Method for Assessing the Effect of Design Parameters on Controllability
Method for Assessing the Effect of Design Parameters on Controllability
Bjorn D. Tyreus
DuPont Central Science and Engineering, Experimental Station, P.O. Box 80101,
Wilmington, Delaware 19880
The interaction between design and control can offer significant opportunities for dynamic
performance improvement if one is willing to consider building and operating a chemical process
at other than the steady-state economic optimum. This paper describes a method that a process
designer could use to identify design and control parameters that could be used to improve the
controllability of a process. The method relies upon designed experimentation in two separate
steps. The first step uses steady-state information as a screening tool to filter the important
factors from the many possible design factors. The second step uses dynamic simulation and
provides more details about how the design and control decisions affect the ultimate dynamic
performance in the presence of disturbances and production rate changes. The capital and
operating costs of the various designs are calculated to indicate the economic penalty for designing
and operating at other than the steady-state optimum. Three examples are provided to illustrate
the method and to develop several design heuristics.
alternative inventory control structures. The number for m columns when the vapor boilup rates are the
of factors and the number of levels of each factor manipulated variables used to control product quality.
determine the size of the problem. Since the method Step 4 generates a vector of the distance of the quality
includes the closed-loop dynamic simulation of each case manipulated variable moves, one for each case in the
for each disturbance, the number of factors should be designed experiment. The vector is then analyzed using
kept small; six or fewer is recommended. If the factors analysis of variance techniques (ANOVA) in order to
that are expected to interact can be grouped together, reach conclusions regarding the relative importance of
such as recycle flowrate and composition, then a series design factors on the controllability. This step serves
of executions of the method can be performed to handle as a filter on the factors allowing the elimination of some
a large number of factors. of them from further study. Because of the large
Step 2 is to organize the factors in a designed number of cases resulting from the inclusion of a single
experiment framework consisting of a set of cases in factor in the designed experiment, the elimination of one
which each factor is varied between two or three distinct or two factors can greatly reduce the number of cases
levels. Depending on the factor, the levels may be required in the dynamic simulation step.
3486 Ind. Eng. Chem. Res., Vol. 35, No. 10, 1996
3. The recycle composition is calculated from a reflux ratio, and the vapor boilup rate can then be
component balance on the column. calculated. Saturated liquid feed to the column is
assumed.
Fzn - (F - D)xb
xd ) (4)
D yf )
Rxf
(11)
1 + (R - 1)xf
4. The reactor volumes and reactor effluent concen-
trations are calculated using equations for CSTR’s in (xd - yf)/(xd - xf)
series: RR ) (RR factor) (12)
1 - (xd - yf)/(xd - xf)
F(1 - (zn/zin)1/n)
Vr ) (5) 7. A column design program is used to determine the
k(zn/zin)1/n number of trays and the optimum feed tray location.
This program starts at the bottom of the column with
zn ) zin ( F
F + Vrk ) n
(6)
the known vapor boilup rate and bottoms composition
and calculates liquid and vapor compositions for each
tray of the column. The procedure is repeated until the
5. The cooling water flowrates and cooling water vapor composition is greater than the distillate composi-
outlet temperatures are calculated from the known tion (Luyben and Wenzel, 1988). The resulting number
reaction rates for each reactor and assumed values for of trays is rounded up to an integer value.
the heat-transfer coefficients and the cooling water inlet 8. A column rating program is used to find the reflux
temperature for each. ratio required to obtain the desired split with an integer
number of trays (Luyben and Wenzel, 1988). This
Reactor 1 adjusts the tray compositions slightly.
