0% found this document useful (0 votes)
23 views80 pages

1747-um076_-en-e

Uploaded by

sie41427
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
23 views80 pages

1747-um076_-en-e

Uploaded by

sie41427
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 80

SLC 500 EtherNet/IP Adapter

Catalog Number 1747-AENTR

User Manual Original Instructions


SLC 500 EtherNet/IP Adapter User Manual

Important User Information


Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

These labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).

The following icon may appear in the text of this document.

Identifies information that is useful and can help to make a process easier to do or easier to understand.

2 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Table of Contents

Preface
About This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Download Firmware, AOP, EDS, and Other Files . . . . . . . . . . . . . . . . . . . . 7
Summary of Changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Chapter 1
About the SLC 500 EtherNet/IP Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Adapter Module Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Hardware Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
The 1747-AENTR in a
Logix System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Hardware/Software
Compatibility. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Diagnostic Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
What the Adapter Does . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Use of the Common Industrial Protocol (CIP). . . . . . . . . . . . . . . . . . . . . . 12
Understand the Producer/Consumer Model . . . . . . . . . . . . . . . . . . . . . . . 12
Support of Direct Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Chapter 2
Install Your Adapter Set the Network Address Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Enable or Disable the Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Determine Power Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Install the Adapter Module in the Chassis . . . . . . . . . . . . . . . . . . . . . . . . . 18
Connect Your Adapter to the Ethernet/IP Network through RJ-45
Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Chapter 3
Configure the Adapter for Your Configuration Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
EtherNet/IP Network IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Gateway Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Subnet Mask . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Use the Rockwell Automation BootP/DHCP Utility . . . . . . . . . . . . . . . . . 24
Save the Relation List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Use DHCP Software to Configure Your Adapter. . . . . . . . . . . . . . . . . . . . 26
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 3


Table of Contents

Chapter 4
Plan to Use Your EtherNet/IP Compatible 1746 and
Adapter 1747 I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Overview of Adapter Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Software Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Module Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Module Keying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Output Operation During Fault and Idle Modes . . . . . . . . . . . . . . . . 30
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Chapter 5
Configure the Adapter for Direct Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Connection through the RSLogix Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Create the Example Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5000 or Logix Designer
Configure the I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Application Add the Local EtherNet/IP Bridge to the I/O Configuration . . . . . . 35
Add the Adapter to the I/O Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 37
Add I/O Modules to the I/O Configuration . . . . . . . . . . . . . . . . . . . . . 39
Add Specialty I/O Modules using Advanced Connection . . . . . . . . . 42
Download the Program to the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Custom Settings (Edit Adapter Configuration). . . . . . . . . . . . . . . . . . . . . 47
Custom Settings for your
I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Online Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Chapter 6
Troubleshoot with the Status Interpret the Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Indicators Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

Appendix A
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

Appendix B
Adapter Web Dialogs Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Work with the Home Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Work with the Diagnostics Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Use the Diagnostic Overview Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Use the Network Settings Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Use the Ethernet Statistics Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Use the I/O Connections Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Work with the Configuration Pages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Use the Device Identity Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Use the Network Configuration Page . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Use the Device Services Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

4 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Table of Contents

Appendix C
Configure the RSLinx Ethernet Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Communication Driver Install the RSLinx Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Configure the AB_ETH/IP Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 5


Table of Contents

Notes:

6 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Preface

About This Publication Describes the procedures you use to install, program and troubleshoot your
EtherNet/IP™ Adapter module. This manual also includes several application
examples.

Download Firmware, AOP, Download firmware, associated files (such as AOP, EDS, and DTM), and access
EDS, and Other Files product release notes from the Product Compatibility and Download Center at
rok.auto/pcdc.

Summary of Changes This publication contains the following new or updated information. This list
includes substantive updates only and is not intended to reflect all changes.
Topic Page
Updated template throughout
Added section Enable or Disable the Web Server 16…18

Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.
Resource Description
Ethernet Design Considerations Reference Manual, ENET-RM002 Provides design considerations such as EtherNet/IP infrastructure components, features,
protocol and prediction of system performance.
EtherNet/IP Device Level Ring Application Technique, Describes DLR network operation, topologies, configuration considerations, and diagnostic
publication ENET-AT007 methods.
EtherNet/IP Web Server Module User Manual, ENET-UM527 Describes how to use the EtherNet/IP Web server module.
EtherNet/IP Network Devices User Manual, ENET-UM006 Describes how to use EtherNet/IP communication modules in Logix 5000™ control systems.
Ethernet Reference Manual, ENET-RM002 Describes basic Ethernet concepts, infrastructure components, and infrastructure features.
Provides guidance on how to conduct security assessments, implement Rockwell
System Security Design Guidelines Reference Manual, SECURE-RM001 Automation products in a secure system, harden the control system, manage user access,
and dispose of equipment.
UL Standards Listing for Industrial Control Products, Assists original equipment manufacturers (OEMs) with construction of panels, to help ensure
publication CMPNTS-SR002 that they conform to the requirements of Underwriters Laboratories.
American Standards, Configurations, and Ratings: Introduction to Motor Provides an overview of American motor circuit design based on methods that are outlined
Circuit Design, publication IC-AT001 in the NEC.
Industrial Components Preventive Maintenance, Enclosures, and Contact Provides a quick reference tool for Allen-Bradley industrial automation controls and
Ratings Specifications, publication IC-TD002 assemblies.
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides
Safety Guidelines for the Application, Installation, and Maintenance of general guidelines for the application, installation, and maintenance of solid-state control in
Solid-state Control, publication SGI-1.1 the form of individual devices or packaged assemblies incorporating solid-state
components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at rok.auto/literature.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 7


Notes:

8 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 1

About the SLC 500 EtherNet/IP Adapter

Overview This chapter provides an introduction to the features and functionalities of the
1747-AENTR SLC™ 500 EtherNet/IP Adapter. It includes the following sections.
Topic Page
Module Description 9
Hardware Components 10
The 1747-AENTR in a Logix System 11
Hardware/Software Compatibility 11
Diagnostic Indicators 11
What the Adapter Does 11
Use of the Common Industrial Protocol (CIP) 12
Understand the Producer/Consumer Model 12
Support of Direct Connections 12

Module Description The 1747-AENTR Adapter enables CompactLogix™ and ControlLogix®


processors to control SLC™ I/O modules. It is primarily designed to enable
migration of existing SLC controlled systems to Logix-based systems.

The adapter mainly acts as a gateway between the SLC backplane and
EtherNet/IP and typically replaces an SLC controller in the 1746 rack. On
remote SLC racks, it replaces the 1747-ASB module or the ControlNet® adapters
1747-ACN15 and 1747-ACNR15.

Control of the backplane I/O is accomplished with a CompactLogix or


ControlLogix controller communicating through an EtherNet/IP router in the
Logix backplane, across EtherNet/IP, and into the 1747-AENTR gateway.

As a gateway between the SLC backplane and EtherNet/IP, the 1747-AENTR


module is a CIP™ server (for both Explicit Messaging and I/O) on the Ethernet
port, and an SLC host on the 1746 backplane.

Connections can be made to support 1746 and 1747 analog, digital, and
specialty I/O modules installed in the backplane.

IMPORTANT Studio 5000 Logix Designer® application (previously RSLogix 5000®)


revision 21 and later, and firmware revision 2.001 and later supports:
• multiple chassis, with a maximum number of three chassis;
• a maximum of 30 SLC I/O modules;
• a maximum of 96 Class 1 connections;
• up to 8 Class 3 connections.

For the complete list of supported I/O modules, see the table, List of I/O
Modules Supported by the 1747-AENTR Adapter on page 27.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 9


Chapter 1 About the SLC 500 EtherNet/IP Adapter

Hardware Components The adapter module consists of the following hardware components:

1747-AENTR
Network switches
5.1 4-character dot matrix display
5
Module status indicator
LINK1 LINK2 MOD

Link 2 status indicator


Latch
Link 1 status indicator

Front cover

7
1.3

5.72

PCB Link 1 Link 2


RJ-45 Ethernet connectors
Side view Front view

45845 45846

Left side view Right side view

1 8
Ethernet connectors (RJ-45)
8 1

45844

Bottom view

10 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 1 About the SLC 500 EtherNet/IP Adapter

The 1747-AENTR in a In this example, the I/O modules communicate with the controller through the
Logix System 1747-AENTR adapter. The controller can produce and consume tags to the I/O.
Configuration of devices and the network is done through the personal
computer running the controller and configuration software.

Computer running
controller and Rockwell
Automation configuration
software

EtherNet/IP Network

ControlLogix controller PanelView™ terminal

1747-AENTR adapter 45848

Hardware/Software The adapter and the applications described in this manual is compatible with
Compatibility the following firmware revisions and software releases.
Firmware Revision/
Product Software Versions
1747-AENTR 1.001 or later
Logix controller v20 or later
RSLogix 5000 or Logix Designer v20 or later
RSLinx® software v2.59 or later

Diagnostic Indicators The module has the following diagnostic indicators:


• Link 1 and Link 2 status indicator
• Module indicator
• 4-character status display

What the Adapter Does The 1747-AENTR EtherNet/IP adapter performs the following primary tasks:
• Control of real-time I/O data (also known as implicit messaging) – the
adapter serves as a bridge between I/O modules and the network
• Support of messaging data for configuration and programming
information (also known as explicit messaging)

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 11


Chapter 1 About the SLC 500 EtherNet/IP Adapter

CONTROLLER
E
N
B
T
EtherNet/IP Network

1 SLC I/O Other


7 Network
4 Devices
7
-
A
E
N
T
R

Use of the Common The adapter uses the Common Industrial Protocol (CIP), the application layer
Industrial Protocol (CIP) protocol specified for EtherNet/IP, the Ethernet Industrial Protocol. It is a
message-based protocol that implements a relative path to send a message
from the producing device in a system to the consuming devices.

