InteliLite 4 AMF 25 1.0.0 Global Guide (7)
InteliLite 4 AMF 25 1.0.0 Global Guide (7)
InteliLite 4
AMF 25
Controller for single gen-set
applications
SW version 1.0.0
1 Document information 5
2 System overview 10
3 Applications overview 20
4 Installation and wiring 22
5 Controller setup 58
6 Communication 172
7 Technical data 200
8 Appendix 201
2.5.3 CM-RS232-485 15
5 Controller setup 58
2.5.4 EM-BIO8-EFCP 15
5.1 Default configuration 58
2.6 CAN modules 16
5.1.1 Binary inputs 58
2.6.1 Inteli IO8/8 16
5.1.2 Binary outputs 58
2.6.2 Inteli AIN8 17
5.1.3 Analog inputs 58
2.6.3 Inteli AIN8TC 17
5.2 Controller configuration and PC tools
2.6.4 Inteli AIO9/1 18 connection 59
2.6.5 IGS-PTM 18 5.2.1 USB 59
1 Document information
1.1 Clarification of Notation 5
1.2 About this Global Guide 5
1.3 Legal notice 5
1.4 General warnings 7
1.5 Functions and protections 8
1.6 Certifications and standards 8
1.7 Document history 8
1.8 Symbols in this manual 9
IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
Example: This type of paragraph contains information that is used to illustrate how a specific function
works.
Official version of the ComAp’s End User's Guide/Manual is the version published in English. ComAp reserves
the right to update this End User's Guide/Manual at any time. ComAp does not assume any responsibility for its
use outside of the scope of the Terms or the Conditions and the License Agreement.
Licensed End User is entitled to make only necessary number of copies of the End User's Guide/Manual. Any
translation of this End User's Guide/Manual without the prior written consent of ComAp is expressly prohibited!
Even if the prior written consent from ComAp is acquired, ComAp does not take any responsibility for the
content, trustworthiness and quality of any such translation. ComAp will deem a translation equal to this End
User's Guide/Manual only if it agrees to verify such translation. The terms and conditions of such verification
must be agreed in the written form and in advance.
For more details relating to the Ownership, Extent of Permitted Reproductions Term of Use of the
Documentation and to the Confidentiality rules please review and comply with the ComAp’s License
Agreement, Terms and Conditions available on www.comap-control.com.
Security Risk Disclaimer
Pay attention to the following recommendations and measures to increase the level of security of ComAp
products and services.
Please note that possible cyber-attacks cannot be fully avoided by the below mentioned recommendations and
set of measures already performed by ComAp, but by following them the cyber-attacks can be considerably
reduced and thereby to reduce the risk of damage. ComAp does not take any responsibility for the actions of
persons responsible for cyber-attacks, nor for any damage caused by the cyber-attack. However, ComAp is
prepared to provide technical support to resolve problems arising from such actions, including but not limited to
restoring settings prior to the cyber-attacks, backing up data, recommending other preventive measures against
any further attacks.
Warning: Some forms of technical support may be provided against payment. There is no legal or factual
entitlement for technical services provided in connection to resolving problems arising from cyber-attack or
other unauthorized accesses to ComAp's Products or Services.
General security recommendations and set of measures
1. AccessCode
• Change the AccessCode BEFORE the device is connected to a network.
• Use a secure AccessCode – ideally a random string of 8 characters containing lowercase, uppercase letters
and digits.
• For each device use a different AccessCode.
2. Password
• Change the password BEFORE the device enters a regular operation.
• Do not leave displays or PC tools unattended if an user, especially administrator, is logged in.
3. Controller Web interface
• The controller web interface at port TCP/80 is based on http, not https, and thus it is intended to be used only
in closed private network infrastructures.
• Avoid exposing the port TCP/80 to the public Internet.
4. MODBUS/TCP
• The MODBUS/TCP protocol (port TCP/502) is an instrumentation protocol designed to exchange data
between locally connected devices like sensors, I/O modules, controllers etc. From it’s nature it does not
contain any kind of security – neither encryption nor authentication. Thus it is intended to be used only in closed
private network infrastructures.
• Avoid exposing the port TCP/502 to the public Internet.
5. SNMP
• The SNMP protocol (port UDP/161) version 1,2 is not encrypted. Thus it is intended to be used only in closed
private network infrastructures.
• Avoid exposing the port UDP/161 to the public Internet.
Used Open Source Software: mBed-TLS
https://www.mbed.com/en/development/software/mbed-tls/
http://www.apache.org/licenses/LICENSE-2.0
Used Font: zpix-pixel-font
WEBLINK to the license conditions: https://github.com/SolidZORO/zpix-pixel-font
Copyright (c) [2019] [Jason Fung]
Note: The controller contains a large number of configurable setpoints, because of this it is impossible to
describe all of its functions. Some functions can be changed or have different behavior in different SW versions.
Always check the Global guide and New feature list for SW version which is used in controller. This manual
only describes the product and is not guaranteed to be set for your application.
IMPORTANT: Be aware that the binary outputs can change state during and after software
reprogramming (before the controller is used again ensure that the proper configuration and
setpoint settings are set in the controller).
The following instructions are for qualified personnel only. To avoid personal injury do not perform any action not
specified in related guides for product.
*Dual-operation **Extension module EM-BIO8-EFCP required *** extension module IGL-RA15 required
EN 60068-2-1 (-20 °C/16 h for std, -40 °C/16 EN 60529 (front panel IP65, back side IP20)
h for LT version)
EN 60068-2-2 (70 °C/16 h)
Connector - Resistor
3 x Phases Grounding
male adjustable
Active Resistive
current Contact GSM sensor
sensor RPTC
GSM RS 232
Contactor
AirGate modem male
Controller RS 232
IG-AVRi
Alternating simplified female
current
Module IG-AVRi
Starter
Analog simplified TRANS
modem
Switch -
Current
Jumper manually
measuring
Battery operated
Current
Load Transformer
Binary measuring
output
USB type B
Diode Mains male
Breaker
contact
Ethernet USB type B
Mains female
Breaker male
contact
Voltage
Ethernet Mobile
measuring
female provider
Breaker
Passive Wifi / WAN /
Fuel
current LAN
solenoid
Breaker sensor
6 back to Document
information
Fuse Pick - up
Breaker
2 System overview
2.1 General description 10
2.2 True RMS measurement 10
2.3 Configurability and monitoring 11
2.4 PC Tools 13
2.5 Plug-in Modules 14
2.6 CAN modules 16
should have a pure sinusoidal waveform. However some nonlinear elements connected to the mains produce
harmonic waveforms with frequencies of multiplies of the basic mains frequency and this may result in
deformation of the voltage waveforms. The True RMS measurement gives accurate readings of effective values
not only for pure sinusoidal waveforms, but also for deformed waveforms.
Note: The harmonic deformation causes that the Power Factor of a generator working parallel with the mains
cannot reach values in a certain range around the PF 1.00. The higher the deformation, the wider the power
factor dead range. If the requested power factor is adjusted inside the dead range, the controller cannot reach
the requested value because of this fact.
Note: Use the InteliConfig PC software to read, view and modify configuration from the controller or disk and
write the new configuration to the controller or disk.
The firmware of controller contains a large number of binary inputs and outputs needed for all necessary
functions available. However, not all functions are required at the same time on the same Gen-set and also the
controller hardware does not have so many input and output terminals. One of the main tasks of the
configuration is mapping of "logical" firmware inputs and outputs to the "physical" hardware inputs and outputs.
The controller is shipped with a default configuration, which should be suitable for most standard applications.
This default configuration can be changed only by using a PC with the InteliConfig software. See InteliConfig
documentation for details.
Note: You need one of communication modules to connect the controller to a PC with InteliConfig. There is a
special easy removable service module for cases when no communication module is permanently attached.
Once the configuration is modified, it can be saved to a file for later usage with another controller or for backup
purposes. The file is called archive and has the file extension .ail3. An archive contains a full image of the
controller at the time of saving (if the controller is online for the PC) except the firmware. Besides configuration it
also contains current adjustment of all setpoints, all measured values, a copy of the history log and a copy of the
alarm list.
The archive can be simply used for cloning controllers, i.e. preparing controllers with identical configuration and
settings.
2.4 PC Tools
2.4.1 InteliConfig
Configuration and monitoring tool for InteliConfig controllers. See more in InteliConfig Reference Guide.
2.4.2 WebSupervisor
Web-based system for monitoring and controlling of controllers. See more at the WebSupervisor webpage.
2.4.3 WinScope
Special graphical controller monitoring software used mainly for commissioning and Gen-set troubleshooting.
See more in the WinScope Reference guide.
2.5.2 CM-4G-GPS
GSM/4G Internet module and GPS locator
Wireless integrated solution
Quick and easy installation
Support of WebSupervisor
Instant alarm SMS notification
System control over SMS
Quad Band GPRS/EDGE modem,
850/900/1800/1900 MHz, FDD LTE: Band 1,
Band 2, Band 3, Band 4, Band 5, Band 7, Band
8, Band 20, all bands with diversity,
WCDMA/HSDPA/HSUPA/HSPA+: Band 1,
Band 2, Band 5, Band 8, all bands with diversity
GPRS multi-slot class 10
TCP/IP communication over GPRS
2.5.3 CM-RS232-485
Communication module with two communication ports.
RS232 and RS485 interface
Modbus
Serial connection to InteliConfig
2.5.4 EM-BIO8-EFCP
Hybrid current input and binary input/output extension module.
One additional AC current (CT) measuring for
Earth Fault Current protection (EFCP)
Wide range of measured current - one input for
1A and 1 input for 5A
Up to 8 additional configurable binary inputs or
outputs
Note: This protection is active ONLY when Engine
is running.
Configuration 8/8
8 Binary inputs (options: pull up or pull down
logic)
8 Binary outputs (options: Low side switch (LSS)
or High side switch (HSS))
2 Analog outputs (options: voltage (0-10 V),
current (0-20 mA) and PWM (5 V, adjustable
frequency 200 Hz-2.4 kHz))
Configuration 16/0
16 Binary inputs (options: pull up or pull down
logic)
0 Binary outputs
2 Analog outputs (options: voltage (0-10 V),
current (0-20 mA) and PWM (5 V, adjustable
frequency 200 Hz-2.4 kHz))
Supported sensors:
Resistor 3-wire input
Common resistor: 0-250 Ω, 0-2400 Ω, 0-
10 kΩ
Temperature sensor: Pt100, Pt1000, Ni100,
Ni1000
Current (active or passive sensors)
±20 mA, 0-20 mA, 4-20 mA
Voltage
±1 V, 0-2.4 V, 0-5 V, 0-10 V
Lambda probes
Thermocouples are not supported (the
measuring loop was designed for lambda
probes, what caused non-support of
thermocouples)
Impulse/RPM sensor:
RPM measuring pulses with frequency 4 Hz-
10 kHz
Impulse
Possibility to measure pulses from
electrometer, flowmeter (measurement of
total consumption, average fuel
consumption)
2.6.5 IGS-PTM
The unit offers the user the flexibility to configure the unit to have 8 binary inputs, 8 binary outputs, 4 analog
inputs and 1 analog outputs.
Configurable 8 binary and 4 analog inputs
Configurable 8 binary and 1 analog output
LEDs indicate the state of binary inputs/outputs
Measures values from Pt100 and Ni100 sensors
Analog inputs (resistance range 0-250 Ω, voltage
range 0-100 mV, current range 0-20 mA –
selectable via jumper)
UL certified
2.6.6 IGL-RA15
Remote annunciator.
15 programmable LEDs with configurable colors
red-green-yellow
Lamp test function with status LED
Customizable labels
Local horn output
Maximal distance 200 m from the controller
Up to 4 units can be connected to the controller
UL certified
3 Applications overview
3.1 AMF – Automatic Mains Failure Start 20
3.2 MRS – Manual Remote Start 20
Note: The package does not contain a communication or extension modules. The required modules should be
ordered separately.
① Plug-in module
Note: Dimension x depends on plug-in module
Note: Dimensions are in millimeters and are the same for all versions of InteliLite.
4.2.2 Mounting
The controller is to be mounted onto the switchboard door. Requested cutout size is 172 mm × 112 mm. Use the
screw holders delivered with the controller to fix the controller into the door as described on pictures below.
Recommended torque for holders is 0.15 N·m.
Note: Enclosure Type rating with mounting instruction – For use on a Flat surface of a type 1 enclosure.
Mains voltage inputs 41-44 Voltage measurement AMF wiring (page 32)
2
Note: Wiring terminal markings to included tightening torque: 0.5 N-m (4.5 lb-in)., and wire size: 2 mm (12-
26 AWG).
4.4.1 General
To ensure proper function:
Use grounding terminals.
Wiring for binary inputs and analog inputs must not be run with power cables.
Analog and binary inputs should use shielded cables, especially when the length is more than 3 m.
Tightening torque, allowable wire size and type, for the Field-Wiring Terminals:
For Mains(Bus) Voltage, Generator Voltage and Current terminals
4.4.2 Grounding
2
The shortest possible length of wire should be used for controller grounding. Use cable min 2.5 mm .
The negative "–" battery terminal must be properly grounded.
Switchboard and engine must be grounded at common point. Use as short cable as possible to the grounding
point.
Maximum continuous DC power supply voltage is 36 V DC. The controller’s power supply terminals are
protected against large pulse power disturbances. When there is a potential risk of the controller being subjected
to conditions outside its capabilities, an outside protection device should be used.
It is necessary to ensure that potential difference between generator current COM terminal and battery "–"
terminal is maximally ±2 V. Therefore is strongly recommended to interconnect these two terminals together.
Note: The controller should be grounded properly in order to protect against lighting strikes. The maximum
allowable current through the controller's negative terminal is 4 A (this is dependent on binary output load).
For the connections with 12 V DC power supply, the controller includes internal capacitors that allow the
controller to continue in operation during cranking if the batter voltage dip occurs. If the voltage dip goes during
cranking to 0 V and after 50 ms it recovers to 4 V, the controller continues operating. This cycle can repeat
several times. During this voltage dip the controller screen backlight can turn off.
Note: In case of the dip to 0 V the high-side binary outputs will be temporarily switched off and after recovering
to 4 V back on.
IMPORTANT: When the controller is power up only by USB and the USB is disconnected then the
actual statistics can be lost.
Note: Suitable conductor protection shall be provided in accordance with NFPA 70, Article 240.
Note: Low voltage circuits (35 volts or less) shall be supplied from the engine starting battery or an isolated
secondary circuit.
Note: It is also possible to further support the controller by connecting the external capacitor and separating
diode. The capacitor size depends on required time. It shall be approximately thousands of μF. The capacitor
size should be 5 000 μF to withstand 150 ms voltage dip under following conditions: Voltage before dip is 12 V,
after 150 ms the voltage recovers to min. allowed voltage, i.e. 8 V.
IMPORTANT: 3 A fuse is calculated without BOUT consumption nor extension modules. Real value
of fuse depends on consumption of binary outputs and modules.
CT Location
a. Load
b. Gen-set
c. None
Note: The current measurement protections are active only when the Gen-set is running.
If the CT Location is set to Load the Short Circuit BOC (page 264) protection is enabled only when GCB is
closed.
3 phase application
IMPORTANT: It is necessary to ensure that potential difference between current COM terminal and
power supply "–" terminal is maximally ±2 V. To do so ground properly both terminals.
IMPORTANT: It is necessary to ensure that potential difference between current COM terminal and
power supply "–" terminal is maximally ±2 V. To do so interconnect these two terminals.
IMPORTANT: It is necessary to ensure that potential difference between current COM terminal and
power supply "–" terminal is maximally ±2 V. To do so ground properly both terminals.
IMPORTANT: It is necessary to ensure that potential difference between current COM terminal and
power supply "–" terminal is maximally ±2 V. To do so interconnect these two terminals.
IMPORTANT: The second phase of split phase connection is connected to the terminal, where is
normally connected the third phase.
IMPORTANT: It is necessary to ensure that potential difference between current COM terminal and
power supply "–" terminal is maximally ±2 V. To do so ground properly both terminals.
IMPORTANT: It is necessary to ensure that potential difference between current COM terminal and
power supply "–" terminal is maximally ±2 V. To do so interconnect these two terminals.
The generator protections are evaluated from different voltages based on Connection type (page 211) setting:
3Ph 4W – Ph-Ph voltage, Ph-N voltage
3Ph 3W – Ph-Ph voltage
SplPhL1L2 – Ph-N voltage
SplPhL1L3 – Ph-N voltage
Mono Ph – Ph-N voltage
ConnectionType: SplPhL1L2
ConnectionType: SplPhL1L3
IMPORTANT: The second phase of split phase connection is connected to the terminal, where is
usually connected the third phase.
The generator protections are evaluated from different voltages based on Connection type (page 211) setting:
3Ph 4W – Ph-Ph voltage, Ph-N voltage
3Ph 3W – Ph-Ph voltage
SplPhL1L2 – Ph-N voltage
SplPhL1L3 – Ph-N voltage
Mono Ph – Ph-N voltage
ConnectionType: SplPhL1L2
ConnectionType: SplPhL1L3
IMPORTANT: The second phase of split phase connection is connected to the terminal, where is
usually connected the third phase.
Note: The name and function or alarm type for each binary input have to be assigned during the configuration.
Note: Every single low current binary output can provide up to 0.5 A of steady current.
Note: Binary output 1 (terminal 4) and binary output 2 (terminal 5) are high current outputs (5 A for long term).
Note: Grey dashed line symbolizes internal connection between E-Stop and binary outputs 1 and 2.
Note: For proper functionality of E-Stop, the terminal T04 must be always wired. Terminal can be connected to
battery+ or to terminal T03 (BATT+)
In the case of grounded sensors, connect the AI COM terminal to the engine body as near to the sensors as
possible.
In the case of isolated sensors, connect the AI COM terminal to the negative power supply terminal of the
controller as well as one pole of each sensor.
Analog inputs are typically used for: Oil Pressure, Coolant Temperature and Fuel Level. All of these parameters
are connected with relevant protections.
Note: Schemes show only analog input connection overview, not actual wiring.
Note: The name, sensor characteristic and alarm types for each analog input have to be assigned during
configuration.
Image 4.36 Analog inputs as tristate Image 4.37 Analog inputs as binary
Note: The name, sensor characteristic and alarm types for each analog input have to be assigned during
configuration.
Note: Tristate and binary sensors are not suitable for Analog Switch functions.
Note: A termination resistor at the CAN (120 Ω) is already implemented on the PCB. For connecting, close the
jumper near the appropriate CAN terminal.
1Recommended data cables: BELDEN (http://www.belden.com) - for shorter distances: 3105A Paired - EIA
Industrial RS-485 PLTC/CM (1x2 conductors); for longer distances: 3106A Paired - EIA Industrial RS-485
PLTC/CM (1x2+1 conductors)
Note: Shielding shall be grounded at one end only. Shielding shall not be connected to CAN COM terminal
For longer distances or in case of surge hazard (connection out of building, in case of storm etc.)
① Recommended PT5-HF-12DC-ST1
RS485 wiring
The wiring of the RS485 communication should be provided in such a way that the following rules are observed:
Note: A termination resistor at the CAN (120 Ω) is already implemented on the PCB. For connecting, close the
jumper near the appropriate CAN terminal.
For longer distances or in case of surge hazard (connection out of building, in case of storm etc.)
① Recommended PT5HF-5DC-ST1
Note: Communication circuits shall be connected to communication circuits of Listed equipment.
Balancing resistors
The transmission bus into the RS485 port enters an indeterminate state when it is not being transmitted to. This
indeterminate state can cause the receivers to receive invalid data bits from the noise picked up on the cable.
To prevent these data bits, you should force the transmission line into a known state. By installing two 620Ω
balancing resistors at one node on the transmission line, you can create a voltage divider that forces the voltage
between the differential pair to be less than 200 mili-Volts, the threshold for the receiver. You should install
these resistors on only one node. The figure below shows a transmission line using bias resistors. Balancing
resistors are placed directly on the PCB of controller. Use jumpers PULL UP/PULL DOWN to connect the
balancing resistors.
4.4.11 USB
This is required for computer connection. Use the shielded USB A-B cable.
Controller can by also power by USB (only for service purpose like a uploading firmware, change of
configuration etc.).
IMPORTANT: Power supply by USB is only for service purpose. Binary inputs and outputs are in
logical 0. Also plug-in modules are not working.
After removing back cover insert the plug-in module. Plug-in module has to be inserted under holders. Start with
holders marked by symbol 1. On the controller are also arrows for better navigation. After inserting plug-in
module under holders 1 press it down to holders marked by symbol 2 which locks the module.
After locking the plug-in module into holders, place back the back cover (small cover for connectors has to be
removed from back cover). Finally insert the small cover for connectors. Small covers are unique for each plug-
in module.
4.6 Maintenance
4.6.1 Backup battery replacement
The internal backup battery lifetime is approx. 6 years. If replacement of backup batter is needed, follow these
instructions:
Connect the controller to a PC and save an archive for backup purposes (not necessary but recommended).
Disconnect all terminals from the controller and remove the controller from the switchboard.
Remove the back cover and all plug-in modules.
Release the rear cover using a flat screwdriver or another suitable tool.
The battery is located in a holder on the circuit board. Remove the old battery with a small sharp screwdriver
and push with a finger the new battery into the holder.
Put the rear cover back. Use slight pressure to lock the snaps into the housing. Pay attention that the cover
is in correct position and not upside down!
Put back the plug-in modules and back cover.
Power the controller on, adjust date and time and check all setpoints.
5 Controller setup
5.1 Default configuration 58
5.2 Controller configuration and PC tools connection 59
5.3 Operator Guide 64
5.4 Remote Display 85
5.5 Functions 90
5.2.1 USB
You may connect to the controller using the USB port. In this case standard USB A to B cable should be used.
5.2.2 RS232/RS485
It is possible to connect to the controller using RS232 or RS485 direct connection (serial port or USB to
RS232/RS485 converter may be used). The following settings need to be checked in the controller:
COM1 Mode (page 377) = Direct
Controller Address has to be set to the same value as in the PC tool
5.2.3 Ethernet
It is possible to connect to the controller using Ethernet port either directly or using ComAp's AirGate service.
Direct connection
When you use direct connection the controller needs to be reachable directly from the PC you use (i.e. one LAN
or WAN without any firewalls and other points that may not allow the connection). The following settings need to
be checked in the controller:
Controller Address (page 228) has to be set to the same value as in the PC tool
IP Address Mode (page 1) can be set to AUTOMATIC when there is DHCP service is available.
Otherwise it needs to be set to FIXED
IP Address (page 1) is either set automatically or it can be adjusted to a specific requested value
Subnet Mask (page 1) is either set automatically or it can be adjusted to a specific requested
Gateway IP (page 1) can be set here when it is used
ComAp TCP Port (page 1) number is 23. Make sure that this port is open for communication in your
network
AirGate connection
You can use ComAp's AirGate service that allows you to connect to any controller via internet no matter what
are the restrictions of the local network (if the controller can connect to the internet AirGate service will work).
The following setpoints have to be adjusted:
Controller Address (page 228) has to be set to the same value as in the PC tool
IP Address Mode (page 1) can be set to AUTOMATIC when there is DHCP service is available.
Otherwise it needs to be set to FIXED
IP Address (page 1) is either set automatically or it can be adjusted to a specific requested value
Subnet Mask (page 1) is either set automatically or it can be adjusted to a specific requested
Gateway IP (page 1) can be set here when it is used
AirGate Connection (page 1) has to be set to Enabled
AirGate Address (page 373) currently there is one AirGate server running at URL airgate.comap.cz (enter
this URL into the setpoint)
Control buttons
Position Picture Description
LEFT button. Use this button to move left or to change the mode. The button can
change the mode only if the main screen with the indicator of currently selected
mode is displayed.
Note: This button will not change the mode if the controller mode is forced by
one of binary inputs listed in the Reference Guide – "Operating modes" chapter.
RIGHT button. Use this button to move right or to change the mode. The button
can change the mode only if the main screen with the indicator of currently
selected mode is displayed.
Note: This button will not change the mode if the controller mode is forced by
one of binary inputs listed in the Reference Guide – "Operating modes" chapter.
HORN RESET button. Use this button to deactivate the horn output without
acknowledging the alarms.
FAULT RESET button. Use this button to acknowledge alarms and deactivate
the horn output. Inactive alarms will disappear immediately and status of active
alarms will be changed to "confirmed" so they will disappear as soon as their
reasons dismiss.
ENTER button. Use this button to finish editing a setpoint or moving right in the
history page.
START button. Works in MAN mode only. Press this button to initiate the start
sequence of the engine.
STOP button. Works in MAN mode only. Press this button to initiate the stop
sequence of the Gen-set. Repeated pressing of button will cancel current phase
of stop sequence (like cooling) and next phase will continue.
GCB button. Works in MAN and TEST modes only. Press this button to open or
close the GCB.
MCB button. Works in MAN and TEST modes only. Press this button to open or
close the MCB.
GCB ON. Green LED is on if GCB is closed. It is driven by GCB CLOSE/OPEN output or by
GCB feedback signal.
LOAD. Green LED is ON if load is supplied by mains or by generator. It means, that Gen-set
or mains is OK and proper circuit breaker is closed.
Main Screen
Symbols
Padlock – active when LBI ACCESS LOCK is active
R – active when there is active remote connection to controller
Exclamation mark – active when there is any alarm in alarmlist
Optional
Value can be chosen via setpoints Main Screen Line 1 (page 226) and Main Screen Line 2 (page 226).
Posibilities are: RPM, PF, Run Hours, ATT, AIN1
Measurement Screens
Note: From all of these pages it is possible to switch seamlessly to the setpoint group page by pressing Page
button.
Note: There can be some additional screens and also some screens can be hidden. Screen’s visibility
depends on actual configuration (usage of extension or communication modules, ECU etc.).
Setpoint Screens
Note: From all measurement pages we can fluently go to the setpoint group page by pressing Page button.
Note: Use Page button to discard changes, to set setpoint to previous value and to return to the list of
setpoints of selected group.
History Log
Note: From all measurement pages we can fluently go to the setpoint group page by pressing Page button.
Note: From setpoint group page we can fluently go to the history log pages by pressing Page button.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the first page of history log.
IMPORTANT: The records are numbered in reverse order, i.e. the latest (newest) record is "0" and
older records have "-1", "-2" etc.
Note: This is only basic history record. There can be some additional screens in case that in controller is
extension module or ECU is configured. Also it depends on connection type.
Active alarms are displayed as white text on black background. It means the alarm is still active, i.e. the
appropriate alarm conditions are still present.
Inactive alarms are displayed as black text on white background. It means the alarm is no more active, i.e.
the appropriate alarm conditions are gone.
Not confirmed alarms are displayed with an asterisk. It means the alarm is still not acknowledged
(confirmed).
ECU alarms: SPN/FMI/OC/SC
SPN – Suspect parameter number
FMI – type of protection
OC – number of errors
SC – source of error
5.3.4 Login
Note: From all measurement pages we can fluently go to the setpoint group page by pressing Page button.
UserID Edit
Note: Use Enter button to confirm the UserID or Page button to cancel entering Login.
PIN Edit
Note: Use Enter button to confirm the PIN and Loging or Page button to cancel entering the Login.
Note: In case that invalid UserID or PIN is entered, the controller shows Wrong Credentials screen. Use Enter
button to enter Login again or Page Button to go back to menu.
+
Note: On Main measurement screen press Enter and Page button together. Enter button has to be pressed
first.
+
Note: On Main measurement screen press Enter and Page button together. Enter button has to be pressed
first.
+ +
Note: On any measurement screen press Enter and Note: On any measurement screen press Enter and
Down button together for lower contrast. Up button together for higher contrast.
Master controller. Front panel buttons on both controllers work the same way. All remote display LEDs shows
the same state as corresponding LEDs on Master controller.
Note: Some settings are not shared between display and control unit (setpoint Backlight Timeout (page 222),
Controller language and Controller user mode).
Note: When IL4-RD firmware is uploaded to controller there is only possible connect InteliConfig using USB
connection. InteliConfig serves only for firmware update when connected to Remote display. There is no
Master controller SCADA displayed, no possibility to adjust setpoints, display Values etc.
Note: Please refer to InteliConfig Global Guide for details about firmware uploading to controller.
5.4.3 Wiring
IL4-RD can be connected to any InteliLite 4 family controller via onboard RS485 communication port or via
external RS232/RS485 communication ports on CM-232-485 communication module . It is possible to connect
only up to three Remote displays to one Master controller, if they are using different communication COMs. To
connect two or more remote displays to one communication line (e.g. RS485) is not possible. Using one
Remote display it is possible to monitor only one Master controller at the time.
Note: IL4 AMF8 and AMF9 don't have onboard RS485 comm port.
It is necessary to use CM-RS232-485 communication module on both Master controller and Remote display.
COM 1 communication channel is used with these settings:
COM 1 Mode: Direct
COM 1 Communication Speed: 57600 or 115200 bps
Controller Address: 1 – 32
The maximal distance between Master controller and Remote display is 10 m for RS-232 connection. It is
recommended to use standard Null modem cable (crossover cable), although three wires (TxD, RxD, GND)
RS-232 connection is enough for communication.
RS485
Any combination of internal RS485 port or external one on CM-232-485 communication module can be used on
Master and Remote Display.
COM 2 communication channel is used with these settings:
COM 2 Mode: Direct
COM 2 Communication Speed: 57600 or 115200 bps
Controller Address: 1 – 32
The maximal distance between Master controller and Remote display is 1200 m for RS485 connection. It is
recommended to use shielded twisted-pair cables that comply with the EIA RS-485 standard to reduce
interference and to achieve maximal distance.
Onboard RS485
Remote display can be connected by onboard RS485 communication port on both master controller and remote
display or a combination of these.
RS485 Mode: Direct
RS485 Communication speed: 57600 or 115200 bps
Controller address: 1-32
The maximal distance between Master controller and Remote display is 1200 m for RS485 connection. It is
recommended to use shielded twisted-pair cables that comply with the EIA RS-485 standard to reduce
interference and to achieve maximal distance.
RS232 + RS485
Master Controller with Two Remote Displays
It is possible to combine two of the previous ways of interconnection and connect two Remote display to one
Master controller concurrently. All the parameters and settings are the same as mentioned above.
Note: Onboard RS485 and CM-232-485 communication module can be used to achieve both remote displays
being connected via RS485 for IL4 MRS16, IL4 AMF25 and IL4 AMF20.
Note: IL4 AMF8 and IL4 AMF9 as master controller can only have up to two remote displays at the same time
and will need to use RS232 combined with RS485.
Example: When AMF controller HW type is used as a Master controller and MRS controller HW type is
used for Remote display there is no possibility to control MCB in MAN mode as there is no MCB button on
MRS controller. However, in general all this not recommended combinations works with similar to above
mentioned limitation considered.
Master device is always able to work without connected Remote display. Disconnecting of the serial line
between Master controller and Remote display has no effect to the Master controller.
When the serial line between Master controller and Remote display is disconnected, or communication cannot
be established, Remote display shows it’s own Init screen and message "Trying to connect" and all LEDs are
off.
Once remote display finds compatible master it shows message "Cfg processing" and downloads configuration
table from master controller. After the configuration from Master controller is downloaded Remote display is
reinitiated, jump to master controllers Main measurement screen and regular operation is started.
It is possible to switch to Remote display’s own Init screen to check IL4-RD FW version and serial number of
used controller and communication status by press and hold Page button for more than 3 seconds.
Note: All controllers from IL4 family can act as either Remote Display of master controller and will always be
compatible with each other.
5.5 Functions
5.5.1 Start-stop sequence 91
5.5.2 AMF sequence 93
5.5.3 Operating Modes 93
5.5.4 Engine start 95
5.5.5 Stabilization 100
5.5.6 Connecting to load 101
5.5.7 MRS operation 101
5.5.8 AMF operation 101
5.5.9 Dual Operation 102
5.5.10 Engine cool down and stop 105
5.5.11 History log 106
5.5.12 Breaker control 107
5.5.13 Exercise timers 110
5.5.14 Rental Timers 117
5.5.15 Service timers 118
5.5.16 Analog switches 118
5.5.17 Additional running engine indications 119
5.5.18 Voltage phase sequence detection 120
5.5.19 Gen-set operation states 120
5.5.20 Load shedding 123
5.5.21 Sensor curves 124
5.5.22 Protections 125
5.5.23 PLC 142
Note: If all generator parameters are OK and Minimal Stabilization Time (page 241) elapsed, indicates that
GCB is possible to close. In AUTO Mode GCB is closed in this moment automatically.
