Unidrive SP size 4 EMC Data Sheet issue 1
Unidrive SP size 4 EMC Data Sheet issue 1
doc
UNIDRIVE SP SIZE 4 (15 to 55 kW)
ELECTROMAGNETIC COMPATIBILITY DATA
Note on issue 1
The following changes have been made from the provisional data sheet:
Additional EMC immunity tests on Secure Disable, also relevant to EN 12016:2004 (lifts and escalators)
Harmonics data for 200V and 600V versions
Information on supply harmonics related to EN 61000-3-12 and EN 12015:2004 (lifts and escalators)
IMMUNITY
The drive complies with the following international and European harmonised standards for immunity:
CH
23/06/06 1/17 Issue 1
UNISP4EMCi1.doc
Unless stated otherwise, immunity is achieved without any additional measures such as filters or suppressors. To
ensure correct operation the wiring guidelines specified in the User Guide must be carefully adhered to. All
inductive components such as relays, contactors, electromagnetic brakes etc. associated with the drive must be
fitted with appropriate suppression, otherwise the immunity capability of the drive may be exceeded.
Surge immunity of control circuits – long cables and connections outside a building
The input/output ports for the control circuits are designed for general use within machines and small systems
without any special precautions.
These circuits meet the requirements of EN 61000-6-2 (1kV surge) provided the 0V connection is not earthed, i.e.
in the common mode. Generally they cannot withstand the surge directly between the control lines and the 0V
connection, i.e. in the series mode.
The surge test simulates the effect of lightning or severe electrical faults in a physically extended electrical system,
where high differential transient voltages may appear between different points in the grounding system. This is a
particular risk where the circuits extend outside the protection of a building, or if the grounding system in a large
building is not well bonded.
In applications where control circuits may be exposed to high-energy voltage surges, some special measures may
be required to prevent malfunction or damage. As a general rule, if the circuits are to pass outside the building
where the drive is located, or if wiring runs within a building exceed 30m, some additional precautions are
advisable. One of the following techniques should be used:
1. Galvanic isolation, i.e. do not connect the control 0V terminal to ground. Avoid loops in the control wiring, i.e.
ensure every control wire is accompanied by its associated return (0V) wire.
2. Screened cable with additional power ground bonding. If isolation at one end is not acceptable, the cable
screen may be connected to ground at both ends, but in addition the ground conductors at both ends of the
cable must be bonded together by a power ground cable (equipotential bonding cable) with cross-sectional
area of at least 10mm2, or 10 times the area of the signal cable screen, or to suit the electrical safety
requirements of the plant. This ensures that fault or surge current passes mainly through the ground cable and
not in the signal cable screen. If the building or plant has a well-designed common bonded network this
precaution is not necessary.
3. Additional over-voltage suppression – for the analogue and digital inputs and outputs, a zener diode network or
a commercially available surge suppressor may be connected in parallel with the input circuit as shown in
Figures 1 and 2.
Signal from plant Signal to drive
+
0V 0V
Figure 1: surge suppression for digital and unipolar analogue inputs and outputs
CH
23/06/06 2/17 Issue 1
UNISP4EMCi1.doc
Signal from plant Signal to drive
0V 0V
Surge suppression devices are available as rail-mounting modules, e.g. from Phoenix Contact GmbH:
Unipolar TT-UKK5-D/24 DC
Bipolar TT-UKK5-D/24 AC
These devices are not suitable for encoder signals or fast digital data networks because the capacitance of the
diodes adversely affects the signal. Most encoders have galvanic isolation of the signal circuit from the motor
frame, in which case no precautions are required. For data networks, follow the specific recommendations for the
particular network.
EMISSION
Emission occurs over a wide range of frequencies. The effects are divided into three main categories:
− Low frequency effects, such as supply harmonics and notching.
− High frequency emission below 30MHz where emission is predominantly by conduction.
− High frequency emission above 30MHz where emission is predominantly by radiation.
SUPPLY HARMONICS
The input current contains harmonics of the supply frequency. The harmonic current levels are affected to some
extent by the supply impedance (fault current level). The table shows the levels calculated with fault level of 10kA.