The producing device contains the path information that steers the message
along the proper route to reach its consumers. Since the producing device
holds this information, other devices along the path simply pass this
information; they do not store it.
This has the following significant benefits:
• You do not need to configure routing tables in the bridging modules,
which greatly simplifies maintenance and module replacement.
• You maintain full control over the route taken by each message, which
enables you to select alternative paths for the same end device.

Understand the Producer/ The CIP producer and consumer networking model replaces the old source
Consumer Model and destination (master and slave) model. The producer and consumer model
reduces network traffic and increases speed of transmission. In traditional I/O
systems, controllers poll input modules to obtain their input status. In the CIP
system, input modules are not polled by a controller. Instead, they produce
(multicast or unicast) their data periodically or at a cyclic rate.

Unicast is the default for version 20 with multicast as a selectable option. The
frequency of update depends upon the options chosen during configuration
and where on the network the input module resides. The input module,
therefore, is a producer of input data, and the controller is a consumer of the
data.

The controller also produces data for other controllers to consume. The
produced and consumed data is accessible by multiple controllers and other
devices over the EtherNet/IP network. This data exchange conforms to the
producer and consumer model.

Support of Direct The EtherNet/IP adapter only supports direct connections. A direct connection
Connections is a real-time data transfer link between a Logix controller and a 1746/1747 I/O
module through the 1747-AENTR adapter. Direct I/O connections occur at a
cyclic rate specified by the RPI during configuration.

12 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 1 About the SLC 500 EtherNet/IP Adapter

The adapter can support direct connections to devices in expansion racks. This
feature is supported on Logix Designer application (previously RSLogix 5000
software) revision 21 and later, and firmware revision 2.001 and later.
See the EtherNet/IP Network Devices User Manual, publication
ENET-UM006, for more information on connections.

Chapter Summary This chapter provided an overview of the module features, what it does, and its
function in a Logix system.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 13


Chapter 1 About the SLC 500 EtherNet/IP Adapter

Notes:

14 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 2

Install Your Adapter

This chapter describes how to install the 1747-AENTR adapter and connect it to
the EtherNet/IP network.

The following table lists where to find specific information.


Topic Page
Set the Network Address Switches 15
Determine Power Requirements 18
Install the Adapter Module in the Chassis 18
Connect Your Adapter to the Ethernet/IP Network through RJ-45 Connection 19
Chapter Summary 20

Set the Network Address The network address switches are set to 999 and DHCP enabled, by default.
Switches You can set the network Internet Protocol (IP) address in the following ways:
• Use the network address switches on the module.
• Use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.
• Retrieve the IP address from nonvolatile memory.

The adapter reads the network address switches first to determine if the
switches are set to a valid number. You set the node address by using the
network address switches. Valid settings range from 001…254.

When the switches are set to a valid number, the adapter’s IP address is
192.168.1.xxx (where xxx represents the number set on the switches).

The adapter’s subnet mask is 255.255.255.0 and the gateway address is set to
0.0.0.0. The adapter does not have a host name assigned, or use any Domain
Name System when using the network address switch settings.

If the switches are set to an invalid number (for example, 000 or a value greater
than 254 excluding 888), the adapter checks to see if DHCP is enabled. Setting
the switches to 888 restores default factory settings.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 15


Chapter 2 Install Your Adapter

IMPORTANT If you set the value of the adapter switch to 888 and then power cycle
the module, the following occurs:
• The DHCP Enabled function is enabled (set to True).
• The Ethernet link is negotiated automatically. The Auto Negotiate
function is set to True.
• The web server is enabled. The Disabled Web Server function is
disabled.
• The Ethernet ports are disabled. Both ports are re-enabled once the
switches are returned to their previous value and power is cycled.

DHCP Enabled and Not Enabled


DHCP Enabled and Not Enabled
If DHCP is Then the Adapter
Asks for an address from a DHCP server. The DHCP server also assigns other Transport Control
Protocol (TCP) parameters.
The 1747-AENTR factory default is DHCP enabled. When you apply power, the module sends a
Enabled message containing its hardware address to any DHCP server on the network. The server(s)
replies by sending a message with an appropriate IP address for the adapter. The adapter
responds by acknowledging to a server that it will use the offered IP address.
Uses the IP address (along with other TCP configurable parameters) stored in nonvolatile
memory.
When the IP address assigned to the module, as indicated in the four-character dot-matrix
Not enabled status display, is changed through the DHCP configuration utility, the DHCP is disabled.
When power is cycled to the device, it uses the new configuration and implements the new IP
address.

See the chapter, Configure the Adapter for Your EtherNet/IP Network on
page 21, for information on how to use your BootP/DHCP utility to configure
your adapter for the network.

Enable or Disable the Web Server


With firmware revision 2.003 or later, the web server feature is disabled by
default. Use the network address switches to enable or disable the web server
for your application.
Value Description
Enables the web server.
000 Cycle power to the adapter for the setting to take effect. When you apply power, the module LED
flashes red and the four-character status display scrolls the message “Web Server Enabled”.
Disables the web server.
901 Cycle power to the adapter for the setting to take effect. When you apply power, the module LED
flashes red and the four-character status display scrolls the message “Web Server Disabled”.

IMPORTANT If you set the value of the switch to 901 and then cycle power to the
adapter, the following occurs:
• The web server is disabled.
• If the product supports SNMP, the SNMP server is also disabled.
This value is a transitional setting, the adapter does not operate while
the switch remains at this value. After the message “Web Server
Disabled” displays, change the value of the switch based on your IP
address mode and cycle power to the adapter.

The following section describes how to enable or disable the web server based
on the IP address mode that is used.

16 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 2 Install Your Adapter

Enable Web Server in Static IP mode


1. Set the switches to 000 and cycle power to the adapter.
The module LED flashes red and the four-character status display scrolls
the message “Web Server Enabled”.
2. Set the switches to the desired IP address and cycle power to the adapter.
3. In your web browser, enter the IP address of the adapter.
The web server home page displays.

Disable Web Server in Static IP mode


1. Set the switches to 901 and cycle power to the adapter.
The module LED flashes red and the four-character status display scrolls
the message “Web Server Disabled”.
2. Set the switches to the desired IP address and cycle power to the adapter.
3. In your web browser, enter the IP address of the adapter.
The web server home page does not display.

Enable Web Server in DHCP mode

Before you begin, verify that you have an active DHCP server on your network.
1. Set the switches to 000 and cycle power to the adapter.
The module LED flashes red and the four-character status display scrolls
the message “Web Server Enabled”.
2. Set the switches to 999 and cycle power to the adapter.
3. In RSLinx software, check the IP address that was assigned to the
adapter by the DHCP server and verify the connection.
4. In your web browser, enter the IP address of the adapter.
The web server home page displays.

Disable Web Server in DHCP mode

Before you begin, verify that you have an active DHCP server on your network.
1. Set the switches to 901 and cycle power to the adapter.
The module LED flashes red and the four-character status display scrolls
the message “Web Server Disabled”.
2. Set the switches to 999 and cycle power to the adapter.
3. In RSLinx software, check the IP address that was assigned to the
adapter by the DHCP server and verify the connection.
4. In your web browser, enter the IP address of the adapter.
The web server home page does not display.

Enable Web Server in User-set IP mode


1. Set the switches to 000 and cycle power to the adapter.
The module LED flashes red and the four-character status display scrolls
the message “Web Server Enabled”.
2. Set the switches to 999 and cycle power to the adapter.
3. In RSLinx software, change the Port Configuration setting to “Manual
IP”, set the desired IP address, and cycle power to the adapter.
4. In your web browser, enter the IP address of the adapter.
The web server home page displays.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 17


Chapter 2 Install Your Adapter

Disable Web Server in User-set IP mode


1. Set the switches to 901 and cycle power to the adapter.
The module LED flashes red and the four-character status display scrolls
the message “Web Server Disabled”.
2. Set the switches to 999 and cycle power to the adapter.
3. In RSLinx software, change the Port Configuration setting to “Manual
IP”, set the desired IP address, and cycle power to the adapter.
4. In your web browser, enter the IP address of the adapter.
The web server home page does not display.

Determine Power The Ethernet adapter requires 5V DC with current consumption of 470 mA.
Requirements The power is supplied through backplane from SLC power supply. Remember
to consider this requirement when planning your system configuration.

Install the Adapter Module After you set the appropriate switch assemblies for your adapter module,
in the Chassis follow these procedures for installation.

See the Industrial Controller Wiring and Grounding Guidelines publication


1770-4.1 for proper grounding and wiring methods to use when installing your
module.
1. Remove power from the I/O chassis before inserting (or removing) the
module.
2. Align the circuit board with the chassis card guide in the left slot.

3. Install the module in slot 0 of the chassis by aligning the circuit board
with the chassis card guide.
The 1747-AENTR module must be installed only in slot 0 (leftmost slot)of
the chassis.

18 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 2 Install Your Adapter

4. Press firmly and evenly to seat the module in its backplane connectors.
To remove the module, press the releases at the top and bottom of the
module and pull it out.

ATTENTION: Do not force the module into the backplane connector. If you
cannot seat the module with firm pressure, check the alignment. Forcing the
module can damage the backplane connector or the module.

Connect Your Adapter to Connect your 1747-AENTR adapter module to an Ethernet/IP network as
the Ethernet/IP Network shown in the following example:

through RJ-45 Connection Wire the RJ-45 connectors as shown.

Signal
1 TxData+
2 TxData-
3 Recv Data+
4 Reserved
5 Reserved
6 Recv Data-
7 Reserved
RJ-45
8 Reserved

1 8
RJ-45 connectors
8 1

45844

1747-AENTR module bottom view

To connect the module to the network, follow these steps:

WARNING: If you connect or disconnect the communication cable with power


applied to this module or any device on the network, an electrical arc can occur.
This could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.
1. Attach the cables with the RJ-45 connectors to the two Ethernet ports on
the bottom of the module.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 19


Chapter 2 Install Your Adapter

2. Attach the other end of the cables to the devices in your network.

IMPORTANT To install systems with rack extensions, you can see the SLC 500
Modular Hardware Style User Manual, publication 1747-UM011.

