Model FDOT421 provides two (2) different alarm sources that can be selected individually (ON or OFF) by the control
panel.
Alarm Source 1 (Neural Network) – Combines smoke (heat) with the following field-selectable profiles:
• Standard • Duct
Standard: This parameter set is the default setting and is well suited for clean applications such as normal office
and hotel lobby-type-applications.
Duct: When using this detector in direct “in-duct” applications, be sure the detector is set to the parameter
“Duct”.
Model FDOT421 contains a tri-color LED indicator, capable of flashing any one (1) of three (3) distinct colors: GREEN |
YELLOW | RED. During each flash interval, the microprocessor-based detector monitors the following fire-system
conditions:
• Smoke in its sensing chamber
• Smoke sensitivity is within the range indicated on the nameplate label
• Internal sensors and electronics
Based on the results of the monitoring, the LED indicator flashes the following:
FLASH
FLASH
CONDITION INTERVAL
COLOR
[in seconds]
Normal supervisory operation.
GREEN: 10
Smoke sensitivity is within rated limits.
YELLOW: Detector is in trouble and needs replacement. 4
RED: `Alarm’ condition 1
NO FLASH: Detector is not powered. –
denotes LED can be turned OFF
Please follow the corresponding description of the panel used.
A quick visual inspection is sufficient to indicate the condition of the detector at any time.
If more detailed information is required, a printed report can be provided from the respective Desigo Fire Safety
Modular | Model FC20-series | FireFinder XLS/V FACPs that indicates the status and settings assigned to each detector.
Siemens
Smart Infrastructure - Building Products –2– usa.siemens.com/fire
Installation
All Model FDOT421 detectors use a surface-mounting base, Model DB-11, DB-11E or DB2-HR. Each base mounts onto a
4-inch (10.2 cm.) octagonal, square or single-gang electrical box. The base utilizes screw-clamp contacts for electrical
connections and self-wiping contacts for increased reliability.
The Model DB-11 detector base can be used with the optional Siemens Model LK-11 detector locking kit, which contains
50 detector locks and an installation tool to prevent unauthorized removal of the detector head. Model DB-11 has
aesthetically pleasing plugs to cover the outer mounting-screw holes.
Model FDOT421 may be installed on the same SLC with the following [when used with Desigo Fire Safety Modular Model
FC20-series | FireFinder XLS/V FACPs] –
• XTRI Series interface modules • HFP-11, HFPT-11 detection devices
Dimensional Data
• HTRI series interface modules • HCP output control modules
• HMS & XMS series manual stations • HZM conventional zone module
Each detector is shipped with a protective dust cover, consists of the following:
• Built-in ISOtechnology for True-Class-X SLC performance
• Dust-resistant photoelectric chamber
• Solid State, non-mechanical thermal sensor
• Microprocessor-based electronics with a low-profile plastic housing
All Model FDOT421 units are approved for operation within a UL-specified temperature range of 32°F to 100°F (0 – 38°C).
Application Data
Installation of Model FDOT421 intelligent, addressable multi-criteria detectors requires connection to a SLC. In many
retrofit cases, existing field wiring may be reused. `T-tapping’ is permitted only for Style 4 (Class B) wiring. Model
FDOT421 is polarity insensitive, which can greatly reduce installation and debugging times. When operating in NFPA 72
Class-X applications SLC polarity must be maintained to support up to 252 isolation ready devices per loop. When used in
mixed mode a maximum of 30 non-isolated devices between isolation devices (wired in polarity-insensitive mode). See
control panel install document for further details.
When used in standard smoke detection applications spacing of 30 feet (9.144 m) on center is recommended. When
used in heat detection applications model FDOT421 can be applied within the maximum 50-feet (15.24 m.) center
spacing (2,500 sq. ft. [232.2 sq. m.]) per Underwriters’ Laboratories Listing. This application guide is based on ideal
conditions, specifically, smooth-ceiling surfaces, minimal air movement, and no physical obstructions between potential
fire sources and the actual detector. Do not mount detectors near to heating | ventilation | air-conditioning (HVAC)
outlets. Exposed joists or beamed ceilings may also affect safe spacing limitations for detectors.
Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire-protection system
engineering and common sense dictate how and when fire detectors are installed and used. Contact your local Siemens
– Fire Safety distributor or sales office whenever you need assistance applying Model FDOT421 in unusual applications.
Be sure to follow NFPA guidelines and UL Listed / ULC Listed installation instructions – included with every Siemens – Fire
Safety detector – and local codes for all fire-protection equipment. Siemens offers the Desigo Detector selection matrix
document no. A6V12111218 for further information when selecting detectors for a specific application.
Specifications
Model FDOT421 is a plug-in, Photoelectric smoke | Thermal (heat) detector, compatible with Model FC20-series Desigo
Fire Safety Modular Model FC20-series | FireFinder XLS/V FACPs. Each Model FDOT421 detector has microcomputer-chip
technology and highly stable, solid-state electronic circuitry. Model FDOT421 detectors utilize a modern, accurate and
shock-resistant thermistor to sense temperature changes. This electronic-sensing method virtually eliminates thermal
lag associated with mechanical temperature-sensing devices, and provides almost instantaneous temperature status to
the FACP.
Model FDOT421 provides two (2) field-selectable, pre-programmed temperature settings:
• Fixed 135°F (57°C) • Rate-of-Rise: 15°F / min. (8.3°C)
This feature is compatible with Model FC20-series Desigo Fire Safety Modular Model FC20-series | FireFinder XLS/V
systems, as well as with FC / FV2025 or FC / FV2050 FACPs.
Siemens
Smart Infrastructure - Building Products –3– usa.siemens.com/fire
Field-Device Programmer / Test Unit
Model FDOT421 is compatible with the Siemens field-device programmer / test unit Model DPU, which is a compact,
portable and menu-driven accessory for electronically programming and testing these addressable detectors promptly and
reliably. For instance, the field technician selects the accessory’s program mode, and enters the desired address.
Model DPU eliminates the need for cumbersome, unreliable mechanical programming methods (e.g. – dip switches and
rotary switches), and reduces installation and service costs by electronically programming and testing the detector prior to
installation. When set in `test’ mode, Model DPU will perform a series of diagnostic tests without altering the address or
other stored data, allowing technicians to determine if the detector is operating properly.
Each field-device programmer / test unit operates on AC power or rechargeable batteries, providing flexibility and
convenience in the programming / testing of fire-safety equipment from practically any location. Additionally, with the
use of a Model DPU unit, there is no longer a cause for concern with any vibration, corrosion and other deteriorating
conditions that can accompany the vitality of an electro-mechanical-addressing mechanism.
The encompassing result is an intelligent detector that provides enhanced detection capability to a wide range of products
of combustion – while offering unsurpassed rejection to nuisance-alarm sources, including: dust | steam | aerosols and
other deceptive phenomena that could cause false alarms.
Siemens
Smart Infrastructure - Building Products –4– usa.siemens.com/fire
NOTICE – The information contained in this data-sheet document is intended only
as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install-type, instruction sheets – as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire-safety professional before specifying or using the product.
Any further questions or assistance concerning
particular problems that might arise, relative to the
proper functioning of the equipment, please contact
Desigo® Fire Safety
the Manufacturer.
Siemens Industry, Inc.
Smart Infrastructure - Building Products
2 Gatehall Drive • Parsippany, NJ 07054
Tel: (973) 593-2600
November - 2024
(Rev. 17)