Flygt SmartRun Tech Spec

The SRC 311 Technical Specification outlines the operational environment, input voltage requirements, and maximum supply ratings for various models. It includes detailed tables for output power and current ratings, dimensions, torque values, and mounting clearances. Additionally, it provides information on control terminals, communication options, and recommendations for cable usage to ensure optimal performance and compliance.

Uploaded by

Armando Guzmán
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views

Flygt SmartRun Tech Spec

The SRC 311 Technical Specification outlines the operational environment, input voltage requirements, and maximum supply ratings for various models. It includes detailed tables for output power and current ratings, dimensions, torque values, and mounting clearances. Additionally, it provides information on control terminals, communication options, and recommendations for cable usage to ensure optimal performance and compliance.

Uploaded by

Armando Guzmán
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Technical

Specification

SRC 311
Technical Specification

Technical Specification
Environment
Ambient temperature
Activity °C (°F)
Operation -10 – 40 (14 – 104)
Operation (de-rated) maximum 50 (122)
Storage -40 – 60 (-40 – 140)

Altitude
Maximum altitude for de-rated operation is 1000 m (3281 ft).
De-rating above 1000 m (3281 ft) is 1% per 100 m (32.8 ft).
Maximum altitude with UL approval is 2000 m (6562 ft)
Maximum altitude without UL approval is 4000 m (13123 ft)
Humidity
The relative humidity must not exeed 95% (non condensing)

Input voltage
Model Number Supply Voltage Phases Frequency (Hz) Maximum phase
imbalance
SRC311-X-X-XXXXX-XX 200 – 240 V +10/-15% 1 50, 60 3%
3
380 – 480 V +10/-15% 3

Depending upon the model and power rating, the drives are designed for direct
connection to the following supplies
For input supplies which have supply imbalance greater than 3% an input line reactor is
recommended. Alternatively, the drives can be operated as a single phase supply drive
with 50% de-rating.

Maximum supply ratings for UL- compliance


The table describe the drivers suitable for a circuit capable of delivering specified
maximum specified short-circuit Amperes symmetrical with the specified maximum supply
voltage.
Table 1: Drive ratings

Voltage (V) Ratings kW (HP) Maximum supply voltage Vrms Maximum supply short-circuit
(AC) current Arms (AC)
230 0.37 – 18.5 (0.5 – 25.0) 240 5
22.0 – 90.0 (30.0 – 120.0) 10
400/460 0.75 – 37.0 (1.0 – 50.0) 500/600 5
45.0 – 132.0 (60.0 – 175.0) 10
160.0 (210.0) 18

SRC 311 Technical Specification 3


Technical Specification

Output power and current ratings


IP66
Table 2: 200 – 240 V (+ / -10%) 3–phase input, 3–phase output

kW HP Frame Size Nominal Fuse/MCB, Supply Nominal 110% Motor cable


Input type B) (A) cable (mm2) Output Output
Current (A) Current (A) Current 60 mm2 AWG
seconds (A)
4.0 5.0 3 17.3 32 6.0 18.0 19.80 2.5 12

Table 3: 380 – 480 V (+ / -10%) 3–phase input, 3–phase output

kW HP Frame Size Nominal Fuse/MCB, Supply Nominal 110% Motor cable


Input type B) (A) cable (mm2) Output Output
Current (A) Current (A) Current 60 mm2 AWG
seconds (A)
4.0 5.0 2 10.8 16 2.5 9.5 10.45 1.5 12
5.5 7.5 3 13.3 20 2.5 14.0 15.40 2.5 12
7.5 10.0 3 18.5 20 4.0 18.0 19.80 2.5 10

IP55
Table 4: 200 – 240 V (+ / -10%) 3–phase input, 3–phase output

kW HP Frame Size Nominal Fuse/MCB, Supply Nominal 110% Motor cable


Input type B) (A) cable (mm2) Output Output
Current (A) Current (A) Current 60 mm2 AWG
seconds (A)
5.5 7.5 4 25.0 40 6.0 24.0 26.40 4.0 10
7.5 10.0 4 46.6 50 10.0 39.0 42.9 6.0 8.0
11.0 15.0 4 54.1 63 16.0 46.0 50.6 10.0 6.0
15.0 20.0 5 69.6 80 25.0 61.0 67.1 16.0 4.0
18.5 25 5 76.9 80 25.0 72 79.2 16.0 4.0
22.0 30.0 6 92.3 100 35.0 90.0 99.0 25.0 2.0
30.0 40.0 6 116.9 125 50.0 110.0 121.0 25.0 1/0
37.0 50.0 6 150.2 160 70.0 150.0 165.0 35.0 2/0