Chapter Summary This chapter provided instructions on how to install and wire the module. It
also included power requirements for the module.

20 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 3

Configure the Adapter for Your


EtherNet/IP Network

Before using your adapter in an EtherNet/IP network, you need to configure it


with an IP address, subnet mask, and optional Gateway address. This chapter
describes these configuration requirements and the procedures for providing
them. Here are ways you can do this:
• Use the Rockwell Automation BootP/DHCP utility, version 2.3 or later,
that ships with RSLogix 5000 or RSLinx software.
- You can also use this utility to reconfigure a device with an IP address
you must change.
• Use a third party DHCP server.
• Use the Network Address rotary switches.
• Have your network administrator configure the adapter via the network
DHCP server.

See the table for a list of where to find information in this chapter.
Topic Page
Configuration Requirements 21
Use the Rockwell Automation BootP/DHCP Utility 24
Use DHCP Software to Configure Your Adapter 26

Configuration Before you can use your adapter, you must configure its IP address, its subnet
Requirements mask, and, optionally, a gateway address. You can use the
Rockwell Automation BootP utility, version 2.3 or later, to perform the
configuration. You can also use a DHCP server or the network address
switches to configure these parameters.

If you need to reset the adapter to factory defaults, see Work with the
Configuration Pages on page 68.

IP Address
The IP address identifies each node on the IP network, or system of connected
networks. Each TCP/IP node on a network, including the adapter, must have a
unique IP address.

The IP address is 32 bits long and has a Network ID part and Host ID part.
Networks are classified A, B, C, or other. The class of the network determines
how an IP address is formatted.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 21


Chapter 3 Configure the Adapter for Your EtherNet/IP Network

0 7 8 31
Class A 0 Network ID Host ID
0 15 16 31
Class B 10 Network ID Host ID

0 23 24 31
Class C 110 Network ID Host ID

You can distinguish the class of the IP address from the first integer in its
dotted-decimal IP address as follows:
Range of first
Range of first integer Class Class
integer
0 1…27 A 192…223 C
128…191 B 224… 255 Other

Each node on the same physical network must have an IP address of the same
class and must have the same network ID. Each node on the same network
must have a different Host ID thus giving it a unique IP address.
IP addresses are written as four decimal integers (0…255) separated by periods
where each integer gives the value of one byte of the IP address.

EXAMPLE For example, the 32-bit IP address:


10000000 00000001 00000000 00000001 is written as 128.1.0.1

Gateway Address
This section applies to multi-network systems. If you have a single network
system, refer to the next section.

The Gateway Address is the default address of a network. It provides a single


domain name and point of entry to the site. Gateways connect individual
physical networks into a system of networks.

When a node needs to communicate with a node on another network, a


gateway transfers the data between the two networks. The figure shows
gateway G connecting Network 1 with Network 2.

128.1.0.1

Network 1 128.1.0.2

B C

128.2.0.1 128.2.0.2 128.2.0.3

Network 2

When host B with IP address 128.2.0.1 communicates with host C, it knows


from C’s IP address that C is on the same network. In an Ethernet
environment, B can then resolve C’s IP address into a hardware address (MAC
address) and communicate with C directly.

When host B communicates with host A, it knows from A’s IP address that A is
on another network (the network IDs are different). In order to send data to A,

22 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 3 Configure the Adapter for Your EtherNet/IP Network

B must use the IP address of the gateway connecting the two networks. In this
example, the gateway’s IP address on Network 2 is 128.2.0.3.

The gateway has two IP addresses (128.1.0.2 and 128.2.0.3). The first must be
used by hosts on Network 1 and the second must be used by hosts on Network
2. To be usable, a gateway of a host must be addressed using a network ID
matching its own.

Subnet Mask
The subnet mask is used for splitting IP networks into a series of subgroups, or
subnets. The mask is a binary pattern that is matched up with the IP address to
turn part of the Host ID address field into a field for subnets.

EXAMPLE Take Network 2 (a Class B network) in the previous example and add
another physical network. Selecting the following subnet mask would
add two additional network ID bits, allowing for four physical networks:
11111111 11111111 11000000 00000000 = 255.255.192.0
These two bits of the Host ID are
used to extend the netdwork ID.

Two bits of the Class B host ID are used to extend the network ID. Each unique
combination of bits in the part of the Host ID where subnet mask bits are 1
specifies a different physical network.

The new configuration is:

128.1.0.1
Network 1 128.1.0.2
G

B C
128.2.64.3

128.2.64.1 128.2.64.2
Network 2.1

G2
D E
128.2.128.3

128.2.128.1 128.2.128.2
Network 2.2

A second network with Hosts D and E was added. Gateway G2 connects


Network 2.1 with Network 2.2.

Hosts D and E will use Gateway G2 to communicate with hosts not on


Network 2.2.

Hosts B and C will use Gateway G to communicate with hosts not on


Network 2.1.

When B is communicating with D, G (the configured Gateway for B) will route


the data from B to D through G2.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 23


Chapter 3 Configure the Adapter for Your EtherNet/IP Network

Use the The Rockwell Automation BootP/DHCP utility is a standalone program that
Rockwell Automation incorporates the functionality of standard BootP software with a user friendly
graphical interface. It is located in the Utility directory on the RSLogix 5000
BootP/DHCP Utility software installation CD. The adapter must have DHCP enabled (factory
default and the network address switches set to an invalid value) to use the
utility.

To configure your adapter using the BootP utility, perform the following steps:
1. Run the BootP software.
In the BOOTP Request History panel you see the hardware addresses of
devices issuing BootP requests.

2. Double-click the hardware address of the device you want to configure.


The New Entry dialog appears with the device’s Ethernet Address (MAC).

3. Enter the IP Address you want to assign to the device and click OK. The
device is added to the Relation List, displaying the Ethernet Address

24 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 3 Configure the Adapter for Your EtherNet/IP Network

(MAC) and corresponding IP Address, Hostname, and Description (if


applicable).

When the address displays in the IP Address column in the Request


History section, the IP address assignment has been made.
4. To make this configuration static in the device, highlight the device in
the Relation List panel, and click the Disable BOOTP/DHCP button.
When power is cycled to the device, it uses the configuration saved in
non-volatile memory and will not issue a DHCP request.
5. To enable DHCP for a device with DHCP disabled, highlight the device in
the Relation List, and click the Enable DHCP button.
You must have an entry for the device in the Relation List panel to re-
enable DHCP.

Save the Relation List


You can save the Relation List for later use. To save the Relation List, perform
the following steps:
1. Select Save As... from the File menu.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 25


Chapter 3 Configure the Adapter for Your EtherNet/IP Network

The Save As dialog appears.

2. Select the folder where you want to save the Relation List.
3. Enter a File name for the Relation List, for example, control system
configuration, and click Save.
You can leave the Save as type at the default setting: Bootp Config Files
(*.bpc).
You now have the option to open the file containing the Relation List at a
later session.

Use DHCP Software to DHCP (Dynamic Host Configuration Protocol) software automatically assigns
Configure Your Adapter IP addresses to client stations logging onto a TCP/IP network.

DHCP is based on BootP and maintains some backward compatibility. The


main difference is that BootP was designed for manual configuration, while
DHCP allows for dynamic allocation of network addresses and configurations
to newly attached devices.

Be cautious about using DHCP software to configure your adapter. A DHCP


server typically assigns a finite lease time to the offered IP address.
When 50% of the leased time has expired, the adapter attempts to renew its IP
address with the DHCP server.
The possibility exists that the adapter will be assigned a different IP address,
which would cause the adapter to cease communicating with the ControlLogix
controller.

See Configure the Adapter with Fixed IP Address on page 45 to configure the
adapter with a fixed IP address.

ATTENTION: To avoid unintended control or loss of control, the I/O adapter


must be assigned a fixed IP address. A dynamically provided IP address
should be used only at initial configuration. If a DHCP server is used, it must
be configured to assign the same IP address to your adapter.
Failure to observe this precaution may result in unintended machine motion
or loss of process control.

Chapter Summary This chapter described the requirements and procedures for configuring the
IP address, subnet mask, and optional Gateway address.

26 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 4

Plan to Use Your EtherNet/IP Adapter

This chapter explains how the adapter operates on Ethernet and provides
information to assist you in configuring your system. This includes
information on:
• compatible 1746 and 1747 modules
• overview of adapter operation
• software requirements
• module connections
• module keying
• output operation during Fault and Idle modes

Compatible 1746 and The majority of 1746 and 1747 discrete, analog and specialty modules are
1747 I/O Modules compatible with the 1747-AENTR adapter.
The following tables provide lists of supported and unsupported modules.
List of I/O Modules Supported by the 1747-AENTR Adapter
Catalog Type Catalog Number Type
Number
1746-BAS BASIC Module 1746-OBP8 DC Digital Output Module
1746-BAS-T BASIC-T Module 1746-OG16 DC Digital Output Module
1746-IA4 AC Digital Input Module 1746-OV8 DC Digital Output Module
1746-IA8 AC Digital Input Module 1746-OV16 DC Digital Output Module
1746-IA16 AC Digital Input Module 1746-OV32 DC Output Module
1746-IB8 DC Digital Input Module 1746-OVP16 DC Digital Output Module
1746-IB16 DC Digital Input Module 1746-OW4 AC/DC Relay Output Module
1746-IB32 DC Input Module 1746-OW8 AC/DC Relay Output Module
1746-IC16 DC Digital Input Module 1746-OW16 AC/DC Relay Output Module
1746-IG16 DC Digital Input Module 1746-OX8 AC/DC Relay Output Module
1746-IH16 DC Digital Input Module 1746-FIO4I Analog Combination Module
1746-IM4 AC Digital Input Module 1746-FIO4V Analog Combination Module
1746-IM8 AC Digital Input Module 1746-INT4 Thermocouple Isolated Input Module
1746-IM16 AC Digital Input Module 1746-NI4 Analog Input Module
1746-IN16 AC/DC Digital Input Module 1746-NI8(1) Analog Input Module
1746-IO4 Digital Combination Module 1746-NIO4I Analog Combination Module
1746-IO8 Digital Combination Module 1746-NIO4V Analog Combination Module
1746-IO12 Digital Combination Module 1746-NO4I Analog Output Module
1746-IO12DC Digital Combination Module 1746-NO4V Analog Output Module
1746-ITB16 DC Digital Input Module 1746-NR4 RTD/Resistance Input Module
1746-ITV16 DC Digital Input Module 1746-NT4 Thermocouple/mV Input Module
1746-IV8 DC Digital Input Module 1746-NI16V(1) Analog Input Module
1746-IV16 DC Digital Input Module 1746-NI16I(1) Analog Input Module
1746-IV32 DC Digital Input Module 1746-NR8(1) RTD/Resistance Input Module

