1._400_kV_M2_REL670_OHL_Calc_Sheet

The document is a calculation sheet for the 400 kV M2 REL670 overhead line protection system at the CARX substation, detailing various electrical parameters such as line lengths, resistances, and fault coverage settings. It includes calculations for different protection zones, including positive and zero sequence reactive and resistive reaches, as well as fault resistance reaches for both phase-phase and phase-earth faults. Additionally, it addresses power swing detection settings and safety margins for the relay operations.

Uploaded by

Manikanda Prabu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
10 views5 pages

1._400_kV_M2_REL670_OHL_Calc_Sheet

The document is a calculation sheet for the 400 kV M2 REL670 overhead line protection system at the CARX substation, detailing various electrical parameters such as line lengths, resistances, and fault coverage settings. It includes calculations for different protection zones, including positive and zero sequence reactive and resistive reaches, as well as fault resistance reaches for both phase-phase and phase-earth faults. Additionally, it addresses power swing detection settings and safety margins for the relay operations.

Uploaded by

Manikanda Prabu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

1.

400 kV M2 REL670 OHL Calc Sheet

SUBSTATION: CARX FEEDER: HSTA CT Ratio 2000/1

RELAY TYPE: REL670 PROTECTION: MAIN 2 DISTANCE VT Ratio 400/0.11

OHL RL XL Zratio 1.82

Line length=7.00 km R1=0.13 ohm X1=1.84 ohm Line angle 86°

k0
R0=0.66 ohm X0=4.46 ohm k0 k0
(Line data)
(to be used in (to be used in calc.
Space between
Date: 23 October 2010 13.1 m 0.48 calc. for Z1) for Z2)
phases
Space between
5.5 m -7.4° 0.48 0.80
phase and gnd

Zone 1

SIR-Check (to be carried out on short lines)

U= 9.66 kV
Zone 1 reach check for k0 (Line data) with regard to
⇒ SIR = 22.98
parallel line out and grounded
ISC = 6.53 kA

Select: Operation = ON Grounded Line: MUSH-WRSN

Positive Sequence Reactive Reach ZM01 X1 Vph Iph 3I0

Saftey margin = 0.75 ⇒ ZM01 = 1.38 ohm prim. 11.95 kV 4.09 kA 3.75 kA

Positive Sequence Resistive Reach ZM01 R1 (For Zone Characteristic Angle) 0.0 deg -83.2 deg -82.8 deg

ZM01 R1= 0.10 ohm prim. Zapparent= 2.03 ohm prim.


Actual Z1
Zero Sequence Reactive Reach ZM01 X0 68%
Underreach
Without mutual: ZM01 X0= 3.35 ohm prim. 0.64
Select ZM01 X0: 3.35 ohm prim. Required (Z1) k0 ≤
With mutual: ZM01 X0= 3.37 ohm prim. -8.0 deg

Zero Sequence Resistive Reach ZM01 R0 (For Zone Characteristic Angle) Suggested (Z1) k0 0.48

ZM01 R0= 0.50 ohm prim. 0.48


Select (Z1) k0 =
Fault Resistance Reach Phase-Phase ZM01 RFPP [Ohm/loop] -7.4 deg

3-ph fault at 80%, I-phase total I-phase relay end

37510 A 6534 A
Measurement errors due to CT and VT
phase displacement errors
Minimum required resistive coverage for ph-ph faults: 1.25 ohm prim.

Select ZM01 RFPP ohm/loop primary value: 2.50 ohm prim. Background Calculations

Fault Resistance Reach Phase-Earth ZM01 RFPE [Ohm/loop]


Beta=1.249 Alfa=1.179
3I0 total 3I0 relay end I-phase relay end I-phase remote end
sqrt(a)=4.247 h=4.667
42957 A 9379 A 8229 A 35728 A
psi=1.695 gamma=0.054
Minimum required resistive coverage for ph-gnd faults: 6.40 ohm prim. Max XError = 0.23 ohm prim.

Select ZM01 RFPE ohm/loop primary value: 6.40 ohm prim. Max. 0.87
Percentage
coverage of the line
Corresponding value in ohm/phase primary value: 4.32 ohm prim. Min. 0.63

Zone 2

Positive Sequence Reactive Reach ZM02 X1

Fault at remote busbar

ITot IShortest line IHighest contribution IZ2 considered Z1Shortest line Shortest line: HSTA-HRSR

39277 A 4810 A 10314 A 2983 A 2.04 ohm prim. Highets contrib.: HSTA-WRSN 1

ZM02 X1≥ 2.21 ohm prim.


