S&C Source-Transfer PMH Pad-Mounted Gear- Detailed Functional Specification Guide (2)
S&C Source-Transfer PMH Pad-Mounted Gear- Detailed Functional Specification Guide (2)
1.0 GENERAL
1.01 The pad-mounted gear shall be in accordance with the single-line diagram, and shall conform
to the following specification.
1.02 The pad-mounted gear shall consist of a single self-supporting enclosure, containing
interrupter switches and power fuses with the necessary accessory components, including
sensing, controls, and control power supply, all completely factory-assembled and
operationally checked.
1.03 Ratings
The ratings for the integrated pad-mounted gear shall be as designated below. (Select values
from the table on page 2.)
Nominal Voltage, kV. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
Maximum Voltage, kV. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
BIL Voltage, kV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
Short-Circuit
Peak Withstand Current, Amperes, Peak. . . . . . . . . . . . . . . . . . . _________________
One-Second Short-Time Withstand Current,
Amperes, RMS, Symmetrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
MVA, Three-Phase Symmetrical,
at Rated Nominal Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
Main Bus
Continuous Current, Amperes . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
Peak Withstand Current, Amperes, Peak. . . . . . . . . . . . . . . . . . . _________________
One-Second Short-Time Withstand Current,
Amperes, RMS, Symmetrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______________
Three-Pole Interrupter Switches
Continuous Current, Amperes . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
Load Dropping Current, Amperes. . . . . . . . . . . . . . . . . . . . . . . . . _________________
Peak Withstand Current, Amperes, Peak. . . . . . . . . . . . . . . . . . . _________________
One-Second Short-Time Withstand Current,
Amperes, RMS, Symmetrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
Three-Time Duty-Cycle Fault-Closing Current,
Amperes, RMS, Symmetrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
Fuses with Integral Load Interrupters
Maximum Current, Amperes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
Load Dropping Current, Amperes. . . . . . . . . . . . . . . . . . . . . . . . . _________________
Duty-Cycle Fault-Closing Current Capability,
Amperes, RMS, Symmetrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
(b) Article 490.21(e) in the National Electrical Code, which specifies that the interrupter
switches in combination with power fuses shall safely withstand the effects of closing,
carrying, and interrupting all possible currents up to the assigned maximum short-circuit
rating.
(c) All portions of ANSI, IEEE, and NEMA standards applicable to the basic switch and fuse
components.
The following optional feature should be specified as required:
(d) Canadian Standards Association listing.
1.06 Enclosure Design
(a) To ensure a completely coordinated design, the pad-mounted gear shall be constructed in
accordance with the minimum construction specifications of the fuse and/or switch manu-
facturer to provide adequate electrical clearances and adequate space for fuse handling.
(b) In establishing the requirements for the enclosure design, consideration shall be given to
all relevant factors such as controlled access, tamper resistance, and corrosion resistance.
(i) Enclosure top side edges shall overlap with roof side edges to create a mechanical maze
which shall allow ventilation of high-voltage compartments to help keep the enclosure
interior dry while discouraging tampering or insertion of foreign objects.
(j) A heavy coat of insulating “no-drip” compound shall be applied to the inside surface of the
roof to minimize condensation of moisture thereon.
(k) Insulating interphase and end barriers of NEMA GPO3-grade fiberglass-reinforced polyes-
ter shall be provided for each interrupter switch and each set of fuses where required to
achieve BIL ratings. Additional insulating barriers of the same material shall separate the
front compartments from the rear compartments and isolate the tie bus.
(l) Full-length steel barriers shall separate side-by-side compartments.
(m) Interrupter switches shall be provided with dual-purpose front barriers. These barriers, in
their normal hanging positions, shall guard against inadvertent contact with live parts. It
shall also be possible to lift these barriers out and insert them into the open gap when the
switch is open. These barriers shall meet the requirements of Section 381G of the National
Electrical Safety Code (ANSI Standard C2).
(n) Interrupter switches shall be provided with window panels to allow viewing of the switch
position without removing the dual-purpose front barriers. Window panels shall be remov-
able to facilitate phasing and shall be secured to the enclosure with stainless-steel or
zinc-nickel plated hardware.
(o) Each fuse shall be provided with a dual-purpose front barrier. These barriers, in their
normal hanging positions, shall guard against inadvertent contact with live parts. It shall
also be possible to lift these barriers out and insert them into the open gaps when the fuses
are in the disconnect position. These barriers shall meet the requirements of Section 381G
of the National Electrical Safety Code (ANSI Standard C2).
