1043271E103

The document provides an instruction sheet for the EV3271/EV3281 controllers used in refrigerated units, detailing user interface functions, settings, and installation precautions. It includes steps for viewing mains voltage, setting configuration parameters, and activating additional functions like defrost and energy saving. The document emphasizes safety measures for electrical connections and the importance of proper installation to ensure device functionality.

Uploaded by

José molina
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views2 pages

1043271E103

The document provides an instruction sheet for the EV3271/EV3281 controllers used in refrigerated units, detailing user interface functions, settings, and installation precautions. It includes steps for viewing mains voltage, setting configuration parameters, and activating additional functions like defrost and energy saving. The document emphasizes safety measures for electrical connections and the importance of proper installation to ensure device functionality.

Uploaded by

José molina
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

EVCO S.p.A. | EV3271/EV3281 | Instruction sheet ver. 1.

0 | Code 1043271E103 | Page 1 of 2 | PT 44/24

Controllers for refrigerated units,


EV3271/EV3281 with compressor protection against mains voltage fluctuations
4 USER INTERFACE AND MAIN FUNCTIONS 5.4 View the mains voltage
Assicurarsi che la tastiera non sia bloccata.

1. Touch the DOWN key for 4 s.

2. Touch the UP or DOWN key within 15 s to select “UOL”.

3. Touch the SET key.

Touch the ON/STAND-BY key (or do not operate for 60 s) to exit


4.
the procedure.
E ENGLISH
- Controllers for normal temperature units
6 SETTINGS
- Power supply 115... 230 VAC
6.1 Setting configuration parameters
- Cabinet probe (PTC/NTC/Pt 1000)
- Door switch/multi-purpose input 1. Touch the SET key for 4 s: the display will show the label “PA”.
- Compressor relay rated 16 res. A @ 250 VAC (EV3271) or 30 res. A @ 250 VAC
(EV3281) 2. Touch the SET key.
- Compressor protection against mains voltage fluctuations
Touch the UP or DOWN key within 15 s to set the PAS value (de-
- Alarm buzzer 3.
4.1 Switching the device on/off fault “-19”).
- TTL MODBUS slave port for EVconnect app, EPoCA remote monitoring system or for
BMS Touch the SET key (or do not operate for 15 s): the display will
1. If POF = 1, touch the ON/STAND-BY key for 4 s. 4.
- Cooling or heating operation show the label “SP”.
If the device is switched on, the display will show the P5 value ("cabinet temperature" default);
5. Touch the UP or DOWN key to select a parameter.
if the display shows an alarm code, see the section ALARMS.
1 MEASUREMENTS AND INSTALLATION
LED ON OFF FLASHING
Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided. 6. Touch the SET key.
compressor on compressor off - compressor protection active
- setpoint setting active
7. Touch the UP or DOWN key within 15 s to set the value.
defrost active - dripping active

8. Touch the SET key (or do not operate for 15 s).


saved HACCP alarm in - -
HACCP
EVlink Touch the SET key for 4 s (or do not operate for 60 s) to exit the
9.
energy saving active - - procedure.

request for compres- - - settings active 6.2 Set the date, time and day of the week (available if EVIF23TSX, EVIF25TBX or
sor service - access to additional functions EVIF25TWX module is connected)
active
- operation with EVconnect APP N.B.
active - Do not disconnect the device from the mains within two minutes since the setting
view temperature - overcooling or overheating active of the time and day of the week
°C/°F
- if the device communicates with the EVconnect app, the date, time and day of the
device off device on device on/off active week will be automatically set by the smartphone or tablet

Check that the keypad is not locked.


If 30 s have elapsed without the keys being pressed, the display will show the “Loc” label and
1. Touch the DOWN key for 4 s.
the keypad will lock automatically.

INSTALLATION PRECAUTIONS 2. Touch the UP or DOWN key within 15 s to select the label “rtc”.
4.2 Unlock keypad
- The thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in) Touch a key for 1 s: the display will show the label “UnL”. Touch the SET key: the display will show the label “yy” followed
- Ensure that the working conditions are within the limits stated in the TECHNICAL 3.
by the last two figures of the year.
SPECIFICATIONS section 4.3 Set the setpoint
- Do not install the device close to heat sources, equipment with a strong magnetic field, Check that the keypad is not locked. 4. Touch the UP or DOWN key within 15 s to set the year.
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
1. Touch the SET key. 5. Repeat actions 3. and 4. to set the next labels.
or shocks
- In compliance with safety regulations, the device must be installed properly to ensure Touch the UP or DOWN key within 15 s to set the value within
2. LAB. DESCRIPTION OF THE NUMBERS FOLLOWING THE LABEL
adequate protection from contact with electrical parts. All protective parts must be the limits r1 and r2 (default “-50... 50”)
n month (01… 12)
fixed in such a way as to need the aid of a tool to remove them
3. Touch the SET key (or do not operate for 15 s). d day (01… 31)
h time (00… 23)
2 ELECTRICAL CONNECTION
n minute (00… 59)
4.4 Activate manual defrost (if r5 = 0, default)
N.B. Touch the SET key: the display will show the label for the day of
Check that the keypad is not locked and that overcooling is not active. 6.
- Use cables of an adequate section for the current running through them the week.
1. Touch the UP key for 2 s. Touch the UP or DOWN key within 15 s to set the day of the
- To reduce any electromagnetic interference connect the power cables as far away 7.
as possible from the signal cables week.
If P4 = 1 (default), defrost is activated provided that the evaporator temperature is lower than
LAB. DESCRIPTION
the d2 threshold.
Mon Monday
4.5 Silence buzzer tuE Tuesday
Touch a key. UEd Wednesday
thu Thursday
5 ADDITIONAL FUNCTIONS Fri Friday
5.1 Activate/deactivate overcooling, overheating and manual energy saving Sat Saturday
Check that the keypad is not locked. Sun Sunday