⇒ Select ZM02 X1: 3.00 ohm prim.
Check Zone 2 reach with k0 (Line data) for remote
ZM02 X1≤ 14.69 ohm prim.
busbar fault
Positive Sequence Resistive Reach ZM02 R1 (For Zone Characteristic Angle) Vph Iph 3I0

ZM02 R1= 0.21 ohm prim. 15.20 kV 2.70 kA 3.08 kA

Zero Sequence Reactive Reach ZM02 X0 0.0 deg -80.6 deg -79.6 deg
Zapparent=
Without mutual: ZM02 X0= 7.26 ohm prim. 3.64 ohm prim.
(with k0 Line data)
Select ZM02 X0: 10.20 ohm prim. Actual Z2
With mutual: ZM02 X0= 10.20 ohm prim. Overreach 0.82
(with k0 Line data)
Required (Z2) k0 ≥
Zero Sequence Resistive Reach ZM02 R0 (For Zone Characteristic Angle) 1.80
(Considering same
reach for pos.seq.
ZM02 R0= 1.51 ohm prim. -9.1 deg
and zero seq.)
Fault Resistance Reach Phase-Phase ZM02 RFPP [Ohm/loop] Suggested (Z1) k0 1.10

3-ph flt at rmt bb, I-phase total I-phase relay end 0.80
Select (Z1) k0 =
39277 A 2983 A -14.0 deg

Minimum required resistive coverage for ph-ph faults: 8.07 ohm prim.

Select ZM02 RFPP ohm/loop primary value: 8.50 ohm prim.

Transmission Protection Department Rev. 1 CARX-HSTA - Page 1 of 5


1. 400 kV M2 REL670 OHL Calc Sheet

Fault Resistance Reach Phase-Earth ZM02 RFPE [Ohm/loop]

Fault at remote busbar


k0 increased from 0,48 to 0,78 in order to dependably
overreach the busbar in HSTA.
3I0 total 3I0 relay end I-phase relay end I-phase remote end

47082 A 5123 A 4104 A 42978 A

Minimum resistive reach setting to cover remote busbar: 4.34 ohm prim.

Minimum resistive coverage to reach to remote end: 14.08 ohm prim.

Select ZM02 RFPE ohm/loop primary value: 14.00 ohm prim.

Corresponding value in ohm/phase primary value: 7.78 ohm prim.

Apparent impedance for fault two buses away

ZAPP = 2.10 ohm ⇒ Time delay=0.55 s Fault at bus: HRSR

Zone 3

Positive Sequence Reactive Reach ZM03 X1

Fault at remote busbar

ITot IShortest line IHighest contribution IZ4 considered Z2Shortest Shortest line: HSTA-HRSR

39277 A 4810 A 10314 A 2983 A 3.40 ohm prim. Highets contrib.: HSTA-WRSN 1

ZM03 X1≥ 2.77 ohm prim.


⇒ Select ZM03 X1: 8.00 ohm prim.
ZM03 X1≤ 23.50 ohm prim.

Positive Sequence Resistive Reach ZM03 R1 (For Zone Characteristic Angle)

ZM03 R1= 0.56 ohm prim.

Zero Sequence Reactive Reach ZM03 X0

Without mutual: ZM03 X0= 19.36 ohm prim.


Select ZM03 X0: 25.00 ohm prim.
With mutual: ZM03 X0= 27.20 ohm prim.

Zero Sequence Resistive Reach ZM03 R0 (For Zone Characteristic Angle)

ZM03 R0= 3.70 ohm prim.

Fault Resistance Reach Phase-Phase ZM03 RFPP [Ohm/loop]


Selected fault resistance coverage Selected fault resistance coverage for zone
for zone 2 4 (calculated below)
8.50 ohm prim. 8.50 ohm prim.

Select ZM03 RFPP ohm/loop primary value: 14.00 ohm prim.

Fault Resistance Reach Phase-Earth ZM03 RFPE [Ohm/loop]


Selected fault resistance coverage Selected fault resistance coverage for zone
for zone 2 4 (calculated below)
14.00 ohm prim. 20.00 ohm prim.

Select ZM03 RFPE ohm/loop primary value: 30.00 ohm prim.

Corresponding value in ohm/phase primary value: 16.67 ohm prim.