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 27


Chapter 4 Plan to Use Your EtherNet/IP Adapter

List of I/O Modules Supported by the 1747-AENTR Adapter (Continued)


Catalog Type Catalog Number Type
Number
1746-OA8 AC Digital Output Module 1746-NT8 Thermocouple/mV Input Module
1746-OA16 AC Digital Output Module 1746-NO8I(1) Analog Output Module
1746-OAP12 AC Digital Output Module 1746-NO8V(1) Analog Output Module
1746-OB6EI DC Digital Output Module 1746-HSTP1 Stepper Controller Module
1746-OB8 DC Digital Output Module 1746-HSCE(2) High-Speed Counter Module
Multi-Channel High-Speed Counter
1746-OB16 DC Digital Output Module 1746-HSCE2(1) Module
1746-OB16E DC Digital Output Module 1746-QS(2) Synchronized Axes Control Module
1746-OB32 DC Digital Output Module 1746-OBP16 DC Digital Output Module
1746-OB32E DC Digital Output Module
(1) This module supports multiple operating classes. The 1747-AENTR adapter automatically promotes multiclass modules to the
highest supported class. The 1746-NI16I, 1746-NI16V, 1746-NR8, 1746-NI8, 1746-NO8I, 1746-NO8V modules are promoted from
class 1 to class 3. The 1746-HSCE2 module is promoted from class 1 to class 4.
(2) This specialty module uses Advanced module connection. Refer to the User Manual specific to the I/O module to learn about
its connection configuration requirements.

List of I/O Modules NOT Supported by the 1747-AENTR Adapter


Catalog Number Type
1746-HSRV Servo Control Module
1746-BTM(1) Barrel Temperature Module
1747-DCM1(1)
1747-DCM2(1)
Direct Communication Modules
1747-DCM3(1)
1747-DCM4(1)
1747-KE/A(1)
DH-485/RS-232C Interface Modules
1747-KE/B(1)
1747-KFC15 ControlNet to RS-232C Interface Module
1747-SDN/D(1) DeviceNet® Scanner module
(1) ControlNet Scanner module
1747-SCNR
1747-SN Remote I/O Scanner Module
1747-BSN(2) Back-Up Remote I/O Scanner Module
1746-QV Open Loop Velocity Control Module
1746-BLM Blow Molding Module
1746-MPM Mold Pressure Module
1203-SM1(1) Scanport Module (Class 4 operation)
(1) The module is not supported by the 1747-AENTR but appears in the RSLogix
5000 pick list (Select Module Type dialog).
(2) The 1747-AENTR is not designed for redundancy support.

IMPORTANT Any 1746/1747 module that is not included in the lists of supported and
unsupported modules is not supported by the 1747-AENTR, as of the
date of writing of this User Manual.
Consult the manufacturer of any third party module to determine if the
module is supported by the 1747-AENTR adapter.

28 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 4 Plan to Use Your EtherNet/IP Adapter

Overview of Adapter As a gateway between the SLC backplane and EtherNet/IP, the 1747-AENTR
Operation module serves as a CIP server (for both Explicit Messaging and I/O) on the
Ethernet port, and an SLC host on the 1746 backplane. Connections can be
made to supported I/O modules installed in the backplane. See List of I/O
Modules Supported by the 1747-AENTR Adapter on page 27.

The module employs the Rockwell Automation Embedded Switch Toolkit. This
implementation is an IEEE 802.3 standard compliant, Layer 2 switch that is
compatible with the IEEE 802.1 ID standard. It has three ports: two are
external ports that function as physical ports of the product and one is an
internal port that connects to the host CPU. Each of the three ports has an
IEEE 802.3 compliant MAC and the ports are interconnected with each other
through full wire speed, non-blocking switching logic. The Embedded Switch
Toolkit provides support for the EtherNet/IP DLR protocol.

The adapter only supports direct connection to individual modules. Up to 96


connections per adapter are possible with a maximum of 240 words supported
per connection on firmware revision 2.001 and Logix Designer application
revision 21. The input data attributes correspond directly to the read area of
the I/O module’s data table image. The output attributes correspond directly to
the write area of the I/O module’s data table image.

IMPORTANT On firmware revision 1.001 and RSLogix 5000 revision 20, the adapter
only supports up to 32 connections per adapter, with a maximum of 240
words supported per connection.

Communication between the 1747-AENTR module and the I/O modules is


polled, similar to an SLC controller scan cycle. The adapter maintains a list of
the module ID for each slot, and handles electronic key validation during
connection requests, while processing ForwardOpen requests to the
Connection Manager.

Software Requirements
RSLogix 5000 revision 20 or greater and RSLinx version 2.59 or greater are
required to configure the 1747-AENTR adapter. For more information on how
to configure your device, see Configure the Adapter for Direct Connection
through the RSLogix 5000 or Logix Designer Application on page 33.

IMPORTANT Logix Designer application (previously RSLogix 5000) revision 21 and


later supports direct connections to more than 13 slots.

Module Connections
The 1747-AENTR adapter supports module connections.

Module connection is performed in a deterministic and repeatable manner.


This connection allows a memory and Ethernet bandwidth efficient way to
connect to individual modules.

Each connection can be configured with the following connection types:


1. Exclusive Owner – specifies an independent connection where a single
device controls the output states in the target device. If you have an
existing Exclusive Owner connection to a target device, you cannot
specify another Exclusive Owner or Redundant connection to that same
target device.
The 1747-AENTR adapter supports one Exclusive Owner connection per
SLC module.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 29


Chapter 4 Plan to Use Your EtherNet/IP Adapter

2. Input Only – specifies an independent connection where a device


receives inputs from the target device and sends configuration data to
the target device. An Input Only connection does not send outputs; it
only receives inputs. You can specify multiple Input Only connections to
the target device from different originators.
The 1747-AENTR adapter supports up to five Input Only connections per
SLC module.
3. Listen Only – specifies a dependent connection where a device receives
inputs from the target device, but does not send configuration data with
the target device. A Listen Only connection only functions properly when
another non-Listen Only connection exists to the same target device. A
Listen Only connection does not send outputs; it only receives inputs.
You can specify multiple Listen Only connections to the target device
from different originators.
The 1747-AENTR adapter supports up to five Listen Only connections per
SLC module.

IMPORTANT When a Listen Only connection is made, there must be an


existing Exclusive Owner or Input Only connection, the
connection RPIs must match exactly, the input chunk
configuration (if any) must match exactly, and all connections to
the same module must be Multicast.
Note that changing a module connection from Input Only to
Listen Only will result to the following:
• reset the RPI to 20 ms
• reset the input chunk configuration (if any) to the default
• set the Input Type to Unicast
All Listen Only connections are terminated when all associated independent
connections are terminated.

Module Keying
Missing or misplaced modules are detected if the module in question is
configured with RSLogix 5000 or Logix Designer application as an individual
module connection and “compatible module” is selected for electronic keying.
If a module connection is attempted to a module which is a missing or
misplaced module, the connection will fail.

Output Operation During Fault and Idle Modes


RSLogix 5000 or Logix Designer application allows configuration to
characterize each module connection activity during certain operational
states.

During idle mode and fault modes, outputs are configured for one of the
following operation states:
Output Action
Reset outputs to off
Hold last state
Write Safe State data to outputs

For comprehensive information about Ethernet/IP networks, consult the


following resources:
• Ethernet Reference Manual, publication ENET-RM002
• EtherNet/IP Network Devices User Manual, publication ENET-UM006

30 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 4 Plan to Use Your EtherNet/IP Adapter

Chapter Summary This chapter provided an overview of adapter operation on an EtherNet/IP


network that can assist you in configuring your system.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 31


Chapter 4 Plan to Use Your EtherNet/IP Adapter

Notes:

32 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 5

Configure the Adapter for Direct Connection


through the RSLogix 5000 or Logix Designer
Application

Overview In the following example, a ControlLogix controller communicates with I/O


modules through the adapter using a direct connection.

The adapter makes a direct connection to each of the modules referenced by


the data. The modules presented in this chapter use RSLogix 5000/Logix
Designer application, revision 20 or later.
Topic Page
Set Up the Hardware 33
Create the Example Application 34
Configure the I/O 35
Add the Local EtherNet/IP Bridge to the I/O Configuration 35
Add the Adapter to the I/O Configuration 37
Add I/O Modules to the I/O Configuration 39
Download the Program to the Controller 46
Custom Settings (Edit Adapter Configuration) 47
Custom Settings for your I/O Module 50

IMPORTANT The steps and screenshots used in this chapter refer to the RSLogix
5000 software, which has since been renamed to Logix Designer
application.
The configuration process in the Logix Designer application follows the
same steps as the configuration process in RSLogix 5000.

IMPORTANT The 1747-AENTR device should always be installed in Slot 0. There


should only be one 1747-AENTR device installed within the same rack or
its connected rack extensions for multiple chassis support.

