S500 Manual provisional
S500 Manual provisional
Represented by:
Warning
Correct functioning of these instruments must be verified by carrying out a calibration
check at least every 6 months but every 3 months is preferable. Install and maintain
all hazardous area equipment in accordance with the relevant regulations and
practices of the country concerned.
Warranty
Monicon Technology warrants all of its products to be free from defects in
workmanship or material under normal use and service within the periods specified in
the individual data sheets.
Monicon Technology will repair or replace without charge any equipment found to be
defective during the warranty period.
Gas detection elements that have been poisoned by contaminants (e.g. silicone, lead,
chlorine, sulphur or phosphor) are not included in the warranty.
In all cases this warranty is limited to the cost of the equipment supplied by Monicon
Technology.
The customer will assume all liability for the misuse of the said equipment by its
employees or other personnel.
Operating Instructions
2-1 CAL Magnetic Switch
2-2 SET Magnetic Switch
2-3 é Magnetic Switch
2-4 ê Magnetic Switch
2-5 STATUS Display
2-6 %LEL Display
2-7 General Operation
System Setup
3-1 Entering System Setup Mode
3-2 A1 Alarm Setpoint
3-3 A2 Alarm Setpoint
3-4 A3 Alarm Setpoint
3-5 ZERO setting
3-6 SPAN setting
3-7 Alarm Relays Energised/de-Energised
3-8 RS485 Address
3-9 Hardware Adjustments
3-10 Overrange Latching
3-11 Factory Default settings
3-12 Saving System Variables
System Specification
7-1 Environmental Specification
7-2 Mechanical Specification
7-3 Electrical Specification
7-4 Cable Specification
User Information
8-1 Wiring Diagram
8-2 Dimensional Diagram
The contents should be carefully removed and checked against the enclosed
packing slip.
Any discrepancies between the contents and the packing slip must be reported to
Monicon Technology within ten days of receipt of the shipment. Monicon
Technology cannot be held responsible for shortages not reported within this
period.
The controller requires free air circulation in order to avoid excessive heat build-up
inside the enclosure. Controllers should not be mounted in close proximity to
heaters or any device that might cause excessive heat build-up inside the
controller.
The mounting should be as free from shock and vibration as possible, and must
be accessible for calibration purposes.
Various detector accessories are available to minimise the effects of rain, wind
and particulate matter.
ð A detector will not detect a gas leak unless that gas actually reaches the
detector!
ð Ensure that detectors are located away from any source of R. F. or any
electromagnetic interference.
Care should be taken, particularly at the detector end, that the screen does not
come into contact with any metal conduit or junction box. Avoid running detector
cables close to high power cables, radio transmission lines or cables subject to
pulses of high current.
When the Power-Up period has expired The STATUS display should change to
"OK" and the %LEL display will indicate gas concentration.
The “OK” display appears as follows:
When the Power-Up period has expired, should the STATUS display not indicate
"OK", a possible fault condition exists and this should be investigated.
1-8 Maintenance
When installed correctly, systems require very little maintenance other than
regular calibration and inspection.
ð Ensure that detector heads are always positioned effectively with respect
to surrounding plant, equipment and potential sources of gas leaks.
ð Ensure that detector heads have not been contaminated by any foreign
matter.
ð Ensure that cables and connections are intact and in good condition.
If the concentration of gas at the sensor reaches 100% LEL, the STATUS display
will change to "OR" (Over-Range) and the %LEL display will indicate "99":
ð A latched over-range should not be reset until it is verified that the gas
concentration has dropped below 100% LEL.
Then if the %LEL display does not indicate 0, the reading can be incremented by
activating the é magnetic switch or decremented by activating the ê magnetic
switch.
Then if the %LEL display does not indicate 50, the reading can be incremented
by activating the é magnetic switch or decremented by activating the ê magnetic
switch.
The Alarm Relay contacts are Normally Open (NO) contacts. If deEnergised is
selected for the Alarm Relays, the relay contacts will be open circuit if there is no
gas alarm and will be short circuit if there is a gas alarm. The reverse will apply if
Energised Alarm Relays are selected.