Note: The start-up sequence can be interrupted in any time by stop request.
Note: Mains failed means mains over/under -voltage, over/under -frequency, voltage asymmetry (preset delay
must elapse)
Note: If during start-up sequence mains returns, then MCB is reclosed with delay MCB Close Delay (page
280)(if opened, depending on MCB Opens On (page 290) setpoint) and start-up sequence is interrupted.
Note: If mains fails during stop procedure (cooling) again, stop sequence is interrupted, MCB opened and GCB
re-closed with Transfer Delay (page 280).
Note: If this setpoint is configured as password-protected, the correct password must be entered prior to
attempting to change the mode.
The following binary inputs can be used to force one respective operating mode independent of the mode
setpoint selection:
Remote OFF (page 488)
Remote TEST (page 490)
Remote MAN (page 488)
Remote AUTO (page 487)
If the respective input is active the controller will change the mode to the respective position according to the
active input. If multiple inputs are active, the mode will be changed according to priorities of the inputs. The
priorities match the order in the list above. If all inputs are deactivated, the mode will return to the original
position given by the setpoint.
OFF
No start of the gen-set is possible .Controller stays in Not ready status and cannot be started any way. The
MCB is closed permanently (MCB Opens On (page 290) = GENRUN) or is open or closed according to
whether the mains is present or not (MCB Opens On (page 290) = MAINSFAIL). No AMF function will be
performed. The buttons MCB , GCB , Start and Stop including the appropriate binary inputs for
external buttons are not active.
IMPORTANT: When engine is running, it is not possible to switch Gen-set to OFF mode.
MAN
The engine can be started and stopped manually using the Start and Stop buttons (or external buttons
wired to the appropriate binary inputs) in MAN mode. When the engine is running, GCB can be closed. Also
MCB can be closed and opened manually using the MCB button, regardless of whether the mains are present or
not. No auto start is performed.
Note: The controller provides interlock between GCB and MCB, it means it is never possible to close both CB
together.
AUTO
The controller does not respond to buttons Start , Stop , MCB ON/OFF and GCB ON/OFF . Engine
start/stop request is evaluated form Mains failure/return.
Note: When the AMF function will start the engine than the engine will be running at least for the time which is
defined in Mains Return Delay (page 279) setpoint, even if the mains would return in the meantime.
TEST
The gen-set will be started when the controller is put to TEST mode and will remain running unloaded. If a mains
failure occurs, the MCB will be opened and after Transfer Delay (page 280) the GCB will be closed and the
Gen-set will supply the load. After the mains have recovered, the delay Mains Return Delay (page 279)l will
count down and if it elapses and the mains is still ok, the controller will transfer the load back to the mains after
Transfer Delay (page 280) and the Gen-set will remain running unloaded again until the mode is changed.
OFF
No start of the gen-set is possible. Controller stays in Not ready status and cannot be started any way. The
buttons GCB , Start and Stop including the appropriate binary inputs for external buttons are not
active.
IMPORTANT: When engine is running, it is not possible to switch Gen-set to OFF mode.
MAN
The engine can be started and stopped manually using the Start and Stop buttons (or external buttons
wired to the appropriate binary inputs) in MAN mode. When the engine is running, GCB can be closed.
AUTO
The controller does not respond to buttons Start , Stop and GCB ON/OFF .Engine start/stop request
is given by binary input Remote Start/Stop (page 489).
After the idle period has finished, the output IDLE/NOMINAL (PAGE 519) is activated and the start-up
sequence is finished. The Stabilization (page 100) phase follows.
GAS engine
The setpoint Fuel Solenoid (page 230) has to be switched to the Gas position.
After the command for start is issued (pressing Start button in MAN mode, auto start condition is fulfilled in
AUTO mode or controller is switched to TEST mode), outputs PRESTART (PAGE 531) and GLOW PLUGS
(PAGE 516) are energized for time period given by the setpoints Prestart Time (page 232) and Glow Plugs
Time (page 233).
After Prestart Time (page 232) and Glow Plugs Time (page 233), starts countdown of Sd Ventilation
Time (page 243)
After Sd Ventilation Time (page 243), the starter of engine is activated by energizing the output STARTER
1 (PAGE 536).
When the engine speed exceeds 30 RPM, the outputs FUEL SOLENOID (PAGE 509) and IGNITION (PAGE 520)
are energized.
When the engine speed exceeds value of Starting RPM (page 232), the starter of engine is de-energized,
the engine is considered as started and the Idle period will follow.
IMPORTANT: Additional running engine indications (page 119) signals are not evaluated during the
start of a gas engine. The Pickup must be used in any case!
The maximum duration that the output STARTER 1 (PAGE 536) is energized is determined by the setpoint
Maximum Cranking Time (page 231). If the engine does not start within this period, outputs STARTER 1
(PAGE 536) and FUEL SOLENOID (PAGE 509) are de-energized and a pause with length determined by
Cranking Fail Pause (page 231) will follow. PRESTART (PAGE 531), GLOW PLUGS (PAGE 516) and IGNITION
(PAGE 520) outputs are active during the pause. After the pause has elapsed, the next start attempt is
executed. The number of start attempts is given by the setpoint Cranking Attempts (page 231).
Once the engine is started, the Idle period follows. The binary output IDLE/NOMINAL (PAGE 519) remains
inactive (as it was during the start). The idle period duration is adjusted by the setpoint Idle Time (page
239).
After the idle period has finished, the output DESCRIPTION (PAGE 519) is activated and the start-up sequence
is finished. The Stabilization (page 100) phase follows.
Dual Starter
Dual Starter function is enabled if LBO STARTER 2 (PAGE 536) is configured and Setpoint Dual Starter
Sequence (page 230) is set to any of sequence options: 1-2 or 11-22.
Dual Starter Sequence options:
Disabled (Default)
1-2 (Controller in cranking phase will activate STARTER 1 (PAGE 536) then STARTER 2 (PAGE 536) according
to the order of option pattern 1-2.
11-22 (Controller in cranking phase will activate STARTER 1 (PAGE 536) then STARTER 1 (PAGE 536) then
STARTER 2 (PAGE 536) then STARTER 2 (PAGE 536) according to the order of option pattern 11-22.
The total number of attempts is defined by the Setpoint Cranking Attempts (page 231).
Example:
Cranking Attempts=5, Dual Starter Sequence =1-2
Gen-set will activate Starter 1 (if failed) then Starter 2 (if failed) then Starter 1 (if failed) then Starter
2 (if failed) then Starter 1
Cranking Attempts=5, Dual Starter Sequence =11-22
Gen-set will activate Starter 1 (if failed) then Starter 1 (if failed) then Starter 2 (if failed) then Starter
2 (if failed) then Starter 1
The order of sequence is affected by the actual status of LBI STARTER PRIORITY (PAGE 491) (0-Starter 1, 1-
Starter 2).
LBIs STARTER 1 DISABLED (PAGE 490), STARTER 2 DISABLED (PAGE 491). If the LBI Starter 1,2 Disabled state
is 1 the starter1 ,2 will be skipped in the sequence. Skipped starter is not counted as cranking attempt.
In case both starters are disabled, controller is in the state not ready.
Value Num Starts (page 425) stores the total successful starts of both starters.
5.5.5 Stabilization
When the Engine start (page 95) sequence is finished, the Gen-set goes into the stabilization phase. There are
two timers (setpoints) in this phase:
Minimal Stabilization Time (page 241) starts to count down just after the idle period has finished.
Generator voltage and frequency are not checked (respective protections are not evaluated) and the GCB
cannot be closed even if the generator voltage and frequency are within limits.
Maximal Stabilization Time (page 242) starts to count down just after the idle period has finished.
Generator voltage and frequency are not checked (respective protections are not evaluated) but, opposite to
the previous timer, the GCB can be closed if generator voltage and frequency are within limits.
In situations where the GCB is closed automatically (AUTO, TEST modes), the closing of GCB will occur in the
first moment when the generator voltage and frequency will get into limits and the Minimal Stabilization Time
(page 241) has already elapsed.
In the event that the generator voltage or frequency are not within limits within the Maximal Stabilization Time
(page 242) period, the appropriate protection(s) will be activated and the Gen-set will be cooled down and
stopped.
Note: The limits for the generator voltage and frequency are given by setpoints in the Group: Generator
settings (page 263)Group: Generator settings (page 263)Group: Generator settings (page 263).
Note: The value of the Minimal Stabilization Time (page 241) setpoint has to be lower than the value of
Maximal Stabilization Time (page 242) setpoint.
The mains voltage is within the limits given by the setpoints Mains Undervoltage (page 283) and Mains
Overvoltage (page 282).
The mains voltage unbalance is within the limits given by the setpoint Mains Voltage Unbalance (page
286).
The mains frequency is within the limits given by the setpoints Mains Underfrequency (page 287) and
Mains Overfrequency (page 286).
The alarm Wrn MCB Fail (page 592) is not active (if MCB feedback is active). This condition is not required
if MCB is open (MCB feedback is inactive).
Phase rotation is correct.
Note: The automatic start of the Gen-set due to AMF function can be disabled by the binary inputs AMF START
BLOCK (PAGE 472) or MAINS FAIL BLOCK (PAGE 482).
If the setpoint MCB Opens On (page 290) is set to Gen Run, the MCB is opened once the generator
voltage is within limits (after Minimal Stabilization Time (page 241) elapses).
Note: If the mains are restored to health and the Gen-set is still not connected to the load, the controller
interrupts the startup process and closes back the MCB.
After Transfer Delay (page 280) elapses, the GCB is closed and the Gen-set begins to supply the load.
After the mains restored to normal, the timer Mains Return Delay (page 279) begins to count down.
Maximum time between closing of MCB and opening GCB is given by the setpoint Transfer Delay (page
280). After GCB is opened, the Gen-set cools down and a stop.
IMPORTANT: Controller has this behavior only in AUTO mode!
IMPORTANT: Dual operation is in fail also during process of adjustment of setpoints. In this
moment slave still tries to control MCB.
IMPORTANT: Setpoint MCB Opens On (page 290) has to be set-up to Mains Fail option.
IMPORTANT: LBI MAINS FAIL BLOCK (PAGE 482) can cause fail of dual operation system. In case of
different states of mains on master and slave controllers, alarm AHI Dual Operation Different Mains
(page 589) is activated and gen-sets are switched to normal operation.
Note: LBI AMF START BLOCK (PAGE 472) is evaluated on both controllers. When this LBI is activated, gen-set
can’t start in dual operation. Second gen-set (without active AMF START BLOCK (PAGE 472)) will start. Gen-
sets are not swapping the load until this LBI is active. Behaviour is the same like with alarm of 2nd level.
Note: MCB Fail protection is not used in Slave controller during Dual Operation. MCB is controlled only via
Master. Slave controller has MCB Close/Open in open position all the time during Dual Operation.
Start/stop events
Event Dual AMF
Mains Fail Evaluated by Master only
LBI REMOTE START /STOP (PAGE 489) Evaluated by Master only
IMPORTANT: It is not possible to use Auto Run option in Exercise timers with dual operation.
Start/stop events
Event Dual MRS
LBI REMOTE START /STOP (PAGE 489) Evaluated by Master only
Communication
Communication is establish on RS232 or RS485 communication line. Plug-in module CM-RS232-485 is
required. Communication line is selected via setpoints COM1 Mode (page 377) or COM2 Mode (page 378) or
RS485 Mode (page 228). There are options DualMaster and DualSlave. These options adjust, which
communication line is selected and which role controller has in Dual Operation.
IMPORTANT: For correct communication it is necessary to have one Master and one Slave
controller on the same communication line.
IMPORTANT: There are no shared setpoints. It is necessary to have the same settings of AMF
setpoints and engine timers in both controllers.
In case of communication fail between controllers, alarm AHI Dual Operation Fail (page 588) is activated.
This alarm is activated on both controllers. Both controllers are switched to normal operation.
Switching of Gen-sets
Switching of Gen-sets is based on their Running Hours (page 426). The time how long the Gen-set is running
is adjusted via setpoint Running Hours Max Difference (page 290). When difference of Running Hours
(page 426) between Gen-sets is bigger then value adjusted in this setpoint, load is transferred from first Gen-set
to second Gen-set. First Gen-set is supplying the load until second Gen-set is in running state. Then the GCB of
first Gen-set is opened. From this moment timer Transfer Delay (page 280) counts down. When it counts
down, GCB of second Gen-set can be closed.
Note: Value of Running Hours (page 426) can be modified by setpoint Running Hours Base (page 291).
This setpoint can add or remove additional running hours to value from statistics. This modified value of running
hours is used in dual operation function.
Note: In case that both Gen-sets have the same running hours, Master controller has higher priority.
Note: Switching of Gen-sets can be inhibit by setpoint Swap Gen-sets (page 291) or by binary input DUAL
SWAP GEN-SETS (PAGE 477).
Note: Priority of Gen-set can be changed by binary input DUAL TOP PRIORITY (PAGE 477). In this case running
hours values are not used to decide, which Gen-set should start.
Record structure
Note: When some setpoint is changed, in history log is written its number of communication object.
An output for control of a contactor. Its state represents the breaker position requested by the
Close/Open controller. The breaker must react within 5 seconds to a close or open command, otherwise
an alarm is issued.
An output giving a 5 second pulse in the moment the breaker has to be closed. The output is
ON coil
intended for control of close coils of circuit breakers.
An output giving a pulse in the moment the breaker has to be opened. The pulse lasts until
OFF coil the feedback deactivates, but at least for 5 seconds. The output is intended for control of
open coils of circuit breakers.
The GCB UV coil output is active the whole time the Gen-set is running (not in idle or
cooling). The MCB UV coil output is active when the controller is switched on. The output is
UV coil
deactivated for at least 5 seconds in the moment the breaker has to be switched off. The
output is intended for control of undervoltage coils of circuit breakers.
until the Gen-set is started and providing voltage. Adjusting the setpoint MCB Opens On (page 290) = Gen
Run will prevent triggering the Wrn MCB Fail (page 592) alarm.
IMPORTANT: Also it is possible to use breakers without feedbacks. In this case there is no check
of breaker real state.
There are three different time delays for breaker fail detection – see following diagrams.
When binary output breaker close/open is in steady state and breaker feedback is changed the breaker fail is
detected immediately (no delay).
When binary output breaker close/open opens there is 5 sec delay for breaker fail detection.
When binary output breaker close/open closes there is 5 sec delay for breaker fail detection.
Once mode
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup.
Note: First of all function of timer has to be adjusted via setpoint Timer 1 Function (page 332).
In timer mode select Once. In timer settings adjust date and time of occurrence of timer. Also adjust the duration
of timer.
Daily mode
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup.
Note: First of all function of timer has to be adjusted via setpoint Timer 1 Function (page 332).
In timer mode select Repeat. In repetition type select Daily. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the x-th day of repetition
(Timer 1 Refresh Period (page 338)) and behavior of timer on weekends (Timer 1 Weekends (page 339)).
Example: On image example first start of timer will be 1/1/2016 at 12:00. Duration will be 1 hour. Timer will
be again activated every 3rd day at 12:00 for 1 hour including weekends.
Weekly mode
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup.
Note: First of all function of timer has to be adjusted via setpoint Timer 1 Function (page 332).
In timer mode select Repeat. In repetition type select Weekly. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the x-th week of repetition
(Timer 1 Refresh Period (page 338) and days when timer should be active (Timer 1 Day (page 336).
Example: On image example first start of timer will be 1/1/2016 at 12:00. Duration will be 1 hour. Timer will
be again activated every 2nd week on Monday, Wednesday and Friday at 12:00 for 1 hour.
Monthly mode
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup.
Note: First of all function of timer has to be adjusted via setpoint Timer 1 Function (page 332).
There are two types of monthly repetition. First of them is based on repeating one day in month.
In timer mode select Repeat. In repetition type select Monthly. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the type of monthly
repetition and the x-th day of repetition (Timer 1 Repeat Day In Month (page 336)). Than select the x-th month
of repetition.
Example: On image example first start of timer will be 1/1/2016 at 12:00. Duration will be 1 hour. Timer will
be again activated every 2nd day in 2nd month at 12:00 for 1 hour.
In timer mode select Repeat. In repetition type select Monthly. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the type of monthly
repetition, the x-th week of repetition and days in week. Than select the x-th month of repetition.
Example: On image example first start of timer will be 1/1/2016 at 12:00. Duration will be 1 hour. Timer will
be again activated every 2nd week in 2nd month on Monday, Wednesday and Friday at 12:00 for 1 hour.
In timer mode select Repeat. In repetition type select Short period. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the interval of repetition
(shorter than 1 day).
Example: On image example first start of timer will be 1/1/2016 at 12:00. Duration will be 1 hour. Timer will
be again activated every 4th hour for 1 hour.
Note: When the engine was running before and all above conditions are fulfilled, additional 2 s delay is
necessary to confirm "still engine".
When any engine running conditions are appeared on still engine than the Wrn Stop Fail (page 590) is
activated with following delay:
For generator voltage from 10 V to < 50 % of nominal voltage, Wrn Stop Fail has delay 1 s
For generator voltage > 50 % of nominal voltage, Wrn Stop Fail has delay 200 ms
Oil pressure > Starting Oil Pressure (page 233), Wrn Stop Fail has delay 1 s
Binary input OIL PRESSURE (PAGE 485) is in logical 0, Wrn Stop Fail has delay 1 s
For detected RPM, there is no delay.
When the total time of stopping will exceed setpoint Stop Time (page 244) than the Wrn Stop Fail (page 590)
and binary outputs are activated. The controller will continuously try to stop the engine.
Image 5.27 Engine stops after first Stop Time (page 244)
Note: Curves can be modified via InteliConfig. In InteliConfig are also prepared some standard curves.
IMPORTANT: For right behavior of function, curve for this analog input has to be in percentage and
setpoint Fuel Tank Volume (page 252) has to be adjusted correctly.
5.5.22 Protections
InteliLite 4 allows users to configure their own protections to any analog or binary input (see Logical binary
inputs alphabetically on page 471). More than one protection can be configured on analog input, number of
configured protections is not limited. Only one protection of 1st level and/or one protection of 2nd level can be
configured on logical binary output.
Fixed Protections
Some selected fixed protections has an option to DISABLE the protection.
The setting is done by using the setpoint which is associated to the fixed protection. Each setpoint offers these
options.
Setpoint options
Alarms Fixed Protection States
Enable Protection is enabled
Disable Protection is blocked
ExtDisable Disabling of the protection can be forced by LBI PROTECTION FORCE DISABLE (PAGE 486)
Generator protections
Protection Alarms / Protection name Fixed Protection States
IDMT Overcurrent Protection BOC Overcurrent IDMT (page FIXED PROTECTIONS
(page 273) 633) STATES 4 (PAGE 566)
Current Unbalance BOC Current Unbalance (page FIXED PROTECTIONS
Current
Protection (page 274) 631) STATES 3 (PAGE 565)
Short Circuit Protection FIXED PROTECTIONS
BOC Short Circuit (page 632)
(page 1) STATES 4 (PAGE 566)
Generator Frequency BOC Generator Overfrequency FIXED PROTECTIONS
Protection (page 277) (page 625) STATES 2 (PAGE 564)
Frequency
Generator Frequency BOC Generator FIXED PROTECTIONS
Protection (page 277) Underfrequency (page 626) STATES 2 (PAGE 564)
ALI Gen Ph L1 Inverted (page FIXED PROTECTIONS
1) STATES 3 (PAGE 565)
ALI Gen Ph L2 Inverted (page FIXED PROTECTIONS
1) STATES 3 (PAGE 565)
ALI Gen Ph L3 Inverted (page FIXED PROTECTIONS
Others
1) STATES 3 (PAGE 565)
ALI Gen Ph Rotation Opposite FIXED PROTECTIONS
(page 604) STATES 3 (PAGE 565)
Sd Earth Fault Current (page FIXED PROTECTIONS
632) STATES 4 (PAGE 566)
Overload Protection (page FIXED PROTECTIONS
BOC Overload (page 632)
273) STATES 4 (PAGE 566)
Power
Reverse Power Protection FIXED PROTECTIONS
BOC Reverse Power (page 631)
(page 278) STATES 3 (PAGE 565)
Sd Generator L1 Overvoltage FIXED PROTECTIONS
(page 619) STATES 2 (PAGE 564)
Sd Generator L2 Overvoltage FIXED PROTECTIONS
(page 619) STATES 2 (PAGE 564)
Sd Generator L3 Overvoltage FIXED PROTECTIONS
(page 620) STATES 2 (PAGE 564)
Sd Generator L1L2 Overvoltage FIXED PROTECTIONS
Generator <> Voltage (page 620) STATES 2 (PAGE 564)
Voltage
Protection (page 275) Sd Generator L2L3 Overvoltage FIXED PROTECTIONS
(page 620) STATES 2 (PAGE 564)
Sd Generator L3L1 Overvoltage FIXED PROTECTIONS
(page 620) STATES 2 (PAGE 564)
BOC Generator L1 FIXED PROTECTIONS
Undervoltage (page 621) STATES 2 (PAGE 564)
BOC Generator L2 FIXED PROTECTIONS
Undervoltage (page 621) STATES 2 (PAGE 564)
Mains protections
Protection Alarms / Protection name Fixed Protection States
Wrn Generator Overfrequency (page FIXED PROTECTIONS STATES 3 (PAGE
597) 565)
Frequency
Wrn Generator Uderfrequency (page FIXED PROTECTIONS STATES 2 (PAGE
597) 564)
FIXED PROTECTIONS STATES 4 (PAGE
ALI Mains Ph L1 Inverted (page 604)
566)
FIXED PROTECTIONS STATES 4 (PAGE
ALI Mains Ph L2 Inverted (page 605)
566)
Others
FIXED PROTECTIONS STATES 4 (PAGE
ALI Mains Ph L3 Inverted (page 605)
566)
ALI Mains Ph Rotation Opposite (page FIXED PROTECTIONS STATES 4 (PAGE
605) 566)
FIXED PROTECTIONS STATES 3 (PAGE
Mains L1 Overvoltage (page 626)
565)
FIXED PROTECTIONS STATES 3 (PAGE
Mains L1 Undervoltage (page 626)
565)
FIXED PROTECTIONS STATES 3 (PAGE
Mains L2 Overvoltage (page 627)
565)
FIXED PROTECTIONS STATES 3 (PAGE
Voltage Mains L2 Undervoltage (page 627)
565)
FIXED PROTECTIONS STATES 3 (PAGE
Mains L3 Overvoltage (page 628)
565)
FIXED PROTECTIONS STATES 3 (PAGE
Mains L3 Overvoltage (page 628)
565)
FIXED PROTECTIONS STATES 3 (PAGE
Mains L1L2 Overvoltage (page 628)
565)
Engine protections
Alarms / Protection
Protection Fixed Protection States
name
Sd Overspeed (page FIXED PROTECTIONS STATES 1 (PAGE
Overspeed Protection (page 1)
617) 563)
Speed
Underspeed Protection (page Sd Underspeed (page FIXED PROTECTIONS STATES 1 (PAGE
278) 617) 563)
Fault Action:
Alarm LBO Horn activation LBO Alarm activation Action: SD Override
Name Level Abbreviation History Reset Gen-set Common LBO
List (inc. Flashing) (inc. Flashing) CB open blocking
needed stop
AL COMMON
Warning 1 Wrn - - -
WRN ( PAGE 501)
Alarm Only 1 Al - - -
Protection blocking
Engine, Generator and the other fixed protections are blocked during starting phases or Ready and Stop states. They become unblocked once Maximal Stabilization
Time (page 242) is elapsed or GCB is closed depends what happens first.
Exceptions are:
Overspeed protection which has two limits defined via setpoints Overspeed Sd (page 249) and Starting Overspeed Sd (page 249). Starting Oversppeed limit is
considered in the starting phase till Starting Overspeed Time elapses. This time starts to count once the RPM exceeds the value of Starting RPM (page 232).
E-Stop and Emergency stop
The other way how fixed protections can be blocked is by active LBI SD OVERRIDE (PAGE 490).
Note: LBI SD OVERRIDE (PAGE 490) (Shutdown Override) does not block evaluation of fixed protection conditions and their visualization. They are recorded into alarm list
or history. It only blocks their actions. Shutdown Override blocks all level 2 (Sd, BOC) fixed protection. It does not block level 1 (Wrn, AHI, Hist) or protection of type Sd
Override.
Source
Analog values Binary states
Binary inputs
Analog inputs
Controller, Modules, ECU, Shared I/O
Controller, Modules
Modbus server, Modbus Master
Values
Binary outputs
ECU, MER, Application, PLC, Shared I/O
PLC
Modbus server, Modbus Master
Protection states
Statistics
LBOs
Protection activation
Type Name of activation Description
Over Limit Protection is activated if value is over limit.
Over Limit + Fls Protection is activated if value is over limit or in a fault state.
Analog Under Limit Protection is activated if value is under limit.
Under Limit + Fls Protection is activated if value is under limit or in a fault state.
Fls only Protection is activated if value is in a fault state.
True Protection is activated if value is Logical 1.
TrueOrFls Protection is activated if value is Logical 1 or in a fault state.
Binary
False Protection is activated if value is Logical 0.
FalseOrFls Protection is activated if value is Logical 0 or in a fault state.
Selecting if the occurrence of a protection is recorded every time or only once after a Fault Reset.
If User protection state is checked the protection is then shown in setpoints under the
Group: User Setpoints (page 295).
Selecting if the occurrence of a protection is recorded every time or only once after a Fault Reset.
If User protection state is checked the protection is then shown in setpoints under the
Group: User Setpoints (page 295).
Protection blocking
It is possible to configure one Protection Blocking to any User Protections (page 130). This function is used to
block certain protections when their function is unwanted or meaningless. Each user protection has an option to
set the blocking condition.
The blocking conditions can be also applied on the Fixed Protections (page 1).
Protection blocking
Block
Description
Type
All the
The protection is not blocked. It can be blocked only by LBI SD OVERRIDE (PAGE 490).
time
Run Only
The protection is blocked depending on engine state and time defined by setpoint Run Only Block
Block
Delay (page 1). It can also be blocked by LBI SD OVERRIDE (PAGE 490).
Delay
Force The protection is blocked by LBI PROTECTION FORCE DISABLE (PAGE 486) or by LBI SD OVERRIDE
Block (PAGE 490).
The protection is blocked depending on engine state. It is unblocked once Maximal Stabilization
Electrical
Time (page 242) is elapsed or GCB is closed. It can also be blocked by LBI SD OVERRIDE (PAGE
Protection
490).
General protections
LBI FORCE PROTECTION DISABLE (PAGE 479) is paired with an option of protection condition "Force Block" and
can be used for Blocking / Disabling of protections, however on user defined protections the option causes
protection Blocking instead of Disabling.
History record
Always
Once
SD OVERRIDE (PAGE 490)
Image 5.31
Protection states
Protection states is a new feature introduced in InteliLite 4, which helps with better management of alarms. Until
now, you could only use LBO ALARM (PAGE 502) which did not specify what is going on. Protection states work
in similar way, like any other LBO. The difference is, that protection state gets active only when there is specific
alarm present in the alarm list. Thanks to this, you can create PLC logic, which will react to specific alarms only.
Alarm management
The controller evaluates two levels of alarms. Level 1 – yellow alarm – is a pre-critical alarm that is only
informative and does not take any action regarding Gen-set control. Level 2 – red alarm – represents a critical
situation, where an action must be taken to prevent damage of the Gen-set or technology.
One alarm of any type can be assigned to each binary input.
Two alarms (one yellow and one red type) can be assigned to each analog input.
There are also Built-in alarms (page 140) with fixed alarm types.
Each alarm is written to the Alarmlist (page 139).
Each alarm causes a record to be written into the history log.
Each alarm activates the Alarm and Horn output.
Each alarm can cause sending of a SMS message or an email.
Alarm handling
There are three different alarm categories regarding the period when the alarms are evaluated. The category is
selectable for alarms assigned to binary/analog inputs and fixed for built-in alarms. The categories are the
following:
The alarm is evaluated all the time when the controller is switched on.
The alarm is evaluated only when the engine is running. This type should be used for e.g. oil pressure. These
alarms begin to be evaluated after the engine has been started with the delay given by the setpoint
Protection Hold Off (page 1).
The alarm is evaluated only when the generator is excited. These alarms begin to be evaluated after the
engine has been started and Maximal Stabilization Time (page 242) has elapsed or the GCB has been
closed. They remain evaluated until cooling has finished. Only Generator under/overvoltage, Generator
voltage unbalance and Generator under/overfrequency belong to this category. This category is not
configurable to binary and analog input alarms.
If an alarm is being evaluated and the appropriate alarm condition is fulfilled, the delay of evaluation will start to
run. The delay is adjustable by a setpoint (in the case of built-in alarms, analog input alarms) or is adjusted via
configuration window in InteliConfig (in the case of binary input alarms). If the conditions persist, the alarm will
activate. The alarm will not activate if the condition is dismissed while the delay is still running.
After pressing the Fault reset button or activating the binary input FAULT RESET BUTTON (PAGE 479), all active
alarms change to confirmed state. Confirmed alarms will disappear from the Alarmlist as soon as the respective
condition dismisses. If the condition is dismissed before acknowledging the alarm, the alarm will remain in the
Alarmlist as Inactive.
Note: The input SD OVERRIDE (PAGE 490) can be used for temporary disabling of red alarms to shutdown the
engine. This input may be used in situations where providing the power is extremely important – e.g. if the Gen-
set drives pumps for fire extinguishers (sprinklers).
Alarm states
An alarm can have following states:
Active alarm: the alarm condition persists, alarm delay has elapsed.
Inactive alarm: the alarm condition has disappeared, but the alarm has not been confirmed.
Confirmed alarm: the alarm condition persists, but the alarm has already been confirmed.
Warning (Wrn)
The alarm appears in the Alarmlist and is recorded into the history log. Activates the output AL COMMON W RN
(PAGE 501) as well as the standard alarm outputs (HORN (PAGE 518) and ALARM (PAGE 502)).
IMPORTANT: The Gen-set can start by itself after acknowledging the alarms if there is no longer an
active red alarm and the controller is in AUTO or TEST mode!
Shutdown (Sd)
The alarm appears in the alarmlist and is recorded into the history log. It causes immediate stop of the Gen-set
without cooling phase. Also GCB breaker is open. The Gen-set cannot be started again while there is a
shutdown alarm in the alarmlist. Activates the output AL COMMON SD (PAGE 500) as well as the standard alarm
outputs (HORN (PAGE 518) and ALARM (PAGE 502)).
Alarmlist
Alarmlist is a container of active and inactive alarms. It will appear automatically on the controller display, if a
new alarm occurs, or can be displayed manually from the display menu.
Active alarms are shown as inverted, not yet confirmed alarms are marked with asterisk before them.
Alarmlist contains three types of alarms:
Controller built-in alarms
User configured alarms on binary or analog inputs
ECU alarms
ECU alarms
The ECU alarms are received from the ECU. The alarms are represented by the Diagnostic Trouble Code,
which contains information about the subsystem where the alarm occurred, the alarm type and the alarm
occurrence counter.
The most common fault codes are translated into text form. Other fault codes are displayed as a numeric code
and the engine fault codes list must be used to determine the reason.
Built-in alarms
Events Protection
Description
specification type
Battery voltage is out of limits given by Battery Undervoltage (page
Wrn Battery Voltage WRN
257) and Battery Overvoltage (page 258) setpoints.
RTC Battery Flat WRN RTC battery weak or flat and has to be changed.
If the controller switches off during starting sequence (STARTER 1
Sd Battery Flat SD (PAGE 536) output is active) it doesn't try to start again and activates
this protection (controller assumes bad battery condition).
Sd Start Fail SD Gen-set start failed. All crank attempts were tried without success.
Sd Gen Lx >V The generator voltage is out of limits given by Generator
SD
BOC Gen Lx <V Undervoltage BOC (page 269) and Generator Overvoltage Sd
BOC
(where x=1,2,3) (page 268) setpoints.
