Modular Substation Technical Data

The document provides comprehensive technical data for modular substations, including common characteristics, HV Gas Insulated Switchgear (GIS) specifications, and various equipment technical data. It outlines standard compliance, application conditions, enclosure details, auxiliary systems, and specific parameters for GIS. The document serves as a detailed reference for the design and implementation of modular substations in accordance with international standards.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
10 views

Modular Substation Technical Data

The document provides comprehensive technical data for modular substations, including common characteristics, HV Gas Insulated Switchgear (GIS) specifications, and various equipment technical data. It outlines standard compliance, application conditions, enclosure details, auxiliary systems, and specific parameters for GIS. The document serves as a detailed reference for the design and implementation of modular substations in accordance with international standards.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 66

Modular Substation Technical Data

Modular Substation
Technical Data

TGOOD
2017.2

1
tgood.com TGQDMK000410
Modular Substation Technical Data

Contents:

Part 1: Common characteristics

Part 2: HV Gas Insulated Switchgear (GIS) Technical Data

Part 3: 110kV Neutral Point Complete Equipment for Service Transformer

Technical Data

Part 4: 40.5kV House Technical Data

Part 5: 40.5kV Arc Suppression Coil House Technical Data

Part 6: 17.5kV House Technical Data

Part 7: 17.5 kV Compensation House Technical Data

Part 8: 12kV Arc Suppression Coil House Technical Data

Part 9: Power Transformer House Technical Data

Part 10: Secondary House Technical Data

2
tgood.com TGQDMK000410
Modular Substation Technical Data

Part 1:
Common Characteristics

3
tgood.com TGQDMK000410
Modular Substation Technical Data

1. Standard compliance
 IEC 62271‐1 High‐voltage switchgear and controlgear Part 1: Common specifications
 IEC 62271‐202 High‐voltage/low‐voltage prefabricated substation
 IEC 62271‐100 High‐voltage alternating‐current circuit‐breakers
 ISO12944 Corrosion protection of steel structures by protective paint systems
 IEC 60529‐2004 Degrees of protection provided by enclosures (IP code)
 IEC364‐4‐41 Protection of grounding, lightning protection and grounding standards
 IEC60071‐1:2011 Insulation Co‐ordination for high‐voltage power transmission and
transformation equipment
 IEC 62271‐102 Alternating current disconnectors and earthing switches
 IEC 62271‐303 Use and handling of sulphur hexafluoride (SF6) in highvoltage
switchgear and controlgear
 IEC 60068‐2 Environmental testing Part 2: Tests (all parts)
 DIN EN ISO 3834‐2 Quality requirements for fusion welding of metallic materials ‐ Part
2: Comprehensive quality requirements
 EN 1090‐2:2008+A1:2011 Execution of steel structures and aluminium structures –
Part 2: Technical requirements for steel structures
 ISO2768‐1:1989 General tolerances for linear and angular dimensions without
individual tolerance indications
 GB/T 1231 Specification of high strength bolts with large hexagon head, large hexagon
nuts, and plain washers for steel structures.
 ISO 898‐1:1999 Mechanical properties of fasteners made of carbon steel and alloy
steel‐‐ Part 1: Bolts, screws and studs
 ISO 6789‐2003 Assembly Tools for Screws and Nuts ‐ Hand Torque Tools ‐
Requirements and Test Methods
 CSA A660‐10 Manufacturers certification of steel building systems
 EN 1090 Assembly of steel structures
 CWB 47.1 Canadian welding standards
 ISO 3834 Welding fabrication certification
 GB/T 9978.1‐2008 Fire‐resistance tests‐elements of building construction‐Part1:
General requirements
 GB/T 9978.8‐2008 Fire‐resistance tests‐elements of building construction‐Part8:
Specific requirements for non‐loadbearing vertical separating elements.

4
tgood.com TGQDMK000410
Modular Substation Technical Data

2 Application condition

Option values of project demand


No Items
standard
Max (°C) +40 +42 +45 — — —
1 Ambient temperature
Min (°C) ‐25 ‐30 ‐35 — — —
2 Altitude (≤m) 1000 2000 2500 3000 3500 4000
3 Solar radiation intensity (W∕cm2) 0.11
4 Maximum icing thickness (mm) 10
The average maximum wind speed (m/s)
5 maintained for 10min at 10m above the 35
ground
6 Ground horizontal acceleration (m/s2) 2
Safety factors of three periods of
7 1.67
sinusoidal resonance (≥)

3. Enclosure

 Lifespan: 30 years
 Frame structure: welded, rolled steel, and the yield strength should not be less than
235MPa.
 IP class: IP33D for ventilation outlets. IP54 without ventilation outlets
 Base of enclosure: welded by high quality of steel, the yield strength should not be less
than 235MPa. Thickness of steel: frame≥2.5mm; Door and top roof: 2mm; Base: ≥3mm,
Filled by nonflammable materials.
 Sealing: Yes, for whole enclosure
 Top roof: inclining degree not less than 5°,
 Hinge: inner side design
 Door opening angle :> 90°
 Smoke detection system: sensor is located at the top
 Anti‐corrosion performance: 30 years
 Temperature control system:
 Wall: 3 layers, overall thickness≥48mm
 Heat conduction ratio between inner plate and outer plate: 2%
 Filled foam density: 37kg/m³
 Automatic temperature control system: AC starts T >50°C or T˂0°C
 Anti‐seismic:
 Frame welded to enhance the mechanical strength
 Vibration resistance: 0.5g (horizontal and vertical)
 Cable passageway:
 Made of 2mm metal sheet
 Fire rating: class A
 Secondary channel: tunnel made of metal sheet

5
tgood.com TGQDMK000410
Modular Substation Technical Data

 Lighting:
 Passageway
 Emergency
 Maintenance
 Anti‐explosion LED
 Earthing:
 Earthing terminal: ˃Ø12
 Earthing point: 4 per house

4. Auxiliary systems

4.1 Standard compliance


 GB16796‐2009 Safety Requirements and Test Method for Security Alarm Equipment
 GB10408.1‐2000 Detection for Intruder Alarm System – Part 1: Requirements for
Detectors – General Requirements
 GB12663‐2007 General Technical Conditions for Fire Alarm Control Unit
 GB4798.4‐2007 Environmental Conditions Existing in the Application of Electric and
Electronic Products – Stationary Use at Non‐weather‐protected Locations
 GB2423.10‐2008 Environmental Testing for Electric and Electronic Products
 IEC364‐4‐41 Standard for Protective Grounding and Lightning Protection
 GA/T75‐94 Engineering Procedure and Requirement of Safety and Alarm System
 GA308‐2001 Acceptance Check Criterion of Security and Alarm Systems
 GA/T74‐2000 Symbols for Use in Diagram of Security and Alarm System
 GB50115‐2009 Design Code of Industrial Television System
 GB/16677‐1996Transfer Equipment of Alarm Picture Signal through Cable

4.2 Prefabricated substation environment and fire protection monitoring

Item Type Unit Qty Note

Ball machine and


Indoor intelligent ball Set 2 Simulation with power supply support
infrared
Point‐type photoelectric
JTY‐GD‐G3 Nr. 4 one for 40 squares
smoke detector
Base of detector DZ‐02 Nr. 4
Manual fire alarm call
J‐SAM‐GST9121 Nr. 2 One for each door
point
Fire audible and visual
HX‐100B Nr. 2
alarm
Temperature & humidity
ST2004 Nr. 6 485 output
sensor

6
tgood.com TGQDMK000410
Modular Substation Technical Data
Temperature and
485 input and Ethernet input; each
humidity protocol ST‐WSD‐5130 Nr. 1
cabinet is provided with one
module
Water sensor ST2003 Nr. 2 DI output
Detection of
SF6 detector (if need) double chamber Nr. 4 485 output
gas
SF6 protocol module (if 485 input and Ethernet input; each
ST‐SF6‐5130 Nr. 1
need) cabinet is provided with one
SF6 audible visual
Horn Set 2 DO
annunciator (if need)
Indoor lighting
ST2007E Set 1
controller
It is of a dimension of 20 (thickness) ×
Auxiliary system 60 (width) × 80 (length) (CM),
equipment box Custom‐made Nr. 1 equipped with guide rail, wiring
(purchased by Party A) terminals, and cabin service power
supply
8 of 10M/100M Switches Huawei Nr. 1
Micro‐positive pressure
TGOOD Set 2
air conditioner
KAKU
Ventilating fan Nr. 4
KA2509HA2‐4
Environment monitoring
ST2201E Set 1
module
Note 1: The above configuration is only for reference, and the specific configuration should be
subject to relevant national regulations and requirements of the operation unit.
Note 2: The manufacturer winning the bidding should take charge of installation and commissioning
of the system equipment in the plant.

