DB Check List

The document is a quality inspection checklist for the electrical panel inspection at the Jockey Garments Factory in Odisha, executed by Blue Star Ltd. It includes a series of items to be inspected, such as general safety, earthing, insulation resistance, and functionality tests of various electrical components. The checklist is designed to ensure compliance with safety standards and proper functioning of the electrical distribution board before commissioning.

Uploaded by

dibyendu3384
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views

DB Check List

The document is a quality inspection checklist for the electrical panel inspection at the Jockey Garments Factory in Odisha, executed by Blue Star Ltd. It includes a series of items to be inspected, such as general safety, earthing, insulation resistance, and functionality tests of various electrical components. The checklist is designed to ensure compliance with safety standards and proper functioning of the electrical distribution board before commissioning.

Uploaded by

dibyendu3384
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

QUALITY INSPECTION CHECKLIST FOR ELECTRICAL PANEL INSPECTION

Project: Jockey Garments Factory at Odisha at Odisha Date:


Executed By - Blue Star Ltd. Location:
Item of Work: DB Pre-commissioning check list
SL.No Item description YES NO NA Remarks/ Corrective Action

PANEL NAME- Location-

General Inspection
1 Drawing - SLD, DB Scheduling shall be Kept inside the DB Pocket.
2 No visible damage to impair safety.
3 Proper Tagging & Labelling
4 All live parts screened with an insulating plate or earthed metal.
5 Phase identification provided on the distribution board
6 All exposed metal parts effectively earthed.
All metal conduits, trunking, switch boxes and exposed metal parts effectively
7 earthed.
All non-armored cables susceptible to damage protected with steel conduit/
8 trunking. Bushing and rubber grommet, where necessary, provided
9 Conductor sized to suit the rating of the FUSE / MCB protecting the circuit.
All joints of metal conduits or trunking to be mechanically sound, electrically
10 continuous and protected against corrosion.
11 All exposed conductive parts effectively earthed.
12 Panel Door Earthing Shall be done.
T&C
13 DB Incoming Cable Tagging shall be done.
Insulation resistance of not less than 0.5 M ohm measured between
14 phases/neutral/ earth.
Busbar IR Value test

N-E = R-E= Y-E= B-E= R-N= Y-N=


IR
VALUE
B-N= R-Y= B-Y= B-R=

I/C Cable IR Value test

N-E = R-E= Y-E= B-E= R-N= Y-N=


IR
VALUE
B-N= R-Y= B-Y= B-R=

15 Checking of Voltage on O/G Power Circuit


16 Checking of Phase Sequence.
17 Checking of (MCCB's) ON/OFF and Manual Trip Test
18 Checking of ELCB/RCCB/RCD

Signature(BSL Site Engg) Signature(BSL QC) Signature(PIL)


Name :- Name :-
Name :- Name :-
Date:- Date:-