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
CONSTRUCTION SHALL GOVERN EXCEPT WHERE NOTED. baker
M0.1 GENERAL NOTES, ABBREVIATIONS, & SYMBOLS 2 ALL WORK SHALL BE IN ACCORDANCE WITH REQUIREMENTS OF GOVERNING STATE AND LOCAL FIRE AND BUILDING CODES, &
M1.1 1ST FLOOR GROUND LEVEL - HVAC
(F) - FUTURE HX - HEAT EXCHANGER
NFPA CODE 101. THESE CODES SHALL BE FOLLOWED AS A MINIMUM, PROVIDING HIGHER GRADES OF MATERIALS AND smith
(N) - NEW IAC - INSTRUMENT AIR COMPRESSOR
s a ii
M1.2 INTERMEDIATE PARKING - HVAC WORKMANSHIP WHERE REQUIRED. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE AUTHORITIES HAVING
A/C - AIR COOLED CHILLER IAS - INSTRUMENT AIR SUPPLY SUPPLY DUCT UP OR DOWN CHS CHILLED WATER SUPPLY
JURISDICTION, AND LOCAL REGULATORY AGENCIES.
M1.2.1 2ND FLOOR - HVAC ABV - ABOVE ID - INSIDE DIMENSION
3 THE DRAWINGS INDICATE GENERAL DESIGN AND ARRANGEMENT OF PIPES, DUCTWORK, EQUIPMENT, AND SYSTEMS. DRAWINGS
M1.2.3 2ND FLOOR MEZZANINE - HVAC ACC - AIR COOLED CHILLER IN - INCHES RETURN DUCT UP OR DOWN CHR CHILLED WATER RETURN ARE DIAGRAMMATIC IN NATURE, AND DO NOT INDICATE ALL REQUIRED OFFSETS, FITTINGS, ETC. FOLLOW DRAWINGS AS CLOSE
M1.3 3RD FLOOR ACCESSIBLE PARKING - HVAC ACU - AIR CONDITIONING UNIT INV - INVERT ELEVATION AS ACTUAL CONSTRUCTION AND THE WORK OF OTHER TRADES PERMITS. PROVIDE ALL MINOR INCIDENTAL ITEMS SUCH AS
M1.3.1 4TH FLOOR PARKING - HVAC AD - ACCESS DOOR KEF - KITCHEN EXHAUST FAN EXHAUST DUCT UP OR DOWN CWS CONDENSER WATER SUPPLY FITTINGS, OFFSETS, ETC. AS REQUIRED, EVEN IF NOT SPECIFICALLY SHOWN ON THE DRAWINGS, OR INDICATED IN THE architects ii
M1.3.2 5TH FLOOR PARKING - HVAC AF - AIR FOIL KSF - KITCHEN SUPPLY FAN SPECIFICATIONS. INSTALL ALL PIPING AND DUCTWORK TO BEST SUIT FIELD CONDITIONS AND COORDINATE WITH THE P L L C
INSTALLATION WORK OF OTHER TRADES. THE DRAWINGS SHALL NOT BE SCALED TO DETERMINE EXACT LOCATIONS OF PIPING
M1.3.3 6TH FLOOR PARKING - HVAC AFF - ABOVE FINISHED FLOOR KW - KILOWATT INSULATED FLEXIBLE DUCT CWR CONDENSER WATER RETURN 189 Maple Ridge Drive Metairie, LA 70001
OR DUCTWORK. (504)885−4477
M1.3.4 7TH FLOOR PARKING - HVAC AFMS - AIRFLOW MEASURING STATION KWH - KILOWATT HOUR [email protected] :−: hbsaii.com
4 THE CONTRACTOR SHALL INSPECT THE BUILDING OR WORK SITE PRIOR TO BID, TO VERIFY THAT THERE IS ADEQUATE
M1.4 8TH FLOOR - HVAC AFR - ABOVE FINISHED ROOF LAT - LEAVING AIR TEMPERATURE HWS HOT WATER SUPPLY since 1961
LINED DUCTWORK CLEARANCE FOR THE PROPOSED MECHANICAL INSTALLATION, IN THE EVENT THE CONTRACTOR HAS OBSERVED A
M1.4.1 9TH FLOOR - HVAC AHU - AIR HANDLING UNIT LBS - POUNDS DISCREPANCY, OR FORESEES A PROBLEM, HE MUST NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY. THE BID SHALL SERVE AS
M1.4.2 10TH - 12TH FLOORS - HVAC AL - ACOUSTICAL LINING LBS/HR - POUNDS PER HOUR EVIDENCE OF THE CONTRACTOR’S KNOWLEDGE OF EXISTING CONDITIONS. NO ADDITIONAL PAYMENT WILL BE MADE TO THE
SQUARE TO ROUND TRANSITION HWR HOT WATER RETURN
M1.4.3 13TH FLOOR - HVAC ALD - AUTOMATIC LOUVER DAMPER LD - LINEAR DIFFUSER CONTRACTOR FOR FIELD CHANGES REQUIRED TO COORDINATE THE EXISTING BUILDING SYSTEMS WITH NEW CONSTRUCTION
M1.4.4 14TH FLOOR- HVAC FOLLOWING THE SUBMITTAL OF BID, WITH THE EXCEPTION OF HIDDEN CONDITIONS, AND UNFORESEEN CIRCUMSTANCES, WHICH
ALT - ALTITUDE LVR - LOUVER ELBOW WITH TURNING PHWS PRIMARY HOT WATER SUPPLY MUST BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER AND THE BUILDING MANAGEMENT IMMEDIATELY WHEN
M1.4.5 15TH FLOOR - HVAC APPROX - APPROXIMATE LWT - LEAVING WATER TEMPERATURE VANES.
OBSERVED.
M1.4.6 16TH FLOOR - HVAC ARCH - ARCHITECTURAL M - MAIN AIR
RADIUS ELBOW PHWR PRIMARY HOT WATER RETURN 5 PROVIDE ALL CONCRETE PADS, SPECIAL SUPPORTS AND ANCHORING FOR ALL MECHANICAL EQUIPMENT REQUIRING SUCH.
M1.4.7 17TH FLOOR HVAC AS - AIR SEPARATOR MA - MAKEUP AIR 6 THIS CONTRACTOR IS RESPONSIBLE FOR ALL ASPECTS OF JOB-SITE SAFETY. THE ARCHITECT/ENGINEER IS NOT RESPONSIBLE
M1.4.8 18TH LEVEL - HVAC ATC - AUTOMATIC TEMPERATURE CONTROL PANEL MAT - MIXED AIR TEMPERATURE FOR MEANS, METHODS AND SAFETY MEASURES EMPLOYED BY THE CONTRACTOR IN THE INSTALLATION OF THE WORK DEPICTED
M3.1 MECHANICAL SECTIONS SPLITTER DAMPER IN DUCT RS REFRIGERANT SUCTION LINE
AVG - AVERAGE MAU - MAKEUP AIR UNIT ON THESE DRAWINGS.
M5.1 MECHANICAL DETAILS B - BOILER MAX - MAXIMUM 7 REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF PARTITIONS, WALLS, PLUMBING FIXTURES, AND GENERAL
M5.2 MECHANICAL DETAILS BD - BLOWDOWN MBD - MANUAL BALANCE DAMPER FLEXIBLE DUCT CONNECTION RL REFRIGERANT LIQUID LINE CONSTRUCTION. INSTALL ALL PIPING AND DUCTWORK TO AVOID ARCHITECTURAL FRAMING, STRUCTURAL MEMBERS, AND OTHER
HARD ROCK
CEILING DIFFUSER D DRAIN LINE PLACING SLEEVES IN FLOORS OR WALLS.
M6.1 MECHANICAL SCHEDULES BF - BELOW FLOOR MCA - MINIMUM CIRCUIT AMPS
M6.2 MECHANICAL SCHEDULES 8 CONTRACTOR SHALL X-RAY FLOOR SLAB AS NECESSARY TO CONFIRM LOCATION OF STRUCTURAL ELEMENTS AND OBJECTS
BFW - BOILER FEEDWATER MCC - MOTOR CONTROL CENTER
NA
ST
EA EXHAUST AIR PLUG VALVE
CWR - CONDENSER WATER SUPPLY RF - RETURN FAN
CWS - CONDENSER WATER RETURN RH - RELATIVE HUMIDITY
SA SUPPLY AIR GLOBE VALVE
GENERAL MECHANICAL ACOUSTIC NOTES RAYMOND E. SMITH
LICENSE. No. 36823
D - DROP OR INDIRECT DRAIN RHC - REHEAT COIL 1. NEOPRENE ISOLATION PADS SHALL BE PROVIDED AND MOUNTED UNDER AIR-COOLED CHILLERS. REGISTERED
NG
MEC
DB - DRY BULB TEMPERATURE RO - REVERSE OSMOSIS 2. NEOPRENE ISOLATION PADS SHALL BE PROVIDED AND MOUNTED UNDER ROOFTOP AIR HANDLING UNITS. PROFESSIONAL ENGINEER
RA RETURN AIR SELENOID VALVE
I
IN
ER
dB - DECIBLES RPBFP - REDUCED PRESSURE BACKFLOW PREVENTER
NI
HA
3. NEOPRENE ISOLATION PADS SHALL BE PROVIDED AND MOUNTED UNDER ALL HVAC PUMPS AND MOTORS.
DDC - DIRECT DIGITAL CONTROL RPM - ROTATIONS PER MINUTE 4. SPRING OR NEOPRENE HANGERS SHALL BE USED FOR SUSPENDING HORIZONTAL FAN COIL UNITS.. CA L ENG I NE
DEG. F - DEGREES FAHRENHEIT S - SANITARY SEWER C (CFM) CUBIC FEET PER MINUTE CHECK VALVE
5. NEOPRENE ISOLATION PADS SHALL BE PROVIDED AND MOUNTED UNDER VERTICAL FAN COIL UNITS. THIS DRAWING IS CONFIDENTIAL AND
DENS - DENSITY SA - SUPPLY AIR 6 NEOPRENE ISOLATION PADS SHALL BE PROVIDED AND MOUNTED UNDER STAIRWELL PRESSURIZATION FANS BASES. NOT BE LOANED, REPRODUCED, COPIED,
DIA - DIAMETER SAD - SUPPLY AIR DUCT AP ACCESS PANEL BUTTERFLY VALVE EITHER WHOLLY OR IN PART, OR MADE
7. NEOPRENE ISOLATION PADS SHALL BE PROVIDED AND MOUNTED UNDER ROOFTOP EXHAUST FAN HOUSINGS AND CURBS. PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
DN - DOWN SAF - SUPPLY AIR FAN FLEXIBLE CONNECTS SHALL BE USED ON THE INLET/OUTLET DUCT CONNECTION FOR EACH FAN. CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
DRN - DRAIN SCD - SMOKE CONTROL DAMPER AHU AIR HANDLING UNIT BALANCING VALVE OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
DWG - DRAWING SD - SMOKE DAMPER ARCHITECTS A PROFESSIONAL L.L.C.
DX - DIRECT EXPANSION SEC - SECOND FCU FAN COIL UNIT SIGHT GLASS
EA - EXHAUST AIR SF - SUPPLY FAN
REVISION HISTORY
EAD - EXHAUST AIR DUCT OR DAMPER SP - STATIC PRESSURE VAV VARIABLE AIR VOLUME REFRIGERANT EXPANSION VALVE
EAT - ENTERING AIR TEMPERATURE SPEC - SPECIFICATION
EDB - ENTERING DRY BULB TEMPERATURE SQ - STATIC PRESSURE REFRIGERANT ANGLE AND
OAV OUTSIDE AIR VALVE
GLOBE VALVE
EF - EXHAUST FAN SS - STAINLESS STEEL
EFF - EFFICIENCY STD - STANDARD EAV EXHAUST AIR VALVE PRESSURE REDUCING VALVE
EP - ELECTRO-PNEUMATIC SWITCH STM - STEAM
ET - EXPANSION TANK SWE - SIDEWALL EXHAUST GRILLE DDC DIRECT DIGITAL CONTROLS PRESSURE REGULATING VALVE
EWB - ENTERING WET BULB TEMPERATURE (°F) SWR - SIDEWALL RETURN GRILLE
EWT - ENTERING WATER TEMPERATURE (°F) SWS - SIDEWALL SUPPLY GRILLE UNDERCUT IN DOOR
U PRESSURE RELIEF VALVE
EXH - EXHAUST SYM - SYMBOL
EXP - EXPANSION SYS - SYSTEM
T TEMPERATURE SENSOR TEMP-PRESSURE RELIEF VALVE
F - FILTER TD - TRANSDUCER
F/SD - COMBINATION FIRE/SMOKE DAMPER TDH - TOTAL DYNAMIC HEAD
H HUMIDITY SENSOR GUAGE COCK
FA - FIRE ALARM TEMP - TEMPERATURE
FACP - FIRE ALARM CONTROL PANEL TOL - THERMAL OVERLOADS COMBINATION TEMP/HUMIDITY
FC - FLEXIBLE CONNECTION TOP - TOP OF PIPE TH PET COCK (AIR VENT)
SENSOR
FCU - FAN COIL UNIT TOR - TOP OF RACK
FD - FIRE DAMPER TOT - TOTAL CO2 CARBON DIOXIDE SENSOR DRAIN COCK
FF - FINAL FILTER TT - TEMPERATURE TRANSMITTER
FLA - FULL LOAD AMPS TWU - THRU-WALL UNIT CO CARBON MONOXIDE SENSOR EXPANSION JOINT
FLR - FLOOR TYP - TYPICAL
FPI - FINS PER INCH U.C. - UNDERCUT CTL EQUIPMENT CONTROLLER FLEXIBLE PIPE CONNECTION
FPM - FEET PER MINUTE UH - UNIT HEATER
MANUAL SWITCH WITH SPRING
FPS - FEET PER SECOND UON - UNLESS OTHERWISE NOTED M CONCENTRIC REDUCER
WOUND TIMER
FS - FLOOR SINK V - VOLTAGE S
FT - FEET VA - VALVE SP STATIC PRESSURE SENSOR ECCENTRIC REDUCER
FV - FACE VELOCITY VAV - VARIABLE AIR VOLUME
GA - GAGE or GAUGE VERT - VERTICAL DP DIFFERENTIAL PRESSURE SENSOR ∅ DIAMETER AND FLAT OVAL
GPH - GALLONS PER HOUR VFD - VARIABLE FREQUENCY DRIVE
GPM - GALLONS PER MINUTE VOL - VOLUME THIS IS A TYPICAL SCHEDULE. NOT ALL SYMBOLS ARE NECESSARILY USED ON THIS PROJECT.
GSM - GALVANIZED SHEET METAL VPE - VACUUM PUMP EXHAUST GENERAL NOTES,
H - HUMIDIFIER VT - VENT (SANITARY) ABBREVIATIONS, &
HC - HEATING COIL VTR - VENT THRU ROOF SYMBOLS
HD - HEAD W - WATTS PROJECT#: 1709
HDT - HORIZONTAL DRAW-THRU W/O - WITHOUT PHASE: PERMIT
HGT - HEIGHT WB - WET BULB TEMPERATURE (°F)
HOA - HAND-OFF-AUTO WR - WALL RETURN
TEAM: MEI
HP - HORSEPOWER WS - WALL SUPPLY CHECKER: RS
HR - HOUR(S) WT - WEIGHT SCALE: AS NOTED
HT - HUMIDITY TRANSMITTER WTR - WATER
HTP - HEAT PUMP ºF - DEGREES FAHRENHEIT ISSUED: 06/05/2018
HVAC - HEATING, VENTILATION, AND AIR CONDITIONING ΔP - PRESSURE DROP or DIFFERENTIAL CONSULTING ENGINEERS
HWR - HOT WATER RETURN ΔT - TEMPERATURE DIFFERENTIAL 909 Poydras Street, Suite 2150
New Orleans, Louisiana 70112-1034
Tel. 504-586-1725
M0.1
HB
# SHEET REFERENCE NOTES # SHEET REFERENCE NOTES # SHEET REFERENCE NOTES Harry
1 GAS METER ROOM SHALL HAVE A 5'-0" MINIMUM LOUVERED DOUBLE DOOR PER 10 0.3 SF FREE AREA OUTSIDE AIR LOUVER WITH MAX .1" WC PRESSURE DROP IN 18 INTERLOCK EXHAUST FAN WITH OVERHEAD DOOR. EXHAUST FAN SHALL RUN baker
ENTERGY REQUIREMENTS. EXTERIOR WALL. COORDINATE WITH ARCHITECTURAL. WHEN DOOR OVERHEAD DOOR IS CLOSED.
2 0.9 SF FREE AREA EXHAUST LOUVER IN EXTERIOR WALL. ROUTE EXHAUST DUCT 11 2.2 SF FREE AREA OUTSIDE AIR LOUVER WITH MAX 0.1" WC PRESSURE DROP IN 19 12"x18" TRANSFER OPENING WITH MOTORIZED DAMPER. PROVIDE TRANSFER
smith
s a ii
TO CONNECT INTO EXTERIOR LOUVER SYSTEM. EXTERIOR WALL. COORDINATE WITH ARCHITECTURAL. PROIVDE SHEET METAL GRILLE ON BOTH SIDES. INSTALL BOTTOM OF OPENING AT 0'-8" ABOVE RECEIVING
3 ROUTE RADIATOR EXHAUST DUCT TO CONNECT INTO EXTERIOR LOUVER SYSTEM. PLENUM OFF THE BACK OF THE LOUVER UNIT AS SHOWN. FLOOR. INTERLOCK DAMPER SO THAT IT OPENS WHEN EF 1-6 IS ENERGIZED.
4 CONNECT DUCT TO RADIATOR, TRANSITION TO OPENING SIZE OF LOUVER. 12 1.65 SF FREE AREA EXHAUST AIR LOUVER WITH MAX .1" WC PRESSURE DROP 20 INSTALL CO SENSOR 6'-0" ABOVE FINISHED FLOOR. ROUTE WIRE FOR SENSOR IN
5 1 SF FREE AREA EXHAUST LOUVER WITH MAX 0.1" WC PRESSURE DROP IN AT1305 CFM IN EXTERIOR WALL. COORDINATE WITH ARCHITECTURAL. PROIVDE METAL CONDUIT.
EXTERIOR WALL. ROUTE EXHAUST DUCT TO CONNECT INTO EXTERIOR LOUVER SHEET METAL PLENUM OFF THE BACK OF THE LOUVER UNIT AS SHOWN. 21 18"x36" TRANSFER OPENING WITH MOTORIZED DAMPER. PROVIDE TRANSFER
SYSTEM. 13 0.4 SF FREE AREA MAKE UP AIR LOUVER WITH MAX 0.1" WC PRESSURE DROP IN GRILLE R2 ON BOTH SIDES. INSTALL OPENING WITHIN CEILING CAVITY OF architects ii
EXTERIOR WALL. COORDINATE WITH ARCHITECTURAL. PROIVDE GRAVITY DAMPER ADJACENT SPACE. INTERLOCK DAMPER SO THAT IT OPENS WHEN EF-1-5 IS P L L C
6 1.3 SF FREE AREA EXHAUST LOUVER SIZED FOR MAX 0.1" WC PRESSURE DROP.
ON BACK END OF UNIT. ENERGIZED. 189 Maple Ridge Drive Metairie, LA 70001
7 1.3 SF FREE AREA MAKE UP AIR LOUVER SIZED FOR MAX 0.1" WC PRESSURE (504)885−4477
DROP. PROVIDE GRAVITY SHUTTER DAMPER ON THE BACK END OF UNIT. 14 2.3 SF FREE AREA MAKE UP AIR LOUVER WITH MAX 0.1" WC PRESSURE DROP IN 22 INSTALL BOTTOM OF ELECTRIC WALL HEATER AT 8'-0" ABOVE FINISHED FLOOR. [email protected] :−: hbsaii.com
EXTERIOR WALL. COORDINATE WITH ARCHITECTURAL. PROIVDE SHEET METAL 23 0.4 SF FREE AREA LOUVER WITH MAX .1" WC PRESSURE DROP AT 315 CFM IN
8 1 SF FREE AREA MAKE UP AIR LOUVER WITH MAX 0.1" WC PRESSURE DROP. PLENUM OFF THE BACK OF THE LOUVER UNIT AS SHOWN. since 1961
PROVIDE AUTOMATIC DAMPER TO THE BACK END OF THE UNIT. DAMPER SHALL BE EXTERIOR WALL. COORDINATE WITH ARCHITECTURAL. PROIVDE SHEET METAL
INTERLOCKED TO OPEN WHEN GENERATOR AND/OR EXHAUST FAN IS ACTIVATED. 15 4.3 SF FREE AREA MAKE UP AIR LOUVER WITH MAX 0.1" WC PRESSURE DROP IN PLENUM OFF THE BACK OF THE LOUVER UNIT AS SHOWN.
EXTERIOR WALL. COORDINATE WITH ARCHITECTURAL. 24 22 SF FREE AREA KITCHEN EXHAUST LOUVER WITH MAX 0.1" WC PRESSURE DROP
9 75 SF FREE AREA MAKE UP AIR LOUVER WITH MAX 0.1" WC PRESSURE DROP.
LOUVER WILL CONSIST OF MULIPLE SECTIONS WITH A MULLION. PROVIDE 16 0.3 SF FREE AREA MAKE UP AIR LOUVER WITH MAX 0.1" WC PRESSURE DROP IN IN EXTERIOR WALL. COORDINATE WITH ARCHITECTURAL. PROIVDE SHEET METAL
AUTOMATIC DAMPER TO THE BACK END OF THE UNIT. DAMPER SHALL BE EXTERIOR WALL. COORDINATE WITH ARCHITECTURAL. PLENUM OFF THE BACK OF THE LOUVER UNIT AS SHOWN.
INTERLOCKED TO OPEN WHEN GENERATOR IS ACTIVATED. 17 17 SF FREE AREA MAKE UP AIR LOUVER WITH MAX 0.1" WC PRESSURE DROP IN 25 .07 SF FREE AREA EXHAUST LOUVER WITH MAX 0.1" WC PRESSURE DROP IN
EXTERIOR WALL. COORDINATE WITH ARCHITECTURAL. PROIVDE SHEET METAL EXTERIOR WALL. ROUTE EXHAUST DUCT TO CONNECT INTO EXTERIOR LOUVER
PLENUM OFF THE BACK OF THE LOUVER UNIT AS SHOWN. SYSTEM.
1,835 CFM
3425 CFM
160 CFM
7"ø
71 51 71 59 62 61 60 63 58 57 64
(690) TYP 4
14"x12" TYP 2 CU 1.5-1
18"x18" AHU-3 8"ø UP
94
10"ø LOADING
POS
10"ø
TRASH
TRASH
9"ø PTE80-A
PTE80-A
81
100 RETAIL
FCU 1-2
VAV 1-2
14"x14"
95
Room 124
VAV 1-4 50 52 56 52 50
10"ø 229 10"ø
12"x10"
8"ø AHU-2 84
20"x20"
10"ø S1 S1 96
FCU 1-3 16"x12" 50 CFM
16"ø 5"ø
93
EUH-1-3 22
(160) Room (220) CONSTANT
91 85
REST.
28"x28" 50 52 56
TYP 7
52 50
TRASH
TRASH
88 83
PTE80-A
PTE80-A PTE80-A
PTE80-A
EF 1-4 6"ø
TYP 6
20"x20"
VAV 1-1 S1
VAV 1-3 64 57 58 63 60 61 62 59 64 57 58
(150) 12"ø
8"ø 89 92
EUH 1-2
12"ø TYP 10 12"x12" 5
S1
14"x14" 12"x12" 6"ø 800 CFM
VAV 2-3 (200)
22"x22"
8"ø SESSIONS 9
20"x20"
S1 VAV 1-5 8"ø 126 TYP 5 EF 1-3
(180) 21
18"x16"
120"x120"
S1 TYP 2 3
20"x20"
FD
S1 107 120"x120" 12"x12"
S1 (100)
8"ø
STAIR 1 S1 S1
(165) 147 (40) FD
Room (140) 2
28"x28"
MAIN LOBBY
TYP 6 5"ø 234 RECEVING Room 8
AND CHECK IN TYP 6 18"x18"
14"x12"
110 102 241
Room
233 THESE PLANS AND SPECIFICATIONS HAVE
S1 Room 800 CFM BEEN PREPARED BY ME OR UNDER MY
(90) 235 8"ø 10"ø CLOSE PERSONAL SUPERVISION AND TO
4"ø FD 24"x24" THE BEST OF MY KNOWLEDGE AND
28"x10" CONDO FD BELIEF THEY COMPLY W ITH ALL CITY,
13 7 STATE AND FEDERAL REQUIREMENTS, AND
S1 ELEVATOR S2 VAV 2-2 Room
D
I AM NOT PROVIDING CONTRACT
LOBBY (25) 245 TRASH PUMP ROOM
PTE68-B
(60) ADMINISTRATION.
D
146 123 122
FILE ROOM CERTIFIED CORRECT
Room 2 1040 CFM ELECTRICAL
CH
109
D D
C
242 M8.1 EUH 1-1 VAULT
C
LO
10"ø FCU 1-8 6
120
TE OF U I S I A
Room FD 24"x24" A
NA
ST
VAV 1-7 4"ø 228 8"x8" S1 R1 R2 14"x12" 6
Room (2225) 1040 CFM
5"ø 10"ø (40) (455)
RAYMOND E. SMITH
FD
S1 247
4"ø S1 6"ø (TYP.)
(25) FD VAV 3-4 12"x10" 26"x10" EF 1-2 7 LICENSE. No. 36823
6"ø (110)
5"ø FD REGISTERED
NG
14"x14"
MEC
5"ø Room
R1 6"ø R1 6"ø S1 8 PROFESSIONAL ENGINEER
R1 244 24"x18"
I
VAV 3-3 5"ø 12"x12" IN
ER
(2225) 5"ø VAV 2-4
NI
HA
CA L ENG I NE
S1 (25) (195) 10"x10" (50)
6"ø
TYP AV EQUIP S1
R1 A/C 1-1 (105) R1 10"x10"
FD
129 R1
(55)
(840) FRONT OFFICE (195) 8"ø (200) 13600 CFM
AHU-1 4"ø 8"ø 12"x10" 8"ø S4 GAS METERS THIS DRAWING IS CONFIDENTIAL AND
28"x28" WORK AREA Room Room Room Room Room WOMEN R1 8"x8" 1 NOT BE LOANED, REPRODUCED, COPIED,
103 (1375) 107
255 248 249 113 (200) FD 17 EITHER WHOLLY OR IN PART, OR MADE
S1
250 251 Room Room Room Room
8"x8" PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
16"x12"
12"x12"
MANAGER Room 118
(110) KEH-5 S1 (175) 238 19
112 REVISION HISTORY
TYP 4
42"x20"
26"x14" (110)
12"x10" R2 11
6"ø (315) FD
05/18/18
BIB
TYP 2
SODA 12"ø 12
PRIVATE CONDO CONDO 20 CO
ENTRANCE AND STORAGE KEF-2 FD
MAIL 104 S1
FD
101 ELECT. S1 13
KEH-6 (535)
12"x10" EF 1-1 143 (165) 12"x12"
MAU 1-1 42"x20"
RECEIVING
14
18"x8" 12"x12" OFFICE S1 EF 1-6 LOADING
18"x8" 600 CFM
22"x20"
R1 119 (370)
103
20"x20"
16"x4" 18
(50)
DEF-1 S1 315 CFM
D EMP. REST. MAU 1-2
144 (50) 24
H H
12"x12" T
EUH-1-4 22
17600 CFM
15
EXIT CORRIDOR
22"x20" 23
2 106
Room M3.1 30"x36"
240 EMPLOYEE R1
CHECK IN (500)
32"x16"
KEF-1A 117
KEH-2
KITCHEN
116 40"x18"
FCU 1-6
S4
FCU 1-5 Room (1100)
UPDATE
239
16"x16" 30"x12"
36"x16"
1
COOLER COOLER BEER COOLER FREEZER 16"x16"
FCU 1-7 17 1ST FLOOR GROUND
S1 FIRE COMMAND
(400) 115
LEVEL - HVAC
PROJECT#: 1709
A B C D E F G H K L N Q R T V W PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
1 0.04 SF FREE AREA OUTSIDE AIR LOUVER WITH MAX .1" WC PRESSURE DROP IN
EXTERIOR WALL. COORDINATE WITH ARCHITECTURAL.
2 0.07 SF FREE AREA LOUVER WITH MAX .1" WC PRESSURE DROP IN EXTERIOR
WALL. COORDINATE WITH ARCHITECTURAL.
architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
2
4"ø
CU 1-3 SF 1.5-1
4"ø
CU 1.5-1 4"ø
FCU FCU
1.5-1 1.5-2
3
EF 1.5-1 2
50 CFM
6"ø
1 1/4"CHWS
1 1 1/4"CHWR
M8.1 4
6"CHWR DN
NA
ST
12"x12" 8
RAYMOND E. SMITH
7 LICENSE. No. 36823
REGISTERED
NG
MEC
PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
CA L ENG I NE
THIS DRAWING IS CONFIDENTIAL AND
NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
2 1/2"CHWR
9
2 1/2"CHWS
3/4"CHWR REVISION HISTORY
3/4"CD 11
3/4"CHWS 3/4"CHWS
1 1/2"CHWS
3/4"CD 12
1 1/2"CHWR 3/4"CHWR
13
14
3/4"CHWR
3/4"CD
15
1 1/4"CHWS
3/4"CHWS 1"CHWS
2 3/4"CD
M3.1 1"CHWR 1 1/4"CHWR
3/4"CHWR
3/4"CHWS
3/4"CHWS 30"x12"
3/4"CHWR
17 INTERMEDIATE PARKING -
3/4"CHWR 1 1/4"CHWS
HVAC
3/4"CHWS 1 1/4"CHWR
PROJECT#: 1709
A B C D E F G H K L N Q R T V W PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
1. 5.4 SF FREE AREA LOUVER WITH MAX 0.1" WC PRESSURE DROP IN EXTERIOR
WALL. COORDINATE WITH ARCHITECTURAL.
2. .8 SF FREE AREA LOUVER WITH MAX 0.1" WC PRESSURE DROP IN EXTERIOR WALL.
COORDINATE WITH ARCHITECTURAL.
3. .4 SF FREE AREA LOUVER WITH MAX 0.1" WC PRESSURE DROP IN EXTERIOR WALL.
COORDINATE WITH ARCHITECTURAL. architects ii
4. 1.1 SF FREE AREA LOUVER WITH MAX 0.1" WC PRESSURE DROP IN EXTERIOR P L L C
WALL. COORDINATE WITH ARCHITECTURAL. 189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
5. 4.6 SF FREE AREA LOUVER WITH MAX 0.1" WC PRESSURE DROP IN EXTERIOR [email protected] :−: hbsaii.com
WALL. COORDINATE WITH ARCHITECTURAL. since 1961
6. 4.9 SF FREE AREA LOUVER WITH MAX 0.1" WC PRESSURE DROP IN EXTERIOR
WALL. COORDINATE WITH ARCHITECTURAL.
7. .5 SF FREE AREA LOUVER WITH MAX 0.1" WC PRESSURE DROP IN EXTERIOR WALL.
COORDINATE WITH ARCHITECTURAL.
8. MOTORIZED DAMPER WIRED TO AHU-4 TO BE OPEN WHEN UNIT IS ON.
24"x18"
16"x16" 12"ø 12"ø
16"x16" 24"x20"
14"x14"
50"x32" 12"x16" 26"x10"
12"ø
14"x16" 18"x16" 26"x10" S3 50"x32" 18"x16" 14"x16"
12"ø
(875)
TYP 2 L5 3
24"x16"
16"x16"
L5
12"ø
12"ø (840)
(840) S1
24"x16"
BALLROOM MEETING ROOM MEETING ROOM TYP 5
TYP 5 (525) 203 204 VAV 6-6
MEETING
14"x14"
201 12"ø 12"ø TYP 4
S1 14"ø
18"x16"
32"x16"
18"x14"
(550) 14"ø VAV 6-1
VAV 5-1 VAV 5-6 16"x16"
16"ø
30"x16" TYP 3 EG-1
VAV 5-2 VAV 5-5 PREFUNCTION 14"x6" VAV 6-2
AREA S1 S1 12"ø (400)
FCU 2-3 6"x4" 8.
202 (550) (550)
14"ø
18"x8"
EG-1
26"ø
R2 18"x8"
20"x16" (400) A/C 2-1
50"x32" (75)
TYP 2 MDF ROOM
EF 2-2
14"ø
14"ø 14"x16" JANITOR 14"x6" 237
12"ø 240
8"x8"
16"ø
14"ø
12"ø
L6 VAV 5-7 205 L6
SEE M1.2.3 FOR CONTINUATION (600)
(540)
(130)
TYP 8
28"ø
TYP 8
28"ø
S4
8009 32"x16" ELEVATOR
LOBBY
234 THESE PLANS AND SPECIFICATIONS HAVE
S1 BEEN PREPARED BY ME OR UNDER MY
CLOSE PERSONAL SUPERVISION AND TO
18"x16" 32"x16" 20"ø 18x18 STAIR (455) 18"x16" 20"ø 20"ø 32"x16" 18"x16"
8"ø
CIRCULATION 12"ø THE BEST OF MY KNOWLEDGE AND
PRESSURIZATION
28"x12" TYP 5 235
BELIEF THEY COMPLY W ITH ALL CITY,
VAV 5-3 UP & DN STAIR S4 VAV 6-3 STATE AND FEDERAL REQUIREMENTS, AND
FCU
20"ø
I AM NOT PROVIDING CONTRACT
(265)
20"ø
PRESSURIZATION ADMINISTRATION.
18"x8"
2-14
AHU-5 CERTIFIED CORRECT
20"x16"
2
FCU M8.1 VAV 6-4 LO
6 E OF U I S I A
VAV 5-4 2-16
S3 S4 12"ø AT
NA
ST
4" CHWS & CHWR-DN (600) (130)
TYP 3 8
14"x16"
RAYMOND E. SMITH
32"x16"
32"x16"
L6
26"x10"
12"x12"
LICENSE. No. 36823
12"ø STAIR REGISTERED
NG
MEC
(510) 22"x22" PROFESSIONAL ENGINEER
PRESSURIZATION
I
TYP 8 IN
ER
KITCHEN
NI
HA
CA L ENG I NE
S4 BALLROOM L6
233 12"ø
(525) 231
(450)
TYP 4 TYP 8
MECHANICAL THIS DRAWING IS CONFIDENTIAL AND
S1 WALK-IN 232 NOT BE LOANED, REPRODUCED, COPIED,
COOLER
18"x16" 24"x16" (225) 22"x22" 50"x32" 24"x16" 18"x16" EITHER WHOLLY OR IN PART, OR MADE
DOAS
50"x18"
PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
S4 2-1 CONSENT OF HBSA II ARCHITECTS,
18"x14" S4 (440) A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
50"x32" OR INVENTION ARE RESERVED AND WILL
24"x16"
FD BOH 3 (540) 18"x12" REMAIN THE SOLE PROPERTY OF HBSA II
206 S3 ARCHITECTS A PROFESSIONAL L.L.C.
FCU TYP 3
20"x14" S4 2-17 (700) 9
WALK-IN TYP 3
(45) COOLER FCU 5. REVISION HISTORY
26"/10"
42"x12" 2-18 22"x22" 11
18"x8" S4
18"x8"
(3695)
DEF-3 28"x12" (230)
S4 S4 4"x4" 50"x18" 12
28"x10" (TYP. OF 12) FCU
(85) PR & MARCOM (100) S4
14"x6" 16"x6" 16"x8" 18"x8" 2-12
MANAGER 6"x6" (115) S4
FOOD TRANS.