7
tgood.com TGQDMK000410
Modular Substation Technical Data

Part 2:
HV Gas Insulated Switchgear (GIS)
Technical Data

8
tgood.com TGQDMK000410
Modular Substation Technical Data

1. Standard compliance
 IEC 62271 High‐voltage switchgear and controlgear Part 1: Common specifications
 IEC62271‐203 Gas‐insulated metal‐enclosed switchgear for rated voltages above 52 kV
 IEC 62271‐104 Switches for rated voltages of 52 kV and above
 IEC 62271‐100 High‐voltage alternating‐current circuit‐breakers
 IEC 62271‐102 Alternating current disconnectors and earthing switches
 IEC 61869‐1‐2007 Instrument transformers‐Part1 General requiremnets
 IEC 61869‐2 addional requirements for current transformers
 IEC 61869‐3:2011 Instrument transformers – Part 3: Additional requirements for
inductive voltage transformers
 IEC 60270 High‐voltage test techniques—Partial discharge measurements
 IEC60071‐1:2011 Insulation Co‐ordination for High‐voltage Power Transmission and
Transformation Equipment
 IEC 62271‐200 AC Metal‐enclosed Switchgear and Control Gear for Rated Voltages
above 3.6kV and up to and including 40.5kV
 IEC 62271‐303 Use and handling of sulphur hexafluoride (SF6) in highvoltage
switchgear and controlgear
 IEC 60265‐2 High‐voltage switches. ‐ Part 2: High‐voltage switches for rated voltages of
52 kV and above
 IEC 62271‐108 Disconnecting circuit‐breakers
 IEC 60044‐8 Electronic current transformers
 IEC 60044‐5 Capacitor voltage transformers
 IEC 60044‐7 Electronic voltage transformers
 IEC60044‐3 Combined transformers
 IEC 60099‐4 Metal‐oxide surge arresters without gaps for a.c. systems
 IEC 60137‐2008 Insulated bushings for alternating voltages above 1000 V
 IEC 61462 Composite hollow insulators ‐ Pressurized and unpressurized insulators for
use in electrical equipment with rated voltage greater than 1000 V ‐ Definitions, test
methods, acceptance criteria and design recommendations
 IEC 62271‐209 Cable connections for gas-insulated metal-enclosed switchgear for
rated voltages above 52kV - Fluid-filled and extruded insulation cables - Fluid-filled and
dry-type cable-terminations

 IEC 61639 Transformer connections

2. HV GIS technical data

S/N Items Unit Data Note


I GIS common parameter

9
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


1 Rated voltage kV 145
Outgoing line Up to 2000
Incoming line Up to 3150
2 Rated current Subsection A
Up to 3150
and buscouple
Main busbar Up to 3150
Rated power‐frequency withstand voltage (1
3 kV 230
min) (relatively)
Peak value of rated lightning impulse
4 kV 550
withstand voltage (1.2/50s) (relatively)
5 Rated short‐circuit breaking current kA 40
6 Rated short‐circuit making current kA 100
7 Rated short‐time withstand current/duration kA/s 40/3
8 Rated peak withstand current kA 100
Short‐time power‐frequency withstand
9 kV 2
voltage of auxiliary and control circuits
10 Radio interference voltage μV ≤500
11 Noise level dB ≤90
Circuit
breaker 0.6MPa
SF6 gas pressure
12 chamber MPa
(20°C gauge pressure)
Other
0.5MPa
compartments
13 SF6 gas leakage rate of each compartment %/Year ≤0.1
Handover
acceptance ≤150
Compartments value
with arc Allowable
decomposition value of
≤300
long‐term
SF6 gas operation
14 μL/L
humidity Handover
acceptance ≤250
Compartments value
without arc Allowable
decomposition value of
≤500
long‐term
operation
Testing
kV 1.1×126/ 3
voltage
15 Partial discharge
Every
pC ≤5
compartment

10
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


Every single
insulating ≤3
part
Bushing ≤5
Current
≤5
transformer
Voltage
≤10
transformer
Lightning
≤10
arrester
Control circuit V DC 220
16 Power supply Auxiliary
V AC 380/220
circuit
17 Service life Year ≥30
18 Overhaul period Year ≥20
SF6 gas quality kg 300
Total weight kg 6000
Maximum
transportation kg 8000
weight
Equipment quality (single
19 Dynamic load
space)
moves kg 2000
downwards
Dynamic load
moves kg 2000
upwards
Overall
dimension of m TGOOD provide
equipment
Maximum
20 Equipment dimension
transportation
m TGOOD provide
clearance of
equipment
Width m 0.8
Three‐phase in one
Breaker
tank
21 Structural Layout
Three‐phase in one
Bus
tank
II Parameters of the breaker
1 Model TGP 145‐40‐31(CB)
2 Layout mode Vertical type
3 Number of fractures 1

11
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


Outgoing line Up to 2000
Incoming line Up to 3150
4 Rated current A
Subsection
Up to 3150
and buscouple
5 Main circuit resistance μΩ 80
6 Current of temperature‐rise test A 1.0 Ir
Across
Rated power‐frequency isolating 230+70
kV
withstand voltage (1 min) distance
To earth 230
7
Across
Peak value of rated lightning
isolating 550+100
impulse withstand voltage kV
distance
(1.2/50s)
To earth 550
Effective value
of AC kA 40
component:
Time
ms 45
Rated short‐circuit breaking constant:
8
current Breaking
Times ≥20
times
First‐phase
breaking 1.5
factor
9 Rated short‐circuit making current kA 100
10 Rated short‐time withstand current/duration kA/s 40/3
11 Rated peak withstand current kA 100
12 Break time ms ≤60
13 Close‐open time ms ≤60
14 Opening time ms ≤40
15 Closing time ms ≤100
16 Reclosing dead time ms ≥300
Opening
Average speed of opening 5±0.5
17 speed m/s
and closing
Closing speed 2.5±0.5
18 Opening non‐synchronism ms ≤3
19 Closing non‐synchronism ms ≤5
20 Mechanical endurance Times 10,000
21 Rated operating sequence O–0.3s–CO–180s–CO
No‐load
Switching no‐load
22 transformer MVA 50
transformer capacity at site
capacity

12
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


No‐load
exciting A 0.5~15
current
Testing
kV 145
voltage
Operating
10×O and 10× (CO)
Sequence
Determined by the
Test current A
actual length of line
Testing
kV 145
voltage
In principle, the line
should not be
equipped with
Charging current test of
23 voltage reducing
field switching non‐load line
Test condition devices, such as
electric reactors,
lightning arresters,
voltage transformers,
etc.
Operating
10× (O‐0.3s‐CO)
Sequence
Test current A Line: 31.5, cable: 140
Testing
kV 1.4×145/ 3
voltage
Class C1: LC1
and CC1:
24×O; LC2
Capacitive current switching and CC2:
24
test (laboratory) 24×CO
Class C2: LC1 Class C1
and CC1:
48×O; LC2
and CC2:
24×O and
24×CO
L90 kA 36
L75 kA 30
Switching capability under 24 (the minimum arc
25
the close‐in fault condition time of L75 is 5ms
L60 kA
greater than that of
L90)

13
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


Operating
O‐0.3s‐CO‐180s‐CO
Sequence
breaking
kA 10
Out‐of phase making and current
26
breaking capacity Testing
kV 2.5×126/ 3
voltage
Out‐of phase making and Operating Mode 1: O‐O‐O
26
breaking capacity Sequence Mode 2: CO‐O‐O
Rated 0.6MPa
SF6 gas pressure Alarm 0.55MPa
27 MPa
(gauge pressure, 20°C) Minimum (in
0.5MPa
block)
Type or model of operating mechanism Spring
Three‐phase
Operating mode
mechanical linkage
Motor voltage V DC220
Rated
operating V DC 220
voltage
Allowable
85% ‐ 110% and
range of
operation is not
operating
allowed below 30%
Closing operating power voltage
supply Coil quantity
Nr. 1
of each phase
Surge of each
A 3.3
coil
28
Steady‐state
current of A DC 220V, 2.5A
each coil
Rated
operating V DC 220
voltage
Allowable
65% ‐ 110% and
range of
operation is not
Opening operating power operating
allowed below 30%
supply voltage
Coil quantity
Nr. 1
of each phase
Surge of each
A 3.3
coil
Steady‐state A DC 220V, 2.5A