Table 5: 380 – 480 V (+ / -10%) 3–phase input, 3–phase output

kW HP Frame Size Nominal Fuse/MCB, Supply Nominal 110% Motor cable


Input type B) (A) cable (mm2) Output Output
Current (A) Current (A) Current 60 mm2 AWG
seconds (A)
15.0 20 4 32.9 50 6.0 30.0 33.00 6.0 6
22.0 30 4 54.1 63 16.0 46.0 50.60 10.0 4
45.0 60 6 92.3 100 35.0 90.0 99.00 25.0 1
75.0 120 6 150.2 160 70.0 150.0 165.00 55.0 3/0

Cable length
The maximum cable length is 100 m (328 ft). Screened cables must be used.

4 SRC 311 Technical Specification


Technical Specification

The PWM output switching from any inverter using a long motor cable can cause an
increase in the voltage at the motor terminals, depending on the cable length and
inductance. The rise time and peak voltage can affect the service life of the motor. Flygt
recommend using an output choke for motor cable lengths of 50 m or more to ensure
good motor service life.
For UL-compliant installation, use Copper wir4 with a minimum insulation temperature
rating of 75°C (167°F). When using fuses type must be Class CC or Class J

Dimensions
Frame size 2 – 3

D A
B

I
J
E
H F
G

Drive A B C D E F G H I
Size
Lengt mm in mm in mm in mm in mm in mm in mm in mm in mm in
h
2 257. 10.1 220. 8.67 200. 7.87 28.5 1.12 238. 9.37 188. 7.40 176. 6.93 4.2 0.17 8.5 0.33
0 2 0 0 0 0 0
3 310. 12.2 276. 10.8 251. 9.90 33.4 1.31 256. 10.0 210. 8.29 197. 7.78 4.2 0.17 8.5 0.33
0 0 5 9 5 0 8 5 5

SRC 311 Technical Specification 5


Technical Specification

Frame size 4 – 7

H
I

A C B

D
F G E

Drive A B C D E F G H I
Size
Lengt mm in mm in mm in mm in mm in mm in mm in mm in mm in
h
4 440. 17.3 418. 16.4 423. 16.6 8.0 0.31 230. 9.06 173. 6.81 110. 4.33 4.25 0.16 7.5 0.29
0 2 0 6 0 5 5 0 0 0 7 5
5 540. 21.2 515. 20.2 520. 20.4 8.0 0.31 270. 10.6 235. 9.25 175. 6.89 4.25 0.16 7.5 0.29
0 6 0 8 0 7 5 0 3 0 0 7 5
6 865. 34.0 830. 32.6 840. 33.0 10.0 0.39 340. 13.3 290. 11.4 200. 7.87 5.50 0.21 11.0 0.43
0 6 0 8 0 7 4 0 9 0 2 0 7 3
7 1280 50.3 1245 49.0 1255 49.4 10.0 0.39 370. 14.5 330. 12.9 200. 7.87 5.50 0.21 11.0 0.43
.0 9 .0 2 .0 1 4 0 7 0 9 0 7 3

Torque values
Screw Frame size Torque Nm (lbs-in.)
Control terminal All 0.8 (7)
Power terminal 2–3 1 (8.85)
4 1.2 – 1.5 (10.6 – 13.2)
5 2.5 – 4.5 (22.5 – 39.8)
6–7 8 (70.8)

6 SRC 311 Technical Specification


Technical Specification

Mounting clearance
X Minimum 200 mm (7.87 in)
X
Y Minimum 10 mm (0.349 in)

Y Y

Typical drive heat losses are 3% of operating load conditions.

NOTICE:
The operating ambient temperature of the drive must be maintained.