This would be typical of a light industrial installation. This meets and exceeds the requirements of IEC 61800-3. For
installations where the fault level is lower, so that the harmonic current is more critical, the harmonic current will
also be lower than that shown.
The calculations have been verified by laboratory measurements on sample drives.
Note that the RMS current in these tables may differ from the maximum specified in the installation guide, since the
latter is a worst-case value provided for safety reasons which takes account of permitted supply voltage imbalance.
The motor efficiency also affects the current, a standard Eff2 4-pole motor has been assumed.
For balanced sinusoidal supplies, all even and triplen harmonics are absent.
The supply voltages for the calculations were 200V, 400V and 690V at 50Hz. The harmonic percentages do not
change substantially for other voltages and frequencies within the drive specification. In particular, the values for
480V 60Hz are very close to those for 400V 50Hz.
This table covers operation in both standard and heavy-duty (shown grey) modes.
CH
23/06/06 3/17 Issue 1
UNISP4EMCi1.doc
CH
23/06/06 4/17 Issue 1
UNISP4EMCi1.doc
Input line reactors (line chokes)
Where necessary, a reduction in harmonic current levels can be obtained by fitting reactors in the input supply lines
to the drive. This also gives increased immunity from supply disturbances such as voltage surges caused by the
switching of high-current loads or power-factor correction capacitors on the same supply circuit. The following table
shows the corresponding harmonics where reactors of approximately 4% are fitted in the supply lines. These
values cause a reduction of up to 3% in the d.c. link voltage, which will normally still permit the full rated torque to
be developed in a standard motor. Higher values should not be used unless some reduction of available torque at
maximum speed is acceptable. Lower values can be used, and the resulting harmonic currents can be estimated
by linear interpolation between the values for no reactor and 4% reactor. Reactor current ratings must be at least
equal to the RMS values shown, and peak current rating (to avoid magnetic saturation) should be twice that value.
The above harmonic currents meet the requirements of (draft) IEC 61000-3-12 Table 4 for RSCE≥120. The minimum
line reactor values required to meet this standard are given below:
Voltage Motor power (kW) Inductance (µH) Voltage Motor power Inductance (µH)
(kW)
220 15 150 220 18.5 80
220 22 50 220 30 0
400 30 0 400 37 500
400 45 315 400 55 0
690 15 2000 690 18.5 1400
690 22 1000 690 30 600
690 37 400 690 45 300
690 55 0
The line reactor values shown for 400V models correspond to Control Techniques stock items as follows:
Inductance (µH) Rated current Part number
(A)
500 60 4401-0169
315 96 4401-0171
CH
23/06/06 5/17 Issue 1
UNISP4EMCi1.doc
Input line reactors for compliance with EN 12015:2004 (EMC standard for lifts and escalators) and IEC
61000-3-4 for RSCE ≥ 250
These standards have a number of requirements for harmonic emission, of which the controlling factor is a
requirement for fifth harmonic current less than 30% of the fundamental. This can be achieved by using a high
value of line reactance.
Note that this value of reactor will only give the required harmonic reduction effect if the load is equal to or greater
than that stated. If the rated load is less than this then the inductance must be increased in inverse proportion. The
high value required means that the drive d.c. bus voltage is reduced by about 5%. Depending on the motor voltage
rating, this may mean that the available torque at base speed is reduced.
Harmonics (%)
5 7 11 13 17 19 23 25
27.6 7.8 6.1 3.6 2.2 1.9 1.0 0.9
29 31 35 37 41 43 47 49
0.6 0.5 0.5 0.4 0.4 0.3 0.2 0.2
Note that the input current of the drive, including the harmonic content, is determined by the output power, i.e. the
product of torque and speed. For a system of drives it is often the case that there is diversity of loading, i.e. the
drives never deliver full rated power simultaneously. This should be allowed for in estimating the total harmonic
current.
Some special series-connected harmonic filters are offered for use specifically with variable speed a.c. drives.