14
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


current of
each coil
voltage V AC 220
Heater Power of each
W 100W
phase
10 for normal open
Qty. Pair and 10 for normal
Standby auxiliary contact closed
Breaking
DC 220V, 2.5A
capacity
Overhaul period Year ≥20
Spring mechanism Charging time s ≤20
Overall
quality of
breaker,
kg 500
including the
auxiliary
equipment
Quality of
29 Breaker quality operating
kg 150
mechanism of
each phase
SF6gas quality
kg 50
of each phase
Overall
transportation kg 800
quality
30 Transportation height m 3.4
Standard parameter
S/N Description Unit
value
31 Hoisting height m 5
III Parameters for Isolating Switch
1 Type/model TGP145‐40‐31 (DS)
Outgoing line A 3150
Incoming line A 3150
2 Rated current
Subsection
A 3150
and buscouple
3 Main circuit resistance μΩ 82.8 max.
4 Current of temperature‐rise test A 1.1Ir
Rated power‐frequency Break 230+70
kV
5 withstand voltage (1 min) To earth 230
Peak value of rated lightning Break kV 550+100

15
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


impulse withstand voltage
To earth 550
(1.2/50s)
6 Rated short‐time withstand current/duration kA/s 40/3
7 Rated peak withstand current kA 100
Opening time ≤660
8 Opening and closing time ms
Closing time 1040
Opening
Average speed of opening 0.148
9 speed m/s
and closing
Closing speed 0.094
10 Mechanical endurance Times 2000
11 Current value of switching small capacitance A 1
12 Current value of switching small inductance A 0.5
Switching
A 1600
current
Electric current
Transforming
13 transformation capacity of V 10
voltage
switching bus
Breaking
Times 100
times
Type or model Electric
Motor voltage V AC 380/220
Control
V AC 220
voltage
Allowed
Operating mechanism
variation
85%~110%
scope of
14 voltage
Operating Three‐phase
mode mechanical linkage
10 for normal open
Qty. Pair and 10 for normal
Standby auxiliary contact closed
Breaking
DC 220V, 2.5A
capacity
IV Parameters of fast earthing switch (FES)
1 Rated short‐time withstand current/duration kA/s 40/3
2 Rated peak withstand current kA 100
3 Rated short‐circuit making current kA 100
4 Closing times of rated short‐circuit current Times ≥2
(provided by the
Opening time
Bidder)
5 Opening and closing time ms
(provided by the
Closing time
Bidder)

16
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


Opening (provided by the
Average speed of opening speed Bidder)
6 m/s
and closing (provided by the
Closing speed
Bidder)
7 Mechanical endurance Times 2000
Reactive
A 50/80
current
Electromagnetic Breaking
Times 10
Switching induction times
induction Induced
kV 0.5/2
Current voltage
8
capacity Capacitive
A 0.4/2
(Type current
A/B) Electrostatic Breaking
Times 10
induction times
Induced
kV 3/6
voltage
Type or model Spring
Motor voltage V AC 380/220
Control
V AC 220
voltage
Operating mechanism
Allowed
variation
85%~110%
9 scope of
voltage
8 for normal open
Quantity Pair and 8 for normal
Standby auxiliary contact closed
Breaking
DC 220V, 2.5A
capacity
V Parameters of maintenance grounding switch
1 Rated short‐time withstand current/duration kA/s 40/3
2 Rated peak withstand current kA 100
3 Mechanical endurance Times 2000
Type or model Electric
Motor voltage V AC 380/220
Control
V AC 220
voltage
4 Operating mechanism
Allowed
variation
85%~110%
scope of
voltage

17
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


8 for normal open
Qty. Pair and 8 for normal
Standby auxiliary contact closed
Breaking
DC 220V, 2.5A
capacity
VI Parameters for Current Transformer (CT)
1 Type or model Electromagnetic type
2 Layout mode Internal
Nominal
400~800~1000/5A
current ratio
Rated burden 20VA
5P30 (line and
Winding 1
subsection)
Accuracy class 5P20 (main
transformer)

Nominal
400~800~1000/5A
current ratio
Rated burden 20VA
Winding 2 5P30 (line and
subsection)
3 Accuracy class
5P20 (main
transformer)
Nominal
400~800~1000/5A
current ratio
Rated burden 20VA
Winding 3 5P30 (line and
subsection)
Accuracy class
5P20 (main
transformer)
Nominal
400~800~1000/5A
current ratio
Winding 4
Rated burden 20VA
Accuracy class 0.5
Nominal
400~800~1000/5A
current ratio
Winding 5
Rated burden 20VA
Accuracy class 0.2S
VII Parameters for voltage transformer (VT)
1 Type or model Electromagnetic type

18
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


110 0.1 0.1
0.1
2 Rated voltage ratio 3 3 3

3 Accuracy class 0.2/0.5/3P,


4 Wiring group Y/Y/Y/
5 Three‐phase imbalance V 1
1min power frequency withstand voltage of
6 kV 3
low voltage winding
1.2×rated
7 Rated voltage factor continuous,
1.5×rated 30S
VIII Lightning arrester parameters
1 Rated voltage kV 108
2 Continuous operating voltage kV 84
3 Nominal discharge current (8/20μs) kA 10
Residual voltage at steep impulse current
4 kV 315
(1/10μs)
Residual voltage under lightning impulse
5 kV 281
current (8/20μs)
Residual voltage at switching impulse current
6 kV 239
(30/60μs)
7 DC 1mA reference voltage kV ≥157
Leak current at 75% of DC 1mA reference
8 μA ≤50
voltage
Power‐frequency reference current (effective
9 kV ≥108
value)
10 Power‐frequency reference current (peak) mA 2
Full current mA 0.85
11 Continuous current Resistive
μA 250
current
Line discharge
2
class
Long duration impulse Impact of
12
withstand current rectangular
A 800
wave current
impact
13 4/10μs large impulse withstand current kA 100
14 Operating load Pass
1.2Ur* 0.2 s
Characteristics of power frequency voltage 1.15Ur* 1.1 s
15
withstand duration 1.1Ur* 10s
1.0 Ur* 20 min

19
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


Absorption capability of kilovolt nominal
16 kJ/kV ≥7.25
voltage
17 Pressure release capacity kA/s 40/0.2
IX Bushing parameters
Large and small
1 Umbrella skirt type
umbrella
2 Material Porcelain Or epoxy
3 Rated current A 2000
4 Rated short‐time withstand current/duration kA/s 40/3
5 Rated peak withstand current kA 100
Rated power‐frequency withstand voltage (1
6 kV 230
min) (relatively)
Peak value of rated lightning impulse
7 kV 550
withstand voltage (1.2/50s) (relatively)
3150
(when the average
diameter is between
300mm (included)
and 500mm
(included), the figure
For DL,
8 Creepage distance mm should multiple by
standard
1.1; when the
average diameter
is greater than
500mm, the figure
should multiple by
1.2)
9 Dry acing distance mm ≥900
10 S/P ≥0.9
Longitudinal 1250
Horizontal N 750
11 Terminal static load Vertical 1000
Safety Static state: 2.75;
coefficient dynamic state: 1.7
Minimum clearance between phases of
12 mm ≥1000
electrified part of metal at bushing top
X Parameters of epoxy casting insulator
Greater than 3 times
1 Safety coefficient
of design voltage
Leakage current under 2 times of nominal
2 μA 50
phase‐phase voltage
3 The maximum field density under 1.1 times kV/mm ≤1.5

20
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


of nominal phase‐voltage
XI Bus parameters
1 Material Aluminum
2 Rated current A 2000
3 Rated short‐time withstand current/duration kA/s 40/3
4 Rated peak withstand current kA 100
Conductor diameter (inner diameter/outer
5 mm (30/60)
diameter)
XII Enclosure parameters
1 Material Aluminum alloy
Cast aluminum and
aluminum alloy: 5
times of the design
voltage;
2 Breakdown pressure for shell
Welded aluminum
shells and steel
shells: 3 times of the
design voltage
Test current A 1.0 Ir
Positions
K ≤30
contactable
Positions may
3 Temperature rise K ≤40
be contactable
Positions
cannot be K 65
contactable
Resistance of casing to be Current kA 40
4
burn‐through Time s 0.3
5 Erection of explosion‐proof membrane Yes
XIII Parameters of expansion joint
1 Material Stainless steel
≥ 30 years or 10,000
2 Service life
times of expansion
XIV Parameters for SF6 Gas
1 Humidity μg/g ≤8
2 Purity % ≥99.8