3.4. Control Structures and Tuning. The control
Q1 ) -MCp(FT1 - F0TF0 - DTd) - λkVrz (7) structure for this system is shown in Figure 1. The
reflux drum and the column base liquid level controllers
Reactor n are assumed to be perfect controllers, as is the flowrate
controller on the reactor outlet stream. The liquid level
in each CSTR is controlled by using the inlet flowrate
Qn ) -MCpF(Tn - Tn-1) - λkVrzn (8) as the manipulated variable. The first reactor utilizes
the fresh feed flowrate for this purpose. The setpoints
-Qn for these level controllers are used to control the
Tcw,n ) + Tn (9) throughput of the process. This control structure was
UAh
found to minimize the snowball effect (Luyben, 1993a-
-Qn c). The controller tuning parameters for the level loops
Fcw,n ) (10) are calculated directly from the linear model for this
McwCp,cw(Tcw,in - Tcw,n) subsystem using a controller reset time of 0.5 h and
choosing the proportional gain such that the roots of the
6. The minimum reflux ratio is calculated from the closed-loop characteristic equation are located on the
known column feed and top compositions using the negative real axis on a root locus plot. The composition
Underwood equations. Multiplying the minimum reflux of the column bottoms is controlled using the vapor
ratio by the RR factor (typically 1.2) gives the actual boilup rate, V. Control structure 1 controls the distillate
3488 Ind. Eng. Chem. Res., Vol. 35, No. 10, 1996
Table 3. Partial Designed Experiment Array effects of six factors at two levels each. As a screening
case 1 2 3 4 5 6 study, a 1/4 fraction of the full 26 design is selected. This
is referred to as a 26-2 design. It is constructed as a
1
normal 24 design with an additional two factors assigned
-1 -1 -1 -1 -1 -1
2 1 -1 -1 -1 1 -1
3 -1 1 -1 -1 1 1 as aliases to interaction effects. The resulting design
4 1 1 -1 -1 -1 1 has 24 ) 16 experiments and a resolution of 4. This
5 -1 -1 1 -1 1 1 resolution will provide information about the main effect
6 1 1 1
7
-1
1 1
-1 -1
for each factor aliased with three factor interactions
only. Also, some two factor interactions are aliased with
-1 -1 -1 -1
8 1 1 1 -1 1 -1
9 -1 -1 -1 1 -1 1 other two factor interactions (Box and Hunter, 1961a,b;
10 1 -1 -1 1 1 1 Montgomery, 1984). The levels for each factor for each
11 -1 1 -1 1 1 -1 case are shown in Table 3. The numbers within the
12 1 1 1
13
-1
1 1
-1
1
-1
table reflect the level of the particular factor that will
be used in the corresponding case. Each case corre-
-1 -1 -1
14 1 -1 1 1 -1 -1
15 -1 1 1 1 -1 1 sponds to an individual design followed by loop tuning
16 1 1 1 1 1 1 and a 15 h simulation in which the process is subjected
to a known disturbance.
composition by manipulating the reflux flowrate (dual- 3.7. Design Results. Step 3 is the calculation of the
ended composition control). Control structure 2 fixes steady-state design for each case. Table 4 shows the
the reflux flowrate (single-ended composition control). results. The steady-state design allows the calculation
The distillate and the bottoms composition loops were of the steady-state operating cost and the capital cost
tuned independently and operated together with no of the equipment. The capital cost for each design is
detuning necessary.
estimated using correlations from the literature (Dou-
3.5. Design and Control Factors. The first step
glas, 1988). The maximum NPV is provided by case 1
in the proposed method is to select design and control
(small RR factor, single CSTR, small D, small zn, and
factors. In this example we wish to determine the
small Ah). The NPV is separated into operating and
influence, if any, of a group of six design factors on the
closed-loop dynamic performance of the entire process. capital costs to study the influence of each of the factors.
These design factors are described in Table 2. The first The 10% change made in the recycle flowrate has no
factor is the control structure. The second factor is a significant influence on the process capital cost. The
multiplication factor that determines the actual reflux number of reactors, n, is the main contributor to the
ratio relative to the minimum reflux ratio for each determination of the capital cost. Using more reactors
design. The remaining factors are self-explanatory. increases the capital cost because of the low conversion
3.6. Design Factor Variation. Step 2 is assembly (40 to 50%). The annual operating cost is proportional
of a designed experiment. The design factors’ influence to the steady-state vapor boilup rate and hence has a
upon the dynamic performance measurement will be minimum corresponding to the minimum in the vapor
evaluated using a fractional factorial designed experi- boilup rate. In turn, the minimum vapor boilup rate
ment. In this study, we desire information about the corresponds to a low RR factor and a low value for D.