BOC Gen V The generator voltage is unbalanced more than the value of Voltage
BOC
Unbalance Unbalance BOC (page 270) setpoint.
The generator frequency is out of limits given by Generator
BOC Gen >,
BOC Overfrequency BOC (page 270) and Generator Underfrequency
<Frequency
BOC (page 271) setpoints.
BOC Current The generator current is unbalanced more than the value of Current
BOC
Unbalance Unbalance BOC (page 267) setpoint.
Generator current exceeds the limit for IDMT protection given by
BOC Current IDMT BOC
Nominal Current (page 209) and IDMT Overcurrent Delay (page
Events Protection
Description
specification type
265) setpoints.
The load is greater than the value given by Overload BOC (page
BOC Overload BOC
263) setpoint.
This alarm is activated when Earth Fault value exceeds Earth Fault
Sd Earth Fault SD
Sd (page 381) limit for at least Earth Fault Delay (page 380) period.
The protection comes active if the speed is greater than Overspeed
Sd Overspeed SD
Sd (page 249) setpoint.
During starting of the engine when the RPM reach the value of
Starting RPM (page 232) setpoint the starter is switched off and the
Sd Underspeed SD speed of the engine can drop under Starting RPM (page 232) again.
Then the Underspeed protection is active. Protection evaluation
starts 5 seconds after reaching Starting RPM (page 232).
If the input Emergency Stop is active shutdown is immediately
Emergency Stop SD
activated.
GCB Fail SD Failure of generator circuit breaker.
MCB Fail WRN Failure of mains circuit breaker.
Failure of magnetic pick-up sensor for speed measurement. This
alarm appears, if starter was disengaged for other reason than over-
Sd RPM
SD crossing Starting RPM (page 232) (like oil pressure or D+) and at
Measurement Fail
the end of timer Maximum Cranking Time (page 231) there are no
RPMs > Starting RPM (page 232) detected.
Gen-set stop failed. See description at Gen-set Operation States
Wrn Stop Fail WRN
chapter.
The period for servicing is set by the Maintenance Timer 1 (page
Wrn Maintenance 1 WRN
260) setpoint. The protection comes if counter reaches zero.
The period for servicing is set by the Maintenance Timer 2 (page
Wrn Maintenance 2 WRN
260) setpoint. The protection comes if counter reaches zero.
The period for servicing is set by the Maintenance Timer 3 (page
Wrn Maintenance 3 WRN
260) setpoint. The protection comes if counter reaches zero.
Charge Alternator
WRN Failure of alternator for charging the battery.
Fail
Wrn Override All Sd WRN The protection is active if the output Sd Override is active.
Mains voltage phases are not wired correctly. MCB closing is
Mains CCW Rot WRN
prohibited by controller.
Gen-set voltage phases are not wired correctly. GCB closing is
Generator CCW Rot WRN
prohibited by controller.
ALI Gen Ph-Rotation Mains voltage phases are not wired correctly. MCB closing is
ALI
Opposite prohibited by controller.
ALI Mains Ph- Mains voltage phases are not wired correctly. GCB closing is
ALI
Rotation Opposite prohibited by controller.
BOC Reverse Power BOC The reverse power is higher than limit adjusted via setpoint Reverse
Events Protection
Description
specification type
Power Level (page 272).
MP Mains Lx >V
The mains voltage is out of limits given by Mains Overvoltage (page
MP Mains Lx <V MP
282) and Mains Undervoltage (page 283) setpoints.
(where x=1,2,3)
Mains Voltage The mains voltage is unbalanced more than the value of Mains
MP
Unbalance Voltage Unbalance (page 286) setpoint.
The mains frequency is out of limits given by Mains Overfrequency
Mains >, <Frequency MP
(page 286) and Mains Underfrequency (page 287) setpoints.
Note: This table does not contain all alarms in controller. It is only list of the most common alarms.
5.5.23 PLC
PLC Editor is powerful tool which helps you to create your own PLC scheme. It has graphical interface to have
user interface easy to use.
Number of blocks is for InteliLite AMF 25. Number of blocks can be different according to controller version.
Note: To delete PLC block just click on it and press delete button. Also delete selection function can be used.
Note: To see context help for selected PLC block just press F1 button.
Inputs
Sheet inputs are located at the left side of a sheet. Follow the procedure below to add or edit an input.
Double-click on a free input position or existing input to add new input or edit the existing one.
Select the source for the input.
If you create a binary input, you can select a source from following categories:
Bin. Values – this category contains all binary values available in the controller as binary inputs,
logical binary outputs etc.
PLC Outputs – this category contains all PLC blocks binary outputs available in the controller.
If you create an analog input, you can select a source from following categories:
Ana. Values – this category contains all analog values available in the controller as analog inputs,
electrical values, values from ECU etc.
All Setpoints – this category contains all setpoints of the controller except the dedicated PLC
setpoints. Names, resolutions and dimensions of these setpoints can not be modified.
PLC Setpoints – this category contains a group of setpoints which are dedicated for using in the PLC
program. PLC setpoints can be renamed, their dimension, resolution and limits can be modified
according to need of PLC blocks where they are used.
Outputs
Sheet outputs are located at the right side of a sheet. Follow the procedure below to add or edit an input.
Double-click on a free output position to add new sheet output.
Double-click on an already created output to configure the output onto a controller output terminal or a logical
binary input (first of all some PLC block output has to be connected to this output to enable configuration of
output).
IMPORTANT: It is necessary to click on Connect button after selecting the output. Otherwise PLC
output is not connected to output.
Creating wires
Wires can be create between PLC inputs and PLC blocks and between PLC blocks and PLC outputs.
IMPORTANT: Keep the order of starting and finishing connection points. Wires between inputs and
blocks have to start from inputs. Wires between blocks and outputs have to start from blocks.
Locate the mouse pointer over the starting point of the wire. If the area under the mouse pointer is a
connection point, the pointer will change the color (fill of pointer will be white).
Press and hold the left mouse button and drag the wire to the destination of required connection point. If you
point over a valid connection point, the connection point will be marked with a red circle.
Release the left mouse button to create a wire between the two points. The wire is routed automatically.
Note: It is possible to make connection only between the outputs and inputs with the same type of value (binary
or analog). Binary values are marked by black pointer, analog values are marked with green pointer.
Note: To delete wire just click on it and press delete button. Also delete selection function can by used.
IMPORTANT: Please always check that the blocks are ordered correctly, especially if you use direct
feedbacks from outputs to inputs within one sheet. Wrong order may lead to incorrect results!!!
Other functions
Consistency check
Use this function to check if all inputs and outputs of PLC block are connected.
Hints
Use this function to enable or disable quick hints for blocks (controller help is not affected by this function).
PLC monitor
PLC Monitor is a powerful tool for monitoring your PLC. Just click on PLC Monitor button on main InteliConfig
page to see you PLC. Active inputs and outputs have blue color. Also wires with active signals have blue color.
IMPORTANT: It is not possible to edit PLC in PLC Monitor tool.
5.5.24 Geo-fencing
Geo-fencing function is kind of protection that evaluates whether the actual GPS location is within predefined
area and based on the evaluation takes an action (sends sms, stops engine, make history record etc.). Function
is enabled by setpoint Geo-Fencing (page 356) or by logical binary input GEO-FENCING ENABLE (PAGE 482).
Using InteliConfig, it is possible to set two concentric geo-circles within which the unit is allowed to be located.
Each geo-circle is defined as circular geographic area with centre (common for both geo-circles) named Home
Position adjusted via setpoints Home Latitude (page 356) and Home Longitude (page 357) and radius
named Fence Radius adjusted via setpoints .Fence Radius 1 (page 358) and Fence Radius 2 (page 360).
Protections can be different for both circles. Protection are adjusted via setpoints Fence 1 Protection (page
358) and Fence 2 Protection (page 359).
It is also possible to see the current position of the controller in WebSupervisor map view.
Note: Lamp icon blinking is defined as displaying active lamp icon and inverse colored active lamp icon in
required frequency.
Analog values
Supported analog values:
DPF Ash Load (page 1)
DPF Soot Load (page 1)
DEF Level (page 1)
Configuration sets can be changed via logical binary inputs ALTERNATE CONFIG 2 (PAGE 472) and ALTERNATE
CONFIG 3 (PAGE 472). Configuration set 1 is active when there is no input activated. In case that inputs
ALTERNATE CONFIG 2 (PAGE 472) and ALTERNATE CONFIG 3 (PAGE 472) are active at the same time, the
configuration set 3 is took in account.
ALTERNATE CONFIG 2 (PAGE 472) ALTERNATE CONFIG 3 (PAGE 472) Active configuration set
0 0 1
1 0 2
0 1 3
1 1 3
IMPORTANT: If LBO ECU POWER RELAY (PAGE 506) is used, change of alternate configuration can
be made only in prestart phase. So prestart has to be set up for enough long time.
Terminology:
The Archive = the native file of InteliConfig, including the complete Configuration + History + Statistic +
Values (in the time of download) + Alarm list.
Configuration = the part of Archive, in the terms of Configuration + Setpoints + PLC + IO definitions +
Languages (for more information see Configuration download on page 156).
New configuration = the configuration created in InteliConfig for the purpose of uploading it into the controller
using the USB memory stick. The new configuration is recognized due to it's name. The name has to
contain the specific string ="InteliLite 4-Genset name-M.N.P.B.aig3".
Compatible firmware = the firmware version compatible with the configuration in the controller. The name of
file including the firmware is "InteliLite 4-M.N.P.B.bin".
Abbreviations:
CU – control unit
FW – firmware
CFG – configuration
Firmware upload
Point 1 – controller detects that USB Flash Drive has been inserted.
If the communication via USB B is running controller will not detect the USB memory key.
On the other hand if the USB memory key was detected, communication via USB B port is not possible.
Point 2 – controller is in OFF mode
All operations with USB memory key are possible only in OFF mode
Point 3 - Conditions for firmware upload with current configuration
The new firmware compatible with the version of the configuration in the controller has been detected
(and there is no new configuration file).
Detection is based on name of firmware – required name: "InteliLite 4-M.N.P.B.bin""
There can be stored more firmwares on the USB Flash Drive. Controller automatically select the
compatible firmware with highest version.
Point 4 – Pop-up message
Confirmation of firmware upload with current configuration
Point 5 – Firmware upload
Current archive is download to USB Flash Drive (Name = SN_YYMMDDHHMM).
New firmware is uploaded into the controller without the change of the configuration
History record "USB Flash Drive FW upgrade" is made
Confirming file (.txt) on USB Flash Drive is made (Name = SN_YYMMDDHHMM)
Content: Serial number, Year/Date/Time, Upgrade to the FW "Name of the new FW" successful.
Confirmation pop-up message: "FW upgrade success"
Configuration upload
Point 1 – controller detects that USB Flash Drive has been inserted.
If the communication via USB B is running controller will not detect the USB memory key.
On the other hand if the USB memory key was detected, communication via USB B port is not possible.
Point 2 – controller is in OFF mode
All operations with USB memory key are possible only in OFF mode
Point 9 – conditions for new configuration upload
The new configuration compatible with the version of the firmware in the controller has been detected
(and there is no new firmware file).
Detection is based on name of configuration – required name: "InteliLite 4-Genset name-M.N.P.B.aig3"
There can be only one configuration file
Point 10 – Pop-up message
Confirmation of configuration upload with current firmware
Point 11 – Configuration upload
Current archive is download to USB key (Name = SN_YYMMDDHHMM).
New configuration is uploaded into the controller without the change of the firmware
Configuration download
Point 1 – controller detects that USB Flash Drive has been inserted.
If the communication via USB B is running controller will not detect the USB memory key.
On the other hand if the USB memory key was detected, communication via USB B port is not possible.
Point 2 – controller is in OFF mode
All operations with USB memory key are possible only in OFF mode
Points 3, 6, 9 – conditions for configuration download
There is no firmware or configuration with required name
5.5.28 E-Stop
Binary outputs for the control of some essential functions are internally wired as "safe", it means, that their
deactivation is directly bind with the dedicated Input E-STOP (not evaluated as the LBI in the controller). This
BO are fully configurable and are used e.g. for the Starter and Fuel control.
The emergency stop circuit must be secured.
No accidental activation on the PCB, circuit must disable the operation of the emergency stop.
The power supply of the associated binary outputs (BOUT1 and BOUT2) is supplied by the E-STOP input,
not by the + battery voltage.
Note: There is no difference int the way of configuration of all binary outputs. Binary outputs BO1 (Starter), BO2
(Fuel Solenoid) are intended for these functions (not dedicated).
There is a measuring of E-STOP input voltage analogically and setting the binary value (representing
emergency stop input level) based on comparison of the measured voltage to two analog levels, which are
derived from the controller supply voltage (battery voltage) perceptually.
If the input voltage of E-stop is higher than high comparison level (for ex. higher than 80% of the supply
voltage), then E-stop is not activated.
If the input voltage of E-stop is lower than low comparison level (for ex. lower than 60% of the supply
voltage), then E-stop is activated.
If the input voltage of E-stop is located somewhere between low and high comparison levels (for ex. between 60
and 80 %of the supply voltage, then E-stop binary value will stay on its previous state (means E-stop binary
value will not change).
Visualization on CU screen
1 – E-STOP has voltage – state is OK
0 – E-STOP has no voltage – protection is active
For more information about connection see Emergency stop on page 48.
Mode setting
There are the following modes of operation (can be set by an individual setpoint for each User button):
MAN ON
MAN OFF
COMMAND
FIXED ON
If the selection setpoint is set to FIXED ON, corresponding User Button is activated and its state cannot be
changed by command. In PC monitoring tool there is a graphical interface clustering all manual settings together
(example shown in the diagram above) i.e. there is a GUI for manual control of userbuttons or selection of
command control. Changes in this GUI directly change the value of the setpoint (redundant access to these
settings).
FIXED OFF
If the selection setpoint is set to FIXED OFF, corresponding User Button is deactivated and its state cannot be
changed by command. In PC monitoring tool there is a graphical interface clustering all manual settings together
(example shown in the diagram above) i.e. there is a GUI for manual control of userbuttons or selection of
command control. Changes in this GUI directly change the value of the setpoint (redundant access to these
settings).
COMMAND
In PC monitoring tool there is a graphical interface clustering all manual settings together (example shown in
diagram above) i.e. there is a GUI for manual control of userbuttons or selection of command control.
There are several commands available (all commands can be used when the mode is set to COMMAND). The
GUI provides easy access to issue commands when COMMAND mode is selected. Commands can be also
sent from other sources (display, SCADA, third party device etc.).
COMMAND ON and COMMAND OFF
User Button state is determined by commands (can be sent from HMI, Modbus etc.). When a command
ON is received, User Button is activated. Subsequent commands ON when User Button is active have
no effect. If a command OFF is received, User Button is deactivated. Subsequent commands OFF when
User Button is inactive have no effect.
COMMAND TOGGLE (previously named ON/OFF)
User Button state is determined by a command (can be sent from HMI, Modbus etc.). When a command
TOGGLE is received, User Button is activated. Next command TOGGLE when User Button is active
deactivates User Button and so on.
COMMAND PULSE
User Button state is determined by a command (can be sent from HMI, Modbus etc.).
When a command PULSE is received, User Button is activated for the set duration.
Pulse length is 200 ms (user can use this pulse in PLC to prolong it using e.g. block Delay)
Consequent commands PULSE sent during duration of the pulse prolong the duration accordingly.
When the setting of pulse duration is changed while the pulse is active, the current pulse will have the
original duration and the new setting is applied for the next pulse.
If the User Button is active (as a result of COMMAND ON or COMMAND TOGGLE) and COMMAND
PULSE comes, User Button remains active for the duration of the pulse and then it deactivates.
While a pulse is active (duration of the pulse) and COMMAND ON, COMMAND OFF or COMMAND
TOGGLE comes, the pulse is canceled. Next state depends on the canceling command:
COMMAND ON – User Button remains active until COMMAND OFF or COMMAND TOGGLE
comes
COMMAND OFF or COMMAND TOGGLE – User Button deactivates until COMMAND ON,
COMMAND TOGGLE or COMMAND PULSE come
Access rights
In sense of access rules the user buttons are grouped to groups of 8 user buttons.
User Button 1-8
User Button 9-16
User Button 17-24
User Button 25-32
It is possible to set the access level for each of these 4 commands separately in access rules management
menu.
Types of interfaces
The controller communication interfaces are split into two categories according to what kind of environment the
interface is exposed.
Trusted
Are USB, RS232, RS485, On board RS485 interfaces. It is expected that these interfaces are operated
locally inside a closed environment / infrastructure where additional measures against misuse or attack
take place (e.g. physical access limitation). Due to nature of this interface less strict cybersecurity rules
apply at it and that is why Implicit account is introduced here to make working with the controller simpler.
Untrusted
Is Ethernet interface. This interface is a general-purpose one and it is expected that it may be exposed to
public networks, such as Internet, which are not under control of the entity operating the controller. Thus,
strict cybersecurity rules apply for this type of interface.
User accounts
User account must be created in the controller by administrator before the particular user can login to the
controller.
Note: User accounts must be created for each controller separately and manually. It is not possible to transfer
the accounts from one controller to another.
User login
To login to the controller the username and password must be provided into the login form of the
application (InteliConfig (page 13), WebSupervisor (page 13), Remote Display (page 85).
Alternatively, at trusted interfaces, it is possible to login using UID and PIN instead of username and
password. This method of login is designed to simplify the login procedure at devices without alphanumeric
keyboard (e.g. InteliVision).
Note: The controller is featured with a protection against brute force attack to user account credentials. For
details see Account break protection on page 165.
Production mode
By default the controller has turned on Production mode. Production mode allows you to work with the controller
without the need to log in as an administrator (access level 3) when connected through trusted interface. All
operations for which an administrator account is usually required are enabled even without logging in (e.g.
writing the configuration). This can be potentially risky, therefore there is active alarm Wrn Production Mode
(page 599) in the alarm list. To turn off the Production mode go to User management and uncheck the checkbox
Production mode or go to Production Mode display screen and select disable. Once it is done the warning
disappears and it will not be possible to work with the controller as an administrator without log in.
Note: There must always remain at least one administrator account in the system. The controller will not allow
deleting last administrator account.
7. Enter the Password Reset Action Code into the appropriate form
Managing accounts
User accounts can be managed from InteliConfig while an online connection to the controller is established. An
user with administrator level must be logged with username/password and is prompted to re-enter accounts
password before the user management dialog is opened.
IMPORTANT: The total available number of accounts in the controller is 5.
Adding account
Click on "+" button in the lower left corner of the user management window, then provide the account properties
as described in User accounts (page 161).
Note: Rules for the User accounts (page 161) credentials apply and some items are optional
Deleting account
Select the account that has to be deleted and click on "-" button in the lower left part of the user management
window.
Note: You can not delete your own administrator account unless there is another administrator account present
in the controller.
Note: It is not possible to change user name or UID. Instead of this create a new account with the required
changes and delete the original one.
Password protection
1. If an user performs five consecutive attempts to login using username/password, providing correct
username but incorrect password, the respective user account is blocked for a time period of 1 minute. The
attempts count regardless of the interface from which it is performed.
2. During the blocking period it is not possible to login with the respective account (username) from any
interface even if correct password is provided.
3. After the blocking period elapsed next attempt to login with the respective account (username) is possible. If
this attempt fails again the account is blocked again, now for period of 2 minutes.
4. The points 1-3 repeats further, the blocking period is multiplied by 2 in each next cycle. However, the
maximal blocking time is 20 minutes, the blocking time is never higher.
PIN protection
If an user performs ten consecutive attempts to login using UID/PIN, providing correct UID but incorrect
PIN, the user account is permanently blocked for login using UID/PIN. The user must login with
username/password and change the PIN to unblock this login method again.
Interface protection
If anyone performs twenty consecutive attempts to login via one particular interface and does not neither
provide a valid username nor a valid uid the respective interface is blocked for 2 minutes.
During this period it is not possible to use that interface for any login. The blocking period is not progressive in
this case.
Reading data
The access level required for reading data from controller is fixedly adjusted to 0. That means reading of data
(except some system objects) is available for any user.
Writing data
The access level required to write (modify) application setpoints or invoke application commands is
configurable via InteliConfig.
Special situations
There are several operations that require administrator level:
Programming firmware
Programming configuration
Managing user accounts
Note: Permanent blocking cannot occur accidentally, just by user mistake. It can be practically triggered only
by a focused activity.
3. Once you receive the reply from ComAp, copy the code from the e-mail (all characters inside the box as
indicated below)
6 back to Functions
6 back to Controller setup
6 Communication
6.1 PC 172
6.2 Connection to 3rd party systems 186
6.1 PC
6.1.1 Direct communication 172
6.1.2 Remote communication 174
RS485 interface uses COM2 Mode (page 378) port of the controller.
Note: Also USB-RS485 convertor can be used.
The static IP used in the controller must be selected in accordance with the local network in which CM-
Ethernet is connected.
The static IP used in the controller must be excluded from the pool of addresses which is assigned by
DHCP server, which is in charge of the respective local network.
The local infrastructure must generally allow using devices with manually assigned IP addresses.
There must not be any other device using the same static IP address. This can be tested from a computer
connected to the same network using "ping <required_ip_address>" command issued from the command
line. The IP address is not occupied if there is not any response to the ping command.
Note: The list above contains only basic rules. Other specific restrictions/rules may take place depending on
the local network security policy, technology used, topology etc.
Next way is to switch the CM-Ethernet to automatic IP address mode. Adjust the setpoint IP Address Mode
(page 1) to AUTOMATIC. In that case all IP settings are assigned by DHCP server. Then configure the DHCP
server to assign always the same IP address (i.e. static IP address) to the particular CM-Ethernet according to
it's MAC address.
Internet connection
Public static IP
If public static IP connection is to be used from the Internet, the IP address, which is entered into the client
computer, must be static and public in scope of the Internet.
If CM-Ethernet is connected to Internet via a local Ethernet network then in most cases port forwarding
must be created from the public IP address of the network gateway to the local IP address of CM-
Ethernet at the port specified for ComAp protocol. Different port numbers can be used to create multiple
port forwarding rules in the same local network.
AirGate
This connection type is intended for remote connection from InteliConfig,or any other ComAp PC tool over the
Internet in situations, where obtaining fixed public IP address is not possible. Only two remote clients can be
connected at the same time.
This connection type is active if AirGate connection is enabled. Setpoint AirGate Address (page 373) must
contain AirGate server address. It can be entered in text form as well as numeric form. There is a public AirGate
server available at address "airgate.comap.cz".
Once the controller is attached to the Internet and the AirGate server address is properly adjusted then the
controller registers automatically to the server and an identification string AirGate ID is given to a controller,
which is visible at the controller screen.
To connect your PC tool to the controller use the AirGate connection, put the the same AirGate address as in
the controller into the AIRGATE ADDRESS field and use the AirGate ID displayed on the controller.
SMS
Event SMS
The InteliLite 4 controller equipped with the CM-GPRS or CM-4G-GPS communication module is able to send
Event SMS according to the setting of setpoint:
Event Message (page 366)
Alarm SMS
The InteliLite 4 controller equipped with the CM-GPRS or CM-4G-GPS communication module is able to send
Alarm SMS according to the setting of setpoints:
Wrn Message (page 366)
Sd Messages (page 367)
BOC Message (page 366)
Message structure:
Gen-set Name
AL=(Alarm 1, Alarm 2, Alarm x)
Note: Asterisk means that alarm is unconfirmed and exclamation mark means that alarm is active.
SMS commands
To control the gen-set equipped with InteliLite 4 controller and CM-GPRS or CM-4G-GPS communication
module (or modem) via SMS requests, send an SMS in the structure of:
# xxxx, yyyy, zzzz, etc.
SMS send to the telephone number of the SIM card in your CM-GPRS module. Where the "#" mark means the
controller access code, "xxxx" means the Command 1, "yyyy" is Command 2, "zzzz" is Command 3, etc.
Note: Access code is set up via InteliConfig.
IMPORTANT: If wrong controller access code is set, then only help command is working.
Note: Between commands are internal delays adjusted due to system requirements.
Example: When the controller, in AUTO mode, with a controller name of "InteliLite 4-Test", with the CM-
GPRS module and access code "0" receives the SMS:
0 man, start, gcb close, gcb open, stop, auto
Controller mode will be changed to MANUAL mode. The engine will be started and GCB will close. Then
GCB will open, the engine will stop and it will go into AUTO mode again.
The controller will send back the SMS (controller will respond to SMS after every command has been
finished, not sooner.):
#InteliLite 4-Test: <OK>,<OK>,<OK>, <OK>,<OK>, <OK>
The value <OK> or <ERROR> means if the command has been performed successfully or not.
Emails
Event Email
The InteliLite 4 controller equipped with the CM-Ethernet communication module is able to send Event Email
according to the setting of setpoint:
Event Message (page 366)
Note: Firstly setpoints Email Address 1 (page 367) and SMTP Sender Address (page 1) (for CM-GPRS) or
SMTP Sender Address (page 1) (for CM-Ethernet) have to be adjusted.
Note: Summer Time Mode (page 331) and Time Zone (page 372) have to be adjusted for correct time in
emails.
Message structure:
Controller
-----------------------------------------------
Name: XXX
Serial number: XXX
SW branch: XXX
SW version: XXX
Application: XXX
Appl. version: XXX
Date: dd/mm/yyyy
Time: hh:mm:ss
Alarm list
-----------------------------------------------
Alarm 1
Alarm 2
Alarm 3
Events
-----------------------------------------------
hh:mm:ss Event 1
hh:mm:ss Event 2
hh:mm:ss Event 3
Alarm Email
The InteliLite 4 controller equipped with the CM-Ethernet communication module is able to send Alarm Emails
according to the setting of setpoints:
Wrn Message (page 366)
Sd Messages (page 367)
BOC Message (page 366)
Note: Firstly setpoints Email Address 1 (page 367) and SMTP Sender Address (page 1) (for CM-GPRS) or
SMTP Sender Address (page 1) (for CM-Ethernet) have to be adjusted.
Note: Summer Time Mode (page 331) and Time Zone (page 372) have to be adjusted for correct time in
emails.
Message structure:
Controller
-----------------------------------------------
Name: XXX
Serial number: XXX
SW branch: XXX
SW version: XXX
Application: XXX
Appl. version: XXX
Date: dd/mm/yyyy
Time: hh:mm:ss
Alarm list
-----------------------------------------------
Alarm 1
Alarm 2
Alarm 3
History events
-----------------------------------------------
0 dd/mm/yyyy hh:mm:ss.0 Event 1
-1 dd/mm/yyyy hh:mm:ss.0 Event 2
-2 dd/mm/yyyy hh:mm:ss.0 Event 3
Note: Asterisk means that alarm is unconfirmed and exclamation mark means that alarm is active.
Web Server
IMPORTANT: The web interface is based on HTTP protocol and is intended to be used only in
private networks. It is not recommended to expose the web interface to the public Internet.
The Web Server is designed for basic monitoring and adjustment of the controller using a web browser. Just put
the controller IP address into the browser to display the main controller web page like http://192.168.1.254. You
will be asked for the controller access code prior to entering the web pages.
IMPORTANT: Do not use the browser navigation buttons as "Back", "Forward" or "Reload". Use
the links and the reload button located in the toolbar instead.
Note: Only two remote clients can be connected to the Web Server at one moment. If you close your web
browser without disconnecting from the CM-Ethernet ("Exit" button at the web pages), the connection will be
blocked for next 5 minutes.
SCADA
Click to the SCADA link in the toolbar to display the SCADA page. The SCADA page is also the main page
which is displayed by default if you just put the CM-Ethernet address into the browser (after entering the right
access code).
Measurement
Click to the MEASUREMENT link in the toolbar to display the measurement page. Then click to the required
group name in the left box to display values of the group in the right box.
Note: The measurement page is automatically refreshed every 60 seconds (this time cannot be changed).
Setpoints
Click to the SETPOINTS link in the toolbar to display the setpoints page.
Click to the required group name in the left box to display setpoints of the group in the right box.
Click to the required setpoint name or value to change the value. If the respective setpoint is protected by
password, which is indicated by a lock icon by the setpoint name, you have to click on the "Controller
password" icon located in the toolbar and then enter valid password.
History
Click to the HISTORY link in the toolbar to display the history page.
Use the control buttons to move within the history file.
Note: The history page is automatically refreshed every 60 seconds. If a new record appears in the controller,
the web page will not show it immediately as e.g. InteliConfig.
6 back to Communication
6.2.1 SNMP
SNMP is an UDP-based client-server protocol used for providing data and events into a supervisory system
(building management system). The controller plays the role of a "SNMP Agent" while the supervisory system
plays the role of a "SNMP Manager".
CM-Ethernet module is required for SNMP function
Supported versions – SNMP v1 and SNMP v2c
The SNMP Agent function is to be enabled by the setpoint SNMP Agent (page 1) in the CM-Ethernet setpoint
group. The setpoints SNMP RD Community String (page 1) and SNMP WR Community String (page 1) in
the same group can be used to customize the "community strings" for the read and write operations which have
function like "passwords". All requests sent from the SNMP Manager have to contain community string which
match with the community string adjusted in the controller otherwise the controller refuses the operation.
MIB table
The „MIB table“ (Management Information Base) is a table which gives to the Manager description of all objects
provided by the Agent.
The MIB table is specific for each controller type and configuration
The MIB table is to be exported from the controller configuration using InteliConfig
Controllers with identical firmware and configuration share also identical MIB table, however if the
configuration and/or firmware is not identical the MIB table is different and must be exported separately for
each controller.
The root node of the MIB table of InteliLite controller is enterprises.comapProjekt.il, which is
1.3.6.1.4.1.28634.14. Under this node there are following sub-nodes :
Notifications group (SMI v2 only) contains definitions of all notification-type objects that the Agent may send
to the Manager.
GroupRdFix contains read-only objects that exist in all controller regardless of the firmware version/type and
configuration.
GroupRdCfg contains read-only objects that depend on the firmware version/type and configuration.
GroupWrFix contains read-write objects that exist in all controller regardless of the firmware version/type
and configuration.
GroupWrCfg contains read-write objects that depend on the firmware version/type and configuration.
GroupW contains write-only objects.
NotificationData group contains objects that are accessible only as bindings of the notification messages.
SMI version
In InteliConfig the MIB table may be exported in two different formats – SMI v1 and SMI v2. The format which
shall be used for export depends on the SNMP Manager and SMI version that it does support.
Typically, SMI v1 is used for SNMP v1 and vice versa, but it is not a rule and SMI v2 may be also used for
SNMP v1.
SNMP notifications
Except the request-response communication model, in which the communication is controlled by the Manager,
there are also messages that the Agent sends without any requests. These messages are called „Notifications“
and inform the Manager about significant events occurred in the Agent.
The controller can send notifications to two different SNMP Managers (two different IP addresses). The
addresses are to be adjusted in the CM-Ethernet setpoint group by the setpoints SNMP Traps IP Address 1
(page 1) and SNMP Traps IP Address 2 (page 1). If the Manager address is not adjusted the particular
notification channel is off. The controller will send the notifications in format adjusted by the setpoint SNMP
Trap Format.
Each notification (kind of event) is identified by an unique identifier (Trap ID in SNMPv1 or Notification OID
in SNMPv2). This unique identifier gives the specific meaning to the notification message, e.g. Protection 1.
level – Fuel Level – alarm activated.
All possible notifications and their identifiers are listed in the MIB table.
The notification message also contains controller name, serial number and textual description of the event.
SMI version
In InteliConfig the MIB table may be exported in two different formats – SMI v1 and SMI v2. The format which
shall be used for export depends on the SNMP Manager and SMI version that it does support. Typically, SMI v1
is used for SNMP v1 and vice versa, but it is not a rule and SMI v2 may be also used for SNMP v1.
Note: *)
For list of commands, arguments and description of the procedure of invoking commands see the description of
the Modbus protocol.
Note: Modbus-RTU serial communication mode is 8-N-1 – startbit 1, 8 data bits, no parity and 1 stopbit.
Address space
The object address space is separated into several areas as described in the table below. The actual mapping of
specific controller data objects to specific Modbus addresses, which depends on configuration, can be exported
into a text file from the appropriate controller archive using InteliConfig. There are several special registers with
fixed meaning (reserved registers) which are listed in a separate table in this chapter.