(p) The low-voltage control compartment shall be provided with an instruction manual holder.
(q) Lifting tabs shall be removable. Sockets for the lifting-tab bolts shall be blind-tapped. A
resilient material shall be placed between the lifting tabs and the enclosure to help prevent
corrosion by protecting the finish against scratching by the tabs. To further preclude
corrosion, this material shall be closed-cell to prevent moisture from being absorbed and
held between the tabs and the enclosure in the event that lifting tabs are not removed.
The following optional feature should be specified as required:
(r) To guard against corrosion due to extremely harsh environmental conditions, the entire
exterior of the enclosure shall be fabricated from 11-gauge Type 304 stainless steel.
(s) Inner barrier panels that meet the Rural Utility Service requirements for “dead-front” and
the requirements of Section 381G of the National Electrical Safety Code (ANSI Standard
C2) shall be provided—one for each door opening providing access to high voltage. These
panels shall be secured in place with recessed pentahead bolts. When so secured, they shall
guard against inadvertent contact with live parts.
(t) A steel (compartmented, noncompartmented) base spacer shall be provided to increase
the elevation of live parts in the pad-mounted gear above the mounting pad by (6, 12, 18,
24) inches.
3.02 Doors
(a) Doors shall be constructed of 11-gauge hot-rolled, pickled and oiled steel sheet.
(b) Doors providing access to high voltage shall have door-edge flanges that overlap with door-
opening flanges, and shall be formed to create a mechanical maze that shall guard against
water entry and discourage tampering or insertion of foreign objects, but shall allow ventila-
tion to help keep the enclosure interior dry.
(c) Doors providing access to the low-voltage control compartment shall have 90-degree flanges
providing a deep overlap with the door openings. To keep low-voltage components clean and
dry, these doors shall be fully gasketed.
(d) Doors shall have a minimum of two extruded-aluminum hinges with stainless-steel hinge
pins, and interlocking extruded-aluminum hinge supports for the full length of the door to
provide strength, security, and corrosion resistance. Mounting hardware shall be stainless
steel or zinc nickel-plated steel, and shall not be externally accessible to guard against
tampering.
(e) In consideration of controlled access and tamper resistance, each set of double doors shall
be equipped with an automatic three-point latching mechanism.
(1) The latching mechanism shall be spring-loaded, and shall latch automatically when
the door is closed. All latch points shall latch at the same time to preclude partial
latching.
(2) A pentahead socket wrench or tool shall be required to actuate the mechanism to
unlatch the door and, in the same motion, recharge the spring for the next closing
operation.
(3) The latching mechanism shall have provisions for padlocking that incorporate a
means to protect the padlock shackle from tampering and that shall be coordinated
with the latches such that:
(i) It shall not be possible to unlatch the mechanism until the padlock is
removed, and
(ii) It shall not be possible to insert the padlock until the mechanism is com-
pletely latched closed.
(f) Doors providing access to solid-material power fuses shall have provisions to store spare
fuse units or refill units.
(g) Each door shall be provided with a zinc-nickel-plated steel door holder located above the
door opening. The holder shall be hidden from view when the door is closed, and it shall
not be possible for the holder to swing inside the enclosure.
3.03 Ventilation Openings
(a) Rain-resistant vents shall be provided on doors providing access to the low-voltage control
compartment.
(b) Each vent shall have an inside screen and baffle to protect against insertion of foreign
objects.
3.04 Finish
(a) Full coverage at joints and blind areas shall be achieved by processing enclosures indepen-
dently of components such as doors and roofs before assembly into the unitized structures.
(b) All exterior seams shall be filled and sanded smooth for neat appearance.
(c) To remove oils and dirt, to form a chemically and anodically neutral conversion coating to
improve the finish-to-metal bond, and to retard underfilm propagation of corrosion, all
surfaces shall undergo a thorough pretreatment process comprised of a fully automated
system of cleaning, rinsing, phosphatizing, sealing, drying, and cooling before any protective
coatings are applied. By utilizing an automated pretreatment process, the enclosure shall
receive a highly consistent thorough treatment, eliminating fluctuations in reaction time,
reaction temperature, and chemical concentrations.
(d) After pretreatment, protective coatings shall be applied that shall help resist corrosion and
protect the steel enclosure. To establish the capability to resist corrosion and protect the
enclosure, representative test specimens coated by the enclosure manufacturer’s finishing
system shall satisfactorily pass the following tests:
(1) 4000 hours of exposure to salt-spray testing per ASTM B 117 with:
(i) Underfilm corrosion not to extend more than 1/32 in. from the scribe, as
evaluated per ASTM D 1645, Procedure A, Method 2 (scraping); and
(ii) Loss of adhesion from bare metal not to extend more than 1/8 from the
scribe.