21
tgood.com TGQDMK000410
Modular Substation Technical Data

Part 3:
110kV Neutral Point Complete
Equipment for Service Transformer
Technical Data

22
tgood.com TGQDMK000410
Modular Substation Technical Data

1. Standard compliance

Standard No. Description of Standard

IEC 60038 Standard Voltage


GB1985‐89 AC High‐voltage Isolating Switch and Earthing Switches
GB 4585.2 AC system applies high‐voltage insulator artificial pollution test, cured layer
method
DL/T 620‐1997 Overvoltage Protection and Insulation Coordination for AC Electrical
Installations
GB 1208 Current transformer
IEC60071‐1:2011 Insulation Co‐ordination for High‐voltage Power Transmission and
Transformation Equipment
GB/T 775.3 ‐1987 Test Method for Insulators
GB5582‐1993 External Insulation Pollution Classes of High‐voltage Electric Power
Equipment
GB/T 7354 ‐1987 Measurement of Partial Discharge
GB/T 11604 Radio Interference Test for High‐voltage Electrical Equipment
‐1989
IEC 60060:2011 High‐voltage Test Techniques
GB 11032‐2000 Metal‐oxide Surge Arresters without Gaps for A.C. Systems
GB 50150‐2006 Standard for Hand‐over Test of Electric Equipment Electric Equipment
Installation Engineering
GB763 Heating of AC High‐voltage Apparatus under Long Runs
GB 191‐1990 Package, Storage and Transportation Identification Marks
GB311.1‐‐1997 Insulation Co‐ordination for High‐voltage Power Transmission and
Transformation Equipment
GB2706 Testing Methods for Dynamic and Thermal Stability Test of AC High‐voltage
Electrical Apparatus
GB5582 External Insulation Pollution Classes of High‐voltage Electric Power
Equipment
GB/T13540 Anti‐seismic Characteristic Test for High‐voltage Switchgear

DL/T620 Overvoltage Protection and Insulation Coordination for AC Electrical


Installations

2 Technical data

2.1 Operation overview of system


23
tgood.com TGQDMK000410
Modular Substation Technical Data
 Nominal voltage of system: 110kV
 Maximum voltage of system: 126kV
 System frequency: 50Hz, 60Hz
 Neutral point operation mode of system: Grounding through isolating switches
2.2 Technical data
 Equipment name and model: neutral point protection device of transformer,
JY‐JXC‐110
 Rated voltage of transformer: 110 kV
 Insulation level of transformer neutral point:
 1.2/50µS Lightning impulse full wave (peak value): 325 kV
 1min power‐frequency withstand voltage (effective value): 140 kV
 Type of the neutral point lightning arrester: YH1.5W‐72/186W
1. Rated frequency of lightning arrester: 50Hz
2. Rated voltage of lightning arrester: 72kV
3. Continuous operating voltage of lightning arrester: 58kV
4. Nominal discharge current: 1.5kA
5. Protection characteristic of the lightning arrester
 Residual voltage under steep current surge (peak value): ≤ kV
 Residual voltage at lightning impulse current (peak value): ≤ 186kV
 Residual voltage at switching impulse current (peak value): ≤ 174kV
6. DC 1mA reference voltage: ≮103kV
7. Leak current at 75% of DC 1mA reference voltage: ≯50 A
8.Frequency reference voltage (frequency reference current noted) 72kV (resistive
current peak value 1mA)
9. High current impulse withstand: 10kA (Residual voltage during high current
impulse can be provided)
10. Pressure release capacity
 Large current: 20kA
 Small current: 400A
11. Radio interference voltage is not greater than: 500V
12. Partial discharge is not greater than: 10pC
 Technical parameters of electrical equipment required by the discharge gap in main
neutral point: (Determined by parameters of neutral point lightning arrester by the
Supplier)
 Gap rated voltage: 83kV±5%
 Scope of gap electrode distance: 50mm~300mm (adjustable)
 Electrode configuration mode: sealed
 Electrode type: Spherical gap material: electroplating steel ball
 Isolating switch: 630A, electrical operating mechanism, auxiliary contacts (6
normally open contacts and 6 normally closed contacts) (silvering)
 Current transformer at neutral points of main transformer: 150/5A double winding
5P30/0, .5 (supply with main transformer, excluded in this supply)
 Integrate isolating switch, discharge gap, lightning arrester and gap current
transformer, and supply in complete set.

24
tgood.com TGQDMK000410
Modular Substation Technical Data
 Base material: hot galvanized steel; Fixing mode: bolt fixing, with equipment
support supplied in complete set by the supplier.
 Insulating articles and supporting pieces have moisture‐proof performance, to
maintain the dielectric strength unchanged. The equipment, of sound sealing, meets
long‐term outdoor operation conditions,
 The conductor section and type connecting to the transformer neutral point shall be
determined by the Demander.
 Provide factory documents such as inspection report and quality certificate during
products supplying
 Install current transformer at gap side: LJW1‐10 200/5A0.5/10P15, 15/15VA, type:
epoxy resin cast fully‐enclosed supporting 10kV

25
tgood.com TGQDMK000410
Modular Substation Technical Data

Part 4:
40.5kV House Technical Data

26
tgood.com TGQDMK000410
Modular Substation Technical Data

1.Standard compliance

Standard No. Description of Standard

3.6kV~40.5kV AC Metal‐enclosed Switchgear and Control Gear for


DL/T 404‐2007
Rated Voltages

DL/T 486‐2000 High‐voltage AC Isolating Switch and Grounding Switch

Common Specifications for High‐voltage Switchgear and Control Gear


IEC 62271‐1
Standards

GB 1207—2006 Voltage Transformer

GB 1208—2006 Current transformer

GB 1984—2003 High‐voltage AC Circuit Breaker

GB 1985—2004 High‐voltage AC Isolating Switch and Grounding Switch

3.6kV~40.5kV AC Metal‐enclosed Switchgear and Control Gear for


GB 3906—2006
Rated Voltages

GB 6450‐1986 Dry‐type Power Transformer

GB 11032—2000 Metal‐oxide Surge Arresters Without Gaps for A.C. Systems

GB 15166.2—2008 AC High‐voltage Fuse Part 2: Current Limiting Fuse

Standard for Hand‐over Test of Electric Equipment Electric Equipment


GB 50150—2006
Installation Engineering

Common Specifications for High‐voltage Switchgear and Control Gear


IEC 62271‐1
Standards

SD 318‐1989 Technical Conditions for Locking Device of High‐voltage Switchgear

IEC 62271‐100 High‐voltage AC Circuit Breaker

2. Technical data

S/N Items Unit Data Note


I Switchgear common parameter
Cable outgoing line 1250
1 Rated current A
Capacitor outgoing line 1250

27
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


Grounding transformer
1250
outgoing line
Busbar equipment 1250
DC220 / DC
Control circuit V
110
2 Power supply
AC 380/ AC
Auxiliary circuit V
220
3 Arc duration S 0.3~0.5
Overall dimension of
Equipment single switchgear (1600×600× Consult us
4 mm
dimension (Length  Width  2350) for details
Height)
II Parameters of the breaker

Switching no‐load No‐load transformer


MVA 10/20/31.5
1 transformer capacity capacity
at site No‐load exciting current A 0.5~15
Class C1:
CC1: 24×O,
CC2: 24×CO; BC1: 24×O,
Capacitive current BC2: 24×CO
2 switching test Class C2: Class C1/C2
(Laboratory) CC1: 48×O,
CC2: 24×O and 24×CO;
BC1: 24×O,
BC2: 80×CO
Motor voltage V AC 380/220
DC220/DC1
Rated operating voltage V
10
Closing operating
power supply DC220 V,
Steady‐state current of
A 2.5A or
each coil
DC110 V, 5A
DC220/DC1
Rated operating voltage V
3 10
Opening operating
power supply DC220V,
Steady‐state current of
A 2.5A or
each coil
DC110V, 5A
Quantity of protection coil Nr. 3
DC220 V,
Auxiliary contact Breaking capacity 2.5A or
DC110 V, 5A
III Parameters of earthing switch
Electric and
Operating Type
1 manual
mechanism
Motor voltage V AC 380/220