Time delay=0.80 s

Transmission Protection Department Rev. 1 CARX-HSTA - Page 2 of 5


1. 400 kV M2 REL670 OHL Calc Sheet

Zone 4
(Used for POTT scheme and non-directional SOTF)
Positive Sequence Reactive Reach ZM04 X1

Overreach factor: 1.4 ZM02 X1= 3.00 ohm prim.

⇒ ZM04 X1= 2.58 ohm prim.

Select ZM04 X1: 3.50 ohm prim.

Positive Sequence Resistive Reach ZM04 R1 (For Zone Characteristic Angle)

ZM04 R1= 0.25 ohm prim.

Zero Sequence Reactive Reach ZM04 X0

Without mutual: ZM04 X0= 8.47 ohm prim.


Select ZM04 X0: 11.90 ohm prim.
With mutual: ZM04 X0= 11.90 ohm prim.

Zero Sequence Resistive Reach ZM04 R0 (For Zone Characteristic Angle)

ZM04 R0= 1.76 ohm prim.

Fault Resistance Reach Phase-Phase ZM04 RFPP [Ohm/loop]

I-phase total I-phase relay end

39277 A 2983 A

Minimum required resistive coverage for ph-ph faults: 2.69 ohm prim.
ZM02 RFPP = 8.50 ohm prim.
(Information)
Select ZM04 RFPP ohm/loop primary value: 8.50 ohm prim.

Fault Resistance Reach Phase-Earth ZM04 RFPE [Ohm/loop]

Fault at remote busbar

3I0 total 3I0 relay end I-phase relay end I-phase remote end

47082 A 5123 A 4104 A 42978 A

Minimum resistive coverage to reach to remote end: 12.96 ohm prim.


ZM02 RFPE = 14.00 ohm prim.
(Information)
Select ZM04 RFPE ohm/loop primary value: 20.00 ohm prim.

Corresponding value in ohm/phase primary value: 11.11 ohm prim.

Zone 5
(Reverse direction for ECHO blocking)
Positive Sequence Reactive Reach ZM05 X1
ZM04 X1
remote =
3.00 ohm prim. ⇒ ZM05 X1= 1.62 ohm prim.

Select ZM05 X1: 3.00 ohm prim.

Positive Sequence Resistive Reach ZM05 R1 (For Zone Characteristic Angle)

ZM05 R1= 0.21 ohm prim.

Zero Sequence Reactive Reach ZM05 X0


ZM04 X0
remote =
8.49 ohm prim. ⇒ ZM05 X0= 5.64 ohm prim.

With respect to selected ZM05 X1 ⇒ ZM05 X0= 7.26 ohm prim.

Select ZM04 X0: 7.00 ohm prim.

Zero Sequence Resistive Reach ZM05 R0 (For Zone Characteristic Angle)

ZM05 R0= 0.83 ohm prim.

Fault Resistance Reach Phase-Phase ZM05 RFPP [Ohm/loop]


ZM04 RFPP
remote = 5.00 ohm prim. ⇒ ZM05 RFPP= 7.00 ohm prim.

Fault Resistance Reach Phase-Earth ZM05 RFPE [Ohm/loop]


ZM04 RFPE
remote = 10.00 ohm prim. ⇒ ZM05 RFPE= 14.00 ohm prim.

Transmission Protection Department Rev. 1 CARX-HSTA - Page 3 of 5


1. 400 kV M2 REL670 OHL Calc Sheet

Phase Selection PHS1

Smax = 2615 MVA ⇒ Imax = 3.77 kA

Umin = 0.90 x 400kV ⇒ 360 kV

Max ϕ = 30° ⇒ cos ϕ = 0.87

⇒ ArgLd = 35°

Saftey margin = 0.90 ⇒ RLdFw = RLdRw = 42.92 ohm prim. [Ohm/phase]

Earth fault Loop Impedance Angle = 84°

Positive Sequence Reactive Reach PHS X1

PHS X1≥ 5.04 ohm prim. ⇒ Select PHS X1: 5.04 ohm prim.

Zero Sequence Reactive Reach PHS X0

PHS X0≥ 17.14 ohm prim. Same proportion as for selected PHS X1: 17.14 ohm prim.

Select PHS X0: 17.14 ohm prim.

Fault Resistance Reach Phase-Phase Forward PHS RFFwPP [Ohm/loop]

RFFwPP = 10.63 ohm prim.

