1319
1319
Published in the proceedings of "The 7th IEEE International Conference on Innovative Smart Grid
Technologies" (IEEE PES ISGT Europe 2017), September 27, 2017, Torino, Italy.
© 2017 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for
all other uses, in any current or future media, including reprinting/republishing this material for
advertising or promotional purposes, creating new collective works, for resale or redistribution to
servers or lists, or reuse of any copyrighted component of this work in other works.
r2 i r1
l2 l1
c
vg vb
vc
rc
The VSM core parameters are chosen to represent a real The simulation results of the linear discrete model (Lin)
synchronous machine (RSM). Swing damping is increased and a nonlinear average model (Sim) are presented in Fig. 5.
beyond the level achievable in RSMs to avoid overshoot and The linear model is valid as long as the coupling between
oscillations of active power. The LC damping controller is active and reactive power is low (Fig. 5, left) and differs with
designed to damp oscillations while minimizing the feedback increasing values for rv (Fig. 5, right).
gain at low frequencies. The chosen voltage droop and time At the operating point P = 0.5 pu, instability occurs for
constant ensure an inherent, instant reaction to low voltage rv > 0.47 pu. Since both models react responses coincide,
events with reactive power, while the reactive power setpoint control design in the linear model is applicable.
is tracked with reasonable delay and reasonable steady-state B. Low Voltage Fault
deviation. The control parameters are given in Table I and The maximum current amplitude of the voltage dip is
hardware parameters are given in Table III. Two grid config- investigated for different values of rv . The fault duration is
urations are considered subsequently: 200 ms and different values for the voltage dip are simulated
• SCR = 23, representing the laboratory configuration in the average model utilizing the SimPowerSystem model
• SCR = 4, representing a unit connected via two trans- suite. The pre-fault steady-state power is 0.5 pu. Fig. 6 de-
formers and a moderately long line. picts the maximum inverter current caused by the fault for
Full View Zoom - Synchronous Resonance Zoom - VSM Core
#10 -3
0.1 3
1 r_v = 0
LC Filter r_v = 0.5
2
0.05
Imaginary Axis 0.5
1
Syn. R. VSM Core
0 0 0
-1
-0.5
-0.05
-2
-1
-0.1 -3
-1 -0.5 0 0.5 1 0.6 0.8 1 0.996 0.998 1
Real Axis Real Axis Real Axis
Fig. 4. Root locus of the VSM for a variation of virtual resistor rv with SCR = 23; Increasing rv increases damping of synchronous resonance and
decreases damping of swing mode. See Table II for eigenfrequencies and damping and comparison to SCR = 4.
Fig. 6. Maximum inverter current during voltage dips at the infinite bus with
SCR = 23 (top) and SCR = 4 (bottom) at P = 0.5 pu.
Fig. 5. Comparison of the nonlinear average model against the linear model
with rv = 0 pu (left) and rv = 0.2 pu (right).
Lab Converter PM90F33 Ametek
Grid L1
i L1 L2 RS270
TABLE IV
M INIMUM VOLTAGE DIP EXPERIMENTED IN THE LAB WITH SCR = 23.
P = 0.25 pu P = 0.5 pu
rv Vfrt max(Iinv ) Vfrt max(Iinv )
0 pu 90 % 1.02 pu 90 % 1.26 pua
0.1 pu 80 % 1.17 pu 90 % 0.88 pu
0.2 pu 70 % 1.26 pu 80 % 1.12 pub
0.3 pu 70 % 1.03 pu 70 % 1.22 pu
a see Fig. 10 b see Fig. 11
with SCR = 23. The fault duration is 200 ms and the pre-fault
steady-state power is 0.5 pu. With respect to the simulation
results from Fig. 6, only certain voltage dips can be tested
before exceeding the the current limit of the inverter. Table IV
Fig. 8. Comparison of experimental data (solid) against the nonlinear model
(dashed)
shows the minimum voltage, which we could test successfully.
Due to the virtual resistor, the range of the fault voltage could
be extended from 90 % down to 70 %.
B. Verification Figure 10 and Fig. 11 depict the result of experimental
To verify the nonlinear model (dashed) with the experimen- voltage dips (Lab). Reactive power is injected during the fault
tal setup (solid), a P ∗ change for different values of rv is inherently. It can be seen that the simulation results (Sim)
conducted (see Fig. 8). With greater coupling of active and with r1 = 0.1 pu are only valid close to the operating point.
reactive power, the two results differ. We assume it is due to For the maximum current at t ≈ 0, r1 = 0.04 pu is a better
a nonlinear behavior of the effective value of r1 . At t = 0 s a approximation, which is another indication for the nonlinear
delayed response in the power output can be observed, which behavior of r1 .
we assume is due a nonlinear effect of r1 close to the operating
V. C ONCLUSION
point P = Q = 0 pu. At about t = 0.17 s, the voltage
source has a switching event in its control resulting in a ripple The virtual resistor is a simple addition to the VSM to
especially observable in the reactive power. reduce fault currents of the VSM drastically while keeping
To further verify the model, the value of rv was changed the inherent reaction of injecting reactive power.
while the inverter is in steady-state condition with P = 0.5 pu, Reasonable values for the VR that guarantee stability have
see Fig. 9. Instability occurs for rv > 0.48 pu, which is similar been selected and the short-circuit behavior was investigated.
to the stability limit observed in the nonlinear model. These theoretical results have been confirmed by laboratory
experiments. The maximum fault current amplitude with VR
C. Low Voltage Fault is reduced to 2.5 pu.
In this section, experimental results of low voltage fault Component costs for over-current capabilities can be re-
scenarios at the voltage source are given. Since the inverter is duced through the VR. For state-of-the-art hardware with strict
directly connected to the voltage source, the l2 impedance of current limits, the rating may still be exceeded during severe
the filter represents the grid impedance, leading to a strong grid faults with Vfrt < 70 %.
applied. Second, a decoupling scheme for the active and
reactive power branches can increase the maximum value for
rv and improve the control quality of active and reactive
power. Third, EMT-grid studies need to be conducted, to verify
power system stability with the proposed control strategy.