Table 12. Product Stream Compositions Table 13. Design Constants for the Ternary Process
composition flowrate parameter value units
stream component (mol fr) (lb mol/h)
z0a 1/0/0/0 mol fr
D2 A 0.010 0.5076 z0b 0/1/0/0 mol fr
B 0.005 0.2538 R 9/1.5/4/1
C 0.985 50.0 U 200 Btu/h/ft2/°F
D 0 0 Ah 1000 ft2
T 140 °F
total 1.0 50.761 Tf0 140 °F
B3 A 0 0 Td3 140 °F
B 0.005 0.251 Tcw,in 100 °F
C 0 0 Hvap 250 Btu/lb
D 0.995 50.0 λ -10000 Btu/lb mol
total 1.0 50.251 M 50 lb/lb mol
Cp 0.75 Btu/lb/°F
these designs shows that those processes that have a Mcw 18 lb/lb mol
large reactor and a small light recycle are more easily Cp,cw 1.0 Btu/lb/°F
controlled. The production rate change (not included kf0 0.2968 × 1011 h-1
here) shows that a large reactor with both recycles small kr0 0.1930 × 107 h-1
gives better controllability. These highly controllable Ef 30000 Btu/lb mol
Er 20000 Btu/lb mol
processes have low reactant concentrations in the reac-
tor; particularly for the light reactant. This can be Table 14. Design Factors for the Ternary Process
shown by locating the six lowest ISE designs on Table
factor level value units
9. The best designs have small values of zA. The best
process using dynamic controllability considerations is Vr 1 4000 lb mol
2 5000
case 1, while the economic optimum process is case 14.
3 6000
The cost of the improved controllability is a decrease of D3 1 45 lb mol/h
$707 000 in the NPV. 2 55
3 65
5. Example 3sQuaternary Process xd3 1 0/0.985/0.010/0.005 mol fr
2 0/0.850/0.100/0.050
The third process studied consists of a reactor, a 3 0/0.700/0.200/0.100
stripper, and two distillation columns with four com-
ponents from the work of Yi, 1994. light recycle, and intermediate purity light recycle) at
5.1. Process Description. The reaction is A + B $3 310 000. For this wide range of designs the NPV is
h C + D that occurs in the liquid phase and is fairly flat. The lowest NPV is case 25 at $2 850 000 (a
exothermic. The relative volatilities are assumed to be difference of only $460 000).
constant: RA ) 9, RB ) 1.5, RC ) 4, RD ) 1. The process 5.3. Disturbance Sensitivity Analysis. The con-
is shown in Figure 5 with one control structure in place. trol structure is shown in Figure 5.
The lightest component A is removed from the reactor The load disturbance is a shift in the fresh feed
effluent using a stripping column. The bottoms product composition of A from 1/0/0/0 to 0.95/0.05/0/0 in mole
of the stripper is fed to a second column for removal fractions of A/B/C/D. The manipulated variables that
and purification of product C, and the bottoms of column control product quality are the three vapor boilup
2 is fed to column 3 for removal and purification of streams. DSA tracks the distance between the two
product D. The distillate stream from column 3 con- steady states in terms of the three vapor boilup rates
tains mostly B and is recycled to the reactor. There are (x(∆V1)2 + (∆V2)2 + (∆V3)2).
four unit operations and two recycle streams. The steady-state distance measurements are shown
5.2. Design Results. As a basis for the process in Table 18. By comparing values in Table 18, one can
design, the reaction rate is fixed at 50 lb mol/h. The find the directions of the factor levels that are predicted
compositions of the product streams are assumed to be to give improved controllability. The higher the purity
as shown in Table 12. Fixing the reaction rate at 50 lb of xd3,B, the better is the DSA. Larger D3’s and Vr’s give
mol/h also fixes the flowrate of both C and D in the lower DSA values. Each of these factor directions tends
product streams at 50 lb mol/h. Since the product to reduce the magnitude of the disturbance that is
streams are not pure C and D, the total flowrates are passed to the columns. This is explained in the follow-
slightly larger than 50 lb mol/h, and hence the flowrates ing section. The factor effects show that none of the
of the fresh feeds are slightly larger also. The fresh main factors can be eliminated from the dynamic testing
feeds F0a and F0b are assumed to be pure A and B, of the load disturbance. These results are compared
respectively. A further assumption is that the recycle with the dynamic simulation results in the next section.
stream from the third column contains no A component The DSA results predict that case 25 is the best design.