Although these can be effective they may disturb the operation of the drive inrush current control system. Please
consult the drive supplier before considering the use of such a filter.
CH
23/06/06 6/17 Issue 1
UNISP4EMCi1.doc
CONDUCTED RADIO FREQUENCY EMISSION
Radio frequency emission in the range from 150kHz to 30MHz is generated by the switching action of the main
power devices (IGBTs) and is mainly conducted out of the equipment through electrical power wiring. It is
essential for compliance with the emission standards that the recommended filter and a shielded (screened) motor
cable should be used. Most types of cable can be used provided it has an overall screen, which is continuous for
its entire length. For example the screen formed by the armouring of steel wire armoured cable is acceptable. The
capacitance of the cable forms a load on the drive and filter, and should be kept to a minimum. Compliance tests
were done with cable having a capacitance between the three power cores and the screen of 412pF per metre
(measured at 1kHz), which is typical of steel wire armoured cable. In addition to motor cable length, conducted
emission will also vary with drive switching frequency: selecting the lowest switching frequency will produce the
lowest level of emission. In order to meet the stated standards the drive, filter and motor cable must be installed
correctly. Wiring guidelines are given later.
The drive contains a cost-effective internal input filter which gives a reduction of about 30dB in the level of emission
at the supply terminals. Unlike a conventional filter, the internal filter continues to provide this attenuation with a
long motor cable. For practical purposes, this filter in conjunction with a screened motor cable is sufficient to
prevent the drive from causing interference to most good-quality industrial equipment. It is recommended that the
filter be used in any situation unless the earth leakage current , which is up to 56mA, is unacceptable. The User
Guide gives instructions on how to remove and replace it.
For applications where there are stricter requirements for radio frequency emission, e.g. to the generic standards
EN 61000-6-4 etc. or unrestricted distribution in EN 61800-3, the optional external filter must be used.
CH
23/06/06 7/17 Issue 1
UNISP4EMCi1.doc
Key to tables
The requirements are listed in descending order of severity, so that if a particular requirement is met then all
requirements listed after it are also met.
Code Standard Description Frequency Limits Application
range
I EN 61000-6-4 Industrial: 0.15 – 0.5MHz 79dBµV quasi AC supply
IEC 61000-6-4 Generic emission peak lines
EN 50081-2 standard for the 66dBµV average
industrial 0.5 –30MHz 73dBµV quasi
environment peak
60dBµV average
EN 61800-3 Product standard for - Requirements for the first environment1: restricted
IEC 61800-3 adjustable speed distribution2
power drive systems
E2U EN 61800-3 Product standard for - Requirements for the second environment:
IEC 61800-3 adjustable speed unrestricted distribution
power drive systems
E2R EN 61800-3 Product standard for - Requirements for the second environment:
IEC 61800-3 adjustable speed restricted distribution
power drive systems
1
The first environment is one where the low voltage supply network also supplies domestic
premises
2
When distribution is restricted, drives are available only to installers with EMC competence
- Caution -
This caution applies where the drive is used in the first environment with restricted distribution according to EN
61800-3.
This is a product of the restricted distribution class according to IEC 61800-3. In a domestic environment this
product may cause radio interference in which case the user may be required to take adequate measures.
Notes
1. Where the drive is incorporated into a system with rated input current exceeding 100A, the higher emission
limits of EN 61800-3 for the second environment are applicable, and no filter is then required.
2. Operation without a filter is a practical cost-effective possibility in an industrial installation where existing levels
of electrical noise are likely to be high, and any electronic equipment in operation has been designed for such
an environment. This is in accordance with EN 61800-3 in the second environment, with restricted distribution.
There is some risk of disturbance to other equipment, and in this case the user and supplier of the drive
system must jointly take responsibility for correcting any problem which occurs.
Recommended filters
Control Techniques part number
Drive Manufacturer Schaffner Manufacturer Epcos
4201 - 4203 4200-6406 4200-6405
4401 - 4403
4601 - 4606 4200-6408 4200-6407
- WARNING -
These filters and the internal filter have earth leakage current exceeding 3.5mA. A permanent fixed earth
connection with cross-section exceeding 10mm2 is necessary to avoid electrical shock hazard.