Number of
Data type Meaning Data maping
registers
MSB = sign extension
Integer8 1-byte signed integer 1
LSB = value
MSB = 0
Unsigned8 1-byte unsigned integer 1
LSB = value
MSB = value, MSB
Integer16 2-byte signed integer 1
LSB = value, LSB
MSB = value, MSB
Unsigned16 2-byte unsigned integer 1
LSB = value, LSB
MSB1 = value, byte 3 (MSB)
LSB1 = value, byte 2
Integer32 4-byte signed integer 2
MSB2 = value, byte 1
LSB2 = value, byte 0 (LSB)
MSB1 = value, byte 3 (MSB)
LSB1 = value, byte 2
Unsigned32 4-byte unsigned integer 2
MSB2 = value, byte 1
LSB2 = value, byte 0 (LSB)
MSB = 0
Binary8 8-bit binary value 1
LSB = value, bits 0-7
MSB = value, bits 8-15
Binary16 16-bit binary value 1
LSB = value, bits 0-7
MSB1 = value, bits 24-31
LSB1 = value, bits 16-23
Binary32 32-bit binary value 2
MSB2 = value, bits 8-15
LSB2 = value, bits 0-7
Char 1-byte ASCII character 1 MSB = 0
Number of
Data type Meaning Data maping
registers
LSB = ASCII value of the character
MSB = 0
StrList Index into a list of strings 1
LSB = index into the list
MSB1 = ASCII value of the 1. character
LSB1 = ASCII value of the 2. character
Zero-terminated string of
ShortStr 8 MSB2 = ASCII value of the 3. character
max 15 ASCII characters.
LSB2 = ASCII value of the 4. character
…
MSB1 = ASCII value of the 1. character
LSB1 = ASCII value of the 2. character
Zero-terminated string of
LongStr 16 MSB2 = ASCII value of the 3. character
max 31 ASCII characters.
LSB2 = ASCII value of the 4. character
…
MSB1 = BCD (dd)
LSB1 = BCD (mm)
Date Date (dd-mm-yy) 2
MSB2 = BCD (yy)
LSB2 = 0
MSB1 = BCD (hh)
LSB1 = BCD (mm)
Time Time (hh-mm-ss) 2
MSB2 = BCD (ss)
LSB2 = 0
MSB1 = reserved for future use
LSB1 = reserved for future use
MSB2 = Alarm level *)
LSB2 = Alarm status **)
Alarm An item of the Alarmlist 27 MSB3 = alarm string ***)
LSB3 = alarm string
MSB4 = alarm string
LSB5 = alarm string
…
Note:
*) 1 .. level 1 (yellow), 2 .. level 2 (red), 3 .. sensor fail
**) Bit0 – alarm is active, Bit1 – alarm is confirmed
***) String encoding is UTF-8
Reserved registers
There are several registers with specific meaning. These registers are available in all controllers regardless of
the configuration.
Register Number of
Access Data type Meaning
addresses registers
4200 - 4201 2 read/write Time RTC Time in BCD code
4202 - 4203 2 read/write Date RTC Date in BCD code
Index of the language that is used for text
4204 1 read/write Unsigned8 data provided by MODBUS (e.g. alarmlist
messages).
Last application error. To be read after the
4205 - 4206 2 read Unsigned32 device returns the exception code 04. It
contains specific information about the error.
Writing:command argument
4207 - 4208 2 read/write Unsigned32
Reading: command return value
4209 1 write Unsigned16 Command code
4010 1 - - Not implemented
4211 1 write Unsigned16 Password
4212 - 4213 2 read Unsigned32 Communication status
4214 1 read Unsigned8 Number of items in the Alarmlist
4215 - 4241 27 read Alarm 1. record in alarm list
4242 - 4268 27 read Alarm 2. record in alarm list
4269 - 4295 27 read Alarm 3. record in alarm list
4296 - 4322 27 read Alarm 4. record in alarm list
4323 - 4349 27 read Alarm 5. record in alarm list
4350 - 4376 27 read Alarm 6. record in alarm list
4377 - 4403 27 read Alarm 7. record in alarm list
4404 - 4430 27 read Alarm 8. record in alarm list
4431 - 4457 27 read Alarm 9. record in alarm list
4458 - 4484 27 read Alarm 10. record in alarm list
4485 - 4511 27 read Alarm 11. record in alarm list
Register Number of
Access Data type Meaning
addresses registers
4512 - 4538 27 read Alarm 12. record in alarm list
4539 - 4565 27 read Alarm 13. record in alarm list
4566 - 4592 27 read Alarm 14. record in alarm list
4593 - 4619 27 read Alarm 15. record in alarm list
4620 - 4646 27 read Alarm 16. record in alarm list
Note: *)
This action is an equivalent of pressing the front panel button
MODBUS examples
Modbus RTU examples
Reading of Battery voltage
Export table of values from InteliConfig
Table: Values
Allowed Modbus functions: 03, 04
Register(s) Com.Obj. Name Dimension Type Len Dec Min Max Group
Controller
01053 8213 BatteryVoltage V Integer 2 1 0 400
I/O
We read value 240 from register 01053. From table of Modbus registers we get dimension of read value and
"Dec". Dec=1 means shift one decimal place to the right. So battery voltage is 24.0 V.
Reading Nominal power
Export table of values from InteliConfig
Table: Values
Allowed MODBUS functions: 03, 04
Register(s) Com.Obj. Name Dimension Type Len Dec Min Max Group
01228 9018 Nominal Power kW Integer 2 0 0 32767 Generator
Table: Values
Allowed Modbus functions: 03, 04
Register(s) Com.Obj. Name Dimension Type Len Dec Min Max Group
Binary
01068 8235 Binary#2 2 0 - - Controller I/O
Inputs
Binary inputs is 00010010. It means Binary input 2 and binary input 5 are active.
Note: You can use Modbus function 4 instead of 3, rest of data remain same (CRC differs).
Table: Binaries
Allowed Modbus functions: 01, 02
Addresses Source
C.O.# Name of Value Bit Name
Modbus Addr. = Value Bit # Group
State # Name of State Activated by protection(s):
Prot. Addr. = State
00000 Value 8235 Binary Inputs 1 GCB Feedback Controller I/O
00001 Value 8235 Binary Inputs 2 MCB Feedback Controller I/O
00002 Value 8235 Binary Inputs 3 Emergency Stop Controller I/O
Note: Command and argument may be written as one "packet" (function 16) or you can split it and write
argument (function 16) and after that write command code (function 6).
Password
This password is the same as in InteliConfig or directly in controller.
Table Reserved registers (page 191)
Table: Setpoints
Allowed Modbus functions: 03, 04, 06, 16
Register(s) Com.Obj. Name Dimension Type Len Dec Min Max Group
Nominal Basic
03008 8276 kW Unsigned 2 0 1 5000
Power Settings
Table: Values
Allowed Modbus functions: 03, 04
Register(s) Com.Obj. Name Dimension Type Len Dec Min Max Group
Controller
01053 8213 BatteryVoltage V Integer 2 1 0 400
I/O
We read value 240 from register 01053. From table of Modbus registers we get dimension of read value and
"Dec". Dec=1 means shift one decimal place to the right. So battery voltage is 24.0 V.
6 back to Communication
Accuracy 1%
Display
Type Build-in monochromatic 3.2"
Resolution 132 × 64 px
Communications
USB Device Non-isolated type B connector
RS485 Isolated
250 / 50 kbps, nominal impedance
CAN 1
120 Ω
Current measurement
Measurement inputs 3ph Gen current
Measurement range 5A
8 Appendix
8.1 Controller objects 201
8.2 Alarms 570
8.3 Modules 636
8.1.2 Setpoints
What setpoints are:
Setpoints are analog, binary or special data objects which are used for adjusting the controller to the specific
environment. Setpoints are organized into groups according to their meaning. Setpoints can be adjusted from
the controller front panel, PC, MODBUS, etc.
All setpoints can be protected by a password against unauthorized changes. Password protection can be
assigned to the setpoints during the configuration procedure. See the chapter Password (page 1) in Operator
guide for instructions on how to enter and modify a password.
IMPORTANT: Do not write setpoints repeatedly (e.g. power control from a PLC by repeated writing
of baseload setpoint via Modbus). The setpoints are stored in EEPROM memory, which can be
5
overwritten up to 10 times without risk of damage or data loss, but it may become damaged, when
the allowed number of writing cycles is exceeded.
For full list of setpoints go to the chapter List of setpoints (page 202).
Subgroup: Name
Gen-Set Name
Setpoint group Basic settings Related FW 1.0.0
Range [units] 0 .. 15 characters [-]
Default value InteliLite Alternative config NO
Step [-]
Comm object 8637 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
User defined name, used for the controller identification at remote phone or mobile connection. Gen-set
Name is maximally 15 characters long and can be entered using InteliConfig or from controller's
configuration menu.
Note: If the Gen-set Name is "TurboRunHours", the running hours will be counted faster – 1 minute in
real will represent 1 hour.
Note: To lock this setpoint against editing you also have to lock setpoint Nominal Power Split Phase
1 (page 389), Nominal Power Split Phase 2 (page 395) and Nominal Power Split Phase 3 (page
401).
Nominal Power
Setpoint group Basic settings Related FW 1.0.0
Range [units] 1 .. 5 000 [kW]
Default value 200 kW Alternative config YES
Step 1 kW
Comm object 8276 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal power of the gen-set. Generator Overload BOC (page 263) protection is based on this setpoint.
Note: This setpoint is used when setpoint Connection type (page 211) is adjusted to Monophase or
Splitphase or 3Ph3Wire or High Leg D or 3Ph4Wire or when Autodetect detects connection type as
3Ph3Wire or High Leg D or 3Ph4Wire.
Note: To lock this setpoint against editing you also have to lock setpoint Nominal Power 1 (page 388),
Nominal Power 2 (page 394) and Nominal Power 3 (page 400).
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Nominal Current
Setpoint group Basic settings Related FW 1.0.0
Range [units] 1 .. 10 000 [A]
Default value 350 A Alternative config YES
Step 1A
Comm object 8275 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Connection type (page 211).
Description
It is current limit for mains current protections and means maximal continuous mains current. Nominal
Current can be different from mains rated current value.
Note: To lock this setpoint against editing you also have to lock setpoint Nominal Current 1 (page
385), Nominal Current 2 (page 391) and Nominal Current 3 (page 397).
CT Ratio
Setpoint group Basic settings Related FW 1.0.0
Range [units] 1 .. 5 000 [A/5A]
Default value 2 000 A/5A Alternative config NO
Step 1 A/5A
Comm object 8274 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Gen-set Mains import current transformers ratio.
Note: Generator Mains currents and power measurement is suppressed if current level is below 1% of
CT range.
CT Location
Setpoint group Basic settings Related FW 1.0.0
Range [units] Load / Gen-set / None [-]
Default value Gen-set Alternative config NO
Step [-]
Comm object 11625 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts position of current measurement.
Load Current CT's are physically placed on Load (typically between GCB and MCB).
Gen-set Current CT's are physically placed on Gen-set (typically before GCB).
None There are no current CT's.
Connection type
Setpoint group Basic settings Related FW 1.0.0
Mono Phase / SplPhL1L2 / SplPhL1L3SplitPhase / 3Ph3Wire / 3Ph4Wire / High
Range [units]
Leg D / Autodetect [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 11628 Related applications AMF, MRS
Config level Standard
Note: To lock this setpoint against editing you also have to lock setpoint Connection Type 1 (page
385), Connection type 2 (page 391) and Connection type 3 (page 397).
Gen VT Ratio
Setpoint group Basic settings Related FW 1.0.0
Range [units] 0.1 .. 500.0 [V/V]
Default value 1.0 V/V Alternative config NO
Step 0.1 V/V
Comm object 9579 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Generator voltage potential transformers ratio. If no VTs are used, adjust this setpoint to 1.
6 back to List of setpoints
Mains VT Ratio
Setpoint group Basic settings Related FW 1.0.0
Range [units] 0.1 .. 500.0 [V/V]
Default value 1.0 V/V Alternative config NO
Step 0.1 V/V
Comm object 9580 Related applications AMF
Config level Advanced
Setpoint visibility Conditioned by the setpoint Default Application Select (page 220)
Description
Mains voltage potential transformers ratio. If no VTs are used, adjust the setpoint to 1.
6 back to List of setpoints
Nominal Frequency
Setpoint group Basic settings Related FW 1.0.0
Range [units] 45 .. 65 [Hz]
Default value 50 Hz Alternative config YES
Step 1 Hz
Comm object 8278 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note: To lock this setpoint against editing you also have to lock setpoint Nominal Frequency 1 (page
384), Nominal Frequency 2 (page 390) and Nominal Frequency 3 (page 396).
Gear Teeth
Setpoint group Basic settings Related FW 1.0.0
Range [units] FGen->RPM / 1 .. 500 [-]
Default value 120 Alternative config NO
Step 1
Comm object 8252 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Number of teeth on the engine flywheel where the pick-up is installed. Set to zero if no pick-up is used and
the Engine speed will be counted from the generator frequency.
Note: If no pickup is used, the D+ or W terminal should be used to prevent possible overcranking, which
can occur if at least 25% of nominal generator voltage is not present immediately after exceeding firing
speed.
Nominal RPM
Setpoint group Basic settings Related FW 1.0.0
Range [units] 100 .. 4 000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 8253 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note: To lock this setpoint against editing you also have to lock setpoint Nominal RPM 1 (page 383),
Nominal RPM 2 (page 389) and Nominal RPM 3 (page 395).
Controller Mode
Setpoint group Basic settings Related FW 1.0.0
Range [units] OFF / MAN / AUTO / TEST [-]
Default value OFF Alternative config NO
Step [-]
Comm object 8315 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint can be used for changing the Controller mode remotely, e.g. via Modbus. Use the mode
selector on the main screen for changing the mode from the front panel. Use mode selector in the control
window for changing the mode from InteliConfig.
6 back to List of setpoints
Power On Mode
Setpoint group Basic settings Related FW 1.0.0
Range [units] Previous / OFF [-]
Default value Previous Alternative config NO
Step [-]
Comm object 13000 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts controller mode after power on of controller.
Previous When controller is power on, than is switched into last mode before power off.
OFF When controller is power on, than is switched into OFF mode.
Note: Remote modes - In case that some LBI remote mode is activated during power on of controller
than this LBI has higher priority than this setpoint - controller mode is forced into mode selected via LBI.
After deactivation of LBI, controller is switched into value selected via setpoint Power On Mode
The breaker is controlled only from controller. Any unexpected change of GCB
feedback causes Sd GCB fail immediately.
Incorrect reaction of the GCB feedback on internal GCB Close command causes
Sd GCB fail (within 5 s when closing to the dead bus, 2 s when synchronising).
Internal
Incorrect reaction of the GCB feedback on internal GCB Open command causes
Sd GCB fail (within 2 s).
Anytime when the controller is synchronizing via GCB the Extranal GCB closing is
being accepted in all GCB control modes.
In this mode is the external GCB opening from the external (protection) device
accepted. There is no alarm issued, only the event "GCB Opened Externally" is
recorded in history log.
Incorrect reaction of the GCB feedback on internal GCB Close command causes
Follow Sd GCB fail (within 5 s when closing to the dead bus, 2 s when synchronising).
Incorrect reaction of the GCB feedback on internal GCB Open command causes
Sd GCB fail (within 2 s).
Anytime when the controller is synchronizing via GCB the Extranal GCB closing is
being accepted in all GCB control modes.
Controller does not control the GCB at all. The GCB is controller Externally, when
the GCB feedback get changed, then the event "GCB Opened" or "GCB Closed" is
recorded in the history log.
Controller always accept the GCB feadback position, do not issue any alarm.
The Controller does not care about the GCB position even the engine is stopped or
running. Gen-set with closed GCB is not blocked against starting.
When the Sd protection shut down the engine, the GCB stays closed. The BOC
External protection do not open the GCB, controller goes to cooling when the BOC
protection was tripped (GCB stays closed until opened externally).
The controller informs the superordinated system about the status of the braker
automat using the signals
LBO FORWARD SYNCHRONISATION (PAGE 1)
LBO REVERSE SYNCHRONISATION (PAGE 1)
LBO IN SYNCHRONISM (PAGE 1)
LBO READY TO LOAD (PAGE 534)
No Button GCB button and LBI GCB button is deactivated.
Reset To Manual
Setpoint group Basic settings Related FW 1.0.0
Range [units] Disabled / Enabled [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 9983 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
If this function is enabled, the controller will switch automatically to MAN mode when there is a red alarm in
the alarm list and fault reset button is pressed. This is a safety function that prevents the gen-set starting
again automatically in specific cases when fault reset button is pressed.
Example: Controller is in AUTO mode and there is red inactive unconfirmed alarm and fault reset
button is pressed, controller will start automatically.
Backlight Timeout
Setpoint group Basic settings Related FW 1.0.0
Range [units] Disabled / 1 .. 255 [min]
Default value Disabled Alternative config NO
Step 1 min
Comm object 10121 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
The display backlight is switched off when this timer exceed. When setpoint is adjusted to disabled then the
display will be backlighted all the time.
6 back to List of setpoints
Horn Timeout
Setpoint group Basic settings Related FW 1.0.0
Range [units] Disabled / 1 .. 599 [s]
Default value 10 s Alternative config NO
Step 1s
Comm object 8264 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Setting of horn behavior.
Disabled Disabling the Horn sounding function
Timeout for HORN (PAGE 518) binary output. The HORN (PAGE 518) output is active
1 .. 599 [s]
when this timeout elapsed.
Note: Horn timeout starts again from the beginning if a new alarm appears before previous Horn timeout
has elapsed.
Note: While there is USB power present (USB cable plagued) the controller is able to turn off when there
is no user interaction but wake up is not possible. USB power has to be cut off (USB cable unplagued).
Note: It is not necessary to restart controller when this setpoint is changed. Change of this setpoint
should be applied immediately.
Screen Filter
Setpoint group Basic settings Related FW 1.0.0
Range [units] Enable/Disabled [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 15889 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables/disables filter values on CU screen.
List of values which are filtered when filter is ON.
Generator Voltage L1-L2
Generator Voltage L2-L3
Generator Voltage L3-L1
Generator Voltage L1-N
Generator Voltage L2-N
Generator Voltage L3-N
Generator Frequency
Load kVA
Load kVA L1
Load kVA L2
Load kVA L3
Load kVAr
Load kVAr L1
Load kVAr L2
Load kVAr L3
Load kW
Load kW L1
Load kW L2
Load kW L3
Phase Rotation
Setpoint group Basic settings Related FW 1.0.0
Range [units] Clockwise / CounterCCW [-]
Default value Clockwise Alternative config NO
Step [-]
Comm object 15122 Related applications AMF, MRS
Config level Advanced
Setpoint visibility All the time
Description
This setpoint adjust the phase sequence of voltage terminals.
Screen Filter
Setpoint group Basic settings Related FW 1.0.0
Range [units] Enable/Disabled [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 15889 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables/disables filter values on CU screen and PC tools.
6 back to List of setpoints
Controller Address
Communication
Setpoint group Related FW 1.0.0
Settings
Range [units] 1 .. 32 [-]
Default value 1 Alternative config NO
Step 1
Comm object 24537 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Controller identification number. It is possible to set controller address different from the default value (1) so
that more controllers can be interconnected (via RS485 ) and accessed e.g. from Modbus terminal.
Note: When opening connection to the controller it's address has to correspond with the setting in PC
tool.
RS485 Mode
Communication
Setpoint group Related FW 1.0.0
Settings
Range [units] Dual Master / Dual Slave [-]
Default value Direct Alternative config NO
Step [-]
Comm object 24134 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Communication protocol switch for on-board RS485.
Subgroup: Starting
Fuel Solenoid
Setpoint group Engine settings Related FW 1.0.0
Range [units] Diesel / Gas [-]
Default value Diesel Alternative config NO
Step [-]
Comm object 9100 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Determines behavior of the Binary output FUEL SOLENOID (PAGE 509)
Diesel: Output is activated before binary output STARTER 1 (PAGE 536). Lead of output is
adjusted via setpoint Fuel Solenoid Lead (page 239). The output is deactivated if
Emergency Stop comes or Gen-set is stopped and in pause between repeated starts.
Gas: Output is activated together with binary output IGNITION (PAGE 520) if RPM is over the
(Gaseous) 30 RPM (fixed value). Output is deactivated after stop command or in pause between
repeated start.
Cranking Attempts
Setpoint group Engine settings Related FW 1.0.0
Range [units] 1 .. 10 [-]
Default value 3 Alternative config NO
Step 1
Comm object 8255 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maximal number of cranking attempts.
6 back to List of setpoints
Prestart Time
Setpoint group Engine settings Related FW 1.0.0
Range [units] 0 .. 600 [s]
Default value 2s Alternative config NO
Step 1s
Comm object 8394 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Time of closing of the PRESTART (PAGE 531) output prior to the engine start. Set to zero if you want to leave
the output PRESTART (PAGE 531) open.
Starting RPM
Setpoint group Engine settings Related FW 1.0.0
Range [units] 5 .. 50 [%]
Default value 25% Alternative config NO
Step 1 % of Nominal RPM (page 218)
Comm object 8254 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint defines the "firing" speed level as percent value of the Nominal RPM (page 218). If this level
is exceeded the engine is considered as started.
Idle RPM
Setpoint group Engine settings Related FW 1.0.0
Range [units] 100 .. 4000 [RPM]
Default value 900 RPM Alternative config NO
Step 1 RPM
Comm object 9946 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts idle speed of engine.
Subgroup: Choke
Choke Function
Setpoint group Engine settings Related FW 1.0.0
Range [units] Disabled /Fixed Time / Temp Based [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 15717 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Only when LBO CHOKE (PAGE 503) is configured.
Description
This setpoint defines choke function behavior.
Disabled Choke function is disabled and logical binary output CHOKE (PAGE 503) is
activated under no circumstances.
Fixed Time Choke time is fixedly defined by Choke Time (page 234) setpoint.
Temp Based Choke time is calculated using actual engine (coolant) temperature. Setpoints
Choke Start Temp (page 235) and Choke Increment (page 236) are taken into
consideration.
Choke Time
Setpoint group Engine settings Related FW 1.0.0
Range [units] 0–3600 [s]
Default value 0s Alternative config NO
Step 1s
Comm object 13011 Related applications AMF, MRS
Config level Advanced
Only when LBO CHOKE (PAGE 503) is configured and setpoint Choke Function (page
Setpoint visibility
234) = Fixed Time.
Description
Defines time logical binary output CHOKE (PAGE 503) is activated for when fixed time is used. When setpoint
Choke Function (page 234) is set to Temp Based value, Choke Time value have no effect.
Note: If setpoint Choke Lead (page 238) is set to nonzero value, total time the CHOKE output is
activated still matches value set by Choke Time setpoint. This mean Choke Timeshould be longer than
Choke Leadto ensure expected Choke behavior.
Choke Increment
Setpoint group Engine settings Related FW 1.0.0
Range [units] 0,00 .. 20,00 [s/°C]
Default value 0,00 s/°C Alternative config NO
Step 0,01 s/°C
Comm object 15715 Related applications AMF, MRS
Config level Advanced
Only when LBO CHOKE (PAGE 503) is configured and setpoint Choke Function
Setpoint visibility
(page 234) = Temp Based.
Description
This setpoint adjust the maximal time of activation of binary output CHOKE (PAGE 503). Calculated time
depends on engine (coolant) temperature. Setpoint adjust curve which is used for calculating actual Choke
Time. When setpoint Choke Function (page 234) is set to Fixed Time value, setpoint Choke Increment has
no effect.
Note: If setpoint Choke Lead (page 238) is set to nonzero value, total time the CHOKE output is
activated still matches calculated value (based on actual temperature and setpoints Choke Increment
and Choke Start Temp (page 235)) This mean that adjusted parameters should ensure that calculated
Choke Time will be longer than Choke Leadto ensure expected Choke behavior.
Choke Voltage
Setpoint group Engine settings Related FW 1.0.0
Range [units] Disabled / 1–100 [%]
Default value Disabled Alternative config NO
Step 1%
Comm object 15718 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Only when LBO CHOKE (PAGE 503) is configured.
Description
This setpoint adjust threshold level for deactivation of CHOKE (PAGE 503) binary output. When generator
voltage is higher than this level, then logical binary output CHOKE is deactivated. In multiphase system it is
sufficient to deactivate CHOKE LBO when at least one voltage crosses this threshold. In case setpoint
Choke Voltage is set to Disabled value, no voltage is taken into account and CHOKE LBO isn't deactivated
on the voltage basis.
Choke Lead
Setpoint group Engine settings Related FW 1.0.0
Range [units] 0 .. Prestart Time [s]
Default value 0s Alternative config NO
Step 1s
Comm object 15774 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Only when LBO CHOKE (PAGE 503) is configured.
Description
This setpoint adjust the lead of logical binary output CHOKE. CHOKE (PAGE 503) is activated before logical
binary output STARTER 1 (PAGE 536).
Note: In case Choke Lead is longer than 8 s (cranking fail pause), Choke Lead will be limited to 8 s
(cranking fail pause time). This limitation is applied only for cranking fail pause, Choke Lead in Prestart
stays unchanged.
Note: LBO PRESTART (PAGE 531) goes to logical zero when Fuel Solenoid Lead goes to logical one.
Note: This setpoint is used only for diesel Fuel Solenoid (page 230)
Idle Time
Setpoint group Engine settings Related FW 1.0.0
Range [units] 0 .. 600 [s]
Default value 12 s Alternative config NO
Step 1s
Comm object 9097 Related applications AMF, MRS
Config level Standard
Sd Ventilation Time
Setpoint group Engine settings Related FW 1.0.0
Range [units] 0 .. 60 [s]
Default value 5s Alternative config NO
Step 1s
Comm object 9695 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
In case Fuel Solenoid (page 230) is set to GAS, the Sd Ventilation Time adjusts the time of the starter to
be switched on for engine pre-ventilation in the case of a first start attempt after shutdown or controller
switch-on.
6 back to List of setpoints
Subgroup: Stopping
Cooling Speed
Setpoint group Engine settings Related FW 1.0.0
Range [units] Idle / Nominal [-]
Default value Nominal Alternative config NO
Step [-]
Comm object 10046 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Selects the function of the binary output IDLE/NOMINAL (PAGE 519) during engine cooling state.
Idle Cooling is executed at Idle speed and generator protections are switched off.
Nominal Cooling is executed at Nominal speed and generator protections are active.
Note: When ECU is connected the predefined value 900 RPM for Idle speed is requested.
Note: Binary output IDLE/NOMINAL (PAGE 519) must be configured and connected to speed governor.
Engine Idle speed must be adjusted on speed governor.
Cooling Time
Setpoint group Engine settings Related FW 1.0.0
Range [units] 0 .. 3 600 [s]
Default value 30 s Alternative config NO
Step 1s
Comm object 8258 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Runtime of the unloaded gen-set to cool the engine before stop.
Stop Time
Setpoint group Engine settings Related FW 1.0.0
Range [units] 0 .. 600 [s]
Default value 60 s Alternative config NO
Step 1s
Comm object 9815 Related applications AMF, MRS
Config level Advanced
Subgroup: D+ Function
D+ Function
Setpoint group Engine settings Related FW 1.0.0
Range [units] Enabled / ChargeFail / Disabled [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 9683 Related applications AMF, MRS
Config level Standard
Enabled The D+ terminal is used for both functions – “running engine” detection and
charge fail detection.
ChargeFail The D+ terminal is used for charge fail detection only
Disabled The D+ terminal is not used.
Note: Delay of this function is adjusted via D+ Delay (page 248) setpoint, threshold of this function is
adjusted via D+ Level setpoint.
D+ Threshold
Setpoint group Engine settings Related FW 1.0.0
Range [units] 0..100 [%]
Default value 80 % Alternative config NO
Step 1%
Comm object 14959 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Only if setpoint D+ Function (page 246) is not set to Disabled value.
Description
This setpoint adjusts threshold level for D+ Function (page 246).
6 back to List of setpoints
D+ Delay
Setpoint group Engine settings Related FW 1.0.0
Range [units] 1..255 [s]
Default value 1s Alternative config NO
Step 1s
Comm object 14960 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Only if setpoint D+ Function (page 246) is not set to Disabled value.
Description
This setpoint adjusts delay for D+ Function (page 246). This delay is used for:
Alarm Wrn Charging Alternator Fail (page 590).
For engine running condition – disengagement of starter
D+ Alarm Type
Setpoint group Engine settings Related FW 1.0.0
Range [units] No Protec/Wrn/Sd [-]
Default value Wrn Alternative config NO
Step [-]
Comm object 15751 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Only if setpoint D+ Function (page 246) is not set to Disabled value.
Description
This setpoint adjusts type of alarm Wrn Charging Alternator Fail (page 590).
6 back to List of setpoints
Overspeed Sd
Setpoint group Engine settings Related FW 1.0.0
Range [units] Underspeed Sd (page 251)50 .. 200 [%]
Default value 115% Alternative config NO
Step 1 % of Nominal RPM (page 218)
Comm object 8263 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for over speed protection. Relative to the nominal speed.
6 back to List of setpoints
Starting Overspeed Sd
Setpoint group Engine settings Related FW 1.0.0
Range [units] 100 ..200 [%]
Default value 115% Alternative config NO
Step 1%
Comm object 11033 Related applications AMF, MRS
Config level Standard
Underspeed Sd
Setpoint group Engine settings Related FW 1.0.0
Range [units] 0 .. Overspeed Sd (page 249) [%]
Default value 25% Alternative config NO
Step 1 % of Nominal RPM (page 218)
Comm object 8260 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for underspeed protection. Relative to the nominal speed.
6 back to List of setpoints
Fuel Pump On
Setpoint group Engine settings Related FW 1.0.0
Range [units] 0 .. Fuel Pump Off (page 254) [%]
Default value 20 % Alternative config YES
Step 1%
Comm object 10100 Related applications AMF, MRS
Config level Advanced
Visible only if the logical binary output FUEL PUMP (PAGE 509) is configured and
Setpoint visibility
logical binary input FUEL PUMP ON/OFF (PAGE 480) isn't configured
Description
Threshold level for switching the binary output FUEL PUMP (PAGE 509) on.
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 480) is configured then binary
output FUEL PUMP (PAGE 509) is control by this binary input. Setpoints Fuel Pump On and
Fuel Pump Off (page 254) are not evaluated!
Note: Value from analog input has higher priority than ECU.
Note: This setpoint is visible only if the logical binary output FUEL PUMP (PAGE 509) is configured.
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 480) is configured then binary
output FUEL PUMP (PAGE 509) is control by this binary input. Setpoints Fuel Pump On (page
253) and Fuel Pump Off are not evaluated!
Note: Value from analog input has higher priority than ECU.
Note: This setpoint is visible only if the logical binary output FUEL PUMP (PAGE 509) is configured.
Temperature Switch On
Setpoint group Engine settings Related FW 1.0.0
Range [units] the range is define by sensor curve (analog or ECU)
the value is defined by
Default value an an sensor curve Alternative config NO
(analog or ECU)
Step the step is defined by an sensor curve (analog or ECU)
Comm object 8688 Related applications AMF, MRS
Config level Standard
Visible only if the logical binary output TEMPERATURE SWITCH (PAGE 539) is
Setpoint visibility
configured.
Description
Threshold level for switching the binary output TEMPERATURE SWITCH (PAGE 539) on.
Note: Value from analog input has higher priority than ECU.
Battery Undervoltage
Setpoint group Engine settings Related FW 1.0.0
Range [units] 8,0 V .. Battery Overvoltage (page 258) [V]
Default value 18,0 V Alternative config NO
Step 0,1 V
Comm object 8387 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Warning threshold for low battery voltage.
6 back to List of setpoints
Battery Overvoltage
Setpoint group Engine settings Related FW 1.0.0
Range [units] Battery Undervoltage (page 257) .. 40,0 [V]
Default value 36,0 V Alternative config NO
Step 0,1 V
Comm object 9587 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Warning threshold for high battery voltage.