Fault Resistance Reach Phase-Phase Reverse PHS RFRvPP [Ohm/loop]

RFRvPP = 10.63 ohm prim.

Fault Resistance Reach Phase-Earth Forward PHS RFFwPE [Ohm/loop]

RFFwPE = 24.00 ohm prim.

Fault Resistance Reach Phase-Earth Reverse PHS RFRvPE [Ohm/loop]

RFRvPE = 24.00 ohm prim.

Power Swing Detection PSD1 PSD is disabled. Dynamic studies do not show any tendency
for power swings to be measured at this relay location. The
Operation = OFF PSD function, if activated, would constitute a risk of
unwanted distance protection blocking for sequential backup
fault clearance.

ISCA ISCA = 32.59 kA


Z<

Zsource_A = 7.09 ohm prim.

In case of double circuit lines, open the CB on both lines

ISCB ISCB = 32.55 kA


Z< ⇒
Zsource_B = 7.09 ohm prim.

In case of double circuit lines, open the CB on both lines

Zsyst = 16.02 ohm prim. Swing frequency Δf= 4.0 Hz

PSD Characteristic

Outer Resistive Load Boundary RLdOutFw [Ohm/phase]

Multiplication factor for inner resistive load boundary: kLdRRv = kLdRFw = 0.80

RLdInFw ≥ 42.92 ohm prim. (PHS) ⇒ RLdOutFw = 53.65 ohm prim.

RLdInFw ≥ 14.00 ohm prim. (ZM) ⇒ RLdOutFw = 17.50 ohm prim.

Note that resistive reach for PSD and PHS-Load ch. Are
set in ohm/phase, whereas other PHS R-reaches, and
Zone R-reaches are set in ohm/loop. This gives an extra Select RLdOutFw : 40.00 ohm prim.
margin for the PSD settings with regard to the R-reaches in
ohm/loop.

RLdOutRv = RLdOutFw ⇒ RLdOutRv : 40.00 ohm prim.

RLd_Min ≥ 47.69 ohm prim. ⇒ Margin = 0.84

ΔFw = 8.00 Ohm


ΔFw = ΔR = ΔX will always be calculated even if Load
Encroachment is disabled :
(ΔFw =) ΔRv = 8.00 Ohm

ArgLd = 25°

Load Encroachment Characteristic can normally be


disabled. The reach settings are however needed in order OperationLdCh = OFF
to get ΔFw and ΔRv

Transmission Protection Department Rev. 1 CARX-HSTA - Page 4 of 5


1. 400 kV M2 REL670 OHL Calc Sheet

Fault Resistance Coverage to Inner Resistive Line R1FInFw [Ohm/phase]

R1FInFw ≥ 14.00 ohm prim. ⇒ Select R1FInFw : 20.00 ohm prim.

R1FInRv = R1FInFw ⇒ R1FInRv : 20.00 ohm prim.

Inner Reactive Boundary X1InFw

X1InFw ≥ 8.00 ohm prim. ⇒ Select X1InFw : 15.00 ohm prim.

X1InRv = X1InFw ⇒ X1InRv : 15.00 ohm prim.

Line Resistance for Inner Characteristic angel R1LIn [Ohm/phase]

R1LIn : 1.05 ohm prim.

Timer for Detection of Initial Power Swing tP1

δout = 31.9°
Time to pass through
⇒ ΔFw :
8 ms
δin = 43.7°

Select tP1 : 0.030 s

Other Timers

Timer for detection of subsequent power swings: Select tP2 : 0.015 s

Waiting time for activation of tP2 timer: Select tW : 0.250 s

Timer for holding power swing START output: Select tH : 0.500 s

Timer giving delay to inhibit by the residual current: Select tR1 : 0.300 s

Timer giving delay to inhibit a very slow swing: Select tR2 : 2.000 s

Fault locator FLO

IA IA = 27.05 kA
Z<

ϕA = 86.8°

IB IA = 14.53 kA
Z< ⇒
ϕA = 87.1°

R1A = 0.48 ohm prim. X1A = 8.53 ohm prim.

R1B = 0.80 ohm prim. X1B = 15.87 ohm prim.

R1L = 0.13 ohm prim. X1L = 1.84 ohm prim.

R0L = 0.66 ohm prim. X0L = 4.46 ohm prim.

Transmission Protection Department Rev. 1 CARX-HSTA - Page 5 of 5