209 S4 208 S4 S4
S4
8"ø S4 (230) 13
FCU 2-4 (125) SESSIONS
(35) S4 (35) S4 BANQUET (60) 8"ø (60)
S4 OFFICE CHAIR STORAGE
(20) (145) MANAGER 14
12"x6"
S4 221
S4 (110) FOOD & BEV.
228 229
8"ø S4 TYP 2 (110) FCU BANQUET SET
FOOD TRANS. (45) COPY AREA UP 18"x8"
BANQUET ASST. 208 S4 (95) 2-10 224 230
6"ø
MANAGER S4 (95) BEVERAGE
8"ø S4 210 FCU CATERING FCU 2-9 OFFICE 2.
(85) (255) 2-15 MANG. 227
R2 S4 S4 (600)
S4 223 S4 S4
(200) MENS BANK DIRECTOR
S4 (90) Room (40) (95)
(230) 15
CONVENTION
Room S4 220 222 (95) STOR. S4 S4 FCU (400)
S4 258 Room TYP 2 (95)
224
226 DEF-2
SERV. (95) 8"ø (120) (230) 2-11
259 8"ø 7.
(85) MANAGER 2
211 M3.1
14"x6" 14"x6"
FCU 2-5
EF 2-1
ASST. GROUP
8"ø SALES
STAIR 2
219
212
S4
(85)
S4
S4
(1100)
S4 (300)
(85) Room
257
ASST. TRANS. FCU 2-8
SALES 30"x12"
213
S4 STORAGE
(205) 217
DIR. REVENUE RESERV. ECOMMERCE
MANA. MANAGER MANAGER 8"ø
215
214 S4 216 S4 S4
S4 (85) FCU 2-6 17 2ND FLOOR - HVAC
(85) (55)
(85) S4
(35) 8"ø
18"x12" PROJECT#: 1709
A B C D E F G H K L N Q R T V W
FCU 2-7 PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
architects
P L L C
ii
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
T1 T1 DIR. OF OPER.
(170) (330) M144 3
EXEC. ADMIN. G.M. FCU FCU
M142 M143 2.5-14 CONFERENCE
2.5-13 M145
S4 S4 S4
(170) (160) (160)
7"ø 20"/8"
S2 CONFERENCE
EXEC. LOBBY S4 T1 M145
(650)
M141 (445) (445)
SEE M1.2.1 FOR CONTINUATION
1
M8.1 50"x30" 4
6" CHWS
DIRECT. SALES
M136 MARKET EXEC. GROUP SALES
M137 M138
T1 T1
AHU-4
(265) (535) 2"CHWS
S4 S4 S4
2"CHWR FCU
(265) (270) (240) THESE PLANS AND SPECIFICATIONS HAVE
BEEN PREPARED BY ME OR UNDER MY
2.5-8 CLOSE PERSONAL SUPERVISION AND TO
8"ø 18"/8" 2" CHWS/CHWR UP THE BEST OF MY KNOWLEDGE AND
BELIEF THEY COMPLY W ITH ALL CITY,
STATE AND FEDERAL REQUIREMENTS, AND
FCU I AM NOT PROVIDING CONTRACT
28x12 STAIR
2.5-12 ADMINISTRATION.
PRESSURIZATION
2 CERTIFIED CORRECT
UP & DN
16"/8" 20"/8" M8.1
LO
S4 T1 S4 STOR 6
TE OF U I S I A
T1
FCU S4 (145) (470) (105)
M139
FCU 12"x12" A
NA
ST
(600) S2
2.5-5 S4 (320) FCU 2.5-11
(900)
(105) TYP 2 2.5-16
8 RAYMOND E. SMITH
S4 SHOP HR MANAGER HR FILES 7 LICENSE. No. 36823
S4 M134 S4 M135 REGISTERED
6"x5"
NG
(540) M101 28x12 STAIR
MEC
(140) (135) PROFESSIONAL ENGINEER
14"/8"
PRESSURIZATION
I
IN
ER
S4 NI
HA
CA L ENG I NE
34"x6" T1 UP & DN
20"/8"
8"x6"
(985) (135)
T1
DOAS (600) S4 S4 THIS DRAWING IS CONFIDENTIAL AND
S4 2.5-1 (150) (150) NOT BE LOANED, REPRODUCED, COPIED,
20"/8"
20"x8"
M102 HR DIRECTOR
(460) S2 M132 36"x10" S4 2.5-3 2.5-19 11
FCU-F (105)
(900) (55)
12"/8"
OFFICE
CASHIER
M127
1 1/2" CHWR S4 PAYROLL S4 12
FCU-F FCU S4M128 S4
(100) 14"x6" 14"x6" T1 (230) T1
3/4" CD 2.5-4 S4 S2 (155) (135)
S4 S4 (460) (135)
1 1/2" CHWS (425) (15) T1 T1
(900) S4 13
STOR & AV (115) (230) 10"/8" 12"/8"
TREAT.2 RACKS MENS (455) (145) DIRECTOR
M104 WOMENS OFFICE T1 FCU S4 M126
S4 M111 M112 S4 14
M113 M114 (145) 2.5-9 VIBE MANAGER (135) S4
(35)
STO. S4 SUPPORT S4 M121 T1 (230)
1 1/2" CHWS
10"/8"
M107 (145) M116 SUPPORT (230) FINANCE (250)
1 1/2" CHWR FCU S4 S4 S4 S4 S4M117 (145)
M124 T1
2.5-7 (220) (260) (125) (310) (310) S4 FCU
SERV. CORR. CASH CONTROL (145)
3/4" CD (240) 12"/8" 10"/8" 2.5-18
M108 M123
20"/8" 9"/8" OFFICE 7"ø 12"/8" 12"/8" 7"ø OFFICE S4
S4 S4 M122 (240) S4 S4 15
TREAT.3 TREAT.4 M115
M105 FCU-F FCU-F M106 R1 (220) 7"ø 12"/8" 12"/8" 7"ø (230) OFFICE (380) 7"ø (145)
STORAGE (500)
S4 T1 (150) M120 M125
T1 T1 1.
(245) (385) 14"x6" 2 14"x6" 14"x6" T1
(600) M3.1 S4 T1 (240)
R1 T1 FCU (380)
T1 (175) (220) S4 STORAGE T1 (180) STORAGE (230) 2.5-15 14"x6"
(245) (180) FCU EF 2.5-1
(TYP. OF 2) M118 (410) M119
2.5-10
S4
(930)
8"ø
GYM
M109
S4 S4 S4
(540) (540) (540)
30"/8" FCU
2.5-6
S4 S4 S4 GYM STORAGE
(460) S4 M110
(460) (460) (325)
17 2ND FLOOR MEZZANINE -
HVAC
PROJECT#: 1709
A B C D E F G H K L N Q R T V W
PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
COORDINATE WITH ARCHITECTURAL.
2. 13.8 SF FREE AREA LOUVER WITH MAX 0.1" WC PRESSURE DROP IN EXTERIOR
WALL. COORDINATE WITH ARCHITECTURAL.
3. CONNECT CHWS AND CHWR PIPES TO UNIT AND ROUTE CONDENSATE TO
NEAREST HUB DRAIN. COORDINATE WITH PLUMBING FOR LOCATION OF NEAREST
HUB DRAIN. PROVIDE PUMP WHERE ELEVATION OF HUB DRAIN IS ABOVE DRAIN architects ii
OUTLET ON THE UNIT. TYPICAL ALL HVAC UNITS. P L L C
4. CONNECT REFRIGERANT PIPES TO UNIT AND ROUTE CONDENSATE TO NEAREST 189 Maple Ridge Drive Metairie, LA 70001
HUB DRAIN. COORDINATE WITH PLUMBING FOR LOCATION OF NEAREST HUB (504)885−4477
[email protected] :−: hbsaii.com
DRAIN. PROVIDE PUMP WHERE ELEVATION OF HUB DRAIN IS ABOVE DRAIN
OUTLET ON THE UNIT. TYPICAL ALL HVAC UNITS. since 1961
CU 2-2 CU 2-1
2"CHWS
THESE PLANS AND SPECIFICATIONS HAVE
2" CHWS/CHWR DN BEEN PREPARED BY ME OR UNDER MY
CLOSE PERSONAL SUPERVISION AND TO
THE BEST OF MY KNOWLEDGE AND
BELIEF THEY COMPLY W ITH ALL CITY,
STATE AND FEDERAL REQUIREMENTS, AND
I AM NOT PROVIDING CONTRACT
28x12 STAIR ADMINISTRATION.
PRESSURIZATION CERTIFIED CORRECT
2"CHWR 2
UP & DN M8.1
LO
6
TE OF U I S I A
12"x12" A
NA
ST
8 RAYMOND E. SMITH
7 LICENSE. No. 36823
CU 1-1 REGISTERED
NG
MEC
PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
CA L ENG I NE
28x12 STAIR THIS DRAWING IS CONFIDENTIAL AND
PRESSURIZATION NOT BE LOANED, REPRODUCED, COPIED,
UP & DN EITHER WHOLLY OR IN PART, OR MADE
PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
R2 9
(50) REVISION HISTORY
11
1.
50"x18"
EF-A 12
STOR (8800)
309 MAU-3
34"x20"
13
FCU 3-1
KEF-3 CU 3-3 14
3.
IT WORK 34"x26"
STATION 34"x20"
OSBF 314 1/2" CHWR
308
1/2" CHWS 2.
3/4" CHWR CU 3-4
3/4" CHWS 3. (11000)
15
FCU 3-3 FCU 3-4 FCU 3-2 6"x8"
S4 2 34"x26"
4. 4.
S4 (230) M3.1
S4 6"ø
(1330)
8"ø
(1330) FS
S4 Room
IT MANAGER
(45) 6
311
1/2" CHWS
S4
1/2" CHWR
(150)
3/4" CHWS
STOR.
3. 3/4" CHWR 306 1 1/4" CHWS
FCU 3-5 1 1/4" CHWR
FCU 3-6
3. 30"x12"
1" CHWS
MDF 1" CHWR
307
DATA CENTER
312
Room
313 1 1/4" CHWS
17 3RD FLOOR ACCESSIBLE
1 1/4" CHWR PARKING - HVAC
PROJECT#: 1709
PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
A B C D E F G H K L N Q R T V W
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
2. 1.9 SF FREE AREA LOUVER WITH MAX 0.1" WC PRESSURE DROP IN EXTERIOR
WALL. COORDINATE WITH ARCHITECTURAL.
3. CONNECT CHWS AND CHWR PIPES TO UNIT AND ROUTE CONDENSATE TO
NEAREST HUB DRAIN. COORDINATE WITH PLUMBING FOR LOCATION OF NEAREST
HUB DRAIN. PROVIDE PUMP WHERE ELEVATION OF HUB DRAIN IS ABOVE DRAIN
OUTLET ON THE UNIT. TYPICAL ALL HVAC UNITS. architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
NA
ST
8 RAYMOND E. SMITH
7 LICENSE. No. 36823
REGISTERED
NG
MEC
PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
CA L ENG I NE
THIS DRAWING IS CONFIDENTIAL AND
NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
UP PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
9
REVISION HISTORY
11
12
7 6 5 2 2 1 10 1 1 10 1 4
1.
13
FOOD
BIB
4
3 SERVICE (1400)
8
9
REFRIGERATION 14
1" CHWS EQUIPMENT
FCU 4-1 1" CHWR 26"x9"
S4
(480) 18"x8" 2.
TYP 4 1 1/2" CHWR
44"x20" FD
DOAS
1 1/2" CHWS
4-1
15
EF 4-1 (750)
22"x8" 32"x10" FD FS
3.
S2
10"x8"
(775)
10"x10" 22"x10"
OA DOWN
18"x8"
& UP
2" CHWR
6"ø
S4
6"ø 7"ø S4 (1650)
5"ø 6"ø (75)
S4 Room S4Room S4 S4 30"x12"
Room
(75) 261 (50)
262 263 (75) (120) Room
6"x6"
265
Room
EG-1 10"x8"14"x8" 264
(175) 17
EG-1 R2 EG-1
4TH FLOOR PARKING -
1 1/2" CHWS HVAC
1 1/2" CHWR (175) (250) (150)
PROJECT#: 1709
PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
A B C D E F G H K L N Q R T V W
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
2. CONNECT CHWS AND CHWR PIPES TO UNIT AND ROUTE CONDENSATE TO
NEAREST HUB DRAIN. COORDINATE WITH PLUMBING FOR LOCATION OF NEAREST
HUB DRAIN. PROVIDE PUMP WHERE ELEVATION OF HUB DRAIN IS ABOVE DRAIN
OUTLET ON THE UNIT. TYPICAL ALL HVAC UNITS.
3. PROVIDE 2 HR SHAFT ENCLOSURE OR 2HR RATED DUCT ALTERNATIVE SUCH AS
UNIFRAX FYRE WRAP OR EQUAL. 2 HR ENCLOSURE SHALL BE CONTINUOUS UP TO
VERTICAL SHAFT ENCLOSURE.
architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
NA
ST
8 RAYMOND E. SMITH
S4 28"x14" 7 LICENSE. No. 36823
(1650) REGISTERED
NG
STAIR PRESSURIZATION
MEC
UP & DN PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
CA L ENG I NE
THIS DRAWING IS CONFIDENTIAL AND
NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
DN UP PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
9
REVISION HISTORY
11
12
13
1.
14
14"x8" 15
3. SPF 5-1 3.
R2 30"x12" 30"x12"
(520)
FS
22"x16"
R2 FCU 5-1
(780) S4
(105)
WATER 18"x8"
HEATERS 2.
501
S4 S4
ENGINEERING
(520) (340) 502 2" CHWS
18"x8" 2" CHWR
s a ii
HUB DRAIN. PROVIDE PUMP WHERE ELEVATION OF HUB DRAIN IS ABOVE DRAIN
OUTLET ON THE UNIT. TYPICAL ALL HVAC UNITS.
architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
2 CERTIFIED CORRECT
M8.1
LO
6
TE OF U I S I A
12"x12" A
NA
ST
8 RAYMOND E. SMITH
28"x14"
7 LICENSE. No. 36823
STAIR PRESSURIZATION
REGISTERED
NG
MEC
UP AND DN PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
CA L ENG I NE
THIS DRAWING IS CONFIDENTIAL AND
NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
UP PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
9
REVISION HISTORY
11
12
13
14
8"x8"
FS
FCU 6-1 1. 1. FCU 6-2
3/4" CHWS
8"ø
S4
(210)
STORAGE 2" CHWS
3/4" CHWR
30"x12"
COMPR
314
17 6TH FLOOR PARKING -
HVAC
PROJECT#: 1709
PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
A B C D E F G H K L N Q R T V W
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
HUB DRAIN. PROVIDE PUMP WHERE ELEVATION OF HUB DRAIN IS ABOVE DRAIN
OUTLET ON THE UNIT. TYPICAL ALL HVAC UNITS.
2. CONNECT REFRIGERANT PIPES TO UNIT AND ROUTE CONDENSATE TO NEAREST
HUB DRAIN. COORDINATE WITH PLUMBING FOR LOCATION OF NEAREST HUB
DRAIN. PROVIDE PUMP WHERE ELEVATION OF HUB DRAIN IS ABOVE DRAIN
OUTLET ON THE UNIT. TYPICAL ALL HVAC UNITS. architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
CU 7-4
A/C 7-4
NA
ST
8 RAYMOND E. SMITH
7 LICENSE. No. 36823
28"x14" REGISTERED
NG
MEC
STAIR PRESSURIZATION PROFESSIONAL ENGINEER
I
UP & DN IN
ER
NI
HA
CA L ENG I NE
THIS DRAWING IS CONFIDENTIAL AND
NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
DN PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
9
REVISION HISTORY
11
12
13
CU 7-3 14
1/2" CHWR
FCU 7-1 15
FS
1. S4
(200) 8"x8"
1/2" CHWS
Room
266
8"x6"
1/2" CHWR
4"ø
S4
2" CHWR (1650)
2" CHWS
s a ii
1. OUTSIDE AIR AND EXHAUST AIR DUCT SIZES AND AIRFLOW ARE TYPICAL FOR
EACH HOTEL ROOM.
2. COORDINATE LOCATIONS OF DAMPERS WITH ARCHITECT. PROVIDE ACCESS
PANELS FOR DAMPERS ABOVE HARD CEILINGS. WHERE ACCESS PANELS WILL
INTERFERE WITH AESTHETICS OF ARCHITECTURAL CEILING, PROVIDE REMOTE
DAMPER OPERATOR FOR INACCESSIBLE DAMPERS. TYPICAL ALL DAMPERS. architects ii
3. CONNECT CHWS AND CHWR PIPES TO UNIT AND ROUTE CONDENSATE TO P L L C
BOTTOM OF RISER AND/OR TO NEAREST HUB DRAIN. COORDINATE WITH 189 Maple Ridge Drive Metairie, LA 70001
PLUMBING FOR LOCATION OF NEAREST HUB DRAIN. TYPICAL ALL HVAC UNITS. (504)885−4477
[email protected] :−: hbsaii.com
4. PROVIDE FSD IN VERTICAL EXHAUST RISER.
since 1961
FS
FCU-A S2 S2
(60) HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM Room HOTEL ROOM HOTEL ROOM HOTEL ROOM 2.4
FS
HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM 3.
3
FS
CE-1 809 HOTEL ROOM S4
810 812 814 827 828 CE-1
(25) 3. 829 (280)
M HOTEL ROOM FCU-K (25)
TYP
10"x6"
5 807 8"x8"
3. CE-1 HOTEL ROOM
S2 (25) 3. 831
(35)
S2 S2 S2 S2
S2
14"x8" 3.1
6"x6"
S2 S2 S2 S2 S2 S2 S2 S2 S2 S2 S2 S2 CE-1 (35)
FS
FS
(35) (40) (40) (40) (40) (35) (35) (35) (35) (35) (35) (35) (35) (40) (40) (35) (25) M
3. CE-1
HOTEL ROOM
12
CE-1 (25)
FCU-B
CE-1 3.
6"x6"
806 3. 3. 3. 3. 3. 3. 3. 3. 3. 3. 3. 3. CE-1 3. 3.
CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 (25) CE-1 CE-1 12"x6"
8"x8" HOTEL ROOM
(25) FS(25) (25) FS(25) (25) FS(25) (25) FS(25) (25) FS(25) S2 (25) FS(25) (25) FS(25) 3. FS 3.
FS
CE-1 S2 832
(60) 4. 3.2
(25) (35)
FCU-K
4"x6" 14"x8"
FS FS FS FS FS FS
FS
FS
M CE-1
4 CE-1 S1 M
HOTEL ROOM (25) 1 (25) 13
FCU-C 14"x8" 805 M8.1 FS 18"x8" FS (150) 20"x8" 18"x8" 16"x6" 4
8"x8"
FD
FCU-K
22"x8"
3. 3. HOTEL ROOM
S2 8"CHWS & 833
5
(35) Room
CE-1 CE-1FS CE-1 CE-1FS S2 CHWR- UP&DN S1 S2
134 (25) 3. 3. (25) (25) 3. 3. (25) 3. Room FCU-K (35)
S2
(60) (435)
136 4.2
TYP 4
24"x10"
24"x8" S1 HOTEL ROOM
(35) 3. S2 Room
HOTEL ROOM 81 S2 3. 834 THESE PLANS AND SPECIFICATIONS HAVE
S2 (45) FS (180) 8"x8"
804 S2 S2 54"x14" 10"ø (35)
BEEN PREPARED BY ME OR UNDER MY
(45) CLOSE PERSONAL SUPERVISION AND TO
CE-1 (35) (45) CE-1 M THE BEST OF MY KNOWLEDGE AND
FCU-C (25) 32"x16" 30"x20" (25) 13 BELIEF THEY COMPLY W ITH ALL CITY,
FS
FS
STAIR 24"x12" STATE AND FEDERAL REQUIREMENTS, AND
I AM NOT PROVIDING CONTRACT
PRESSURIZATION
7"ø
9"x8"
14"x8" 4.3 ADMINISTRATION.
DUCT 9"x8" FS
FCU-8-1 2 14"x8" CERTIFIED CORRECT
8"x6"
FD
FS
FCU-A
FS
R1 M8.1 CE-1
CE-1 LO
E OF U I S I A
M M 6
HOTEL ROOM (2100) (25)
3 FCU-C 803
(25) Room 28"x18" 13
AT
NA
957
ST
FS 10"ø 8"x8"
2. M S1 STAIR 12"x12" FCU-K 3. ROOM
S2
3. 8 (150) PRESSURIZATION 860 8 RAYMOND E. SMITH
CE-1 7
(35) 4. DUCT
S2 LICENSE. No. 36823
9"x6"
(25) EF-A
HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM S4 REGISTERED
NG
(35)
FS
MEC
S2 811 813 815 817 819
CE-1 4"ø ELEC
8"ø (1650) PROFESSIONAL ENGINEER
I
(45) 8000 S1 S2 IN
ER
HOTEL ROOM 7.1 NI
HA
3. (25)
HOTEL ROOM
FCU-C TYP 2
S2
(15) 9"ø
(100) (35)
FCU-K 8"x8"
836
CA L ENG I NE
M 802 CE-1 4"ø CE-1 M
2 (25) FCU-C 4. 13 THIS DRAWING IS CONFIDENTIAL AND
(25)
14"x6"
FS
FS
6"ø
S2 EITHER WHOLLY OR IN PART, OR MADE
8"ø
(40) WOMEN 14"x8" PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
5"ø
3. 1. S1 5"ø CONSENT OF HBSA II ARCHITECTS,
BATH TYP CE-1 8002 14"x8"
FCU-B EF-A (100) MEN WOMEN 7.4 A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
FS
801-1 S2
FS
(25) OR INVENTION ARE RESERVED AND WILL
HOTEL ROOM CE-1 M M M CE-1 8005 8006
801 (25) (35) TYP 8 FCU-C 20
FCU-C
8 (25) EF-A EF-A
CE-1 M 7.5 REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
HOTEL ROOM (25) 13
800 FCU-C FS S2 9
S1 8"x8"
STORAGE (35) HOTEL ROOM
S2 (85) 3. REVISION HISTORY
S1 8007 S2 837
8"x6"
0' - 8" (35) 11
(75) (20) FCU-K
FS
HOTEL ROOM HARD ROCK S2 HOTEL ROOM 12
FCU-E 841 USE 3. (35) 3.
FS
838
8003 CE-1 8"x8"
(25) S2 CE-1 13
(35) M
FS
M M STAIRWAY FCU-K (25)
8 14
1 8004 R1 14
S2 HOTEL ROOM 14"x8" (280)
FCU-C S2 (15) 840
3.
IT TYP
(35) S2
FS
3. 8008
4. (35) CE-1
(25)
FCU-C S2 3. HOTEL ROOM
15
839
(35) 6"x6"
M
6 4"ø
4"ø
4"ø
4"ø
4"ø
CE-1
FS S2
(25) CE-1 CE-1 CE-1 CE-1 (35) M FCU-C M FCU-C
FS 3. 3. 3. 8 15
(25) (25) (25) (25) 3.
S2 S2 S2
(35)
10"x6"
(35) (35)
HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM
843 844 845 846
842 14.1
FCU-A
FCU-B
M 2 1/2" CHWR
5 2 1/2" CHWS 17 8TH FLOOR - HVAC
FCU-C
15.1
FCU-C PROJECT#: 1709
M M
A A2 B C C1 D D1 L K1
4 6 PHASE: PERMIT
A1 D2 E E2 F G H H1 H2 K J1 K2 L1 L2 N M1 Q N1 N2 R P1 P2 T Q1 Q2 V
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
1. COORDINATE LOCATIONS OF DAMPERS WITH ARCHITECT. PROVIDE ACCESS
PANELS FOR DAMPERS ABOVE HARD CEILINGS. WHERE ACCESS PANELS WILL
INTERFERE WITH AESTHETICS OF ARCHITECTURAL CEILING, PROVIDE REMOTE
DAMPER OPERATOR FOR INACCESSIBLE DAMPERS. TYPICAL ALL DAMPERS.
architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
FS
916 918
FCU-A 922 923 924 926
HOTEL ROOM HOTEL ROOM 2.4
FS
M 10"x10"
920 921
6 10"x10"
14"x8"
S2 S2
FS
FS
CE-1 (40) (35) CE-1
S4 3
M (25) (280)
(25) S2 TYP
5 HOTEL ROOM 8"x8" (35) HOTEL ROOM
907 S2
(35) 10"x6" 9"x9" 936
9"x9" FCU-K
3.1
6"x6"
14"x8"
CE-1
FS
FS
S2 M
(25) CE-1
(35) S2 12
HOTEL ROOM S2 (25)
FCU-B CE-1 S2 S2 S2 S2 (35)
6"x6"
M 906 CE-1 CE-1 CE-1 CE-1 CE-1 S2 CE-1 CE-1 S2 S2 CE-1 CE-1 S2 S2 CE-1 CE-1 S2 S2 CE-1 CE-1 S2 S2 CE-1 CE-1 S2 S2 S2
4 (25) (40) (40) (40) (40) (35) (35) 8"x8" HOTEL ROOM
FS(25) (25) FS(25) (25) FS FS(25) (25) FS FS (25) (35) (35) (25) FS(25) (35) (35) (25) (25) (35)
FS (35) (25) FS (25) (35) (35) (25) FS(25) (40) (40) (35) FS
FS
937
CE-1 9"x9" M 3.2
10"x10" (25) 13 FCU-K
9"x9"
10"x10" 10"x10" 14"x8"
FS 10"x10" 10"x10" 10"x10" FS 10"x10" FS FS FS 9"x9"
FS
4"x6"
FS
FD
S2 (25) HOTEL ROOM
938
(35) 9"x9" FS FCU-K 5
CE-1FS CE-1FS
22"x8"
CE-1 S2 S2 CE-1 S2 S2 S2 S2 CE-1 S2 S2 CE-1 CE-1 S2 14"x6" S2
S2
(25) (35) (25) (25) (45) (45) (25)
(45) (60) (60) (25) (40) (40) (25) (25) (35) (35) (35)
FCU-K
4.2
24"x8"
HOTEL ROOM
S2 22"x8" 939
HOTEL ROOM (35) THESE PLANS AND SPECIFICATIONS HAVE
FS BEEN PREPARED BY ME OR UNDER MY
904 8"x8"
CE-1 8"CHWS & CE-1
CLOSE PERSONAL SUPERVISION AND TO
M THE BEST OF MY KNOWLEDGE AND
FCU-C (25) 30"x20" 13
CHWR- UP&DN 12"x6" (25) BELIEF THEY COMPLY W ITH ALL CITY,
FS
32"x16"
FS
STATE AND FEDERAL REQUIREMENTS, AND
STAIR I AM NOT PROVIDING CONTRACT
7"ø
20"x30"
HOTEL ROOM HOTEL ROOM 12"x12" 14"x8"
PRESSURIZATION FS 927 929 HOTEL ROOM 4.3 ADMINISTRATION.
8"x8"
FD
UP & DN FS 931
2 14"x8" CERTIFIED CORRECT
8"x6"
FCU-A
FS
HOTEL ROOM
FS
28"x18" M8.1
LO
E OF U I S I A
M CE-1 925 CE-1 M 6
3 FCU-C
HOTEL ROOM
903
(25)
FCU-C S1 STAIR (25) 13
AT
NA
ST
(125) PRESSURIZATION 8"x8"
S2 1. M
(35) 8 UP & DN HOTEL ROOM
940
8 RAYMOND E. SMITH
FCU-C CE-1 FCU-C M CE-1 FCU-K
19 (25) S2 7 LICENSE. No. 36823
(25)
14"x6"
REGISTERED
FS
HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM S2 IDF
NG
(35)
FS
MEC
911 913 915 917 919 (15) 9002 FCU-K PROFESSIONAL ENGINEER
HOTEL ROOM S2 CE-1
I
CE-1 HOTEL ROOM IN
ER
S2 7.1
CE-1 NI
HA
CA L ENG I NE
902 (45) (25) 9"x9" 941
(25) FCU-C (25) (35) 8"x8"
M TYP ELEC. CE-1 M
2 CE-1 CE-1
S2 9001.1 FCU-C FCU-B FCU-B FCU-B (25) 13 THIS DRAWING IS CONFIDENTIAL AND
(25) S2 M
FS
(25)
FS
FS NOT BE LOANED, REPRODUCED, COPIED,
S2 (35) (15) 19 EITHER WHOLLY OR IN PART, OR MADE
(40) TYP M M 14"x8" PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CE-1 18 17 14"x8" CONSENT OF HBSA II ARCHITECTS,
FCU-B HOTEL ROOM (25) 10"x10" 7.4 A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
FS
FS
8"x6"
9001
FS (35) FCU-K
HOTEL ROOM 9"x9"
947 S2 S2 HOTEL ROOM 12
FS
FCU-E (35) (35) 944
HOTEL ROOM 8"x8"
10"x6"
CE-1
CE-1
953
(25) CE-1 13
M S2 (25)
1 M (25)
8 (35) M R1
6"x6" 19 S2 14
FS
(35) 14"x8" (280)
FCU-C TYP
S2
FS
HOTEL ROOM M
(60) FS FCU-C 945 10"x10" CE-1
(25) 14
HOTEL ROOM
FCU-C
FS
S2 S2
S2 FS FS 946 15
(35) (40) CE-1
FS
M (35)
6 (25)
CE-1 FS
CE-1 S2 CE-1 CE-1
(25) (25) (35) S2 M FCU-C M FCU-C
(25) (25)
(40) 8 15
HOTEL ROOM
HOTEL ROOM 950
948
FCU-A
FCU-B
M
6 17 9TH FLOOR - HVAC
FCU-C
15.1
FCU-C PROJECT#: 1709
PHASE: PERMIT
A A1 A2 B C C1 D D1 D2 E E2 F G H H1 H2 K M J1 L K1
K2 M L1 L2 N M1 Q N1 N2 R P1 P2 T Q1 Q2 V
5 4 TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
1. COORDINATE LOCATIONS OF DAMPERS WITH ARCHITECT. PROVIDE ACCESS
PANELS FOR DAMPERS ABOVE HARD CEILINGS. WHERE ACCESS PANELS WILL
INTERFERE WITH AESTHETICS OF ARCHITECTURAL CEILING, PROVIDE REMOTE
DAMPER OPERATOR FOR INACCESSIBLE DAMPERS. TYPICAL ALL DAMPERS.
architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
FS FS
FCU-A 1009 HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM
HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM 10"x10" 2.4
FS
CE-1
(35) R2 3
M (25) S2 (600)
5 HOTEL ROOM
(40)
1007 S2 28"x12" M
(35) 10"x6" 12 HOTEL ROOM
1036
9"x9" 9"x9" S4 3.1
CE-1
6"x6"
S2 (600)
12"x8"
HOTEL ROOM
FS
1006 (35) (25)
S2
S2 S2 S2 S2 S2 S2 S2 S2 S2 (35) FCU-M
FCU-B S2 S2 S2 S2 CE-1 S2 S2
FS6"x6"
CE-1 CE-1 S2 S2 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1
CE-1 (40) (40) (35) (35) (35) (35) (35) (35) (35) (35) (35) (35) (25) (40) (40) (35)
(25) (40) (40) (25)
(25) (25)FS (25) FS (25) (25) FS (25) (25) FS (25) (25) FS(25) (25) FS (25) (25) FS CE-1 FS
9"x9" 3.2
(25) M
13
M FS FS FS FS FS 4"x6" FS FS FS
S1
FS
FS
4 CE-1 14"x8"
CE-1 1 (125) (25) HOTEL ROOM
FCU-C 12"x8" (25) M8.114"x8" FS FS 18"x8" 16"x8" FS FS 14"x8" 12"x8" 1037 4
HOTEL ROOM S2 8"x8"
S2
FD
1005
(35)
(35) 5
12"x6"
STAIR 1
CE-1 CE-1 FS CE-1 CE-1FS FS FCU-K
20"x8"
147 S2 S2 S2 S2 S2 S2 CE-1 S2 S2 CE-1 CE-1 S2
(25) (25) (25) (25)
20"x8"
Room (35) (40) (40) (40) (60) (60) (25) (40) (40) (25) (25) (35) Room
134 136
FCU-K 4.2
S2 HOTEL ROOM
(35) 8"CHWS & S2 1038
HOTEL ROOM THESE PLANS AND SPECIFICATIONS HAVE
FS CHWR - (35) 8"x8" BEEN PREPARED BY ME OR UNDER MY
1004
CE-1 Room UP&DN CLOSE PERSONAL SUPERVISION AND TO
10"x6"
CE-1 THE BEST OF MY KNOWLEDGE AND
FCU-C (25) 188
30"x20" (25)
7"ø
BELIEF THEY COMPLY W ITH ALL CITY,
FS
14"x8"
FS
STATE AND FEDERAL REQUIREMENTS, AND
10"x10" 18x18 STAIR 20"x30" M I AM NOT PROVIDING CONTRACT
PRESSURIZATION 8"x8" FS 13 4.3 ADMINISTRATION.