(2) 1000 hours of humidity testing per ASTM D 4585 using the Cleveland Condensing
Type Humidity Cabinet, with no blistering as evaluated per ASTM D 714.
(3) 500 hours of accelerated weathering testing per ASTM G 53 using lamp UVB-313,
with no chalking as evaluated per ASTM D 659, and no more than 10% reduction of
gloss as evaluated per ASTM D 523.
(4) Crosshatch-adhesion testing per ASTM D 3359 Method B, with no loss of finish.
(5) 160-inch-pound impact, followed by adhesion testing per ASTM D 2794, with no
chipping or cracking.
(6) 3000 cycles of abrasion testing per ASTM 4060, with no penetration to the substrate.
Certified test abstracts substantiating the above capabilities shall be furnished upon
request.
(e) After the finishing system has been properly applied and cured, welds along the enclosure
bottom flange shall be coated with a wax-based anticorrosion moisture barrier to give these
areas added corrosion resistance.
(f) A resilient closed-cell material, such as PVC gasket, shall be applied to the entire underside of
the enclosure bottom flange to protect the finish on this surface from scratching during
handling and installation. This material shall isolate the bottom flange from the alkalinity of a
concrete foundation to help protect against corrosive attack.
(g) After the enclosure is completely assembled and the components (switches, fuses, bus, etc.)
are installed, the finish shall be inspected for scuffs and scratches. Blemishes shall be
touched up by hand to restore the protective integrity of the finish.
(8) All arcing accompanying solid-material power fuse operation shall be contained
within the fuse, and all arc products and gases evolved shall be effectively con-
tained within the exhaust control device during fuse operation.
(9) Solid-material power fuses shall be equipped with a blown-fuse indicator that shall
provide visible evidence of fuse operation while installed in the fuse mounting.
(b) Electronic Power Fuses
(1) Electronic power fuses shall utilize an expendable interrupting module and a
reusable control module.
(i) The interrupting module shall consist of a main-current section and a
fault-interrupting section. These sections shall be arranged coaxially and
contained within the same housing.
(ii) The main-current section shall carry current under normal operating
conditions.
(iii) The fault-interrupting section shall operate only under fault conditions. It
shall not carry current continuously and shall not determine the minimum
operating time-current characteristic curve shape.
(iv) The current-limiting-section fusible element shall not be subject to damage
due to current surges.
(v) All arc accompanying operation of the electronic power fuse shall be
contained within the interrupting module and fuse operation shall be silent,
without any exhaust.
(vi) The control module shall continuously monitor the line current through an
electronic sensing circuit.
(vii) The electronic components shall be located within a cylindrical cast-alumi-
num housing that shall serve as both a path for continuous current and as a
shield to protect the electronic components against interference from
external electric fields.
(iix) To prevent damage to the control-module circuits by surges (such as due to
lightning or inrush currents), the control module shall be free of external
control wiring and connections to ground, and shall incorporate a device
that acts as a buffer to isolate the electronic components at a level of cur-
rent well below their surge-withstand capability.
(ix) The control module shall be factory-sealed to assure a dry, contaminant-free
environment for the electronic components.
(x) The control module shall be self-powered with the capability to supply
power for operating the sensing logic circuits and to actuate the interrupt-
ing module when a fault occurs.
(xi) The control module shall include one or more integrally mounted current
transformers to provide both the sensing signal and the control power.
(xii) The current transformer used to provide control power shall be designed to
act as a buffer against surges in the line by saturating at a level of current
well below the surge-withstand capability of the electronic components.
(xiii) No leads (including coaxial leads) between the current transformers and
the electronic components shall be exposed.
(2) To ensure the integrity of the electrical connection between the interrupting and
control modules is independent of the mechanical force with which the modules
are joined, the connection shall be through a louvered ring-type sliding contact.
(3) Electronic power fuses shall be equipped with a blown-fuse indicator that shall
provide visible evidence of fuse operation while installed in the fuse mounting.
Fuse mountings shall be of the disconnect style.
(4) It shall not be necessary to replace unblown companion interrupting modules
following operation of an electronic power fuse.
(5) Electronic power fuses shall have time-current characteristics that are permanently
accurate. Time-current characteristics shall be available which permit coordination
with source-side and load-side protective relays, automatic circuit reclosers, and
other fuses.