CH
23/06/06 8/17 Issue 1
UNISP4EMCi1.doc
- Caution -
Neither the internal nor external filters must be used with an IT supply unless an earth leakage relay is fitted
between the filter and drive, arranged to trip the drive in the event of excessive earth leakage current caused by a
motor earth fault. Typical relay setting is 150mA.
RADIATED EMISSION
When installed in a standard metal enclosure according to the wiring guidelines, the drive will meet the radiated
emission limits required by the generic industrial emission standard EN 61000-6-4 (previously EN 50081-2).
Important note
Compliance was achieved in tests using representative enclosures and following the guidelines given. No special
EMC techniques were used beyond those described here. Every effort was made to ensure that the arrangements
were robust enough to be effective despite the normal variations which will occur in practical installations.
However no warranty is given that installations built according to these guidelines will necessarily meet the same
emission limits.
The limits for emission required by the generic emission standards are summarised in the following table:
EN 61800-3 (IEC 61800-3) requires the following, in order of increasing emission level:
As EN 61000-6-3 First environment - unrestricted distribution
As EN 61000-6-4 First environment - restricted distribution
30 – 230MHz 40dBµV/m at 30m Second environment – unrestricted distribution
230 – 1000MHz 50dBµV/m at 30m
CH
23/06/06 9/17 Issue 1
UNISP4EMCi1.doc
Test Data
The test data is based on radiated emission measurements made in a standard steel enclosure containing a single
SP4402 drive, in a calibrated open area test site. Details of the test arrangement are described:
A standard Rittall steel enclosure was used having dimensions 1900mm (high) × 600mm (wide) × 500mm
(deep). Two ventilation grilles, both 200mm square, were provided on the upper and lower faces of the door.
No special EMC features were incorporated.
The drive and recommended RFI input filter were fitted to the internal back-plate of the enclosure, the filter
casing making electrical contact with the back-plate by the fixing screws. Standard unscreened power cable
was used to connect the cubicle to the supply.
A standard 11kW AC induction motor was connected by 3m of shielded cable (steel braided - type SY) and
mounted externally. The cable screen was clamped directly to the back-plate near the drive, and connected
to the motor frame by a pig-tail approximately 50mm long. In order to allow for realistic imperfections in the
installation, the motor cable was interrupted by a DIN rail terminal block mounted in the enclosure. The
screen pigtails (50mm long) were connected to the back plate through an earthed DIN rail terminal block.
The motor cable screen was not bonded to the enclosure wall at the point of entry.
A 2m screened control cable was connected to the drive control terminals, and its screen clamped to the
drive EMC grounding bracket as recommended in the user guide, but the screen was not allowed to contact
the cubicle wall.
The drive was operated at 6Hz, with a switching frequency of 8kHz which is the worst case for RF emission.
No additional EMC preventative measures were taken, e.g. RFI gaskets around the cubicle doors.
The following table summarises the results for radiated emission, showing the six highest measurements over the
frequency range 30 to 1000 MHz:
The results show that the limit for the industrial emission standard is met with a margin of at least 4dB.
The limit for EN 61800-3 (IEC 61800-3) is met for the first environment with restricted distribution, and for the
second environment without restriction.
Enclosure construction
For most installations the enclosure will have a back-plate which will be used to mount variable speed drive
modules, RFI filters and ancillary equipment. This back-plate can be used as the EMC earth plane, so that all metal
parts of these items and cable screens are fixed directly to it. Its surface should have a conductive protective
surface treatment such as zinc plate. If it is painted then paint will have to be removed at the points of contact to
ensure a low-inductance earth connection which is effective at high frequency.
The motor cable screen must be clamped directly to the back-plate. It may also be bonded at the point of exit,
through the normal gland fixings.
Depending on construction, the enclosure wall used for cable entry might have separate panels and have a poor
connection with the remaining structure at high frequencies. If the motor cable is only bonded to these surfaces
and not to a back-plate, then the enclosure may provide insufficient attenuation of RF emission.
