Desigo® Fire Safety

Detectors and Peripherals


Multi-Criteria Fire Detector
Model FDOT421

Architect & Engineer Specifications Product Overview


 UL 268 7th Edition Listed The Photoelectric | Thermal (Heat) Detector (Model FDOT421) is an intelligent,
 Built-in ISOtechnologyTM addressable multi-criteria detector that incorporates optical and thermal sensors, and
 252 Isolation devices per SLC uses signals in a neural network to create an intelligent multi-criteria detector. The
 Each detector is self-testing: encompassing result is a detector that provides enhanced detection to a wide range of
- complete diagnostics performed every products of combustion.
10 seconds Model FDOT21 is UL 268 7th Ed. listed and incorporates advanced built-in
- self-monitored for sensitivity within
UL Listed limits ISOtechnologyTM - True Class-X SLC operation (use is optional) greatly improves
 Listed, approved as a heat detector:
reliability, circuit integrity and provides advanced addressable fault finding.
- Rate-of-Rise Detection: 15°F / min. The multi-criteria detector additionally has state-of-the-art microprocessor
(8.3°C / min.) circuitry, as well as detector self-diagnostics and supervision programs that is used
- Fixed: 135°F (57°C) on Desigo Fire Safety Modular | FireFinder XLS/V and on Model FC/FV20-series
 Superior electromagnetic interference Desigo Fire Safety fire-alarm control panels (FACPs).
(EMI) and radio-frequency interference Additionally, Model FDOT421 is a plug-in and addressable multi-criteria detector
(RFI) immunity
(with both photoelectric and thermal sensors) whose value is increased with built-
 Field programmable as rate-of-rise or in ISOtechnology feature, that is compatible with all current Siemens intelligent,
fixed temperature, per `Alarm Source 2’ | addressable systems.
Standard parameter
 Tri-color detector-status light-emitting Operation
diode (LED) with 360° view
Model FDOT421 utilizes an infrared light emitting diode (IRLED), and infrared
 Compatible with Model DPU (device light-sensing photodiode. Under normal conditions, light transmitted by the LED
programmer / loop tester)
is directed away from the photodiode and scattered through the smoke chamber
 Polarity insensitive via SureWireTM in a controlled pattern.
technology (in non-isolator mode)
The smoke chamber is designed to manage light dissipation and extraneous
 Functions with Model DB-11–series reflections from dust particles or other non-smoke, airborne contaminants in such
mounting bases a way as to maintain stable, consistent detector operation. When smoke enters
 Restriction of Hazardous Substances the detector chamber, light emitted from the IRLED is scattered by the smoke
(RoHS compliant) particles, and is received by the photodiode.
 Automatic environment compensation Model FDOT421 also utilizes a modern, accurate and shock-resistant thermistor to
 UL Listed | FM, CSFM Approved sense temperature changes.
- UL 268: `Open Area Smoke Detection’ The signal processing with detection algorithms
- UL 268A (Duct) - `Direct-in-Duct’ use
- UL 521: `Open Area Heat Detection’ allows the detector to first gather smoke and thermal
- ULC-S529: `System Smoke Detector’ data, and then analyze this information in the
- ULC-S530: `Heat Actuated Fire Detection’ detector’s `neural network.’ By comparing data
- FM 3230: `Open Area Smoke Detection’ received with the common characteristics of fires or
- FM 3210: `Open Area Heat Detection’ fire signatures, Model FDOT421 can compare these
- CSFM | File: 7272-0067:0258
signals to those of deceptive phenomena that cause
Model FDOT421-
other detectors to trigger a false alarm.
Multi-Criteria Fire Detector
Each Model FDOT421 detector provides two (2) pre-programmed parameter sets
that can be selected by the FACP.

Siemens Data Sheet 6150


Smart Infrastructure - Building Products usa.siemens.com/fire
1. Dust cover 1
1. Labyrinth 2. Multi-criteria detector
2. Optical NOTE: Each detector consists of a
transmitter dust-resistant photoelectric
chamber; a solid state, non-
3. Optical mechanical thermal sensor,
receiver and microprocessor-based
electronics with a low-profile
4. Heat sensor
plastic housing.
Every Model FDOT421
fire detector is shipped with
a protective dust cover.
2
Model FDOT421

Profile Overview
Model FDOT421 provides two (2) different alarm sources that can be selected individually (ON or OFF) by the control
panel.

Alarm Source 1 (Neural Network) – Combines smoke (heat) with the following field-selectable profiles:
• Standard • Duct

Standard: This parameter set is the default setting and is well suited for clean applications such as normal office
and hotel lobby-type-applications.

Duct: When using this detector in direct “in-duct” applications, be sure the detector is set to the parameter
“Duct”.

Alarm Source 2 (Thermistor) – Heat only; provides the following:


• Static / fixed at 135°F (57°C), default setting
• Rate-of-Rise detection at 15°F / min. (8.3°C / min.)