FD
32"x16" 2 CERTIFIED CORRECT
8"x6"
UP & DN STAIR
FS
FCU-A
FS
NA
HOTEL ROOM
ST
1. M FS FS S2 8"x8"
1003 S2 FCU-C 8
8 HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM (35)
(35) 1011 CE-1 FCU-C CE-1 1025 1027 1029
HOTEL ROOM 28"x18"
FCU-K RAYMOND E. SMITH
HOTEL ROOM
(25) M 1031
STAIR 7 LICENSE. No. 36823
1019 (25) STAIR 3
12"x6"
19 PRESSURIZATION REGISTERED
FS
FCU-K
NG
MEC
140
UP AND DN HOTEL ROOM PROFESSIONAL ENGINEER
HOTEL ROOM S2 HOTEL ROOM S2 CE-1
I
BATH HOTEL ROOM HOTEL ROOM S2 1040
7.1 IN
ER
1002
(45) 1013 CE-1 (15) NI
HA
CA L ENG I NE
1000-1 1015 1017 (25) FS (35)
(25) 8"x8" M
M CE-1 S2 FCU-C 13
2 CE-1 CE-1
(25) (35) S2 FCU-C FCU-B FCU-B FCU-B THIS DRAWING IS CONFIDENTIAL AND
(25) (25)
FS
FS
TYP HOTEL ROOM
10"x10" (25) M M M 1041 EITHER WHOLLY OR IN PART, OR MADE
S2 14"x8" PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
TYP 19 18 17 S4 M CONSENT OF HBSA II ARCHITECTS,
FCU-B (40) 7.4 A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
FS
HOTEL ROOM CE-1 (300) 13
FS
8"x6"
S2
FS (35)
FCU-K
14"x8" S2
HOTEL ROOM 12
1044
FCU-E S2
(35) 8"x8"
CE-1 (35)
M HOTEL ROOM CE-1 (25) CE-1 13
(25)
FS
1 M 1046 (25)
8 M R1
6"x6" 19 S2 14
S2 14"x8" (280)
FCU-C (35)
(35) TYP
S2
FS
HOTEL ROOM M
(60) 1043 CE-1 14
S2
(25) HOTEL ROOM
S2 (35) FCU-C 1045
FCU-C (35) FS S2
FS 15
(40) CE-1FS
M (25)
6
CE-1FS CE-1 S2 S2 FS
CE-1 CE-1
(25) (25) (35) (40) (25) (25) M FCU-C M FCU-C
8 15
HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM HOTEL ROOM
14.1
1047 1048 1049 1050 1051
FCU-A
FCU-B
M
5 17 10TH - 12TH FLOORS -
FCU-C HVAC
15.1
M FCU-C M
PROJECT#: 1709
4 6 PHASE: PERMIT
A A1 A2 B C C1 D D1 D2 E E2 F G H H1 H2 K J1 L K1
K2 L1 L2 N M1 Q N1 N2 R P1 P2 T Q1 Q2 V
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
1. COORDINATE LOCATIONS OF DAMPERS WITH ARCHITECT. PROVIDE ACCESS
PANELS FOR DAMPERS ABOVE HARD CEILINGS. WHERE ACCESS PANELS WILL
INTERFERE WITH AESTHETICS OF ARCHITECTURAL CEILING, PROVIDE REMOTE
DAMPER OPERATOR FOR INACCESSIBLE DAMPERS. TYPICAL ALL DAMPERS.
architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
FS FS
HOTEL ROOM HOTEL ROOM
FCU-A 1327 1329
2.4
FS
6"x6"
CE-1
FS
33"x6"
(25) S4
6"x6"
S2 S2 (300)
FCU-B S2 S2 S2 (40) S2 S2 S2 S2 S2 S2 CE-1 S2 S2 S2 S2 CE-1 S2 S2 (40)
HOTEL ROOM CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1 CE-1
(40) (40) (40) (40) (40) (25) (40) (40) (40) (40) CE-1 S2
1306
FS(25) (25) FS (25) (40) (40) (40) (40) (25) FS(25) FS(25) FS (25) (40) (40) FS
FS
(25) FS (25) (25) (25) FS (25) (25) FS(25) (25) (25) (40) M 3.2
13 FCU-M
M
4 FS FS FS FS FS FS FS
FS
CE-1
FS
4"x6" CE-1 S4
(25) 1 HOTEL ROOM
FCU-C 14"x8" M8.1 14"x8" FS 18"x8" FS FS
20"x8" 16"x8" FS 14"x8" (25) (300) 1335 4
HOTEL ROOM S2
S2
22"x8"
1305
FD
10"x6" S1 S2 (40)
(40) CE-1 S2 5
14"x6"
STAIR 1 CE-1 FS
CE-1 (200) CE-1 (40) S2 CE-1
FS CE-1 S2
(25)
20"x8"
S2 S2 CE-1 (40) S2 S2
S2
147
(25) (25) TYP 2 (25) (40) (25) (25) (40) FCU-K
(40) (40) (25) 4"ø (40) (40) 4.2
(40)
22"x10" HOTEL ROOM
24"x8" 1336 THESE PLANS AND SPECIFICATIONS HAVE
FS 10"ø 10" CHWS & CHWR- UP & CE-1 FCU-K BEEN PREPARED BY ME OR UNDER MY
CE-1 8" CHWS & CHWR-DN (25) CLOSE PERSONAL SUPERVISION AND TO
19"x6"
HOTEL ROOM M S4 THE BEST OF MY KNOWLEDGE AND
FCU-C 1304 (25) CE-1 30"x20" BELIEF THEY COMPLY W ITH ALL CITY,
13
FS
(25) (300)
FS
40"x16" STATE AND FEDERAL REQUIREMENTS, AND
I AM NOT PROVIDING CONTRACT
STAIR 14"x6" M
PRESSURIZATION
HOTEL ROOM HOTEL ROOM
FS HOTEL ROOM
10"x10" 4.3 ADMINISTRATION.
FD
1311 1313 1322 13 CERTIFIED CORRECT
12"x6"2
8"x6"
CE-1 FCU-A
FS
FS
M8.1 S4
LO
M M 14"x6" CE-1 6 E OF U I S I A
19"x6"
(25)
3 FCU-C HOTEL ROOM 8 HOTEL ROOM HOTEL ROOM (25)
(300)
AT
NA
1324
ST
1303 FS FCU-C FS 1326 HOTEL ROOM
S2 HOTEL ROOM
S2 FCU-C M
(40) 8 20"x32"1328 (40)
1337 8 RAYMOND E. SMITH
M CE-1 STAIR
S1 19 7 LICENSE. No. 36823
S2 1. (25) PRESSURIZATION
FCU-C (200) STAIR 3 FCU-K REGISTERED
NG
FS
MEC
(40) 140 PROFESSIONAL ENGINEER
I
S2 IN
ER
BATH 4"ø HOTEL ROOM 7.1 NI
HA
1300-1 (40) M 1338 CA L ENG I NE
14"x6"
13
19"x6"
HOTEL ROOM CE-1 FCU-C S2 CE-1
M 1302 (40) CE-1 S4
2 (25) S2 FCU-C FCU-B FCU-B FCU-B (25) THIS DRAWING IS CONFIDENTIAL AND
CE-1 M (25) (300)
FS
FS
S2 19 EITHER WHOLLY OR IN PART, OR MADE
(25) M M 16 PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
(40) TYP M
18 17 S4 CONSENT OF HBSA II ARCHITECTS,
TYP S2 13 7.4
FS
FCU-B HOTEL ROOM (300) A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
(40)
FS
19"x6"
FCU-C FCU-C 33"x6" CE-1 (300)
REMAIN THE SOLE PROPERTY OF HBSA II
(25) 1300 8 20 8 (25) (25) HOTEL ROOM
ARCHITECTS A PROFESSIONAL L.L.C.
8"x6"
Room
HOTEL ROOM 195 (40) CE-1
1343 S2 (25)
12
(40)
FS
FCU-E M
CE-1 14
M CE-1 (25) 13
1 M (25)
FS
8 M
6"x6" 19 S2 14
FS
HOTEL ROOM (40)
FCU-C
S2 1341
HOTEL ROOM
(40) FS S2 1342
S2 (40)
(40) FCU-C
FCU-C
FS FS
S2
FS FS 15
(40) CE-1
10"x6"
M (25)
6
CE-1 CE-1 S2 S2
(40) CE-1 CE-1
(25) (25) (40) (25) (25) M FCU-C M FCU-E
8 15
HOTEL ROOM
1344 HOTEL ROOM HOTEL ROOM
14.1
1345 1346 HOTEL ROOM
1347 HOTEL ROOM
1348
FCU-A
FCU-B
s a ii
1. COORDINATE LOCATIONS OF DAMPERS WITH ARCHITECT. PROVIDE ACCESS
PANELS FOR DAMPERS ABOVE HARD CEILINGS. WHERE ACCESS PANELS WILL
INTERFERE WITH AESTHETICS OF ARCHITECTURAL CEILING, PROVIDE REMOTE
DAMPER OPERATOR FOR INACCESSIBLE DAMPERS. TYPICAL ALL DAMPERS.
architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
1402 1404 1406 1408 1410 1412 1413 1414 1415 1416 1418 1420 1422 1423 1424
6"x6"
CE-1 S2
Room 10"x6"
(35)
203 (40)
14"x8" 3.1
FS
6"x6"
FCU-L 24"x12" 24"x12" M
FS
FS
CE-1 12 S4
S2 S2
6"x6"
FS
(35) 10"x10" CE-1 S2 (40)
(35)
FS
FS
(35) (35) HOTEL ROOM 3.2
FS
FS
(35)
FS
(40) (35) (35) (40) (40) S2 (35) (35) S2 (35) (40) FCU-K
S2 S2 S2 S2 S2 S2 (40) S2 S2 1426
CE-1 (40) (40) (40) (40) (40) (40) (40) (40) 9"x9"
(40) 10"x10" M 14"x8"
FS (35) Room CE-1
FS 4"x6" 13
199 S1
1 FS (35)
(125)
24"x12"
M8.1 18"x8" 24"x6" 20"x8" 18"x8" 4
S2 8"x8" HOTEL ROOM
CE-1 CE-1
FD
CE-1 (40) 1427
FS
FS
FS
FS
(35) 5
FS
(35)
9"x9"
S1 (35) CE-1 S2 CE-1 FCU-K
33"x6"
9"x9"
22"x8"
S2 S2 S2 S2 S2 24"x10" S2 S2
(60) S2 (35) (40) (40) (35) CE-1 S2
(40) (40) (40) (40) (40) 10"CHWS (40) 4.2
10"x10"
20"x10"
(40) 9"x9" (40)
10"x10"
S2 FS (35)
FS & CHWR - Room HOTEL ROOM
(1650) UP&DN FCU-K
1 1/2"CHWS
10"x10"
8"x6"
10"ø
CLOSE PERSONAL SUPERVISION AND TO
16"x30" (35) M THE BEST OF MY KNOWLEDGE AND
30"x20" 13
FS
1 1/2"CHWR
1405 1407 1409 1411 HOTEL ROOM 1419 1421 I AM NOT PROVIDING CONTRACT
STAIR 20"x30" 14"x8" 4.3 ADMINISTRATION.
24"x12"
FS 1417
S1 PRESSURIZATION
FD
2 14"x8" CERTIFIED CORRECT
(60) MECH. FS
FCU-A 12"x8" M8.1
6"x6" 1439 CE-1 LO
E OF U I S I A
M 6
S1 FCU-C
(35) 13
AT
NA
14"x6"
ST
FS (125) FS 20"x32" 8"x8"
M S2 FCU-K
STAIR (40)
HOTEL ROOM
8
8 1429 RAYMOND E. SMITH
CE-1 9"x9" PRESSURIZATION
FCU-C M 7 LICENSE. No. 36823
(35)
12"x6"
S2 S4 REGISTERED
NG
19
FS
MEC
(40) (1650) PROFESSIONAL ENGINEER
S2 CE-1
I
Room S2 IN
ER
(35) FCU-K 7.1 NI
HA
CA L ENG I NE
9"x9" FCU-C (40) 219 FS (40)
8"x8" HOTEL ROOM
10"x10"
9"x9" M
14"x6"
1430
FCU-C FCU-B FCU-B FCU-B 13 THIS DRAWING IS CONFIDENTIAL AND
CE-1
FS
4"ø
19 CE-1 (35) EITHER WHOLLY OR IN PART, OR MADE
CU 15-1 CONDO OFFICE M M (35) 14"x8" PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
1440 CE-1 CE-1 18 17 CONSENT OF HBSA II ARCHITECTS,
10"x10" 14"x8"
(35) (35) HOTEL ROOM
7.4 A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
FS OR INVENTION ARE RESERVED AND WILL
M M M CE-1
1 1/2"CHWS
TYP
8 FCU-C 20
FCU-C
8
1432 M 7.5 REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
(35)
10"x10"
CU 15-2 13
FCU-C FS4"ø FCU-C HOTEL ROOM 9
S2 S2 8"x8" FCU-K 1431
FCU-L (40) (40) REVISION HISTORY
S2 M
S2 14 11
8"x6"
HOTEL ROOM (40) HOTEL ROOM
FS 1436 1437 FS (40)
9"x9" 12
1 1/2"CHWR
HOTEL ROOM
S2 1433
CE-1 8"x8"
(40) FCU-K
(35) 13
M CE-1
10"x6"
FS
FS
CE-1
(35)
S1 S1 14.1
(140) (140)
8"x8" 8"x8"
FCU-L 8"x8"
S1 S1 S1
(130) (130) (130) 17 14TH FLOOR- HVAC
15.1
PROJECT#: 1709
A A1 A2 B C C1 D D1 D2 E E2 F G H H1 H2 K J1 L K1
K2 L1 L2 N M1 Q N1 N2 R P1 P2 T Q1 Q2 V PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
1. TERMINATE KITCHEN AND BATHROOM EXHAUST DUCTS AT LOUVER ON EXTERIOR 4. DIFFUSERS LOCATED IN CONDO UNITS SHALL HAVE BALANCING DAMPERS AT THE
WALL. PROVIDE 12" DEEP PLENUM BOX FOR CONNECTING DUCTS TO LOUVER. DIFFUSER, OPEARABLE AT THE DIFFUSER FACE, TO ELIMINATE THE NEED FOR
LOUVER SHALL BE SIZED FOR MINIMUM 1 SF FREE AREA AND VELOCITY OF 500 ACCESS PANELS.
FPM OR LESS WHILE DISCHARGING 500 CFM. THE OVERALL PRESSURE DROP 5. SEE CONDO 6 AND 20 ON THIS SHEET AND COND 1610 ON SHEET M1.4.4 FOR
SHALL BE NO GREATER THAN 0.08 IWC. LOUVER SIZE SHALL BE AS SELECTED BY GENERAL HVAC LAYOUT OF CONDO UNITS. ALL CONDOS SHALL HAVE EXHAUST
ARCHITECT (APPROXIMATELY 12"X36") TO THE EXTERIOR WITH OUTSIDE AIR INTAKE AT THE EXTERIOR A MINIMUM 10 architects ii
2. PROVIDE SEIHO MODEL SFZC DRYER VENT TERMINAL WITH BACKDRAFT DAMPER. FEET AWAY FROM EXHAUST. SEE HVAC SCHEDULES FOR ACTUAL HVAC UNIT SIZE P L L C
MOUNT WITHIN SHEET METAL PANEL ON BUILDING EXTERIOR. COORDINATE SERVING EACH CONDO. PROVIDE EACH TOILET WITH AN EXHAUST FAN. PROVIDE 189 Maple Ridge Drive Metairie, LA 70001
PANEL LOCATION AND SIZE WITH THE ARCHITECT. AIR IN EACH BEDROOM, FULL BATHROOM, AND LIVING ROOM AND KITCHEN AREAS. (504)885−4477
[email protected] :−: hbsaii.com
3. TERMINATE VENTILATION DUCTS AT LOUVER ON EXTERIOR WALL. PROVIDE 12" LARGE CLOSETS AND LAUNDRY ROOMS SHALL ALSO HAVE SUPPLY AIR. MAKE
DEEP PLENUM BOX FOR CONNECTING DUCT TO LOUVER. LOUVER SHALL BE SIZED ADJUSTEMTS TO AIRFLOW, DUCT SIZE, THERMOSTAT LOCATION, ETC. AS since 1961
FOR MINIMUM 0.16 SF FREE AREA AND VELOCITY OF 500 FPM OR LESS WITH NECESSARY TO INSTALL SYSTEMS BASED ON DIFERENCES IN TYPICAL CONDO VS
INTAKE CFM MATCHING OA LISTED ON THE SCHEDULE FOR THE CORRESPONDING CONDO BE CONSTRUCTED.
UNIT. THE OVERALL PRESSURE DROP SHALL BE NO GREATER THAN 0.08 IWC.
LOUVER SIZE SHALL BE AS SELECTED BY ARCHITECT (APPROXIMATELY 12"X12")
6"ø
4"ø
1503-4 BEDROOM BEDROOM 1 1505-4
(75) 1504-6
6"ø
1503-5 1504-9
?
R1 EF-B
KITCHEN
LIVING
KITCHEN ? 3
1501-7 CLOSET A/C-G
1507-4
6"ø
(500) 1506-4
1506-6 A/C-F
6"ø GYM RR BATH 2
1501-11 A/C-F A/C-F CLOSET
1502 A/C LAUNDRY
A/C 1504-10 KITCHEN
R1 1502-6
16"x8"
S2 KITCHEN 1503-6 HALL HALL CLOSET HALL HALL 1506-7
(1600) A/C-G LAUNDRY 1502-3 HALL CLOSET CLOSET LAUNDRY HALL LIVING 1504-14 1504-7 1505-10
1505-1
1506-8
R2 (45) CLOSET 1503-9
1501-6
1501-5 1502-9 1502-7 KITCHEN 1503-7 1504-11 1504-13 1504-5 T 3.1
(75) 1503-3 CD-1 A/C
BATH 2 (115) 1506-9
1504-8 KITCHEN
LIVING
IDF EF-B 1508-2
FCU-15-1
1503 BATH BATH 1 A/C-F BATH 2 1508-3
ENTRY BATH 1504-12 BATH CD-1 BATH
1501-1 1502-8 1503-8 H20 1507-3
A/C-F 1505-9 (25) 5. 5. 5.
LAUNDRY ENTRY 5. 5. ENTRY 1504-2 CLOS. 1506-10
5. BATH 1 A/C 5. 1502-1 LAUNDRY ENTRY 4.
1502-2 5.
1504-1 EF-B
A/C STOR.STOR.
1506-3
WD
3.2
6"ø
6"ø
1509-1 1509-3
6"ø
A/C-G A/C-F CLOSE PERSONAL SUPERVISION AND TO
6"ø A/C CLOSET THE BEST OF MY KNOWLEDGE AND
HALL R1 30"x20" A/C
10"x10"
1513-6 1513-5 BELIEF THEY COMPLY W ITH ALL CITY,
48"x16" A/C-H 1520-8 (800) T BATH 2 20"x30" 1514-6
10"x10"
A/C STATE AND FEDERAL REQUIREMENTS, AND
BATH 1 1519-9 KITCHEN I AM NOT PROVIDING CONTRACT
STAIR CD-1 1509-2
1520-9 A/C 6"ø 1514-7 BATH 2 4.3 ADMINISTRATION.
4"ø
PRESSURIZATION 1520-10
CLOSET (40)
KITCHEN 1520-18 1513-10 2 A/C-F CLOSET CERTIFIED CORRECT
1520-7 S1 M8.1 1510-7
LO
6 E OF U I S I A
16"x10"
BATH 3 CLOSET CLOSET (250) CLOSET BEDROOM
1 1520-11
CLOSET
1519-10 1519-11 EF-A
LAUNDRY CLOSET LAUNDRY 1513-11 1510-6 AT
M8.1
NA
ST
IDF 1520-17 1514-11 1514-10 1513-12 BATH
6"ø 20"x12" 16"x12" 14"x10" 12"x12"
1504 CD-1 LIVING 1510-8 8 RAYMOND E. SMITH
R2 EF-B CLOSET (140) CLOSET 1514-8 LAUNDRY H2O
(75) LAUNDRY / H2O 1520-13 BEDROOM 2 FS 1518-8 LAUNDRY 20"x32" 1510-3 1510-4 7 LICENSE. No. 36823
1515-7 STAIR
1519-12 REGISTERED
NG
CLOS. 1521-3
MEC
LIVING LIVING BEDROOM PRESSURIZATION
2 STAIR 3
1521-2 PROFESSIONAL ENGINEER
CLOS. BEDROOM 2 1513-8 1513-9 140 5.
I
KITCHEN 1519-13
A/C-F Room LIVING IN
ER
7.1
6"ø
1515-6 1514-9
NI
HA
CA L ENG I NE
1521-4 BEDROOM 3 219 1510-5
1520-14
6"ø
10"x10"
1521-6 1520-15 1520-16 1510-1
BEDROOM A/C-F
A/C (135) 1518-6 A/C-F BEDROOM 1 THIS DRAWING IS CONFIDENTIAL AND
TYP 3 NOT BE LOANED, REPRODUCED, COPIED,
1521-5 STUDY 1515-5 EITHER WHOLLY OR IN PART, OR MADE
A/C-F 1518-7 A/C PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
? LIVING 1510-2 CONSENT OF HBSA II ARCHITECTS,
?
BEDROOM
1521-9 7.4 A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
1521-7 BATH 1
1. 2. 3. 5. 5. 1511-4 BEDROOM 1 7.5 REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
5. 5. 1511-6
9
LIVING LIVING A/C-F
1518-2 1515-4 LAUNDRY HALL REVISION HISTORY
1512-3 1511-3 11
ENTRY
1511-1 STOR.
BATH 2 CLOSET
1511-5
1511-8 1511-7 12
S1 BATH 2 LIVING
1515-10 LIVING CLOS. LAUNDRY 1511-14 13
KITCHEN (250) 1512-8 1511-9 1511-10
1518-1 TYP 8 BATH 2
CLOS.
1515-9 14
1515-11
BATH 1
LIVING BATH 1
1517-14
1517 HALL 1516-13 HALL
1517-13 1516-14 LIVING
1516-9 14.1
CLOSET CLOSET
1517-12 1516-12
15.1
PROJECT#: 1709
B C C1 D D1 D2 E E2 F G H H1 H2 K J1 L K1
K2 L1 L2 N M1 Q N1 N2 R P1 P2 T Q1 Q2 V PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
1. TERMINATE KITCHEN AND BATHROOM EXHAUST DUCTS AT LOUVER ON EXTERIOR 4. DIFFUSERS LOCATED IN CONDO UNITS SHALL HAVE BALANCING DAMPERS AT THE
WALL. PROVIDE 12" DEEP PLENUM BOX FOR CONNECTING DUCTS TO LOUVER. DIFFUSER, OPEARABLE AT THE DIFFUSER FACE, TO ELIMINATE THE NEED FOR
LOUVER SHALL BE SIZED FOR MINIMUM 1 SF FREE AREA AND VELOCITY OF 500 ACCESS PANELS.
FPM OR LESS WHILE DISCHARGING 500 CFM. THE OVERALL PRESSURE DROP 5. SEE CONDO 6 AND 20 ON SHEET M1.4.3 AND COND 1610 ON THIS SHEET FOR
SHALL BE NO GREATER THAN 0.08 IWC. LOUVER SIZE SHALL BE AS SELECTED BY GENERAL HVAC LAYOUT OF CONDO UNITS. ALL CONDOS SHALL HAVE EXHAUST
ARCHITECT (APPROXIMATELY 12"X36") TO THE EXTERIOR WITH OUTSIDE AIR INTAKE AT THE EXTERIOR A MINIMUM 10 architects ii
2. PROVIDE SEIHO MODEL SFZC DRYER VENT TERMINAL WITH BACKDRAFT DAMPER. FEET AWAY FROM EXHAUST. SEE HVAC SCHEDULES FOR ACTUAL HVAC UNIT SIZE P L L C
MOUNT WITHIN SHEET METAL PANEL ON BUILDING EXTERIOR. COORDINATE SERVING EACH CONDO. PROVIDE EACH TOILET WITH AN EXHAUST FAN. PROVIDE 189 Maple Ridge Drive Metairie, LA 70001
PANEL LOCATION AND SIZE WITH THE ARCHITECT. AIR IN EACH BEDROOM, FULL BATHROOM, AND LIVING ROOM AND KITCHEN AREAS. (504)885−4477
[email protected] :−: hbsaii.com
3. TERMINATE VENTILATION DUCTS AT LOUVER ON EXTERIOR WALL. PROVIDE 12" LARGE CLOSETS AND LAUNDRY ROOMS SHALL ALSO HAVE SUPPLY AIR. MAKE
DEEP PLENUM BOX FOR CONNECTING DUCT TO LOUVER. LOUVER SHALL BE SIZED ADJUSTEMTS TO AIRFLOW, DUCT SIZE, THERMOSTAT LOCATION, ETC. AS since 1961
FOR MINIMUM 0.16 SF FREE AREA AND VELOCITY OF 500 FPM OR LESS WITH NECESSARY TO INSTALL SYSTEMS BASED ON DIFERENCES IN TYPICAL CONDO VS
INTAKE CFM MATCHING OA LISTED ON THE SCHEDULE FOR THE CORRESPONDING CONDO BE CONSTRUCTED.
UNIT. THE OVERALL PRESSURE DROP SHALL BE NO GREATER THAN 0.08 IWC.
LOUVER SIZE SHALL BE AS SELECTED BY ARCHITECT (APPROXIMATELY 12"X12")
2
1. 2. 3. 1. 3. 1. 3.
2.2
MASTER 2.
1. 1. (0)
BEDROOM 2. 1. 3. 4. 4.
1601-10 4. 4. 2.
(0) 2. 3. 2. 1. (0) 2.
BEDROOM 2.3
(0) 3. (0) 1608-6
4. (0) 4. MASTER
BEDROOM
LIVING 4. 4. 1609-5 2.4
1604-5 4. BEDROOM LIVING
BEDROOM LIVING LIVING 1607-5 1608-4
BEDROOM
1603-7 BEDROOM 1605-4 1606-5 LIVING KITCHEN
1604-8
1605-5
1607-4 1609-2 3
EF-A LIVING LAUNDRY
1603-4 BEDROOM 1608-7 CLOSET
1606-7 MASTER BATH
A/C-F 1608-8
CLOSET EF-A
1609-8
2. A/CA/C DINING 1609-7
A/C-F A/C LAUNDRY LAUNDRY 1607-8 A/C-F
1607-8 1607-3
1603-6
CLOSET 1604-7 UTILITY DINING 1606-8 KITCHEN WATER HEATER
EF-A CLOSET 3.1
EF-A 1603-8
1605-8 1605-3 KITCHEN 1608-2 1608-10 1609-14
1. CLOSET HALL 1606-3 UTILITY EF-A
1604-9 1605-6 HALL KITCHEN 1609-10 BEDROOM
HALL 1606-6 1607-1 BATHROOM A/C-G
BATH 1609-12
1603-5 LAUNDRY KITCHEN LAUNDRY WATER HEATER 1608-11 A/C 1609-13
1603-10 1604-1 A/C A/C-F 1607-10 1607-9 1609-11
1606-10 EF-A ENTRY
EF-A
A/C
A/C-G
PANTRYLAUNDRY
EF-A A/C-F 1608-1 ENTRY 3.2
1601-3 1601-2 1602-7 BATH 1609-1
A/C-F A/C-F KITCHEN (0)
1605-11 2.
EF-A 1605-2 BATH S1
3. S1 POWDER ENTRY ENTRY 1607-11 EF-A MASTER BATH
1602-3 PANTRY EF-A PANTRY WATER HEATER 1605-1 EF-A1606-1WATER HEATER BATH (250) 1610-8 CLOSET
(250) 1606-2 1606-11 PANTRY 1610-7
1603-2 1604-3 1604-2 9"ø
9"ø
1607-2 4
S1 EF-A S1 MASTER
EF-A (250) 10"CHWS & (250) BEDROOM
EF-A
CHWR - UP&DN HALL
1610-6 5
EF-A 10"x10" 10"x10" 1610-5
4.2
16"x30" 16"x30"
2. THESE PLANS AND SPECIFICATIONS HAVE
BEEN PREPARED BY ME OR UNDER MY
LIVING CLOSE PERSONAL SUPERVISION AND TO
30"x20" 5. KITCHEN 1610-4 THE BEST OF MY KNOWLEDGE AND
EF-A 20"x30" EF-A 4. BELIEF THEY COMPLY W ITH ALL CITY,
EF-A 1610-3
STATE AND FEDERAL REQUIREMENTS, AND
1. 3.
48"x16" I AM NOT PROVIDING CONTRACT
STAIR
S1 S1 ENTRY 4.3 ADMINISTRATION.
PRESSURIZATION EF-A 2 1610-1 CERTIFIED CORRECT
(250) (250) M8.1
9"ø
6 LO
1 FS A/C-F TE OF U I S I A
M8.1 A/C-F
DINING A
NA
ST
4. 1610-2
A/C-G A/C-G 1.8
20"x32" CLOSET A/C
RAYMOND E. SMITH
EF-A STAIR 1610-16 1610-13 (0) 7 LICENSE. No. 36823
PRESSURIZATION
STAIR 3 BEDROOM 2.
REGISTERED
NG
MEC
140 1610-11
PROFESSIONAL ENGINEER
EF-A
I
A/C-G 7.1 IN
ER
CLOSET
NI
HA
CA L ENG I NE
EF-A EF-A 1610-10
A/C-H EF-A HEATER
WATER A/C POWDER
POWDER 1614-7 1614-8 4. 4. 6"ø 1611-3 TOILET ROOM
A/C-F MASTER CD-1 BATH THIS DRAWING IS CONFIDENTIAL AND
1614-6 LAUNDRY 1611-12 EF-A NOT BE LOANED, REPRODUCED, COPIED,
CLOSET (65) 1611-11 CD-1
4. 1611-23
1611-2 EF-A EITHER WHOLLY OR IN PART, OR MADE
4. BEDROOM
S1 BEDROOM 3. 2. 2. 3. (30) CLOSET PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
(250) 1. CD-1
CONSENT OF HBSA II ARCHITECTS,
1617-6 1614-9 ENTRY
1611-1
CLOSET 1611-13
CD-1 7.4 A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
6"ø
ENTRY (135) A/C-J 1611-9 OR INVENTION ARE RESERVED AND WILL
(135) 7.5 REMAIN THE SOLE PROPERTY OF HBSA II
3. 2. 1. 2. 3. 1617-1 KITCHEN 3. ARCHITECTS A PROFESSIONAL L.L.C.
6"ø
1614-1
6"ø 6"ø 9
4"ø
16"x12"
6"ø
2.
MASTER BATH EF-A REVISION HISTORY
2. 11
6"ø
3. 1611-22 T
LIVING
4. CD-1 HALL
TOILET
CD-1
1. LIVING 1614-3 1611-20 (165)
4. A/C (30) 1611-21
6"ø
1617-9 CLOSET
1617-10 HALL
1611-15
TYP 4 12
6"ø
CLOSET 1611-14
A/C-G
16"x12"
1617-11
ENTRY EF-A
CLOSET BEDROOM 1. R1
1615-1 1615-8 1615-7 (1400) 13
CD-1 A/C CLOS.
6"ø
1611-16 1611-17
MASTER BATH (115) 4.
3. BEDROOM EF-A EF-A1615-6 3. KITCHEN 14
1617-12 MASTER 1611-6 LIVING
MASTER BATH
BEDROOM 6"ø
1617-13 1611-5
1611-19
6"ø
LIVIING
1615-5 CD-1 OFFICECD-1
(0) LAUNDRY ENTRY (115) 1611-18(115)
2.
CLOSET 1616-2 1616-1 KITCHEN 4. 15
1616-3 1615-4
A/C-F 2.
2. 1.
EF-A
A/C-I
1.
3. BATH
1616-6 CLOSET
CLOSET 1616-9 LIVING
1616-13 1616-18
KITCHEN 14.1
1616-17
TOILET ROOM 4.
1616-15
MASTER
BEDROOM EF-A
1616-16 BEDROOM 2
1616-11
17
16TH FLOOR - HVAC
1.
15.1
PROJECT#: 1709
B C C1 D D1 D2 E E2 F G H H1 H2 K J1 L K1
K2 L1 L2 N M1 Q N1 N2 R P1 P2 T Q1 Q2 V PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
1. FOR WORK INVOLVING THE BUILDING HVAC WITHIN CONDO UNITS AND SERVING
COORIDOR, SEE THE 16TH FLOOR HVAC PLAN ON SHEET M1.4.6. WORK ON THIS
SHEET SHOWS HVAC RELATED TO ROUTING OF MAJOR SYSTEMS FROM THE
ROOF.
architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
2
2.2
LIVING
2.3
LIVING/ DINING
MASTER 1701-6 1702-8 MASTER
BEDROOM LVING BEDROOM
BEDROOM
1701-7 LIVING 1708-4 1709-6 1709-7 2.4
LIVING/ DINING 1708-3
1702-8 BEDROOM LIVING LIVING
BEDROOM
1702-9
1703-5
LIVING BEDROOM
BEDROOM LIVING 1706-4 BEDROOM
BEDROOM 1707-4 3
LIVING 1704-5 1704-6 1705-4 1707-5
TOILET 1705-5 1706-5 LAUNDRY DINING
CLOS. 1703-4
1701-9 1701-10 DINING DINING 1708-6 CLOSET 1709-5
MASTER BATH 1701-5 1708-2 1708-7 CLOSET MASTER BATH
1701-8 DINING HALL CLOSET
90"x24" 1708-5 1709-4
1709-9 1709-8
CLOSET A/C 1706-3
30"x16" 1702-11 DINING 1703-7 LAUNDRY LAUNDRY A/C
DINING
BATH 1703-3 CLOSET DINING 1704-8 LAUNDRY 1706-7
CLOSET
1707-8 A/C WATER HEATER 3.1
1702-10 1705-8 1708-8 1708-9 LAUNDRY
CLOSET HALL 1703-8 1704-4 HALL DINING Room CLOSET 1707-7 KITCHEN
1709-3 CLOSET
KITCHEN 1702-12 30"x16" 1703-6 1704-7 CLOS. HALL 1705-3 30"x16" 1706-8 1709-1
KITCHEN CLOSET KITCHEN 1709-12
1702-7 1705-7 1705-6 KITCHEN HALL
1701-1 1704-10 LAUNDRY 1708-1 BEDROOM
BEDROOM BATH LAUNDRY WATER HEATER LAUNDRY
A/C 10" CHWS 1706-2 STOR. 1706-6 WATER HEATER A/C BATHROOM
1707-9 1709-10
30"x20"
1704-9 CLOSET A/C BATH
1701-10 CLOS. 1701-6 1702-5 1703-9 1703-10 1706-9 1707-10 1709-2 1709-11
1705-9 1705-10 1708-10
1701-11 KITCHEN
A/C PANTRYPANTRY
A/C
1703-1 BATH
KITCHEN KITCHEN 3.2
1702-4 1705-2 1707-1
1701-3 1701-21702-6 BATH KITCHEN BATH
10" CHWS
1704-11 BATH BATH BATH
1703-11 1704-1 1707-11
ENTRY POWDER 1704-11 1705-11 1706-10 S1
S1 1702-1 1702-3 ENTRY (250)
TOILET CLOSET
10"CHWR ENTRY WATER HEATER
30"x20"
(250) PANTRY WATER HEATER 1706-1 PANTRY 1710-10 1710-7
CLOS. PANTRY 1705-1 1706-11 MASTER
1703-2 1704-3 1707-2 9"ø MASTER BATH BEDROOM 4
BEDROOM 1702-2 1704-2
1710-9 1710-8
1700-4 S1 Unoccupied S1 HALL
(250) (250)
Unoccupied 1710-5 5
28"x12" 10"x10" WATER HEATER
2363 SF
2 1/2" CHWS
FS
1710-6
FS
BATH S4 2 1/2" CHWR UTILITY 4.2
1700-6 LAUNDRY 1712-2
(1650) BATH
LAUNDRY BATH CLOSET CLOSET 1713-2 CLOSET
1719-2 THESE PLANS AND SPECIFICATIONS HAVE
1700-3 1718-2 1718-4 FS 1713-8 KITCHEN KITCHEN 1712-8
BEDROOM ENTRY BEDROOM FS 1713-1 KITCHEN BEEN PREPARED BY ME OR UNDER MY
48x16 1712-1 1710-3 CLOSE PERSONAL SUPERVISION AND TO
1719-3 1718-1 1718-3
DOWN TOILET TOILET
THE BEST OF MY KNOWLEDGE AND
10"CHWS & BELIEF THEY COMPLY W ITH ALL CITY,
1719-16 1718-17 STATE AND FEDERAL REQUIREMENTS, AND
CHWR-DN LIVING I AM NOT PROVIDING CONTRACT
BATHROOM BATHROOM
48"x16" MASTER BATH MASTER BATH
S1 S1 1713-7 1712-7
1710-4 4.3 ADMINISTRATION.