It is the bonding to a common metal plate which minimises radiated emission. There is no need for a special EMC
enclosure with gaskets etc. In the tests described, opening the cubicle door had little effect on the emission level,
showing that the enclosure itself does not provide significant screening.
CH
23/06/06 10/17 Issue 1
UNISP4EMCi1.doc
Related product standards
The radiated emission levels specified in EN 61000-6-4 are equivalent to the levels required by the following
product standards:
CH
23/06/06 11/17 Issue 1
UNISP4EMCi1.doc
WIRING GUIDELINES
The wiring guidelines on the following pages should be observed to achieve minimum radio frequency emission.
The details of individual installations may vary, but aspects which are indicated in the guidelines as important for
EMC must be adhered to closely.
The guidelines do not preclude the application of more extensive measures which may be preferred by some
installers. For example, the use of full 360° ground terminations on shielded cables in the place of ‘pig-tail’ ground
connections is beneficial, but is not necessary unless specifically stated in the instructions.
1. The drive and filter must be mounted on the same metal back-plate, and their mounting surfaces must make a
good direct electrical connection to it. The use of a plain metal back-plate (eg galvanised not painted) is
beneficial for ensuring this without having to scrape off paint and other insulating finishes.
2. The filter must be mounted above and close to the drive but allowing a space of 100mm as advised in the user
guide, to allow free exit of cooling air from the drive.
3. A shielded (screened) or steel wire armoured cable must be used to connect the drive to the motor. The shield
must be fixed in direct contact with the metal back-plate of the panel by a suitable clamp.
4. The AC supply connections must be kept at least 4in (100mm) from the drive, motor cable and braking resistor
cable.
100mm (4in)
100mm
(4in)
Ensure direct
metal contact
at drive and
filter mounting
points (any
paint must be
removed).
Figure 3: Grounding the drive, filter and motor cable screen Figure 4: Input wiring spacing
5. Connect the shield of the motor cable to the ground terminal of the motor frame using a link that is as short as
possible and not exceeding 50mm (2 in) in length. A full 360° termination of the shield to the motor terminal
housing (if metal) is beneficial.
CH
23/06/06 12/17 Issue 1
UNISP4EMCi1.doc
6. If an additional safety earth wire is required for the motor, it can either be carried inside or outside the motor
cable shield. If it is carried inside then it must be terminated at both ends as close as possible to the point
where the screen is terminated. It must always return to the drive and not to any other earth circuit.
7. Wiring to the braking resistor should be shielded. The shield must be bonded to the back-plate using an
uninsulated metal cable-clamp. It need only be connected at the drive end.
8. If the braking resistor is outside the enclosure then it should be surrounded by an earthed metal shield.
Enclosure Enclosure
OR
+DC BR +DC BR
Optional external
braking resistor
Optional external
braking resistor
9. Signal and control wiring must be kept at least 12in (300mm) from the drive and motor cable.
CH
23/06/06 13/17 Issue 1
UNISP4EMCi1.doc
≥300mm
(12in)
Sensitive
signal
cable
10. The control wiring “0V” connection should be earthed at one point only, preferably at the controller and not at a
drive.
• Use shielded cables (one overall shield or separate shielded cables) and clamp the shield(s) to the grounding
bracket provided, as shown in Figure 8.
CH
23/06/06 14/17 Issue 1
UNISP4EMCi1.doc
or:
• Pass the control wires through a ferrite ring part number 3225-1004. More than one cable can pass through a
ring. Ensure the length of cable between the ring and drive does not exceed 125mm (5in).
CH
23/06/06 15/17 Issue 1
UNISP4EMCi1.doc
Back-plate
Enclosure
To the motor
Isolator
(If required)
CH
23/06/06 16/17 Issue 1
UNISP4EMCi1.doc
Figure 11: Example conducted emission plot (SP4403, 100m cable, 3kHz switching frequency)
CH
23/06/06 17/17 Issue 1