6 back to List of setpoints
Maintenance Timer 1
Setpoint group Engine settings Related FW 1.0.0
Range [units] -10 000 ... 9 999 [h] / Disabled
Default value 1 000 h Alternative config NO
Step 1h
Comm object 11616 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maintenance timer 1 counts down when engine is running. If reaches zero, an alarm appears, but the timer
still counting down into negative values. When the value 10000 is set, than the Maintenance function is
disabled and counter does not count. Counter value disappear from controllers statistics.
6 back to List of setpoints
Maintenance Timer 2
Setpoint group Engine settings Related FW 1.0.0
Range [units] -10 000 ... 9 999 [h] / Disabled
Default value 1 000 h Alternative config NO
Step 1h
Comm object 11617 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maintenance timer 2 counts down when engine is running. If reaches zero, an alarm appears, but the timer
still counting down into negative values. When the value 10000 is set, than the Maintenance function is
disabled and counter does not count. Counter value disappear from controllers statistics.
6 back to List of setpoints
Maintenance Timer 3
Setpoint group Engine settings Related FW 1.0.0
Range [units] -10 000 ... 9 999 [h] / Disabled
Default value 1 000 h Alternative config NO
Step 1h
Comm object 11618 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maintenance timer 3 counts down when engine is running. If reaches zero, an alarm appears, but the timer
still counting down into negative values. When the value 10000 is set, than the Maintenance function is
disabled and counter does not count. Counter value disappear from controllers statistics.
6 back to List of setpoints
Maintenance Timer 4
Setpoint group Engine settings Related FW 1.0.0
Range [units] [DD/MM/YYYY]
Default value 01/01/2015 Alternative config NO
Step 1 day
Comm object 16384 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
This maintenance timer is based on date. At the midnight of the last day the alarm Wrn Maintenance 4
(page 608) appears in alarmlist.
IMPORTANT: To disable this maintenance timer, set date to 01/01/2015.
Maintenance Timer 5
Setpoint group Engine settings Related FW 1.0.0
Range [units] [DD/MM/YYYY]
Default value 01/01/2015 Alternative config NO
Step 1 day
Comm object 16385 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
This maintenance timer is based on date. At the midnight of the last day the alarm Wrn Maintenance 5
(page 608) appears in alarmlist.
IMPORTANT: To disable this maintenance timer, set date to 01/01/2015.
Maintenance Timer 6
Setpoint group Engine settings Related FW 1.0.0
Range [units] [DD/MM/YYYY]
Default value 01/01/2015 Alternative config NO
Step 1 day
Comm object 16386 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
This maintenance timer is based on date. At the midnight of the last day the alarm Wrn Maintenance 6
(page 609) appears in alarmlist.
IMPORTANT: To disable this maintenance timer, set date to 01/01/2015.
Subgroup: Ventilation
Overload BOC
Setpoint group Generator settings Related FW 1.0.0
Range [units] Overload Wrn (page 264) .. 200 [%]
Default value 120 % Alternative config NO
Step 1 % of Nominal Power (page 209)
Comm object 8280 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold level for generator overload (in % of Nominal power) protection. Protection is BOC (Breaker Open
and Gen-set Cooldown).
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Overload Wrn
Setpoint group Generator settings Related FW 1.0.0
Range [units] 0 .. Overload BOC (page 263) [%]
Default value 120 % Alternative config NO
Step 1 % of Nominal Power (page 209)
Comm object 9685 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold level for generator overload (in % of Nominal power) protection. This is only warning.
6 back to List of setpoints
Overload Delay
Setpoint group Generator settings Related FW 1.0.0
Range [units] 0,0 .. 600,0 [s]
Default value 5,0 s Alternative config NO
Step 0,1 s
Comm object 8281 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Delay for Overload BOC (page 263)Overload BOC (page 263) and Overload Wrn (page 264) protection.
6 back to List of setpoints
Note: Reaction time is limited to 3600 s = 60 minutes. IDMT protection is not active for Reaction time
values longer than 60 minutes.
Generator Overvoltage Sd
Setpoint group Generator settings Related FW 1.0.0
Range [units] Generator Overvoltage Wrn (page 268) .. 200 [%]
Default value 110 % Alternative config NO
Step 1 % of Nominal Voltage Ph-N (page 214) or Nominal Voltage Ph-Ph (page 214)
Comm object 8291 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for generator overvoltage protection. All three phases are checked. Maximum out of three is used.
Note: Phase to phase and phase to neutral voltages are used for this protection.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Group: Protections
Overload Protection
Setpoint group Protections Related FW 1.0.0
Range [units] Enabled/Disabled/By LBIExtDisable [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15664 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Overload protection.
Underspeed Protection
Setpoint group Protections Related FW 1.0.0
Range [units] Enabled / Disabled / By LBIExtDisable [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15671 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Underspeed protection.
Transfer Delay
Setpoint group Process Control Related FW 1.0.0
Range [units] 0.0 .. 600.0 [s]
Default value 1.0 s Alternative config NO
Step 0.1 s
Comm object 8303 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Default Application Select (page 220)
Description
Delay used in dual operation function. This delay is used when load from first Gen-set is transferred to
second Gen-set. Delay starts to countdown when GCB of first Gen-set is open. When this delay countdown,
GCB of second Gen-set is closed. This delay is important for correct function of external interlock.
Delay after GCB opening to MCB closing during the return procedure. Delay after MCB opening to GCB
closing if the setpoint MCB Opens On (page 290) is set to GENRUN.
The time charts bellow show recommended setting of Transfer Delay setpoint.
If the Transfer Delay setpoint is set shorter than the time required for opening of the circuit breaker, the
controller closes GCB CLOSE/OPEN (PAGE 511) output straight away (100 ms) after the MCB FEEDBACK
(PAGE 484) input deactivates.
If some delay between MCB FEEDBACK (PAGE 484) deactivation and closing of GCB CLOSE/OPEN (PAGE
511) output is required, then the Transfer Delay must be set to sum of “MCB opening” + “Delay” time.
This delay is also used in dual operation function. This delay is used when load from first Gen-set is
transferred to second Gen-set. Delay starts to countdown when GCB of first Gen-set is open. When this
delay countdown, GCB of second Gen-set is closed. This delay is important for correct function of external
interlock.
IMPORTANT: This is a fixed parameter, it isn't possible to adjust it in any manner. This
parameter isn't visible either in controller or in PC tools.
Mains Overvoltage
Setpoint group Mains Settings Related FW 1.0.0
Range [units] Mains Undervoltage (page 283) .. 150 [%]
Default value 110 % Alternative config NO
Step 1 % of Nominal Voltage Ph-Ph (page 214)
Comm object 8305 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Default Application Select (page 220)
Description
Threshold for Mains overvoltage. All three phases are checked. Maximum out of three is used.
6 back to List of setpoints
Mains Undervoltage
Setpoint group Mains Settings Related FW 1.0.0
Range [units] 50 .. Mains Overvoltage (page 282) [%]
Default value 60 % Alternative config YES
Step 1 % of Nominal Voltage Ph-Ph (page 214)
Comm object 8307 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Default Application Select (page 220)
Description
Threshold for Mains undervoltage. All three phases are checked. Minimum voltage out of three phases is
used.
6 back to List of setpoints
Mains Overfrequency
Setpoint group Mains Settings Related FW 1.0.0
Range [units] Mains Underfrequency (page 287) .. 150 [%]
Default value 102.0 % Alternative config NO
Step 1.0 % of Nominal Frequency (page 217)
Comm object 8310 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Default Application Select (page 220)
Description
Threshold for Mains overfrequency.
Mains Underfrequency
Setpoint group Mains Settings Related FW 1.0.0
Range [units] 50 .. Mains Overfrequency (page 286) [%]
Default value 98.0 % Alternative config NO
Step 1.0 % of Nominal Frequency (page 217)
Comm object 8312 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Default Application Select (page 220)
Description
Threshold for Mains underfrequency.
6 back to List of setpoints
Controller remains in AUT mode and the manual return to Mains is done via MCB
button. Manual Restore (page 599) message is displayed in alarmlist to notify
Manual operator – it will disappear automatically after MCB close button is pushed.
Note: Select MANUAL in case you need to manually control the moment
when the load is transferred back to the mains.
Auto No automatic mode change is performed.
IMPORTANT: This is a fixed parameter, it isn't possible to adjust it in any manner. This
parameter isn't visible either in controller or in PC tools.
MCB Logic
Setpoint group Mains Settings Related FW 1.0.0
Range [units] Close On / Close Off [-]
Default value Close Off Alternative config NO
Step [-]
MCB Opens On
Setpoint group Mains Settings Related FW 1.0.0
Range [units] Mains Fail / Gen Run [-]
Default value Gen Run Alternative config NO
Step [-]
Comm object 9850 Related applications AMF
Config level Advanced
Setpoint visibility Conditioned by the setpoint Default Application Select (page 220)
Description
Setpoint adjust the behavior of opening MCB in AUTO mode when there is mains fail.
Mains The command to open the MCB is given immediately after mains fail condition is
Fail evaluated.
If the mains will return into parameters after MCB was opened and before GCB is closed,
timer MCB Close Delay (page 280) is applied before MCB closing.
Gen Run MCB will be opened when engine will be running and it will be possible to transfer load
from Mains to gen-set (after stabilization phase).
Note: This option should be used for MCBs using 230V control and not equipped with the undervoltage
coil.
Swap Gen-sets
Setpoint group Dual operation Related FW 1.0.0
Range [units] Enabled / Disabled [-]
Default value Enabled h Alternative config NO
Step [-]
Comm object 16041 Related applications AMF, MRS
Config level Advanced
Only if relevant module is installed + conditioned by the setpoint COM1 Mode (page
Setpoint visibility
377) and COM2 Mode (page 378)
Description
This setpoint enables or disables swapping of gen-sets on load in dual operation.
Enabled Master and Slave are swapped based on their actual running hours.
Master and Slave are not swapped. Controller with lower running hours starts and then
Disabled
runs until mains returns or until controller shutdown - then second controller starts.
Transfer Delay
Setpoint group Dual operation Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Advanced
Only if relevant module is installed + conditioned by the setpoint COM1 Mode (page
Setpoint visibility
377) and COM2 Mode (page 378)
Description
.
Disabled The Load shedding function is disabled. All the outputs are open.
Gen only The function is active when Breaker State (page 428) = IsOper.
Load shedding outputs are activated / deactivated one by one in island
operation
All Loadshedding outputs are tripped once the Gen-set comes into the island
operation from "NO LOAD" operation (MCB and (M)GCB were opened ->
Gen-set started and (M)GCB closed).
All the time Load shedding Outputs are controlled by the load shedding function regardless of
breaker positions.
Loadshedding is active in island operation, in parallel operation too.
All Loadshedding outputs are never tripped at once.
Rising edge on binary input MANUAL LD RECON resets controller to the lower stage,
Disabled but only if the load is under the Load Reconnection Level (page 294). Load
Reconnection Delay (page 294) is not taken into account in this case.
Load reconnection is automatic depend on setpoints Load Reconnection Level (page
Enabled 294) and Load Reconnection Delay (page 294). Binary input MANUAL LOAD
RECONNECTION (PAGE 483) has no function.
Oil Pressure Sd
Setpoint group User Setpoints Related FW 1.0.0
Range [units] [bar]
Default value Alternative config NO
Step
Comm object 65533 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 1
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 2
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 3
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 4
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 5
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 6
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 7
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 8
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 9
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 10
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 11
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 12
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 13
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 14
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 15
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 16
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 17
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 18
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 19
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 20
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 21
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 22
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 23
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 24
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 25
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 26
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 27
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 28
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 29
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 30
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 31
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
User Button 32
Setpoint group User Buttons Related FW 1.0.0
Range [units]
Default value Alternative config NO
Step
Comm object Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
.
AIN Switch01 On
Setpoint group Analog Switches Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
the value is defined by
Default value Alternative config NO
an analog sensor curve
Step the step is defined by an analog sensor curve
Comm object 11407 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical binary output AIN SWITCH01 (PAGE 494) is configured
Description
Threshold level for switching the binary output AIN SWITCH01 (PAGE 494) on. The value is measured from
AIN SWITCH 01 (PAGE 543) analog input.
AIN Switch02 On
Setpoint group Analog Switches Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
the value is defined by
Default value Alternative config NO
an analog sensor curve
Step the step is defined by an analog sensor curve
Comm object 11408 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical binary output AIN SWITCH02 (PAGE 494) is configured
Description
Threshold level for switching the binary output AIN SWITCH02 (PAGE 494) on. The value is measured from
AIN SWITCH 02 (PAGE 543) analog input.
AIN Switch03 On
Setpoint group Analog Switches Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
the value is defined by
Default value Alternative config NO
an analog sensor curve
Step the step is defined by an analog sensor curve
Comm object 11409 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical binary output AIN SWITCH03 (PAGE 495) is configured
Description
Threshold level for switching the binary output AIN SWITCH03 (PAGE 495) on. The value is measured from
AIN SWITCH 03 (PAGE 543) analog input.
AIN Switch04 On
Setpoint group Analog Switches Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
the value is defined by
Default value Alternative config NO
an analog sensor curve
Step the step is defined by an analog sensor curve
Comm object 14385 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical binary output AIN SWITCH04 (PAGE 495) is configured
Description
Threshold level for switching the binary output AIN SWITCH04 (PAGE 495) on. The value is measured from
AIN SWITCH 04 (PAGE 544) analog input.
AIN Switch05 On
Setpoint group Analog Switches Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
the value is defined by
Default value Alternative config NO
an analog sensor curve
Step the step is defined by an analog sensor curve
Comm object 14963 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical binary output AIN SWITCH05 (PAGE 496) is configured
Description
Threshold level for switching the binary output AIN SWITCH05 (PAGE 496) on. The value is measured from
AIN SWITCH 05 (PAGE 544) analog input.
AIN Switch06 On
Setpoint group Analog Switches Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
the value is defined by
Default value Alternative config NO
an analog sensor curve
Step the step is defined by an analog sensor curve
Comm object 14964 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical binary output AIN SWITCH06 (PAGE 496) is configured
Description
Threshold level for switching the binary output AIN SWITCH06 (PAGE 496) on. The value is measured from
AIN SWITCH 06 (PAGE 544) analog input.
AIN Switch07 On
Setpoint group Analog Switches Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
the value is defined by
Default value Alternative config NO
an analog sensor curve
Step the step is defined by an analog sensor curve
Comm object 14965 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical binary output AIN SWITCH07 (PAGE 497) is configured
Description
Threshold level for switching the binary output AIN SWITCH07 (PAGE 497) on. The value is measured from
AIN SWITCH 07 (PAGE 545) analog input.
AIN Switch08 On
Setpoint group Analog Switches Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
the value is defined by
Default value Alternative config NO
an analog sensor curve
Step the step is defined by an analog sensor curve
Comm object 14966 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical binary output AIN SWITCH08 (PAGE 497) is configured
Description
Threshold level for switching the binary output AIN SWITCH08 (PAGE 497) on. The value is measured from
AIN SWITCH 08 (PAGE 545) analog input.
AIN Switch09 On
Setpoint group Analog Switches Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
the value is defined by
Default value Alternative config NO
an analog sensor curve
Step the step is defined by an analog sensor curve
Comm object 14967 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical binary output AIN SWITCH09 (PAGE 498) is configured
Description
Threshold level for switching the binary output AIN SWITCH09 (PAGE 498) on. The value is measured from
AIN SWITCH 09 (PAGE 545) analog input.
AIN Switch10 On
Setpoint group Analog Switches Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
the value is defined by
Default value Alternative config NO
an analog sensor curve
Step the step is defined by an analog sensor curve
Comm object 14968 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical binary output AIN SWITCH10 (PAGE 498) is configured
Description
Threshold level for switching the binary output AIN SWITCH10 (PAGE 498) on. The value is measured from
AIN SWITCH 10 (PAGE 546) analog input.
Group: Scheduler
Time
Setpoint group Scheduler Related FW 1.0.0
Range [units] HH:MM:SS [-]
Default value 0:0:0 Alternative config NO
Step [-]
Comm object 24554 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Real time clock adjustment.
Note: RTC has no backup battery. This setpoint needs to be set-up after connection of +/- terminal.
Date
Setpoint group Scheduler Related FW 1.0.0
Range [units] DD/MM/YYYY [-]
Default value 1.1.2015 Alternative config NO
Step [-]
Comm object 24553 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Actual date adjustment.
Note: RTC has no backup battery. This setpoint needs to be set-up after connection of +/- terminal.
Subgroup: Timer 1
Timer 1 Function
Setpoint group Scheduler Related FW 1.0.0
Range [units] Disable / No Func / TEST / Test OnLd / MFail Blk / /Auto Run / Mode OFF [-]
Default value Disable Alternative config NO
Step [-]
Comm object 15358 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
It is possible to choose from following timer functions. Binary output EXERCISE TIMER 1 (PAGE 508) is
always activated when Timer is active regardless of chosen timer function. Timer functions require controller
running in AUTO mode.
Timer 1 has higher priority over Timer 2. So if Timer 1 Function (page 332) is configured for OFF mode and
Timer 2 Function (page 340) is over the same time configured for AUTO mode, controller will work in OFF
mode.
Controller activates timer whenever it is powered up even in period, where timer should be already running.
Timer 1 Setup
Setpoint group Scheduler Related FW 1.0.0
Range [units] [-]
Default value [-] Alternative config NO
Step [-]
Comm object 10969 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Related setpoints for timer 1 are:
Timer 1 Function (page 332) Timer 1 Day (page 336)
Timer 1 Repetition (page 334) Timer 1 Repeated Day In Week (page 336)
Timer 1 First Occur. Date (page 333) Timer 1 Repeat Day In Month (page 336)
Timer 1 First Occur. Time (page 334) Timer 1 Repeat Week In Month (page 337)
Timer 1 Duration (page 334) Timer 1 Refresh Period (page 338)
Timer 1 Repeated (page 335) Timer 1 Weekends (page 339)
Timer 1 Repeat Day (page 335)
Timer 1 Duration
Setpoint group Scheduler Related FW 1.0.0
Range [units] [HH:MM]
Default value 00:00 Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 1 Function (page 332)
Description
Timer 1 Function (page 332) duration time.
6 back to List of setpoints
Timer 1 Repetition
Setpoint group Scheduler Related FW 1.0.0
Range [units] Off / Once / Repeated [-]
Default value Off Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 1 Function (page 332)
Description
Defines repetition of Timer 1 Function (page 332).
Timer 1 Repeated
Setpoint group Scheduler Related FW 1.0.0
Range [units] Daily / Weekly / Monthly / Short Period [-]
Default value Daily Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 1 Function (page 332)
Description
Repeated interval of Timer 1 Function (page 332).
Chose one day in month when Timer 1 Function (page 332) will be
Repeated Day
activated.
Chose days in one week when Timer 1 Function (page 332) will be
Repeated Day In Week
activated.
Timer 1 Day
Setpoint group Scheduler Related FW 1.0.0
Range [units] Monday / Tuesday / Wednesday / Thursday / Friday / Saturday/ Sunday[-]
Default value All OFF Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 1 Function (page 332)
Description
Use this setpoint to include or exclude individual days of week. To select the day use Up and Down buttons.
To change the value of day use Enter button.
6 back to List of setpoints
Range [units]: 1 .. 1000 [day]. This setpoint adjust that every X day the timer will
be activated.
Daily Example: If you have daily repetition and you set this setpoint to 2, then
every second day from first occurrence of Timer 1 Function (page 332), the
Timer 1 Function (page 332) will be activated.
Range [units]: 1 .. 60 [week]. This setpoint adjust that every X week the timer
will be activated.
Example: If you have weekly repetition and you set this setpoint to 2, then
Weekly
every second week from first occurrence of Timer 1 Function (page 332),
the Timer 1 Function (page 332) will be activated in selected days adjusted
by Timer 1 Day (page 336).
Range [units]: 1 .. 12 [month]. This setpoint adjust that every X month the timer
will be activated.
Example: If you have monthly repetition and you set this setpoint to 2, then
every second month from first occurrence of Timer 1 Function (page 332),
Monthly
the Timer 1 Function (page 332) will be activated in selected day of month
adjusted by Timer 1 Repeat Day In Month (page 336) or in selected days
of week of month adjusted by Timer 1 Day (page 336) and Timer 1 Repeat
Week In Month (page 337).
Range [units]: [HH:MM]. This setpoint adjust that every X short period the timer
will be activated.
Short Period Example: If you have short period repetition and you set this setpoint to 2,
then every second minute from first occurrence of Timer 1 Function (page
332), the Timer 1 Function (page 332) will be activated.
Timer 1 Weekends
Setpoint group Scheduler Related FW 1.0.0
Range [units] Including / Skip / Postpone [-]
Default value Including Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 1 Function (page 332)
Description
Behavior of Timer 1 Function (page 332) on weekends.
Timer 1 Function (page 332) counter is running on the weekends and Timer 1
Including
Function (page 332) can be active.
Timer 1 Function (page 332) counter is running on the weekends but Timer 1
Skip
Function (page 332) isn’t active.
Timer 1 Function (page 332) counter isn’t running on the weekends and Timer 1
Function (page 332) isn’t active. If the activation of timer is counted on the
Postpone
weekend, than timer will be activated after weekend. Another activation of timer is
counted from original date of first occurrence date.
Subgroup: Timer 2
Timer 2 Function
Setpoint group Scheduler Related FW 1.0.0
Range [units] Disable / No Func / TEST / Test OnLd / MFail Blk / /Auto Run / Mode OFF [-]
Default value No Func Alternative config NO
Step [-]
Comm object 15359 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
It is possible to choose from following Timer functions. Binary output EXERCISE TIMER 2 (PAGE 508) is
always activated when Timer is active regardless of chosen timer function. Timer functions require controller
running in AUTO mode.
Timer 1 has higher priority over Timer 2. So if Timer 1 Function (page 332) is configured for OFF mode and
Timer 2 Function (page 340) is over the same time configured for AUTO mode, controller will work in OFF
mode.
Controller activates timer whenever it is powered up even in period, where timer should be already running.
Timer 2 Setup
Setpoint group Scheduler Related FW 1.0.0
Range [units] [-]
Default value [-] Alternative config NO
Step [-]
Comm object 10970 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Related setpoints for timer 2 are:
Timer 2 Function (page 340)
Timer 2 Repetition (page 342)
Timer 2 Duration
Setpoint group Scheduler Related FW 1.0.0
Range [units] [HH:MM]
Default value 00:00 Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 2 Function (page 340)
Description
Timer 2 Function (page 340) duration time.
6 back to List of setpoints
Timer 2 Repetition
Setpoint group Scheduler Related FW 1.0.0
Range [units] Off / Once / Repeated [-]
Default value Off Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 2 Function (page 340)
Description
Defines repetition of Timer 2 Function (page 340).
Timer 2 Repeated
Setpoint group Scheduler Related FW 1.0.0
Range [units] Daily / Weekly / Monthly / Short Period [-]
Default value Daily Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 2 Function (page 340)
Description
Repeated interval of Timer 2 Function (page 340).
Chose one day in month when Timer 2 Function (page 340) will be
Repeated Day
activated.
Chose days in one week when Timer 2 Function (page 340) will be
Repeated Day In Week
activated.
Timer 2 Day
Setpoint group Scheduler Related FW 1.0.0
Range [units] Monday / Tuesday / Wednesday / Thursday / Friday / Saturday/ Sunday[-]
Default value All OFF Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 2 Function (page 340)
Description
Use this setpoint to include or exclude individual days of week. To select the day use Up and Down buttons.
To change the value of day use Enter button.
6 back to List of setpoints
Range [units]: 1 .. 1000 [day]. This setpoint adjust that every X day the timer will
be activated.
Daily Example: If you have daily repetition and you set this setpoint to 2, then
every second day from first occurrence of Timer 2 Function (page 340), the
Timer 2 Function (page 340) will be activated.
Range [units]: 1 .. 60 [week]. This setpoint adjust that every X week the timer
will be activated.
Example: If you have weekly repetition and you set this setpoint to 2, then
Weekly
every second week from first occurrence of Timer 2 Function (page 340),
the Timer 2 Function (page 340) will be activated in selected days adjusted
by Timer 2 Day (page 344).
Range [units]: 1 .. 12 [month]. This setpoint adjust that every X month the timer
will be activated.
Example: If you have monthly repetition and you set this setpoint to 2, then
every second month from first occurrence of Timer 2 Function (page 340),
Monthly
the Timer 2 Function (page 340) will be activated in selected day of month
adjusted by Timer 2 Repeat Day In Month (page 344) or in selected days
of week of month adjusted by Timer 2 Day (page 344) and Timer 2 Repeat
Week In Month (page 345).
Range [units]: [HH:MM]. This setpoint adjust that every X short period the timer
will be activated.
Short Period Example: If you have short period repetition and you set this setpoint to 2,
then every second minute from first occurrence of Timer 2 Function (page
340), the Timer 2 Function (page 340) will be activated.
Timer 2 Weekends
Setpoint group Scheduler Related FW 1.0.0
Range [units] Including / Skip / Postpone [-]
Default value Including Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 2 Function (page 340)
Description
Behavior of Timer 2 Function (page 340) on weekends.
Timer 2 Function (page 340) counter is running on the weekends and Timer 2
Including
Function (page 340) can be active.
Timer 2 Function (page 340) counter is running on the weekends but Timer 2
Skip
Function (page 340) isn’t active.
Timer 2 Function (page 340) counter isn’t running on the weekends and Timer 2
Function (page 340) isn’t active. If the activation of timer is counted on the
Postpone
weekend, than timer will be activated after weekend. Another activation of timer is
counted from original date of first occurrence date.
Subgroup: Timer 3
Timer 3 Function
Setpoint group Scheduler Related FW 1.0.0
Range [units] Disable / No Func / TEST / Test OnLd / MFail Blk / /Auto Run / Mode OFF [-]
Default value No Func Alternative config NO
Step [-]
Comm object 15359 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
It is possible to choose from following Timer functions. Binary output EXERCISE TIMER 3 (PAGE 508) is
always activated when Timer is active regardless of chosen timer function. Timer functions require controller
running in AUTO mode.
Timer 1 has higher priority over Timer 2. So if Timer 1 Function (page 332) is configured for OFF mode and
Timer 3 Function (page 348) is over the same time configured for AUTO mode, controller will work in OFF
mode.
Controller activates timer whenever it is powered up even in period, where timer should be already running.
Timer 3 Setup
Setpoint group Scheduler Related FW 1.0.0
Range [units] [-]
Default value [-] Alternative config NO
Step [-]
Comm object 10970 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Related setpoints for timer 3 are:
Timer 2 Function (page 1)
Timer 2 Repetition (page 1)
Subgroup: Timer 4
Timer 4 Function
Setpoint group Scheduler Related FW 1.0.0
Range [units] Disable / No Func / TEST / Test OnLd / MFail Blk / /Auto Run / Mode OFF [-]
Default value No Func Alternative config NO
Step [-]
Comm object 15359 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
It is possible to choose from following Timer functions. Binary output EXERCISE TIMER 2 (PAGE 508) is
always activated when Timer is active regardless of chosen timer function. Timer functions require controller
running in AUTO mode.
Timer 1 has higher priority over Timer 2. So if Timer 1 Function (page 332) is configured for OFF mode and
Timer 4 Function (page 350) is over the same time configured for AUTO mode, controller will work in OFF
mode.
Controller activates timer whenever it is powered up even in period, where timer should be already running.
Timer 4 Setup
Setpoint group Scheduler Related FW 1.0.0
Range [units] [-]
Default value [-] Alternative config NO
Step [-]
Comm object 10970 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Related setpoints for timer 4 are:
Timer 2 Function (page 1)
Timer 2 Repetition (page 1)
Rental Timer 1
Setpoint group Scheduler Related FW 1.0.0
Range [units] Disabled / 1 .. 8 760 [h]
Default value Disabled Alternative config NO
Step 1h
Comm object 14326 Related applications AMF, MRS
Config level Advanced
When the Rental Timer 1 (page 351) elapsed during engine run the Gen-set will not stop immediately. The
adjustable Rental Timer BOC (page 355) timer will start in this moment. The engine will be cooled and
stopped when the Rental Timer BOC (page 355) time elapsed.
The Running Hours Overrun counter will start increment when the engine is continue running after the Rental
Timer 1 (page 351) elapsed.
Note: There is no priority between Rental Timer 1 and Rental Timer 2. The sooner timer will activated the
Rental Timer BOC (page 355) protection.
Rental Timer 2
Setpoint group Scheduler Related FW 1.0.0
Range [units] [DD/MM/YYYY]
Default value 01/01/2015 Alternative config NO
Step 1 day
Comm object 14367 Related applications AMF, MRS
Config level Advanced
When the Rental Timer 2 (page 353) elapsed during engine run the Gen-set will not stop immediately. The
adjustable Rental Timer BOC (page 355) timer will start in this moment. The engine will be cooled and
stopped when the Rental Timer BOC (page 355) time elapsed.
The Running Hours Overrun counter will start increment when the engine is continue running after the Rental
Timer 2 (page 353) elapsed.
Note: There is no priority between Rental Timer 1 and Rental Timer 2. The sooner timer will activated the
Rental Timer BOC (page 355) protection.
Group: Geo-Fencing
Geo-Fencing
Setpoint group Geo-Fencing Related FW 1.0.0
Range [units] Disabled / Enabled / LBI Enable [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 11681 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables geo-fencing function.
Fence 1 Protection (page 358) and Fence 2 Protection (page 359) are
Disabled
disabled.
Fence 1 Protection (page 358) and Fence 2 Protection (page 359) are
Enabled
enabled.
Fence 1 Protection (page 358) and Fence 2 Protection (page 359) are enabled
LBI Enable
only when logical binary input .GEO-FENCING ENABLE (PAGE 482) is active.
Subgroup: Position
Home Latitude
Setpoint group Geo-Fencing Related FW 1.0.0
Range [units] -90,0000..90,0000 [°]
Default value 0,0000 ° Alternative config NO
Step 0,0001 °
Comm object 14606 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint adjust latitude of "home" position. Home is position where gen-set should runs. Positions on
north hemisphere have positive value, position on south hemisphere have negative value.
Note: This value with Home Longitude (page 357) are used for counting Fence Radius 1 (page 358)
and Fence Radius 2 (page 360).
Note: This value can be also obtained automatically via logical binary input GEO HOME POSITION (PAGE
481). In case of activation of this binary input for at least 2 seconds, setpoint will be adjusted
automatically from actual coordinates from GPS signal.
Home Longitude
Setpoint group Geo-Fencing Related FW 1.0.0
Range [units] -180,0000..180,0000 [°]
Default value 0,0000 ° Alternative config NO
Step 0,0001 °
Comm object 14607 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint adjust longitude of "home" position. Home is position where gen-set should runs. Positions on
east hemisphere have positive value, position on west hemisphere have negative value.
Note: This value with Home Latitude (page 356) are used for counting Fence Radius 1 (page 358)
and Fence Radius 2 (page 360).
Note: This value can be also obtained automatically via logical binary input GEO HOME POSITION (PAGE
481). In case of activation of this binary input for at least 2 seconds, setpoint will be adjusted
automatically from actual coordinates from GPS signal.
Subgroup: Fence 1
Fence 1 Protection
Setpoint group Geo-Fencing Related FW 1.0.0
Range [units] HistRecOnl / Wrn / Sd / BOC[-]
Default value HistRecOnl Alternative config NO
Step [-]
Comm object 14610 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Protection type for geo-fencing 1 protection. Fence of circle area is adjusted by setpoint Fence Radius 1
(page 358). Delay for protection is adjusted by setpoint Fence 1 Delay (page 359).
Protection types
HistRecOnl Position of gen-set is only measured and displayed on the LCD screen but not used
for protection. History record is made if position is out of Fence Radius 1 (page 358).
Wrn Position of gen-set is used for warning protection only. Protection is activated when
position of the gen-set is out of Fence Radius 1 (page 358).
Sd Position of gen-set is used for shutdown protection. Protection is activated when
position of the gen-set is out of Fence Radius 1 (page 358).
BOC Position of gen-set is used for BOC (Breaker Open and Cooling) protection. Protection
is activated when position of the gen-set is out of Fence Radius 1 (page 358).
Note: Protection is activated also when GPS signal is lost for Fence 1 Delay (page 359).
