EE3003D Topic 8
EE3003D Topic 8
Topic 8
Thus it is slightly different from its operation in parallel with another generator. But a change in the
prime mover input or excitation of a synchronous generator operating on infinite bus bars affects the
real and reactive power sharing between the generators in the same manner as that of a synchronous
generator operating in parallel with another generator.
A per phase equivalent representation of a non salient pole synchronous generator operating on
infinite bus bars is as shown below.
The relevant network equation of the synchronous generator is again given as E = V + IZS.
*
Then, I = (E - V)/ Zs and S = P ± j Q = 3VI .
Different to the case of a synchronous generator operating in parallel with another generator, the
terminal voltage takes a constant value at all conditions here. So a change in excitation of a
synchronous generator will effectively change the reactive component of the current supplied and
hence the reactive power delivered by it. Similarly, a change in prime mover input of a synchronous
generator effectively changes the active component of the current supplied and hence the real power
delivered by it.
If the field current (If) is increased to a value greater than the normal field current (Ifn), the generated
emf, IEI becomes greater than the terminal voltage, IVI, causing the generator to deliver a lagging
reactive current (Ir) and hence a lagging reactive power (Q) to the bus bars, the operating point being
represented by 2 in the phasor diagram shown in (b). Here, the E phasor has moved from the
operating point 1 to 2 along the IZS phasor, which always leads the Ir phasor by the impedance angle
( ) of the machine. With real power, P = 0, the tip of E phasor lies on the same straight line drawn at
the tip of V phasor at an angle, to Ir, for any If > Ifn, known as over excitation.
If the excitation (If) is reduced to a value less than the normal field current (I fn), the generated emf, IEI
becomes less than the terminal voltage, IVI, causing the generator to deliver a leading reactive current
(Ir) and hence a leading reactive power (Q) to the bus bars, the operating point being represented by 3
in the phasor diagram shown in (c).
Here again, the E phasor has moved from the operating point 1 to 3 along the IZS phasor, which
always leads the Ir phasor by the impedance angle ( ) of the machine. With real power, P = 0, the tip
of E phasor lies on the same straight line drawn at the tip of V phasor at an angle, to Ir, for any If <
Ifn, known as under excitation also.
Hence, it is seen that all the operating points with real power, P = 0 shall fall on the same straight line
drawn at the tip of V phasor at an angle, (90- ) to it, for any excitation. This straight line is known as
the ZPF line, since it represents all the operating points of the machine at ZPF. One half of this ZPF
line corresponds to under excitation while other half of it corresponds to over excitation.
Hence, it is seen that all the operating points with reactive power, Q = 0 shall fall on the same straight
line drawn at the tip of V phasor at an angle, to it, for any value of prime mover input. This straight
line is known as the UPF line, since it represents all the operating points of the machine at UPF.
Obviously, the UPF line which represents all the operating points of the machine with Q = 0 is
perpendicular to the ZPF line which represents all its operating points with P = 0.
If the excitation (If) is reduced to a value less than the normal field current (I fn) while the generator is at
the operating point 4, the generated emf, IEI shows a corresponding decrease in its value causing the
generator to deliver a leading reactive current (Ir) in addition to the existing active component of
current (Ia), the total current (I) being leading in nature. The generator is then made to deliver real
power (P) and leading reactive power (Q) to the bus bars, the operating point being represented by 6
in the phasor diagram shown in (f).
The phasor diagram of a synchronous generator shown in (f) clearly displays all its operating points 1
to 6 considered here, with a comparison of the relevant P and Q values under certain assumptions.
Thus it reveals the possibility of developing a general load diagram by which the operation of a
synchronous machine on infinite bus bars can be represented diagrammatically for all possible modes
and conditions.
Data required
Sr and Vr obtained from the name plate of the synchronous machine.
Synchronous impedance per phase, Zs obtained from the OCC and SCC.
Concentric circles known as emf, E-circles are drawn with centre O as shown in the diagram.
The E-circle with radius CO is designated as 100% E-circle corresponding to normal excitation.
E-circles corresponding to under and over excitation are designated in terms of % excitation as shown.
The phase angles corresponding to P and Q axes are marked as 0º and 90º respectively.
Regions above and below Q-axis are marked for generator and motor operations respectively.
I quadrant is assigned for generator operation with lagging power factor.
II quadrant is assigned for generator operation with leading power factor.
III quadrant is assigned for motor operation with lagging power factor.
IV quadrant is assigned for motor operation with leading power factor.
General load diagram becomes ready for measurements corresponding to various operating points.
Any 2 out of these 6 quantities are sufficient to locate the relevant operating point of the machine on
the general load diagram and get the remaining quantities measured. This is considered as the main
advantage of the general load diagram, since it replaces the time consuming analytical computations
for the performance analysis of the machine to a greater extent. This is subject to the fact that the
precision of the results obtained shall depend up on the scale used for the construction of the diagram.
Additionally, it makes the loci of various quantities with respect to the variation of other relevant
quantities directly visible. (i) Locus of generated voltage for constant real power and variable excitation
and (ii) Locus of generated voltage for constant excitation and variable real power are examples of
that kind. The diagram is also capable of providing data to plot various performance graphs of the
machine such as V-curves and inverted V-curves.
Examples
1. A 3-phase synchronous generator which has an impedance of (0.8 + j 10) per phase, delivers
200A at a power factor of 0.8 lagging to 11kV, constant frequency bus bars. If its excitation stands
unchanged and the prime mover input is increased to have an increase in real power delivered by
25%, find the new values of the current and power factor.
IVI = 11000/ √3 = 6350.85V, V = 6350.85∠0ºV
I1 = 200 (0.8 - j 0.6) = (160 - j 120)A
*
S1 = 3 V I1 = 3 (6350.85 + j 0) (160 + j 120) = (3.048 + j 2.286)MVA
2. The effective resistance and synchronous reactance per phase of a 7.5MVA, 3-phase, star-
connected synchronous generator operating on 11kV bus-bars are 0.8Ω and 8Ω respectively. If the
excitation of the machine is adjusted to 80% of its normal value, what will be the current, reactive
power delivered and the power factor of operation when the real power delivered is 5MW?
IVI = 11000/ √3 = 6350.85V, V = 6350.85∠0ºV
Zs = (0.8 + j 8) = 8.04∠84.29º, IZsI = 8.04 and = 84.29º
E1 = IE1I∠ 1 = 5080.68∠26.974ºV
I1 = (E1 - V)/ Zs = (262.653 + j 254.126) = 365.47∠44.1ºA
*
S1 = 3 V I1 = 3 (6350.85 + j 0) (262.653 - j 254.126) = (5 - j 4.842)MVA