ACKNOWLEDGMENT
The authors would like to thank the German Federal
Ministry for Economic Affairs and Energy for funding this
research within Transstabil-EE (FKZ: 0325796A).
R EFERENCES
[1] T. L. Vandoorn, J. d. Kooning, B. Meersman, and L. Vandevelde,
“Review of primary control strategies for islanded microgrids with
power-electronic interfaces,” Renewable and Sustainable Energy Re-
views, vol. 19, pp. 613–628, 2013.
[2] UCTE, “Final Report System Disturbance on 4 November 2006.”
[3] D. Duckwitz, “Performance of df/dt-based Inertia Control during
Emergency Islanding,” in 15th Wind Integration Workshop, Vienna,
2016. [Online]. Available: http://publica.fraunhofer.de/documents/
N-421317.html
[4] J. Lehner, “Necessary Time Response of LFSM-O to Ensure Frequency
Fig. 10. Experimental result of voltage dips with Vfrt = 90 %, rv = 0 pu.
Stability in the ENSO-E Continental Europe Synchronous Area,” in Wind
The pre-fault steady-state power is 0.5 pu.
Integration Workshop 2016.
[5] Agora Energiewende - Agorameter. [Online]. Available:
https://www.agora-energiewende.de/de/themen/-agothem-/Produkt/
produkt/76/Agorameter/
[6] national grid UK: Future Energy Scenario 2016. [Online]. Available:
http://fes.nationalgrid.com/
[7] R. Hesse, D. Turschner, and H.-P. Beck, “Micro grid stabilization using
the Virtual Synchronous Maschine,” 2009.
[8] S. D’Arco, J. A. Suul, and O. B. Fosso, “Automatic Tuning of Cascaded
Controllers for Power Converters Using Eigenvalue Parametric Sensitiv-
ities,” IEEE Transactions on Industry Applications, vol. 51, no. 2, pp.
1743–1753, 2015.
[9] J. Wang, Y. Wang, Y. Gu, W. Li, and X. He, “Synchronous frequency
resonance of virtual synchronous generators and damping control,” in
2015 9th International Conference on Power Electronics and ECCE Asia
(ICPE-ECCE Asia). IEEE, 2015, pp. 1011–1016.
[10] S. D’Arco and J. A. Suul, “Virtual synchronous machines — Classifica-
tion of implementations and analysis of equivalence to droop controllers
for microgrids,” in PowerTech (POWERTECH), 2013 IEEE Grenoble,
2013, pp. 1–7.
[11] A. Engler, Regelung von Batteriestromrichtern in modularen und erweit-
erbaren Inselnetzen. Berlin: Dissertation.de, 2002.
[12] K. d. Brabandere, B. Bolsens, J. van den Keybus, A. Woyte, J. Driesen,
and R. Belmans, “A Voltage and Frequency Droop Control Method for
Parallel Inverters,” IEEE Transactions on Power Electronics, vol. 22,
no. 4, pp. 1107–1115, 2007.
[13] S. Laudahn, J. Seidel, B. Engel, T. Bulo, and D. Premm, “Substitution of
Fig. 11. Experimental result of voltage dips with Vfrt = 80 %, rv = 0.2 pu synchronous generator based instantaneous frequency control utilizing
(bottom). The pre-fault steady-state power is 0.5 pu. inverter-coupled DER,” in 2016 IEEE 7th International Symposium on
Power Electronics for Distributed Generation Systems (PEDG). IEEE,
2016, pp. 1–8.
[14] D. Duckwitz, B. Fischer, and M. Shan, “Synchronous Inertia Control
With increased values for the VR, the coupling between for Wind Turbines: Application of the Virtual Synchronous Machine to
active and reactive power reduces swing damping and even- Wind Turbines for providing Distributed Contributions to Power System
Inertia,” in 13th Wind Integration Workshop, Berlin, 2014. [Online].
tually causes instability. Furthermore the quality of active Available: http://publica.fraunhofer.de/dokumente/N-356526.html
and reactive power control decreases. From the experimental [15] “Fuji Electic: IGBT Module Datasheet: 2MBI300VE-120-50.”
results, it can be seen that the effective value of the hardware [16] J. M. Guerrero, J. Matas, L. Garcia de Vicuna, M. Castilla, and J. Miret,
“Decentralized Control for Parallel Operation of Distributed Generation
resistor r1 shows a nonlinear dependency with the operating Inverters Using Resistive Output Impedance,” IEEE Transactions on
point. Industrial Electronics, vol. 54, no. 2, pp. 994–1004, 2007.
[17] V. Blasko and V. Kaura, “A novel control to actively damp resonance
Coupling, instability and maximum current all depend on in input LC filter of a three-phase voltage source converter,” IEEE
the value of the virtual resistor rv and on the circuit value r1 . Transactions on Industry Applications, vol. 33, no. 2, pp. 542–550, 1997.
This sets the foundation for further research. First, a model
for r1 is helpful for better simulation models and system
understanding. Adaptive control or gain-scheduling may be