Model FDOT421 contains a tri-color LED indicator, capable of flashing any one (1) of three (3) distinct colors: GREEN |
YELLOW | RED. During each flash interval, the microprocessor-based detector monitors the following fire-system
conditions:
• Smoke in its sensing chamber
• Smoke sensitivity is within the range indicated on the nameplate label
• Internal sensors and electronics

Based on the results of the monitoring, the LED indicator flashes the following:
FLASH
FLASH
CONDITION INTERVAL
COLOR
[in seconds]
Normal supervisory operation.
GREEN: 10
Smoke sensitivity is within rated limits.
YELLOW: Detector is in trouble and needs replacement. 4
RED: `Alarm’ condition 1
NO FLASH: Detector is not powered. –

denotes LED can be turned OFF
Please follow the corresponding description of the panel used.
A quick visual inspection is sufficient to indicate the condition of the detector at any time.
If more detailed information is required, a printed report can be provided from the respective Desigo Fire Safety
Modular | Model FC20-series | FireFinder XLS/V FACPs that indicates the status and settings assigned to each detector.

Siemens
Smart Infrastructure - Building Products –2– usa.siemens.com/fire
Installation
All Model FDOT421 detectors use a surface-mounting base, Model DB-11, DB-11E or DB2-HR. Each base mounts onto a
4-inch (10.2 cm.) octagonal, square or single-gang electrical box. The base utilizes screw-clamp contacts for electrical
connections and self-wiping contacts for increased reliability.
The Model DB-11 detector base can be used with the optional Siemens Model LK-11 detector locking kit, which contains
50 detector locks and an installation tool to prevent unauthorized removal of the detector head. Model DB-11 has
aesthetically pleasing plugs to cover the outer mounting-screw holes.
Model FDOT421 may be installed on the same SLC with the following [when used with Desigo Fire Safety Modular Model
FC20-series | FireFinder XLS/V FACPs] –
• XTRI Series interface modules • HFP-11, HFPT-11 detection devices
Dimensional Data
• HTRI series interface modules • HCP output control modules
• HMS & XMS series manual stations • HZM conventional zone module

Each detector is shipped with a protective dust cover, consists of the following:
• Built-in ISOtechnology for True-Class-X SLC performance
• Dust-resistant photoelectric chamber
• Solid State, non-mechanical thermal sensor
• Microprocessor-based electronics with a low-profile plastic housing

All Model FDOT421 units are approved for operation within a UL-specified temperature range of 32°F to 100°F (0 – 38°C).
Application Data
Installation of Model FDOT421 intelligent, addressable multi-criteria detectors requires connection to a SLC. In many
retrofit cases, existing field wiring may be reused. `T-tapping’ is permitted only for Style 4 (Class B) wiring. Model
FDOT421 is polarity insensitive, which can greatly reduce installation and debugging times. When operating in NFPA 72
Class-X applications SLC polarity must be maintained to support up to 252 isolation ready devices per loop. When used in
mixed mode a maximum of 30 non-isolated devices between isolation devices (wired in polarity-insensitive mode). See
control panel install document for further details.
When used in standard smoke detection applications spacing of 30 feet (9.144 m) on center is recommended. When
used in heat detection applications model FDOT421 can be applied within the maximum 50-feet (15.24 m.) center
spacing (2,500 sq. ft. [232.2 sq. m.]) per Underwriters’ Laboratories Listing. This application guide is based on ideal
conditions, specifically, smooth-ceiling surfaces, minimal air movement, and no physical obstructions between potential
fire sources and the actual detector. Do not mount detectors near to heating | ventilation | air-conditioning (HVAC)
outlets. Exposed joists or beamed ceilings may also affect safe spacing limitations for detectors.
Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire-protection system
engineering and common sense dictate how and when fire detectors are installed and used. Contact your local Siemens
– Fire Safety distributor or sales office whenever you need assistance applying Model FDOT421 in unusual applications.
Be sure to follow NFPA guidelines and UL Listed / ULC Listed installation instructions – included with every Siemens – Fire
Safety detector – and local codes for all fire-protection equipment. Siemens offers the Desigo Detector selection matrix
document no. A6V12111218 for further information when selecting detectors for a specific application.

Specifications
Model FDOT421 is a plug-in, Photoelectric smoke | Thermal (heat) detector, compatible with Model FC20-series Desigo
Fire Safety Modular Model FC20-series | FireFinder XLS/V FACPs. Each Model FDOT421 detector has microcomputer-chip
technology and highly stable, solid-state electronic circuitry. Model FDOT421 detectors utilize a modern, accurate and
shock-resistant thermistor to sense temperature changes. This electronic-sensing method virtually eliminates thermal
lag associated with mechanical temperature-sensing devices, and provides almost instantaneous temperature status to
the FACP.
Model FDOT421 provides two (2) field-selectable, pre-programmed temperature settings:
• Fixed 135°F (57°C) • Rate-of-Rise: 15°F / min. (8.3°C)

This feature is compatible with Model FC20-series Desigo Fire Safety Modular Model FC20-series | FireFinder XLS/V
systems, as well as with FC / FV2025 or FC / FV2050 FACPs.