KITCHEN 1719-14 1718-14 2 CERTIFIED CORRECT
1700-2 (250) (250) A/C M8.1 DINING
10" CHWR LO
6 E OF U I S I A
WATER HEATER
KITCHEN
FS FS 2"CHWS&
1713-3 1710-1
1
1719-15 LAUNDRY
KITCHEN
1719-5 LAUNDRY
1718-5 CHWR-UP DINING DINING
A/C
1712-3 AT
M8.1
NA
ST
CLOSET 1719-6 1718-6 1713-4 1712-4 CLOSET
CLOSET CLOSETHALL CLOSET 16"x10" 12"x12"
1719-12
HALL 1719-13 1718-121717-11 1718-13 34"x22" CLOSET
1710-15 8 RAYMOND E. SMITH
LAUNDRY A/C
1719-11 A/C A/C LAUNDRY PANTRY BEDROOM STAIR S4 1710-2 1710-17 1710-12 HALL
BEDROOM 7 LICENSE. No. 36823
1719-10 1718-10 BATH 1717-9 1713-6 BEDROOM PRESSURIZATION (1650) 1710-14
1717-10 REGISTERED
9"ø
NG
DINING DINING CLOSET BATHROOM STAIR 3 1710-11
MEC
1717-11 1712-6
1719-7 1718-7 1714-11 1714-10 LIVING 140 BATHROOM PROFESSIONAL ENGINEER
I
LIVING IN
ER
1712-5 1710-16 7.1 NI
HA
CA L ENG I NE
MASTER 1713-5 CLOSET
MASTER BEDROOM 1710-13
BEDROOM 1718-9 BATHROOMWATER HEATERA/C POWDER
1719-9 LIVING 1714-6 1714-7 1714-8 LAUNDRY 1711-2 TOILET THIS DRAWING IS CONFIDENTIAL AND
LIVING BEDROOM NOT BE LOANED, REPRODUCED, COPIED,
LIVING 1719-8 1718-8 1711-3 1711-14 BEDROOM
1717-12 BEDROOM BATHROOM EITHER WHOLLY OR IN PART, OR MADE
1700-7 BEDROOM 1711-9 PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
S1 1714-9 1711-12
CLOSET
CLOSET 1162 CONSENT OF HBSA II ARCHITECTS,
(250) 1711-13 7.4 A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
1714-4 LAUNDRY OR INVENTION ARE RESERVED AND WILL
MASTER BATH ENTRY BATHROOM
1700-10 1717-1
1714-5
1711-4 HALL
7.5 REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
1711-8
KITCHEN ENTRY CLOSET CLOSET 9
DINING 1714-1 1711-1 1711-11 1711-10
LIVING REVISION HISTORY
BALCONY 1717-3 DINING 1714-3
1700-11 LIVING 1714-2 MASTER TOILET 11
1717-4 BATHROOM HALL 1711-23
A/C 1711-24 1711-22
CLOSET1717-2
CLOSET
HALL
CLOSET
1711-16
LIVING
1711-7
12
1717-7 1711-15
1711-25 CLOSET
LAUNDRY 1711-17
ENTRY 1715-2 CLOSET A/C CLSET
13
1715-1 BATHROOM BEDROOM
1715-8 1711-19 1711-20
1715-9 1715-7 MASTER
MASTER
BEDROOM BEDROOM
KITCHEN 14
A/C 1711-5
1717-5 MASTER BATH 1711-21
1715-3 DINING
1717-6 OFFICE 1711-6
1711-18
LIVING
KITCHEN DINING 1715-6
CLOSET LAUNDRY 1715-4 1715-5 15
1716-7 1716-6
BEDROOM
1716-8
A/C
1716-10 CLOSET
1716-12 LIVING
1716-3
BATHROOM
1716-9 CLOSET
ENTRY 1716-2
1716-1
BATHROOM
1716-14
15.1
PROJECT#: 1709
B C C1 D D1 D2 E E2 F G H H1 H2 K J1 L K1
K2 L1 L2 N M1 Q N1 N2 R P1 P2 T Q1 Q2 V PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
2. CONDENSING UNITS SERVING CONDOS SHALL BE LOCATED TO MINIZE
REFRIGERANT PIPING LENGTHS. THE CURRENT LAYOUT IS A SUGGESTED LAYOUT.
THE CONTRACTOR SHALL SUBMIT A LAYOUT FOR APPROVAL AND VERY THAT LINE
LENGTHS WILL NOT EXCEED THE RECOMMENDED MAXIMUM.
3. CHWS AND CHWR PIPING TO AND FROM CHILLERS SHALL BE INSTALLED PER
DETAIL ON M5.1. architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
C1 D2
2
2.2
2.3
HP-G HP-F HP-F HP-G HP-F HP-F HP-F HP-F HP-F HP-F HP-F
HP-G HP-G
2.4
3
HP-F HP-F
HP-F HP-F HP-F HP-G HP-F DOAS 1. DOAS HP-F HP-F HP-F HP-F
18-1 18-2 HP-J HP-G
CU 18-3 CU 18-4
CU 18-1
CH-2 CH-1 CH-3
2. 1. CU 18-2 3.1
2. 1.
10" CHWS
3.
S1
3.
3.2
WOMEN'S (50)
RESTROOM S1 IDF RACKS PANTRY
1805 26"x18" 32"x18"
10" CHWR (120) 1808 25
25 1804 19 15
828-5
M8.1
STORAGE 23
23
14"x10" 15
A/C 18-2
CHWP-A 11-3 (195) 1802
18
4
2 1/2" CHWS
BIB VAV
FD
FD
12"x10" 17
CHWP-A VAV 5
26"x18"
(250) FAMILY RESTROOM R1 (370)
1806 11-2 (2425) TYP 2
DOAS 20 21
4.2
13
13
C
20"x16"
D D
9 9
C
AS-1 THE BEST OF MY KNOWLEDGE AND
C
CH
H
12"x8"
ELEV. 3,4,5,6 CONTROL 12
BELIEF THEY COMPLY W ITH ALL CITY,
MEN'S
D
38"x24" STATE AND FEDERAL REQUIREMENTS, AND
PTE68-B
828-4
PTE68-B
D
S1 RESTROOM I AM NOT PROVIDING CONTRACT
D
D
PTE68-B
8 8
PTE68-B
ELEV. 1&2 CONTROL 1807 ADMINISTRATION.
D
D
3
CH
S3
D D
C
C
12"x12"
C
2
D
6
LO
E OF U I S I A
EF-18-1 VAV 4
4
(820) M8.1
11-5 DRAFT
DRA F TBEER
AND
ANDDRIP
BEETOWER
R TOW ER
D RI TRAY
P TRAY (TYP. OF 5) 6 AT
5
12"x12"
NA
ST
VAV 16"x14" 10"x14"
11-4 7
7
34"x22" RAYMOND E. SMITH
1
8
30"x16" 16"x16"
2
LICENSE. No. 36823
7 REGISTERED
NG
MEC
PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
16x48 STAIR
7.1 CA L ENG I NE
PRESSURIZATION S3
THIS DRAWING IS CONFIDENTIAL AND
DN (810) NOT BE LOANED, REPRODUCED, COPIED,
(TYP. OF 5) EITHER WHOLLY OR IN PART, OR MADE
PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
7.4 OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
7.5
9 REVISION HISTORY
11
12
13
14
15
14.1
s a ii
2. CONDENSING UNITS SERVING CONDOS SHALL BE LOCATED TO MINIZE
REFRIGERANT PIPING LENGTHS. THE CURRENT LAYOUT IS A SUGGESTED LAYOUT.
THE CONTRACTOR SHALL SUBMIT A LAYOUT FOR APPROVAL AND VERY THAT LINE
LENGTHS WILL NOT EXCEED THE RECOMMENDED MAXIMUM.
architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
A1 C1 D2
2.3
2.4
3.2
DOAS
1 18-3
M8.1
HP-F
4
HP-F HP-F HP-G HP-F HP-F HP-G HP-J HP-G HP-G
2. 5
2 1/2" CHWS HP-F HP-H 4.2
2 1/2" CHWR AHU-6 HP-G
HP-G
HP-F HP-G
HP-F HP-H HP-F HP-H HP-F HP-F EF-18-1
SPF-B HP-F HP-G THESE PLANS AND SPECIFICATIONS HAVE
BEEN PREPARED BY ME OR UNDER MY
2. HP-F HP-F CLOSE PERSONAL SUPERVISION AND TO
1. THE BEST OF MY KNOWLEDGE AND
HP-F HP-G SPF-A BELIEF THEY COMPLY W ITH ALL CITY,
4.3 STATE AND FEDERAL REQUIREMENTS, AND
1. HP-F HP-G 2 I AM NOT PROVIDING CONTRACT
ADMINISTRATION.
48"x16"
NA
ST
HP-I HP-I HP-G 6
7
1. RAYMOND E. SMITH
8
LICENSE. No. 36823
REGISTERED
NG
7.1
MEC
PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
CA L ENG I NE
THIS DRAWING IS CONFIDENTIAL AND
CU 15-1 NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
7.4 PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
CU 15-2 REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
7.5
9 REVISION HISTORY
11
12
13
14
15
14.1
17
ROOF DECK - HVAC
15.1
A A2 B C D D1 E E2F G H H1 H2 K J1 L K1
K2 L1
LN2 M1 Q N1 N2 R P1 P2 T Q1 Q2 V W
PROJECT#: 1709
PHASE: PERMIT
TEAM: Author
CHECKER: Checker
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
s a ii
architects
P L L C
ii
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
3/4"CHWR 1
3/4"CHWS
Room
PITARD'S
232 2
HARD ROCK
T
71 51 71 59 62 61 60 63 58 57 64
1 1/2" Room
231
UP
94
LOADING
POS
TRASH
TRASH
PTE80-A
PTE80-A
81
100 T RETAIL
FCU 1-2
VAV 1-2
Room T FCU-4
95
124
VAV 1-4 50 52 56 52 50
229 FCU-3
1 1/2" AHU-2 84
T 96
93
3
EUH-1-3
3/4"CHWR
VAV 1-2 Room 91 85
50 52 56 52 50
T CONSTANT
160 CFM VAV 1-6 230 VAV 2-1 GRIND
82
FCU 1-3
2 1/2"CHWS
90
TRASH
TRASH
TRASH
88 83
PTE80-A
PTE80-A
(7 TYP)
PTE80-A
PTE80-A
3/4"CHWS
127
97
T
VAV 2-1 T
VAV 1-1 8"Ø EUH 1-2
VAV 1-3 64 57 58
TYP
63 60 61 62 59 64 57 58
89 92
T
VAV 3-2
2 1/2"CHWR
T VAV 1-6 EF 1-3
T VAV 2-3 SESSIONS
VAV 1-5 2"CHWR 2"CHWR 126 EF 1-3
2"CHWS 2"CHWS
VAV 3-2
VAV 3-1 3"CHWS
6" CHWS & EF 1-5
3"CHWR GENERATOR
CHWR-UP
1 43 40 44 45 42 41
121
M8.1 STAR SERVICES VAV 2-2 4
107 VAV 2-3 T T
54
STAIR 1
147
6"CHWS
Room MAIN LOBBY Room
225 T AND CHECK IN 234 53 RECEVING Room
110 59 102 241
VAV 3-1
6"CHWR
Room
CONDO 233
62
ELEVATOR Room 60
LOBBY 235 56
146 58
1"CHWS
VAV 2-2 Room T EF 1-2
D
67
PTE68-B
53
D
Room 123 122
FILE ROOM
227 Room 2 ELECTRICAL
CH
109 Room
D D
C
242 M8.1 EUH 1-1 VAULT
C
66
243
120 6
6"CHWS FCU 1-8
4"CHWR
Room 6"CHWR THESE PLANS AND SPECIFICATIONS HAVE
228 BEEN PREPARED BY ME OR UNDER MY
Room
VAV 1-7 247 8 CLOSE PERSONAL SUPERVISION AND TO
THE BEST OF MY KNOWLEDGE AND
VAV 3-4 EF 1-2 7 BELIEF THEY COMPLY W ITH ALL CITY,
STATE AND FEDERAL REQUIREMENTS, AND
FRONT OFFICE
4"CHWS
NA
ST
AHU-1 GAS METERS
Room RoomRoom Room Room WOMEN 107
255 248 249 113
WORK AREA
250 251 Room Room Room Room
RAYMOND E. SMITH
256 252 253 254
LICENSE. No. 36823
111
Room
MEN REGISTERED
NG
MEC
114 236
PROFESSIONAL ENGINEER
FCU 1-1
I
IN
ER
NI
HA
CA L ENG I NE
FRONT OFFICE STORAGE
MANAGER Room 118 9
112
KEH-5 238
43 40 44 45 42 41
3/4"CHWR
BIB PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
4"CHWS
33 33 34 35
SODA
PRIVATE CONDO CONDO 3"CHWR 1
12 CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
KEF-2
4"CHWR
ENTRANCE AND STORAGE 3"CHWS OR INVENTION ARE RESERVED AND WILL
31
3/4"CHWS
36 37 37 36
3"CHWR ARCHITECTS A PROFESSIONAL L.L.C.
101 ELECT.
KEH-6 24
143
3"CHWS MAU 1-1
23
30
RECEIVING
14 REVISION HISTORY
EF 1-1 OFFICE EF 1-6 LOADING
23
3"CHWR 119 103
30
24
47 46 48 6
3"CHWS
31
DEF-1 74
21 31 31
6 D EMP. REST. MAU 1-2
29
H H
144 3"CHWS
T
68
23 23
1"CHWR EUH-1-4 15
12
3"CHWS 20
25 19.1
16
EXIT CORRIDOR 1 1/4"CHWS
2 106
3"CHWR
Room M3.1
240
1"CHWS
27
1 1/4"CHWR
EMPLOYEE
KEF-1A
26
28
CHECK IN
117
7 28 8 11 10
9 KEH-2
48.1 6 2 5 5 5 4
KITCHEN 2 38 6
116
FCU 1-6
FCU 1-5
1 1/2"CHWS
Room
239
1 1 1 1 1 1
2"CHWR 2"CHWS
2"CHWS 2"CHWR 1 1
FIRE COMMAND
1 1/2" CHWR 3/4"CHWR 1
3/4"CHWS 1
115
COOLER 3/4"CHWR
COOLER BEER COOLER FREEZER FCU 1-7
1 1/2"CHWR 17
70 70 70 70
1 1/2"CHWS 70
1 1/4"CHWR
1 1/4"CHWS
A B C D E F G H 3/4"CHWS K L N Q R T V W
s a ii
architects
P L L C
ii
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
1.
HARD ROCK
2
40 39 36 38 37 40 41 39 36 38 37 35 34
1 1/4"CHWS
1 1/4" CHWS
1 1/4" CHWR
1 1/4"CHWR 3
BALLROOM MEETING ROOM MEETING ROOM
MEETING 203 204 VAV 6-6
3"CHWS
201
1"CHWS
3"CHWR
VAV 5-1 VAV 5-6 VAV 6-1
1"CHWS
VAV 5-2 VAV 5-5 PREFUNCTION VAV 6-2
AREA
FCU 2-3
202 1"CHWR
VAV 6-7
A/C 2-1
MDF ROOM
3/4"CHWR JANITOR
EF 2-2 237
1"CHWR
688 FU 240
AV RACKS A/C 2-2 VAV 5-8
1 207
M8.1 FCU 1 1/4"CHWS 4
BALLROOM
LOBBY 2-13 1 1/4"CHWR
VAV 5-7 205
3/4"CHWS
HALL
8"CHWS & CHWR-UP & VAV 6-5
8009 6" CHWS & CHWR-DN ELEVATOR
LOBBY
3/4"CHWR 3/4"CHWS 234
CIRCULATION
235
VAV 5-3 STAIR 4"CHWR VAV 6-3
FCU THESE PLANS AND SPECIFICATIONS HAVE
PRESSURIZATION 4"CHWR 4"CHWS
2-14 BEEN PREPARED BY ME OR UNDER MY
AHU-5 CLOSE PERSONAL SUPERVISION AND TO
2
4"CHWS FCU M8.1 THE BEST OF MY KNOWLEDGE AND
VAV 5-4 2-16 VAV 6-4 6 BELIEF THEY COMPLY W ITH ALL CITY,
STATE AND FEDERAL REQUIREMENTS, AND
I AM NOT PROVIDING CONTRACT
ADMINISTRATION.
4" CHWS & CHWR-DN
8 CERTIFIED CORRECT
7 LO
1
TE OF U I S I A
8
23 23
STAIR A
NA
ST
25
24
3 3
PRESSURIZATION
8
28
27 KITCHEN
RAYMOND E. SMITH
13.1 6
29
233
6
BALLROOM
231
2 6 16 LICENSE. No. 36823
26
REGISTERED
NG
26
5
MECHANICAL
MEC
26
30 30 WALK-IN 232 PROFESSIONAL ENGINEER
I
COOLER
IN
13
15
ER
7
NI
HA
CA L ENG I NE
22
30 30 DOAS
2-1
22
14
2-17 22 30
9
30 9 PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
22 22 22 WALK-IN
8
3/4"CHWR 22
30 30
COOLER FCU A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
9 OR INVENTION ARE RESERVED AND WILL
11
7
3/4"CHWR
FCU 12
FCU 2-4 8 2 5
REVISION HISTORY
PR & MARCOM 3/4"CHWR 2-12
MANAGER 531 FU FOOD TRANS.
1
14
1"CHWR
18
BEVERAGE 230
MANAGER 3/4"CHWS FCU OFFICE 3/4"
210 CATERING FCU 2-9 227
18
3/4"CD 22 3/4"
2-15 MANG. Room CHAIR STORAGE
1 1/4"CHWR
CONVENTION 223 224 229 3/4"CHWS
26
2 1"CHWS
M3.1 1
FCU 2-5
EF 2-1
ASST. GROUP STAIR 2
SALES 1 1/4"CHWS
219
212
ASST. TRANS.
SALES
213
Room
257
FCU 2-8
STORAGE
217
DIR. REVENUE RESERV. ECOMMERCE
MANA. MANAGER MANAGER
214 215 216
1 1/4"CHWS
1 1/4"CHWR
FCU 2-6 17
s a ii
architects
P L L C
ii
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
2"CHWS
HOTEL ROOM 1332
HOTEL ROOM
1308 1330
1 1/2"CHWR
HOTEL ROOM HOTEL ROOM
FCU-A
2"CHWS
1 1/2"CHWS
2"CHWS
1327 1329
HOTEL ROOM HOTEL ROOM HOTEL ROOM 2.4
2"CHWS
HOTEL ROOM
2"CHWS
2"CHWR
1314 1316 1317 HOTEL ROOM
2"CHWS
1315
2"CHWS
1318
2"CHWS
2"CHWS 2"CHWR
HOTEL ROOM HOTEL ROOM HOTEL ROOM
3
1 1/2"CHWS
2"CHWR
2"CHWR
1307 1319 1320 HOTEL ROOM
M
2"CHWR
2 1/2"CHWR
2"CHWR
5
2"CHWR
1 1/4"CHWS 1333
2"CHWR
HOTEL ROOM HOTEL ROOM M
1 1/2"CHWR
1 1/4"CHWR
2"CHWR
2"CHWR
1323 1325 12
3.1
2"CHWR
2"CHWS
8"CHWR
3.2
FCU-M
M 6"CHWS 6"CHWS 6"CHWS 6"CHWS 6"CHWS 2 1/2"CHWS
4 6"CHWR 6"CHWR 6"CHWR 6"CHWR
6"CHWR 6"CHWR
2 1/2"CHWS
2 1/2"CHWR
8"CHWS
1 HOTEL ROOM
FCU-C M8.1 4
2"CHWS
1335
HOTEL ROOM M
4"CHWS
4"CHWR
1305 13
4"CHWR
STAIR 1 5
147 FCU-K
4.2
1 1/2"CHWS
THESE PLANS AND SPECIFICATIONS HAVE
4"CHWS
3"CHWR BEEN PREPARED BY ME OR UNDER MY
2"CHWS
2"CHWR HOTEL ROOM CLOSE PERSONAL SUPERVISION AND TO
3"CHWS FCU-K 1336 THE BEST OF MY KNOWLEDGE AND
2"CHWS 10" CHWS & CHWR- UP &
1 1/2"CHWS
2 1/2"CHWR
8" CHWS & CHWR-DN 1 1/2"CHWS STATE AND FEDERAL REQUIREMENTS, AND
2"CHWR
4"CHWS
2 1/2"CHWS
HOTEL ROOM M
FCU-C 1304
I AM NOT PROVIDING CONTRACT
1 1/2"CHWR 13 ADMINISTRATION.
2"CHWR
1 1/2"CHWR
CERTIFIED CORRECT
STAIR M
HOTEL ROOM HOTEL ROOM HOTEL ROOM 4.3
2"CHWS
LO
E OF U I S I A
PRESSURIZATION
2 1/2"CHWS
4"CHWR
2
AT
2 1/2"CHWR
3"CHWS M8.1
6
NA
ST
M
3 FCU-C HOTEL ROOM HOTEL ROOM HOTEL ROOM
RAYMOND E. SMITH
1 1/2"CHWR
1324
1303 FCU-C 1326 HOTEL ROOM HOTEL ROOM
M FCU-C M 1328 1337 8 LICENSE. No. 36823
8 8 REGISTERED
NG
M
1 1/2"CHWS
MEC
STAIR 7 PROFESSIONAL ENGINEER
1. 19 PRESSURIZATION
I
FCU-C FCU-K IN
ER
STAIR 3
NI
HA
3"CHWR
1 1/2"CHWR
2"CHWR 140
CA L ENG I NE
BATH 2"CHWS HOTEL ROOM 7.1
1 1/2"CHWS 1300-1 M 1338
THIS DRAWING IS CONFIDENTIAL AND
HOTEL ROOM 13 NOT BE LOANED, REPRODUCED, COPIED,
M FCU-C EITHER WHOLLY OR IN PART, OR MADE
1302 FCU-C FCU-B FCU-B FCU-B
2 M PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
M CONSENT OF HBSA II ARCHITECTS,
19 16 A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
M M M OR INVENTION ARE RESERVED AND WILL
2"CHWS 18 17 13 REMAIN THE SOLE PROPERTY OF HBSA II
FCU-B HOTEL ROOM 7.4 ARCHITECTS A PROFESSIONAL L.L.C.
1301 2"CHWR
HOTEL ROOM M M M
1300 8 FCU-C 20
FCU-C
8
7.5
HOTEL ROOM
REVISION HISTORY
FCU-C HOTEL ROOM 1339 9
2"CHWS 1340
4"CHWR
2"CHWR FCU-C
FCU-L
3"CHWR FCU-K 11
Room
HOTEL ROOM 195 3"CHWS
1343
12
FCU-E M
14
M 13
4"CHWS
1 1/2"CHWS
1 M
8 M 1 1/4"CHWS
1 1/2"CHWR
1 1/2"CHWS 19 1 1/4"CHWR
14
1 1/2"CHWR
FCU-C 2"CHWR HOTEL ROOM
1341
2 1/2"CHWS 2"CHWS HOTEL ROOM
1342
2 1/2"CHWR
1 1/2"CHWS FCU-C 2"CHWR
FCU-C 1 1/2"CHWR 15
1 1/2"CHWR
1 1/2"CHWS 2"CHWS
M
6
1 1/4"CHWR
M FCU-C M FCU-E
2 1/2"CHWR 8 15
HB
Harry
baker
smith
S2
8"ø
FCU 4-1
20"x34" 20"x34"
HARD ROCK
MEZZANINE
2ND- 10"
28' FLOOR
MEZZANINE
27' - 10"
14"ø
2ND FLOOR RETAIL
19' - 0"
20"x22" 20"x22"
28"x12" 36"x30"
INTERMEDIATE
36"x30" PARKING
30"x30" 10' - 0"
24"ø 8"x18"
KEH-4 4"x96"
1ST FLOOR
GROUND LEVEL
0' - 0"
2 KITCHEN
AT
LO
E OF U I S I A
NA
ST
SCALE: 3/16" = 1'-0"
RAYMOND E. SMITH
LICENSE. No. 36823
REGISTERED
NG
MEC
PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
CA L ENG I NE
THIS DRAWING IS CONFIDENTIAL AND
NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
4TH FLOOR
PARKING
45' - 10"
S2 14"x22" KEF-3
(820) MAU-3
36"x16" 36"x16"
FCU 3-2
CU 3-4
S4
FCU 3-3 FCU 3-4 22"x14" (145)
8"/20" 7"ø 7"ø 8"/12" OA 8"/10" OA PARKING GARAGE
37' - 0"
s a ii
architects
P L L C
ii
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
24"ø
KEF-2
24"ø
24"ø
KEF-1B
24"x20"
24"ø
34"x24"
24"ø
22"x20"
DEF-1
30"x36"
NA
ST
2 KITCHEN DUCTS
SCALE: 18"x8"
MAU 1-2
42"x20"
RAYMOND E. SMITH
LICENSE. No. 36823
REGISTERED
NG
MEC
PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
CA L ENG I NE
30"x36" THIS DRAWING IS CONFIDENTIAL AND
NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
REVISION HISTORY
MECHANICAL SECTIONS
PROJECT#: 1709
PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
New Orleans, Louisiana 70112-1034
Tel. 504-586-1725
M3.2
1" QUICK FILL BYPASS
HB
PUMP DISCHARGE PUMP SUCTION
PRESSURE REDUCING VALVE. SET AT A Harry
PRESSURE 4 PSI HIGHER THAN PRESSURE AT
MANUAL AIR VENT
HIGH CAPACITY FLOAT TYPE AIR VENT TO HIGH POINT IN SYSTEM baker
WITH PLUG (TYPICAL) DRAIN (12 PSI INITIAL SETPOINT)
2-WAY CONTROL VALVE smith
s a ii
(TWO POSITION FOR FAN COILS.
MODULATING FOR AIR HANDLERS)
UNION (TYPICAL) BRACKETS FOR OVERHEAD SUPPORT LOW CAPACITY AUTOMATIC AIR VENT
TO
DRAIN
COIL DRAIN WITH HOSE END INTERNAL STRAINER. INSTALL UNITS PRESSURE GUAGE
END CONNECTION & CAP WITH SUFFICIENT HEIGHT TO
SHUT OFF REMOVE
LY VALVE 4" HIGH CONCRETE
PP STRAINER.
SU STRAINER WITH HOSE END P&T TEST HOUSEKEEPING PAD BLOWDOWN DRAIN VALVE WITH AIR CHARGING VALVE. PRESSURIZE
CONNECTION & CAP PORT CAPPED HOSE END CONNECTION DRY TANK TO EQUAL TO FILL
VALVE PRESSURE.
SHUT OFF VALVE (TYP.) FLOOR
HARD ROCK
TO 10', 1" FOR EQUIVALENT LENGTHS UP TO
NOTES: 30', AND 1 1/4" FOR EQUIVALENT LENGTHS UP TO 100'. BLADDER TYPE EXPANSION TANK
MOTORIZED
ACTUATOR
(TYP.) PRESSURE
GAUGE
(TYP) THERMOMETER (TYP)
BUTTERFLY SHUT-OFF
VALVE (TYP.) P&T TEST PORT (TYP)
FLEX CONNECTOR (TYP)
M CH-3
CH-1 M M CH-2
8"
8" 8"
CHILLER
(TYP)
8" 8"
TO
TO DRAIN
TO THESE PLANS AND SPECIFICATIONS HAVE
DRAIN BEEN PREPARED BY ME OR UNDER MY
DRAIN CLOSE PERSONAL SUPERVISION AND TO
THE BEST OF MY KNOWLEDGE AND
BELIEF THEY COMPLY WITH ALL CITY,
STATE AND FEDERAL REQUIREMENTS, AND
CONTROL PANEL I AM NOT PROVIDING CONTRACT
ADMINISTRATION.
8"CHS 8"CHS 8"CHS
CERTIFIED CORRECT
8"CHR 8"CHR 8"CHR
CHILLER
LO
TE OF U I S I A
DISCHARGE AUTOMATIC AIR VENT (TYP.) A
NA
ST
PRESSURE REDUCING VALVE PRESSURE
DIFFERENTIAL GAUGE RAYMOND E. SMITH
SUCTION LICENSE. No. 36823
TRUMPET CHWP (TYP. TO DRAIN PRESSURE
REGISTERED
NG
VALVE SEE DETAIL) SWITCH
MEC
FLOW 1" DOMESTIC PROFESSIONAL ENGINEER
SHUT-OFF
I
WATER AIR/DIRT IN
ER
BALANCING
NI
HA
VALVE
DEVICE CONNECTION
TO DRAIN
SEPARATOR CA L ENG I NE
(SEE DETAIL)
BRACKET THIS DRAWING IS CONFIDENTIAL AND
8"CHS 8"CHS 8"CHS TO LOAD
REFER TO NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
BALANCING 1/4" SHUT-OFF 8"CHR FROM LOAD
-
S
CH
PIPE STAND
HOUSEKEEPING EVAPORATOR
ET-1
PAD FLEXIBLE SHELL
FLOOR CONNECTOR
INERTIA BASE (TYP.)
PUMP (SEE
(ONLY REQUIRED FOR CHEMICAL POT
SCHEDULE)
10 HP AND ABOVE) FEEDER
(ELASO--- PAD FOR (SEE DETAIL) R STRAINER WITH
EXPANSION TANK CH BLOW DOWN
BELOW 10 HP)
(SEE
DETAIL)
MECHANICAL DETAILS
PROJECT#: 1709
PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
New Orleans, Louisiana 70112-1034
Tel. 504-586-1725
M5.1
HB
Harry
baker
smith
TOP
s a ii
architects
P L L C
ii
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
90° OR LESS [email protected] :−: hbsaii.com
TYPICAL since 1961
CEILING
HARD ROCK
WELDS LOCATED BELOW CEILING
ATTACH TO DISH MACHINE IN
STAIRWELL
PRESSURIZATION
FAN VFD SEQUENCE OF OPERATION: THESE PLANS AND SPECIFICATIONS HAVE
BEEN PREPARED BY ME OR UNDER MY
CLOSE PERSONAL SUPERVISION AND TO
1. STAIRWELL PRESSURIZATION FAN IS ACTIVATED BY THE FIRE ALARM THE BEST OF MY KNOWLEDGE AND
SYSTEM. BELIEF THEY COMPLY WITH ALL CITY,
STATE AND FEDERAL REQUIREMENTS, AND
I AM NOT PROVIDING CONTRACT
2. STAIRWELL SHALL MAINTAIN A POSITIVE PRESSURE OF 0.02 IWC. ADMINISTRATION.
MAINTAIN POSITIVE PRESSURE IN THE STAIRWELL AS DOORS OPEN AND CERTIFIED CORRECT
CLOSE IN VARIOUS COMBINATIONS, BY MODULATING THE FAN SPEED.
LO
TE OF U I S I A
3. WITH ALL DOORS CLOSED, OPENING FORCE REQUIRED TO OPEN A A
NA
ST
DOOR SHALL NOT BE MORE THAN 30 LBS/FT.
STAIRWELL OR ELEVATOR SHAFT
(TYPICAL EACH STAIRWELL. ELEVATORS RAYMOND E. SMITH
SUPPLIED FROM TOP ONLY ) LICENSE. No. 36823
REGISTERED
NG
MEC
PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
CA L ENG I NE
REFRIGERANT PIPING THIS DRAWING IS CONFIDENTIAL AND
NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
INSULATION
REVISION HISTORY
PRESSURIZATION AIR OUTLET
(TYPICAL EVERY OTHER FLOOR OR
AS SHOWN ON PLANS)
DRAW BAND
120V
COUNTER FLASHING
FIRE FIGHTER
CONTROL PANEL COUNTER FLASHING FLASHING COLAR
SAME MATERIAL AS
PIPE BY MECHANICAL
CONTRACTOR. SOLDER
TO REFRIGERANT LINE. ROOF FERRULE
ROOF ROOF
(+ POSITIVE PRESSURE) (- NEGATIVE PRESSURE) (REFER TO ARCHITECTURAL (REFER TO ARCHITECTURAL
PLANS FOR ROOF TYPE) PLANS FOR ROOF TYPE)
INSULATION
REFRIGERANT PIPING
MECHANICAL DETAILS
PROJECT#: 1709
PHASE: PERMIT
TEAM: MEI
3 STAIRWELL PRESSURIZATION
SCALE: N.T.S.
4 REFRIGERANT PIPING THRU ROOF
SCALE: N.T.S.
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
New Orleans, Louisiana 70112-1034
Tel. 504-586-1725
M5.2
HB
Harry
FLEXIBLE DUCT TO DIFFUSER INLET. baker
MAXIMUM LENGTH OF 5 FEET.
smith
s a ii
STAINLESS STEEL CLAMP WITH
WORM GEAR OPERATOR. STD SPRING END DAMPER CONNECTOR.
ALUMAGUARD, ALUMAGUARD ALL MANUAL DAMPER WITH COKING QUAD TYPE architects ii
WEATHER 16 GA. STEEL WALL P L L C
INDICATING REGULATOR.
OR ALUMAGUARD LITE - DO NOT ALLOW TO SLEEVE AND SHROUD DIFFUSER INLET NECK DIAMETER
PROVIDE AIR GAP FOR 189 Maple Ridge Drive Metairie, LA 70001
TOUCH ROOF MEMBRANE SYSTEM EXPANSION IN ACCORDANCE UNLESS SHOWN OTHERWISE ON EXTERNAL DUCT INSULATION (504)885−4477
[email protected] :−: hbsaii.com
WITH MANUFACTURERS PLANS OR SECTIONS.
