1._400_kV_M2_REL670_OHL_Calc_Sheet
1._400_kV_M2_REL670_OHL_Calc_Sheet
k0
R0=0.66 ohm X0=4.46 ohm k0 k0
(Line data)
(to be used in (to be used in calc.
Space between
Date: 23 October 2010 13.1 m 0.48 calc. for Z1) for Z2)
phases
Space between
5.5 m -7.4° 0.48 0.80
phase and gnd
Zone 1
U= 9.66 kV
Zone 1 reach check for k0 (Line data) with regard to
⇒ SIR = 22.98
parallel line out and grounded
ISC = 6.53 kA
Saftey margin = 0.75 ⇒ ZM01 = 1.38 ohm prim. 11.95 kV 4.09 kA 3.75 kA
Positive Sequence Resistive Reach ZM01 R1 (For Zone Characteristic Angle) 0.0 deg -83.2 deg -82.8 deg
Zero Sequence Resistive Reach ZM01 R0 (For Zone Characteristic Angle) Suggested (Z1) k0 0.48
37510 A 6534 A
Measurement errors due to CT and VT
phase displacement errors
Minimum required resistive coverage for ph-ph faults: 1.25 ohm prim.
Select ZM01 RFPP ohm/loop primary value: 2.50 ohm prim. Background Calculations
Select ZM01 RFPE ohm/loop primary value: 6.40 ohm prim. Max. 0.87
Percentage
coverage of the line
Corresponding value in ohm/phase primary value: 4.32 ohm prim. Min. 0.63
Zone 2
ITot IShortest line IHighest contribution IZ2 considered Z1Shortest line Shortest line: HSTA-HRSR
39277 A 4810 A 10314 A 2983 A 2.04 ohm prim. Highets contrib.: HSTA-WRSN 1
Zero Sequence Reactive Reach ZM02 X0 0.0 deg -80.6 deg -79.6 deg
Zapparent=
Without mutual: ZM02 X0= 7.26 ohm prim. 3.64 ohm prim.
(with k0 Line data)
Select ZM02 X0: 10.20 ohm prim. Actual Z2
With mutual: ZM02 X0= 10.20 ohm prim. Overreach 0.82
(with k0 Line data)
Required (Z2) k0 ≥
Zero Sequence Resistive Reach ZM02 R0 (For Zone Characteristic Angle) 1.80
(Considering same
reach for pos.seq.
ZM02 R0= 1.51 ohm prim. -9.1 deg
and zero seq.)
Fault Resistance Reach Phase-Phase ZM02 RFPP [Ohm/loop] Suggested (Z1) k0 1.10
3-ph flt at rmt bb, I-phase total I-phase relay end 0.80
Select (Z1) k0 =
39277 A 2983 A -14.0 deg
Minimum required resistive coverage for ph-ph faults: 8.07 ohm prim.
Minimum resistive reach setting to cover remote busbar: 4.34 ohm prim.
Zone 3
ITot IShortest line IHighest contribution IZ4 considered Z2Shortest Shortest line: HSTA-HRSR
39277 A 4810 A 10314 A 2983 A 3.40 ohm prim. Highets contrib.: HSTA-WRSN 1
Time delay=0.80 s
Zone 4
(Used for POTT scheme and non-directional SOTF)
Positive Sequence Reactive Reach ZM04 X1
39277 A 2983 A
Minimum required resistive coverage for ph-ph faults: 2.69 ohm prim.
ZM02 RFPP = 8.50 ohm prim.
(Information)
Select ZM04 RFPP ohm/loop primary value: 8.50 ohm prim.
3I0 total 3I0 relay end I-phase relay end I-phase remote end
Zone 5
(Reverse direction for ECHO blocking)
Positive Sequence Reactive Reach ZM05 X1
ZM04 X1
remote =
3.00 ohm prim. ⇒ ZM05 X1= 1.62 ohm prim.
⇒ ArgLd = 35°
PHS X1≥ 5.04 ohm prim. ⇒ Select PHS X1: 5.04 ohm prim.
PHS X0≥ 17.14 ohm prim. Same proportion as for selected PHS X1: 17.14 ohm prim.
Power Swing Detection PSD1 PSD is disabled. Dynamic studies do not show any tendency
for power swings to be measured at this relay location. The
Operation = OFF PSD function, if activated, would constitute a risk of
unwanted distance protection blocking for sequential backup
fault clearance.
PSD Characteristic
Multiplication factor for inner resistive load boundary: kLdRRv = kLdRFw = 0.80
Note that resistive reach for PSD and PHS-Load ch. Are
set in ohm/phase, whereas other PHS R-reaches, and
Zone R-reaches are set in ohm/loop. This gives an extra Select RLdOutFw : 40.00 ohm prim.
margin for the PSD settings with regard to the R-reaches in
ohm/loop.
ArgLd = 25°
δout = 31.9°
Time to pass through
⇒ ΔFw :
8 ms
δin = 43.7°
Other Timers
Timer giving delay to inhibit by the residual current: Select tR1 : 0.300 s
Timer giving delay to inhibit a very slow swing: Select tR2 : 2.000 s
IA IA = 27.05 kA
Z<
⇒
ϕA = 86.8°
IB IA = 14.53 kA
Z< ⇒
ϕA = 87.1°