28
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note


DC220 V,
Auxiliary contact Breaking capacity 2.5A or
DC110 V, 5A
IV Parameters for current transformer
200~1250/1
Nominal current ratio
(5)
Winding 1 Rated burden VA 15/20/30
10P10/10P2
Accuracy class
0
200~1250/1
Nominal current ratio
(5)
Winding 2 Rated burden VA 15/20/30
10P10/10P2
Accuracy class
1 0
200~1250/1
Nominal current ratio
(5)
Winding 3 Rated burden VA 15/20/30
Accuracy class 0.5
200~1250/1
Nominal current ratio
(5)
Winding 4 Rated burden VA 15/20/30
Accuracy class 0.2S
V Parameters for voltage transformer
1 Rated capacity VA 20/50/100
VI Fuse parameter
1 Fuse type RNP‐0.5
2 Rate current of fuse A 0.5A
3 Rated short‐circuit breaking current for fuse kA 31.5kA
VIII Parameters of busbar

1 Rated current A 2000A

29
tgood.com TGQDMK000410
Modular Substation Technical Data

Part 5:
40.5kV Arc Suppression Coil
House
Technical Data

30
tgood.com TGQDMK000410
Modular Substation Technical Data

1. Standard compliance

Standard No. Description of Standard


Insulation Co‐ordination for High‐voltage Power Transmission and
IEC60071‐1:2011
Transformation Equipment
IEC 60060 High‐voltage Test Techniques
GB 8287.1 High‐voltage Pillar Porcelain Insulator
Standard for Hand‐over Test of Electric Equipment Electric Equipment
GB 50150
Installation Engineering
IEC 62271‐102 Alternating Current Disconnectors and Earthing Switches
GB10230 On‐load Tap‐changer
GB11032 Metal‐oxide Surge Arresters without Gaps for A.C. Systems
Metal‐enclosed Switchgear for Alternating Current at Rated Voltages of
IEC 62271‐200
Between 1 and 52 kV
GB1094.1~5 Power Transformer
GB1094.3 Insulation Levels, Dielectric Tests and External Clearances in Air
GB1094.11 Dry‐type Power Transformer
GB10229 Reactor
GB7328 Determination of Power Transformer and Reactor Sound Levels
GB7354 Partial Discharge Measurements
Guide to the Lightning Impulse and Switching Impulse Testing of Power
GB7449
Transformers and Reactors
GB/T13540 Anti‐seismic Characteristic Test
GB/T14549 Quality of Electric Energy ‐ Harmonics in Public Supply Network
GB/T17626.2~12 Electromagnetic Compatibility Testing and Measurement Techniques
Technical Specifications of Automatic Tracking and Compensation and
DL/T1057
Arc Suppression Coil Device
Overvoltage Protection and Insulation Coordination for AC Electrical
DL/T 620
Installations
IEC 62271‐103: Switches for Rated Voltages above 1 and Less Than 52 kV
IEC 60255 Measurement Relay and Protection Unit
IEC 60282‐2 High Voltage Fuses
IEC 61869‐2 Current Transformers
IEC 61869‐3 Voltage Transformers
IEC 60529 Defining the Protection Indices Provided by the Enclosures

IEC 62271‐206: Voltage Presence Indicating Systems

31
tgood.com TGQDMK000410
Modular Substation Technical Data

Regulations of Condition‐based Maintenance & Test for Electric


Q/GDW168
Equipment
SGCC Technical Standard for 10kV~66kV Arc Suppression Coil Devices
GJDWS [2004]
Anti‐accident Measures for 10kV~66kV Arc Suppression Coil Devices
No. 61
GJDWS [2006] Instructions on Technical Transformation of Arc Suppression Coil
No. 51 Devices

SGCC [2005] Technical Standard for 10kV~66kV Arc Suppression Coil Devices

2. Technical data

S/N Items Unit Value Note

1 Operating conditions Indoor

Rated voltage kV 40.5

Rated frequency Hz 50, 60

Power frequency (1min)


withstand voltage
(effective): 85kV
Insulation level kV Lightning full‐wave
impulse withstand
voltage (peak value):
200kV

2 Unit package Rated capacity of


arc suppression kVA 1800
coil

Rated current of
arc suppression A 0~81
coil

Measuring error
of capacitance % <±2
current

Residual current A ≤5

32
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Value Note

Neutral point
displacement ≯15% of nominal phase
voltage of the grid voltage
at mounting point

Arrival time of
ground ms Less than 10μs s
compensation

Incoming &
Cable
outgoing modes

Rated capacity kVA 1800

Rated current A 0~81

Adjusting mode Phase control

Regulating range 50~100%

Linearity range of
volt‐ampere 0~110%UN
characteristics

Type of Insulation Dry type (Class F)

Power frequency (1min)


withstand voltage
(effective): 85kV
Insulation level kV
3 Extinction coil Lightning impulse
withstand voltage (peak
value): 200kV

Not to
exceed 95K
Top oil under rated
operation
conditions.
Temperature‐rise
limit HV TGOOD
K winding specify
(Working
Condition)
Fuel tank,
iron core
and TGOOD
surface of specify
metal
structure

33
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Value Note

Winding
hot point

Continuous
operation time of
hour 2
rated current
(min.)

Self‐cooling (equipped
with temperature
Cooling mode display, control and
tele‐transmission
functions)

External
≥20 ≥20
insulation mm/kV
(indoor) (indoor)
creepage distance

Partial discharge pC < 3.6

0.3 m away from the


Noise dB
transformer body ≤ 50dB

Electrical life of
Not less than 200,000
switch contact on
times of movement
tap switch

Mechanical life
Not less than 800,000
switch contact on
times of movement
tap switch

High reliability, high


degree of integration,
dedicated computer or
Type
programming controller
for industrial use with
modular structure.
Control
4
Device DC220V or DC110V,
Rated voltage V reliable working voltage
range 75%~115%

Measuring error
of capacitance % ‐2 ~ +2
current

34
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Value Note

Measuring error
for neutral point
% ‐2 ~ +2
displacement
voltage

Recording times
of fault Times 500
information

Power frequency
kV 2
withstand voltage

Times of fault
Times ≥50
recording

Tuning‐off degree % ≤10

Neutral point
displacement ≯ 10% of nominal
voltage of the grid phase voltage
at mounting point

Functions of
man‐machine
interaction,
self‐checking, alarming,
printing, memory,
display,
tele‐transmission,
Main functions
on‐line running,
automatic blocking
(turn‐adjusting type),
hibernation, line
selection principle,
statistics and fault
recording.

Resistance value Ω Specify by TGOOD

Long‐time
Damping A Specify by TGOOD
working current
resistor
5
(Turns‐adjusting DC resistance
% ±2
type) allowable error

Short‐time
kA Specify by TGOOD
allowable current

35
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Value Note

Earth insulation MΩ >100

If turn‐adjusting type is
applied,
Line selection
6 Type Paralleled medium
device (options)
resistance shall be
selected.

Not less than IP20


7 Box outer cover Protection grade
(indoor)

36
tgood.com TGQDMK000410
Modular Substation Technical Data

Part 6:
17.5kV House
Technical Data

37
tgood.com TGQDMK000410
Modular Substation Technical Data

1. Standard compliance

 IEC 62271‐1: Clauses common to high voltage switchgear


 IEC 62271‐100: High voltage alternating current circuit‐breakers
 IEC 62271‐102: Alternating current disconnectors and earthing switches
 IEC 62271‐103: Switches for rated voltages above 1 and less than 52 kV
 IEC 62271‐200: Metal‐enclosed switchgear for alternating current at rated voltages of
between 1 and 52 kV
 IEC 60282‐2: High voltage fuses
 IEC 60255: Measurement relay and protection unit
 IEC 61869‐2: Current transformers
 IEC 61869‐3: Voltage transformers
 IEC 60529: Defining the protection indices provided by the enclosures
 IEC 62271‐206: Voltage Presence Indicating Systems (high voltage