RECOMMENDATIONS since 1961
RIGID INSULATION WITH
FSK, ASI OR FOIL
FACING DUCT
(BY OTHERS) BREAKAWAY SLIP JOINT SLEEVE MAIN DUCT.
(NO SCREWS PERMITTED)
1-1/2x1-1/2" 14 GAUGE
RETAINING ANGLE FASTENED
TO DAMPER SLEEVE ONLY
ROOF CURB (TYP.) W/ SCREWS ON 8"
(BY OTHERS) CENTERS MIN. NEOPRENE GASKET
ALUMAGUARD ALL WEATHER 1"
DAMPER OPERATOR. LOCATE
OR ALUMAGUARD LITE - DO ROOFING OUT OF AIR STREAM ON
NOT MEMBRANE EXTERIOR SIDE OF DUCT
ALLOW TO TOUCH ROOF (BY OTHERS)
HARD ROCK
FLOW
CAULK PERIMETER ANGLE
ROOF DECK ROOF DECK
INSTALL DAMPER IN ACCORDANCE WITH MFRS. UL APPROVED INSTRUCTIONS. EXTERNAL DUCT INSULATION
METAL FLASHING
(BY OTHERS)
CONDENSING UNIT
MOUNTED ON
ROOF
SUSPEND EXHAUSTER
FROM STRUCTURE WITH
BAND IRON STRIPS AT
EACH CORNER
PITCH SUCTION
LINE DOWN THESE PLANS AND SPECIFICATIONS HAVE
BEEN PREPARED BY ME OR UNDER MY
DUCTWORK - CLOSE PERSONAL SUPERVISION AND TO
THE BEST OF MY KNOWLEDGE AND
SEE PLANS FOR BELIEF THEY COMPLY WITH ALL CITY,
SIZE. STATE AND FEDERAL REQUIREMENTS, AND
I AM NOT PROVIDING CONTRACT
ADMINISTRATION.
CERTIFIED CORRECT
LO
TE OF U I S I A
A
NA
ST
RAYMOND E. SMITH
BACKDRAFT LIQUID LINE LICENSE. No. 36823
REGISTERED
NG
DAMPER
MEC
PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
SPORLAN CATCH- CA L ENG I NE
ALL
REPLACEABLE CORE THIS DRAWING IS CONFIDENTIAL AND
NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
SPORLAN REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
SEE-ALL LIQUID AND SUCTION LINES
THRU WALL WITH
SLEEVES. REVISION HISTORY
SOLENOID VALVE
COOLING COIL (TYP.)
EXPANSION VALVE
(TYP.)
CEILING ASSEMBLY
(SEE ARCH. DWG'S)
CEILING EXHAUSTER WITH
REMOVABLE EXHAUST
GRILLE FOR ACCESS TO AND DOUBLE SUCTION RISER
SERVICE OF BLOWER
ASSEMBLY
EXPANSION VALVE
BULB (TYP.)
MECHANICAL DETAILS
PROJECT#: 1709
PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
New Orleans, Louisiana 70112-1034
Tel. 504-586-1725
M5.3
HB
Harry
baker
DEDICATED OUTSIDE AIR UNITS SCHEDULE smith
s a ii
REMARKS: ACCESSORIES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. 1. VIBRATION ISOLATION ROOF CURB.
2. PROVIDE HOT GAS REHEAT TO SUPPLY NEUTRAL SUPPLY AIR. 2. BACKNET COMPATIBLE DIRECT DIGITAL CONTROLS WITH INTEGRATION .
3. MOUNT UNIT ON CURB HIGH ENOUGH TO ROUTE DUCT WITHIN THE CURB. 3. VARIABLE FREQUENCY DRIVE.
SUPPLY FAN DATA (EACH) EXHAUST FAN DATA (EACH) Dx COOLING COIL ENTHALPY WHEEL PERFORMANCE HOT GAS REHEAT GAS POST HEAT ELECTRICAL DATA BASIS OF DESIGN
OUTSIDE AIR EXHAUST AIR
architects ii
P L L C
WINTER
189 Maple Ridge Drive Metairie, LA 70001
EAT EAT LAT LAT SUMMER (°F) (°F) SUMMER (°F) MAX MIN FINAL (504)885−4477
FAN SUPPLY EXT SP MOTOR FAN EXHAUST ESP MOTOR TOT SENS DB WB DB WB EAT-D EAT-W LAT-D LAT-W EAT-D EAT-W WINTE CAPACITY LAT OUTPUT EAT LAT MODULATION PREFILTER FILTER VOLT PH FREQ FLA MCA MOCP WEIGHT [email protected] :−: hbsaii.com
MARK LOCATION QTY. (CFM) (IWC) (HP) QTY. (CFM) (IWC) (HP) (MBH) (MBH) (°F) (°F) (°F) (°F) B B B B EAT LAT B B R EAT (MBH) (°F) (MBH) (°F) (°F) (%) REFRIGERANT (MERV) (MERV) (V) (φ) (Hz) (A) (A) (A) MFG MODEL (lbs) ACCESSORIES REMARKS since 1961
DOAS 18-1 ROOF 2 4300 1 3 2 2300 1 1 593.9 265.7 79.4 72.6 51.4 51.4 84.5 79.9 79.4 72.6 15 44.1 75 63.8 68 181.1 72 475.2 15 70 25-100 R-410A 8 11 460 3 60 0.0 109.7 125 VALENT VPRE-352-50C-60I-C-1DA 9862 1., 2., 3. 1., 2.
DOAS 18-2 ROOF 2 4300 1 3 2 2300 1 1 593.9 265.7 79.4 72.6 51.4 51.4 84.5 79.9 79.4 72.6 15 44.1 75 63.8 68 181.1 72 475.2 15 70 25-100 R-410A 8 11 460 3 60 0.0 109.7 125 VALENT VPRE-352-50C-60I-C-1DA 9862 1., 2., 3. 1., 2., 3.
DOAS 18-3 ROOF 2 2915 0.75 1.5 506.6 253 84.5 79.9 52.8 52.4 120.9 72 346.3 15 70 25-100 R-410A 8 11 460 3 60 87.9 100 VALENT VPR-352-40C-60I-C-0DX 7138 1., 2., 3. 1., 2.
AIR COOLED CHILLER SCHEDULE HVAC FANS SCHEDULE I AM NOT PROVIDING CONTRACT
ADMINISTRATION.
CERTIFIED CORRECT
REMARKS: ACCESSORIES: REMARKS:
LO
1. PROVIDE VARIABLE SPEED COMPRESSOR(S) WITH VARIABLE SPEED/FREQUENCY DRIVES. 1. FACTORY INSTALLED FLOW SWITCH. 1. PROVIDE EQUIP ROOF BASE/CURB AS REQUIRED FOR ROOF MOUNTED FAN. FAN BASE/CURB AND FAN ATTACHMENTS SHALL WITHSTAND WIND LOADING AS INDICATED ON STRUCTURAL DRAWINGS AND SPECIFICATIONS.
TE OF U I S I A
2. PROVIDE MFG STANDARD SOUND CONTROL OPTION. 2. EVAPORATOR HEATER POWERED BY SEPARATE 115V, 15A POWER SOURCE. 2. DISCONNECT TO BE PROVIDED BY UNIT MANUFACTURER. A
NA
ST
NOM EVAPORATOR PERFORMANCE AMBIENT EFFICIENCY ELECTRICAL 3. PROVIDE VARIABLE FREQUENCY DRIVE.
CAP # OF EWT LWT DESIGN MIN FLOW WPD VOLT PH FREQ MCA MOCP WEIGHT 4. UNIT SHALL BE SEALED FOR OUTDOOR USE. PROVIDE INSECT SCREEN AND INCLUDE DRAIN CONNECTION.
RAYMOND E. SMITH
MARK (TON) REFRIGERANT PASSES (°F) (°F) FLOW (GPM) (GPM) (FT) EAT (°F) COP EER IPLV NPLV (V) (φ) (Hz) (A) (A) (lbs) MFG MODEL ACCESSORIES REMARKS LICENSE. No. 36823
5. PROVIDE SOLID STATE SPEED CONTROLLER REGISTERED
NG
MEC
CH-1 350 R-134A 2 56 42 686.66 418.8 16.7 95 3 9.5 17.18 14.5 460 3 60 686.6 1000 20672 CARRIER 30XV350 1., 2. 1., 2. PROFESSIONAL ENGINEER
6. FAN SHALL BE UL LISTED FOR SMOKE CONTROL OPERATION.
I
CH-2 350 R-134A 2 56 42 686.66 418.8 16.7 95 3 9.5 14.835 14.5 460 3 60 686.6 1000 20672 CARRIER 30XV350 1., 2. 1., 2. IN
ER
NI
HA
CH-3 350 R-134A 2 56 42 686.66 418.8 16.7 95 3 9.5 14.835 14.5 460 3 60 686.6 1000 20672 CARRIER 30XV350 1., 2. 1., 2. 7. PROVIDE LINE VOLTAGE THERMOSTAT.
CA L ENG I NE
8. INTERLOCK FAN WITH CONDENSING UNIT. PROVIDE FILTER ON FAN INTAKE.
FAN DATA SOUND DATA ELECTRICAL DATA BASIS OF DESIGN THIS DRAWING IS CONFIDENTIAL AND
NOT BE LOANED, REPRODUCED, COPIED,
EA OA/MIN EXT SP FAN MOTOR MOTOR SOUND VOLT PH FREQ FLA WEIGHT EITHER WHOLLY OR IN PART, OR MADE
PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
MARK LOCATION SYSTEM TYPE (CFM) (CFM) (IWC) RPM (HP) (W) (dBA) SONES (V) (φ) (Hz) (A) MFG MODEL (lbs) REMARKS CONSENT OF HBSA II ARCHITECTS,
DEF-1 1ST FLOOR DISHWASHER EXHAUST INLINE 600 0.75 1330 0.5 8.2 115 1 60 8.4 CAPTIVEAIRE SIF11DD 126 2. A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
DEF-2 2ND FLOOR DISHWASHER EXHAUST INLINE 600 0.75 1330 0.5 8.2 115 1 60 8.4 CAPTIVEAIRE SIF11DD 126 2. REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
DEF-3 2ND FLOOR DISHWASHER EXHAUST INLINE 600 0.75 1330 0.5 8.2 115 1 60 8.4 CAPTIVEAIRE SIF11DD 126 2.
EF 1-1 1ST FLOOR RESTROOM EXHAUST INLINE 600 0.4 1574 0.167 57 8.3 115 1 60 GREENHECK SG-95-VG 51 2., 5.
EF 1-2 1ST FLOOR PUMP ROOM INLINE 1040 0.2 716 0.125 46 3.9 115 1 60 GREENHECK SQ-140-C 98 2., 5., 7. REVISION HISTORY
EF 1-3 1ST FLOOR GENERATOR ROOM INLINE 800 0.2 640 0.125 44 3.2 115 1 60 GREENHECK SQ-140-C 98 2., 5., 7.
EF 1-4 1ST FLOOR RESTROOM EXHAUST CEILING 50 0.2 772 10 0.3 115 1 60 GREENHECK SP-A70 13 2., 5.
EF 1-5 1ST FLOOR LOADING DOCK INLINE 1305 0.4 955 0.75 55 7.1 115 1 60 GREENHECK SQ-140-VG 98 2., 5.
EF 1-6 1ST FLOOR LOADING DOCK INLINE 315 0.3 1163 0.167 49 5.3 115 1 60 GREENHECK SG-95-VG 51 2., 5.
EF 1.5-1 1ST FLR MEZZ RESTROOM EXHAUST CEILING 50 0.2 772 10 0.3 115 1 60 GREENHECK SP-A70 13 2., 5.
EF 2-1 2ND FLOOR RESTROOM EXHAUST INLINE 400 0.3 1374 0.1 51 6 115 1 60 GREENHECK SQ-90-G 60 2., 5.
EF 2-2 2ND FLOOR RESTROOM EXHAUST INLINE 875 0.4 843 0.125 51 5.6 115 1 60 GREENHECK SQ-140-C 90 2., 5.
EF 2.5-1 2ND FLR MEZZ RESTROOM EXHAUST INLINE 500 0.5 1168 0.25 55 8.4 115 1 60 GREENHECK SQ-99-VG 58 2., 5.
EF 4-1 2ND FLOOR RESTROOM EXHAUST INLINE 750 0.4 1725 0.167 60 10 115 1 60 GREENHECK SQ-95-VG 60 2., 5.
EF-18-1 ROOF RESTROOM EXHAUST UPBLAST 910 0.2 GREENHECK CSP-A110
EF-A SEE DWGS. RESTROOM EXHAUST CEILING 50 0.2 950 20 30 0.8 120 1 60 0.26 GREENHECK CSP-A110 25
EF-B SEE DWGS. RESTROOM EXHAUST CEILING 75 0.2 950 20 30 0.8 120 1 60 0.26 GREENHECK CSP-A110 25
KEF-1A 1ST FLR MEZZ KITCHEN EXHAUST TUBULAR INLINE 10672 2 1247 7.5 22 460 3 60 9.6 CAPTIVEAIRE RMFI245CA 515 2.
KEF-1B 1ST FLR MEZZ KITCHEN EXHAUST TUBULAR INLINE 5336 2 1247 5 22 460 3 60 9.6 CAPTIVEAIRE RMFI245CA 515 2.
KEF-2 1ST FLR MEZZ KITCHEN EXHAUST TUBULAR INLINE 6325 2 1079 5 17.7 460 3 60 6.8 CAPTIVEAIRE RMFI245CA 488 2.
KEF-3 2ND FLR KITCHEN EXHAUST TUBULAR INLINE 9000 2.2 1196 7.5 21 208 3 60 8.4 CAPTIVEAIRE RMFI245CA 515 2.
SF 1.5-1 2ND FLOOR RESTROOM EXHAUST CEILING 0 30 0.2 1131 0.02 38 2.2 115 1 60 GREENHECK SQ-65-G 47 2., 5., 8.
SPF 5-1 5TH FLOOR STAIRWELL PRESSURIZATION TUBE AXIAL 5500 460 3 60 GREENHECK 900
SPF-A ROOF STAIRWELL PRESSURIZATION TUBE AXIAL 12925 1 1105 7.5 78 27 460 3 60 GREENHECK QEID-27-85-B75 900 1., 2., 3., 4., 6.
SPF-B ROOF STAIRWELL PRESSURIZATION TUBE AXIAL 11000 1 1109 5 78 27 460 3 60 GREENHECK QEID-27-70-B50 800 1., 2., 3., 4., 6.
s a ii
2. PROVIDE THERMAL OVERLOAD PROTECTION FOR ELECTRICAL HEATERS. 2. FUSED SERVICE SWITCH.
REMARKS:
3. PROVIDE BACNET THERMOSTAT COMPATIBLE WITH ENERGY MANAGEMENT SYSTEM. 3. DRAIN PAN FLOAT SWITCH.
1. ALL TERMINAL UNITS ARE VARIABLE FLOW AND VOLUME DOWN TO MIN. AIR FLOW SHOWN UNLESS NOTED OTHERWISE
4. SELECT UNIT FOR MEDIUM FAN SPEED AT DESIGN AIRFLOW. 4. BUILT-IN CONDENSATE PUMP.
2. PROVIDE UNIT WITH DDC CONTROLS OPTION. PROVIDE 24VAC CONTROL WIRING FROM MAIN CONTROL XFMR CABINET TO CONNECT TO TERMINAL UNITS.
5. PROVIDE STAND-ALONE CONTROLS WITH 24VAC T'STAT TO BE FURNISHED AND INSTALLLED BY MECHANICAL CONTRACTOR. 5. 2-WAY NC VALVE WITH 24V ACTUATOR.
3. BOX SHALL BE INSULATED WITH A FOIL FACED LINER.
6. SCHEDULED ESP DOES NOT INCLUDE CABINET LOSSES, DIRTY FILTER, ELECTRIC HEAT STRIP, COOLING COIL, AND RETURN AIR GRILLE. 6. 24VAC WALL THERMOSTAT.
4. SEE DUCT CONNECTION AT REHEAT BOX DETAIL. architects ii
ELECTRIC HEATING ELECTRICAL P L L C
5. PROVIDE MINIMUM OF 2 DUCT DIAMETERS OF STRAIGHT DUCT ON INLET FOR ALL TERMINAL UNITS UNLESS OTHERWISE ALLOWED BY UNIT MANUFACTURER.
FAN DATA COOLING COIL DATA DATA BASIS OF DESIGN DATA 189 Maple Ridge Drive Metairie, LA 70001
MAX 6. PROVIDE STAGED ELECTRIC HEAT. (504)885−4477
[email protected] :−: hbsaii.com
SUPPLY OA EXT SP MOTOR (FAN) TOT CAP SENS CAP EAT DB EAT WB LAT DB LAT WB FLOW PD CAP WEIGHT VOLT PH FREQ AIRFLOW DATA HEATING DATA ELECTRICAL CAPACITY BASIS OF DESIGN
MARK LOCATION AREA SERVED TYPE (CFM) (CFM) (IWC) (HP) QTY. (MBH) (MBH) (°F) (°F) (°F) (°F) (GPM) (FT) (kW) LAT (°F) (lbs) MFG MODEL (V) (φ) (Hz) ACCESSORIES REMARKS NO. OF MIN since 1961
FCU 1-1 1ST FLOOR BOH HORIZONTAL 900 245 0.15 0.5 1 28.8 19.6 81.5 67.7 55 53.9 4.1 4 7 85 200 CARRIER BCHD 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. MIN COOLING HEATING CAPACITY STAGES/ EAT LAT
FCU 1-2 1ST FLOOR ROCK SHOP HORIZONTAL 930 190 0.15 0.5 1 32.1 21.8 77.8 66.5 55.9 54.9 4.6 4 5 85 285 CARRIER BCHD 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. MARK LOCATION (CFM) (CFM) (CFM) (kW) SCR (°F) (°F) VOLT (V) PH (φ) FREQ (Hz) MFG MODEL SIZE REMARKS
FCU 1-4 1ST FLOOR ENTRY LOBBY HORIZONTAL 700 70 0.15 0.5 1 21.2 16.3 77.7 65.1 55.8 54.7 3 4 3 85 200 CARRIER BCHD 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. VAV 1-1 1ST FLOOR 470 2000 900 9.5 2 52 84 480 3 60 KRUEGER LMHS 12 1., 2., 3., 4., 5., 6.
FCU 1-5 1ST FLOOR KITCHEN HORIZONTAL 6660 810 0.15 1 1 200.8 155.9 80.6 67.3 58.9 57.7 28.7 4 15 85 285 CARRIER BCHD 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. VAV 1-2 1ST FLOOR 140 1000 650 6.5 2 52 84 480 3 60 KRUEGER LMHS 9 1., 2., 3., 4., 5., 6.
FCU 1-6 1ST FLOOR KITCHEN HORIZONTAL 6600 810 0.15 1 1 199.2 154.3 80.5 67.3 58.9 57.7 28.5 4 14 85 285 CARRIER BCHD 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. VAV 1-3 1ST FLOOR 850 1100 850 9 2 52 84 480 3 60 KRUEGER LMHS 9 1., 2., 3., 4., 5., 6.
FCU 1-7 1ST FLOOR FIRE CONTROL HORIZONTAL 550 70 0.15 1 1 14.3 11.6 78.2 66.1 58.8 57.7 2.1 4 7 85 285 CARRIER BCHD 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. VAV 1-4 1ST FLOOR 600 2400 1050 11 SCR 52 84 480 3 60 KRUEGER LMHS 14 1., 2., 3., 4., 5., 6.
FCU 1-8 1ST FLOOR BOH HORIZONTAL 1260 170 0.15 0.5 1 38.5 32 83.4 68.2 59.9 58.5 5.5 4 2 85 285 CARRIER BCHD 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. VAV 1-5 1ST FLOOR 800 1050 800 8 2 52 84 480 3 60 KRUEGER LMHS 9 1., 2., 3., 4., 5., 6.
FCU 2-1 2ND FLOOR MEETING RM 203 HORIZONTAL 1750 300 0.15 0.5 1 64.5 42.2 76.9 66.1 54.5 53.6 9.2 4 12 85 200 CARRIER BCHD 480 3 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. VAV 1-6 1ST FLOOR 600 1300 600 6 2 52 84 480 3 60 KRUEGER LMHS 10 1., 2., 3., 4., 5., 6.
FCU 2-2 2ND FLOOR MEETING RM 204 HORIZONTAL 1750 300 0.15 0.5 1 66.5 43.4 76.2 65.5 53.6 52.8 9.5 4 12 85 200 CARRIER BCHD 480 3 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. VAV 1-7 1ST FLOOR 35 110 35 0.5 1 52 84 480 3 60 KRUEGER LMHS 5 1., 2., 3., 4., 5., 6.
FCU 2-3 2ND FLOOR 2ND FLR CORR HORIZONTAL 4050 250 0.3 0.5 1 83.6 72.2 71.2 61.1 54.7 53.7 12 4 19 85 200 CARRIER BCHD 480 3 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. VAV 2-1 1ST FLOOR 330 1700 350 4 1 52 84 480 3 60 KRUEGER LMHS 12 1., 2., 3., 4., 5., 6.
VAV 2-2 1ST FLOOR 385 1000 400 2 1 52 84 480 3 60 KRUEGER LMHS 9 1., 2., 3., 4., 5., 6.
HARD ROCK
FCU 2-5 2ND FLOOR 211 VERT. STACK 340 0.15 0.067 1 7.6 6.9 73.3 60.1 52 50.8 1.09 2.1 2 85 415 KRUEGER KVPH 06 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6.
FCU 2-6 2ND FLOOR 211 VERT. STACK 460 0.15 0.04 1 7.8 7.1 73 60.1 52 50.8 1.12 1.5 2 85 400 KRUEGER KVPH 04 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. VAV 2-4 1ST FLOOR 435 700 450 3 1 52 70 480 3 60 KRUEGER LMHS 7 1., 2., 3., 4., 5., 6.
FCU 2-7 2ND FLOOR 211 VERT. STACK 85 0.15 0.03 1 1.9 1.7 73.3 60.1 52 50.8 0.27 0.9 1 85 400 KRUEGER KVPH 03 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. VAV 3-1 1ST FLOOR 750 1500 750 8 2 52 84 480 3 60 KRUEGER LMHS 12 1., 2., 3., 4., 5., 6.
FCU 6-1 6TH FLOOR STORAGE 602 VERT. STACK 535 0.2 0.33 1 11.6 10.9 78.4 65.3 59.5 58.3 1.7 2.1 3 85 415 KRUEGER KVPH 06 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. COP DATA DATA CERTIFIED CORRECT
FCU 6-2 6TH FLOOR STORAGE 602 VERT. STACK 535 0.2 0.33 1 11.6 10.9 78.4 65.3 59.5 58.3 1.7 2.1 3 85 415 KRUEGER KVPH 06 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. TOT AMB TOT AMB or SEER FLA LO
FCU 7-1 7TH FLOOR ENGINEERING VERT. STACK 770 0.2 0.5 1 12.2 11 79.5 63.8 55 53.5 1.8 5 3 85 460 KRUEGER KVPH 12 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. WT MODULE CAP DB CAP TEMP HSP or VOLT PH FREQ MCA MOCP COMP RLA 1 EACH TE OF U I S I A
MARK (lbs) LOCATION QTY (MBH) (°F) (MBH) (°F) REFRIG. F IEER EER (V) (φ) (Hz) (A) (A) QTY (A) QTY (A) MFG MODEL ACC REMARKS
A
NA
ST
FCU 7-2 7TH FLOOR ENGINEERING VERT. STACK 770 0.2 0.5 1 12.2 11 79.5 63.8 55 53.5 1.8 5 3 85 460 KRUEGER KVPH 12 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6.
FCU-8-1 8TH FLOOR AMENITY HORIZONTAL 2100 0.3 0.25 1 43.7 40.6 76.3 62.4 55 53.7 6.3 5 7.5 85 480 3 60 1., 2., 3., 4. 1., 2., 3., 4. CU 1-1 66 3RD FLOOR 1 6.1 95 R-410A 15 208 1 60 7.9 15 1 6.8 1 0.17 DAIKIN RKN09NMVJU 2. 1., 3.
CU 1-3 283 1ST FLR MEZZ 1 37.4 95 14.7 30 R-410A 9 16 11 208 1 60 27 30 1 19.6 2 0.3 DAIKIN RZQ42PVJU8 2. 1. RAYMOND E. SMITH
FCU-A GUESTROOM GUESTROOM VERT. STACK 280 0.05 0.33 1 7.8 5.8 74 61 55 54 1.2 0.9 2.5 80 400 KRUEGER KVPH 03 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. LICENSE. No. 36823
FCU-B GUESTROOM GUESTROOM VERT. STACK 325 0.05 0.33 1 9.1 6.7 74 61 55 54 1.3 1.5 2.5 80 400 KRUEGER KVPH 04 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. CU 1.5-1 140 1ST FLR MEZZ 1 21.3 95 9.0 30 R-410A 4.56 18 12.7 208 1 60 22.6 25 1 17.5 1 0.42 DAIKIN 3MXL24RMVJU 2 1., 3. REGISTERED
NG
MEC
FCU-C GUESTROOM GUESTROOM VERT. STACK 380 0.05 0.33 1 10.7 7.8 74 61 55 54 1.5 2.1 2.5 80 415 KRUEGER KVPH 06 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. CU 2-1 115 3RD FLOOR 1 16.7 95 R-410A 15 208 1 60 18.3 20 1 14.5 1 0.53 DAIKIN RKN24NMVJU 2. 1., 3. PROFESSIONAL ENGINEER
I
IN
ER
CU 2-2 106 3RD FLOOR 1 12.4 95 R-410A 15 208 1 60 13.3 15 1 10.0 1 0.38 DAIKIN RKN18NMVJU 2. 1., 3. NI
HA
CA L ENG I NE
FCU-D GUESTROOM GUESTROOM VERT. STACK 725 0.05 0.5 1 20.4 14.9 74 61 55 54 2.9 3 4.5 80 415 KRUEGER KVPH 08 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6.
FCU-E GUESTROOM GUESTROOM VERT. STACK 800 0.05 0.5 1 22.5 16.4 74 61 55 54 3.2 3.9 4.5 80 460 KRUEGER KVPH 10 277 1 60 1., 2., 3., 4. 1., 2., 3., 4., 5., 6. CU 3-3 283 3RD FLOOR 1 28.2 95 0.0 30 R-410A 0 16 11 208 1 60 27 30 1 19.6 2 0.3 DAIKIN RZQ42PVJU8 2. 1., 3., 4.
FCU-F 2ND & MEZZ OFFICES WALL MOUNT 270 0.1 0.02 1 6.7 6.2 75 62.6 54.1 53.8 1.2 0.8 3 85 85 EMI WCP12D3 208 1 60 1., 4., 5., 6. 1., 2., 5. CU 3-4 283 3RD FLOOR 1 28.2 95 0.0 30 R-410A 0 16 11 208 1 60 27 30 1 19.6 2 0.3 DAIKIN RZQ42PVJU8 2. 1., 3., 4.
THIS DRAWING IS CONFIDENTIAL AND
FCU-K GUESTROOM GUESTROOM HORIZONTAL 280 0.05 0.33 1 7.8 5.8 74 61 55 54 1.2 0.9 2.5 80 225 KRUEGER KHFH 277 1 60 1., 2., 3., 4. 1., 2., 3., 4. CU 7-3 115 7TH FLOOR 1 20.7 95 R-410A 15 208 1 60 18.3 20 1 14.5 1 0.53 DAIKIN RKN24NMVJU 2. 1., 3., 4. NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
FCU-L HORIZONTAL 380 0.05 0.33 1 10.7 6.2 74 61 55 54 1.5 0.9 2 80 225 KRUEGER KHFH 277 1 60 1., 2., 3., 4. 1., 2., 3., 4. CU 7-4 283 7TH FLOOR 1 40.5 95 R-410A 15 208 1 60 27 30 1 19.6 2 0.3 DAIKIN RZR42PVJU8 2. 1., 3., 4. PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CU 15-1 294 14TH FLOOR 1 57 95 R-410A 15 208 1 60 34.2 50 1 26.4 1 1.2 CARRIER 24VNA961 2. 2. CONSENT OF HBSA II ARCHITECTS,
FCU-L GUESTROOM GUESTROOM HORIZONTAL 380 0.05 0.33 1 10.7 6.2 74 61 55 54 1.5 0.9 2 80 225 KRUEGER KHFH 277 1 60 1., 2., 3., 4. 1., 2., 3., 4. A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
CU 15-2 170 14TH FLOOR 1 17.8 95 0.0 30 R-410A 0 15.3 0 208 1 60 11.8 20 1 9.0 1 0.5 CARRIER 24VNA918 2. 2. OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
CU 18-1 106 18TH FLOOR 1 12.4 95 R-410A 15 208 1 60 13.3 15 1 10.0 1 0.38 DAIKIN RKN18NMVJU 2. 1., 3., 4. ARCHITECTS A PROFESSIONAL L.L.C.
CU 18-2 283 18TH FLOOR 1 40.5 95 R-410A 15 208 1 60 27 30 1 19.6 2 0.3 DAIKIN RZR42PVJU8 2. 1., 3., 4.
CU 18-3 283 18TH FLOOR 1 40.5 95 R-410A 15 208 1 60 27 30 1 19.6 2 0.3 DAIKIN RZR42PVJU8 2. 1., 3., 4.
REVISION HISTORY
CU 18-4 283 18TH FLOOR 1 40.5 95 R-410A 15 208 1 60 27 30 1 19.6 2 0.3 DAIKIN RZR42PVJU8 2. 1., 3., 4.
HP-F 170 ROOF 1 17.8 95 0.0 30 R-410A 0 15.3 0 208 1 60 11.8 20 1 9.0 1 0.5 CARRIER 24VNA918 2.
HP-G 200 ROOF 1 24 95 0.0 30 R-410A 0 15.3 0 208 1 60 16.5 25 1 12.8 1 0.5 CARRIER 24VNA924 2.
HP-H 200 ROOF 1 28.8 95 0.0 30 R-410A 0 15.3 0 208 1 60 18.1 30 1 14.1 1 0.5 CARRIER 24VNA930 2.
HP-I 215 ROOF 1 34.8 95 0.0 30 R-410A 0 15 0 208 1 60 22.1 35 1 16.7 1 1.2 CARRIER 24VNA936 2.
HP-J 245 ROOF 1 41.5 95 0.0 30 R-410A 0 15 0 208 1 60 27.6 40 1 21.1 1 1.2 CARRIER 24VNA942 2.
s a ii
2. INSTALL TANK PER MANUFACRURER'S RECOMMENDATION. TANK SHALL BE ASME RATED. 2. MOUNT ON VIBRATION ISOLATION PUMP BASE. 2. TRIPLE DUTY VALVE
CHARGE BASIS OF DESIGN 3. PUMPS SHALL BE PIPED IN REVERSE RETURN CONFIGURATION. 3. FLEXIBLE PIPE CONNECTIONS
ACCEPT VOL TANK VOL PRESS WEIGHT
(GAL) (GAL) (PSI) (lbs) SYSTEM ELECTRICAL DATA BASIS OF DESIGN
MARK LOCATION SYSTEM TYPE MANUFACTURER MODEL REMARKS
FLOW HEAD PRESSURE MOTOR MOTOR VOLT PH FREQ WEIGHT
ET-1 ROOF CHILLED WATER DIAPHRAGM 8.1 105 50 BELL AND GOSSETT D-200V 600 1., 2.
MARK SYSTEM LOCATION TYPE (GPM) (FT) (PSI) (HP) (RPM) (V) (φ) (Hz) MANUFACTURER MODEL (LBS) ACCESSORIES REMARKS architects ii
CHWP-A CHILLED WATER ROOF BASE MOUNTED END-SUCTION 690 100 100 25 460 3 60 BELL AND GOSSETT E-1510 4EB 1., 2., 3. 1., 2., 3. P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
HARD ROCK
CAPACITY NO. OF LAT VOLTAGE PHASE FREQUENCY WEIGHT
MARK (kW) STAGES (°F) (V) (φ) (Hz) MANUFACTURER MODEL (LBS) ACCESSORIES REMARKS
LINEAR DIFFUSERS AND GRILLES SCHEDULE DIFFUSER, REGISTERS, AND GRILLES SCHEDULE
REMARKS: ACCESSORIES: REMARKS: ACCESSORIES:
1. PROVIDE ACCESS PANEL AT MANUAL VOLUME DAMPER FOR DIFFUSERS MOUNTED IN GYPSUM BOARD CEILINGS WHERE BRANCH DUCT 1. OPPOSED BLADE DAMPER (UNLESS IN BRANCH DUCT). 1. PROVIDE ACCESS PANEL AT MANUAL VOLUME DAMPER FOR DIFFUSERS MOUNTED IN GYPSUM BOARD CEILINGS WHERE BRANCH 1. OPPOSED BLADE DAMPER (UNLESS IN BRANCH DUCT).
SERVING THE DIFFUSER IS ALSO ABOVE INACCESSIBLE CEILING. 2. ENGINEERED SLOT PLENUM DUCT SERVING THE DIFFUSER IS ALSO ABOVE INACCESSIBLE CEILING. 2. EQUALIZING GRID.
2. COORDINATE DIFFUSER LOCATION WITH ARCHITECTURAL REFLECTED CEILING PLANS AND WALL ELEVATIONS. COORDINATE COLOR 3. 2. ALL DIFFUSERS IN THE SAME ROOM OR SPACE SHALL HAVE THE SAME FACE/MODULE SIZE USING THE LARGEST SIZE OF THE 3. SECTORIZING BAFFLE (LESS THAN 4-WAY BLOW).
SELECTION WITH ARCHITECT AND SUBMIT FOR APPROVAL. 4. SCHEDULED DIFFUSERS IN THAT SPACE. 4. ROUND NECK ADAPTOR.
3. FURNISH AND INSTALL BRANCH DUCT TO MATCH NECK SIZE UNLESS OTHERWISE NOTED ON PLANS. 5. 3. FURNISH AND INSTALL BRANCH DUCT TO MATCH NECK SIZE UNLESS OTHERWISE NOTED ON PLANS. 5. 24"X24" MOUNTING FRAME.
4. BORDER TYPE TO MATCH CEILING/WALL CONSTRUCTION. COORDINATE WITH ARCHITECTURAL CEILING/WALL PLAN. 6. 4. FRAME TYPE TO MATCH CEILING/WALL CONSTRUCTION. COORDINATE WITH ARCHITECTURAL CEILING/WALL PLAN. 6. 12"X12" MOUNTING FRAME.