Fence Radius 1
Setpoint group Geo-Fencing Related FW 1.0.0
Range [units] 0,0..99,9 [km]
Default value 0,0 km Alternative config NO
Step 0,1 km
Comm object 11677 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Radius for circle area 1. When the Gen-set leaves this area, Fence 1 Protection (page 358) is activated
after Fence 1 Delay (page 359).
Note: The center of this circle area is defined by "Home" position – setpoints Home Longitude (page
357) and Home Latitude (page 356).
Fence 1 Delay
Setpoint group Geo-Fencing Related FW 1.0.0
Range [units] 0..3600 [s]
Default value 0s Alternative config NO
Step 1s
Comm object 11682 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Delay for Fence 1 Protection (page 358).
Subgroup: Fence 2
Fence 2 Protection
Setpoint group Geo-Fencing Related FW 1.0.0
Range [units] HistRecOnl / Wrn / Sd / BOC[-]
Default value HistRecOnl Alternative config NO
Step [-]
Comm object 14611 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Protection type for geo-fencing 2 protection. Fence of circle area is adjusted by setpoint Fence Radius 2
(page 360). Delay for protection is adjusted by setpoint Fence 2 Delay (page 360).
Protection types
HistRecOnl Position of gen-set is only measured and displayed on the LCD screen but not used
for protection. History record is made if position is out of Fence Radius 2 (page 360).
Wrn Position of gen-set is used for warning protection only. Protection is activated when
position of the gen-set is out of Fence Radius 2 (page 360).
Sd Position of gen-set is used for shutdown protection. Protection is activated when
position of the gen-set is out of Fence Radius 2 (page 360).
BOC Position of gen-set is used for BOC (Breaker Open and Cooling) protection. Protection
is activated when position of the gen-set is out of Fence Radius 2 (page 360).
Note: Protection is activated also when GPS signal is lost for Fence 2 Delay (page 360).
Fence Radius 2
Setpoint group Geo-Fencing Related FW 1.0.0
Range [units] 0,0..99,9 [km]
Default value 0,0 km Alternative config NO
Step 0,1 km
Comm object 14608 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Radius for circle area 2. When the gen-set leaves this area, Fence 2 Protection (page 359) is activated
after Fence 2 Delay (page 360).
Note: The center of this circle area is defined by "Home" position - setpoints Home Longitude (page
357) and Home Latitude (page 356).
Fence 2 Delay
Setpoint group Geo-Fencing Related FW 1.0.0
Range [units] 0..3600 [s]
Default value 0s Alternative config NO
Step 1s
Comm object 14609 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Delay for Fence 2 Protection (page 359).
Subgroup: Slot A
Slot A
Setpoint group Plug-In Modules Related FW 1.0.0
Range [units] ENABLED / DISABLED [-]
Default value ENABLED Alternative config NO
Step [-]
Comm object 24280 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
This setpoint enable or disable module in slot A.
Subgroup: Slot B
Slot B
Setpoint group Plug-In Modules Related FW 1.0.0
Range [units] ENABLED / DISABLED [-]
Default value ENABLED Alternative config NO
Step [-]
Comm object 24279 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
This setpoint enable or disable module in slot B.
6 back to List of setpoints
Group: CM-4G-GPS
Internet Connection
CM-GPRS; CM-4G-
Setpoint group Related FW 1.0.0
GPS
Range [units] Enabled / Disabled [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 24315 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint adjust the communication mode of module.
IMPORTANT: When this setpoint is changed the controller has to be restarted to apply
changes.
Network Mode
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] 2G/3G/4G/Automatic [-]
Default value Automatic Alternative config NO
Step [-]
Comm object 24132 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint adjusts preferred connection type of CM-4G-GPS module.
SMTP Encryption
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] None / SSL-TLS / Starttls [-]
Default value None Alternative config NO
Step [-]
Comm object Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet
Setpoint visibility
ConnectionMode (page 1)
Description
.
Message Language
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] Depends on CU languages [-]
Default value English Alternative config NO
Step [-]
Comm object 24299 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Use this setpoint to set the language of SMS and e-mail.
Note: Numbers correspond with languages in language list. See the chapter Language selection (page
84) for more information.
Event Message
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] ON / OFF [-]
Default value ON Alternative config NO
Step [-]
Comm object 10926 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables Event Messages.
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Wrn Message
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] ON / OFF [-]
Default value ON Alternative config NO
Step [-]
Comm object 8482 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables Wrn Messages.
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
BOC Message
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] ON / OFF [-]
Default value ON Alternative config NO
Step [-]
Comm object 10566 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables BOC Messages.
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Sd Messages
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] ON / OFF [-]
Default value ON Alternative config NO
Step [-]
Comm object 8484 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables Sd Messages.
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Email Address 1
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] 0..63 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24298 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361) (CM-GPRS and CM-4G-GPS modules)
Description
Enter in this setpoint a valid e-mail address where the alarm and event e-mails shall be sent. Leave this
setpoint blank if alarm and event email should not be send.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Email Address 2
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] 0..63 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24297 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361) (CM-GPRS and CM-4G-GPS modules)
Description
Enter in this setpoint a valid e-mail address where the alarm and event e-mails shall be sent. Leave this
setpoint blank if alarm and event email should not be send.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Email Address 3
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] 0..63 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24145 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361) (CM-GPRS and CM-4G-GPS modules)
Description
Enter in this setpoint a valid e-mail address where the alarm and event e-mails shall be sent. Leave this
setpoint blank if alarm and event email should not be send.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Email Address 4
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] 0..63 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24144 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361) (CM-GPRS and CM-4G-GPS modules)
Description
Enter in this setpoint a valid e-mail address where the alarm and event e-mails shall be sent. Leave this
setpoint blank if alarm and event email should not be send.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Telephone Number 1
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] 0..31 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24296 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Enter in this setpoint either a valid GSM phone number where the alarm messages shall be sent. For GSM
numbers use either the national format (i.e. the number you would dial if you wanted to make a local call) or
the full international format beginning with a “+” character followed by the country prefix.
IMPORTANT: Telephone number has to be entered without spaces.
Telephone Number 2
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] 0..31 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24295 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Enter in this setpoint either a valid GSM phone number where the alarm messages shall be sent. For GSM
numbers use either the national format (i.e. the number you would dial if you wanted to make a local call) or
the full international format beginning with a “+” character followed by the country prefix.
IMPORTANT: Telephone number has to be entered without spaces.
Telephone Number 3
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] 0..31 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24143 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Enter in this setpoint either a valid GSM phone number where the alarm messages shall be sent. For GSM
numbers use either the national format (i.e. the number you would dial if you wanted to make a local call) or
the full international format beginning with a “+” character followed by the country prefix.
IMPORTANT: Telephone number has to be entered without spaces.
Telephone Number 4
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] 0..31 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24142 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Enter in this setpoint either a valid GSM phone number where the alarm messages shall be sent. For GSM
numbers use either the national format (i.e. the number you would dial if you wanted to make a local call) or
the full international format beginning with a “+” character followed by the country prefix.
IMPORTANT: Telephone number has to be entered without spaces.
GPS Tracking
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] Enabled / Disabled [-]
Default value Enabled Alternative config NO
Step [-]
Comm object Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet
Setpoint visibility
ConnectionMode (page 1)
Description
.
Time Zone
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] GMT-12:00 .. GMT+13:00 [hours]
Default value GMT+1:00 hour Alternative config NO
Step [-]
Comm object 24366 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint is used to select the time zone where the controller is located. See your computer time zone
setting (click on the time indicator located in the rightmost position of the Windows task bar) if you are not
sure about your time zone.
Note: If the time zone is not selected properly the active e-mails may contain incorrect information about
sending time, which may result in confusion when the respective problem actually occurred.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Subgroup: ComAp/TCP
AirGate Connection
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] Disabled/ Enabled [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 24273 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361)
Description
This setpoint enable or disable AirGate connection via CM-GPRS or via CM-4G-GPS.
DISABLED: Only SMS are sent. Internet-enabled SIM card is not required. AirGate is not used.
ENABLED This mode uses the “AirGate” service. Internet-enabled SIM card must be used. The
AirGate server address is adjusted by the setpoint AirGate Address (page 373).
IMPORTANT: When this setpoint is changed the controller has to be restarted to apply
changes.
AirGate Address
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] [-]
Default value airgate.comap.cz Alternative config NO
Step [-]
Comm object 24364 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361) (CM-GPRS module)
Description
This setpoint is used for entering the domain name or IP address of the AirGate server. Use the free AirGate
server provided by ComAp at airgate.comap.cz.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Airgate Port
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] 1 .. 65535 [-]
Default value 54440 Alternative config NO
Step 1
Comm object Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet
Setpoint visibility
ConnectionMode (page 1)
Description
.
Direct Connection
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] Disabled / Enabled [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 24099 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Use this to enable/disable direct connection of a ComAp client (e.g. InteliConfig) to the IP address of the
controller.
Note: For Direct connection the controller IP address must be reachable from the client IP address.
Subgroup: IP Protocol
IP Firewall
Setpoint group CM-4G-GPS Related FW 1.0.0
Range [units] Enabled / Disabled [-]
Default value Disable Alternative config NO
Step [-]
Comm object Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet
Setpoint visibility
ConnectionMode (page 1)
Description
.
Group: CM-RS232-485
COM1 Mode
Setpoint group CM-RS232-485 Related FW 1.0.0
Range [units] Direct / MODBUS / DualSlave / Dual Master [-]
Default value Direct Alternative config NO
Step [-]
Comm object 24522 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Communication protocol switch for the COM1 channel.
COM2 Mode
Setpoint group CM-RS232-485 Related FW 1.0.0
Range [units] Direct / MODBUS / DualSlave / Dual Master [-]
Default value Direct Alternative config NO
Step [-]
Comm object 24451 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Communication protocol switch for the COM2 channel.
Only if relevant module is installed + conditioned by the setpoint COM2 Mode (page
Setpoint visibility
378)
Description
If the direct mode is selected on COM2 channel, the direct communication speed of controller part of line can
be adjusted here. Speed of second part of line has to be adjusted to the same value.
Note: WinScope supports only 19200, 38400, 57600 speeds.
Group: EM-BIO8-EFCP
Earth Fault Sd
Setpoint group EM-BIO8-EFCP Related FW 1.0.0
Range [units] 0,03 .. 5,00 [A]
Default value 0,30 A Alternative config NO
Step 0,01 [A]
Comm object 11632 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Limit value for Earth Fault Current protection.
CU AIN1 Calibration
Setpoint group CU AIN Calibration Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
0 (number of decimal is
Default value Alternative config NO
given by sensor curve)
Step the step is defined by an analog sensor curve
Comm object 8431 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Calibrating constant to adjust the measured value of controller analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Note: Unit is adjusted via InteliConfig in configuration of analog input 1.
CU AIN2 Calibration
Setpoint group CU AIN Calibration Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
0 (number of decimal is
Default value Alternative config NO
given by sensor curve)
Step the step is defined by an analog sensor curve
Comm object 8407 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Calibrating constant to adjust the measured value of controller analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Note: Unit is adjusted via InteliConfig in configuration of analog input 2.
CU AIN3 Calibration
Setpoint group CU AIN Calibration Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
0 (number of decimal is
Default value Alternative config NO
given by sensor curve)
Step the step is defined by an analog sensor curve
Comm object 8467 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Calibrating constant to adjust the measured value of controller analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Note: Unit is adjusted via InteliConfig in configuration of analog input 3.
CU AIN4 Calibration
Setpoint group CU AIN Calibration Related FW 1.0.0
Range [units] the range is defined by an analog sensor curve
0 (number of decimal is
Default value Alternative config NO
given by sensor curve)
Step the step is defined by an analog sensor curve
Comm object 8793 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Calibrating constant to adjust the measured value of controller analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Note: Unit is adjusted via InteliConfig in configuration of analog input 4.
Subgroup: Configuration 1
Nominal RPM 1
Setpoint group Alternate Config Related FW 1.0.0
Range [units] 100 .. 4000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 9915 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Nominal engine speed (RPM revolutions per minute).
Note: This value is used when any other alternate configuration is not active.
Nominal Frequency 1
Setpoint group Alternate Config Related FW 1.0.0
Range [units] 45 .. 65 [Hz]
Default value 50 Hz Alternative config YES
Step 1 Hz
Comm object 9913 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note: This value is used when any other alternate configuration is not active.
Nominal Current 1
Setpoint group Alternate Config Related FW 1.0.0
Range [units] 1 .. 10 000 [A]
Default value 350 A Alternative config YES
Step 1A
Comm object 12049 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
It is current limit for generator current protections and means maximal continuous generator current. Nominal
Current can be different from generator rated current value.
Note: This value is used when any other alternate configuration is not active.
Connection Type 1
Setpoint group Alternate Config Related FW 1.0.0
Mono Phase / SplPhL1L2 / SplPhL1L3SplitPhase / 3Ph3Wire / 3Ph4Wire / High
Range [units]
Leg D / Autodetect [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 12058 Related applications AMF, MRS
Config level Standard
3PH3Wire or 3Ph4Wire
L1 >=100V
L2 >=100V
or
L3 >=100V
SplPhL1L2
L1 >=100V
L2 >=100V
or
L3 <= 20V
SplPhL1L3SplitPhase
L1 >=100V
L2 <= 20V
or
L3 >=100V
Mono Phase
L1 >=100V
L2 <= 20V
or
L3 <= 20V
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 472) is active.
Nominal Power 1
Setpoint group Alternate Config Related FW 1.0.0
Range [units] 1 .. 5 000 [kW]
Default value 200 kW Alternative config YES
Step 1 kW
Comm object 12046 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal power of the Gen-set. Generator Overload BOC (page 263) protection is based on this setpoint.
Note: This setpoint is used when setpoint Connection type (page 211) is adjusted to Monophase or
Splitphase or 3Ph3Wire or High Leg D or 3Ph4Wire or when Autodetect detects connection type as
3Ph3Wire or High Leg D or 3Ph4Wire.
Note: This value is used when any other alternate configuration is not active.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Note: This value is used when any other alternate configuration is not active.
Subgroup: Configuration 2
Nominal RPM 2
Setpoint group Alternate Config Related FW 1.0.0
Range [units] 100 .. 4000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 9916 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 472) is active.
Nominal Frequency 2
Setpoint group Alternate Config Related FW 1.0.0
Range [units] 45 .. 65 [Hz]
Default value 50 Hz Alternative config YES
Step 1 Hz
Comm object 9914 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 472) is active.
Nominal Current 2
Setpoint group Alternate Config Related FW 1.0.0
Range [units] 1 .. 10000 [A]
Default value 350 A Alternative config YES
Step 1A
Comm object 12050 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
It is current limit for generator current protections and means maximal continuous generator current. Nominal
Current can be different from generator rated current value.
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 472) is active.
Connection type 2
Setpoint group Alternate Config Related FW 1.0.0
Mono Phase / SplPhL1L2 / SplPhL1L3SplitPhase / 3Ph3Wire / 3Ph4Wire / High
Range [units]
Leg D / Autodetect [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 12059 Related applications AMF, MRS
Config level Standard
3PH3Wire or 3Ph4Wire
L1 >=100V
L2 >=100V
or
L3 >=100V
SplPhL1L2
L1 >=100V
L2 >=100V
or
L3 <= 20V
SplPhL1L3SplitPhase
L1 >=100V
L2 <= 20V
or
L3 >=100V
Mono Phase
L1 >=100V
L2 <= 20V
or
L3 <= 20V
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 472) is active.
Nominal Power 2
Setpoint group Alternate Config Related FW 1.0.0
Range [units] 1 .. 5 000 [kW]
Default value 200 kW Alternative config YES
Step 1 kW
Comm object 12047 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal power of the gen-set. Generator Overload BOC (page 263) protection is based on this setpoint.
Note: This setpoint is used when setpoint Connection type 2 (page 391) is adjusted to Monophase or
Splitphase or 3Ph3Wire or High Leg D or 3Ph4Wire or when Autodetect detects connection type as
3Ph3Wire or High Leg D or 3Ph4Wire.
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 472) is active.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 472) is active.
Subgroup: Configuration 3
Nominal RPM 3
Setpoint group Alternate Config Related FW 1.0.0
Range [units] 100 .. 4 000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 15196 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 472) is active.
Nominal Frequency 3
Setpoint group Alternate Config Related FW 1.0.0
Range [units] 45 .. 65 [Hz]
Default value 50 Hz Alternative config YES
Step 1 Hz
Comm object 15197 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 472) is active.
Nominal Current 3
Setpoint group Alternate Config Related FW 1.0.0
Range [units] 1 .. 10 000 [A]
Default value 350 A Alternative config YES
Step 1A
Comm object 12051 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
It is current limit for generator current protections and means maximal continuous generator current. Nominal
Current can be different from generator rated current value.
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 472) is active.
Connection type 3
Setpoint group Alternate Config Related FW 1.0.0
Mono Phase / SplPhL1L2 / SplPhL1L3SplitPhase / 3Ph3Wire / 3Ph4Wire / High
Range [units]
Leg D / Autodetect [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 12060 Related applications AMF, MRS
Config level Standard
3PH3Wire or 3Ph4Wire
L1 >=100V
L2 >=100V
or
L3 >=100V
SplPhL1L2
L1 >=100V
L2 >=100V
or
L3 <= 20V
SplPhL1L3SplitPhase
L1 >=100V
L2 <= 20V
or
L3 >=100V
Mono Phase
L1 >=100V
L2 <= 20V
or
L3 <= 20V
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 472) is active.
Nominal Power 3
Setpoint group Alternate Config Related FW 1.0.0
Range [units] 1 .. 5 000 [kW]
Default value 200 kW Alternative config YES
Step 1 kW
Comm object 12048 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal power of the gen-set. Generator Overload BOC (page 263) protection is based on this setpoint.
Note: This setpoint is used when setpoint Connection type 3 (page 397) is adjusted to Monophase or
Splitphase or 3Ph3Wire or High Leg D or 3Ph4Wire or when Autodetect detects connection type as
3Ph3Wire or High Leg D or 3Ph4Wire.
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 472) is active.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 472) is active.
8.1.3 Values
What values are:
Values (or quantities) are analog or binary data objects, measured or computed by the controller, that are
intended for reading from the controller screen, PC, MODBUS, etc. Values are organized into groups according
to their meaning.
For full list of values go to the chapter List of values (page 402).
Invalid flag
If valid data is not available for a particular value, the invalid flag is set to it. This situation may be due to the
following:
The value is not being evaluated in the scope of the current application and configuration.
Sensor fail has been detected on an analog input.
The configured ECU or extension module does not provide the particular value.
The communication with the ECU or extension module is interrupted.
A value containing the invalid flag is displayed as “####” in InteliConfig and on the controller screen. If such a
value is read out via MODBUS, it will contain the data 32768 in the case of signed values and 65535 in the case
of unsigned values.
Log Bout 13 433 Network Status 443 Fixed Protections States 1 456
User Buttons 2 433 Network Mode 446 Fixed Protections States 4 456
User Buttons 3 433 Network Name 446 Fixed Protections States 5 457
Group: Engine
ECU AIN 1
ECU AIN 2
ECU AIN 3
ECU AIN 4
ECU AIN 5
ECU AIN 6
ECU AIN 7
ECU AIN 8
ECU AIN 9
ECU-AIN-EXT-1
ECU State
RPM
Speed Request
Note: Accelerator pedal position will be 0 if the engine is not running or loaded.
Required RPM
Group: Generator
Generator Frequency
Nominal Current
Nominal Power
Nominal Voltage
Group: Load
Load Current L1
Load Current L2
Load Current L3
Load Character
Load Character L1
Load Character L2
Load Character L3
Load kVA
Load kVA L1
Load kVA L2
Load kVA L3
Load kVAr
Load kVAr L1
Load kVAr L2
Load kVAr L3
Load kW
Load kW L1
Load kW L2
Load kW L3
Group: Mains
Mains Frequency
Battery Volts
Binary Inputs
Binary Outputs
Coolant Temp
D+
E-Stop
Fuel Level
Not Used
Oil Pressure
Group: Statistics
Genset kWh
Genset kVArh
Genset kVArh
Mains kWh
Mains kVArh
Maintenance 1
Maintenance 2
Maintenance 3
Maintenance 4
Maintenance 5
Maintenance 6
Num E-Stops
Num Starts
Pulse Counter 1
Pulse Counter 2
Rental 1
Rental 2
Running Hours
Shutdowns
Group: Info
Active Application
Application
Breaker State
Connection Type
Engine State
FW Branch
FW Version
ID String
SPI Module A
SPI Module B
Timer Text
Timer Value
Log Bout 1
Log Bout 2
Log Bout 3
Log Bout 4
Log Bout 5
Log Bout 6
Log Bout 7
Log Bout 8
Log Bout 9
Log Bout 10
Log Bout 11
Log Bout 12
Log Bout 13
User Buttons 1
User Buttons 2
User Buttons 3
User Buttons 4
User Buttons 5
User Buttons 6
User Buttons 7
User Buttons 8
User Buttons 9
User Buttons 10
User Buttons 11
User Buttons 12
User Buttons 13
User Buttons 14
User Buttons 15
User Buttons 16
User Buttons 17
User Buttons 18
User Buttons 19
User Buttons 20
User Buttons 21
User Buttons 22
User Buttons 23
User Buttons 24
User Buttons 25
User Buttons 26
User Buttons 27
User Buttons 28
User Buttons 29
User Buttons 30
User Buttons 31
User Buttons 32
Group: CM-GPRS
AirGate ID
AirGate Status
Code Description
0 SIM card is not inserted
1 Controller registered, waiting for authorization
2 Not possible to register, controller blacklisted
3 Not possible to register, server has no more capacity
4 Not possible to register, other reason
5 Controller registered and authorized
CM-GPRS; CM-4G-
Value group Related FW 1.0.0
GPS (4G part)
Units [-]
Comm object 24288 Related applications AMF, MRS
Description
Diagnostic code for the CM-GPRS or CM-4G-GPS module.
GSM Diag Code – Common list of diagnostic codes for cellular modules
Code Description
0 OK. No error.
1 Not possible to hang up.
2 Modul is switched off
3 Module is switched on
4 Module – error in initialization
5 Module – not possible to set the APN
6 Module – not possible to connect to GPRS network
7 Module – not possible to retrieve IP address
8 Module – not accepted DNS IP address
9 Error in modem detection
10 Error in initialization of analog modem
SIM card is locked (Possibly PIN code required, PIN needs to be deactivated) or
11
unknown status of SIM locking
12 No GSM signal
13 Not possible to read the SIM card parameters
GSM modem did not accepted particular initialization command, possibly caused by
14
locked SIM card
15 Unknown modem
16 Bad answer to complement initialization string
17 Not possible to read GSM signal strength
18 CDMA modem not detected
19 No CDMA network
20 Unsuccessful registration to CDMA network
21 SIMCom/ME909s: can´t read FW version
22 SIMCom: GSM signal not found
23 SIMCom: can´t detect module speed
24 SIMCom: HW reset issued
25 PUK is required
26 Error of SIM card detected
27 ME909s: can't set module bps
28 ME909s: can't set link configuration
29 ME909s: can't do power-off
30 ME909s: can't do power-on
31 ME909s: can't do hardware reset
32 ME909s: ME909s not started
CM-GPRS; CM-4G-
Value group Related FW 1.0.0
GPS (4G part)
Units %
Comm object 24300 Related applications AMF, MRS
Description
This value contains information about relative quality of the cellular signal received by the CM-GPRS module
or by CM-4G-GPS module. The lower value means higher quality of signal.
Network Status
CM-GPRS; CM-4G-
Value group Related FW 1.0.0
GPS (4G part)
Units [-]
Comm object 24290 Related applications AMF, MRS
Description
The text of this value represents the status of the GSM modem.
CM-GPRS; CM-4G-
Value group Related FW 1.0.0
GPS (4G part)
Units %
Comm object 24302 Related applications AMF, MRS
Description
This value contains information about relative strength of the cellular signal received by the CM-GPRS
module or by CM-4G-GPS module. It is a relative value helping to find the best signal and for troubleshooting
cases.
CM-GPRS; CM-4G-
Value group Related FW 1.0.0
GPS (4G part)
Units [-]
Comm object 24307 Related applications AMF, MRS
Description
Result of last email, which was sent by controller.
Code Description
0 Email was successfully sent.
2 It is not possible to establish connection with SMTP server.
3 SMTP server is not ready for communication.
4 Maximum length of data can’t be read.
5 No appeal to send command.
6 Command can’t be send.
7 Command can’t be send.
8 HELO command was refused.
11 AUTH LOGIN command was refused.
12 Wrong user name.
13 Wrong password.
14 MAIL FROM command was refused.
15 RCPT TO command was refused.
16 DATA command was refused.
17 Sending of email failed.
18 SMTP server refused the data of email.
19 SMTP server refused the data of email.
20 QUIT command was refused.
21 Lost of connection.
23 Error during closing the connection.
24 No answer from server.
25 It is impossible to create data for command DATA.
26 It is impossible to read data for command DATA.
28 Error of encoding.
29 There was no attempt to send email.
Network Mode
CM-GPRS; CM-4G-
Value group Related FW 1.0.0
GPS (4G part)
Units [-]
Comm object 24146 Related applications AMF, MRS
Description
The type of data connection.
Network Name
CM-GPRS; CM-4G-
Value group Related FW 1.0.0
GPS (4G part)
Units [-]
Comm object 24147 Related applications AMF, MRS
Description
The name of operator which to SIM card is connected.
Note: If roaming service is used then prefix "R" is added before the name of operator.
Group: CM-4G-GPS
Active Satellites
AirGate ID
AirGate Status
Code Description
0 SIM card is not inserted
1 Controller registered, waiting for authorization
2 Not possible to register, controller blacklisted
3 Not possible to register, server has no more capacity
4 Not possible to register, other reason
5 Controller registered and authorized
Altitude
CM-4G-GPS (GPS
Value group Related FW 1.0.0
part)
Units m
Comm object 24266 Related applications AMF, MRS
Description
Actual GPS altitude.
CM-GPRS; CM-4G-
Value group Related FW 1.0.0
GPS (4G part)
Units %
Comm object 24302 Related applications AMF, MRS
Description
This value contains information about relative strength of the cellular signal received by the CM-GPRS
module or by CM-4G-GPS module. It is a relative value helping to find the best signal and for troubleshooting
cases.
Current IP Address
GPS Status
HomePosDist
CM-GPRS; CM-4G-
Value group Related FW 1.0.0
GPS (4G part)
Units [-]
Comm object 24307 Related applications AMF, MRS
Description
Result of last email, which was sent by controller.
Code Description
0 Email was successfully sent.
2 It is not possible to establish connection with SMTP server.
3 SMTP server is not ready for communication.
4 Maximum length of data can’t be read.
5 No appeal to send command.
6 Command can’t be send.
7 Command can’t be send.
8 HELO command was refused.
11 AUTH LOGIN command was refused.
12 Wrong user name.
13 Wrong password.
14 MAIL FROM command was refused.
15 RCPT TO command was refused.
16 DATA command was refused.
17 Sending of email failed.
18 SMTP server refused the data of email.
19 SMTP server refused the data of email.
20 QUIT command was refused.
21 Lost of connection.
23 Error during closing the connection.
24 No answer from server.
25 It is impossible to create data for command DATA.
26 It is impossible to read data for command DATA.
28 Error of encoding.
29 There was no attempt to send email.
Latitude
CM-4G-GPS (GPS
Value group Related FW 1.0.0
part)
Units [-]
Comm object 24268 Related applications AMF, MRS
Description
Actual GPS latitude. Positions on north hemisphere have positive value, position on south hemisphere have
negative value.
Longitude
CM-4G-GPS (GPS
Value group Related FW 1.0.0
part)
Units [-]
Comm object 24267 Related applications AMF, MRS
Description
Actual GPS longitude. Positions on east hemisphere have positive value, position on west hemisphere have
negative value.
Network Mode
CM-GPRS; CM-4G-
Value group Related FW 1.0.0
GPS (4G part)
Units [-]
Comm object 24146 Related applications AMF, MRS
Description
The type of data connection.
Network Name
CM-GPRS; CM-4G-
Value group Related FW 1.0.0
GPS (4G part)
Units [-]
Comm object 24147 Related applications AMF, MRS
Description
The name of operator which to SIM card is connected.
Note: If roaming service is used then prefix "R" is added before the name of operator.
Network Status
CM-GPRS; CM-4G-
Value group Related FW 1.0.0
GPS (4G part)
Units [-]
Comm object 24290 Related applications AMF, MRS
Description
The text of this value represents the status of the GSM modem.
Primary DNS
Speed
Group: CM-Ethernet
AirGate ID
AirGate Status
Code Description
0 Ethernet cable is disconnected
1 Controller registered, waiting for authorization
2 Not possible to register, controller blacklisted
3 Not possible to register, server has no more capacity
4 Not possible to register, other reason
5 Controller registered and authorized
Current Gateway
Current IP Address
Code Description
0 Email was successfully sent.
2 It is not possible to establish connection with SMTP server.
3 SMTP server is not ready for communication.
8 HELO command was refused.
9 EHLO command was refused.
11 AUTH LOGIN command was refused.
12 Wrong user name.
13 Wrong password.
14 MAIL FROM command was refused.
15 RCPT TO command was refused.
16 DATA command was refused.
17 Sending of email failed.
20 QUIT command was refused.
25 It is impossible to create data for command DATA.
26 It is impossible to read data for command DATA.
27 Email address can’t be read.
30 SMTP server address translation error (from DNS server).
31 Error reading email content data (24327).
MAC Address
Primary DNS
Secondary DNS
Group: Date/Time
Date
Time
Fixed Protection
Value group Related FW 1.0.0
States
Units
Comm object 20744 Related applications AMF, MRS
Description
.
Fixed Protection
Value group Related FW 1.0.0
States
Units
Comm object 20745 Related applications AMF, MRS
Description
.
Fixed Protection
Value group Related FW 1.0.0
States
Units
Comm object 20744 Related applications AMF, MRS
Description
.
Fixed Protection
Value group Related FW 1.0.0
States
Units
Comm object 20747 Related applications AMF, MRS
Description
.
Fixed Protection
Value group Related FW 1.0.0
States
Units
Comm object 20748 Related applications AMF, MRS
Description
.
EM Analog Input A 1
EM Analog Input A 2
EM Analog Input A 3
EM Analog Input A 4
EM Analog Input A 5
EM Analog Input A 6
EM Analog Input A 7
EM Analog Input A 8
EM Analog Input A 9
EM Analog Input A 10
EM Analog Input A 11
EM Analog Input A 12
EM Analog Input A 13
EM Analog Input A 14
EM Analog Input A 15
EM Analog Input A 16
EM Analog Input B 1
EM Analog Input B 2
EM Analog Input B 3
EM Analog Input B 4
EM Analog Input B 5
EM Analog Input B 6
EM Analog Input B 7
EM Analog Input B 8
EM Analog Input B 9
EM Analog Input B 10
EM Analog Input B 11
EM Analog Input B 12
EM Analog Input B 13
EM Analog Input B 14
EM Analog Input B 15
EM Analog Input B 16
EM BIO A
EM BIO B
Group: PLC
PLC-BOUT 1
PLC-BOUT 2
PLC-BOUT 3
PLC-BOUT 4
PLC-BOUT 5
PLC-BOUT 6
PLC-BOUT 7
PLC Resource 1
PLC Resource 2
PLC Resource 3
PLC Resource 4
PLC Resource 5
PLC Resource 6
PLC Resource 7
PLC Resource 8
For full list of Logical binary inputs go to the chapter Logical binary inputs alphabetically (page 471).
LBI: A
Access Lock
Related FW 1.0.0 Related applications AMF, MRS
Comm object 1
Description
When this input is active, no setpoints can be adjusted from controller's front panel and controller mode (OFF
/ MAN / AUTO / TEST) cannot be changed. The front panel buttons can not be used as well.
Note: Access Lock does not protect setpoints and mode changing from InteliConfig. To avoid
unqualified changes the selected setpoints have to be password protected.
Also the buttons Fault Reset and Horn Reset are not blocked at all and buttons Start and Stop
in MAN mode are not blocked.
Application AMF
Related FW 1.0.0 Related applications AMF
Comm object
Description
LBI is used to select AMF mode. It has higher priority than the setpoint Default Application Select (page
220).