SRC 311 Technical Specification 7


Technical Specification

Control terminal

+24 V
RL1-C

DI 1
RL1-NO

DI 2
RL1-NC

DI 3

+10 V
RL2-A

AI 1
RL2-B

AI 2

0V

AO1

STO - 0V

STO + AO2

Table 6: Main terminal strip

Terminal Abbreviation Description Area of use


1 +24 V + 24 V User Output (Input) 100 mA User Output/+24 V back
up supply.
2 DI 1 Input 1 Digital 8 - 30 V DC
3 DI 2 Input 2 Digital 8 - 30 V DC
4 DI 3 Input 3 Digital 8 - 30 V DC
5 +10 V + 10 V User Output 10 mA for user potentiometer
6 AI 1 Input 4 Digital 8 - 30 V DC/Analog Input
1, -10 – 10 V, 0/4 – 20 mA
7 0V 0 V Common
8 AO1 Output 1 1st Analog/Digital Output, 0 – 10
V, 4 – 20 mA/+24 V DC Digital
9 0V 0 V Common
10 AI 2 Input 5 Digital 8 - 30 V DC/Analog Input
2, 0 – 10 V, 0/4 – 20 mA or Motor
PTC
11 AO2 Output 2 2nd Analog/Digital Output, 0 – 10
V, 4 – 20 mA/+24 V DC Digital
12 STO+ Drive hardware inhibit Safe +24 V input - must be linked
to ext +24 V (18 - 30 V) DC to
enable power stage

8 SRC 311 Technical Specification


Technical Specification

Terminal Abbreviation Description Area of use


13 STO- Inhibit 0 V input 0 V return for the +24 V "Safe"
(STO)

Table 7: Additional terminal strip

Terminal Abbreviation Description Area of use


14 RL1-C Relay Output 1 Common Relay contacts, 250 V AC, 30 V DC,
5A
15 RL1-NO Relay Output 1 NO
16 RL1-NC Relay Output 1 NC
17 RL2-A Relay Output 2 Common
18 RL2-B Relay Output 2 NO

Communication
The unit is equipped with an RJ45 connector. The connection is used to set up a network
via a wired connection. The connector contains two independent RS485 connections and
both can be used simultaneously.
Do not connect directly into an Ethernet port. The voltage destroys the Ethernet device.
1 2 3 4 5 6 7 8

1. Not used
2. Not used
3. 0V
4. Optibus/Remote Keypad/PC connection -
5. Optibus/Remote Keypad/PC connection +
6. 24 V Remote Keypad power supply
7. RS485- Modbus RTU/BACnet
8. RS485+ Modbus RTU/BACnet

Options
External Keypads and Optistick
• OLED External Keypad
• Optidrive P2/E2 Optistick
Pluggable modules
• Extended I/O
• Extended relay
• TTL Encoder Module
• Ethernet IP Module
• Profibus Module
• Devicenet Module

SRC 311 Technical Specification 9


Technical Specification

Cables splitters, PC Kit


• RS485 Data cable Splitter
• RS485 Data cable w- RJ45
• USB to RS485 Connection kit

10 SRC 311 Technical Specification


Xylem |’zīləm|
1) The tissue in plants that brings water upward from the roots
2) A leading global water technology company

We're 12,000 people unified in a common purpose: creating


innovative solutions to meet our world's water needs. Developing new
technologies that will improve the way water is used, conserved, and
re-used in the future is central to our work. We move, treat, analyze,
and return water to the environment, and we help people use water
efficiently, in their homes, buildings, factories and farms. In more than
150 countries, we have strong, long-standing relationships with
customers who know us for our powerful combination of leading
product brands and applications expertise, backed by a legacy of
innovation.

For more information on how Xylem can help you, go to xyleminc.com

Xylem Water Solutions AB Visit our Web site for the latest version of this document and
more information
Gesällvägen 33
174 87 Sundbyberg The original instruction is in English. All non-English
instructions are translations of the original instruction.
Sweden
Tel. +46-8-475 60 00 © 2011 Xylem Inc

Fax +46-8-475 69 00
http://tpi.xyleminc.com

882877_1.0_en.US_2011-12_TS_SRC311