Siemens
Smart Infrastructure - Building Products –3– usa.siemens.com/fire
Field-Device Programmer / Test Unit
Model FDOT421 is compatible with the Siemens field-device programmer / test unit Model DPU, which is a compact,
portable and menu-driven accessory for electronically programming and testing these addressable detectors promptly and
reliably. For instance, the field technician selects the accessory’s program mode, and enters the desired address.
Model DPU eliminates the need for cumbersome, unreliable mechanical programming methods (e.g. – dip switches and
rotary switches), and reduces installation and service costs by electronically programming and testing the detector prior to
installation. When set in `test’ mode, Model DPU will perform a series of diagnostic tests without altering the address or
other stored data, allowing technicians to determine if the detector is operating properly.
Each field-device programmer / test unit operates on AC power or rechargeable batteries, providing flexibility and
convenience in the programming / testing of fire-safety equipment from practically any location. Additionally, with the
use of a Model DPU unit, there is no longer a cause for concern with any vibration, corrosion and other deteriorating
conditions that can accompany the vitality of an electro-mechanical-addressing mechanism.
The encompassing result is an intelligent detector that provides enhanced detection capability to a wide range of products
of combustion – while offering unsurpassed rejection to nuisance-alarm sources, including: dust | steam | aerosols and
other deceptive phenomena that could cause false alarms.

Technical Data Panel Compatibilities Details for Ordering


MODEL PART
OPERATING +32° – +100°F MODEL DATA PRODUCT
PANEL OR TYPE NUMBER
TEMPERATURE: (0° – +38°C) OR TYPE SHEET
Addressable
XLS 6300 FireFinder® (fire-only overview) FDOT421 S54320-F6-A1 Multi-Criteria Fire
RELATIVE 0 – 95%
Detector
HUMIDITY: (non-condensing)
XLSV 6340 FireFinder (fire w/ voice) Compatible Devices:
AIR PRESSURE: No effect MODEL PART
PRODUCT
Desigo Desigo Modular OR TYPE NUMBER
7300
Modular (system overview) Buzzer Version
INPUT VOLTAGE Audible Base
16VDC – 30VDC ABHW-4B S54320-F13-A1
RANGE: (standard 3,000 Hz
Desigo Fire Safety tone)
FC901 6813
`ALARM’ 50-point addressable
410μA ABHW-4BZ S54320-F13-A2 Audible Base
CURRENT, MAX.:
Desigo Fire Safety Sleeping Room
FC2025
252-pt. addressable (fire) Version, 520 Hz Low
`STANDBY’ ABHW-4S S54320-F14-A1
250μA 6815 Frequency Audible
CURRENT, MAX.:
Desigo Fire Safety 504-pt. Base
FC2050
addressable (fire)
MAXIMUM ABHW-4SZ S54320-F14-A2 Audible Base
30–ft. (9.144 m.) centers
SPACING: Surface Mount
(900 sq. ft. | 83.6 sq. m.), Desigo Fire Safety
Smoke detection ADB-BOX 500-698360 Adapter Box for
per NFPA 72 and ULC-S524 252-point addressable
application FV2025 Audible Base
(fire w/ Intelligent Voice
MAXIMUM Communication [IVC] ) Relay base
50–ft. (15.24 m.) centers 6821 compatible with
SPACING:
(2500 sq. ft. | 232.3 sq. m.), DB2-HR S54370-F12-A1 Siemens standard
Heat detection 504-pt. addressable
per NFPA 72 and ULC-S530 and advanced
application FV2050 (fire w/ Intelligent Voice
detectors
Communication [IVC] )
• Fixed 135°F (57°C) Detector Mounting
DB-11 500-094151
Base (for Series 11)
THERMAL • Rate-of-Rise:
RATING: 15°F / min. (8.3°C) Detector Base
DB-11E 500-094151E
at fixed 135°F (57°C) (small)
Remote Alarm
DETECTOR Indicator:
0.317 Lbs. (0.144 kg.) RL-HW 500-033310
WEIGHT: Single-gang-box
mount, red
MECHANICAL UL Listed / ULC Listed Remote Alarm
PROTECTION with STI Guard Model Indicator:
GUARD: STI-9604 RL-HC 500-033230 4” (10.2 cm.)
octagon-box mount,
red
Base Locking Kit
LK-11 500-695350
(for Series 11)
See: www.STI-USA.com for further details
on ordering Model STI-9604
S

Siemens
Smart Infrastructure - Building Products –4– usa.siemens.com/fire
NOTICE – The information contained in this data-sheet document is intended only
as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install-type, instruction sheets – as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire-safety professional before specifying or using the product.
Any further questions or assistance concerning
particular problems that might arise, relative to the
proper functioning of the equipment, please contact
Desigo® Fire Safety
the Manufacturer.
Siemens Industry, Inc.
Smart Infrastructure - Building Products
2 Gatehall Drive • Parsippany, NJ 07054
Tel: (973) 593-2600
November - 2024