Note: Tier4 ECU is recognized when there is an logioindex corresponding to particular controller for SPN
3695 (logioindex 961) or SPN 3696 (logioindex 960). (i.e. RegenInhibitSW or RegenForceSW). Due to
this fact, it is necessary to add one of the two SPNs to each ESC file that contains aftertreatment
support. Without one of these SPNs, the controller would not activate the Aftertreatment screen. (From
latest testing it seems that logioindex 960 has to be first and 961 has to be second for afterteatment
screen to appear)
Note: Selected lamps are controlled by following SPN: 3697, 6915, 3698, 5246, 5245, 3703, 6918.
Note: Severity of lamps state is following (from lowest to highest): inactive, active, blinking slow,
blinking fast. Activation of an icon then means that the state increase its severity. Deactivating of an
icon means that the state decrease its severity.
Note: umping to Aftertreatment screen can be bypassed by jumping to alarmlist instead. This is used on
older controllers and displays.
Note: Tier4 ECU is recognized when there is an logioindex corresponding to particular controller for SPN
3695 (logioindex 961) or SPN 3696 (logioindex 960). (i.e. RegenInhibitSW or RegenForceSW). Due to
this fact, it is necessary to add one of the two SPNs to each ESC file that contains aftertreatment
support. Without one of these SPNs, the controller would not activate the Aftertreatment screen. (From
latest testing it seems that logioindex 960 has to be first and 961 has to be second for afterteatment
screen to appear)
Note: Selected lamps are controlled by following SPN: 3697, 6915, 3698, 5246, 5245, 3703, 6918.
Note: Severity of lamps state is following (from lowest to highest): inactive, active, blinking slow,
blinking fast. Activation of an icon then means that the state increase its severity. Deactivating of an
icon means that the state decrease its severity.
Note: umping to Aftertreatment screen can be bypassed by jumping to alarmlist instead. This is used on
older controllers and displays.
ATT Interlock
Related FW 1.0.0 Related applications AMF
Comm object
Description
Note: SPN 3695 serves as a command. Thus the aftertreatment screen and alarm list reflects the
response from ECU (SPN 3703) instead of SPN 3695). User shall be informed about real status of the
ECU and aftertreatment system (SPN3703), not about the command (SPN3695).
Note: Tier4 ECU is recognized when there is an logioindex corresponding to particular controller for SPN
3695 (logioindex 961) or SPN 3696 (logioindex 960). (i.e. RegenInhibitSW or RegenForceSW). Due to
this fact, it is necessary to add one of the two SPNs to each ESC file that contains aftertreatment
support. Without one of these SPNs, the controller would not activate the Aftertreatment screen. (From
latest testing it seems that logioindex 960 has to be first and 961 has to be second for afterteatment
screen to appear)
Note: Selected lamps are controlled by following SPN: 3697, 6915, 3698, 5246, 5245, 3703, 6918.
Note: Severity of lamps state is following (from lowest to highest): inactive, active, blinking slow,
blinking fast. Activation of an icon then means that the state increase its severity. Deactivating of an
icon means that the state decrease its severity.
Note: umping to Aftertreatment screen can be bypassed by jumping to alarmlist instead. This is used on
older controllers and displays.
LBI: B
Battery Charger
Related FW 1.0.0 Related applications AMF, MRS
Comm object 623
Description
When binary input is active and its delay Battery Charger Fail Delay (page 258) is out of time then alarm
Wrn Battery Charger Fail (page 599) is activated, written into history log and logical binary output AL
BATTERY CHARGER (PAGE 1) is activated.
LBI: C
Choke Inhibit
Related FW 1.0.0 Related applications AMF, MRS
Comm object 946
Description
Logical binary input CHOKE INHIBIT prevent Choke functionality when logical binary output CHOKE (PAGE
503) is activated. If CHOKE INHIBIT is activated when CHOKE LBO is active, CHOKE LBO is deactivated
immediately and vice versa if LBI CHOKE INHIBIT is deactivated and LBO CHOKE should be active then is
activated.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
Wrn Binary input is used for warning protection only.
Stp Binary input is used for slow stop protection
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
LBI: D
Dark Mode
Related FW 1.0.0 Related applications AMF, MRS
Comm object 930
Description
This binary input activates function of dark mode. It means that backlight of display is turn off (information on
controller screens are not affected) and LEDs (Mains, Generator, Load, Breakers, etc.) are turn off (LEDs
don’t react on normal condition of their activation and deactivation).
Note: After deactivation of dark mode, backlight of display is turned on and than behaves normally.
Note: After deactivation of dark mode, Front Face status LEDs are turned on due to current situation of
gen-set.
Note: If this LBI is active on both gen-sets, the behavior is not changed. Decision is based on running
hours values.
LBI: E
ECU Key Switch
Related FW 1.0.0 Related applications AMF, MRS
Comm object 951
Description
This binary input is used to switch on ECU POWER RELAY (PAGE 506), when engine start is not requested. It
is intended to enable engine values reading, when engine doesn't run.
When this binary input is active, binary output ECU POWER RELAY (PAGE 506) is active too.
When this binary input is inactive, function of ECU POWER RELAY (PAGE 506) is not affected.
Emergency Stop
Related FW 1.0.0 Related applications AMF, MRS
Comm object 40
Description
The shutdown procedure will start immediately when this input is activated. Input is inverted (NC = normaly
closed) in default configuration.
Note: In case of controller hardware or software fail, safe stop of the engine doesn’t have to be ensured.
To back-up the Emergency Stop function it is recommended to connect separate circuit for
disconnection of Fuel Solenoid and Starter signals.
LBI: F
Fault Reset Button
Related FW 1.0.0 Related applications AMF, MRS
Comm object 191
Description
Binary input has the same function as Fault Reset button on the InteliLite 4 front panel.
Fuel Level
Related FW 1.0.0 Related applications AMF, MRS
Comm object 626
Description
Binary input for FUEL LEVEL (PAGE 548) protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
Wrn Binary input is used for warning protection only.
Stp Binary input is used for slow stop protection
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 480) is configured then binary
output FUEL PUMP (PAGE 509) is control by this binary input.
IMPORTANT: It is necessary to configure analog input FUEL LEVEL (PAGE 548) for proper
function of this binary input.
LBI: G
GCB Button
Related FW 1.0.0 Related applications AMF, MRS
Comm object 193
Description
Binary input has the same function as GCB button on the InteliLite 4 front panel. It is evaluated in MAN
mode only.
GCB Feedback
Related FW 1.0.0 Related applications AMF, MRS
Comm object 63
Description
Use this input for indication whether the generator circuit breaker is open or closed.
Note: InteliLite 4 controller can work even without breaker feedbacks, in this case do not configure the
feedback to binary inputs.
Geo-Fencing Enable
Related FW 1.0.0 Related applications AMF, MRS
Comm object 218
Description
This binary input enables or disables Fence 1 Protection (page 358) and Fence 2 Protection (page 359) if
Group: Geo-Fencing (page 356) is adjusted to value "LBI Enable".
LBI: H
Horn Reset Button
Related FW 1.0.0 Related applications AMF, MRS
Comm object 192
Description
Binary input has the same function as Horn reset button on the InteliLite 4 front panel.
LBI: I
Idle Speed
Related FW 1.0.0 Related applications AMF, MRS
Comm object 624
Description
This binary input changes cooling speed from nominal to idle.
LBI: M
Mains Fail Block
Related FW 1.0.0 Related applications AMF
Comm object 622
Description
If the input is active, the automatic start of the Gen-set at Mains failure is blocked. In case of running Gen-
set in AUTO mode, timer Mains Return Delay (page 279) is started and when it elapses GCB is opened,
Gen-set goes to cooling procedure and stops. When GCB is opened after Transfer Delay (page 280)Open
Transition Min Break (page 1) the MCB is closed.
Note: This input simulates healthy Mains.
This binary input has the same function as MCB button on the InteliLite 4 front panel. It is evaluated in
MAN mode only.
MCB Feedback
Related FW 1.0.0 Related applications AMF
Comm object 65
Description
Use this input for indication whether the mainsbus circuit breaker is open or closed.
Note: InteliLite 4 controller can work even without breaker feedbacks, in this case do not configure the
feedback to binary inputs.
LBI: N
Not Used
Related FW 1.0.0 Related applications AMF, MRS
Comm object 184
Description
Binary input has no function. Use this configuration when binary input is not used.
LBI: O
Oil Pressure
Related FW 1.0.0 Related applications AMF, MRS
Comm object 43
Description
Binary input for OIL PRESSURE (PAGE 550) protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
Wrn Binary input is used for warning protection only.
Sd Binary input is used for shutdown protection.
IMPORTANT: This binary input is also used for evaluating engine running condition.
Example: Normally close connection – when LBI is active then oil pressure is OK and is higher than
starting oil pressure.
Note: In case that you want to use binary input of oil pressure sensor just for protection please use one
of the BIN PROTECTION 1 (PAGE 1).
LBI: P
Prestart Bypass
Related FW 1.0.0 Related applications AMF, MRS
Comm object
Description
This logic binary input enables or disables protections adjusted as LBI Enable.
LBI: R
Rem TEST On Load
Related FW 1.0.0 Related applications AMF, MRS
Comm object 61
Description
Closing of the GCB in MRS or transferring of the load from the mains to Gen-set in AMF.
Remote MAN
Related FW 1.0.0 Related applications AMF, MRS
Comm object 618
Description
The controller is switched to the MAN mode (there are fourthree modes OFF / MAN / AUTO / TEST) when
this binary input is active. When opens controller is switched back to previous mode.
Remote control priority:
Remote OFF (Highest priority)
Remote TEST
Remote MAN
Remote AUTO (Lowest Priority)
Remote Start/Stop
Related FW 1.0.0 Related applications AMF, MRS
Comm object 38
Description
Use this input to start and stop the Gen-set in AUTO and TEST mode.
Note: If the binary input Remote Start/Stop is active and engine is running and mains failure occurs, the
MCB breaker opens, after Transfer Delay (page 280) the GCB breaker is closed. Once the mains is
OK, the Mains Return Delay (page 279) elapses and the GCB breaker is opened. Then after Transfer
Delay (page 280) is MCB breaker closed. Gen-set remains running as long as binary input Rem
Start/Stop is active. For more details see timing diagram below.
Remote TEST
Related FW 1.0.0 Related applications AMF, MRS
Comm object 621
Description
The controller is switched to the TEST mode (there are fourthree modes OFF / MAN / AUTO / TEST) when
this binary input is active. When opens controller is switched back to previous mode.
Remote control priority:
Remote OFF (Highest priority)
Remote TEST
Remote MAN
Remote AUTO (Lowest Priority)
LBI: S
Sd Override
Related FW 1.0.0 Related applications AMF, MRS
Comm object 44
Description
If this input is active, all alarms except Emergency Stop and Overspeed are suppressed. The suppressed
alarms will be displayed in the alarm list, but they will not take effect regarding the Gen-set control.
Note: Sd Override (page 490) is indicated in the alarm list if Sd Override mode is active to inform the
operator that the engine is not protected.
Binary input has the same function as Start Button on the InteliLite 4 front panel. It is evaluated in MAN
mode only.
Starter 2 Disabled
Related FW 1.0.0 Related applications AMF, MRS
Comm object
Description
When Gen-set has two starters available this LBI is used to disable starter 2.
Binary input has the same function as Stop Button on the InteliLite 4 front panel. It is evaluated in MAN
Mode only.
For full list of Logical binary inputs go to the chapter Logical binary outputs alphabetically (page 493).
LBO: A
AIN Switch01
Related FW 1.0.0 Related applications AMF, MRS
Comm object 1400
Description
This is an output from the General Analog Input 1 switch function. The behavior of the switch depends on the
adjustment of the setpoints AIN Switch01 On (page 310) and AIN Switch01 Off (page 311). The value is
measured from AIN SWITCH 01 (PAGE 543) analog input.
AIN Switch03
Related FW 1.0.0 Related applications AMF, MRS
Comm object 1402
Description
This is an output from the General Analog Input 3 switch function. The behavior of the switch depends on the
adjustment of the setpoints AIN Switch03 On (page 314) and AIN Switch03 Off (page 315). The value is
measured from AIN SWITCH 03 (PAGE 543) analog input.
AIN Switch05
Related FW 1.0.0 Related applications AMF, MRS
Comm object 1787
Description
This is an output from the General Analog Input 5 switch function. The behavior of the switch depends on the
adjustment of the setpoints AIN Switch05 On (page 318) and AIN Switch05 Off (page 319). The value is
measured from AIN SWITCH 05 (PAGE 544) analog input.
AIN Switch07
Related FW 1.0.0 Related applications AMF, MRS
Comm object 1789
Description
This is an output from the General Analog Input 7 switch function. The behavior of the switch depends on the
adjustment of the setpoints AIN Switch07 On (page 322) and AIN Switch07 Off (page 323). The value is
measured from AIN SWITCH 07 (PAGE 545) analog input.
AIN Switch09
Related FW 1.0.0 Related applications AMF, MRS
Comm object 1791
Description
This is an output from the General Analog Input 9 switch function. The behavior of the switch depends on the
adjustment of the setpoints AIN Switch09 On (page 326) and AIN Switch09 Off (page 327). The value is
measured from AIN SWITCH 09 (PAGE 545) analog input.
Air Valves
Related FW 1.0.0 Related applications AMF, MRS
Comm object 1247
Description
This output is activated together with binary output PRESTART (PAGE 531) and opens after the engine is
stopped or in case that engine is not ready.
AL Common Fls
Related FW 1.0.0 Related applications AMF, MRS
Comm object 6
Description
Output is activated when any sensor fail alarm appears.
The output opens, if:
No sensor fail alarm is active and
AL Common Wrn
Related FW 1.0.0 Related applications AMF, MRS
Comm object 3
Description
Output is activated when any warning alarm appears.
The output opens, if:
No warning alarm is active and
AL Mains Fail
Related FW 1.0.0 Related applications AMF
Comm object 197
Description
Output for signaling Mains Failure. This output is active when at least one mains frequency BOC or Sd alarm
or at least one mains voltage BOC or Sd alarm is present in alarmlist or isn’t confirmed.
LBO: C
Choke
Related FW 1.0.0 Related applications AMF, MRS
Comm object 2091
Description
Logical binary output for choke valve control. Output CHOKE is activated every time when logical binary
output STARTER 1 (PAGE 536) is activated. Output is deactivated when one of these conditions is fulfilled:
Choke Time is elapsed
Generator voltage is higher than Choke Voltage
Logical binary input Choke Inhibit is activated
Or when some of these situations during start occurs:
Any second level alarm
Emergency stop
Stop command
Cranking pause
LBO: D
Dual Operation OK
Related FW 1.0.0 Related applications AMF, MRS
Comm object 2096
Description
This LBO is active when there is not AHI Dual Operation Fail (page 588) alarm in alarmlist.
LBO: E
ECU Comm OK
Related FW 1.0.0 Related applications AMF, MRS
Comm object 347
Description
This output is active when an ECU is configured, connected and the communication with the ECU is
established.
Note: When ECU POWER RELAY (PAGE 506) is not configured, output is evaluated all the time. If ECU
POWER RELAY (PAGE 506) is configured, output is evaluated only when engine is not stop (ECU POWER
RELAY (PAGE 506) is active).
IMPORTANT: This LBO also affects evaluation of Sd ECU Communication Fail (page 616) or
Wrn ECU Communication Fail (page 585) alarms. With configured LBO ECU Power Relay,
these alarms are evaluated only when this LBO is active. Without configured LBO ECU
Power Relay, these alarm are evaluated all the time.
Exercise Timer 1
Related FW 1.0.0 Related applications AMF, MRS
Comm object 1250
Description
This is an output from the Exercise timer 1. This output makes it easy to make periodic tests of the Gen-set
and its activation depends on the setpoints in the Subgroup: Timer 1 (page 332) subgroup. This output is
active when Timer 1 is active.
Note: In the event that both Timers are active at the same time, Subgroup: Timer 1 (page 332) has a
higher priority than Subgroup: Timer 2 (page 340).
LBO: F
FltRes Button Echo
Related FW 1.0.0 Related applications AMF, MRS
Comm object 592
Description
This output provides 1s pulse when:
Fault Reset button is pressed on the controller front facia or
Fault Reset button is pressed on any of external local/remote terminals or
Fault Reset command is received via communication line or
The input FAULT RESET BUTTON (PAGE 479) is activated.
Diesel:
The output is activated before binary output STARTER 1 (PAGE 536).The lead time is adjusted by setpoint
Fuel Solenoid Lead (page 239).
Gas:
The output closes together with binary output IGNITION (PAGE 520) when engine RPM exceed 30 RPM (fix
value).
LBO: G
GCB Button Echo
Related FW 1.0.0 Related applications AMF, MRS
Comm object 35
Description
This output provides 1s pulse when:
GCB button is pressed on the controller front facia or
GCB button is pressed on any of external local/remote terminals or
GCB command is received via communication line or
the input GCB BUTTON is activated.
Note: InteliLite 4 controllers can work even without breaker feedbacks, in this case do not configure the
feedback to binary inputs.
GCB ON Coil
Related FW 1.0.0 Related applications AMF, MRS
Comm object 42
Description
The output is intended for control of close coil of generator circuit breaker. The output gives at least 5 second
pulse in the moment the breaker has to be closed.
This output is dedicated for diesel engine only. This output will be active for exact time pre-set by setpoint
Glow Plugs Time (page 233) before every starting attempt. The output is deactivated at the same time as
the STARTER 1 (PAGE 536) output is activated (100 ms after PRESTART (PAGE 531) output is deactivated).
When the Glow Plugs Time (page 233) is longer than Cranking Fail Pause (page 231) then the Glow
Plugs Time (page 233) in Cranking Fail Pause (page 231) is long as Cranking Fail Pause (page 231).
When the Glow Plugs Time (page 233) is shorter than Cranking Fail Pause (page 231) then the Glow
Plugs Time (page 233) in Cranking Fail Pause (page 231) is long as normal Glow Plugs Time (page
233).
LBO: H
Heartbeat
Related FW 1.0.0 Related applications AMF, MRS
Comm object 81
Description
This output toggles on/off in a period of 500 ms whenever the controller is switched on and functional.
LBO: I
Idle/Nominal
Related FW 1.0.0 Related applications AMF, MRS
Comm object 39
Description
This output is used for switching between idle speed and nominal speed of the engine during the startup
phase, if this feature (input) is available on the particular engine. In the case of some EFI engines, the
idle/nominal switching is performed over the communication bus.
The output Idle/Nominal is activated after the timer Idle Time (page 239) elapses. The Idle Time (page
239) starts to countdown when Starting RPM (page 232) reached. The underspeed protection is not
evaluated during fixed 5 seconds period after reaching Starting RPM (page 232). A Start Fail protection
occurs if the RPM drop below 2RPM during idle.
Note: Connect binary output Idle/Nominal to speed governor to switch the speed:
opened = Idle
closed = Nominal
(for normally open contact type)
Ignition
Related FW 1.0.0 Related applications AMF, MRS
Comm object 37
Description
This output is dedicated to controlling the ignition at a gas engine. the output is active together with binary
output FUEL SOLENOID (PAGE 509) in the moment when the timer Sd Ventilation Time (page 243) elapsed
and the gen-set reaches at least 30 RPM during cranking. The timer Sd Ventilation Time (page 243)
become active when the gen-set has been stopped for any Sd protection or the controller has been turned on
only before first cranking attempt. the output is deactivated 500 ms after all Additional running engine
indications (page 119) will be inactive. the output is deactivated when the Gen-set has to be stopped or in
pause during repeated starts.
Ignition On
LBO: L
Load Shedding Stage 1
Related FW 1.0.0 Related applications AMF, MRS
Comm object 51
Description
Particular instances of the load shedding functionality
The load shedding outputs are activated (load is beeing shedd) in the order 1, 2, 3, 4, 5.
The load shedding outputs are deactivated (load is beeing reconnected) in the order 5, 4, 3, 2, 1.
The load disconnected by the LBO Nr.1 is the less essential load of these three possible loads instances.
The load shedding outputs are activated (load is beeing shedd) in the order 1, 2, 3, 4, 5.
The load shedding outputs are deactivated (load is beeing reconnected) in the order 5, 4, 3, 2, 1.
The load disconnected by the LBO Nr.1 is the less essential load of these three possible loads instances.
The load shedding outputs are activated (load is beeing shedd) in the order 1, 2, 3, 4, 5.
The load shedding outputs are deactivated (load is beeing reconnected) in the order 5, 4, 3, 2, 1.
The load disconnected by the LBO Nr.1 is the less essential load of these three possible loads instances.
The load shedding outputs are activated (load is beeing shedd) in the order 1, 2, 3, 4, 5.
The load shedding outputs are deactivated (load is beeing reconnected) in the order 5, 4, 3, 2, 1.
The load disconnected by the LBO Nr.1 is the less essential load of these three possible loads instances.
The load shedding outputs are activated (load is beeing shedd) in the order 1, 2, 3, 4, 5.
The load shedding outputs are deactivated (load is beeing reconnected) in the order 5, 4, 3, 2, 1.
The load disconnected by the LBO Nr.1 is the less essential load of these three possible loads instances.
LBO: M
Mains Healthy
Related FW 1.0.0 Related applications AMF
Comm object 78
Description
This output is active while Mains failure is not detected and Mains voltage and frequency is within limits.
The limits for under/overvoltage and under/overfrequency are the same as for mains voltage/frequency and
can be found in the Mains Settings setpoint group.
Manual Ready
Related FW 1.0.0 Related applications AMF, MRS
Comm object 1258
Description
This output is active when controller is in MAN mode and the engine is stopped and it is possible to start it
i.e. no red alarm is activated or SD OVERRIDE (PAGE 490) is active (Output READY (PAGE 533) is active).
MCB ON Coil
Related FW 1.0.0 Related applications AMF
Comm object 46
Description
The output is intended for control of close coil of mainsbus circuit breaker. The output gives at least 5 second
pulse in the moment the breaker has to be closed.
MCB UV Coil
Related FW 1.0.0 Related applications AMF
Comm object 48
Description
The output is intended for control of undervoltage coil of mainsbus circuit breaker. The output is active the
whole time when the controller is switched on. The output is deactivated for at least 5 seconds in the
moment the breaker has to be switched off.
Mode MAN
Related FW 1.0.0 Related applications AMF, MRS
Comm object 18
Description
This output is active whenever the controller is in MAN mode.
LBO: N
Not In AUTO
Related FW 1.0.0 Related applications AMF, MRS
Comm object 1248
Description
This output is active when controller isn’t in AUTO mode.
LBO: P
Prestart
Related FW 1.0.0 Related applications AMF, MRS
Comm object 36
Description
This output can be used for control of any device, which has to be activated just before start. the output is
active for time period of Prestart Time (page 232). The output is deactivated 100 ms before the STARTER 1
(PAGE 536) output is activated.
When the Prestart Time (page 232) is longer than Cranking Fail Pause (page 231) then the Prestart
Time (page 232) in Cranking Fail Pause (page 231) is long as Cranking Fail Pause (page 231) minus
100 ms.
When the Prestart Time (page 232) is shorter than Cranking Fail Pause (page 231) then the Prestart
Time (page 232) in Cranking Fail Pause (page 231) is long as normal Prestart Time (page 232).
LBO: R
Ready
Related FW 1.0.0 Related applications AMF, MRS
Comm object 62
Description
The binary output is active when the engine is stopped and it is possible to start it i.e. no red alarm is
activated or SD OVERRIDE (PAGE 490) is active.
The binary output is switch on when the Ready state occurs.
The binary output is switch off when the Prestart or the Not Ready or the Stop state occurs i.e. always
except Ready state.
Ready To Load
Related FW 1.0.0 Related applications AMF, MRS
Comm object 58
Description
the output is active whenever the GCB is closed or can be closed i.e. the stabilization phase is finished, the
Gen-set is running and the Minimal Stabilization Time (page 241) timer has elapsed and the Gen-set
voltage and frequency are within limits.
If GCB is open then Gen-set voltage and frequency must be in limits.
If GCB is close then Gen-set voltage and frequency can be out of limits, but protection delay can’t be count
down. If Gen-set voltage and frequency will return into limits until delay is count down then output is still
active.
LBO: S
Sd Override
Related FW 1.0.0 Related applications AMF, MRS
Comm object 962
Description
The output is active if SD OVERRIDE (PAGE 490) input is active and open if SD OVERRIDE (PAGE 490) input is
inactive. This output is usually used to send information about SD OVERRIDE (PAGE 490) input into ECU.
Starter 1
Related FW 1.0.0 Related applications AMF, MRS
Comm object 24
Description
This output is dedicated for starter motor control. The number of cranking attempts is adjusted by setpoint
Cranking Attempts (page 231) in Engine Settings group. Cranking fail pause is adjusted by setpoint
Cranking Fail Pause (page 231).
Still Log 1
Related FW 1.0.0 Related applications AMF, MRS
Comm object 27
Description
Logical binary output which is still in logical 1.
This output is dedicated to control the stop solenoid (valve). The output is activated when an engine stop
command is received and is deactivated 12 s after last running engine indication went off, i.e. engine is
stopped.
Note: If Additional running engine indications (page 119) went off during 5 s pause than Stop
Solenoid is not activated again otherwise stop solenoid is activated again.
Supplying Load
Related FW 1.0.0 Related applications AMF, MRS
Comm object 1249
Description
The binary output depends on measured generator active power. Power is compared with generator nominal
active power with use of hysteresis and with delay of switch 1 s.
When the measured active power is equal to or bigger than 5 % of Nominal Power (page 209) for 1 s then
the binary output is active.
When the measured active power is equal to or lower than 3 % of Nominal Power (page 209) for 1 s then
the binary output is active.
LBO: T
Temperature Switch
Related FW 1.0.0 Related applications AMF, MRS
Comm object 563
Description
This is an output from the Temperature switch function. The behavior of the switch depends on the
adjustment of the setpoints Temperature Switch On (page 256) and Temperature Switch Off (page 257).
Note: Setpoints Temperature Switch On (page 256) and Temperature Switch Off (page 257) are
invisible until configuration of this LBO.
LBO: V
Ventilation
Related FW 1.0.0 Related applications AMF, MRS
Comm object 38
Description
This logical binary output is activated at the beginning of start procedure together with PRESTART (PAGE 531)
LBO. Ventilation output is deactivated when engine stops revolving.
Ventilation LBO is also deactivated immediately when EMERGENCY STOP (PAGE 479) (or E-Stop) is
For full list of Logical analog inputs go to the chapter Logical analog inputs alphabetically (page 542).
6 back to Controller
objects
LAI: A
AIN Switch 01
Related FW 1.0.0 Related applications AMF, MRS
Comm object 209
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 49. This analog input controls logical binary output AIN
SWITCH01 (PAGE 494). The behavior of the switch depends on the adjustment of the setpoints AIN
Switch01 On (page 310) and AIN Switch01 Off (page 311).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 04
Related FW 1.0.0 Related applications AMF, MRS
Comm object 212
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 49. This analog input controls logical binary output AIN
SWITCH04 (PAGE 495). The behavior of the switch depends on the adjustment of the setpoints AIN
Switch04 On (page 316) and AIN Switch04 Off (page 317).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 07
Related FW 1.0.0 Related applications AMF, MRS
Comm object 280
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 49. This analog input controls logical binary output AIN
SWITCH07 (PAGE 497). The behavior of the switch depends on the adjustment of the setpoints AIN
Switch07 On (page 322) and AIN Switch07 Off (page 323).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 10
Related FW 1.0.0 Related applications AMF, MRS
Comm object 283
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 49. This analog input controls logical binary output AIN
SWITCH10 (PAGE 498). The behavior of the switch depends on the adjustment of the setpoints AIN
Switch10 On (page 328) and AIN Switch10 Off (page 329).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
LAI: C
Coolant Temp
Related FW 1.0.0 Related applications AMF, MRS
Comm object 67
Description
Logical analog input designed for coolant temperature value received from analog sensor. For more
information about wiring of analog inputs see Analog inputs on page 49. Limits for this protection are
adjusted by setpoints Coolant Temperature Wrn (page 1) and Coolant Temperature Sd (page 1). Delay
is adjusted by setpoint Coolant Temperature Delay (page 1).
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn+Stp Analog value is used for warning and slow stop protection
Stp Analog value is used for slow stop protection
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Note: This analog function can by also configured on binary input as binary function. In this case chose
COOLANT TEMP (PAGE 476) binary input in the list of binary inputs. Delay of this binary input is adjusted
via the same setpoint like for analog function.
IMPORTANT: Value from analog input has higher priority than value from ECU.
LAI: F
Fuel Level
Related FW 1.0.0 Related applications AMF, MRS
Comm object 78
Description
Logical analog input designed for fuel level value received from analog sensor. For more information about wiring
of analog inputs see Analog inputs on page 49. Limits for this protection are adjusted by setpoints Fuel Level
Wrn (page 1) and Fuel Level Sd (page 1). Delay is adjusted by setpoint Fuel Level Delay (page 1).
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn+Stp Analog value is used for warning and slow stop protection
Stp Analog value is used for slow stop protection
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
IMPORTANT: For right behavior of this function, curve for analog input has to be in
percentage and setpoint Fuel Tank Volume (page 252) has to be adjusted correctly.
Note: This analog function can by also configured on binary input as binary function. In this case chose
FUEL LEVEL (PAGE 480) binary input in the list of binary inputs. Delay of this binary input is adjusted via
the same setpoint like for analog function.
IMPORTANT: Value from analog input has higher priority than value from ECU.
LAI: N
Not Used
Related FW 1.0.0 Related applications AMF, MRS
Comm object 230
Description
Input has no function.
LAI: O
Oil Pressure
Related FW 1.0.0 Related applications AMF, MRS
Comm object 9
Description
Logical analog input designed for oil pressure value received from analog sensor. Limits for this protection
are adjusted by setpoints Oil Pressure Wrn (page 1) and Oil Pressure Sd (page 1). Delay is adjusted by
setpoint Oil Pressure Delay (page 1).
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + Sd Analog value is used for warning and Sd protection.
Sd Analog value is used for Sd protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Note: This analog function can by also configured on binary input as binary function. In this case chose
OIL PRESSURE (PAGE 485) binary input in the list of binary inputs. Delay of this binary input is adjusted
via the same setpoint like for analog function.
IMPORTANT: Value from analog input has higher priority than value from ECU.
8.1.7 PLC
List of PLC groups
For full list of PLC blocks go to the chapter List of PLC blocks (page 551).
OR/AND
PLC group Basic logical functions
Related FW 1.0.0
Comm object 1
Inputs
Outputs
Description
The block performs logical operation OR / AND of 2 - 8 binary operands. The inputs as well as the output can be
inverted.
Function OR
Input 1 Input 2 Output
0 0 0
0 1 1
1 0 1
1 1 1
Function AND
Input 1 Input 2 Output
0 0 0
0 1 0
1 0 0
1 1 1
There have to be at least 2 inputs every time. There may be up to 8 inputs configured.
XOR/RS
PLC group Basic logical functions
Related FW 1.0.0
Related applications AMF, MRS
Comm object 2
Inputs
Outputs
Description
The block provides logical function of two values – XOR or RS flip-flop. Both inputs and output can be
inverted.
Function XOR
Input 1 Input 2 Output
0 0 0
0 1 1
1 0 1
1 1 0
Function RS
R S Qn+1
0 0 Qn
0 1 1
1 0 0
1 1 0
Outputs
Description
The block compares the input value with the comparative levels. The behavior depends on whether the ON
level is higher than OFF level or vice versa.
Note: Level On and Level Off can be constants or values from controller.
IMPORTANT: In case that values on inputs have different decimal numbers than the values
are converted and the name of block is red. It is strongly recommended to use values with
the same decimal numbers.
Outputs
Description
The block works as an analog switch. It compares the input value with the comparative level. The output will
switch on if the input is equal or higher than the comparative level for time longer than the delay.
Related FW 1.0.0
Comm object 14
Inputs
Outputs
Description
The block works as a countdown timer which is decreased by 1 every PLC cycle. The timer initial value is
adjustable by the "Reload value" input. The timer is automatically reloaded with the initial value when it
reaches zero or it can be reloaded in any other moment using the "reload" input. The timer is held at reload
value until the reload input is deactivated. The timer output is inverted always when the timer is reloaded.