Set Up the Hardware In this example, a ControlLogix chassis contains the Logix5575 controller in
slot 1 and a 1756-EN2TR bridge module in slot 3. The 1747-AENTR adapter is
mounted on an SLC chassis in slot 0, with a 1746-IO8 input module in slot 1, a
1746-IA4 module in slot 2, a 1746-BAS/B module in slot 3, and a power supply.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 33


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

To work along with this example, set up your system as shown in the figure.
1747-AENTR
10.88.70.2
Slot 0 1 2 3

Local Data
chassis
Slot 0 1 2 3 1746-BAS/B
1746-IA4
1756-EN2TR
Logix5575 1746-IO8
10.88.70.4 (slot 3)
controller (slot 1)
Switch

10.88.70.26

Programming
terminal

45176

• In the example application, we assume that the Logix5575 controller and


1756-EN2TR module (firmware revision 3.1, or later) are in the slots
shown in the figure.
• Verify the IP addresses for your programming terminal, 1756-EN2TR
module, and adapter.
• Verify the position (slot) of the I/O modules on the DIN rail.
• Verify that you connected all wiring and cabling properly.
• Be sure you configured your communication driver (for example,
AB_ETH-1 or AB-ETHIP-1) in RSLinx software, as described in Configure
the AB_ETH/IP Driver on page 73.

Create the Example Perform the following steps to create the example application:
Application 1. Start RSLogix 5000 Enterprise Series software to open the RSLogix 5000
software main dialog.
2. From the File menu, select New.

34 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

3. The New Controller dialog opens.

• Enter an appropriate Name for the Controller.


• Select the correct Chassis Type, and Slot number of the Logix5575
controller, and the folder where you want to save the RSLogix 5000 file
(Create In). The Description is optional.
4. Click OK.

Configure the I/O Setting up a sample I/O Configuration project involves the following:
• Adding the local 1756-EN2TR module to the I/O configuration.
• Adding the 1747-AENTR adapter as a child of the 1756-EN2TR module on
the Ethernet network.
• Adding I/O modules as children of the 1747-AENTR adapter.

IMPORTANT Click the Help button on the configuration dialogs shown in this section
if you need assistance in selecting and setting the parameters.

Add the Local EtherNet/IP Bridge to the I/O Configuration


1. Right-click the I/O Configuration folder in the project dialog, and choose
New Module from the dropdown list.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 35


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

The Select Module Type dialog opens.

2. Select the 1756-EN2TR EtherNet/IP Bridge and click Create.


3. The New Module dialog opens. Configure your 1756-EN2TR
EtherNet/IP Bridge module. You can configure the bridge module
through the different tabs available.

4. Enter values for Name, IP Address, Slot, Electronic Keying, and Revision,
noting that we used the following values:
Name EN2TR
IP Address 10.88.70.4
Slot 3
Electronic Keying Compatible Module
Revision 3.1

5. Click OK to accept the configuration.

36 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

Add the Adapter to the I/O Next, you must add the 1747-AENTR adapter as a child of the local
Configuration 1756-EN2TR module.
1. In the Project dialog, right-click the local 1756-EN2TR module under the
I/O Configuration folder, and select New Module.

The Select Module Type dialog opens.

2. Choose 1747-AENTR. Click Create.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 37


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

3. The Module Properties dialog opens. Specify the properties of the


adapter.

Note that for the purposes of illustration we have specified the following
properties in the General tab of the New Module dialog.
Name TEST_1747AENTR
IP Address 10.88.70.2
Slot 0

IMPORTANT The Slot field appears grey because the slot is automatically 0
for the 1747-AENTR adapter.
4. Click Change...
The Module Definition dialog opens.

5. Choose values for Chassis Size, Electronic Keying and Revision, noting
that we used the following values for our example:
Connection None (only choice available)
Chassis Size 4
Electronic Keying Compatible Module
Revision 1.1

IMPORTANT The chassis size value equals 1 (for the adapter) plus the number
of I/O modules installed or physically present on the I/O
backplane.

38 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

Connection is None by default because we are only making direct


connections.
6. Click OK to accept the configuration.
The name of your adapter appears under the Ethernet folder.

Add I/O Modules to the I/O Configuration


First, check the List of I/O Modules Supported by the 1747-AENTR Adapter on
page 27, to see if your I/O module is supported by the adapter.

Then, add the I/O module to the I/O Configuration List under the adapter.

In this example, you add a 1746-IO8 and a 1746-IA4 module with standard
configurations. Use these steps as a guide when configuring different I/O
modules for your system.
This example application uses I/O module default configurations. For more
information, refer to the SLC 500 Systems Selection Guide, publication 1747-SG001.
1. Right-click the name of the 1747-AENTR adapter under the
I/O Configuration folder and select New Module.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 39


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

The Select Module Type dialog opens.

2. Select the 1746-IO8 module from the list and click Create.
The New Module dialog opens.

3. Enter values for Name and Slot, noting that we used the following values.
Name TEST_1746IO8
Slot 1

4. Select the Connection tab.


The RPI is selectable since it is a direct connection.

40 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

5. Enter 50 for requested packet interval (RPI) to set how often you
exchange data with the I/O adapter.

IMPORTANT The default RPI of 20 ms is suitable for typical applications.


Rockwell Automation recommends that you check or enable the option
“Major Fault On Controller If Connection Fails While in Run Mode” on both the
1747-AENTR device and supported 1746 I/O modules.
6. Click OK to save the configuration.
The module now appears under the I/O Configuration tree.

To add 1746-IA4 module to the project, follow the same procedure.


After adding 1746-IA4, the I/O Configuration tree should appear as
follows:

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 41


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

Add Specialty I/O Modules using Advanced Connection


The previous example illustrates how to add I/O modules that use Simple
connection. This section shows how to add and configure a specialty I/O
module with Advanced connection (in this example, 1746-BAS/B).

IMPORTANT Consult the User Manual and related documentation for your I/O module
to help you specify required values during configuration. User Manuals
and other related publications for 1746/1747 modules are available in
the Rockwell Automation Literature Library: rok.auto/literature
For the 1746-BAS/B module, for example, you can see the following
publications to get module-specific configuration information:
• SLC 500 BASIC and BASIC-T Modules User Manual,
publication 1746-UM004
• BASIC Language Reference Manual, publication 1746-RM001

Follow these steps to add and configure your 1746-BAS/B module.


1. In the I/O Configuration tree, right-click SLC Chassis or 1747-AENTR and
choose New Module...

2. On the Select Module Type dialog that appears, select 1746-BAS/B and
click Create.
3. Enter a name for the device.

42 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

Note that the following values are used in this example.


Field Value
Name TEST_1746BASB
Revision 2.1
Electronic Keying Compatible Module (default)
Connections Exclusive Owner – Advanced (default)

4. Click Change... on the General tab.

On the Module Definition screen, configure data type as INT,


Input Size = 72 (INTs), Output Size = 72 (INTs). The Input Size should
match the total size of all three Input Chunks. The Output Size should
match the total size of all three Output Chunks. If the I/O sizes are larger
than the chunk totals, the adapter will reject the connection request. If
the chunk totals are larger than the I/O sizes, the adapter will accept the
connection (but the backplane scan may waste cycles reading input data
that will never be used).
5. Click OK on the Module Definition screen. Then, click Yes on the RSLogix
5000 change confirmation screen that appears.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 43


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

6. Click Connection tab. Enter 50 for requested packet interval (RPI) to set
how often you exchange data with the I/O adapter.
Note that Connection is set as Exclusive Owner - Advanced by default.

IMPORTANT The default RPI of 20 ms is suitable for typical applications.


Rockwell Automation recommends that you check or enable the option
“Major Fault On Controller If Connection Fails While in Run Mode” on both the
1747-AENTR device and supported 1746 I/O modules.
7. Click Configuration tab.

The Chunk configuration determines the 1747-AENTR SLC backplane


scan. Set up the chunks as follows:
• Output Chunk 1
- Size = 8 (number of Output INTs to scan)
- File = Output File
- Offset = 0 (starting INT offset in Output File)

44 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

• Output Chunk 2
- Size = 64 (number of M0 INTs to scan)
- File = M0 File
- Offset = 0 (starting INT offset in M0 File)

• Output Chunk 3
- Size = 0
- File = <Don’t Care>
- Offset = 0
• Input Chunk 1
- Size = 8 (number of Input INTs to scan)
- File = Input File
- Offset = 0 (starting INT offset in Input File)

• Input Chunk 2
- Size = 64 (number of M1 INTs to scan)
- File = M1
- Offset = 0 (starting INT offset in M1 File)

• Input Chunk 3
- Size = 0
- File = <Don’t Care>
- Offset = 0
8. Click OK to save the configuration.
9. On the Controller Organizer window, right-click Controller Tags under
the Controller <name> folder. Select Monitor Tags.

10. Examine the tags created for 1746-BAS/B.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 45


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

• TEST_1747AENTR:3:I.Data[0-7] represents Input File data (Input


Chunk #1).
• TEST_1747AENTR:3:I.Data[8-71] represents M1 file data (Input Chunk
#2).
• TEST_1747AENTR:3:O.Data[0-7] represents Output File data (Output
Chunk #1).
• TEST_1747AENTR:3:O.Data[8-71] represents M0 file data (Output
Chunk #2).
After adding the 1746-BAS/B module, the I/O Configuration tree should
appear as follows:

Download the Program to Follow this procedure to download the program you just saved to the
the Controller ControlLogix controller.
1. From the main menu, choose Communications>Who-Active.
The Who Active dialog opens.

2. Navigate to select the slot where the controller is located in the chassis.
3. Choose Set Project Path.
4. Choose Download.
The Download dialog opens with a reminder of the following.
• The controller is in Remote Run mode.

46 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

• The mode changes to Remote Program prior to download.

5. On the Download dialog, choose Download.


The RSLogix 5000/Studio 5000® software dialog opens.

Notice that the 1756-EN2TR Bridge is now online.

Custom Settings (Edit You have now built the I/O Configuration tree in the RSLogix 5000 software.
Adapter Configuration) You can edit the configuration of the 1747-AENTR adapter through the Module
Properties screen.

The RSLogix 5000 software automatically creates module-defined data types


and tags when a module is created. This section describes how to modify the
default configuration.