5. 7. 5. 4-WAY THROW PATTERN UNLESS OTHERWISE NOTED ON PLANS. 7.
6. 8. 6. COORDINATE DIFFUSER LOCATION WITH ARCHITECTURAL REFLECTED CEILING PLANS AND WALL ELEVATIONS. 8.
AIRFLOW RANGE NECK SIZE (INCH) DIFFUSER SIZE (INCH) # OF SLOT/BAR BASIS OF DESIGN AIRFLOW RANGE NECK SIZE (INCH) FACE SIZE (INCH) BLADE BASIS OF DESIGN
MIN. MAX. DIA. LENGTH SLOTS/BAR SPACING MAX MIN. MAX. DIA. DEFLECTION SPACING MAX
MARK SERVICE LOCATION TYPE (CFM) (CFM) (ø) L W (INCH) WIDTH S (INCH) . NC MFG. MODEL ACCESSORIES REMARKS MARK SERVICE LOCATION TYPE (CFM) (CFM) (ø) L W LENGTH WIDTH (°) (INCH) . NC MFG. MODEL ACCESSORIES REMARKS
L1 SUPPLY CEILING LINEAR SLOT 0 60 5 - - 12 - 2 1 30 PRICE SDS100 1. 1., 2., 3., 4. S1 SUPPLY CEILING PLAQUE 0 95 6 - - 24 24 - - 30 PRICE ASPD 3. 1., 3., 4., 5., 6.
L1 SUPPLY CEILING LINEAR SLOT 61 120 6 - - 24 - 2 1 30 PRICE SDS100 1., 2. 1., 2., 3., 4. S1 SUPPLY CEILING PLAQUE 96 205 8 - - 24 24 - - 30 PRICE ASPD 3. 1., 3., 4., 5., 6.
L1 SUPPLY CEILING LINEAR SLOT 121 180 6 - - 36 - 2 1 30 PRICE SDS100 1., 2. 1., 2., 3., 4. S1 SUPPLY CEILING PLAQUE 206 375 10 - - 24 24 - - 30 PRICE ASPD 3. 1., 3., 4., 5., 6.
L1 SUPPLY CEILING LINEAR SLOT 181 240 7 - - 48 - 2 1 30 PRICE SDS100 1., 2. 1., 2., 3., 4. S1 SUPPLY CEILING PLAQUE 376 605 12 - - 24 24 - - 30 PRICE ASPD 3. 1., 3., 4., 5., 6.
L1 SUPPLY CEILING LINEAR SLOT 241 300 8 - - 60 - 2 1 30 PRICE SDS100 1., 2. 1., 2., 3., 4. S1 SUPPLY CEILING PLAQUE 606 855 14 - - 24 24 - - 30 PRICE ASPD 3. 1., 3., 4., 5., 6.
L2 SUPPLY SIDEWALL LINEAR BAR GRILLE 0 75 - 4 6 4 6 10 1/2 30 PRICE LBP 16B 1. 1., 2., 3., 4. S1 SUPPLY CEILING PLAQUE 851 980 15 - - 24 24 - - 30 PRICE ASPD 3. 1., 3., 4., 5., 6.
L2 SUPPLY SIDEWALL LINEAR BAR GRILLE 76 110 - 6 6 6 6 10 1/2 30 PRICE LBP 16B 1. 1., 2., 3., 4. S2 SUPPLY CEILING PLAQUE 0 35 4 - - 12 12 - - 30 PRICE ASPD 3. 1., 3., 4., 5., 6.
L2 SUPPLY SIDEWALL LINEAR BAR GRILLE 111 180 - 10 6 10 6 10 1/2 30 PRICE LBP 16B 1. 1., 2., 3., 4. S2 SUPPLY CEILING PLAQUE 36 60 5 - - 12 12 - - 30 PRICE ASPD 3. 1., 3., 4., 5., 6.
L2 SUPPLY SIDEWALL LINEAR BAR GRILLE 181 290 - 16 6 16 6 10 1/2 30 PRICE LBP 16B 1. 1., 2., 3., 4. S2 SUPPLY CEILING PLAQUE 61 95 6 - - 12 12 - - 30 PRICE ASPD 3. 1., 3., 4., 5., 6.
L2 SUPPLY SIDEWALL LINEAR BAR GRILLE 291 505 - 28 6 28 6 10 1/2 30 PRICE LBP 16B 1. 1., 2., 3., 4. S2 SUPPLY CEILING PLAQUE 96 145 7 - - 12 12 - - 30 PRICE ASPD 3. 1., 3., 4., 5., 6.
L3 RETURN/EXHAUST CEILING LINEAR SLOT 0 90 6 - - 12 - 2 1 30 PRICE SDR100 2., 3., 4. S2 SUPPLY CEILING PLAQUE 146 205 8 - - 12 12 - - 30 PRICE ASPD 3. 1., 3., 4., 5., 6. THESE PLANS AND SPECIFICATIONS HAVE
L3 RETURN/EXHAUST CEILING LINEAR SLOT 91 180 8 - - 24 - 2 1 30 PRICE SDR100 2. 2., 3., 4. S3 SUPPLY CEILING CURVED VANE 0 75 - 6 4 L+1-3/4 W+1-3/4 - - 30 PRICE CVD 1. 1., 2., 3., 4., 5., 6. BEEN PREPARED BY ME OR UNDER MY
CLOSE PERSONAL SUPERVISION AND TO
L3 RETURN/EXHAUST CEILING LINEAR SLOT 181 270 9 - - 36 - 2 1 30 PRICE SDR100 2. 2., 3., 4. S3 SUPPLY CEILING CURVED VANE 76 140 - 8 6 L+1-3/4 W+1-3/4 - - 30 PRICE CVD 1. 1., 2., 3., 4., 5., 6. THE BEST OF MY KNOWLEDGE AND
BELIEF THEY COMPLY WITH ALL CITY,
L3 RETURN/EXHAUST CEILING LINEAR SLOT 271 360 10 - - 48 - 2 1 30 PRICE SDR100 2. 2., 3., 4. S3 SUPPLY CEILING CURVED VANE 141 225 - 10 8 L+1-3/4 W+1-3/4 - - 30 PRICE CVD 1. 1., 2., 3., 4., 5., 6. STATE AND FEDERAL REQUIREMENTS, AND
I AM NOT PROVIDING CONTRACT
L3 RETURN/EXHAUST CEILING LINEAR SLOT 361 450 12 - - 60 - 2 1 30 PRICE SDR100 2. 2., 3., 4. S3 SUPPLY CEILING CURVED VANE 226 325 - 12 10 L+1-3/4 W+1-3/4 - - 30 PRICE CVD 1. 1., 2., 3., 4., 5., 6. ADMINISTRATION.
L4 RETURN/EXHAUST SIDEWALL LINEAR BAR GRILLE 0 75 - 4 6 4 6 10 1/2 30 PRICE LBP 15B 2., 3., 4. S3 SUPPLY CEILING CURVED VANE 326 445 - 14 12 L+1-3/4 W+1-3/4 - - 30 PRICE CVD 1. 1., 2., 3., 4., 5., 6. CERTIFIED CORRECT
L4 RETURN/EXHAUST SIDEWALL LINEAR BAR GRILLE 76 110 - 6 6 6 6 10 1/2 30 PRICE LBP 15B 2., 3., 4. S4 SUPPLY SIDEWALL LOUVERED 0 105 - 6 5 L+1-3/4 W+1-3/4 30 3/4 30 PRICE 22 1. 2., 3., 4., 6.
LO
L4 RETURN/EXHAUST SIDEWALL LINEAR BAR GRILLE 111 180 - 10 6 10 6 10 1/2 30 PRICE LBP 15B 2., 3., 4. S4 SUPPLY SIDEWALL LOUVERED 106 255 - 10 6 L+1-3/4 W+1-3/4 30 3/4 30 PRICE 22 1. 2., 3., 4., 6.
TE OF U I S I A
L4 RETURN/EXHAUST SIDEWALL LINEAR BAR GRILLE 181 290 - 16 6 16 6 10 1/2 30 PRICE LBP 15B 2., 3., 4. S4 SUPPLY SIDEWALL LOUVERED 256 650 - 14 10 L+1-3/4 W+1-3/4 30 3/4 30 PRICE 22 1. 2., 3., 4., 6. A
NA
ST
L4 RETURN/EXHAUST SIDEWALL LINEAR BAR GRILLE 291 505 - 28 6 28 6 10 1/2 30 PRICE LBP 15B 2., 3., 4. S4 SUPPLY SIDEWALL LOUVERED 651 1500 - 20 16 L+1-3/4 W+1-3/4 30 3/4 30 PRICE 22 1. 2., 3., 4., 6.
L5 SUPPLY CEILING LINEAR SLOT 720 960 12 - - 72 - 5 1 30 PRICE SDS100 1., 2. 1., 2., 3., 4. S4 SUPPLY SIDEWALL LOUVERED 1501 2980 - 30 24 L+1-3/4 W+1-3/4 30 3/4 30 PRICE 22 1. 2., 3., 4., 6. RAYMOND E. SMITH
LICENSE. No. 36823
L6 SUPPLY CEILING LINEAR SLOT 420 719 12 - - 72 - 3 1 30 PRICE SDS100 1., 2. 1., 2., 3., 4. R1 RETURN/EXHAUST CEILING EGGCRATE 0 130 - 6 6 12 12 - - 30 PRICE 80 2., 3., 4., 6. REGISTERED
NG
MEC
S3 SUPPLY CEILING CURVED VANE 0 75 - 6 4 L+1-3/4 W+1-3/4 - - 30 PRICE CVD 1. 1., 2., 3., 4., 5., 6. R1 RETURN/EXHAUST CEILING EGGCRATE 131 280 - 8 8 12 12 - - 30 PRICE 80 2., 3., 4., 6. PROFESSIONAL ENGINEER
I
IN
ER
S3 SUPPLY CEILING CURVED VANE 76 140 - 8 6 L+1-3/4 W+1-3/4 - - 30 PRICE CVD 1. 1., 2., 3., 4., 5., 6. R1 RETURN/EXHAUST CEILING EGGCRATE 281 800 - 12 12 24 24 - - 30 PRICE 80 2., 3., 4., 6. NI
HA
S3 SUPPLY CEILING CURVED VANE 141 225 - 10 8 L+1-3/4 W+1-3/4 - - 30 PRICE CVD 1. 1., 2., 3., 4., 5., 6. R1 RETURN/EXHAUST CEILING EGGCRATE 801 2015 - 20 18 24 24 - - 30 PRICE 80 2., 3., 4., 6. CA L ENG I NE
S3 SUPPLY CEILING CURVED VANE 226 325 - 12 10 L+1-3/4 W+1-3/4 - - 30 PRICE CVD 1. 1., 2., 3., 4., 5., 6. R1 RETURN/EXHAUST CEILING EGGCRATE 2016 2225 - 22 20 24 24 - - 30 PRICE 80 2., 3., 4., 6.
THIS DRAWING IS CONFIDENTIAL AND
S3 SUPPLY CEILING CURVED VANE 326 445 - 14 12 L+1-3/4 W+1-3/4 - - 30 PRICE CVD 1. 1., 2., 3., 4., 5., 6. R2 RETURN SIDEWALL LOUVERED 0 80 - 6 5 L+1-3/4 W+1-3/4 - 3/4 30 PRICE 60 2., 3., 4., 6. NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
S4 SUPPLY SIDEWALL LOUVERED 0 105 - 6 5 L+1-3/4 W+1-3/4 30 3/4 30 PRICE 22 1. 2., 3., 4., 6. R2 RETURN SIDEWALL LOUVERED 81 125 - 8 6 L+1-3/4 W+1-3/4 - 3/4 30 PRICE 60 2., 3., 4., 6. PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
S4 SUPPLY SIDEWALL LOUVERED 106 255 - 10 6 L+1-3/4 W+1-3/4 30 3/4 30 PRICE 22 1. 2., 3., 4., 6. R2 RETURN SIDEWALL LOUVERED 126 185 - 10 8 L+1-3/4 W+1-3/4 - 3/4 30 PRICE 60 2., 3., 4., 6. CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
S4 SUPPLY SIDEWALL LOUVERED 256 650 - 14 10 L+1-3/4 W+1-3/4 30 3/4 30 PRICE 22 1. 2., 3., 4., 6. R2 RETURN SIDEWALL LOUVERED 186 260 - 12 10 L+1-3/4 W+1-3/4 - 3/4 30 PRICE 60 2., 3., 4., 6. OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
S4 SUPPLY SIDEWALL LOUVERED 651 1500 - 20 16 L+1-3/4 W+1-3/4 30 3/4 30 PRICE 22 1. 2., 3., 4., 6. R2 RETURN SIDEWALL LOUVERED 261 435 - 18 12 L+1-3/4 W+1-3/4 - 3/4 30 PRICE 60 2., 3., 4., 6. ARCHITECTS A PROFESSIONAL L.L.C.
S4 SUPPLY SIDEWALL LOUVERED 1501 2980 - 30 24 L+1-3/4 W+1-3/4 30 3/4 30 PRICE 22 1. 2., 3., 4., 6. R2 RETURN SIDEWALL LOUVERED 436 605 - 24 14 L+1-3/4 W+1-3/4 - 3/4 30 PRICE 60 2., 3., 4., 6.
R2 RETURN SIDEWALL LOUVERED 1250 1720 - 48 20 L+1-3/4 W+1-3/4 - 3/4 30 PRICE 60 2., 3., 4., 6.
REVISION HISTORY
T1 TRANSFER SIDEWALL LOUVERED 0 330 - 20 16 L+1-3/4 W+1-3/4 - - 30 PRICE ATG 2., 4., 6.
T1 TRANSFER SIDEWALL LOUVERED 331 600 - 26 20 L+1-3/4 W+1-3/4 - - 30 PRICE ATG 2., 4., 6.
MECHANICAL SCHEDULES
PROJECT#: 1709
PHASE: PERMIT
TEAM: Author
CHECKER: Checker
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
New Orleans, Louisiana 70112-1034
Tel. 504-586-1725
M6.3
GENERAL CONTROL NOTES CHW AHU CONTROL POINTS LIST CHILLED WATER SYSTEM CONTROL POINTS LIST CONTROLS ABBREVIATIONS
HB
Harry
1. CONTROL POINTS FOR MAU-1 SHALL BE VISIBLE THROUGH A BACNET NETWORK INTERFACE HARDWARE POINTS SOFTWARE POINTS HARDWARE POINTS SOFTWARE POINTS ABBREVIATION ABBREVIATED TERMS
GRAPHIC
GRAPHIC
CARD. A POINTS LIST IS NOT PROVIDED. THE POINTS SHOWN ON THE DIAGRAM ON DWG M600 baker
SCHED
SCHED
TREND
TREND
ALARM
ALARM
AI - ANALOG INPUT
SHALL BE REPRESENTATIVE OF THE MINIMUM POINTS REQUIRED TO BE AVAILABLE THROUGH
THE INTERFACE. THE MANUFACTURER SHALL PROVIDE THEIR STANDARD CONTROL SCHEME
AO - ANALOG OUTPUT smith
POINT DESCRITPION AI AO BI BO AV BV POINT DESCRITPION AI AO BI BO AV BV
s a ii
CLOSELY RELATED TO SEQUENCE DEFINED ON CONTROL DIAGRAM. ASC - APPLICATION SPECIFIC CONTROLLER
DISCHARGE AIR TEMPERATURE X X X X X CHILLER WATER DIFFERENTIAL PRESSURE X X X CR - CONTROL RELAY
2. CONTROL POINTS FOR DOAS-1 SHALL BE VISIBLE THROUGH A BACNET NETWORK INTERFACE MIXED AIR TEMPERATURE X X X X X CHILLER 1 WATER FLOW X X X
CARD. A POINTS LIST IS NOT PROVIDED. THE POINTS SHOWN ON THE DIAGRAM ON DWG M600 CT - CURRENT TRANSDUCER SENSOR
SHALL BE REPRESENTATIVE OF THE MINIMUM POINTS REQUIRED TO BE AVAILABLE THROUGH RETURN AIR TEMPERATURE X X X X X CHILLER 2 WATER FLOW X X X DAT - DISCHARGE AIR TEMPERATURE
THE INTERFACE. THE MANUFACTURER SHALL PROVIDE THEIR STANDARD CONTROL SCHEME COOLING COIL AIR TEMPERATURE X X X X X CHILLER 1 WATER RETURN TEMPERATURE X X X DDC - DIRECT DIGITAL CONTROL
CLOSELY RELATED TO SEQUENCE DEFINED ON CONTROL DIAGRAM. MINIMUM OUTSIDE AIR X X X X X CHILLER 1 WATER SUPPLY TEMPERATURE X X X DI - DIGITAL INPUT
architects ii
3. CONTROL POINTS FOR RTU-3 SHALL BE VISIBLE THROUGH A BACNET NETWORK INTERFACE TEMPERATURE CHILLER 2 WATER RETURN TEMPERATURE X X X X P L L C
DO - DIGITAL OUTPUT
CARD. A POINTS LIST IS NOT PROVIDED. THE POINTS SHOWN ON THE DIAGRAM ON DWG M603 CHILLER 2 WATER SUPPLY TEMPERATURE X X X 189 Maple Ridge Drive Metairie, LA 70001
SHALL BE REPRESENTATIVE OF THE MINIMUM POINTS REQUIRED TO BE AVAILABLE THROUGH DP - DIFFERENTIAL PRESSURE (504)885−4477
SUPPLY AIR STATIC PRESSURE X X X X X MAIN CHILLED WATER RETURN TEMPERATURE X X X [email protected] :−: hbsaii.com
THE INTERFACE. THE MANUFACTURER SHALL PROVIDE THEIR STANDARD CONTROL SCHEME EAT - ENTERING AIR TEMPERATURE
DISCHARGE AIR HUMIDITY X MAIN CHILLED WATER SUPPLY TEMPERATURE X X X since 1961
CLOSELY RELATED TO SEQUENCE DEFINED ON CONTROL DIAGRAM. LAN - LOCAL AREA NETWORK
RETURN AIR HUMIDITY X X X X X CHILLED WATER PUMP 1 VFD SPEED X X X X
4. SEE EQUIPMENT SCHEDULES AND CONTROL DIAGRAMS FOR EQUIPMENT REQUIRING VFDS. LAT - LEAVING AIR TEMPERATURE
OUTSIDE AIR HUMIDITY X X CHILLED WATER PUMP 2 VFD SPEED X X X X
5. CONTROL POINTS LISTS INCLUDE ALL POINTS FOR DIFFERENT EQUIPMENT TYPES. SEE MAT - MIXED AIR TEMPERATURE
OUTSIDE AIR TEMPERATURE X X X CHILLED WATER BYPASS VALVE X X X
CONTROL DIAGRAMS FOR THOSE POINTS ASSOCIATED WITH INDIVIDUAL PIECES OF PID - PROPORTIONAL INTEGRAL DERIVATIVE
EQUIPMENT. SUPPLY FAN FLOW X X X X X MAIN CHILLED WATER SUPPLY TEMPERATURE SETPOINT RESET X X X RAT - RETURN AIR TEMPERATURE
RETURN AIR FLOW X X X X X CHILLER 1 EMERGENCY SHUTDOWN X X X VFD - VARIABLE FREQUENCY DRIVE
CHILLER 2 EMERGENCY SHUTDOWN X X X
FREEZE STAT X X X X X MAIN CHILLED WATER ISOLATION VALVE STATUS X X X
SUPPLY STATIC HIGH LIMIT X X X X X CHILLED WATER PUMP 1 STATUS X X X
RETURN STATIC LOW LIMIT
HUMIDITY HIGH LIMIT
X
X
X
X
X
X
X
X
X
X
CHILLED WATER PUMP 2 STATUS
CHILLED WATER PUMP 1 VFD
X
X
X X
X
VFD CONTROL POINTS LIST
HARDWARE POINTS SOFTWARE POINTS
GRAPHIC
PRE-FILTER PRESSURE DROP X X X X X CHILLED WATER PUMP 2 VFD X X
TREND
ALARM
FINAL FILTER PRESSURE DROP X X X X X CHILLED WATER PUMP 1 VFD ALARM X
HARD ROCK
FIRE ALARM SHUTDOWN X X X CHILLED WATER PUMP 2 VFD ALARM X
POINT DESCRIPTION AI AO BI BO AV BV
FIRE ALARM SMOKE EVACUATION X X X CHILLED WATER PUMP 1 VFD AMP X X
GRAPHIC
CHILLED WATER DIFFERENTIAL PRESSURE SETPOINT X X X
SCHED
TREND
ALARM
SUPPLY FAN ENABLE X X X X CHILLED WATER FLOW SETPOINT X X X
SUPPLY FAN STATUS X X X X CHILLED WATER ISOLATION VALVE FAILURE X POINT DESCRIPTION AI AO BI BO AV BV
CHILLED WATER ISOLATION VALVE IN HAND X FAN START/STOP X X X X
SUPPLY FAN X - CFM FLOW X X X X X CHILLED WATER PUMP 1 FAILURE X FAN STATUS X X X
RETURN FAN X - CFM FLOW X X X X X CHILLED WATER PUMP 2 FAILURE X STATIC PRESSURE X X
VFD ALARM X X X X CHILLED WATER PUMP 1 RUNNING IN HAND X SCHEDULE X
VFD HERTZ X X X X CHILLED WATER PUMP 2 RUNNING IN HAND X AIRFLOW X X X
VFD AMPS X X X X HIGH CHILLED WATER DIFFERENTIAL PRESSURE X DAMER POSITION X
LOW CHILLED WATER DIFFERENTIAL PRESSURE X
LOW CHILLED WATER X
CHILLER 1 RUNNING IN HAND X
CHILLER 2 RUNNING IN HAND X VAV CONTROL POINTS LIST
HIGH MAIN CHILLED WATER SUPPLY TEMPERATURE X
DBP-1 CONTROL POINTS LIST
GRAPHIC
HARDWARE POINTS SOFTWARE POINTS
LOW MAIN CHILLED WATER SUPPLY TEMPERATURE X
TREND
ALARM
COLOR GRAPHIC
HARDWARE SOFTWARE HIGH MAIN CHILLED WATER RETURN TEMPERATURE X SCH
POINTS POINTS LOW MAIN CHILLED WATER RETURN TEMPERATURE X POINT DESCRITPION AI AO BI BO AV BV ED
CHILLER 1 FAILURE X X ZONE CO2 (PPM) X X X
SCHEDULE
CHILLER 2 FAILURE X X ZONE TEMP X X X
TREND
ALARM
LEAD CHILLER FAILURE X X AIRFLOW X X X
POINT NAME AI AO BI BO AV BV X ZONE SET POINT ADJ. X X X THESE PLANS AND SPECIFICATIONS HAVE
X ZONE DAMPER X X X BEEN PREPARED BY ME OR UNDER MY
DOM. HOT WATER RETURN TEMPERATURE X CLOSE PERSONAL SUPERVISION AND TO
DOM. HOT WATER SUPPLY TEMPERATURE X HEATING STAGE X X X THE BEST OF MY KNOWLEDGE AND
BELIEF THEY COMPLY WITH ALL CITY,
DOM. HOT WATER PUMP 1 STATUS X STATE AND FEDERAL REQUIREMENTS, AND
I AM NOT PROVIDING CONTRACT
DOM. HOT WATER PUMP 2 STATUS X ADMINISTRATION.
LO
HARDWARE POINTS SOFTWARE POINTS HARDWARE POINTS SOFTWARE POINTS TE OF U I S I A
GRAPHIC
GRAPHIC
HIGH DOM. HOT WATER SUPPLY TEMP.
A
SCHED
SCHED
TREND
TREND
ALARM
ALARM
NA
ST
LOW DOM. HOT WATER SUPPLY TEMP.
DOM. HOT WATER PUMP 1 FAILURE
POINT DESCRITPION AI AO BI BO AV BV POINT DESCRIPTION AI AO BI BO AV BV RAYMOND E. SMITH
DOM. HOT WATER PUMP 1 RUNNING IN HAND
FILTER DIFFERENTIAL PRESSURE X X X UNIT CONTROLS OCCUPIED/UNOCCUPIED X X X X LICENSE. No. 36823
DOM. HOT WATER PUMP 2 FAILURE REGISTERED
NG
MEC
BUILDING STATIC PRESSURE X X X SUPPLY AIR TEMPERATURE SETPOINT X X X PROFESSIONAL ENGINEER
DOM. HOT WATER PUMP 2 RUNNING IN HAND
I
OUTSIDE AIRFLOW X X X UNIT STATUS X X X IN
ER
NI
HA
CA L ENG I NE
DOM. HOT WATER PUMP 1 RUNTIME EXCEEDED
DISCHARGE AIR TEMPERATURE X X X FAN STATUS X X X
DOM. HOT WATER PUMP 2 RUNTIME EXCEEDED
RETURN AIR TEMPERATURE X X X FAN START/STOP X X X
THIS DRAWING IS CONFIDENTIAL AND
ZONE TEMPERATURE X X X VFD FAULT X X X NOT BE LOANED, REPRODUCED, COPIED,
MIXED AIR TEMPERATURE X X X FAN FAILURE X EITHER WHOLLY OR IN PART, OR MADE
PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
RETURN AIR CARBON DIOXIDE X X X FAN RUNNING IN HAND X CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
RETURN AIR HUMIDITY X X OUTSIDE AIR DAMPER X X OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
SUPPLY FAN VFD SPEED X X X AIRFLOW MEASURING STATION (S/A) X X X ARCHITECTS A PROFESSIONAL L.L.C.
NATURAL GAS HEATING COIL VALVE X X X FILTER DIFFERENTIAL PRESSURE SWITCH X X X
COOLING COIL VALVE X X X ELECTRIC HEATER ENABLE/DISABLE X
REVISION HISTORY
ZONE SETPOINT ADJUSTMENT X X X ELECTRIC HEATER STATUS X X X
OUTSIDE AIR DAMPER X X X DX COOLING ENABLE/DISABLE X
RETURN AIR DAMPER X X X DX COOLING STATUS X X X
EXHAUST AIR DAMPER X X X SUPPLY AIR STATIC PRESSURE X
SUPPLY FAN START/STOP X X X HIGH STATIC PRESSURE SWITCH X X
HIGH STATIC X AIRSTREAM TEMPERATURE X X X X
SUPPLY FAN STATUS X X X AIRSTREAM HUMIDITY X X X X
SUPPLY FAN VFD ALARM X AIRSTREAM ENTHALPY X
SMOKE DETECTOR (RETURN) X X DUCT SMOKE DETECTOR X
SMOKE DETECTOR (SUPPLY) X X
CONDENSATE SAFETY SWITCH X X X X
GRAPHIC
SCHED
TREND
ALARM
CHW FCU CONTROL POINTS LIST
HARDWARE POINTS SOFTWARE POINTS POINT DESCRIPTION AI AO BI BO AV BV
GRAPHIC
ON/OFF SETTING X X X
SCHED
TREND
ALARM
ON/OFF (MONITORING) X X X
POINT DESCRIPTION AI AO BI BO AV BV ALARM SIGNAL X X
HEATING STAGE 1 X X X ERROR CODE X X
SCHEDULE X OPERATIONAL MODE (SETTING) X X X
ZONE TEMPERATURE X X X OPERATIONAL MODE (MONITORING) X X X
ZONE TEMPERATURE ADJUST X X FAN SPEED (SETTING) X X X
DISCHARGE AIR TEMPERATURE X X X FAN SPEED (MONITORING X X X
ZONE HUMIDITY X X X ROOM TEMPERATURE (SETTING) X X X
HEATING SETPOINT X X ROOM TEMPERATURE (MONITORING) X X X
COOLING SETPOINT X X X FILTER SIGN X X X
FAN SPEED X X X FILTER SIGN RESET X X X
CHILLED WATER VALVE X X X PROHIBITION ON/OFF X X
FAN STATUS X PROHIBITION MODE X X MECHANICAL CONTROLS 1
HIGH ZONE HUMIDITY X PROHIBITION FILTER SIGN RESET X X
LOW ZONE HUMIDITY X PROHIBITION SET TEMPERATURE X X
PROJECT#: 1709
HIGH ZONE TEMPERATURE X M-NET COMMUNICATION STATE X X X
LOW ZONE TEMPERATURE X SYSTEM FORCED OFF X X X PHASE: PERMIT
HIGH DISCHARGE TEMPERATURE X AIR DIRECTION (SETTING) X X X TEAM: MEI
LOW DISCHARGE TEMPERATURE X AIR DIRECTION (MONITORING) X X X
FILTER CHANGE REQUIRED X EXP. CONTROLLER COMMUNICATION STATE X X X CHECKER: RS
FAN RUNNING IN HAND X SCALE: AS NOTED
FAN FAILURE X X
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
New Orleans, Louisiana 70112-1034
Tel. 504-586-1725
M7.1
HB
HORIZONTAL CHILLED WATER FAN COIL UNIT WITH ELECTRIC REHEAT- SEQUENCE OF OPERATION (FCU'S TYPICAL FOR ALL EXCEPT HOTEL GUESTROOM Harry
FCU'S): COOLING COIL VALVE: baker
RUN CONDITIONS:
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE
smith
THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND MODULATE THE
s a ii
FOLLOWING MODES: COOLING COIL VALVE TO MAINTAIN ITS COOLING SETPOINT.
• OCCUPIED MODE: THE UNIT SHALL MAINTAIN THE COOLING SHALL BE ENABLED WHENEVER:
• A 74°F (ADJ.) COOLING SETPOINT
• A 70°F (ADJ.) HEATING SETPOINT. • THE ZONE TEMPERATURE IS ABOVE COOLING SETPOINTAND THE FAN IS ON
• UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN • LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS architects ii
• A 85°F (ADJ.) COOLING SETPOINT. THAN 40°F (ADJ.). P L L C
• A 55°F (ADJ.) HEATING SETPOINT. 189 Maple Ridge Drive Metairie, LA 70001
FAN STATUS: (504)885−4477
[email protected] :−: hbsaii.com
ALARMS SHALL BE PROVIDED AS FOLLOWS:
CHW THE CONTROLLER SHALL MONITOR THE FAN STATUS.ALARMS SHALL BE PROVIDED since 1961
AI - ZONE TEMP • HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE AS FOLLOWS:
RA SA
COOLINGSETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).
T • LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING • FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
M SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.). • FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
BI - FAN STATUS ZONE SETPOINT ADJUST: ELECTRIC HEATING STAGE:
CT
CS AI - ZONE SETPOINT ADJUST THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND STAGE THE
AO - FAN SPEED (HI-MED-LO) COOLING SETPOINTS AT THE ZONE SENSOR. HEATING TO MAINTAIN ITS HEATING SETPOINT. TO PREVENT SHORT CYCLING,
ELEC THE STAGE SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME. THE HEATING
*BI - CONDENSATE SAFETY SWTICH ZONE OPTIMAL START: SHALL BE ENABLED WHENEVER:
THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS • THE ZONE TEMPERATURE IS BELOW HEATING SETPOINT
HARD ROCK
BO - HEATING STAGE 1
AO - COOLING VALVE WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF SCHEDULED
M
OCCUPIED PERIOD. FILTER HOURS:
• LOW SPEED SHALL RUN ANYTIME THE ZONE TEMPERATURE IS WITHIN CONDENSATE SAFETY SWITCH:
SETPOINTS.
• MEDIUM SPEED SHALL RUN ANYTIME THE ZONE TEMPERATURE IS OUTSIDE PROVIDE CONDENSATE SAFETY SWITCH IN CONDENSATE DRAIN OF UNIT. SHUT
OF SETPOINTS. DOWN UNIT UNIT ON SWITCH CLOSURE AND PROVIDE ALARM TO BUILDING
• HIGH SPEED SHALL RUN ANYTIME THE ZONE TEMPERATURE IS OUTSIDE OF AUTOMATION SYSTEM.
SETPOINTS BY A DEFINABLE AMOUNT (ADJ.).
1 HORIZONTAL CHILLED WATER FAN COIL WITH ELECTRIC REHEAT CONTROL DIAGRAM
SCALE: N.T.S.
NA
ST
STARTER MANUFACTURER. ALL INTERFACE
POINTS SHALL BE COORDINATED RAYMOND E. SMITH
WITH THE VFD SUPPLIER. LICENSE. No. 36823
REGISTERED
NG
MEC
PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
CA L ENG I NE
REVISION HISTORY
4
CONSULTING ENGINEERS
VARIABLE AIR VOLUME TERMINAL UNIT CONTROL DIAGRAM 909 Poydras Street, Suite 2150
SCALE: N.T.S. New Orleans, Louisiana 70112-1034
Tel. 504-586-1725
M7.2
BO - CHILLED WATER FLOW STATUS
HB
AIR COOLED CHILLER PLANT CONTROL - SEQUENCE OF OPERATION (CH-1,CH-2): Harry
CHILLER - RUN CONDITIONS: ALARMS SHALL BE PROVIDED AS FOLLOWS:
baker
smith
THE CHILLER SHALL BE ENABLED TO RUN WHENEVER: CHILLED WATER PUMP 1
s a ii
• FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• A DEFINABLE NUMBER OF CHILLED WATER COILS NEED COOLING • RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• THE OUTSIDE AIR TEMPERATURE IS GREATER THAN 40°F (ADJ.). • VFD FAULT.
TO PREVENT SHORT CYCLING, THE CHILLER SHALL RUN FOR AND BE OFF FOR MINIMUM ADJUSTABLE CHILLED WATER PUMP 2
TIMES (BOTH USER DEFINABLE), UNLESS SHUTDOWN ON SAFETIES OR OUTSIDE AIR CONDITIONS. architects ii
THE CHILLER SHALL RUN SUBJECT TO ITS OWN INTERNAL SAFETIES AND CONTROLS. • FAILURE: COMMANDED ON, BUT THE STATUS IS OFF. P L L C
• RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON. 189 Maple Ridge Drive Metairie, LA 70001
• VFD FAULT. (504)885−4477
CHILLER CHILLER LEAD/LAG OPERATION: [email protected] :−: hbsaii.com
THE TWO CHILLERS SHALL OPERATE IN A LEAD/LAG FASHION. THE FOLLOWING SETPOINTS since 1961
BO - CHILLED WATER PUMP 1 START/STOP
ARE RECOMMENDED VALUES. ALL SETPOINTS SHALL BE FIELD ADJUSTED DURING THE COMMISSIONING CHILLED WATER DIFFERENTIAL PRESSURE CONTROL:
BV - CHILLER STATUS AV - OIL DIFFERENTTAIL PRESSURE AO - CHILLED WATER PUMP 1 VFD SPEED PERIOD TO MEET THE REQUIREMENTS OF ACTUAL FIELD CONDITIONS.