(xd3,A ) 0). This is a good assumption since any A that 5.4. Dynamic Controllability. The dynamic con-
makes it to the bottoms stream of the stripping column trollability of the quaternary process is measured using
will go out with the D2 product. The reactor tempera- the integral squared error of the sum of deviations in
ture is 140 °F, and the reaction rate constants for the each of the impurity levels in both product streams. The
forward and reverse reactions are 0.35 and 0.10 h-1, deviations that are added together are deviations in
respectively. All of the design constants and parameters variables: xd2,A, xd2,B, xd2,D, xb3,A, xb3,B, and xb3,C. The
are shown in Table 13. ISE is calculated for each of the 27 cases using control
The parameters Vr, D3, and xd3 are selected to fix the structure 1 with single-ended control on column 3 for a
plant designs. These factors and their levels are shown load disturbance consisting of a shift in the fresh feed
in Table 14. composition of A from 1/0/0/0 to 0.95/0.05/0/0 in mole
The design procedure is detailed in Lyman, 1995. The fractions of A/B/C/D.
resulting designs are shown in Tables 15-17. The An example of the dynamic responses is shown in
highest NPV is provided by case 2 (small reactor, small Figure 6 using the results from case 1. The reactor
Ind. Eng. Chem. Res., Vol. 35, No. 10, 1996 3493
Table 15. Design Results for the Quaternary Process (Cases 1-9)
case
1 2 3 4 5 6 7 8 9
Vr (lb mol) 4000 4000 4000 4000 4000 4000 4000 4000 4000
D3 (lb mol/h) 45 45 45 55 55 55 65 65 65
xd3,B (mol fr) 0.985 0.850 0.700 0.985 0.850 0.700 0.985 0.850 0.700
xd3,C (mol fr) 0.010 0.100 0.200 0.010 0.100 0.200 0.010 0.100 0.200
xd3,D (mol fr) 0.005 0.050 0.100 0.005 0.050 0.100 0.005 0.050 0.100
Nt1 (trays) 11 11 13 10 11 12 10 10 11
Nt2 (trays) 19 15 13 20 15 13 20 15 13
Nt3 (trays) 52 40 35 52 40 35 52 40 35
zA (mol fr) 0.296 0.372 0.515 0.246 0.304 0.405 0.209 0.265 0.351
zB (mol fr) 0.182 0.138 0.089 0.220 0.176 0.124 0.259 0.203 0.148
zC (mol fr) 0.333 0.316 0.253 0.345 0.338 0.307 0.345 0.352 0.333
zD (mol fr) 0.190 0.174 0.143 0.188 0.183 0.165 0.187 0.180 0.169
F (lb mol/h) 300 340 430 305 328 380 307 338 380
V1 (lb mol/h) 154 194 284 149 172 224 141 172 214
V2 (lb mol/h) 139 130 128 142 138 130 151 142 132
V3 (lb mol/h) 269 261 240 304 284 256 341 316 279
R2 (lb mol/h) 89 80 77 91 87 79 100 91 81
R3 (lb mol/h) 224 216 195 249 229 201 276 251 214
B1 (lb mol/h) 146 146 146 156 156 156 166 166 166
B2 (lb mol/h) 95 95 95 105 105 105 115 115 115
cap cost (1000 $) 1646 1548 1531 1675 1563 1518 1708 1580 1523
oper cost (1000 $) 308 320 357 326 325 334 346 345 342
NPV (1000 $) 3254 3310 3204 3166 3279 3294 3063 3196 3263
Table 16. Design Constants for the Quaternary Process (Cases 10-18)
case
10 11 12 13 14 15 16 17 18
Vr (lb mol) 5000 5000 5000 5000 5000 5000 5000 5000 5000
D3 (lb mol/h) 45 45 45 55 55 55 65 65 65
xd3,B (mol fr) 0.985 0.850 0.700 0.985 0.850 0.700 0.985 0.850 0.700
xd3,C (mol fr) 0.010 0.100 0.200 0.010 0.100 0.200 0.010 0.100 0.200
xd3,D (mol fr) 0.005 0.050 0.100 0.005 0.050 0.100 0.005 0.050 0.100
Nt1 (trays) 11 11 12 10 10 11 9 10 11
Nt2 (trays) 19 15 13 20 15 13 20 15 13
Nt3 (trays) 52 40 35 52 40 35 52 40 35
zA (mol fr) 0.254 0.314 0.408 0.212 0.265 0.344 0.184 0.228 0.297
zB (mol fr) 0.192 0.151 0.108 0.230 0.182 0.134 0.262 0.213 0.159
zC (mol fr) 0.353 0.346 0.313 0.361 0.365 0.344 0.365 0.370 0.361
zD (mol fr) 0.201 0.189 0.171 0.197 0.188 0.178 0.189 0.189 0.182
F (lb mol/h) 284 313 359 292 320 354 306 322 352
V1 (lb mol/h) 138 167 213 136 164 198 140 156 186
V2 (lb mol/h) 139 130 128 142 138 130 151 142 132
V3 (lb mol/h) 269 261 240 304 284 256 341 316 279
R2 (lb mol/h) 89 80 77 91 87 79 100 91 81
R3 (lb mol/h) 224 216 195 249 229 201 276 251 214
B1 (lb mol/h) 146 146 146 156 156 156 166 166 166
B2 (lb mol/h) 95 95 95 105 105 105 115 115 115
cap cost (1000 $) 1764 1663 1626 1794 1677 1626 1825 1698 1638
oper cost (1000 $) 299 305 318 318 321 320 346 336 327
NPV (1000 $) 3166 3245 3240 3071 3180 3234 2948 3107 3199