⇒ It should also be noted that the same RS485 address must not be used
on two S-500’s sharing the common RS485 interface. If the RS485
address is not unique, bus contention will occur and remote access will
not be possible, however, local operation will not be affected.
The following is an explanation of the possible problems that the system may
identify:
A third type of memory is also used by the S-500. This is called EEPROM
(Electrically Erasable Programmable Read Only Memory). EEPROM provides
permanent data storage but the data can be erased and new information written.
EEPROM is used to store the system variables during system setup. However,
EEPROM is very slow and the software required to store and retrieve information
from EEPROM is very complex. Because of this, certain occurrences of electrical
interference may corrupt the data while it is in the process of being written to the
EEPROM.
To ensure 100% data integrity, after the S-500 writes information to the EEPROM,
it reads it back again to verify that the stored information is correct. If the
information read back differs from the information written, then the display
indicates "ER EP" as follows:
If this error occurs, simply activate the CAL switch twice and the S-500 will make a
further attempt to write the system variables to the EEPROM.
A1 Relay A2 Relay
Terminal Colour
REF Black
JNC Grey
ACT Red
Each S-500 operates in polled slave mode. This means that the S-500 cannot
initiate a communication, it can only respond when addressed by the master
computer. The master computer broadcasts an address, a command code, a
variable field and a checksum. The addressed S-500 then responds with its
identification, a response identifier, a variable field and a checksum.
To reduce the effect of interference from external electrical signals the RS485
interface uses a differential signal over a “twisted pair” cable. To further reduce
the effects of interference, a low Baud rate of 2400 Baud is used. Finally, each
communication is accompanied by a checksum. The use of a checksum ensures
that if data corruption does occur, the information is disregarded and the
information is transmitted again.
It will be noted that D7 is always set on the address frame but always cleared on
other frames. This allows the S-500 to differentiate between address frames and
other frames.
The checksum is derived from the arithmetic sum (truncated to the least
significant 7 bits) of the previous data.
The Status column indicates valid commands for the S-500 by the symbol ü.
Invalid commands for the S-500 are indicated by the symbol û. The complete
command set has been listed for compatibility with other instruments in the range
and for future extensions to the software.
LS
MS 0 1 2 3 4 5 6 7 8 9 A B C D E F
0 ì é è ê ç ¿ à Ø ø ò ù Ñ ç ê É é
1 è Æ æ Å å Ä ä Ö ö Ü ü °C °F ß £ ¥
2 ! “ # $ % & ‘ ( ) * + , - . /
3 0 1 2 3 4 5 6 7 8 9 : ; < = > ?
4 @ A B C D E F G H I J K L M N O
5 P Q R S T U V W X Y Z [ \ ] ^ _
6 ` a b c d e f g h I j k l m n o
7 p q r s t u v w x y z { | } ~
A screened, multicore cable may be user to carry power, analogue output and
RS485 signals. For power and analogue output a 3-core screened cable will be
required. For power, analogue output and RS485 a 5-core screened cable will be
required. Ideally, the RS485 should be a twisted pair or alternatively should be
separately screened.
Chart Recorder
0V
PSU
+24V
A1 Relay A2 Relay
Red
CGS500
EEx d IIC T6
II 2 G BAS00ATEX2246X
It is designated Category 2 Equipment and is suitable for installation in Zone 1 Hazardous
Areas with Apparatus Group II. The sensor carries a Temperature Classification (T Rating) of
T6, which means that no surface temperature of the sensor will exceed 85ºC when in service.
The sensor must be fitted into an appropriately rated terminal box or conduit and must not be
removed while the connected circuits are energised.
The sensor assembly does not incorporate an external earthing facility. lt is the responsibility
of the user to ensure adequate earth bonding via the mounting arrangements. The flying
leads must be protected against mechanical damage and be terminated in an enclosure
suitable for the conditions of use.
The maximum voltage for safe operation is 3V while the maximum current for safe operation
is 400mA. Note that the maximum operating voltages and currents may be lower. The
following table lists values for the more common elements.
The sensor does not contain any user serviceable parts or adjustments. Under no
circumstances should the sensor assembly be opened.
Red (ACT)
Grey (JNC)
Black (REF)