THE CONTROLLER SHALL MEASURE CHILLED WATER DIFFERENTIAL PRESSURE
AV - CHILLER KW AV - OIL TEMP BI - CHILLED WATER PUMP 1 VFD FAULT BI - EMERGENCY SHUTDOWN TO PREVENT SHORT CYCLING, THERE SHALL BE A USER DEFINABLE DELAY (ADJ.) BETWEEN STAGING UP AND MODULATE THE LEAD CHILLED WATER PUMP VFD TO MAINTAIN ITS
AV - OPERATING HOURS AV - CONDENSER REFRIGERANT PRESSURE OR DOWN, UNLESS SHUTDOWN ON SAFETIES OR FAILURE. EACH CHILLER SHALL RUN SUBJECT TO ITS CHILLED WATER DIFFERENTIAL PRESSURE SETPOINT. THE FOLLOWING
OWN INTERNAL SAFETIES AND CONTROLS. SETPOINTS ARE RECOMMENDED VALUES. ALL SETPOINTS SHALL BE FIELD
AV - CHILLER WATER SUPPLY TEMP SETPOINT AV - EVAPORATOR REFRIGERANT PRESSURE ADJUSTED DURING THE COMMISSIONING PERIOD TO MEET
VFD THE REQUIREMENTS OF ACTUAL FIELD CONDITIONS.
THE LEAD CHILLER SHALL RUN FIRST.
BI - CHILLED WATER PUMP 1 STATUS
CT ON FAILURE OF THE LEAD CHILLER, THE LAG CHILLER SHALL RUN AND THE LEAD CHILLER SHALL TURN THE CONTROLLER SHALL MODULATE CHILLED WATER PUMP SPEED TO
OFF. MAINTAIN A CHILLED WATER DIFFERENTIAL PRESSURE OF 12LBF/IN2 (ADJ.). THE
M VFD MINIMUM SPEED SHALL NOT DROP BELOW 10% (ADJ.).
ON INCREASING MAIN CHILLED WATER SUPPLY TEMPERATURE ABOVE 52°F (ADJ.), THE LAG CHILLER ON DROPPING CHILLED WATER DIFFERENTIAL PRESSURE, THE VFDS SHALL
HARD ROCK
P1
TEMPERATURE SETPOINT.
BO - CHILLED WATER FLOW STATUS BO - CHILLED WATER ISOLATION VALVE
AI - CHILLED WATER SUPPLY TEMP • THE CONTROLLER SHALL MODULATE THE LEAD VFD TO MAINTAIN
M • CHILLER 1 FAILURE: COMMANDED ON, BUT THE STATUS IS OFF. • IF THE VFDS SPEEDS THEN DROPS BACK TO 60% (ADJ.) BELOW
• CHILLER 2 FAILURE: COMMANDED ON, BUT THE STATUS IS OFF. SETPOINT , THE LAG VFD SHALL STAGE OFF.
BI - CHILLED WATER PUMP 2 STATUS
CT • LEAD CHILLER FAILURE: THE LEAD CHILLER IS IN FAILURE AND THE LAG CHILLER IS ON. • THE LEAD VFD SHALL CONTINUE TO RUN TO MAINTAIN SETPOINT.
• HIGH MAIN CHILLED WATER SUPPLY TEMP: IF THE MAIN CHILLED WATER SUPPLY TEMPERATURE IS
GREATER ALARMS SHALL BE PROVIDED AS FOLLOWS:
CHILLER VFD THAN 56°F (ADJ.).
AI - CHILLED WATER • LOW MAIN CHILLED WATER SUPPLY TEMP: IF THE MAIN CHILLED WATER SUPPLY TEMPERATURE IS • HIGH CHILLED WATER DIFFERENTIAL PRESSURE: IF THE CHILLED
BO - CHILLED WATER PUMP 2 START/STOP H DIFFERENTIAL PRESSURE LESS THAN 38°F (ADJ.). WATER DIFFERENTIAL PRESSURE IS 25% (ADJ.) GREATER THAN
• HIGH MAIN CHILLED WATER RETURN TEMP: IF THE MAIN CHILLED WATER RETURN TEMPERATURE SETPOINT.
BV - CHILLER STATUS AV - OIL DIFFERENTTAIL PRESSURE L
AO - CHILLED WATER PUMP 2 VFD SPEED IS GREATER THAN 68°F (ADJ.).
AV - CHILLER KW AV - OIL TEMP • LOW MAIN CHILLED WATER RETURN TEMP: IF THE MAIN CHILLED WATER RETURN TEMPERATURE • LOW CHILLED WATER DIFFERENTIAL PRESSURE: IF THE CHILLED
AV - OPERATING HOURS AV - CONDENSER REFRIGERANT PRESSURE BI - CHILLED WATER PUMP 2 VFD FAULT IS LESS THAN 47°F (ADJ.). WATER DIFFERENTIAL PRESSURE IS 25% (ADJ.) LESS THAN SETPOINT.
AV - CHILLER WATER SUPPLY TEMP SETPOINT AV - EVAPORATOR REFRIGERANT PRESSURE EMERGENCY SHUTDOWN: CHILLED WATER BYPASS VALVE - MINIMUM FLOW CONTROL:
P3
THE CHILLER SHALL SHUT DOWN AND AN ALARM GENERATED UPON RECEIVING AN EMERGENCY THE CONTROLLER SHALL MEASURE CHILLED WATER FLOW THROUGH THE
M SHUTDOWN SIGNAL STATUS. CHILLER AND, AS THE CHILLED WATER FLOW DROPS BELOW SETPOINT, THE
CONTROLLER SHALL MODULATE THE CHILLED WATER BYPASS VALVE OPEN TO
BI - CHILLED WATER PUMP 3 STATUS
CT CHILLED WATER ISOLATION VALVE: MAINTAIN THE MINIMUM CHILLED WATER FLOW SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
THE VALVE SHALL OPEN ANYTIME THE CHILLER IS CALLED TO RUN. THE VALVE SHALL ALSO OPEN
VFD WHENEVER THE CHILLED WATER PUMP RUNS FOR FREEZE PROTECTION. THE VALVE SHALL OPEN PRIOR • LOW CHILLED WATER FLOW: IF THE CHILLED WATER FLOW IS 25% (ADJ.)
TO THE CHILLER BEING ENABLED AND SHALL CLOSE ONLY AFTER THE CHILLER IS DISABLED. THE VALVE LESS THAN SETPOINT.
BO - CHILLED WATER PUMP 3 START/STOP SHALL THEREFORE HAVE:
CHILLER START-UP:
AO - CHILLED WATER PUMP 3 VFD SPEED • A USER ADJUSTABLE DELAY ON START.
• A USER ADJUSTABLE DELAY ON STOP. THE CHILLER SHALL BE ENABLED AT A USER ADJUSTABLE TIME AFTER PUMP
BI - CHILLED WATER PUMP 3 VFD FAULT STATUSES ARE PROVEN ON. THE CHILLER SHALL THEREFORE HAVE A
THESE PLANS AND SPECIFICATIONS HAVE
THE DELAY TIMES SHALL BE SET APPROPRIATELY TO ALLOW FOR ORDERLY CHILLED WATER SYSTEM USER ADJUSTABLE DELAY ON START. BEEN PREPARED BY ME OR UNDER MY
BO - CHILLED WATER FLOW STATUS AO - CHILLED WATER BYPASS VALVE START-UP, SHUTDOWN AND SEQUENCING. CLOSE PERSONAL SUPERVISION AND TO
M THE DELAY TIME SHALL BE SET APPROPRIATELY TO ALLOW FOR ORDERLY THE BEST OF MY KNOWLEDGE AND
BELIEF THEY COMPLY WITH ALL CITY,
ALARMS SHALL BE PROVIDED AS FOLLOWS: CHILLED WATER SYSTEM START-UP, SHUTDOWN AND SEQUENCING. STATE AND FEDERAL REQUIREMENTS, AND
I AM NOT PROVIDING CONTRACT
AI - CHILLED WATER RETURN TEMP ADMINISTRATION.
• FAILURE: VALVE COMMANDED OPEN BUT THE STATUS INDICATES CLOSED. THE CHILLER SHALL RUN SUBJECT TO ITS OWN INTERNAL SAFETIES AND
CERTIFIED CORRECT
• OPEN IN HAND: VALVE COMMANDED CLOSED BUT THE STATUS INDICATES OPEN. CONTROLS.
T LO
CHILLED WATER PUMP LEAD/STANDBY OPERATION: ALARMS SHALL BE PROVIDED AS FOLLOWS: TE OF U I S I A
CHWR CHWR A
NA
ST
THE TWO CHILLED WATER PUMPS SHALL RUN ANYTIME THE CHILLER IS CALLED TO RUN. THE CHILLED • CHILLER FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
AI - CHILLED WATER FLOW WATER PUMP SHALL ALSO RUN FOR FREEZE PROTECTION WHENEVER THE OUTSIDE AIR TEMPERATURE • CHILLER RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON. RAYMOND E. SMITH
IS LESS THAN A USER DEFINABLE SETPOINT (32°F - ADJ.). LICENSE. No. 36823
REGISTERED
NG
CHILLED WATER SUPPLY TEMPERATURE - SETPOINT RESET:
MEC
PROFESSIONAL ENGINEER
THE LEAD PUMP SHALL START PRIOR TO THE CHILLER BEING ENABLED AND SHALL STOP ONLY AFTER THE
I
IN
ER
NI
HA
THE CHILLED WATER SUPPLY TEMPERATURE SETPOINT SHALL RESET USING A
CA L ENG I NE
CHILLER IS DISABLED. THE PUMP(S) SHALL THEREFORE HAVE:
TRIM AND RESPOND ALGORITHM BASED ON COOLING REQUIREMENTS.
CHILLER • A USER ADJUSTABLE DELAY ON START.
THE CHILLED WATER SUPPLY TEMPERATURE SETPOINT SHALL RESET TO A THIS DRAWING IS CONFIDENTIAL AND
• A USER ADJUSTABLE DELAY ON STOP. NOT BE LOANED, REPRODUCED, COPIED,
LOWER VALUE AS THE FACILITY'S CHILLED WATER VALVES OPEN BEYOND A EITHER WHOLLY OR IN PART, OR MADE
THE DELAY TIMES SHALL BE SET APPROPRIATELY TO ALLOW FOR ORDERLY CHILLED WATER SYSTEM USER DEFINABLE THRESHOLD (90% OPEN, TYP.). ONCE THE CHILLED WATER PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
BV - CHILLER STATUS AV - OIL DIFFERENTTAIL PRESSURE START-UP, SHUTDOWN AND SEQUENCING. COILS ARE SATISFIED (VALVES CLOSING) THEN THE CHILLED WATER SUPPLY A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
AV - CHILLER KW AV - OIL TEMP CHILLED WATER PUMP LEAD/LAG OPERATION: TEMPERATURE SETPOINT SHALL GRADUALLY RISE OVER TIME TO REDUCE OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
COOLING ENERGY USE. ARCHITECTS A PROFESSIONAL L.L.C.
AV - OPERATING HOURS AV - CONDENSER REFRIGERANT PRESSURE
THE TWO VARIABLE SPEED CHILLED WATER PUMPS SHALL OPERATE IN A LEAD/LAG FASHION.
AV - CHILLER WATER SUPPLY TEMP SETPOINT AV - EVAPORATOR REFRIGERANT PRESSURE CHILLED WATER TEMPERATURE MONITORING:
• THE LEAD PUMP SHALL RUN FIRST. REVISION HISTORY
• ON FAILURE OF THE LEAD PUMP, THE LAG PUMP SHALL RUN AND THE LEAD PUMP SHALL TURN THE FOLLOWING TEMPERATURES SHALL BE MONITORED:
OFF.
• CHILLED WATER SUPPLY.
ON DECREASING CHILLED WATER DIFFERENTIAL PRESSURE, THE LAG PUMP SHALL STAGE ON AND RUN IN • CHILLED WATER RETURN.
UNISON WITH THE LEAD PUMP TO MAINTAIN CHILLED
THE DESIGNATED LEAD PUMP SHALL ROTATE UPON ONE OF THE FOLLOWING CONDITIONS (USER ALARMS SHALL BE PROVIDED AS FOLLOWS:
SELECTABLE):
• HIGH CHILLED WATER SUPPLY TEMP: IF THE CHILLED WATER SUPPLY
• MANUALLY THROUGH A SOFTWARE SWITCH TEMPERATURE IS GREATER THAN 55°F (ADJ.).
• DAILY • LOW CHILLED WATER SUPPLY TEMP: IF THE CHILLED WATER SUPPLY
• WEEKLY TEMPERATURE IS LESS THAN 36°F (ADJ.).
• MONTHLY
THE CONTROLLER SHALL MONITOR AND RECORD THE HIGH AND MECHANICAL CONTROLS 3
LOW TEMPERATURE READINGS FOR THE OUTSIDE AIR. THESE
READINGS SHALL BE RECORDED ON A DAILY, MONTH-TO-DATE,
AND YEAR-TO-DATE BASIS. PROJECT#: 1709
PHASE: PERMIT
TEAM: MEI
CHECKER: RS
SCALE: AS NOTED
s a ii
BI - SMOKE DETECTOR
HARD ROCK
SELECT THE DESIRED OPERATION MODE ON.
• OFF ZONE TEMPERATURE CONTROL: • FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME
• ON EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
LO
TE OF U I S I A
A
NA
ST
BI - SMOKE DETECTOR
RAYMOND E. SMITH
AI - RETURN AIR CARBON DIOXIDE PPM LICENSE. No. 36823
REGISTERED
NG
MEC
SINGLE ZONE VAV ROOFTOP AIR HANDLING UNIT - SEQUENCE OF OPERATION (RTU-1,2, AND 3): PROFESSIONAL ENGINEER
AI - RETURN AIR HUMIDITY
I
IN
ER
NI
HA
CA L ENG I NE
AO - EXHAUST AIR DAMPER RUN CONDITIONS: ZONE TEMPERATURE CONTROL: DISCHARGE AIR TEMPERATURE:
AI - RETURN AIR TEMP AI - BUILDING STATIC PRESSURE
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME THE UNIT SHALL MAINTAIN ZONE SETPOINTS BY THE CONTROLLER SHALL MONITOR THE DISCHARGE THIS DRAWING IS CONFIDENTIAL AND
M CO2 H T SCHEDULE IN THE FOLLOWING MODES: CONTROLLING THE SUPPLY FAN SPEED AND CONTROL AIR TEMPERATURE. NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
VAVLES AS OUTLINED BELOW: PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
H L OCCUPIED MODE: THE UNIT SHALL MAINTAIN ALARMS SHALL BE PROVIDED AS FOLLOWS: CONSENT OF HBSA II ARCHITECTS,
EA RA • A 74°F (ADJ.) COOLING SETPOINT HEATING MODE: • HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
• A 70°F (ADJ.) HEATING SETPOINT. • FAN CONTROL: FAN VFD SPEED SHALL BE SET TO A TEMPERATURE IS GREATER THAN 120°F (ADJ.). REMAIN THE SOLE PROPERTY OF HBSA II
VALUE THAT MAINTAINS SCHEDULED AIRFLOW. VALUE • LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR ARCHITECTS A PROFESSIONAL L.L.C.
N.C. INSIDE OUTSIDE UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL DETERMINED DURING TAB PROCESS. TEMPERATURE IS LESS THAN 40°F (ADJ.).
MAINTAIN • COOLING COIL VALVE CONTROL: COOLING COIL VALVE
REVISION HISTORY
• A 85°F (ADJ.) COOLING SETPOINT. SHALL BE CLOSED. FAN STATUS:
• A 55°F (ADJ.) HEATING SETPOINT. • MODULATING GAS HEAT: NATURAL GAS HEATER
SHALL BE ENABLED. HEATER SHALL MODULATE TO THE CONTROLLER SHALL MONITOR THE FAN STATUS.
THE OCCUPANT SHALL BE ABLE TO OVERRIDE AUTOMATIC MAINTAIN SPACE HEATING SETPOINT.
AI - ZONE TEMPERATURE OPERATION THROUGH THE ZONE SENSOR AS FOLLOWS: ALARMS SHALL BE PROVIDED AS FOLLOWS:
T COOLING MODE: • FAN FAILURE: COMMANDED ON, BUT THE STATUS IS
ADJUST THE COOLING AND HEATING SETPOINTS • FAN CONTROL: THE CONTROLLER SHALL MEASUER OFF.
ZONE TEMPERATURE AND MODULATE THE SUPPLY • FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS
AO - ZONE SETPOINT ADJUST SELECT THE DESIRED OPERATION MODE FAN VFD SPEED TO MAINTAIN SPACE COOLING ON.
• OFF SETPOINT. THE MIN. VFD SPEED SHALL BE 20HZ(ADJ.) • FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME
• ON DURING COOLING MODE. EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
• COOLING COIL VALVE: THE CONTROLLER SHALL
AO - RETURN AIR DAMPER ALARMS SHALL BE PROVIDED AS FOLLOWS: MEASURE SUPPLY AIR TEMPERATURE AND MODULATE CONDENSATE SAFETY SWITCH:
AI - FILTER DIFFERENTIAL PRESSURE • HIGH STATIC SHUTDOWN: THE UNIT SHALL SHUTDOWN
M N.O. THE COOLING COIL CONTROL VALVE TO MAINTAIN A
AND GENERATE AN ALARM UPON RECEIVING A HIGH SUPPLY LAT OF 55 DEG. F (ADJ.). PROVIDE CONDENSATE SAFETY SWITCH IN UNIT SAFETY PAN
STATIC SHUTDOWN SIGNAL. • MODULATING GAS HEAT: THE NATURAL GAS HEATER OVERFLOW DRAIN . SHUT DOWN UNIT UNIT ON SWITCH
AI - MIXED AIR TEMPERATURE • SUPPLY/RETURN AIR SMOKE DETECTION: THE UNIT SHALL BE DISABLED. CLOSURE AND PROVIDE ALARM TO BUILDING AUTOMATION
SHALL SHUTDOWN AND GENERATE AN ALARM UPON SYSTEM.
RECEIVING A SUPPLY AIR SMOKE DETECTOR STATUS. DEHUMIDIFICATION MODE:
BI - HIGH STATIC SHUTDOWN • THE CONTROLLER SHALL MEASURE THE ZONE
EMERGENCY SHUTDOWN: RELATIVE HUMIDITY. WHEN ZONE RH RISES ABOVE
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM 70% (ADJ.) DEHUMIDIFICATION SHALL BE ENABLED.
UPON RECEIVING AN EMERGENCY SHUTDOWN SIGNAL. WHEN ZONE RH IS BELOW 55%(ADJ.)
BI - SMOKE DETECTOR DEHUMIDIFICATION MODE SHALL BE DISABLED. WHEN
AO - OUTSIDE AIR DAMPER SUPPLY FAN: OUTDOOR TEMP. ARE BELOW 55 DEG. F
AI - DISCHARGE AIR TEMPERATURE DEHUMIDIFICATION MODE SHALL BE DISABLED.
THE FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO • FAN CONTROL: THE CONTROLLER SHALL MEASURE
H L H L RUN, UNLESS SHUTDOWN ON SAFETIES. TO PREVENT SHORT ZONE TEMPERATURE AND MODULATE SUPPLY FAN
M T T
CYCLING, THE SUPPLY FAN SHALL HAVE A USER DEFINABLE VFD SPEED TO MAINTAIN ZONE HEATING TEMP.
CHW GAS (ADJ.) MINIMUM RUNTIME. SETPOINT. FAN VFD SPEED SHALL DECREASE AS
OA SA TEMPERATURE DROPS BELOW HEATING SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS: MINIMUM VFD SPEED SHALL BE 20HZ (ADJ.).
• SUPPLY FAN FAILURE: COMMANDED ON BUT STATUS • COOLING COIL VALVE: THE CONTROLLER SHALL
N.C. M IS OFF. MEASURE SUPPLY AIR TEMPERATURE AND MODULATE
AO - GAS HEATING VALVE • SUPPLY FAN IN HAND: COMMANDED OFF BUT STATUS THE COOLING COIL VALVE TO MAINTAIN A SUPPLY LAT
BI - SUPPLY FAN STATUS M OF 55 DEG. F (ADJ.)
BI - CONDENSATE SAFETY SWTICH CT IS ON.
CS • SUPPLY FAN RUNTIME EXCEEDED: STATUS RUNTIME • MODULATING GAS HEAT: THE NATURAL GAS HEATER MECHANICAL CONTROLS 4
LAN EXCEEDS A USER DEFINABLE LIMIT (ADJ.). SHALL BE DISABLED.
AO - COOLING VALVE VFD
M
OUTSIDE AIR DAMPER: FITLER STATUS: PROJECT#: 1709
NG
BO - SUPPLY FAN START/STOP
• OUTSIDE AIR DAMPER: IN OCCUPIED MODE THE • A DIFFERENTIAL PRESSURE SWITCH SHALL MONITOR PHASE: PERMIT
AO - SUPPLY FAN VFD SPEED DAMPER SHALL MODULATE TO MAINTAIN THE SPACE DIFFERENTIAL PRESSURE ACROSS THE FILTER WHEN TEAM: MEI
CO2 LEVEL BELOW 1100 PPM(ADJ.). IN UNOCCUPIED THE FAN IS RUNNING. IF SWITCH CLOSES DURING
CHWR MODE THE OUTSIDE AIR DAMPER IS FULLY CLOSED. OCCUPIED MODE, DIRTY FILTER ALARM SHALL BE CHECKER: RS
BI - SUPPLY FAN VFD FAULT • RETURN AIR DAMPER: IN OCCUPIED MODE THE ANNUNCIATED.
CHWS SCALE: AS NOTED
RETURN AIR DAMPER SHALL MODULATE TO MAINTAIN
THE SUPPLY AIR FLOW. IN OCCUPIED MODE THE ISSUED: 06/05/2018
RETURN AIR DAMPER IS FULL OPEN.
• EXHAUST AIR DAMER: IN OCCUPIED MODE THE CONSULTING ENGINEERS
EXHAUST AIR DAMPER IS OPEN. IN UNOCCUPIED 909 Poydras Street, Suite 2150
M7.4
MODE THE EXHAUST AIR DAMPER IS CLOSED. New Orleans, Louisiana 70112-1034
3 SINGLE ZONE VAV ROOFTOP AIR HANDLING UNIT SCHEMATIC - MODULATING GAS
SCALE: NTS
Tel. 504-586-1725
HB
Harry
baker
smith
RUN CONDITIONS:
AO - OUTSIDE AIR DAMPER STARTED VIA KITCHEN HOOD CONTROL PANEL AS OUTLINED OA TEMPERATURE IS LESS 43 DEG. F (ADJ.) (504)885−4477
[email protected] :−: hbsaii.com
IN SPECIFICATION SECTION 23 74 33. CONTROLLER SHALL MODULATE NATURAL GAS FIRED KITCHEN HOOD EXHAUST FAN (KEF-1,2,3) SEQUENCE OF OPERATION:
AI - DISCHARGE AIR TEMPERATURE EA since 1961
HEATER TO MAINTAIN 53 DEG. F (ADJ.) DISCHARGE AIR
H L STOP CONDITIONS: TEMPERATURE. WHENEVER OA TEMPERATURE IS RUN CONDITIONS:
M T GREATER 43 DEG. F (ADJ.) NATURAL GAS FIRED
GAS HEATER SHALL BE DISABLED. M THE FAN(S) SHALL BE MANUALLY AND AUTOMATICALLY STARTED
THE UNIT(S) SHALL BE MANUALLY AND AUTOMATICALLY
STARTED VIA KITCHEN HOOD CONTROL PANEL AS OUTLINED BI - FAN STATUS VIA KITCHEN HOOD CONTROL PANEL AS OUTLINED IN
OA OA CT
IN SPECIFICATION SECTION 23 74 33. FITLER STATUS: SPECIFICATION SECTION 23 74 33.
BO - FAN START/STOP STOP CONDITIONS:
N.C. M MAKE-UP AIR FAN: • A DIFFERENTIAL PRESSURE SWITCH SHALL MONITOR
DIFFERENTIAL PRESSURE ACROSS THE FILTER WHEN THE FAN SHALL BE MANUALLY AND AUTOMATICALLY STOPPED
BO - DX COOLING COIL STATUS BI - SUPPLY FAN STATUS THE FAN IS RUNNING. IF SWITCH CLOSES DURING VIA THE KITCHEN HOOD CONTROL PANEL AS OUTLINED IN
CT AO - GAS HEATING VALVE • THE FAN SHALL RUN ANYTIME THE UNIT IS
M COMMANDED TO RUN, UNLESS SHUTDOWN ON OPERATION DIRTY FILTER ALARM SHALL BE SPECIFICATION SECTION 23 36 13.
SAFETIES. ANNUNCIATED.
LAN DISHWASHER EXHAUST FAN (DEF-1) SEQUENCE OF OPERATION:
VFD
HARD ROCK
BO - SUPPLY FAN START/STOP NG • OUTSIDE AIR DAMPER SHALL BE OPEN ANYTIME THE
THE FAN(S) SHALL BE STARTED BY A SIGNAL FROM THE
UNIT IS COMMANDED TO RUN.
AO - SUPPLY FAN VFD SPEED DISHWASHER CONTROLLER.
DEDICATED OUTDOOR AIR UNIT (DOAS-1) - DEDICATED OUTDOOR AIR UNIT (DOAS-2) -
SEQUENCE OF OPERATION : SEQUENCE OF OPERATION :
THE OUTDOOR AIR UNIT IS REQUIRED TO MAINTAIN A MAXIMUM SUPPLY AIR DEWPOINT THE OUTDOOR AIR UNIT IS REQUIRED TO MAINTAIN A MAXIMUM SUPPLY AIR DEWPOINT TEMPERATURE
TEMPERATURE BETWEEN 48°F-51°F WHILE SUPPLYING 68°F AIR TO THE REQUIRED ZONES. THE BETWEEN 48°F-51°F WHILE SUPPLYING 68°F AIR TO THE REQUIRED ZONES. THE DEDICATED OUTDOOR
DEDICATED OUTDOOR AIR SYSTEM (DOAS) IS TO BE A DX-SPLIT SYSTEM CONSISTING OF A AIR SYSTEM (DOAS) CONSISTS OF AN ENTHALPY CORE, VARIABLE VOLUME SUPPLY FAN, DX COOLING
VARIABLE VOLUME SUPPLY FAN, (2) CIRCUIT INTERLACED DX COOLING COIL, ELECTRIC HEATING COIL, NATURAL GAS FURNACE FOR HEATING, MODULATING HOT GAS REHEAT COIL, VARIABLE VOLUME
COIL WITH SCR CONTROL, MODULATING HOT GAS REHEAT COIL, HOT GAS BYPASS (CIRCUIT #2 EXHAUST FAN, AND FILTER SECTIONS FOR THE OUTDOOR AIR AND EXHAUST AIRSTREAMS. THIS
ONLY), VARIABLE SCROLL COMPRESSOR (CIRCUIT #1 ONLY) AND FILTER SECTION FOR THE SEQUENCE IS BASED ON FULLY CONDITIONED OUTDOOR AIR BEING SUPPLIED THROUGH A LOW
OUTDOOR AIRSTREAM. THIS SEQUENCE IS BASED ON FULLY CONDITIONED OUTDOOR AIR BEING PRESSURE DUCT SYSTEM DIRECTLY TO THE GUEST ROOMS AND MAIN CORRIDORS AND EXHAUST AIR
SUPPLIED THROUGH A MEDIUM PRESSURE DUCT SYSTEM CONNECTED TO SINGLE DUCT VAV BEING DRAWN THROUGH A LOW PRESSURE DUCT SYSTEM DIRECTLY FROM GUEST REST ROOMS. THE
BOXES REFERRED TO AS OUTSIDE AIR VALVES (OAV). THE FOLLOWING SETPOINTS AND SETTINGS FOLLOWING SETPOINTS AND SETTINGS ARE RECOMMENDED VALUES AND SHALL BE ADJUSTABLE
(2) CIRCUIT DX CT BI VFD FAULT ARE RECOMMENDED VALUES AND SHALL BE ADJUSTABLE FROM THE OPERATOR'S WORKSTATION FROM THE OPERATOR'S WORKSTATION AND LOCAL CONTROLLER. THE UNIT SHALL BE CONTROLLED
EVAPORATOR COIL AND THE LOCAL CONTROLLER. THE UNIT SHALL BE CONTROLLED BY A FACTORY PROGRAMMED BY A FACTORY PROGRAMMED AND TESTED CONTROLLER WITH BACNET INTERFACE AND SHALL
AO FAN SPEED
AND TESTED CONTROLLER WITH BACNET INTERFACE AND SHALL CONTROL THE FOLLOWING CONTROL THE FOLLOWING FUNCTIONS UNLESS OTHERWISE NOTED
BO FAN START/STOP FUNCTIONS UNLESS OTHERWISE NOTED.
FILTER DIFFERENTIAL RUN CONDITIONS: THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE FROM
BI BI FAN STATUS
PRESSURE SWITCH RUN CONDITIONS: THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE FROM THE BAS SYSTEM OR THE LOCAL CONTROLLER.
SUPPLY AIR STATIC PRESSURE AI THE BAS SYSTEM OR THE LOCAL CONTROLLER.
DAMPER STATUS BI STOP CONDITIONS: THE UNIT SHALL SHUT DOWN AND GENERATE AND ALARM UPON ANY OF THE
VFD ELEC FOLLOWING CONDITIONS:
H DP L STOP CONDITIONS: THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON ANY OF THE THESE PLANS AND SPECIFICATIONS HAVE
BEEN PREPARED BY ME OR UNDER MY
OPEN/CLOSE O/A DAMPER BO M H DP L FOLLOWING CONDITIONS. • IF SUPPLY AIR DEWPOINT TEMPERATURE (DPT2) EXCEEDS 60°F (ADJ.) CLOSE PERSONAL SUPERVISION AND TO
• SUPPLY AIR DEWPOINT TEMPERATURE (DPT2) EXCEEDS 60°F (ADJ.). • RECEIVING A SUPPLY AIR OR RETURN AIR SMOKE DETECTOR STATUS. THE BEST OF MY KNOWLEDGE AND
BELIEF THEY COMPLY WITH ALL CITY,
• RECEIVING A SHUTDOWN SIGNAL FROM THE FIRE ALARM SYSTEM. • RECEIVING A SHUTDOWN SIGNAL FROM THE FIRE ALARM SYSTEM. STATE AND FEDERAL REQUIREMENTS, AND
OUTSIDE AIR DX HGR SUPPLY AIR • RECEIVING A SHUTDOWN SIGNAL FROM THE CONDENSATE SAFETY SWITCH STATUS. I AM NOT PROVIDING CONTRACT
• RECEIVING A SUPPLY AIR SMOKE DETECTOR STATUS. START COMMAND: ADMINISTRATION.
• ACTUATORS FOR THE OA DAMPER, EXHAUST DAMPER AND THE BYPASS DAMPERS ARE CERTIFIED CORRECT
START COMMAND: POWERED AND OPEN STATUS IS VERIFIED BY AN END SWITCH SIGNALS TO THE CONTROLLER.
H DP L LO
E OF U I S I A
T H T T H
• ACTUATOR FOR THE OA DAMPER IS POWERED AND OPEN STATUS IS VERIFIED BY AN END • EXHAUST FAN STARTS AFTER A 120 SEC (ADJ) DELAY AFTER DAMPER STATUS IS VERIFIED T
SWITCH SIGNAL TO THE CONTROLLER. • SUPPLY FAN STARTS AFTER 5 SEC (ADJ) DELAY AFTER EXHAUST FAN STARTS A
NA
ST
ELECTRIC HEAT COIL BI HIGH STATIC PRESSURE SWITCH • SUPPLY FAN STARTS AFTER A 120 SEC (ADJ) DELAY AFTER DAMPER STATUS IS VERIFIED.
FILTER CS SUPPLY FAN (SCR CONTROL) AI SUPPLY AIR HUMIDITY SENSOR (RH2) STOP COMMAND: RAYMOND E. SMITH
OUTDOOR AIR TEMPERATURE SENSOR (T1) AI STOP COMMAND: • FANS DE-ENERGIZE LICENSE. No. 36823
AI SUPPLY AIR TEMPERATURE SENSOR (T3) • FAN DE-ENERGIZES. • ALL DAMPERS DE-ENERGIZE AND SPRING RETURN TO CLOSED POSITION AFTER 120 SEC (ADJ) REGISTERED
NG
MEC
OUTDOOR AIR HUMIDITY SENSOR (RH1) AI MODULATING • DAMPER DE-ENERGIZE AND SPRING RETURN TO CLOSED POSITION AFTER 120 SEC (ADJ) DELAY PROFESSIONAL ENGINEER
DAMPER STATUS BI BI DUCT SMOKE DETECTOR (TYP)
I
HGR COIL IN
ER
DELAY.
NI
HA
OFF COIL TEMPERATURE SENSOR (T2) AI SUPPLY FAN: THE SUPPLY FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN UNLESS SHUT CA L ENG I NE
SUPPLY FAN: THE SUPPLY FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN UNLESS DOWN ON SAFETIES. TO PREVENT SHORT CYCLING, THE FAN SHALL HAVE A MINIMUM RUNTIME (ADJ.)
SHUT DOWN ON SAFETIES. TO PREVENT SHORT CYCLING, THE FAN SHALL HAVE A MINIMUM UNLESS SHUTDOWN ON SAFETIES. MOTORIZED DAMPER LOCATED ON OUTSIDE AIR INTAKE SHALL BE THIS DRAWING IS CONFIDENTIAL AND
DOAS-1 CONTROL DIAGRAM RUNTIME (ADJ.) UNLESS SHUTDOWN ON SAFETIES. MOTORIZED DAMPER LOCATED ON OUTSIDE AIR INTERLOCKED TO OPEN WHEN SUPPLY FAN IS COMMANDED TO RUN. NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
INTAKE SHALL BE INTERLOCKED TO OPEN WHEN THE SUPPLY FAN IS COMMANDED TO RUN. PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
SUPPLY FAN VFD: DURING START-UP THE SUPPLY FAN VFD SHALL BE USED TO INITIALLY BALANCE THE CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
SUPPLY AIR DUCT STATIC PRESSURE CONTROL: SUPPLY CFM TO THE SCHEDULED VALUE. THE CFM SHALL BE VERIFIED BY THE SUPPLY AIR FLOW OR INVENTION ARE RESERVED AND WILL
• THE CONTROLLER SHALL MEASURE DUCT STATIC PRESSURE AND MODULATE THE SUPPLY MEASURING STATION (AF1). REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
BO OA DAMPER MOTOR FAN VFD SPEED TO MAINTAIN A DUCT STATIC PRESSURE SETPOINT. THE SPEED SHALL NOT
DROP BELOW 20HZ (ADJ.). THE STATIC PRESSURE SETPOINT SHALL BE RESET TO MAINTAIN EXHAUST FAN: THE EXHAUST FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN UNLESS
BO OA DAMPER MOTOR THE "CRITICAL ZONE" VAV AIR DAMPER POSITION AT LEAST 85% (ADJ.) OPEN. ALL OAV AIR SHUT DOWN ON SAFETIES. TO PREVENT SHORT CYCLING, THE FAN SHALL HAVE A MINIMUM RUNTIME REVISION HISTORY
BO FAN START/STOP DAMPERS SHALL BY DYNAMICALLY POLLED TO DETERMINE THE "CRITICAL ZONE." (ADJ.) UNLESS SHUTDOWN ON SAFETIES. MOTORIZED DAMPER LOCATED ON EXHAUST OUTLET SHALL
• THE STATIC PRESSURE SETPOINT SHALL BE DETERMINED DURING THE TAB PROCESS. THE OPEN WHEN THE EXHAUST FAN IS COMMANDED TO RUN.