composition controller increases F0a to maintain zA. The The largest effect upon the ISE is due to a two-factor
excess B that enters with F0a in this disturbance collects interaction between D3 and xd3. The ISE values for each
in the third column reflux drum and the level controller combination of D3 and xd3 are averaged together and
reduces F0b. V1 increases to bring xb1,A back to setpoint. plotted in Figure 8. Small D3 and more impure xd3
The impurities in D2 and B3 are controlled by V2 and result in especially large ISE’s and therefore poor
V3. This case does not use dual-ended composition controllability. The main contributor to the ISE is the
control; hence, xd3,B can vary. deviation of xd2,A. This can be explained using steady-
The ISE values that result from the dynamic simula- state arguments as follows. Small D3 and more impure
tions are shown in Table 18. The best process using xd3 result in a low flowrate of component B returned to
dynamic considerations alone is case 26, although the the reactor in the recycle stream. This must be com-
four best cases (cases 26, 17, 27, and 14) have very close pensated for by a large zA to achieve the same produc-
ISE’s. tion rate. A large vapor boilup rate in the stripper is
An ANOVA analysis of this vector gives the design required to remove the A from the reactor effluent. The
factor and factor interaction effects. These are shown flowrate of reactor effluent is correspondingly large. The
plotted along side the DSA results in Figure 7. From load disturbance results in a reactor effluent flowrate
these results, all three factors are seen to be equally change, while the reactor composition of A is fixed. The
important, and there is a significant two-factor interac- net result is that small D3 and more impure xd3 designs
tion between D3 and xd3. Examination of the ISE values have a larger reactor effluent flowrate (F) that carries
shows that larger reactor volumes, larger D3 flowrates, a larger disturbance to the stripper expressed in lb mol
and intermediate xd3 compositions give better control- A/h. This value is calculated and averaged together for
lability. Specific case comparisons can be used to each combination of D3 and xd3 in the same manner
understand these findings. described above. The combination of D3 and xd3 that
3494 Ind. Eng. Chem. Res., Vol. 35, No. 10, 1996
Table 17. Design Constants for the Quaternary Process (Cases 19-27)
case
19 20 21 22 23 24 25 26 27
Vr (lb mol) 6000 6000 6000 6000 6000 6000 6000 6000 6000
D3 (lb mol/h) 45 45 45 55 55 55 65 65 65
xd3,B (mol fr) 0.985 0.850 0.700 0.985 0.850 0.700 0.985 0.850 0.700
xd3,C (mol fr) 0.010 0.100 0.200 0.010 0.100 0.200 0.010 0.100 0.200
xd3,D (mol fr) 0.005 0.050 0.100 0.005 0.050 0.100 0.005 0.050 0.100
Nt1 (trays) 10 10 11 10 10 11 9 10 11
Nt2 (trays) 19 15 13 20 15 13 20 15 13
Nt3 (trays) 52 40 35 52 40 35 52 40 35
zA (mol fr) 0.232 0.287 0.365 0.191 0.238 0.306 0.165 0.205 0.266
zB (mol fr) 0.195 0.154 0.113 0.237 0.189 0.142 0.269 0.220 0.166
zC (mol fr) 0.370 0.368 0.342 0.370 0.378 0.365 0.372 0.381 0.377
zD (mol fr) 0.203 0.192 0.180 0.202 0.195 0.188 0.194 0.195 0.190
F (lb mol/h) 283 310 343 284 308 336 298 313 338
V1 (lb mol/h) 137 164 197 128 152 180 132 147 172
V2 (lb mol/h) 139 130 128 142 138 130 151 142 132
V3 (lb mol/h) 269 261 240 304 284 256 341 316 279
R2 (lb mol/h) 89 80 77 91 87 79 100 91 81
R3 (lb mol/h) 224 216 195 249 229 201 276 251 214
B1 (lb mol/h) 146 146 146 156 156 156 166 166 166
B2 (lb mol/h) 95 95 95 105 105 105 115 115 115
cap cost (1000 $) 1872 1770 1728 1906 1788 1735 1937 1810 1748
oper cost (1000 $) 299 304 309 314 315 310 342 331 319
NPV (1000 $) 3060 3144 3167 2974 3089 3158 2850 3013 3114
gives the largest deviation in the flowrate of A to the to xd2,A) and hence will give a lower ISE value. The
stripper corresponds to the combination that gives the manipulated variables move less for a larger reactor,
poorest controllability. as shown in the plots on the right side of Figure 9.