(6) Mountings for electronic power fuses shall also accommodate current-limiting
fuses.
(c) Fuse-mounting jaw contacts shall incorporate an integral load interrupter that shall permit
live switching of fuses with a hookstick.
(1) The integral load interrupter housing shall be of a thermoplastic material.
(2) The integral load interrupter shall be in the current path continuously. Auxiliary
blades or linkages shall not be used.
(3) Live switching shall be accomplished by a firm, steady opening pull on the fuse
pull-ring with a hookstick. No separate load-interrupting tool shall be required.
(4) The integral load interrupter shall require a hard pull to unlatch the fuse, reducing
the possibility of an incomplete opening operation.
(5) Internal moving contacts of the integral load interrupter shall be self-resetting after
each opening operation, permitting a closing operation to be performed
immediately.
(6) Circuit interruption shall take place completely within the integral load interrupter
with no external arc or flame.
(7) The integral load interrupter and the fuse shall be provided with separate fault-clos-
ing contacts and current-carrying contacts. The fuse hinge shall be self-guiding and,
together with the fault-closing contacts, shall guide the fuse into the current-carry-
ing contacts during closing operations. Circuit-closing inrush currents and fault
currents shall be picked up by the fault-closing contacts, not by the current-carry-
ing contacts or interrupting contacts.
(8) Integral load interrupters for fuses for 14.4 kV rated pad-mounted gear shall have a
three-time duty-cycle fault-closing capability equal to the interrupting rating of the
fuse. Integral load interrupters for fuses for 25 kV rated pad-mounted gear shall
have a two time duty-cycle fault-closing capability equal to the interrupting rating
of the fuse. The duty-cycle fault-closing capability defines the level of available fault
current into which the fuse can be closed the specified number of times (twice or
(g) Stored-energy operators shall be provided with a charging shaft and a removable manual
charging handle to allow manual charging of the quick-make quick-break mechanism in the
event control power is lost. The manual charging shaft shall be accessible only when the
operation selector is in the “charging” position.
(h) Stored-energy operators shall be equipped with provisions for local mechanical trip-open
and trip-closed operation in the event control power is lost.
(i) Stored-energy operators shall be located in a grounded, steel-enclosed low-voltage control
compartment. The control compartment shall provide complete isolation from high voltage
to help protect operating personnel.
(j) Stored-energy operators shall be equipped with indicators to show whether the quick-make
quick-break mechanism is charged or discharged; whether the associated source inter-
rupter switch is in the open or closed position; and whether the stored-energy operator is in
the switch-open or switch-closed position.
(k) Each stored-energy operator shall be equipped with an operation counter.
(l) Stored-energy operators shall be provided with a decoupling feature, permitting decou-
pling of the stored-energy operator from the associated source interrupter switch for
testing and exercising of the stored-energy operator and source-transfer control without
opening or closing the interrupter switch and without exposure to high voltage. A tool shall
not be required for decoupling or coupling the switch and switch operator. An indicator
shall be provided to show whether the operator is coupled or decoupled. When the stored-
energy operator is decoupled, the associated source interrupter switch shall be locked in
the position it was in at the time of decoupling. It shall not be possible to recouple the
stored-energy operator to the source interrupter switch unless the stored-energy operator
is in the same position (open or closed) as the source interrupter switch.
The following optional features should be specified as required:
(m) Stored-energy operators shall be provided with an extra 4-PST auxiliary switch coupled to
each source interrupter switch.
(n) Stored-energy operators shall be provided with an extra 4-PST auxiliary switch coupled to
each stored-energy operator.
(o) Mechanical cable interlocks shall be provided between each stored-energy operator and
the associated switch-compartment door to prevent operation of the source interrupter
switch when the associated compartment door is open.
(p) A receptacle shall be provided for attachment of a remote-control station to allow electri-
cal trip-open and trip-closed operation from an adjacent area.
4.04 Source-Transfer Control
(a) Operating Description
(1) Transfer on Loss and Return of Source Voltage
(4) A light-emitting diode lamp shall be furnished for indicating that both stored-energy
operators are coupled to their respective interrupter switches and in the correct
positions, the control is in the automatic mode, the operation selector for each
stored-energy operator is in the operating position, and all control circuitry is
properly connected for automatic transfer. The display specified in 4.04 (b) (2),
when not being used to show menu information, shall show messages explaining
why this lamp is not lighted.
