Que2. A single phase TL has copper conductor of 0.775 cm2 cross section through which
200 kW at UPF at 330 V is to be maintained. If the efficiency of transmission line is 90%,
then the minimum length of TL is ___________(in km and take specific resistance to be
1.785 μΩ/cm).
a) 13.6 km
b) 14 km
c) 136 km
d) 16.4 km
Que3. A three phase transformer has a nameplate rating of 30 MVA, 230Y/69Y kV with a
leakage -reactance of 10% and the transformer connection is wye-wye. Choosing a base of
30MVA and 230 kV on high voltage side, the reactance of transformer in per units is
__________
a) 0.1
b) 0.3
c) 0.03
d) 1.5
Que.5 A three phase transformer has a nameplate rating of 30 MVA, 230Y/69Y kV with a
leakage -reactance of 10% and the transformer connection is wye-wye. Choosing a base of
30MVA and 230 kV on high voltage side, the low voltage side impedance is ___________
a) 158.7 Ω
b) 176.3 Ω
c) 1763.3 Ω
d) 15.87 Ω
Que.6. What is the per unit impedance Z(Pu) in a three phase system?
a. ( Z * (MVA)B) / (KV)2
b. ( 1000 * (KV)B) / √3 IB
c. ( Z * (KV)2 ) / (MVA)B
d. None of these
Que.7 Which among the following assumptions are made in the reactance
diagram?
Que. 8. What will be the per unit impedance of a synchronous motor having
a rating of 100 kVA, 13.2 kV and having a reactance of 75 Ω / ph?
a. 0.043 pu
b. 0.057 pu
c. 0.036 pu
d. 0.298 pu
a. Per unit impedance of transformers is the same referred to either side of it.
b. For simulating steady state and transient models in the computer this method is very
useful.
c. Manufactures usually specify the impedance of an apparatus in per unit system.
d. All of these
a. A ratio of actual value in any units to the base or reference value in the same units
b. A ratio of the base or reference value in any units to the actual value in the same
units.
c. Ratio of the square of the actual value in any units to the square of base or the
reference value in the same units
d. All of these
a. 10/ Ö 3 %
b. 10Ö 3 %
c. 10 %
Que.20. The percentage reactance can be converted into ohmic value with the following
formula
a. X(ohms)=X(%)*100*kV2 /kVA
b. X(ohms)=X(%)*1000*kV2 /kVA
c. X(ohms)=X(%)*kV2 /(1000*kVA)
d. None of these
Que.21. How many independent base quantities could there be in a power system?
They could be two. Usually, base VA (or MVAb), and base voltage (or kVb).
Sd1=15+j5 pu
Sd2=25+j15 pu
Zcable = j0.05pu
|V1|=|V2|=1 pu. The torue angle for the system will be __________
a) 14.4
b) 22.1
c) 16.2
d) 18.2
Que.34.