Data types symbolically name module configuration, input and output data.
Tags let you provide each a unique name, such as where the user-defined data
type and slot reside on the controller. This information is used to
communicate data between the controller and module.

Follow these steps to modify the default adapter configuration.


1. In the Project dialog, right-click the 1747-AENTR adapter under I/O
Configuration.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 47


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

2. Select Properties. The following tabs are available for configuration.


Tabs can be selected in any order. The following examples are for
instructional purposes.

3. Click the Connection tab.


Choose from the options in the Connection tab. Note that RPI is not
applicable and is left blank.
Connection Tab Options
Field Name Description
Requested Packet Interval (RPI) RPI is not applicable and is grayed out.
Check the box to prevent communication between the owner-
Inhibit module controller and the module. This option allows for maintenance of
the module without faults being reported to the controller.
Major fault On Controller If Connection Check the box to create a major fault if there is a connection
Fails While in Run Mode failure with the module while in Run mode.
The fault box is empty if you are offline. The type of connection
Module Fault fault appears in the text box if a fault occurs when the module is
online.

Rockwell Automation recommends that you check or enable the option


“Major Fault On Controller If Connection Fails While in Run Mode” on both the
1747-AENTR device and supported 1746 I/O modules.
4. To configure your IP settings, click the Internet Protocol tab. This tab is
only available for editing when the device is online.

48 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

To manually configure your IP settings, specify the IP address in the


Physical Module IP Address field.

5. On the other fields (Domain Name, Host Name, Primary DNS Server
Address, Secondary DNS Server Address), specify the corresponding
parameter. Click Set and then click OK.
To learn more about how to configure the adapter’s IP settings, see
Configure the Adapter for Your EtherNet/IP Network on page 21.
6. To configure the Ethernet ports, click the Port Configuration tab.
This tab is only available for editing when the device is online.

To configure the ports:


To Then
Use the default port speed and duplex Leave Auto-negotiate port speed and duplex checked.
settings This setting determines the actual speed and duplex setting.
Follow these steps.
1. Clear the Auto-negotiate port speed and duplex checkbox.
Manually configure your port’s speed and 2. From the Current Port Speed pull-down menu, choose a port
duplex settings speed.
3. From the Current Duplex pull-down menu, choose the
appropriate Duplex value, that is, Half Duplex or Full Duplex.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 49


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

IMPORTANT Consider the following when you configure the module’s port
settings:
• If the module is connected to an unmanaged switch, leave Auto-
negotiate port speed and duplex checked or the module will fail.
• If you are forcing the port speed and duplex with a managed
switch, the corresponding port of the managed switch must be
forced to the same settings or the module will fail.
7. Click OK.

Custom Settings for your


I/O Module IMPORTANT To fully customize the settings of your I/O module, consult the User
Manual for your module. User Manuals and other reference publications
for 1746/1747 modules are available in the Rockwell Automation
Literature Library: rok.auto/literature
You can edit the default configuration of your 1746/1747 module through the
Module Properties dialog available in RSLogix 5000.
1. On the I/O Configuration tree for your project in RSLogix 5000,
right-click the name of your I/O module.

2. Select Properties. The Module Properties dialog appears and has the
following tabs available for configuration.

Note that for certain I/O modules, the Configuration tab may not be
available.
3. Click Change... on the General tab to access the Module Definition dialog
and edit the following information:
• Revision
• Electronic Keying
• Connections

50 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

1746-IO8 Module Definition shown

Module Definition Fields


Field Description
Revision Specifies the major and minor module revision.
The electronic keying feature automatically compares the expected module, as shown in
the RSLogix 5000 I/O Configuration tree, to the physical module before I/O communication
begins. You can use electronic keying to help prevent communication to a module that
does not match the type and revision expected.
For each module in the I/O Configuration tree, the user-selected keying option determines
if, and how, an electronic keying check is performed.
Typically, two keying options are available:
• Compatible Module
• Disable Keying

Electronic Keying

Compatible Module indicates that the module determines whether to accept or reject
communication. Compatible Keying is the default setting. It allows the physical module to
accept the key of the module configured in the software, provided that the configured
module is one the physical module is capable of emulating. The exact level of emulation
required is product and revision specific.
Disable Keying indicates the keying attributes are not considered when attempting to
communicate with a module. Other attributes, such as data size and format, are
considered and must be acceptable before I/O communication is established. With
Disabled Keying, I/O communication may occur with a module other than the type specified
in the I/O configuration tree with unpredictable results. We generally do not recommend
using Disabled Keying.
Defines the type of connection employed by the module. The following options are
available for non-specialty I/O modules:
• Exclusive Owner (default)
• Listen Only
• Input Only
For specialty I/O modules that require Advanced connections, the following connection
Connections options are available:
• Exclusive Owner – Advanced (default)
• Listen Only – Advanced
• Input Only – Advanced
To learn more about the different types of connections, see Module Connections on
page 29.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 51


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

4. Click the Connection tab.

The following information is available and can be configured in the


Connection tab.
Connection Tab Fields
Field Description
Specifies the type of connection for the module. Connection type is defined
in the Module Definition dialog (see previous step) and cannot be edited in
Name the Connection tab.
For more information about Exclusive Owner, Listen Only, and Input Only
connections, see Module Connections on page 29.
A user-defined rate at which the module updates the information sent to its
Requested Packet Interval (RPI) owner-controller.
This interval defines the slowest rate at which a module sends its data to the
(ms) owner-controller. The time ranges from 2.0…750 ms and is sent to the
module with all other configuration parameters.
Defines the input type, whether unicast or multicast, for data sent over the
network. The default input type is unicast.
Unicast connections are point to point transmissions between a source
node and destination node on the network. A Frame is sent to a single
destination.
Input type Multicast connections deliver information from one sender to multiple
receivers simultaneously. Copies of a single frame are passed to a selected
subset of possible destinations.
Note: The Input Type field cannot be updated for Listen Only and Input Only
connections.
Specifies the type of data update. Input trigger is cyclic by default. Data
transfer is initiated on a time basis as defined by the requested packet
Input trigger interval (RPI) value.
Note: This field cannot be edited on the Connection tab.
Check the box to prevent communication between the owner-controller and
Inhibit Module the module. This option allows for maintenance of the module without faults
being reported to the controller.
Major fault On Controller If
Connection Fails While in Run Check the box to create a major fault if there is a connection failure with the
module while in Run mode.
Mode
The fault box is empty if you are offline. The type of connection fault
Module Fault appears in the text box if a fault occurs when the module is online.

To edit the parameters in the Configuration tab, consult the User Manual
specific to your I/O module.

52 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

Online Monitoring Some of the screens that appear during initial module configuration process
are blank (such as Module Info and Network). These tabs provide device
information and status and can be important during online monitoring.

Status line indicates module fault

Chapter Summary This chapter provided instructions on how to configure the EtherNet/IP
adapter for direct connection through the RSLogix 5000 software.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 53


Chapter 5 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

Notes:

54 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 6

Troubleshoot with the Status Indicators

This chapter describes the different status indicators available in the 1747
EtherNet/IP Adapter and how to use them to troubleshoot the module.

Interpret the Indicators The module has the folowing status indicators:
• Module status indicator – indicates the state of the adapter.
• Four-character dot matrix status display – works in conjunction with the
Module status indicator to report normal operation and error conditions
in your module. It also displays the module IP address.
• Link 1 and Link 2 status indicator – indicates the port speed and activity
on Ethernet ports 1 and 2.

Four character display

Module status indicator

Link 1 and Link 2 status indictators

45847

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 55


Chapter 6 Troubleshoot with the Status Indicators

Status Indicators
Indicator State Description
Off No power applied to device
Green Device operating normally
Flashing green Device has not been configured
Recoverable fault.
Module • IP Address switches do not match configuration in use.
Flashing red • The device has completed a reset to factory default request
because the switches were set to 888 at power up, and a power
cycle is required.
• The device is performing a firmware flash update.
Red Unrecoverable fault, may require device replacement
Displays IP address and module status description.
Four-character Display See table, Four-character Status Display, for a description of all the
possible module status.
Off No link established.
Solid green Link established @ 100 Mbps.
Link 1 or Link 2 Flashing green Transmit or receive activity present on indicated port @ 100 Mbps.
Solid yellow Link established @ 10 Mbps.
Flashing yellow Transmit or receive activity present on indicated port @ 10 Mbps.

The four-character display indicates module status as shown in the table


below.
Four-character Status Display
Recommended
MOD LED Display Description Probable Cause Action
System startup
Red-green flash Module is performing
followed by Dotted display on Power On Self Test None None
Solid Red (POST)
“OK”
(The first scroll cycle
displays the software
Green revision in the format POST is successful None None
“Rev
majorRev.minorRev.su
bMinorRev”)
Document the error
The adapter has either
4-digit error hex code POST Failure codes. Power cycle
failed a hardware test, or
Red (For example, 0100 and (0100 = IOFPGA failure) the adapter.
gone into a state from
0101) (0101=ESFPGA failure) Contact Technical
which it cannot recover.Support.
Power off the
adapter. Remove
“OK” alternates with the the adapter from
Node switches have
message: the chassis. Change
been set to 888. The
“Factory Defaults Factory defaults the node address
Flashing Red AENTR remains in this
Restored. Change restored mode until the switches switch to something
Address Switches and other than 888.
are changed.
Reset.” Replace the adapter
in the chassis, and
apply power.
Runtime

56 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Chapter 6 Troubleshoot with the Status Indicators

Four-character Status Display (Continued)


Recommended
MOD LED Display Description Probable Cause Action
“OK” alternates with
“Port x baud/dpx”
where: Module is
x = port number 1 or 2 None None
communicating.
baud = Link rate, “10” or
“100”
dpx = “FULL” or “HALF”
Flashing green “OK” alternates with Module is not Ethernet port is not Connect Ethernet
“Port x down” communicating. connected. port.
“OK” alternates with Use RSLinx BootP-
“BOOTP DHCP server or set
Module is on network None
XX:XX:XX:XX:XX:XX” or IP statically with
waiting for IP address
“DHCP thumb wheel
XX:XX:XX:XX:XX:XX” switches.
The adapter has Correct the
“Duplicate IP Module is not detected a duplicate duplicate node to
XX:XX:XX:XX:XX:XX” communicating node address on the address problem.
network.
Adapter firmware is
“Flash update in Firmware update being updated via
None
Flashing red progress” mode ControlFlash update
utility
Ensure that you
Firmware update with have a valid
“Corrupt Certificate Firmware update invalid security security certificate
Received” failure certificate attempted. to download
firmware.
Make sure proper
Firmware update with ControlFLASH
“Corrupt Image Firmware update corrupt image has been update procedure is
Received” failure attempted. followed. Retry
update.
Module is
Solid green <IP address> communicating and None None
working properly.
The adapter has failed a Verify the correct
hardware test, number of I/O racks
discovered too many and power cycle the
Solid Red “0001” Fatal error racks (that is, greater adapter. Contact
than 3), or gone into a Technical Support if
state from which it problem persists.
cannot recover.