(5) A selector switch shall be furnished for choosing manual or automatic operating
mode. In the manual mode, local electrical trip-open and trip-closed operation by
means of push buttons shall be enabled while automatic switching shall be
inhibited.
(6) Test keys shall be furnished for simulating loss of voltage on each of the two
sources, as well as for checking the functioning of the lamps, display, and keypad.
(7) The control shall include built-in diagnostics for analyzing system events. The
device shall automatically record system status and source-transfer control status
every time a control operation occurs. All such operations shall be indicated by the
illumination of a light-emitting diode lamp and shall be available for display by
means of a dedicated event key.
(8) The present source voltage and current inputs, and the present status of discrete
inputs to and outputs from the control shall be available for display by means of a
dedicated examine key.
(9) The control shall have the capability to automatically calibrate to a known
voltage on each source. This capability shall be keypad-selectable.
(c) Construction Features
(1) The source-transfer control shall use an advanced microprocessor and other
solid-state electronic components to provide the superior reliability and service-
ability required for use in power equipment. All components shall be soldered on
printed-circuit boards to minimize the number of interconnections for increased
reliability.
(2) All interconnecting-cable connector pins and receptacle contacts shall be gold-
over-nickel plated to minimize contact pressure.
(3) The surge withstand capability of the control shall be verified by subjecting the
device to both the ANSI/IEEE Surge Withstand Capability Test (ANSI Standard
C37.90.1) and to a 5-kV, 3.75-joule capacitive-discharge test. For the capacitive-
discharge test, a suitable capacitor shall be charged to 5 kV, and shall then be used
to discharge 3.75 joules into each input circuit and each output circuit of the device.
(4) To identify and eliminate components that might be prone to early failure, the
control shall be subjected to a dielectric test, a functional check, and a 48-hour
screening test followed by a second functional check. For the screening test, the
device shall be energized at rated control voltage while subjected to 48 hours of
temperature cycling repeatedly between -40° C and +65° C.
(5) The control shall be located in the grounded, steel-enclosed low-voltage compart-
ment/enclosure, with the operators. The compartment shall provide isolation from
high voltage.
5.0 LABELING
5.01 Hazard-Alerting Signs
(a) All external doors providing access to high voltage shall be provided with “Warning—Keep
Out—Hazardous Voltage Inside—Can Shock, Burn, or Cause Death” signs.
(b) The inside of each door providing access to high voltage shall be provided with a “Danger—
Hazardous Voltage—Failure to Follow These Instructions Will Likely Cause Shock, Burns,
or Death” sign. The text shall further indicate that operating personnel must know and
obey the employer’s work rules, know the hazards involved, and use proper protective
equipment and tools to work on this equipment.
(c) Interrupter switch compartments shall be provided with “Danger” signs indicating that
“Switches May Be Energized by Backfeed.”
(d) Fuse compartments shall be provided with “Danger” signs indicating that “Fuses May Be
Energized by Backfeed.”
(e) Barriers used to prevent access to energized live parts shall be provided with “Danger—
Keep Away—Hazardous Voltage—Will Shock, Burn, or Cause Death” signs.
5.02 Nameplates, Ratings Labels, and Connection Diagrams
(a) The outside of each set of double doors providing access to high voltage shall be provided
with a nameplate indicating the manufacturer’s name, catalog number, model number, date
of manufacture, and serial number.
(b) The inside of each set of double doors shall be provided with a ratings label indicating the
following:
(1) Overall pad-mounted gear ratings: nominal voltage, kV; maximum voltage, kV; BIL
voltage, kV; power frequency, Hz; short-circuit peak withstand current, amperes,
peak; short-circuit one-second short-time withstand current, amperes, RMS,
symmetrical; and short-circuit MVA, three-phase symmetrical, at rated nominal
voltage.
(2) Main bus ratings: continuous current, amperes; peak withstand current, amperes,
peak; and one-second short-time withstand current, amperes, RMS symmetrical.
(3) Switch ratings: continuous current, amperes; load splitting current, amperes; load
dropping current, amperes; peak withstand current, amperes, peak; one-second
short-time withstand current, amperes, RMS, symmetrical; and three-time duty-
cycle fault-closing current, amperes, RMS symmetrical.
(4) Fuse type and integral load interrupter ratings and capabilities: maximum current,
amperes; load splitting current, amperes; load dropping current, amperes; and
duty-cycle fault-closing current, amperes, RMS symmetrical or asymmetrical.
(c) The inside of each set of double doors shall be provided with a three-line connection
diagram showing interrupter switches, fuses with integral load interrupters, voltage sen-
sors, and bus, along with the manufacturer’s model number.