Note: If you want the output to start at logical 0, tick First down option. Otherwise the output will start at
logical 1.
IMPORTANT: In case that inputs are not connected and First down option isn´t tick, than
output is active.
Delay
PLC group Time functions
Related FW 1.0.0
Related applications AMF, MRS
Comm object 33
Inputs
Outputs
Description
This block can work in two modes of operation:
Delay mode - the rising edge at the output is generated with delay of "input time up" when a rising
edge at the input is detected. The falling edge at the output is generated with delay of "input time
down" when a falling edge at the input is detected. If the delayed falling edge at the output came
earlier than the delayed rising edge, then no pulse would be generated at the output.
Pulse mode - a pulse of "input time up" length is generated at the output when a rising edge is
detected, a pulse of "input time down" length is generated at the output when a falling edge is
detected.
Note: If Input time up or Input time down value is <0, this input is internally set to zero.
Note: Input time up and Input time down values can be constants or values from controller.
Note: Use Pulse on edge option to choose between delay and pulse mode.
8.2 Alarms
What alarms are:
The controller evaluates two levels of alarms. For more information see Alarm management on page 136.
6 back to Alarms
Wrn Module: Slot 1
Alarm Type WRN
Alarmlist message Module: Slot 1
Alarm evaluated All the time
Related applications AMF, MRS
This alarm is issued if controller will not be able to communicate with preconfigured
Description module 1.
Note: This alarm has FPS – FIXED PROTECTIONS STATES 1 (PAGE 563).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 1 (PAGE 563).
Description
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Description
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Description
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Description
Note: Gen-set cannot be started until this alarm is inactive and reset.
Note: This alarm has FPS – FIXED PROTECTIONS STATES 1 (PAGE 563).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Wrn Overload
Alarm Type WRN
Alarmlist message Overload
Alarm evaluated All the time
Related applications AMF, MRS
The alarm is issued when the Gen-setmains power is over the limit for time period
longer than the delay. The following setpoints are related to it:
Overload Wrn (page 264) adjusts the overload limit.
Overload BOC (page 263) Overload Del adjusts the delay.
Description
Overload Wrn (page 1) adjusts the overload limit.
Overload MPRBOR (page 1)Overload MPRBOR (page 1) Overload Del
adjusts the delay.
Note: This alarm has FPS – FIXED PROTECTIONS STATES 4 (PAGE 566).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 5 (PAGE 567).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 5 (PAGE 567).
Wrn Al/Hist.msg. 2
Alarm Type WRN
Alarmlist message Al/Hist.msg. 2
Alarm evaluated All the time
Related applications AMF, MRS
Description This alarm is issued when history event 2 will trigger.
Wrn Al/Hist.msg. 7
Alarm Type WRN
Alarmlist message Al/Hist.msg. 7
Alarm evaluated All the time
Related applications AMF, MRS
Description This alarm is issued when history event 7 will trigger.
Wrn Al/Hist.msg. 12
Alarm Type WRN
Alarmlist message Al/Hist.msg. 12
Alarm evaluated All the time
Related applications AMF, MRS
Description This alarm is issued when history event 12 will trigger.
Description
Note: This alarm has FPS – FIXED PROTECTIONS STATES 4 (PAGE 566).
Description Voltage Unbalance BOC (page 270) adjusts the maximum allowed
difference between the highest and lowest phase voltage at any given time.
Voltage Unbalance BOC Delay (page 270) adjusts the alarm delay.
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Description Voltage Unbalance BOC (page 270) adjusts the maximum allowed
difference between the highest and lowest phase voltage at any given time.
Voltage Unbalance BOC Delay (page 270) adjusts the alarm delay.
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Description
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Description
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Wrn Maintenance 6
Alarm Type WRN
Alarmlist message Wrn Maintenance 6
Alarm evaluated All the time
Related applications AMF, MRS
Adjust the setpoint Maintenance Timer 6 (page 262) to the interval of the next
maintenance check. The value of the setpoint will count down while the engine is
running and if reaches zero, this alarm will be issued. The alarm message will
Description remain in the alarm list (even if the controller is switched off and on again) until the
setpoint is re-adjusted to a positive value.
Note: This alarm has FPS – FIXED PROTECTIONS STATES 5 (PAGE 567).
6 back to Alarms
Sd Module: Slot 1
Alarm Type SD
Alarmlist message Module: Slot 1
Alarm evaluated All the time
Related applications AMF, MRS
This alarm is issued if controller will not be able to communicate with preconfigured
Description module 1.
Note: This alarm has FPS – FIXED PROTECTIONS STATES 1 (PAGE 563).
Sd Module: Slot 4
Alarm Type SD
Alarmlist message Module: Slot 4
Alarm evaluated All the time
Related applications AMF, MRS
This alarm is issued if controller will not be able to communicate with preconfigured
Description module 4.
Note: This alarm has FPS – FIXED PROTECTIONS STATES 1 (PAGE 563).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 1 (PAGE 563).
Description
Note: This alarm has FPS – FIXED PROTECTIONS STATES 5 (PAGE 567).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 1 (PAGE 563).
Sd GCB Fail
Alarm Type SD
Alarmlist message Sd GCB Fail
Alarm evaluated All the time
Related applications AMF, MRS
This alarm will occur when the GCB FEEDBACK (PAGE 481) input does not match
the expected position given by the GCB CLOSE/OPEN (PAGE 511) output. It stays
active until the mismatch between the output and feedback persists.
If there was no command issued by the controller and the breaker
Description (feedback) changes suddenly the position itself, the alarm will be issued
immediately.
The alarm will be also issued if the breaker does not respond to an open or
close command within 2 seconds.
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Sd Generator L3 Overvoltage
Alarm Type SD
Alarmlist message Sd Generator L3 > Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
This alarm evaluates the generator phase voltage in phase 3. The following
setpoints are related to it:
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Description Voltage Unbalance BOC (page 270) adjusts the maximum allowed
difference between the highest and lowest phase voltage at any given time.
Voltage Unbalance BOC Delay (page 270) adjusts the alarm delay.
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Description Voltage Unbalance BOC (page 270) adjusts the maximum allowed
difference between the highest and lowest phase voltage at any given time.
Voltage Unbalance BOC Delay (page 270) adjusts the alarm delay.
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 2 (PAGE 564).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Mains L3 Overvoltage
Alarm Type ProtMP
Alarmlist message No
Alarm evaluated All the time
Related applications AMF, MRS
This alarm evaluates the Mains phase voltage in phases. The following setpoints
are related to it:
Mains Overvoltage (page 282)
Mains <> Voltage Delay (page 283)
Description
Note: Alarm is active only in case the setpoint Connection type (page 211) is
set to 3Ph4Wire.
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Mains Overfrequency
Alarm Type ProtMP
Alarmlist message No
Alarm evaluated All the time
Related applications AMF, MRS
This alarm evaluates the Mains phase voltage in phases 1. The following setpoints
are related to it:
Description
Mains Overfrequency (page 286)
Mains < > Frequency Delay (page 1)
Description Current Unbalance BOC (page 267) adjusts the maximum allowed
difference between the highest and lowest phase current at any given time.
Current Unbalance BOC Delay (page 267) adjusts the alarm delay.
Note: This alarm has FPS – FIXED PROTECTIONS STATES 3 (PAGE 565).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 4 (PAGE 566).
Description Short Circuit BOC (page 264) adjusts the short current limit
Short Circuit BOC Delay (page 265) adjusts the delay in fine steps
Note: This alarm has FPS – FIXED PROTECTIONS STATES 4 (PAGE 566).
Note: This alarm has FPS – FIXED PROTECTIONS STATES 4 (PAGE 566).
Sd Fence 1 Alarm
Alarm Type Shutdown
Alarmlist message Sd Fence 1 Alarm
Alarm evaluated All the time
Related applications AMF, MRS
This alarm evaluates the GPS position of gen-set. The following setpoint are
related to it:
Description Geo-Fencing (page 356)
Fence 1 Protection (page 358)
Fence Radius 1 (page 358)
Description
Note: This alarm has FPS – FIXED PROTECTIONS STATES 5 (PAGE 567).
6 back to Alarms
Fls AIN Prot 1
Alarm Type Fls
Alarmlist message Fls + name of analog input 1
Alarm evaluated All the time
Related applications AMF, MRS
This alarm indicates that the value of general analog protection is out of range or is
Description
missing.
8.3 Modules
8.3.1 Plug-in modules
IMPORTANT: 2nd generation of InteliLite 4 controllers does not support new modules and 3rd
generation does not support all old modules.
CM-Ethernet
CM-4G-GPS
CM-GPRS
CM-RS232-485
EM-BIO8-EFCP
Communication modules
CM-RS232-485 637
CM-Ethernet 639
CM-4G-GPS 641
CM-RS232-485
CM-RS232-485 is optional plug-in card to enable InteliLite 4 the RS232 and RS485 communication. This is
required for computer or Modbus connection. The CM-RS232-485 is a dual port module with RS232 and RS485
interfaces at independent COM channels. The RS232 is connected to COM1 and RS485 to COM2.
IMPORTANT: Any manipulation with plug-in module shall be done with disconnected power
supply to controller.
Note: Balancing resistors shall be both closed at only one device in whole RS485 network.
Maximal distance of line is 10 m for RS232 line and 1200 m for RS485 line.
Terminator 120 Ω
Balancing resistor +5 V
Technical data
40 mA / 8 VDC
26 mA / 12 VDC
Power consumption
14 mA / 24 VDC
10 mA / 36 VDC
Isolation Galvanic separation
Firmware upgrade
Download the newest FW of module from ComAp website (in form of PSI file or installation package)
Instal package to computer or open PSI to instal it into InteliConfig
Plug the module into the controller and power the controller on.
Open a connection with controller via InteliConfig
Go the menu Tools -> Firmware upgrade, select the Plug-in modules tab and select the appropriate firmware
you want to program into the module (in InteliConfig).
Press the OK button to start upgrade of firmware.
The firmware update process may be performed via any kind of connection including connection via the same
module in which the firmware is to be updated. The connection is reestablished again automatically when the
update process is finished.
CM-Ethernet
CM-Ethernet is a plug-in card with Ethernet 10/100 Mbit interface in RJ45 connector. It provides an interface for
connecting a PC with through ethernet/internet network, for sending active e-mails and for integration of the
controller into a building management (MODBUS TCP and SNMP protocols). This card also enables to monitor
and control the gen-set over web browser from any location with internet access using appropriate security
measures.
IMPORTANT: Any manipulation with plug-in module shall be done with disconnected power
supply to controller.
Use an Ethernet UTP cable with a RJ45 connector for linking the module with your Ethernet network. The
module can also be connected directly to a PC using cross-wired UTP cable.
Technical data
120 mA / 8 VDC
82 mA / 12 VDC
Power consumption
35 mA / 24 VDC
25 mA / 36 VDC
Module setup
All settings related to the module are to be adjusted via the controller setpoints. The respective setpoints are
located in the setpoint Group: CM-Ethernet (page 1).
All actual operational values like actual IP address etc. are available in controller values in a specific group as
well.
Status LED
Blinking frequency Color
Green – everything is OK
Red – some of following errors occurred:
1 Hz unplugged Ethernet cable
module cannot connect to AirGate
module can not obtain IP address from DHCP
Green – firmware is currently being programmed
10 Hz
Red – no firmware present in the module
Firmware upgrade
Download the newest FW of module from ComAp website (in form of PSI file or installation package)
Instal package to computer or open PSI to instal it into InteliConfig
Plug the module into the controller and power the controller on.
Open a connection with controller via InteliConfig
Go the menu Tools -> Firmware upgrade, select the Plug-in modules tab and select the appropriate firmware
you want to program into the module (in InteliConfig).
Press the OK button to start upgrade of firmware.
The firmware update process may be performed via any kind of connection including connection via the same
module in which the firmware is to be updated. The connection is reestablished again automatically when the
update process is finished.
CM-4G-GPS
CM-4G-GPS plug-in module containing a GPS receiver and GSM/WCDMA/LTE modem which can works in
two modes of operation based on the settings in the setpoint Internet Connection (page 361).
IMPORTANT: Any manipulation with plug-in module shall be done with disconnected power
supply to controller.
IMPORTANT: CM-4G-GPS and CM-GPRS modules cant be used in one controller in the same time.
Note: Cellular data service must be enabled in your SIM card by your mobile operator for successful operation.
Technical data
55 mA / 8 VDC
35 mA / 12 VDC
Power consumption
8 mA / 24 VDC
5 mA / 36 VDC
Note: Make sure that your SIM supports the packet data network type you want to use. – i.e. if you want to use
the module in LTE (4G) network you have to confirm with the operator that the particular SIM card supports 4G
network.
Contact your mobile operator for getting packet data APN (APN = Access Point Name), username and
password.
Example: APN Name = "internet", UserName = [blank], Password = [blank].
Make sure SIM card does not require PIN code. Use any mobile phone to switch the SIM PIN security off.
Place the SIM card into slot on CM-4G-GPS card
Connect the antenna to Cellular module antenna connector.
If you want to use the built-in GPS receiver connect also an active GPS antenna to the GPS antenna
connector.
Switch off the controller.
Insert CM-4G-GPS module into controller
Power up the controller.
Select the mode of CM-4G-GPS module by adjusting setpointModeInternet Connection (page 361).
Enter correct APN Name, APN User Name and APN User Password in controller’s setpoint group CM-4G-
GPS which is accessible by PAGE button from any measurement screen on controller. Setpoints can be set
on controller’s front panel keyboard or by InteliConfig.
Switch the controller off and on.
Wait for approx 2 - 4 minutes for first connection of the system to AirGate. AirGate will generate
automatically the AirGate ID value. Then navigate to measurement screens where you will find signal
strength bar and AirGate ID identifier.
GSM Diag Code – Common list of diagnostic codes for cellular modules
GSM Diag Code – Common list of diagnostic codes for cellular modules
Code Description
0 OK. No error.
1 Not possible to hang up.
2 Modul is switched off
3 Module is switched on
4 Module – error in initialization
5 Module – not possible to set the APN
6 Module – not possible to connect to GPRS network
7 Module – not possible to retrieve IP address
8 Module – not accepted DNS IP address
9 Error in modem detection
10 Error in initialization of analog modem
SIM card is locked (Possibly PIN code required, PIN needs to be deactivated) or unknown
11
status of SIM locking
12 No GSM signal
13 Not possible to read the SIM card parameters
GSM modem did not accepted particular initialization command, possibly caused by locked
14
SIM card
15 Unknown modem
16 Bad answer to complement initialization string
17 Not possible to read GSM signal strength
18 CDMA modem not detected
19 No CDMA network
20 Unsuccessful registration to CDMA network
21 SIMCom/ME909s: can´t read FW version
22 SIMCom: GSM signal not found
23 SIMCom: can´t detect module speed
Code Description
0 Waiting for connection to AirGate Server
1 Controller registered, waiting for authorization
2 Not possible to register, controller blacklisted
3 Not possible to register, server has no more capacity
4 Not possible to register, other reason
5 Controller registered and authorized
Firmware upgrade
Download the newest FW of module from ComAp website (in form of PSI file or installation package)
Instal package to computer or open PSI to instal it into InteliConfig
Plug the module into the controller and power the controller on.
Open a connection with controller via InteliConfig
Go the menu Tools -> Firmware upgrade, select the Plug-in modules tab and select the appropriate firmware
you want to program into the module (in InteliConfig).
Press the OK button to start upgrade of firmware.
The firmware update process may be performed via any kind of connection including connection via the same
module in which the firmware is to be updated. The connection is reestablished again automatically when the
update process is finished.
Extension modules
EM-BIO8-EFCP 645
EM-BIO8-EFCP
EM-BIO8-EFCP is optional plug-in card. Through this card controller can accommodate one AC current (CT)
measuring input (1A or 5A input) and up to 8 binary inputs or outputs. In InteliConfig PC configuration tool it is
possible to easily choose if particular I/O will be binary input or output.
IMPORTANT: Any manipulation with plug-in module shall be done with disconnected power
supply to controller.
Note: Current inputs are supported only in MRS 16 and AMF 25 controllers.
Note: Current inputs are supported only in MRS 16 and AMF 25 controllers.
Power supply
Power supply range 8-36 VDC
40 mA / 8 VDC
27 mA / 12 VDC
Power consumption
22 mA / 24 VDC
19 mA / 36 VDC
Binary inputs
Number Up to 8, non-isolated
Close/Open 0-2 VDC close contact
indication >6 VDC open contact
Binary outputs
Number Up to 8 , non-isolated
Max. current 0,5A
Switching to positive supply terminal
Firmware upgrade
Download the newest FW of module from ComAp website (in form of PSI file or installation package)
Instal package to computer or open PSI to instal it into InteliConfig
Plug the module into the controller and power the controller on.
Open a connection with controller via InteliConfig
Go the menu Tools -> Firmware upgrade, select the Plug-in modules tab and select the appropriate firmware
you want to program into the module (in InteliConfig).
Press the OK button to start upgrade of firmware.
The firmware update process may be performed via any kind of connection including connection via the same
module in which the firmware is to be updated. The connection is reestablished again automatically when the
update process is finished.
IMPORTANT: In slot 3, 4 and 5 CAN modules Inteli IO8/8 and Inteli IO16/0 are supported without
analog outputs. Analog outputs of these CAN modules are supported only in slot 1 and 2.
It is possible to add up to 80 binary inputs or up to 68 binary outputs or up to 32 analog inputs on CAN modules.
Extension modules
Inteli AIN8 649
Inteli IO8/8 654
IGS-PTM 661
Inteli AIN8TC 667
Inteli AIO9/1 671
IGL-RA15 676
Inteli AIN8
Inteli AIN8 module is extension module equipped with analog inputs. Inteli AIN8 module is connected to
controller by CAN1 bus.
Terminals
Analog inputs
8 channels
can be configured as:
resistor three wire input
current input
voltage input
All inputs can be configured to any logical function or protection.
IMPORTANT: Impulse input is not supported in controller.
Supported sensors
Sensors
User curves NI100 [°F] (fix) 0-5 V
PT100 [°C] (fix) NI1000 [°F] (fix) 0-10 V
PT1000 [°C] (fix) 4-20 mA passive
Sensors
NI100 [°C] (fix) 0-2400 Ω 4-20 mA active
NI1000 [°C] (fix) 0-10 kΩ 0-20 mA passive
PT100 [°F] (fix) ±1 V ±20 mA active
PT1000 [°F] (fix) 0-2.4 V
CAN address
DIP switch determinates CAN address for analog inputs.
Note: In case of setting the CAN address to zero, the appropriate group of signals is deactivated.
Programming firmware
Firmware upgrade process:
1. Disconnect all terminals from the unit.
2. Separate the top cover of module
3. Put the TEST jumper on a pins
4. Connect the unit with PC via RS232-null modem cable and AT-Link conv
9. Wait till process is done (If the process doesn't start – after 60 second the "Timeout" will be evaluated. In
this case please check:
You have proper connection with the unit
COM port selection is correct
Module has power supply, (no CAN bus connection, status LED lights continuously)
10. After successful programming disconnect AT-Link conv , remove TEST jumper and disconnect power
supply
11. Connect power supply again (status LED should blinking)
12. Module FW is upgraded
LED indication
Wiring
The following diagrams show the correct connection of sensors.
Terminator
Voltage sensor
Technical data
General data
Power supply 8 to 36 V DC
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Interface to controller CAN1
Protection IP20
Storage temperature -40 °C to +80 °C
Operating temperature -30 °C to +70 °C
Dimensions (WxHxD) 110 × 110 × 46 mm (4.3" × 4.3" × 1.8")
Weight 221.5 grams
Analog inputs
Number of channels 8
Range 0-10 V
Voltage
Accuracy: ±0.25 % of actual value + ±25 mV
Range: ±20 mA
Current
Accuracy: ±0.25 % of actual value + ±50 µA
Range: 0- 10 kΩ
Resistive
Accuracy: ±0.5 % of actual value + ±2 Ω
Inteli IO8/8
Inteli IO8/8 module is an extension module equipped with binary inputs, binary outputs and analog outputs.
Inteli IO8/8 is the name of the module, but it is possible to configure the module (by internal switch) to two
configurations:
Inteli IO8/8 – 8 binary inputs, 8 binary outputs and 2 analog outputs
Inteli IO16/0 – 16 binary inputs, 0 binary outputs and 2 analog outputs
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication speed
detection is done by reset of the module.
Terminals
Always all 8 inputs are configured to one type (HSS/LSS) together. All 8 outputs can be modified to inputs by
switch on the PCB ( Inteli IO8/8 to Inteli IO16/0).
Analog outputs
2 channels
can be configured as:
voltage 0-10V
current 0-20mA
PWM (level 5 V, with adjustable frequency from 200 Hz to 2400 Hz, with step 1 Hz)
All inputs/outputs can be configured to any logical function or protection.
CAN address
In Inteli IO8/8 mode CAN address for binary inputs is determined by DIP switch A, CAN address for binary
output and analog outputs is determined by DIP switch B.
In Inteli IO16/0 mode CAN address for binary inputs is determined by DIP switch A, first group of 8 input has
address A, second group of 8 inputs has address A+1. CAN address of analog outputs is set by DIP switch B.
Note: In case of setting the CAN address to zero, the appropriate group of signals is deactivated.
Programming firmware
Firmware upgrade process:
1. Disconnect all terminals from the unit.
2. Separate the top cover of module
3. Put the TEST jumper on a pins
4. Connect the unit with PC via RS232-null modem cable and AT-Link conv
LED indication
Binary input
Each binary input has LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Each binary output has LED which indicates output signal. Binary output LED is shining when binary output is
set. When this LED is shining, then module is configured as 8 binary inputs and 8 binary outputs. When this
LED is dark, then the module is configured as 16 binary inputs.
LED at power connector – status LED
Wiring
The following diagrams show the correct connection of inputs and outputs.
Binary inputs – pull up
There are two options of wiring. On upper picture you can see case when binary input is connected between
BIN2 and COM (COM is connected internally to the GND (-) – dashed line).
On lower picture is case of wiring between BIN2 and GND (-). Both ways are correct.
Binary inputs – pull down
There are two options of wiring. On upper picture you can see case when binary input is connected between
BIN2 and COM (COM is connected internally to the Ucc (+) – dashed line).
On lower picture is case of wiring between BIN2 and Ucc (+). Both ways are correct.
When high side setting of outputs is chosen – binary output must be connected to the minus potential directly
Terminal VHS (voltage High side) has to be connected to positive potential directly. Maximal current of each
binary output is 500 mA. Size of fuse depends on load.
Binary outputs – low side
When low side setting of outputs is chosen – binary output must be connected to the plus potential of power
supply directly. Minus potential is connected internally – dashed line.
Analog outputs
IMPORTANT: Terminator for analog output has special analog ground (AGND), which must not be
connected to the GND.
Technical data
General data
Power supply 8 to 36 V DC
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Interface to controller CAN1
Protection IP20
Storage temperature -40 °C to +80 °C
Analog outputs
Number of channels 2
Range 0-10 V
Voltage Accuracy: ±20 mV + ±0.5 % of actual value
Imax 5 mA
Range: 0-20 mA
Current Accuracy: ±100 µA + ±0.5 % of actual value
Rmax 500 Ω
Level 5 V
PWM Frequency – adjustable 200÷2400 Hz
Imax 20 mA
Binary inputs
Number of channels 8 for Inteli IO8/8, 16 for Inteli IO16/0
Input resistance 4400 Ω
Input range 0 to 36 V DC
Switching voltage level for open contact
0 to 2 V DC
indication
Max voltage level for close contact indication 6 to 36 V DC
Binary outputs
Number of channels 8 for Inteli IO8/8, 0 for Inteli IO16/0
Max current 500 mA
Max switching voltage 36 V DC
IGS-PTM
IGS-PTM module is extension module equipped with binary inputs, binary outputs, analog inputs and analog
output. IGS-PTM module is connected to controller by CAN1 bus.
Terminals
Analog inputs
Analog inputs can be configured for:
Resistance measurement
Current measurement
Voltage measurement
The type of analog inputs is configured via jumpers RUI located on lower PCB.
Supported sensors
Sensors
PT100 [°C] (fix) User curves
NI100 [°C] (fix) 0-100 mV
PT100 [°F] (fix) 0-2400 Ω
NI100 [°F] (fix) ±20 mA
CAN address
Controller type selection
The type of controller to be used with IGS-PTM must be selected via jumper labeled IGS accessible at the lower
PCB.
Address configuration
If InteliLite controller type is selected (by IGS jumper), address of IGS-PTM could be modified via jumpers
labeled ADR1 and ADR2.
ADR1 ADR2 ADR offset BIN module BOUT module AIN module
Open Open 0 (default) 1 1 1
Close Open 1 2 2 2
Open Close 2 3 3 3
Close Close 3 4 4 4
Programing firmware
Firmware upgrade is via AT-link (TTL). For programming is necessary to close jumper BOOT. RESET jumper is
used to reset the device. Close jumper to reset the device. For programming is used FlashProg PC tool.
LED indication
Binary input
Each binary input has LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Each binary output has LED which indicates output signal. Binary output LED is shining when binary output is
set.
LED at power connector – status LED
Wiring
Binary inputs
Binary outputs
Resistance sensor
Voltage sensor
IMPORTANT: Physical analog input range is 0-20 mA. In sensor configuration in PC tool it is
necessary to chose ±20 mA active sensor HW type to ensure proper function of analog input.
Analog outputs
Technical data
General data
Power supply 8 to 36 V DC
Current consumption 100 mA at 24V ÷ 500 mA
Interface to controller CAN1
Protection IP20
Storage temperature -40 °C to +80 °C
Operating temperature -30 °C to +70 °C
Dimensions (WxHxD) 95 × 96 × 43 mm (3.7" × 3.8" × 1.7")
Analog inputs
Number of channels 8
Range 0-100 mV
Voltage
Accuracy: 1.5 % ±1 mV out of measured value
Range: 0-20 mA
Current
Accuracy: 2.5 % ±0.5 Ω out of measured value
Range: 0-250 Ω
Resistive
Accuracy: 1 % ±2 Ω out of measured value
Analog outputs
Number of channels 1
Range: 0 to 20 mA ± 0.33 mA
Current
Resolution 10 bit
Binary inputs
Number of channels 8
Input resistance 4700 Ω
Input range 0 to 36 V DC
Switching voltage level for open contact
0 to 2 V DC
indication
Max voltage level for close contact indication 8 to 36 V DC
Binary outputs
Number of channels 8
Max current 500 mA
Max switching voltage 36 V DC
Number of channels 8
Range 0-100 mV
Voltage
Accuracy: 1.5 % ±.1 mV out of measured value
Range: 0-20 mA
Current
Accuracy: 2.5 % ± 0.5 Ω out of measured value
Range: 0-250 Ω
Resistive
Accuracy: 1 % ±2 Ω out of measured value
Inteli AIN8TC
Inteli AIN8TC module is extension module equipped with 8 analog inputs dedicated for thermocouple sensors
only.
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication speed
detection is done by reset of the module.
Terminals
Analog inputs
8 channels
can be configured as thermocouple sensors only
Supported sensors
Sensors
Thermocpl J [°C] (fix)
Thermocpl K [°C] (fix)
Thermocpl L [°C] (fix)
Thermocpl J [°F] (fix)
Thermocpl K [°F] (fix)
Thermocpl L [°F] (fix)
Thermocpl (nc) J [°C] (fix)
Note: "nc" means not cold junction compensation (by external sensor). In this case is used internal temperature
sensor on the PCB
LED indication
Wiring
Analog inputs
Terminator
Technical data
Power supply 8 to 36 V DC
Protection IP20
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Heat radiation 2W
Inteli AIO9/1
Inteli AIO9/1 module is extension module equipped with analog inputs and outputs – designed for DC
measurement.
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication speed
detection is done by reset of the module.
Terminals
Analog inputs
4 channels AIN1 – AIN4 can be configured as:
Sensor ±65V (it is determinated for measurement of battery voltage)
4 channels AIN5 – AIN8 can be configured as:
Thermocouples – type J,K or L (in °C or °F)
Sensor ±75mV DC – (for connecting current shunts)
1 channel AIN9 can be configured as:
RTD (Pt1000, Ni1000)
Common resistance 0-2400Ω
Analog outputs
1 channel AOUT1. Type of output:
0-10V DC
0-20mA
PWM (5 V, freq 2.4 Hz ÷2.4 kHz)
Analog output has 4-pins connector – GND and one pin for each type of output.
All analog inputs can be configured to any logical function or protection.
Supported sensors
Sensors
User curves
PT1000 [°C] (fix)
NI1000 [°C] (fix)
PT1000 [°F] (fix)
NI1000 [°F] (fix)
0-2400 Ω (fix linear)
±65 V DC (fix linear)
±75 mV (fix linear)
Thermocpl J [°C] (fix)
Thermocpl K [°C] (fix)
Thermocpl L [°C] (fix)
Thermocpl (nc) J [°C] (fix)
Thermocpl (nc) K [°C] (fix)
Thermocpl (nc) L [°C] (fix)
Thermocpl (nc) J [°F] (fix)
Thermocpl (nc) K [°F] (fix)
Thermocpl (nc) L [°F] (fix)
LED indication
Wiring
The following diagrams show the correct connection of sensors.
Technical data
Analog output
I 0-20mA /500Rmax. ± 1 % of actual value + ± 200 uA
U 0-10V ± 0.5 % of actual value + ± 50 mV
PWM – 5 V, 200 Hz-2.4kHz 15 mA max.
Galvanic separated from power supply
Galvanic separation CAN bus is galvanic separated from the measurement and power supply
Power supply 8 to 36 V DC
Protection IP20
Current consumption 150 mA at 24 V ÷ 400 mA at 8 V
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 80 °C
IGL-RA15
Remote annunciator (IGL-RA15) is designed as an extension signaling unit.
The unit is equipped with a fully configurable tri-color (red, orange, green) LED for intuitive operation
together with high functionality.
Terminals
Horn Horn
CAN CAN1 line
Power Power supply
CAN address
SW changing of CAN1 address is enabled only when both jumpers are closed. Any one of these addresses (1+2
or 3+4 or 5+6 or 7+8) can be set by following steps:
Switch to programming mode (Hold the Horn reset and Lamp test when unit is powering on). Status led is
yellow
LED indication
Each LED color is adjusted independently of controller output settings. If controller output 1 is set as "Common
Shutdown" it doesn’t mean red LED1 color for iGL-RA15. The LEDs color can be adjusted by following steps:
Switch to programming mode (Hold the Horn reset and Lamp test when unit is powering on). Status led is
yellow
Press Horn reset to change the LED1 color (green, yellow, red)
Press Lamp test to switch to the next LED color adjusting
Continue to adjust all LEDs color
After LED15 color adjusting press three times Lamp test
Note: If there is no operator action during address setting, color adjusting or timeout setting, the unit returns to
normal operation without changes saving.
Status LED
The signals LEDs are handled like binary outputs. It means all what can be configured to binary outputs can be
also configured to the LEDs of IGL-RA15.
Power LED
Horn setting
The horn output is activated if any of red or yellow LED is on. Output is on until pressing Horn reset or horn
timeout counts down. The timeout can by set by following steps:
Switch to programming mode (Hold the Horn reset and Lamp test when unit is powering on). Status led is
yellow
Press Lamp test fifteen times
Note: If there is no operator action during address setting, color adjusting or timeout setting, the unit returns to
normal operation without changes saving.
Wiring
* terminator resistor only when iGL-RA 15 is the last unit on the CAN1 bus.
Note: The shielding of the CAN bus cable has to be grounded at one point only!
Note: See the section Technical data (page 200) for recommended CAN bus cable type.
Technical data
General data
Power supply 8 to 36 V DC
Current consumption 0.35-0.1A (+1Amax horn output) depends on supply voltage
Protection IP65
Humidity 85%
Storage temperature -30 °C to +80 °C
Operating temperature -20 °C to +70 °C
Dimensions (WxHxD) 180 × 120 × 55 mm
Weight 950 g
Horn output
Maximum current 1.0 A
Maximum switching voltage 36 V DC
6 back to Appendix