Chapter Summary This chapter described the different status indicators that can help you
troubleshoot the module.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 57


Chapter 6 Troubleshoot with the Status Indicators

Notes:

58 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Appendix A

Specifications

The 1747-AENTR has the following specifications, ratings, and certifications.


Ethernet Communication
Attribute Value
EtherNet communication rate 10/100 Mbits/s, half or full-duplex
Ethernet ports 2, configured as Embedded Switch
Ethernet network topologies supported Star, Tree, Daisy chain/Linear, and Ring
Ethernet connector RJ-45, Category 5
Ethernet cable Category 5: shielded or unshielded

General Specifications
Attribute Value
Module location Always at Slot 0 (leftmost slot) on chassis
Current consumption, backplane 470 mA @ 5V DC
Thermal dissipation 2.49 W = 8.4962 Btu (IT)/hour
Isolation voltage 50V (continuous), Basic Insulation Type
145.3 x 34.8 x 130.8 mm
Dimensions (HxWxD), approx. (5.72 x 1.37 x 5.15 in.)
Enclosure type rating None (open-style)
Wiring category(1) 1 – on communication ports
Weight, approx. 168 g (0.37 lb)
North American temp code T3C
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1.

Environmental Specifications
Attribute Value
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
Temperature, operating IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…60 °C (32…140 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
Temperature, nonoperating IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…+85 °C (-40…+185 °F)
Temperature, surrounding air, 60 °C (140°F)
max
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
Relative humidity 5…95% noncondensing
IEC 60068-2-6 (Test Fc, Operating):
Vibration 2.5g @ 57…2000Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Shock, operating 30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Shock, nonoperating 50 g
Emissions CISPR 11: Group 1, Class A

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 59


Appendix A Specifications

Environmental Specifications (Continued)


Attribute Value
IEC 61000-4-2:
ESD immunity 6 kV contact discharges
8 kV air discharges
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
IEC 61000-4-4:
EFT/B immunity ± 3 kV @ 5 kHz on communication ports
IEC 61000-4-5:
Surge transient immunity ± 2 kV line-earth(CM) on communication ports
IEC 61000-4-6:
Conducted RF immunity 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications
Certification
Value
(when product is marked)(1)
UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E322657.
c-UL-us UL Listed for Class I, Division 2 Group A, B, C, D Hazardous Locations, certified for
U.S. and Canada. See UL File E334470.
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
CE EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
Australian Radiocommunications Act, compliant with:
C-Tick AS/NZS CISPR 11; Industrial Emissions
EtherNet/IP ODVA conformance tested to EtherNet/IP specifications
Korean Registration of Broadcasting and Communications Equipment, compliant
KC with:
Article 58-2 of Radio Waves Act, Clause 3
(1) See the Product Certification link at rok.auto/certifications for Declaration of Conformity, Certificates, and other
certification details.

60 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Appendix B

Adapter Web Dialogs

Overview The Web dialog of the I/O adapter offers extensive internal and network
diagnostics. To view the Web dialogs, enter the IP address of the I/O adapters
into your browser.
Topic Page
Work with the Home Page 61
Work with the Diagnostics Pages 62
Use the Diagnostic Overview Page 63
Use the Network Settings Page 65
Use the Ethernet Statistics Page 66
Use the I/O Connections Page 67
Work with the Configuration Pages 68
Use the Device Identity Page 69
Use the Network Configuration Page 69
Use the Device Services Page 71

Work with the Home Page Use the adapter diagnostics home page to access other adapter diagnostics
web pages and see the following information.
• Host Name
• Module Description
• Module Location
• IP Address
• Ethernet Address (MAC)
• DHCP Enabled
• Product Revision
• Serial Number
• Status
• Auto Negotiate
• Media Speed
• Half or Full Duplex

To display and work with the adapter diagnostics home page, follow these
procedures.

IMPORTANT Make sure that your PC Internet LAN setting and your TCP/IP settings
are configured to access the subnet on which your adapter
communicates.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 61


Appendix B Adapter Web Dialogs

1. From your web browser, enter the adapter IP address to see the Home
page.
Enter the adapter IP address
to see the home page.

2. From the Home page, click Expand to show options, or minimize to see
Diagnostics and Configuration.

Click Expand to
show options.

3. From the Home page, complete one of these, as desired.


• Click one of the following to access www.ab.com.
- Allen-Bradley logo at the top of the page
• Click Rockwell Automation at the top right to go to
www.rockwellautomation.com.
• Click the following to see additional diagnostics web pages.
- Diagnostics – Diagnostic overview, Network Settings, Ethernet
Statistics, I/O Connections
- Configuration – Identity, Network, Services

Work with the Diagnostics To work with the Diagnostics options, follow these procedures.
Pages 1. From the Home page, click Diagnostics or Expand to see the following
diagnostics options from the panel at the left.
• Diagnostic Overview
• Network Settings
• Ethernet Statistics
• I/O Connections
2. In the Refresh Rate field, you can type a refresh rate, noting that the
default rate is 15 seconds.

62 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Appendix B Adapter Web Dialogs

3. From the panel at the left or tabs at the top of the page, click one of the
diagnostics options to see the corresponding page.

Click tabs to see the


corresponding page

Click Diagnostics options to


see corresponding pages

Type a refresh rate

Use the Diagnostic Overview Page


To use the Diagnostic Overview page for general diagnostics information,
follow this procedure.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 63


Appendix B Adapter Web Dialogs

1. Click Diagnostic Overview from the tab at the top of the page or panel on
the left.
The Diagnostic Overview page opens.

2. From the Diagnostic Overview page, you can view the following:
• Ring Status
- Network Topology
- Network Status
- Ring Supervisor

• System Resource Utilitization


- CPU Utilization
- Module Uptime

• CIP Connection Statics


- Current CIP MSG Connections
- CIP MSG Connection Limit
- Max Msg Connections Observed
- Current CIP I/O Connections
- CIP I/O Connection Limit
- Max I/O Connections Observed
- Conn Opens
- Open Errors
- Conn Closes
- Close Errors
- Conn Timeout

64 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Appendix B Adapter Web Dialogs

• Module Settings
- Switches

• SLC Backplane Statistics


- I/O Errors
- I/O Scans Completed
- Maximum Scan Time
- Average Scan Time

Use the Network Settings Page


To use the Network Settings page for network related information, follow this
procedure.
1. Click Network Settings tab at the top of the page or panel on the left.
This opens the Network Settings page.

2. From the Network Settings page, you can view the following:
• Network Interface
- Ethernet Address (MAC)
- IP Address
- Subnet Mask
- Default Gateway
- Primary Name Server
- Secondary Name Server
- Default Domain Name
- Host Name
- Name Resolution

• Ethernet Interface Configuration


- How the Network Configuration was obtained - Static or Dynamic

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 65


Appendix B Adapter Web Dialogs

• Ethernet Port 1 and 2


- Interface State
- Link Status
- Media Speed
- Duplex
- Autonegotiate Status

Use the Ethernet Statistics Page


To use the Ethernet Statistics page for information about the Ethernet link and
interface and media counters, use this procedure.
1. Click Ethernet Statistics tab at the top of the page or from the panel on
the left.
The Ethernet Statistics page opens.

2. From the Ethernet Statistics page, you can view the following:
• Ethernet Port 1 and Port 2
- Interface State
- Link Status
- Media Speed
- Duplex
- Autonegotiate Status

66 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Appendix B Adapter Web Dialogs

• Media Counters Port 1 and Port 2


- Alignment Errors
- FCS Errors
- Single Collisions
- SQE Test Errors
- Deferred Transmissions
- Late Collisions
- Excessive COllisions
- MAC Transmit Errors
- Carrier Sense Errors
- Frame Too Long
- MAC Receive Errors

• Interface Counters
- Alignment Errors
- In Octets
- In Ucast Packets
- In NUcast Packets
- In Discards
- In Errors
- In Unknown Protos
- Out Octets
- out UCast Packets
- Out NUcast Packets
- Out Discards
- Out Errors

Use the I/O Connections Page


To use the I/O Connections page for CIP I/O (Class 1) connection information,
follow this procedure.
1. Click I/O Connections tab at the top of the page or panel on the left.
The I/O Connections page opens.
The top value in this column representing Lost shows
the number of packets from the missing source.

2. From the I/O Connections page, view the following:


• Connection Number
• Uptime

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 67


Appendix B Adapter Web Dialogs

• Missed Rx Packets
• O-T (Originator-Target) Connection ID
• T-O (Target-Originator) Connection ID
• O-T (Originator-Target) Size
• T-O (Target-Originator) Size
• O-T (Originator-Target) Type
• T-O (Target-Originator) Type
• O-T (Originator-Target) API
• T-O (Target-Originator) API
• Timeout (msec)

Work with the Configuration To work with the Configuration pages, follow these procedures.
Pages IMPORTANT The values on these pages are in non-volatile memory. Changes to
these parameters do not take effect until you reset or cycle power
through the I/O adapter.