2 Technical data

No Items Unit Data Note


I Switchgear common parameter
1 Structural Type CB middle rolling type
2 Rated voltage kV 17.5
3 Rated frequency Hz 50, 60
4 Rated current A 630‐3150
5 Temperature rise test 1.0Ir
Rated power‐frequency withstand
6 kV 38
voltage (1 min)
Peak value of rated lightning
7 impulse withstand voltage kV 95
(1.2/50s)
Rated short‐circuit breaking
8 kA 31.5
current
Rated short‐circuit making 82 at
9 kA 80
current (50Hz) 60Hz
Rated short‐time withstand
10 kA/s 31.5/3
current/duration
Rated peak withstand current 82 at
11 kA 80
(50Hz) 60Hz
Short‐time power‐frequency
12 withstand voltage of auxiliary and kV 2
control circuits
Testing
13 Partial discharge
voltage
kV 1.1×12/ 3

38
tgood.com TGQDMK000410
Modular Substation Technical Data

No Items Unit Data Note


Single
≤3
insulating part
Voltage pC
transformer
≤10
and current
transformer
Control circuit V DC220 / DC 110
14 Power supply Auxiliary
V AC 380/ AC 220
circuit
15 Service life Year ≥30
Overall
dimension of
single
650/800/1000x1560x230
switchgear
0
(Width 
Depth 
Equipment
16 Height) mm
dimension
Maximum
transportation
dimension
1200x1760x2500
(Width 
Depth 
Height)
Enclosure IP4X
Protection
17 Compartment
degree IP2X
s
Porcelain
DL
materials (To ≥216
standard
Creepage earth)
18 mm
distance Organic
DL
materials (To ≥240
standard
earth)
Clear distance between phases
19 and that between phase and mm ≥125
ground (air insulation)
Loss of service continuity
20 LSC‐2B
category
Insulating bush or fluidized
21 Heat shrinkable bushing
coating
Minimum clear distance from SMC
22 clapboard to insulating bush of mm ≥30
the connector or fluidized coating
23 Thickness of SMC clapboard mm ≥5
24 Thickness of cabinet wall mm ≥2
25 Layout of circuit breaker Withdrawable/ fixed

26 Racking truck mechanism Electric/ manual

39
tgood.com TGQDMK000410
Modular Substation Technical Data

No Items Unit Data Note


27 Cooling mode Self‐cooling/ air‐cooling

28 Heater power Specified by TGOOD

29 Internal arc classification kA, s AFLR,31.5kA, 1s

II Parameters of the breaker


1 Type Vacuum
2 Rated voltage kV 17.5
3 Rated frequency Hz 50, 60
4 Rated current A 630‐3150
5 Main circuit resistance μΩ ≤105
6 Temperature rise test 1.0Ir
Rated power‐frequency withstand
kV 38
voltage (1 min)
7 Peak value of rated lightning
impulse withstand voltage kV 95
(1.2/50s)
Effective value
of AC kA 31.5
component:
Time
Rated ms 45
constant:
8 short‐circuit
breaking current Electric
Times E2
endurance
First‐phase
breaking 1.5
factor
Rated short‐circuit making 82(60Hz
9 kA 80
current (50Hz) )
Rated short‐time withstand
10 kA/s 31.5/3
current/duration
Rated peak withstand current 82(60Hz
11 kA 80
(50HZ) )
12 Break time ms 60
13 Time for contact closing ms 2
14 Opening time ms 45
15 Closing time ms 70
17 Reclosing dead time ms 300
Average speed of Opening speed 0.27
18 opening and m/s
closing Closing speed 0.17

40
tgood.com TGQDMK000410
Modular Substation Technical Data

No Items Unit Data Note


19 Opening non‐synchronism ms 2
20 Closing non‐synchronism ms 2
M2 10000
21 Mechanical endurance
times
Feeder: O–0.3s–CO–180s–
CO
22 Rated operating sequence Power receiving and
subsection: O–180s–CO–
180s–CO
Short‐time power frequency
23 withstand voltage of auxiliary and kV 2
control circuits

Breaking test of out‐phase


3 /Double rated
24 short‐circuit breaking
grounding fault
current
Cable: 25,
Test current A
Capacitor bank: ≥400
Testing
voltage
kV 1.4×12/ 3
Class C1:
Capacitive CC1: 24×O,
current CC2: 24×CO;
25 BC1: 24×O,
switching test
(Laboratory) BC2: 24×CO
Class C2: Class C2
CC1: 48×O,
CC2: 24×O and
24×CO;
BC1: 24×O ,
BC2: 80×CO
Type or model of operating
Spring
mechanism
Three‐phase mechanical
Operating mode
linkage
CB charging motor voltage V DC 220
Rated
26 operating V DC220
voltage
Closing Allowable
operating power range of 85%~110%, 30% is not
supply operating allowed to be operated
voltage
Coil quantity
Nr. 1
of each phase

41
tgood.com TGQDMK000410
Modular Substation Technical Data

No Items Unit Data Note


Surge of each
A Specify by TGOOD
coil
Steady‐state
current of A DC220 V, 2.5A
each coil
Rated
operating V DC220
voltage
Allowable
range of 65%~110%, 30% is not
operating allowed to be operated
Opening voltage
operating power
Coil quantity
supply Nr. 1
of each phase
Surge current
A Specified by TGOOD
of each coil
Steady‐state
current of A DC220V, 2.5A
each coil
10 for normal open and 10
Quantity Pair
Standby for normal closed
auxiliary contact Breaking
DC220 V, 2.5A
capacity
Overhaul period Year ≥15
Energy storage time of spring
s ≤20
mechanism
Vacuum degree of vacuum arc
27 Pa ≤1.33×10‐3
extinguish chamber
III Parameters of Disconnector (if any)
1 Type TGOOD parts
2 Rated current A 630‐3150
3 Main circuit resistance μΩ ≤110
4 Current of temperature‐rise test A 1.0Ir

Rated Across
power‐frequenc isolating 48
distance kV
y withstand
5 voltage (1 min) To earth 42

Peak value of Across


rated lightning isolating kV 85
impulse distance

42
tgood.com TGQDMK000410
Modular Substation Technical Data

No Items Unit Data Note


withstand
voltage To earth 75
(1.2/50s)
Rated short‐time withstand
6 kA/s 40/4(31.5/4)
current/duration
7 Rated peak withstand current kA 100/80

Opening and Opening time ≤45


8 ms
closing time Closing time ≤70
Average speed of Opening speed ≥0.27
9 opening and m/s
closing Closing speed ≥0.17

10 Breaking capacitance current A 0.5


11 Breaking inductive current A 0.5
12 Mechanical endurance Times ≥3000
Type or model Manual
Motor voltage V DC220
Control
V DC220
voltage
Operating
mechanism Allowed
variation
85%~110%
13 scope of
voltage
Operating Three‐phase mechanical
mode linkage
Quantity Pair 10 NO 10NC
Standby
auxiliary contact Breaking
DC220 V, 2.5A
capacity
IV Parameters for earthing switch
Rated short‐time withstand
1 kA/s 31.5/4
current/duration
2 Rated peak withstand current kA 100/80
3 Rated making current kA 100/80
4 Rated on‐off frequency Times 2
5 Mechanical endurance Times ≥3000
Motor
Type Manual
optional
Operating
6 Motor voltage V AC 380/220
mechanism
Control
V DC220
voltage

43
tgood.com TGQDMK000410
Modular Substation Technical Data

No Items Unit Data Note


Allowed
variation
85%~110%
scope of
voltage
Operating Three‐phase mechanical
mode linkage
8 for normal open and 8 for
Quantity Pair
Standby normal closed
auxiliary contact Breaking
DC220 V, 2.5A
capacity
V Parameters of Current Transformer (CT)
1 Type Block or ring type

Nominal In terms of primary


current ratio drawings
Winding 1
Rated burden VA 20
Accuracy class 0.2S

Nominal In terms of primary


current ratio drawings
Winding 2
Rated burden VA 20
Accuracy class 0.5
2
Nominal In terms of primary
current ratio drawings
Winding 3
Rated burden VA 30
Accuracy class 10P20

Nominal In terms of primary


current ratio drawings
Winding 4
Rated burden VA 30
Accuracy class 10P20
VII Parameter of voltage transformer (VT) and fuse
1 Type Block type
10/√3: 0.1/√3: 0.1/√3:
2 Rated voltage ratio
0.1/3
3 Accuracy class 0.2/0.5/3P
4 Connection grade Yn/yn/yn/
5 Rated capacity VA 10/20/30
6 Three‐phase imbalance V 1
1min power frequency withstand
7 kV 2
voltage of low voltage winding

44
tgood.com TGQDMK000410
Modular Substation Technical Data

No Items Unit Data Note


1.2×rated continuous,
8 Rated voltage factor
1.9×rated 8h
9 Fuse type Specify by TGOOD