(c) A single-line diagram model of the system shall be prepared, and shall include the following
information:
(1) Identification of each bus.
(2) Voltage at each bus.
(3) Maximum available fault current, in kA symmetrical, on the utility source side of
the incoming feeder or first upstream device.
(4) Data for each transformer
(i) Three-phase kVA rating
(ii) Percent impedance
(iii) Temperature rise, 65°C and 55/65°C
(iv) Primary voltage
(v) Primary connection
(vi) Secondary voltage
(vii) Secondary connection
(iix) X/R ratio
(ix) Tap settings and available settings
(d) The manufacturer shall use commercially available PC-based computer software such as
Power System Analysis Framework (PSAF—Fault) from CYME International, CYMDIST,
and/or SKM Power Tools® for Windows with the PTW Dapper Module to calculate three-
phase, phase-to-phase, and phase-to-ground fault currents at relevant locations in the
electrical system, in accordance with ANSI Standards C37.010, C37.5, and C37.13. If appli-
cable, an ANSI closing-and-latching duty analysis shall also be performed to calculate the
maximum currents following fault inception.
7.02 Overcurrent Protective Device Coordination Analysis
(a) The manufacturer shall provide an overcurrent protective device coordination analysis to
verify that electrical equipment is protected against damage from short-circuit currents.
Analysis results shall be used to select appropriately rated protective devices and settings
that minimize the impact of short-circuits in the electrical system, by isolating faults as
quickly as possible while maintaining power to the rest of the system.
(b) As applicable, the analysis shall take into account pre-load and ambient-temperature
adjustments to fuse minimum-melting curves, transformer magnetizing-inrush current,
full-load current, hot-load and cold-load pick-up, coordination time intervals for series-
connected protective devices, and the type of reclosers and their reclosing sequences.
Locked-rotor motor starting curves and thermal and mechanical damage curves shall be
plotted with the protective-device time-current characteristic curves, as applicable.
(c) Differing per-unit fault currents on the primary and secondary sides of transformers (attrib-
utable to winding connections) shall be taken into consideration in determining the
required ratings or settings of the protective devices.
(d) The time separation between series-connected protective devices, including the upstream
(source-side) device and largest downstream (load-side) device, shall be graphically
illustrated on log-log paper of standard size. The time-current characteristics of each
protective device shall be plotted such that all upstream devices shall be clearly depicted
on one sheet.
(e) The manufacturer shall furnish coordination curves indicating the required ratings or
settings of protective devices to demonstrate, to the extent possible, selective coordina-
tion. The following information shall be presented on each coordination curve, as
applicable:
(1) Device identifications.
(2) Voltage and current ratios.
(3) Transformer through-fault withstand duration curves.
(4) Minimum-melting, adjusted, and total-clearing fuse curves.
(5) Cable damage curves.
(6) Transformer inrush points.
(7) Maximum available fault current, in kA symmetrical, on the utility source side of
the incoming feeder or first upstream device.
(8) Single-line diagram of the feeder branch under study.
(9) A table summarizing the ratings or settings of the protective devices,
including:
(i) Device identification.
(ii) Relay current-transformer ratios, and tap, time-dial, and instantaneous-
pickup settings.
(iii) Circuit-breaker sensor ratings; long-time, short-time, and instantaneous
settings; and time bands.
(iv) Fuse type and rating.
(v) Ground fault pickup and time delay.
(f) The manufacturer shall use commercially available PC-based computer software such as
CYMTCC from CYME International and/or SKM Captor to create the time-current charac-
teristic curves for all protective devices on each feeder.
(g) As applicable, a technical evaluation shall be prepared for areas of the electrical system
with inadequate overcurrent protective device coordination, with recommendations for
improving coordination.
7.03 Arc-Flash Hazard Analysis
(a) The manufacturer shall provide an arc-flash hazard analysis to verify that electrical equip-
ment on the system is “electrically safe” for personnel to work on while energized. An arc
flash is a flashover of electric current in air from one phase conductor to another phase
conductor, or from one phase conductor to ground that can heat the air to 35,000° F. It can
vaporize metal and cause severe burns to unprotected workers from direct heat exposure
and ignition of improper clothing. And the arc blast resulting from release of the concen-
trated radiant energy can damage hearing and knock down personnel, causing trauma
injuries.
(b) The arc-flash hazard analysis shall include the following:
(1) Identification of equipment locations where an arc-flash hazard analysis is required.