IMPORTANT If you set the value of the adapter switch to 888 and then power cycle
the module, the following occurs:
• The DHCP Enabled function is enabled (set to True).
• The Ethernet link is negotiated automatically. The Auto Negotiate
function is set to True.
• The web server is enabled. The Disabled Web Server function is
disabled.
• The Ethernet port are disabled. Both ports are re-enabled once the
switches are returned to their previous value and power is cycled.
• The password for this page resets to the factory default which is
“<blank>”.
Note the value of the switches before you enter the 888 value because
you must return the adapter to those values once this process is
complete.
1. From the Home page, click Configuration or Expand to see the
Configuration options, if needed.
2. From the Configuration page, click one of the following:
• Identity
• Network
• Services
A login dialog opens as shown. The dialog may vary in appearance
depending on your operating system and browser.

68 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Appendix B Adapter Web Dialogs

3. From the user name and password dialog, enter values, noting the
following:
• The values for user name and password are case sensitive.
• The default user name is “administrator”.
• The default password is “<blank>”.
4. Click OK to log in. After you log in, you can go to any of the Configuration
pages without having to log in again.
5. Refer to the section of this manual that corresponds to the section you
clicked:
• Identity
• Network Configuration
• Services

Use the Device Identity Page


To use the Device Identity page to make entries for the device name, device
description, and device location, use this procedure.
1. Click Device Identity from the tab at the top of the page or panel on the
left.
The Identity page opens.

2. From the Identity page, complete entries for the following, noting that
the description and location help you identify where modules are in the
facility:
• Device Name (this is 1747-AENTR by default)
• Device Description
• Device Location
3. Click Apply Changes to save the modified values.

Use the Network Configuration Page


To use the Network Configuration page to make entries for enabling or
disabling DHCP and setting TCP/IP parameters and Ethernet link operation,
follow this procedure.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 69


Appendix B Adapter Web Dialogs

1. Click Network Configuration tab at the top of the page or panel on the
left. The Network Configuration page opens.

2. From the Network Configuration page, complete these entries, noting


that values for Network Interface are disabled when DHCP is Dynamic
DHCP and port speed and duplex mode are disabled when Autonegotiate
Speed and Duplex is selected.
• For Initial Network Configuration:
- Ethernet Interface Configuration
- Static
- Dynamic DHCP

• For Network Interface, fill out these fields:


- IP Address
- Subnet Mask
- Gateway Address
- Primary Name Server
- Secondary Name Server
- Domain Name

• For Ethernet Link Port 1 and Port 2, specify the following:


- Autonegotiate Status
- Autonegotiate Speed and Duplex
- Force Speed and Duplex
70 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021
Appendix B Adapter Web Dialogs

- Select Port Speed – 10 megabits, 100 megabits


- Select Duplex Mode – Half Duplex, Full Duplex
3. From the Network Configuration page, click Apply Changes to save the
modified values.

Use the Device Services Page


To use the Services page to change the password for the Configuration web
page or disable the web server, follow these steps.
1. Click Device Services tab at the top of the page or panel on the left.
The Device Services page opens.

2. From the Services page, make these entries.


• Click the Enable box to change whether the web server runs after the
module is reset.
• Change the password by typing a new value for New Password and
Confirm Password, noting the following:
- The entry is case sensitive.
- The default value is <blank>.
3. Click Apply Changes.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 71


Appendix B Adapter Web Dialogs

Notes:

72 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Appendix C

Configure the RSLinx Ethernet Communication


Driver

Overview To communicate with your adapter over your network, you must configure the
RSLinx EtherNet/IP driver (AB-ETHIP). You can configure the AB_ETH driver
with the IP addresses of all the Ethernet devices on your system. You need one
of these drivers to download the example application programs in this manual.
See the table for a list of the contents of this appendix.
Topic Page
Install the RSLinx Software 73
Configure the AB_ETH/IP Driver 73

Install the RSLinx Software Use this procedure to install theRSLinx software on your computer.
1. Insert the CD in the CD-ROM drive.
Note that the CD-ROM supports Windows Autorun. Once inserted into
the CD-ROM drive, if you have Autorun configured, the installation
automatically starts at the first setup screen.
If Autorun is not configured for your CD-ROM drive, go to step 2.
2. From the Start menu, choose Run. The Run dialog opens.
3. Type D:/setup (if it doesn’t appear automatically), where D: is your CD-
ROM drive letter.
4. Click OK.
The progress bar, followed by the welcome screen opens

Configure the AB_ETH/IP To configure the AB-ETHIP Ethernet communication driver, perform the
Driver following steps.
1. Start the RSLinx software.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 73


Appendix C Configure the RSLinx Ethernet Communication Driver

2. From the Communications menu, select Configure Drivers.

3. Select EtherNet/IP Devices from the list and click Add/New...

The Configure Dialog box opens.

Make sure the Browse Local Subnet button is selected.


The RSLinx software browses your local subnet and automatically reads
the IP address.

74 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Appendix C Configure the RSLinx Ethernet Communication Driver

4. Click OK.
The AB-ETHIP driver is now configured and appears in the configured
drivers window.

5. Close the RSLinx software.

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 75


Appendix C Configure the RSLinx Ethernet Communication Driver

Notes:

76 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


Index

Numerics connections 29, 30


advanced 42
1746-BAS/B 33, 42 controller 34
1746-IA4 33
ControlLogix 33
1746-IO8 33 L63 33
1747-AENTR 29 Logix 11
configuration 33 tags 45
connect through RJ-45 19 ControlLogix 9, 33
custom settings 47 current consumption 59
drawing 10 cyclic trigger 12
installation 15
ratings 59
specifications 59 D
status indicators 55
1756-EN2TR 33, 34 DHCP 15, 26
DHCP Enabled 61
DHCP enabled 15
A direct 33
adapter 29 direct connection 12, 33
mounted 33 domain name 49
adapter operation 29 download
auto negotiate 16, 61 program 46

B E
backplane 9, 18, 29, 44 EFT/B immunity 60
BootP/DHCP 15, 21 electronic keying 30, 36, 38
relation List 25 emissions 59
enclosure type rating 59
C ESD immunity 60
EtherNet/IP 12
certifications Exclusive Owner 29
CE 60
C-Tick 60
c-UL-us 60 F
KC 60
ODVA 60 fault 30, 48
chassis 18 ForwardOpen 29
ControlLogix 33
size 38
SLC 42 G
chunk configuration 44
gateway address 22
CIP (Common Industrial Protocol) 12
communication with I/O modules 29
CompactLogix 9 H
compatibility hardware
1746/1747 modules 27 components 10
hardware/software 11 setup 33
conducted RF immunity 60
configuration
chunk 44 I
for EtherNet/IP network 21 I/O
through RSLogix 5000 33
modules 33
configure
I/O Configuration 35
adapter 33
add 1747-AENTR 37
for direct connection 33
add I/O module 39
connection 33 I/O configuration
direct 29, 33 add Ethernet bridge 35
maximum 29
simple 42 IEEE 802.1 ID 29
IEEE 802.3 29

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 77


Index

indicator RSLinx 11, 21, 29, 34


Link 1 status 10 configure Ethernet driver 73
Link 2 status 10 install 73
Link1 and Link 2 55 RSLogix 5000 11, 21, 24, 29, 33, 47, 50
status 10, 55 connection properties 44
indicators custom settings for I/O modules 50
diagnostic 11 Module Definition 43
troubleshoot with 55
inhibit module 48
Input Only 30 S
installation 15 sample application 34
IP address 21, 34, 62 shock
isolation voltage 59 nonoperating 59
shock, operating 59
SLC backplane 9
L software 29
latch 10 software requirements 29
Listen Only 30 specifications 59
Logix system 11 environmental 59
Ethernet communication 59
general 59
M status indicators 55
master and slave 12 subnet mask 21, 23
media speed 61 surge transient immunity 60
mode 30 switches
module 29 network 10, 15, 21
dimensions 59
inhibit 48
location 59
T
revision 38 T3C 59
Module Properties 50 TCP 16
General tab 38 temperature
Internet Protocol 48 nonoperating 59
multicast 12 operating 59
surrounding air 59
thermal dissipation 59
O troubleshooting 55
operation 29
U
P unicast 12
ports 29
auto-negotiate speed 49
Ethernet 49 V
speed 49 vibration 59
power supply 33
producer-consumer 12
W
web server 16, 61
R diagnostic overview 63
Radiated RF immunity 60 home page 61
ratings 59 I/O Connections 67
relation list 25 network settings 65
relative humidity 59 weight 59
requirements 29 wiring category 59
configuration 21
power 18
RJ-45 10
wire 19
RPI 12, 40, 41, 44
default value 41

78 Rockwell Automation Publication 1747-UM076E-EN-E - August 2021


SLC 500 EtherNet/IP Adapter User Manual

Rockwell Automation Publication 1747-UM076E-EN-E - August 2021 79


Rockwell Automation Support
Use these resources to access support information.
Technical Support Center Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support
Knowledgebase Access Knowledgebase articles. rok.auto/knowledgebase
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center Download firmware, associated files (such as AOP, EDS, and DTM), and access product rok.auto/pcdc
(PCDC) release notes.

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our
content, complete the form at rok.auto/docfeedback.

Waste Electrical and Electronic Equipment (WEEE)

At the end of life, this equipment should be collected separately from any unsorted municipal waste.

Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.

Allen-Bradley, CompactLogix, ControlLogix, expanding human possibility, FactoryTalk, Logix 5000, PanelView, Rockwell Automation, RSLinx, RSLogix 5000, SLC, SLC 500, Studio 5000,
Studio 5000 Logix Designer, and TechConnect are trademarks of Rockwell Automation, Inc.
CIP, ControlNet, DeviceNet, and EtherNet/IP are rademarks of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur

Connect with us.

Publication 1747-UM076E-EN-E - August 2021


Supersedes Publication 1747-UM076D-EN-E - January 2019 Copyright © 2021 Rockwell Automation, Inc. All rights reserved.

You might also like