10 Rate current of fuse A Specify by TGOOD


Rated short‐circuit breaking
11 kA Specify by TGOOD
current for fuse
VII
Lightning arrester parameters
I
1 Type YH5WZ‐24/62 400A
2 Rated voltage kV 17.5
3 Continuous operating voltage kV 19.2
4 Nominal discharge current kA 5
Residual voltage peak at steep
5 kV ≤72
impulse current (5kA, 1/3μs)
Residual voltage peak under
k
6 lightning impulse current (5kA, ≤62
V
8/20μs)
Residual voltage peak at switching k
7 ≤52
impulse current (250A, 30/60μs) V
8 DC 1mA reference voltage kV ≥34
Leak current at 75% of DC 1mA
9 μA ≤ 50
reference voltage
Power‐frequency reference
10 kV 17.5
current (effective value)
Power‐frequency reference
11 mA 1
current (peak)
Full current mA ≤ 1.2
Continuous
12 Resistive
current μA ≤ 300
current
Long duration impulse withstand
13 A 400 (peak value)
current
4/10μs large impulse withstand
14 kA 65 (peak value)
current
15 Operating load 65kA, 2 times
Characteristics of power
16 frequency voltage withstand 1.2 Ur, 0.1s
duration
Absorption capability of kilovolt
17 kJ/kV 3.4
nominal voltage
18 Pressure release capacity kA/s 25/0.2

45
tgood.com TGQDMK000410
Modular Substation Technical Data

No Items Unit Data Note


IX Parameters for busbar
1 Material Copper
2 Rated current A 4000
Rated short‐time withstand
3 kA/s 40/3
current/duration
4 Rated peak withstand current kA 100

5 Section of conductor mm2 TGOOD specify

X Service transformer

1 Type Dry type


2 Capacity ≤4000

3 Rated voltage ratio 4.16kV‐24kV/120V‐600V

4 Impedance TGOOD specify

5 Connection symbol Dyn11, Yyn0

6 Full load efficiency ≥98%

46
tgood.com TGQDMK000410
Modular Substation Technical Data

Part 7:
17.5 kV Compensation House
Technical Data

47
tgood.com TGQDMK000410
Modular Substation Technical Data

1.Standard compliance

 IEC 60071‐1:2011 Insulation Co‐ordination for High‐voltage Power Transmission and

Transformation Equipment

 IEC 61869‐2 Current Transformer

 IEC 62271‐102 Alternating current disconnectors and earthing switches

 GB 1985 AC High‐voltage Isolating Switches and Earthing Switches

 GB 7354 Measurement of Partial Discharge

 GB 8287 High‐voltage Pillar Porcelain Insulator

 GB 11032 Metal‐oxide Surge Arresters without Gaps for A.C. Systems

 GB 50060 Design Code for High‐voltage Electrical Installation (3~110kV)

 GB 50227 Standard Design Code for Parallel‐connected Capacitor Package shall be

applicable to the unit

 GB 50260 Design Code of Seismic of Electrical Installations

 GB 15166.5 AC High‐voltage Fuse in Parallel Connection with External Protective

Fuse of the Capacitor

 GB/T 5582 External Insulation Pollution Classes of High‐voltage Electric Power

Equipment

 GB/T 11024 Parallel Capacitor for AC Electric Power System with Nominal Voltage

over 1kV

 GB/T 16927.1~16927.2 High‐voltage Testing Techniques

3 Technical data

S/N Items Unit Data Note

I Parameter of capacitor

1 Device type TBB10‐4800/400‐AKW

2 Rated voltage kV 10

48
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note

3 Rated capacity kVAR 4800

4 Rated reactance ratio % 5

5 Rated phase capacitance F 105.5

Rated voltage (phase) of the capacitor


6 kV 11/√3
bank

Deviation of capacitor bank capacitance


7 % 0~+5
and rated capacitance

Ratio of maximum value and minimum

8 value of each phase capacitance of ≤1.01

capacitor bank

Ratio of maximum capacitance and

9 minimum capacitance of each series TGOOD specify

section of capacitor bank

10 Connection method Single‐star structure

Series‐parallel number of each phase 1 for series and 4 for


11
capacitor parallel

Differential Protection of
12 Protection mode
Phase

Secondary calculation value of initial


13 TGOOD provides
unbalanced current (or voltage)

14 Setting value of relay protection TGOOD proposes

Allowable overvoltage times for

15 complete components for setting value 1.3

calculation of relay protection

16 Connection Diagram of Equipment TGOOD provides

17 Capacitor bank model Frame style

Direction and position of the incoming


18 Lower incoming line
line of capacitor bank

49
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note

Short‐circuit current endurance


19 kA 31,5kA
capacity of equipment

II Parameter of single capacitor

1 Type BAM 11/√3‐400‐1W

2 Rated voltage kV 11/√3

3 Rated capacity kvar 400

4 Design field intensity (K=1) kV/mm ≤57

pC Partial discharge≤ 50

Extinguishing voltage of

5 Partial discharge performance partial discharge is not


UN
less than 1.2 at the lower

temperature limit

6 Temperature type °C (See part1)

Bushing of roll‐on and

7 Bushing structure roll‐off integrated

structure

Requirements of the leading‐out


8 N ≥500 (horizontal pull)
terminal and bushing

9 Blasting energy endurance of capacitor kW·s ≥15

Discharging for 5 times in

10 minutes at the DC

10 Short‐circuit discharge test voltage of 2.5UN with

change of capacitance

less than 2%

Attached drawings and series and

11 parallel number of internal /

components of capacitor

12 Protection mode for single capacitor External fuse wire

50
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note

(Effective isolating

measures) shall be taken


13 Installation position of inner fuse wire
in the middle and end of

elements

Lower voltage limit ≤0.9

2 UN
14 Test of inner fuse wire
Upper voltage limit ≥2.2

2 UN

Allowable overvoltage times for


≤ 1.3times rated voltage
15 complete components of capacitor with
of elements
inner fuse wire

16 Performance of discharging device min/V 10min/75V

17 Installation mode of capacitor Horizontal configuration

III Parameter of discharge coil

1 Rated voltage of primary winding kV 11/√3

2 Rated voltage of secondary winding V 100

3 Rated capacity of secondary winding VA /

4 Accuracy class 0.5

Power frequency withstand voltage (1


kV/kV 42
min)/ testing voltage

Lightning impulse withstand voltage/


kV/kV 75
testing voltage
5
Interaction withstand voltage of
2.15Un/60s
primary winding

Earthing power frequency withstand kV/1mi


3
voltage of secondary winding n

6 Structure mode (See Part 1)

51
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note

7 Capacity of accessory capacitor (phase) kvar ≥1336

Voltage of capacitor bank

decrease from 2 UN to

less than 50V in 5s after

disconnecting the power


8 Discharge performance supply.

Discharge is not damaged

at allowable maximum

capacitance of 1.9UN of

capacitor bank

IV Metal Oxide Arrester

1 Rated voltage kV 17

2 Continuous operating voltage kV 13.6

3 Nominal discharge current kA 5

Residual voltage at nominal discharge


4 kV 46
current

2ms rectangular wave discharge


5 A ≥500
current capacity

Power frequency withstand voltage


(See optional technical
(power frequency/lightning) modified
6 kV/kV parameter table of
in terms of external insulation
project company)
elevation

V Post insulator of busbar

1 Rated voltage kV 10

2 Rated compressive strength N·m /

3 Creepage distance mm/kV (See part 1)

4 Withstand testing voltage (power kV/kV (See Part 1)

52
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note

frequency/lightning) modified in terms

of elevation

5 Installation method Front installation

VI Isolating Switches and earthing switches

1 Rated voltage kV 20

Short‐circuit current endurance


2 kA (3s) 31.5kA
capacity of equipment

(See optional technical


Short‐circuit current endurance
3 kA parameter table of
capacity of equipment
project company)

4 Rated current (Isolating Switch) A ≥400

(See optional technical

5 Type parameter table of

project company)

Withstand testing voltage (power See optional technical

6 frequency/lightning) modified in terms kV/kV parameter table of

of elevation project company)

VII Series reactor

1 Type Dry type

2 Rated voltage kV 10

3 Rated terminal voltage kV 0.32

4 Rated capacity kvar 240

5 Rated inductance mH Specif by TGOOD

6 Rated current A Specified by TGOOD

kW/kva
7 Loss Iron core ≤0.015
r

8 Temperature rise K ≤70

9 Reactance ratio % 5

53
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note

Insulation level (power frequency/


10 kV/kV 42/75
lightning)