BI FAN STATUS CONTROL ALGORITHM SHALL ADJUST THE STATIC PRESSURE SETPOINT BY +/- 0.3" W.C.
AO VFD SPEED (ADJ.) USING TRIM AND RESPOND LOGIC AS OUTLINED BELOW: EXHAUST FAN VFD: DURING START-UP THE EXHAUST FAN VFD SHALL BE USED TO INITIALLY BALANCE
1. THE INITIAL DUCT STATIC PRESSURE SETPOINT SHALL BE 1.0" W.C. (ADJ.). THE EXHAUST CFM TO THE SCHEDULED VALUE. THE CFM SHALL BE VERIFIED BY THE EXHAUST AIR
BI VFD FAULT AI RETURN AIR TEMPERATURE (T3) 2. AS AIRFLOW DEMAND INCREASES, THE SET POINT SHALL INCREMENTALLY RESET FLOW MEASURING STATION (AF2).
UP TO A MAXIMUM OF 1.3" W.C. (ADJ. TBD.)
BI FILTER DIFFERENTIAL PRESSURE SWITH AI RETURN AIR HUMIDITY (RH2) 3. AS AIRFLOW DEMAND DECREASES, THE SET POINT SHALL INCREMENTALLY ENTHALPY CORE:
VFD AI AIRFLOW MEASURING STATION (AF2) RESET DOWN TO A MINIMUM OF 0.7" W.C. (ADJ. TBD.) • COOLING MODE: THE ENTHALPY WHEEL SHALL RUN FOR COOLING ENERGY RECOVERY
• DURING THE TAB PROCESS, PROVIDE PROGRAMMING AS REQUIRED TO REMOVE VAV'S WHENEVER: 1. THE OUTSIDE AIR ENTHALPY (H1) IS GREATER THAN THE RETURN AIR
M H DP L
T H AF FROM THE CONTROL ALGORITHM THAT HAVE DAMPER POSITIONS CONSISTENTLY ABOVE ENTHALPY (H3). 2. AND THE OUTDOOR TEMPERATURE IS GREATER THAN
THE CRITICAL ZONE. THE SUPPLY AIR TEMPERATURE SETPOINT (T3) 3. AND THE SUPPLY FAN IS ON.
• HEATING MODE: THE ENTHALPY WHEEL SHALL RUN FOR HEATING ENERGY RECOVERY
RETURN
EA DX COOLING/MODULATING HOT GAS REHEAT/HOT GAS BYPASS: THE COOLING COIL SHALL BE WHENEVER: 1.THE OUTSIDE AIR ENTHALPY (H1) IS LESS THAN THE RETURN AIR ENTHALPY
AIR
ENABLED TO RUN ANYTIME THE UNIT IS COMMANDED TO RUN. THE CONTROLLER SHALL CONTROL (H3) 2. AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE
ALL FUNCTIONS OF THE AIR COOLED DIRECT EXPANSION COOLING SYSTEM TO ACHIEVE SUPPLY AIR TEMPERATURE SETPOINT (T3) 3. AND THE SUPPLY FAN IS ON.
SEQUENCE OUTLINED BELOW. • PERIODIC SELF CLEANING: THE ENTHALPY WHEEL SHALL RUN FOR 10 SECONDS (ADJ.) EVERY 4
• COOLING SHALL BE LOCKED OUT WHEN THE OUTSIDE AIR TEMPERATURE IS LESS THAN 50° HOURS (ADJ.) THE UNIT IS IN OPERATION AND THE ENTHALPY CORE IS NOT ACTIVE.
AO RETURN AIR DAMPER MOTOR F (ADJ) AND THE OUTSIDE AIR HUMIDITY IS LESS THAN 50% RH (ADJ).
ENTHALPY WHEEL
• THE UNIT SHALL MAINTAIN THE OFF THE COIL TEMPERATURE SETPOINT (T2). THE SYSTEM DX COOLING: THE COOLING COIL SHALL BE ENABLED TO RUN ANYTIME THE UNIT IS COMMANDED TO
BO FAN START/STOP SHALL ENERGIZE AND MODULATE THE (2) COOLING CIRCUITS AS NEEDED TO MAINTAIN RUN. THE CONTROLLER SHALL CONTROL ALL FUNCTIONS OF THE AIR COOLED DIRECT EXPANSION
BI FAN STATUS SETPOINT (T2). CIRCUIT #1 SHALL UTILIZE A VARIABLE SCROLL COMPRESSOR WHILE COOLING SYSTEM TO ACHIEVE SEQUENCE OUTLINED BELOW.
M CIRCUIT #2 UTILIZES A HOT GAS BYPASS SYSTEM.
AO VFD SPEED • THE UNIT SHALL MAINTAIN THE DISCHARGE AIR TEMPERATURE (T3) AND HUMIDITY (RH2) • COOLING SHALL BE LOCKED OUT WHEN THE OUTSIDE AIR TEMPERATURE IS LESS THAN 50°F
BI VFD FAULT SETPOINTS. THE SYSTEM SHALL UTILIZE A MODULATING HOT GAS REHEAT COIL TO (ADJ) AND THE OUTSIDE AIR HUMIDITY IS LESS THAN 50% RH (ADJ).
MAINTAIN SETPOINTS (T3 & RH2). • THE UNIT SHALL MAINTAIN THE OFF THE COIL TEMPERATURE SETPOINT (T2). THE SYSTEM
TEMPERATURE SENSOR (TYP)
SHALL ENERGIZE AND MODULATE THE (2) COOLING CIRCUITS AS NEEDED TO MAINTAIN
VFD ELECTRIC HEATING COIL (SCR CONTROL): THE HEATING COIL SHALL BE ENABLED ANYTIME THE SETPOINT (T2). BOTH CIRCUITS SHALL UTILIZE A VARIABLE SCROLL COMPRESSOR.
DX COOLING COIL HUMIDITY SENSOR (TYP) UNIT IS COMMANDED TO RUN AND OUTDOOR AIR TEMPERATURES ARE BELOW 65°F (ADJ.). THE • THE UNIT SHALL MAINTAIN THE DISCHARGE AIR TEMPERATURE (T3) AND HUMIDITY (RH2)
CONTROLLER SHALL CONTROL ALL FUNCTION OF THE HEATING COIL TO ACHIEVE THE SEQUENCE SETPOINTS. THE SYSTEM SHALL UTILIZE A MODULATING HOT GAS REHEAT COIL TO MAINTAIN
GAS BELOW: SETPOINTS (T3 & RH2).
SUPPLY • THE ELECTRIC HEATING COIL SHALL MODULATE TO MAINTAIN THE SUPPLY AIR
OA DX HGR
AIR TEMPERATURE SETPOINT (T3). GAS FURNACE HEATING: THE HEATING COIL SHALL BE ENABLED ANYTIME THE UNIT IS COMMANDED TO
RUN AND OUTDOOR AIR TEMPERATURES ARE BELOW 65°F (ADJ.). THE CONTROLLER SHALL CONTROL
FILTER STATUS: A DIFFERENTIAL PRESSURE SWITCH SHALL MONITOR THE DIFFERENTIAL ALL FUNCTION OF THE FURNACE TO ACHIEVE THE SEQUENCE BELOW:
H DP L T H AF T T H H DP L
M PRESSURE ACROSS THE FILTER WHEN THE FAN IS RUNNING. IF THE SWITCH CLOSES DURING • THE GAS FURNACE SHALL MODULATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT MECHANICAL CONTROLS 5
GAS
NORMAL OPERATION, A DIRTY FILTER ALARM SHALL BE ANNUNCIATED (TYPICAL FOR SUPPLY & (T4).
FURNACE
AI AIRFLOW MEASURING STATION (AF1) BI HIGH STATIC PRESSURE EXHAUST AIRSTREAMS).
HGR COIL FILTER STATUS: A DIFFERENTIAL PRESSURE SWITCH SHALL MONITOR THE DIFFERENTIAL PRESSURE
AI OUTSIDE AIR HUMIDITY (RH1) AI SUPPLY AIR HUMIDITY (RH3)
ACROSS THE FILTER WHEN THE FAN IS RUNNING. IF THE SWITCH CLOSES DURING NORMAL PROJECT#: 1709
AI OUTSIDE AIR TEMPERATURE (T1) AI SUPPLY AIR TEMPERATURE (T4) OPERATION, A DIRTY FILTER ALARM SHALL BE ANNUNCIATED (TYPICAL FOR SUPPLY & EXHAUST PHASE: PERMIT
FILTER DIFFERENTIAL PRESSURE AIRSTREAMS).
BI BI DUCT SMOKE DETECTOR (TYP) TEAM: MEI
SWITCH
BO OA DAMPER MOTOR AI OFF COIL TEMPERATURE SENSOR (T2) CHECKER: RS
BI OA DAMPER STATUS SCALE: AS NOTED
ISSUED: 06/05/2018
DOAS-2 CONTROL DIAGRAM CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
HB
Harry
6
6 baker
smith
s a ii
16"x48"
architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
S4 S4 since 1961
(1650) (1650)
16"x48"
16"x40"
S2
(1650) S4
(1650)
16"x32"
THESE PLANS AND SPECIFICATIONS HAVE
BEEN PREPARED BY ME OR UNDER MY
CLOSE PERSONAL SUPERVISION AND TO
THE BEST OF MY KNOWLEDGE AND
BELIEF THEY COMPLY WITH ALL CITY,
STATE AND FEDERAL REQUIREMENTS, AND
I AM NOT PROVIDING CONTRACT
ADMINISTRATION.
S2 CERTIFIED CORRECT
S4
(1650) LO
E OF U I S I A
(1650)
AT
NA
ST
RAYMOND E. SMITH
LICENSE. No. 36823
REGISTERED
NG
MEC
16"x28"
PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
CA L ENG I NE
THIS DRAWING IS CONFIDENTIAL AND
NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
S4 S4
ARCHITECTS A PROFESSIONAL L.L.C.
(1650) (1650)
REVISION HISTORY
12"x28"
S4 S4
(1375) (1650)
10"x28"
S4
(1375)
S4
(1375)
STAIR PRESSURIZATION
RISER DIAGRAM
PROJECT#: 1709
PHASE: PERMIT
TEAM: MEI
1 NORTH STAIRWELL - SECTION A-A
SCALE: 3/32" = 1'-0"
2 SOUTH STAIRWELL - SECTION B-B
SCALE: 3/32" = 1'-0"
CHECKER: RS
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
New Orleans, Louisiana 70112-1034
Tel. 504-586-1725
M8.1
HB
# SHEET REFERENCE NOTES Harry
1 DRAINS MAY BE ROUTED TO PRIMARY STORM DRAIN SYSTEM AT CONTRACTORS
DISCRESTION. SEE PLUMBING DRAWINGS FOR NEARBY STORM DRAIN PIPES.
baker
smith
s a ii
architects
P L L C
ii
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
HARD ROCK
FCU-E FCU-B FCU-C FCU-C FCU-C FCU-B FCU-A FCU-C
NA
ST
RAYMOND E. SMITH
LICENSE. No. 36823
REGISTERED
NG
MEC
FCU-E FCU-B FCU-C FCU-C FCU-C FCU-B FCU-A FCU-C PROFESSIONAL ENGINEER
I
IN
ER
NI
HA
3/4" CHWR CA L ENG I NE
1" CDWR 3/4" CHWR 3/4" CHWR
3/4" CHWS 3/4" CHWS
1" CHWS 3/4" CHWS 3/4" CHWS THIS DRAWING IS CONFIDENTIAL AND
10TH FLOOR 10TH FLOOR 3/4" CHWR 10TH FLOOR 10TH FLOOR 10TH FLOOR 10TH FLOOR NOT BE LOANED, REPRODUCED, COPIED,
EITHER WHOLLY OR IN PART, OR MADE
HOTEL
10TH FLOOR HOTEL HOTEL
10TH FLOOR HOTEL HOTEL
10TH FLOOR HOTEL HOTEL
10TH FLOOR HOTEL HOTEL
10TH FLOOR HOTEL HOTEL
10TH FLOOR HOTEL PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
9th FLOOR102' T.O.S.
102' - 8"
- 8" 9th FLOOR102' T.O.S.
102' - 8"
- 8" 9th FLOOR102' T.O.S.
102' - 8"
- 8" 9th FLOOR102' T.O.S.
102' - 8"
- 8" 9th FLOOR102' T.O.S.
102' - 8"
- 8" 9th FLOOR102' T.O.S.
102' - 8"
- 8"
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
102' - 1 1/2" 102' - 1 1/2" 1 1/2" CHWR
102' - 1 1/2" 102' - 1 1/2" 102' - 1 1/2" 102' - 1 1/2" OR INVENTION ARE RESERVED AND WILL
1 1/4" CHWR 1" CHWR 1 1/4" CHWS 3/4" CHWS 1" CHWR REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
1 1/4" CHWS 1 1/2" CHWS 1 1/4" CHWR 3/4" CHWR 1" CHWS
1" CHWS
3/4" DR 3/4" DR 3/4" DR 3/4" DR
3/4" DR REVISION HISTORY
M8.3
3/4" DRAIN TO HUB DRAIN (SEE 3/4" DRAIN TO HUB DRAIN (SEE 1
3/4" DRAIN TO HUB DRAIN (SEE 1
3/4" DRAIN TO HUB DRAIN (SEE 1 3/4" DRAIN TO HUB DRAIN (SEE 1 1 1 3/4" DRAIN TO HUB DRAIN (SEE PLUMBING DRAWINGS) PLUMBING DRAWINGS)
PLUMBING DRAWINGS) PLUMBING DRAWINGS) PLUMBING DRAWINGS)
PLUMBING DRAWINGS)
DRAINS MAY BE ROUTED TO PRIMARY
STORM DRAIN SYSTEM AT CONTRACTORS
DISCRESTION. SEE PLUMBING DRAWINGS
FOR NEARBY STORM DRAIN PIPES. MECHANICAL WATER
RISER DIAGRAMS
HB
1 DRAINS MAY BE ROUTED TO PRIMARY STORM DRAIN SYSTEM AT CONTRACTORS
DISCRESTION. SEE PLUMBING DRAWINGS FOR NEARBY STORM DRAIN PIPES.
Harry
14TH FLOOR
baker
T.O.S. smith
s a ii
156' - 11 1/2"
FCU-K architects ii
P L L C
189 Maple Ridge Drive Metairie, LA 70001
3/4" CHWR (504)885−4477
3/4" CHWS [email protected] :−: hbsaii.com
FCU-D FCU-C
FCU-B FCU-B FCU-E 3/4" CHWR
3/4" CHWR 3/4" CHWR 3/4" CHWR FCU-B
3/4" CHWS 3/4" CHWS 3/4" CHWS 1" CHWR 1" CHWS 3/4" CHWS
2" CHWS & CHWR TO
CHILLER (SEE M1.4.4) 3/4" CHWR 1" CHWR 2" CHWS & CHWR TO
2" CHWS & CHWR TO 1" CHWS 3/4" DR
3/4" CHWS CHILLER (SEE M1.4.4)
CHILLER (SEE M1.4.4) 13TH FLOOR
14TH FLOOR HOTEL 13TH FLOOR
14TH FLOOR HOTEL
14TH &FLOOR
POOL DECK 14TH &FLOOR
POOL DECK 13TH FLOOR
14TH FLOOR HOTEL 13TH FLOOR
14TH FLOOR HOTEL 13TH FLOOR
14TH FLOOR HOTEL
T.O.S.
144' 144' - 4"
- 4" T.O.S.
144' 144' - 4"
- 4" 13TH FLOOR
14TH FLOOR HOTEL 14TH &FLOOR
POOL DECK 14TH &FLOOR
POOL DECK 14TH &FLOOR
POOL DECK
14TH &FLOOR
POOL DECK T.O.S.
144' 144' - 4"
- 4" T.O.S.
144' 144' - 4"
- 4" T.O.S.
144' 144' - 4"
- 4"
143' - 9 1/2" 143' - 9 1/2" T.O.S.
144' - 4"
144' - 4" 143'
2" CHWS1/2"
- 9 & CHWR TO CHILLER 143' - 9 1/2" 143'
FCU-M - 9 1/2"
2" CHWS 143' - 9 1/2" 2" CHWS (SEE SHEET M1.4.4)
HARD ROCK
3/4" DR 1 1/2" CHWS 2" CHWS & CHWR TO 1 1/2" CHWR
3/4" DR 1" CHWR
1 1/2" CHWS CHILLER (SEE M1.4.4) 3/4" DR
1 1/2" CHWR 1" CHWS
1 1/2" CHWR 2" CHWS & CHWR TO
FCU-D FCU-C
FCU-B FCU-B FCU-C
FCU-B
3/4" CHWR 3/4" CHWS
3/4" CHWS
3/4" CHWS 3/4" CHWR 3/4" CHWR 1 1/2" CHWS
3/4" CHWR 3/4" CHWR 1 1/2" CHWR
12TH FLOOR 12TH FLOOR 3/4" CHWS
11TH FLOOR 11TH FLOOR 3/4" CHWS 12TH FLOOR 12TH FLOOR 12TH FLOOR
HOTEL
12TH FLOOR HOTEL HOTEL
12TH FLOOR HOTEL 12TH FLOOR 11TH FLOOR 11TH FLOOR 3/4" DR 11TH FLOOR
T.O.S.
123' 123' - 6"
- 6" T.O.S.
123' 123' - 6"
- 6" 11TH FLOOR HOTEL
12TH FLOOR HOTEL HOTEL
12TH FLOOR HOTEL HOTEL
12TH FLOOR HOTEL
HOTEL
12TH FLOOR HOTEL T.O.S.
123' 123' - 6"
- 6" T.O.S.
123' 123' - 6"
- 6" T.O.S.
123' 123' - 6"
- 6"
122' - 11 1/2" 122' - 11 1/2" T.O.S.
123' - 6"
1 1/2" CHWS 123' - 6" 122' - 11 1/2" 122' - 11 1/2" 122' - 11 1/2"
122' - 11 1/2" FCU-M
1 1/2" CHWR 1 1/4" CHWS 1 1/2" CHWS
1 1/4" CHWS
3/4" DR 1 1/4" CHWS 1 1/2" CHWR
1 1/4" CHWR 1 1/4" CHWR
1 1/4" CHWR 3/4" DR 1" CHWR
3/4" DR 3/4" DR
3/4" DR 1" CHWS
3/4" DR
FCU-D FCU-C
FCU-B FCU-B FCU-C THESE PLANS AND SPECIFICATIONS HAVE
FCU-B BEEN PREPARED BY ME OR UNDER MY
CLOSE PERSONAL SUPERVISION AND TO
3/4" CHWR 3/4" CHWS THE BEST OF MY KNOWLEDGE AND
3/4" CHWS BELIEF THEY COMPLY W ITH ALL CITY,
3/4" CHWS 3/4" CHWR 3/4" CHWR 1 1/4" CHWS STATE AND FEDERAL REQUIREMENTS, AND
3/4" CHWR 3/4" CHWR
11TH FLOOR 11TH FLOOR 3/4" CHWS 1 1/4" CHWR I AM NOT PROVIDING CONTRACT
10TH FLOOR 10TH FLOOR 3/4" CHWS 11TH FLOOR 11TH FLOOR 11TH FLOOR ADMINISTRATION.
HOTEL
11TH FLOOR HOTEL HOTEL
11TH FLOOR HOTEL 11TH FLOOR 10TH FLOOR 10TH FLOOR 3/4" DR 10TH FLOOR CERTIFIED CORRECT
T.O.S.
113' - 1"
113' - 1" T.O.S.
113' - 1"
113' - 1" 10TH FLOOR HOTEL
11TH FLOOR HOTEL HOTEL
11TH FLOOR HOTEL HOTEL
11TH FLOOR HOTEL
HOTEL T.O.S.
113' - 1" T.O.S.
113' - 1" T.O.S.
113' - 1"
LO
E OF U I S I A
112' - 6 1/2" 112' - 6 1/2" 11TH FLOOR HOTEL
T.O.S.
113' - 1" 113' - 1" 113' - 1" 113' - 1"
1 1/4" CHWS 113' - 1" 112' - 6 1/2" 112' - 6 1/2" 112' - 6 1/2"
FCU-M AT
112' - 6 1/2"
NA
ST
1 1/4" CHWR 1 1/4" CHWS 1 1/2" CHWS
1 1/4" CHWS
1 1/2" CHWR
3/4" DR 1 1/4" CHWR 1" CHWS
3/4" DR 1 1/4" CHWR RAYMOND E. SMITH
3/4" DR 1" CHWR 3/4" DR 1" CHWR LICENSE. No. 36823
3/4" DR 1" CHWS REGISTERED
NG
MEC
PROFESSIONAL ENGINEER
3/4" DR
I
IN
ER
NI
HA
FCU-D FCU-C CA L ENG I NE
FCU-B FCU-B FCU-C
FCU-B THIS DRAWING IS CONFIDENTIAL AND
NOT BE LOANED, REPRODUCED, COPIED,
3/4" CHWR 3/4" CHWS EITHER WHOLLY OR IN PART, OR MADE
3/4" CHWS PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
3/4" CHWS 3/4" CHWR 3/4" CHWR 1" CHWS
3/4" CHWR 3/4" CHWR CONSENT OF HBSA II ARCHITECTS,
10TH FLOOR 10TH FLOOR 3/4" CHWS 1" CHWR A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
FCU-D FCU-C
FCU-B FCU-B FCU-C BALANCING
FCU-B VALVE
3/4" CHWR 3/4" CHWS
3/4" CHWS
3/4" CHWS 3/4" CHWR 3/4" CHWR 3/4" CHWS
3/4" CHWR 3/4" CHWR
3/4" CHWS 3/4" CHWR
3/4" CHWS
9TH FLOOR HOTEL
9TH FLOOR HOTEL 9TH FLOOR HOTEL
9TH FLOOR HOTEL 3/4" DR
8TH FLOOR 92'T.O.S.
92' - 3"
- 3" 8TH FLOOR 92'T.O.S.
92' - 3"
- 3" 9TH FLOOR HOTEL
9TH FLOOR HOTEL 9TH FLOOR HOTEL
9TH FLOOR HOTEL 9TH FLOOR HOTEL
9TH FLOOR HOTEL
9TH FLOOR HOTEL
9TH FLOOR HOTEL 8TH FLOOR 92'T.O.S.
92' - 3"
- 3" 8TH FLOOR 92'T.O.S.
92' - 3"
- 3" 8TH FLOOR 92' T.O.S.
92' - 3"
- 3"
91' - 8 1/2" 91' - 8 1/2" 8TH FLOOR 92'T.O.S.
92' - 3"
BALANCING 3/4" CHWS BALANCING - 3" 91' - 8 1/2" 91' - 8 1/2" FCU-K
91'
FCU-K
- 8 1/2"
VALVE VALVE 91' - 8 1/2" BALANCING BALANCING
3/4" CHWR 3/4" CHWS BALANCING VALVE
1" CHWS VALVE
3/4" DR 3/4" CHWR 3/4" CHWS VALVE 3/4" CHWS
3/4" DR 1" CHWR 3/4" CHWR 3/4" CHWR
3/4" DR 3/4" CHWR 3/4" CHWR
3/4" DR 3/4" DR 3/4" CHWS 3/4" CHWS
3/4" DR 3/4" DR
FCU-D FCU-C
FCU-B FCU-B FCU-C 3/4" DRAIN TO HUB DRAIN (SEE
FCU-B PLUMBING DRAWINGS)
3/4" CHWR 3/4" CHWS
3/4" CHWS
3/4" CHWS 3/4" CHWR 3/4" CHWR
3/4" CHWR
3/4" CHWR 3/4" CHWS
3/4" CHWS
8TH FLOOR HOTEL
8TH FLOOR HOTEL 8TH FLOOR HOTEL
8TH FLOOR HOTEL
81' -81'10"
- 10"
81' -81'10"
- 10" 8TH FLOOR HOTEL
8TH FLOOR HOTEL 8TH FLOOR HOTEL
8TH FLOOR HOTEL 8TH FLOOR HOTEL
8TH FLOOR HOTEL
8TH FLOOR HOTEL
8TH FLOOR HOTEL
81' -81'10"
- 10"
81' -81'10"
- 10"
81' -81'10"
- 10"
3/4" DRAIN TO HUB DRAIN (SEE 81' -81'10"
- 10"
1 PLUMBING DRAWINGS) 3/4" DRAIN TO HUB DRAIN (SEE
3/4" DRAIN TO HUB DRAIN (SEE 1
1 3/4" DRAIN TO HUB DRAIN PLUMBING DRAWINGS)
PLUMBING DRAWINGS) 1 3/4" DRAIN TO HUB DRAIN (SEE
(SEE PLUMBING DRAWINGS) PLUMBING DRAWINGS)
1 MECHANICAL WATER
RISER DIAGRAMS
PROJECT#: 1709
PHASE: PERMIT
TEAM: MEI
s a ii
architects
P L L C
ii
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
FCU-K FCU-K FCU-L
since 1961
3/4" CHWR FCU-C 3/4" CHWR
3/4" CHWS 3/4" CHWS
3/4" DR 3/4" CHWS 3/4" DR
3/4" CHWR 3/4" CHWS
3/4" CHWR 3/4" CHWR
13TH FLOOR
14TH FLOOR HOTEL 3/4" DR
3/4" CHWS 14TH &FLOOR
POOL DECK
3/4" DR T.O.S.
144' 144'
- 4"- 4"
FCU-B FCU-B
3/4" CHWS
143' - 9 1/2"
2" CHWR
3/4" CHWR 3/4" CHWR
1-1/2" CHWS & CHWR TO 1-1/4" CHWS & CHWR TO 2" CHWS
13TH FLOOR 13TH FLOOR 13TH FLOOR
HARD ROCK
T.O.S.
144' 144' - 4"
- 4" T.O.S.
144' - 4"
144' - 4" 2" CHWS & CHWR TO T.O.S.
144' - 4"
144' - 4"
143' - 9 1/2" 143' - 9 1/2" CHILLER (SEE M1.4.4) FCU-L 143' - 9 1/2" 13TH FLOOR
14TH FLOOR
14TH &FLOORHOTEL
POOL DECK
T.O.S.
T.O.S.
113' 113' - 1"
- 1" FCU-B FCU-B
CERTIFIED CORRECT
112' - 6 1/2" LO
1" CHWS 1" CHWS 1 1/4" CHWR TE OF U I S I A
1" CHWR 11TH FLOOR 11TH FLOOR 11TH FLOOR 3/4" CHWR A
NA
ST
1" CHWR 1 1/4" CHWS
3/4" DR 10TH FLOOR
HOTEL
11TH FLOOR HOTEL 3/4" DR
10TH FLOOR
HOTEL
11TH FLOOR HOTEL 3/4" DR 10TH FLOOR
HOTEL
11TH FLOOR HOTEL 3/4" CHWS
T.O.S.
113' - 1" T.O.S.
113' - 1" T.O.S.
113' - 1"
11TH FLOOR RAYMOND E. SMITH
113' - 1" 113' - 1" 113' - 1" LICENSE. No. 36823
112'
FCU-K - 6 1/2" 112' - 6 1/2" FCU-L 112' - 6 1/2" 10TH FLOOR
HOTEL
FCU-K 11TH FLOOR HOTEL REGISTERED
NG
MEC
T.O.S.
113' 113' - 1"
- 1" PROFESSIONAL ENGINEER
I
112' - 6 1/2" IN
ER
NI
HA
3/4" CHWR 3/4" CHWR FCU-C 3/4" CHWR 1 1/4" CHWS CA L ENG I NE
3/4" CHWS 3/4" CHWS 3/4" CHWS 3/4" CHWS 1 1/4" CHWR
3/4" DR 3/4" DR 3/4" DR THIS DRAWING IS CONFIDENTIAL AND
3/4" CHWS 3/4" CHWR 3/4" DR NOT BE LOANED, REPRODUCED, COPIED,
3/4" CHWR 3/4" DR EITHER WHOLLY OR IN PART, OR MADE
PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
10TH FLOOR BALANCING CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
HOTEL
10TH FLOOR HOTEL VALVE OR INVENTION ARE RESERVED AND WILL
9th FLOOR102' T.O.S.
102' - 8"
- 8" FCU-B FCU-B
REMAIN THE SOLE PROPERTY OF HBSA II
ARCHITECTS A PROFESSIONAL L.L.C.
102' - 1 1/2"
3/4" CHWS 3/4" CHWS 1" CHWR
3/4" CHWR 10TH FLOOR 3/4" CHWR 10TH FLOOR 1" CHWS 10TH FLOOR 3/4" CHWR REVISION HISTORY
3/4" DR HOTEL HOTEL 3/4" DR HOTEL 3/4" CHWS
10TH FLOOR HOTEL 3/4" DR 10TH FLOOR HOTEL 10TH FLOOR HOTEL
9th FLOOR102' T.O.S.
102' - 8"
- 8" 9th FLOOR102' T.O.S.
102' - 8"
- 8" 9th FLOOR102' T.O.S.
102' - 8"
- 8" 10TH FLOOR
102'
FCU-K
- 1 1/2" FCU-K 102' - 1 1/2" 102' - 1 1/2" HOTEL
10TH FLOOR HOTEL
FCU-L 9th FLOOR102' T.O.S.
102' - 8"
- 8"
102' - 1 1/2"
3/4" CHWR 3/4" CHWR FCU-C 3/4" CHWR BALANCING
1" CHWS VALVE
3/4" CHWS 3/4" CHWS 3/4" CHWS
3/4" DR 1" CHWR
3/4" DR 3/4" DR 3/4" DR
3/4" CHWS
3/4" CHWR 3/4" DRAIN TO HUB DRAIN (SEE
BALANCING VALVE 1
BALANCING VALVE PLUMBING DRAWINGS)
9TH FLOOR HOTEL
9TH FLOOR HOTEL
8TH FLOOR 92'T.O.S.
92' - 3"
- 3" FCU-B FCU-B
91' - 8 1/2"
3/4" CHWS 3/4" CHWS 3/4" CHWR BALANCING
3/4" CHWR VALVE 3/4" CHWR
3/4" CHWR 3/4" CHWS
3/4" DR 9TH FLOOR HOTEL 9TH FLOOR HOTEL 3/4" DR 9TH FLOOR HOTEL 3/4" CHWS
9TH FLOOR HOTEL 3/4" DR 9TH FLOOR HOTEL 9TH FLOOR HOTEL
8TH FLOOR 92'T.O.S.
92' - 3"
- 3" 8TH FLOOR 92'T.O.S.
92' - 3"
- 3" 92' 92' - 3"
- 3"
91' - 8 1/2"
FCU-K FCU-K 91' - 8 1/2" 9TH FLOOR HOTEL
9TH FLOOR HOTEL
92' 92' - 3"
- 3"
3/4" CHWR BALANCING 3/4" CHWR FCU-C
3/4" DRAIN TO HUB DRAIN (SEE
3/4" CHWS VALVE 3/4" CHWS 1
PLUMBING DRAWINGS)
3/4" DR 3/4" DR
3/4" CHWS
3/4" CHWR
s a ii
architects
P L L C
ii
189 Maple Ridge Drive Metairie, LA 70001
(504)885−4477
[email protected] :−: hbsaii.com
since 1961
FCU-C FCU-B FCU-C FCU-C FCU-C
HARD ROCK
3/4" DR
CHILLER (SEE M1.4.4)
NA
ST
3/4" DR 3/4" DR
RAYMOND E. SMITH
LICENSE. No. 36823
REGISTERED
NG
MEC
PROFESSIONAL ENGINEER
FCU-C FCU-B FCU-C FCU-C FCU-C
I
IN
ER
NI
HA
CA L ENG I NE
3/4" CHWS 3/4" CHWS 3/4" CHWS THIS DRAWING IS CONFIDENTIAL AND
3/4" CHWR 3/4" CHWR NOT BE LOANED, REPRODUCED, COPIED,
10TH FLOOR 10TH FLOOR 3/4" CHWR 10TH FLOOR EITHER WHOLLY OR IN PART, OR MADE
PUBLIC IN ANY MANNER WITHOUT THE WRITTEN
HOTEL
10TH FLOOR HOTEL HOTEL
10TH FLOOR HOTEL HOTEL
10TH FLOOR HOTEL
CONSENT OF HBSA II ARCHITECTS,
A PROFESSIONAL L.L.C. ALL RIGHTS OF DESIGN
9th FLOOR102' T.O.S.
102' - 8"
- 8" 9th FLOOR102' T.O.S.
102' - 8"
- 8" 9th FLOOR102'T.O.S.102' - 8"
- 8" OR INVENTION ARE RESERVED AND WILL
REMAIN THE SOLE PROPERTY OF HBSA II
102' - 1 1/2" 102' - 1 1/2" 102' - 1 1/2" ARCHITECTS A PROFESSIONAL L.L.C.
BALANCING VALVE 1 1/2" CHWS
1" CHWR BALANCING
1" CHWS VALVE 1 1/2" CHWR
3/4" DR 3/4" DR REVISION HISTORY
3/4" CHWR
3/4" CHWS
3/4" DR
FCU-C FCU-C
3/4" CHWS
3/4" CHWR
8TH FLOOR8TH
HOTEL
FLOOR HOTEL
81' - 10"
81' - 10"
3/4" DRAIN TO HUB DRAIN (SEE
1
PLUMBING DRAWINGS)
MECHANICALWATER
RISER DIAGRAMS
PROJECT#: 1709
PHASE: PERMIT
1 CHILLED WATER RISER 18
SCALE: 1/4" = 1'-0"
2 CHILLED WATER RISER 19
SCALE: 1/4" = 1'-0"
3 CHILLED WATER RISER 20
SCALE: 1/4" = 1'-0"
TEAM: Author
CHECKER: Checker
SCALE: AS NOTED
ISSUED: 06/05/2018
CONSULTING ENGINEERS
909 Poydras Street, Suite 2150
New Orleans, Louisiana 70112-1034
Tel. 504-586-1725
M8.5