Lecture 1-2
Lecture 1-2
0.85 f c Ag Dc S f sy f sy
1
s s
8.20 Ac 4 Dc S 4
or,
0.41 f c Ag
s
f sy A 1 (15)
c
The constant in the previous equation is replaced by 0.45 to get the equation given in ACI 9.10.3.
0.45 f c Ag
And 1 (16)
s
f sy Ac
Combining equations (14) and (16), the pitch of the spiral S is given as
4 as
S (17)
A f
0.45 Dc g 1 c
Ac f sy
Pu As f y (18)
where is the strength reduction factor for axial tension = 0.90, and As is the area of column
reinforcement.
Design Considerations
Maximum and Minimum Reinforcement Ratios
ACI Code 10.9.1 specifies that a minimum reinforcement ratio of 1 % is to be used in tied or
spirally reinforced columns. This minimum reinforcement is needed to safeguard against any
bending, reduce the effect of shrinkage and creep and enhance ductility of columns. Maximum
reinforcement ratio is limited to 8 % for columns in general to avoid honeycombing of concrete.
For compression member with a cross section larger than required by consideration of loading,
ACI Code 10.8.4 permits the minimum area of steel reinforcement to be based on the gross
sectional area required by analysis. The reduced sectional area is not to be less than one half the
actual cross sectional dimensions. In regions of high seismic risk, ACI Code 10.8.4 is not
applicable.
10
Minimum Number of Reinforcing Bars
ACI Code 10.9.2 specifies a minimum of four bars within rectangular or circular sections; or one
bar in each corner of the cross section for other shapes and a minimum of six bars in spirally
reinforced columns.
Clear Distance between Reinforcing Bars
ACI Code 7.6.3 and 7.6.4 specify that for tied or spirally reinforced columns, clear distance
between bars, shown in Figure 8, is not to be less than the larger of 1.50 times bar diameter or 4
cm. This is done to ensure free flow of concrete among reinforcing bars. The clear distance
limitations also apply to the clear distance between lap spliced bars and adjacent lap splices since
the maximum number of bars occurs at the splices.
Bundled Bars
For isolated situations requiring heavy concentration of reinforcement, bundles of standard bar
sizes can save space and reduce congestion for placement and compaction of concrete. Bundling
of parallel reinforcing bars in contact is permitted but only if ties enclose such bundles.
According to ACI Code 7.6.6, groups of parallel reinforcing bars bundled in contact to act as one
unit are limited to four in any one bundle, as shown in Figure 9.b.
(a) (b)
Figure 12: Beams on all column faces
Spirals
Spiral reinforcement must extend from the top of footing or slab in any story to the level of the
lowest horizontal reinforcement in slabs, drop panels, or beams above. If beams or brackets do
not frame into all sides of the column, ties must extend above the top of the spiral to the bottom of
the slab or drop panel, shown in Figure 13.
(a) (b)
Figure 13: Beams on all column faces
16
Design Procedure for Short Axially Loaded Columns
1. Evaluate the factored axial load Pu acting on the column.
2. Decide on a reinforcement ratio g that satisfies ACI Code limits. Usually a 1 % ratio is
chosen for economic considerations.
3. From equations (8) or (9) for tied and spirally reinforced columns respectively, determine the
gross sectional area Ag of the concrete section.
4. Choose the dimensions of the cross section based on its shape. For rectangular sections, the
ratio of the longer to shorter side is recommended to not exceed 3.
5. Readjust the reinforcement ratio by substituting the actual cross sectional area in Equations
(8) or (9). This ratio has to fall within the specified code limits.
6. Calculate the needed area of longitudinal reinforcement ratio based on the adjusted reinforced
ratio and the chosen concrete dimensions.
7. From reinforcement tables, choose the number and diameters of needed reinforcing bars. For
rectangular sections, a minimum of four bars is needed, while a minimum of six bars is used
for circular columns.
8. Design the lateral reinforcement according to the type of column, either ties or spirals, as
explained in the previous sections of this chapter.
9. Check whether the spacing between longitudinal reinforcing bars satisfies ACI Code
requirements.
10. Draw the designed section showing concrete dimensions and with required longitudinal and
lateral reinforcement.
Example (1):
The cross section of a short axially loaded tied column is shown in Figure 14. It is reinforced with
6 16 mm bars.
Calculate the design load capacity of the cross section. Use f c = 280 kg/cm2 and f y = 4200
kg/cm2.
40 2 4 2 0.80 3 1.60
Clear distance between bars = 12.80 cm
2
Since the clear distance between bars is less than 15 cm, only one tie is required for the cross
section.
The spacing between ties is not to exceed the smallest of
16 (1.6) = 25.60 cm
48 (0.80) = 38.40 cm
25 cm
8 mm ties spaced @ 25 cm (one set, since only corner bars are used).
Thus, ACI requirements regarding reinforcement ratio, clear distance between bars and tie
spacing are all satisfied.
Substituting in Equation (6)
Pu 0.52 0.85 f 'c Ag AS As f y
Pu 0.52 / 1000 0.85 280 40 25 12.10 12.10 4200
Pu 148.69 ton
Example (2):
The cross section of a short axially loaded tied column is shown in Figure 14. It is reinforced with
6 16 mm bars.
Calculate the design tensile load capacity of the cross section. Use f c = 280 kg/cm2 and f y =
4200 kg/cm2.
Solution:
4200
Pu As f y 0.90 12.10 45.74 tons
1000
Example (3):
Design a short tied column to support a factored concentric load of 80 tons, with one side of the
cross section equals to 25 cm.
Use f c = 280 kg/cm2, f y = 4200 kg/cm2 and g 1%.
Solution:
1- The factored load Pu is given as 80 tons.
18
2- The reinforcement ratio g is given as 1%.
3- From Equation (8), determine the gross sectional area Ag of the concrete section:
Pu 0.52 Ag 0.85 f ' c g f y 0.85 f ' c
80 ,000 0.52 Ag 0.85 280 0.01 4200 0.85 280
Ag 554.16 cm 2
7- From reinforcement tables, choose the number and diameters of needed reinforcement:
use 4 14 mm A s 6.16 cm 2
10- The designed cross section together with needed longitudinal and lateral reinforcement
is shown in Figure 15.
19
Example (4):
Design a short, spirally reinforced column to support a service dead load of 45 tons and a service
live load of 60 tons.
Use f c = 280 kg/cm2, f y = 4200 kg/cm2.and g 1%.
Solution:
1- Pu 1.20 PD 1.60 PL = 1.20 (45) + 1.6 (60) = 150 tons
2- The reinforcement ratio g is given as 1%.
3- From equation (10.19.b), determine the gross sectional area Ag of the concrete section:
Ag 847.54 cm 2
7- From reinforcement tables, choose the number and diameters of needed reinforcement:
use 7 14 mm ( As 10.78 cm2 )
8- Design the needed spiral:
From Equation (16) and trying 8 mm spiral,
Dc 35 4 4 27 cm
20
4 as
S
Ag f c
0.45 Dc 1
A f
c sy
4 0.50
S 3.63 cm
/ 4 35 2 280
0.45 27 1
/ 4 27
2
4200
10- The designed cross section together with needed longitudinal and lateral reinforcement
is shown in Figure 16.