11 Noise dB ≤50

12 Inductance deviation % 0~+5

Withstand testing voltage (power (See optional technical

13 frequency/lightning) modified in terms kV/kV parameter table of

of elevation project company)

Deviation of reactance

between value of each

14 Three‐phase inductance deviation % phase and average value

of three‐phase is not

more than ±2%

Three‐phase integration,

15 Installation layout mode semi‐iron core, stack

mounting

54
tgood.com TGQDMK000410
Modular Substation Technical Data

Part 8:
12kV Arc Suppression Coil
House Technical Data

55
tgood.com TGQDMK000410
Modular Substation Technical Data

1. Standard compliance
Standrad Description
IEC60071‐1:2011 Insulation Co‐ordination for High‐voltage Power Transmission and
Transformation Equipment
IEC60060 High‐voltage Test Techniques
GB 8287.1 High‐voltage Pillar Porcelain Insulator
GB 50150 Standard for Hand‐over Test of Electric Equipment Electric Equipment
Installation Engineering
GB 4208 Enclosure Protection Class (IP Code)
GB10230 On‐load Tap‐changer
GB11032 Metal‐oxide Surge Arresters without Gaps for A.C. Systems
GB 1208 Current Transformer
GB1094.1~5 Power Transformer
GB1094.3 Insulation Levels, Dielectric Tests and External Clearances in Air
GB1094.11 Dry‐type Power Transformer
GB10229 Reactor
GB7328 Determination of Power Transformer and Reactor Sound Levels
GB7354 Partial Discharge Measurements
GB7449 Guide to the Lightning Impulse and Switching Impulse Testing of Power
Transformers and Reactors
GB/T13540 Anti‐seismic Characteristic Test
GB/T14549 Quality of Electric Energy ‐ Harmonics in Public Supply Network
GB/T17626.2~12 Electromagnetic Compatibility Testing and Measurement Techniques
DL/T1057 Technical Specifications of Automatic Tracking and Compensation and
Arc Suppression Coil Device
DL/T 620 Overvoltage Protection and Insulation Coordination for AC Electrical
Installations
Q/GDW168 Regulations of Condition‐based Maintenance & Test for Electric
Equipment
SGCC Technical Standard for 10kV~66kV Arc Suppression Coil Devices
GJDWS [2004] Anti‐accident Measures for 10kV~66kV Arc Suppression Coil Devices
No. 61
GJDWS [2006] Instructions on Technical Transformation of Arc Suppression Coil Devices
No. 51
SGCC (2005) Technical Standard for 10kV~66kV Arc Suppression Coil Devices

56
tgood.com TGQDMK000410
Modular Substation Technical Data

2 Technical data

S/N Items Unit Data Note

1 Operating conditions Indoor

Rated voltage kV 12

Rated
Hz 50
frequency

Power frequency (1min)


withstand voltage (effective):
35kV
Insulation level kV
Lightning full‐wave impulse
withstand voltage (peak
value): 75kV

Rated capacity
of arc
kVA 400
suppression
coil

Rated current
of arc
A 50
suppression
2 Unit package coil

Measuring
error of
% ‐2~+2
capacitance
current

Residual
A ≤5
current

Neutral point
displacement
≯15% of nominal phase
voltage of the
voltage
grid at
mounting point

Arrival time of
ground ms Less than 60
compensation

Incoming &
Cable
outgoing modes

57
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note

10.5 (/0.4 kV)


Rated voltage kV (Equipped with secondary
coil)

Capacity of
grounding kVA 630
transformer

Capacity of
secondary coil
(doubles as kVA 200
house
transformer)

Zero sequence
Ω/phase ≤9
reactance

connection
group and the
grade number
of connection
ZN, yn11
group (only for
connection
Earthing with secondary
3 winding)
transformer

Type of
Dry type (Class F)
Insulation

Power frequency (1min)


withstand voltage (effective):
35kV
Insulation level kV
Lightning full‐wave impulse
withstand voltage (peak
value): 75kV

Temperature Not to exceed 100K under


K
rise rated operation conditions.

Self‐cooling (equipped with


temperature display, control
Cooling mode
and tele‐transmission
functions)

External
insulation ≥20
mm/kV ≥30 (outdoor)
creepage (indoor)
distance

58
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note

Partial
pC <5
discharge

0.3 m away from the


Noise dB
transformer body ≤ 55

Rated capacity kVA 400

Rated current A 50

Adjusting mode Phase control type

Regulating
50~100%
range

Type of
Dry type (Class F)
insulation

Linearity range
of volt‐ampere 0~110%Un
characteristics

Power frequency (1min)


withstand voltage (effective):
35kV
Insulation level kV
4 Extinction coil Lightning full‐wave impulse
withstand voltage (peak
value): 75kV

Temperature Not to exceed 100K under


K
rise rated operation conditions.

Continuous
operation time
h 2
of rated current
(min.)

Self‐cooling (equipped with


temperature display, control
Cooling mode
and tele‐transmission
functions)

External
insulation
mm/kV ≥20 (indoor)
creepage
distance

59
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note

Partial
pC <5
discharge

0.3 m away from the


Noise dB
transformer body ≤ 55

Electrical life of
Not less than 200,000 times
switch contact
of movement
on tap switch

Mechanical life
Not less than 800,000 times
switch contact
of movement
on tap switch

High reliability, high degree of


integration, dedicated
Type computer or programming
controller for industrial use
with modular structure.

DC220V or DC110V , reliable


Control voltage V working voltage range
75%~115%

Measuring
error of
% ‐2~+2
capacitance
current

Control Measuring
5
equipment error for
neutral point % ‐2~+2
displacement
voltage

Recording
times of fault Times 500
information

Power
frequency
kV 2
withstand
voltage

Times of fault
Times ≥50
recording

60
tgood.com TGQDMK000410
Modular Substation Technical Data

S/N Items Unit Data Note

Tuning‐off
% ≤10
degree

Neutral point
displacement
≯15% of nominal phase
voltage of the
voltage
grid at
mounting point

Functions of man‐machine
interaction, self‐checking,
alarming, printing, memory,
display, tele‐transmission,
on‐line running, automatic
blocking (turn‐adjusting
Main functions
type), hibernation, line
selection principle, statistics
and fault recording;
IEC‐61850 protocol interface
is required for Intelligent
Substation.

Long‐time
working A 10
current
Damping
resistor
6 DC resistance
(Turns‐adjusting % ±2
allowable error
type)
Earth
MΩ >100
insulation

If turn‐adjusting type is
Line selection applied, line selection device
7 Type
device (options) of paralleled medium
resistance shall be selected.

Protection Not less than IP20


8 Box outer cover
grade (Indoor)

61
tgood.com TGQDMK000410
Modular Substation Technical Data

Part 9:
Power Transformer House
Technical Data

62
tgood.com TGQDMK000410
Modular Substation Technical Data

1. Standard compliance
Standard Description

IEC60038 Standard Voltage


IEC 60076 Power Transformers
IEC 62271‐102 Alternating Current Disconnectors and Earthing Switches
GB 4585.2 Artificial Pollution Test Methods of Composite Insulator
GB 1208 Current Transformer
IEC60071‐1:2011 Insulation Co‐ordination for High‐voltage Power Transmission and
Transformation Equipment
GB/T 775.3‐1987 Insulator Test Method
GB5582‐1993 External Insulation Pollution Classes of High Voltage Electric Power
Equipments
IEC 60270 High‐Voltage Test Techniques – Partial Discharge Measurements
GB/T 11604‐1989 Test Methods for Measuring Radio Interference for High Voltage
Equipment
IEC 60060 High‐voltage Test Techniques
IEC 60099 Surge Arresters
GB 50150‐2006 Standard for Hand‐over Test of Electric Equipment Installation...
ISO780‐1985 Packaging‐Pictorial Markings for Handling of goods

2. Power transformer technical data

Refer to transformer data from supplier.

63
tgood.com TGQDMK000410
Modular Substation Technical Data

Part 10:
Secondary House
Technical Data

64
tgood.com TGQDMK000410
Modular Substation Technical Data
See dedicated document <Secondary House Technical Data>

65
tgood.com TGQDMK000410
Modular Substation Technical Data

66
tgood.com TGQDMK000410