AVA Series 200 - English
AVA Series 200 - English
SERIES 200
BASIC SERIES
• 200Nm torque output makes the Series 200 perfect for large size ball valves
and butterfly valves.
• Introduces ‘Wiring Box’ and removes pre wired cable.
• Multi Voltage 24VAC/DC or 95-265VAC voltage range, reducing stock
required to be held to cover possible on site voltages.
• Declutchable manual override selector button located in top cover.
• Available with internal super capacitor fitted for Failsafe functionality.
• 2 x M20 Conduit Entry
Technical Specifications
Rated Torque Nm (in.lbs): 240Nm Break (2124) / Run 200Nm (1170) Enclosure: PC+ PET Plastic Housing ** IP67/Nema 4X
ISO 5211: F07/10 x 22mm Output Drive LED Status Light: Yes, RGB Open, Close, Alarm.
Connecting Cable: 2 x M20 Conduit Wiring Box Weight: 6Kg - only available in plastic currently
Working Angle Range: 0-270 degrees. Set via internal cams. Temperature Range: -20 > +80C ***
Sound Power Level: Max50dB(A) Vibration Rating: 10 to 55Hz, 1.5mm double amplitude
Position Indicator: Mechanical Dome Window. As above Installation : Vertical/Horizontal - not underslung
Withstand Voltage: 500VAC for 1 minute Maintenance: Maintenance Free - do not remove cover
Insulation Resistance: 100MΩ/ 500VDC Approvals: TUV CE & EMC Certified, REACH, RoHS***
Explosion Proof: No, not to be used in a hazardous location. Can only be used in safe area applications.
* Series 200 doesn't have pre wired cable. Customer to supply and fit own cable as required. However, we can supply prewired, speak to your sales representative.
** PC+PET plastic cover as standard. Aluminium cover to be made available in the future.
*** Note that we can extend the lower temperature range through special lubricant and grease and upgraded heater system. Speak to your sales representative.
*** AVA has began the process to have all of our electric actuators approved for UL and CSA
Main Ordering Codes for Basic Series: *indicates standard options for stock product Example : B2045-PHB-22
Series > Function > Voltage + Housing > Heater > Wiring + Output Drive>
New feature, we are adding a QR label to all of our products that will enable users of our
product to have quicker and more direct access to support documents via our new purpose
built QR website. Simply scan the QR code using your Smart phone camera and you will be
taken directly to the specific actuator you have on site and will have access to Technical
Datasheets, Firmware guides and product support videos.
SMART SERIES
• Larger OLED screen to display more information than ever before.
• New SmartMenu provides onboard Firmware and enables user to change certain
parameters in the actuator including speed, angle, accuracy.
• Self diagnostic tool, actuator will check its vital components to ensure eve-
rything is in good working order. Motor RPM, ambient temperature, humidity.
• Local Control as standard allows the user to operate the actuator open > close via the
touch buttons.
Technical Specifications:
Rated Torque Nm (in.lbs): 240Nm Break (2124) / Run 200Nm (1170) Alarm Relay: Yes, option for fault alarm output
ISO 5211: F07/10 x 22mm Output Drive LED Status Light: Yes, RGB Open, Close, Alarm.
Connecting Cable: 2 x M20 Conduit Wiring Box 3 Position Function: Yes, setup via SmartMenu firmware
Working Angle Range: 0-270 degrees. Set via digital encoder. Working angle can be digitally set via SmartMenu firmware.
Duty Cycle: 75% rated - 100% rated for Modulating Brushless Motor: Yes, DC brushless motor
Sound Power Level: Max50dB(A) Modulating Control: Pre set at factory where applicable.
Position Indicator: Mechanical connected to digital encoder sensor for accurate position sensing.
Local Control: Yes via SmartMenu using touch buttons Reverse Acting: Yes, set via SmartMenu
Speed Control: PWM or PULSE speed control via SmartMenu Fail to 3rd Position: Yes, set via SmartMenu
Explosion Proof: No, not to be used in a hazardous location. Can only be used in safe area applications.
** See previous page for details on options available on pre wired cable lengths, temperature rating, cover and upcoming approvals.
Main Ordering Codes for Smart Series: *indicates standard options for stock product Example : S20010-6PHE-22
Series + Function > Voltage + Housing + Heater + Wiring > Output Drive>
34 Modbus Failsafe
Failsafe via internal super capacitor if you have selected
35 Modbus Modulating Failsafe version. Capacitor is charged whilst power ap-
plied. When power is removed capacitor will close/open
actuator.
Power Ratings for most common series: Note that internal heater power is 2W.
Code Voltage Power Time Fuse Peak Code Voltage Power Time Fuse Peak
B2005-PHB-11 95-265VAC 120W 25s 10A 7.5A S20025-6PHP/U-11 24VAC/DC 120W 25s 10A 7.5A
B2006-PHB-11 24VAC/DC 120W 25s 10A 7.5A S20026-5PHP/U-11 95-265VAC 150W 25s 10A 7.5A
B2045-PHB-11 95-265VAC 150W 25s 10A 7.5A S20026-6PHP/U-11 24VAC/DC 150W 25s 10A 7.5A
B2046-PHB-11 24VAC/DC 150W 25s 10A 7.5A S20031-5PHW-11 95-265VAC 120W 25s 10A 7.5A
S20010-5PHE-11 95-265VAC 120W 25s 10A 7.5A S20031-6PHW-11 24VAC/DC 120W 25s 10A 7.5A
S20010-6PHE-11 24VAC/DC 120W 25s 10A 7.5A S20034-5PHW-11 95-265VAC 150W 25s 10A 7.5A
S20014-5PHE-11 95-265VAC 150W 25s 10A 7.5A S20034-6PHW-11 24VAC/DC 150W 25s 10A 7.5A
S20014-6PHE-11 24VAC/DC 150W 25s 10A 7.5A S20035-5PHW-11 95-265VAC 120W 25s 10A 7.5A
S20025-5PHP/U-11 95-265VAC 120W 25s 10A 7.5A S20035-6PHW-11 24VAC/DC 120W 25s 10A 7.5A
Standard On Off, Failsafe and Hi-Speed Open/Close Wir- Standard Modulating including Failsafe and Hi-Speed
ing: Additional wiring options available online. Wiring: Additional wiring options available online.
1.BLUE BLUE
Neutral /- Neutral /-
Power
Live Close /+ 2.RED Power Live /+ RED
FUSE
Switch
FUSE
Live Open /+ 3.BLACK
*Do not apply power to
Ground 3.EARTH Control & Feedback. This
will cause major damage
to actuator.
Important, we are changing our wiring box in Q4 2022 to a separate the power and feed-
back as shown to the left hand side compared to the current style as shown in the image
of the actuator above. This will help prevent users accidentally applying power to the
feedback terminals. See IOMs document for more information.
* Note that the Basic and Smart series are the same physical size.
We are able to supply our actuators with a prewired cable with IP67/68
weatherproof rated plug and play connector. We can supply both male and female
connectors with a pre determined cable length required. We are able to terminate
the cable for your PLC as required, loose for you to terminate or with a panel mount
connector for example. Options include screw terminal and welded (soldered) con-
nection.