The larger the reactor inventory, the smaller is the The effect of different recycle flowrates can be seen
steady-state change in F. Also, the dynamic transition
in Figure 10. In this figure cases 2, 5, and 8 have D3
gets easier. This is shown by comparing three cases in
flowrates of 45, 65, and 75 lb mol/h, respectively. These
which only the reactor inventory differs. Cases 3, 12,
and 21 have reactor inventories of 4000, 5000, and 6000 cases were selected such that the other factors are the
lb mol/h, respectively. The other two factor levels are same for all three. The larger the recycle flowrate, the
the same for all three. The change in FzA (the distur- better is the controllability. As the recycle flowrate is
bance imposed upon the separation section) when mov- increased, there is more component B in the reactor and
ing between these two steady states is smaller for the less A is needed to achieve the same production rate
larger reactor processes. For cases 3, 12, and 21 the (the reactor temperature and volume are held constant).
steady-state changes in FzA are 4.51, 2.97, and 2.49 lb Since the compositions of component A in the reactor
mol A/h, respectively. The larger reactors also act to are held constant in each design, the steady-state
reduce the dynamic deviations in zA as shown in Figure deviation in the stripper feed can be expressed as zA∆F.
9. This results in a smaller deviation in xb1,A (equivalent With the larger recycle flowrates, zA is lower and the
Ind. Eng. Chem. Res., Vol. 35, No. 10, 1996 3495
Table 18. DSA Results for the Quaternary Process
case Vr (lb mol) D3 (lb mol/h) xd3,B (mol fr) x(∆V1)2 + (∆V2)2 + (∆V3)2 ISE results (109)
1 4000 45 0.985 4.17 0.1857
2 4000 45 0.850 5.03 0.1620
3 4000 45 0.700 6.84 0.5308
4 4000 55 0.985 3.78 0.0906
5 4000 55 0.850 4.20 0.1198
6 4000 55 0.700 5.14 0.2072
7 4000 65 0.985 3.42 0.1683
8 4000 65 0.850 4.03 0.0637
9 4000 65 0.700 4.78 0.1018
10 5000 45 0.985 3.88 0.1117
11 5000 45 0.850 4.52 0.1270
12 5000 45 0.700 5.42 0.2572
13 5000 55 0.985 3.59 0.1509
14 5000 55 0.850 4.09 0.0579
15 5000 55 0.700 4.70 0.1122
16 5000 65 0.985 3.43 0.1281
17 5000 65 0.850 3.79 0.0579
18 6000 65 0.700 4.36 0.0823
19 6000 45 0.985 3.89 0.0967
20 6000 45 0.850 4.50 0.0780
21 6000 45 0.700 5.14 0.1391
22 6000 55 0.985 3.48 0.0900
23 6000 55 0.850 3.93 0.0848
24 6000 55 0.700 4.41 0.0860
25 6000 65 0.985 3.33 0.1789
26 6000 65 0.850 3.66 0.0567
27 6000 65 0.700 4.15 0.0579
change in FzA is lower. This change is 2.54, 1.81, and in their recycle compositions but have the same values
1.49 lb mol A/h for cases 2, 5, and 8 respectively. for the other two factors. This figure shows that the
The dynamic responses of two impurity concentra- most impure recycle (case 3) has the largest deviation
tions are plotted in Figure 11 for three cases that differ in xb1,A while the other two are nearly identical. This
3496 Ind. Eng. Chem. Res., Vol. 35, No. 10, 1996