1. Touch the DOWN key. 8. Touch the SET key: the device will exit the procedure.

9. Touch the ON/STAND-BY key to exit the procedure beforehand.


FUNCTION CONDITION CONSEQUENCE
overcooling r5 = 0, r8 = 1 and defrost the setpoint becomes “setpoint -
not active r6”, for the r7 duration 6.3 Restore the factory settings (default) and store customized settings as default
overheating r5 and r8 = 1 the setpoint becomes “setpoint +
r6”, for the r7 duration N.B.
energy saving r5 = 0 and r8 = 2 the setpoint becomes “setpoint + - Check that the factory settings are appropriate; see the section CONFIGURATION
r4”, at maximum for HE2 duration PARAMETERS.
- the storing of customized settings overwrites the default.
5.2 View/delete compressor functioning hours and view compressor start-up
number
1. Touch the SET key for 4 s: the display will show the label “PA”.
PRECAUTIONS FOR ELECTRICAL CONNECTION Check that the keypad is not locked.
- If using an electrical or pneumatic screwdriver, adjust the tightening torque
1. Touch the DOWN key for 4 s. 2. Touch the SET key.
- If the device has been moved from a cold to a warm place, the humidity may have
caused condensation to form inside. Wait about an hour before switching on the power
2. Touch the UP or DOWN key within 15 s to select a label. 3. Touch the UP or DOWN key within 15 s to set the value.
- Make sure that the supply voltage, electrical frequency and power are within the set
limits. See the section TECHNICAL SPECIFICATIONS LAB. DESCRIPTION VAL. DESCRIPTION
- Disconnect the power supply before doing any type of maintenance CH view compressor functioning hours (hundreds) 149 value to restore the factory settings (default)
- Do not use the device as safety device rCH delete compressor functioning hours 161 value to store customized settings as default
- For repairs and for further information, contact the EVCO sales network nS1 compressor start-up number (thousands) Touch the SET key (or do not operate for 15 s): the display will
4. show the label “dEF” (when value “149” is set) or the label
3 FIRST-TIME 3. Touch the SET key.
“MAP” (when value “161” is set).
1. Install following the instructions given in the section MEASUREMENTS AND INSTALLA-
Touch the UP or DOWN key to set “149” (when label “rCH” is se-
TION. 4. 5. Touch the SET key.
lected).
2. Power up the device as shown in the section ELECTRICAL CONNECTION and an internal
test will be run. 5. Touch the SET key. 6. Touch the UP or DOWN key within 15 s to set “4”.
The test normally takes a few seconds, when it is finished the display will switch off.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit Touch the SET key (or do not operate for 15 s): the display will
3. Configure the device as shown in the section Setting configuration parameters. 6.
the procedure. 7. show for 4 s “- - -“ flashing, then the device will exit the proce-
Recommended configuration parameters for first-time use.
dure.
PAR. DEF. PARAMETER MIN... MAX.
5.3 View the temperature detected by the probes 8. Interrupt the power supply to the device.
SP 0.0 setpoint r1... r2
Check that the keypad is not locked. Touch the SET key 2 s before action 6. to exit the procedure be-
P0 1 probe type 0 = PTC 1 = NTC 9.
1. Touch the DOWN key for 4 s. forehand.
2 = Pt 1000
P2 0 temperature unit of measurement 0 = °C 1 = °F
7 CONFIGURATION PARAMETERS
d1 0 defrost type 0 = electric 1 = hot gas 2. Touch the UP or DOWN key within 15 s to select a label.
2 = compressor stopped
LAB. DESCRIPTION N. PAR. DEF. SETPOINT MIN... MAX.
Pb1 cabinet temperature 1 SP 0.0 setpoint r1... r2
Then check that the remaining settings are appropriate; see the section CONFIGURA-
Pb2 auxiliary temperature (if P4 = 1 or 2) N. PAR. DEF. ANALOGUE INPUTS MIN... MAX.
TION PARAMETERS.
4. Disconnect the device from the mains. 2 CA1 0.0 cabinet probe offset -25... 25 °C/°F
3. Touch the SET key.
5. Make the electrical connection as shown in the section ELECTRICAL CONNECTION with- 3 CA2 0.0 auxiliary probe offset -25... 25 °C/°F
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit 4 P0 1 probe type 0 = PTC 1 = NTC
out powering up the device. 4.
the procedure. 2 = Pt 1000
6. For the connection in an RS-485 network, connect the EVIF22TSX or EVIF23TSX inter-
face. To activate real time functions, connect the EVIF23TSX module. To use the device 5 P1 1 enable °C decimal point 0 = no 1 = yes
5.4 View the project number and the firmware revision 6 P2 0 temperature unit of measure- 0 = °C 1 = °F
with the app EVconnect, connect the EVIF25TBX interface. To use the device with the
Check that the keypad is not locked. ment
EPoCA remote monitoring system, connect the EVIF25TWX module. If the EVIF22TSX
or EVIF23TSX interface is used, set parameter bLE to 0. 1. Touch the DOWN key for 4 s. 7 P4 1 configurable input function 0 = door switch/multi-pur-
7. Power up the device. pose input
2. Touch the UP or DOWN key within 15 s to select a label. 1 = evaporator probe
2 = condenser probe
LAB. DESCRIPTION 8 P5 0 value displayed 0 = cabinet temperature
PrJ view the project number 1 = setpoint
rEU view the firmware revison 2 = auxiliary temperature

3. Touch the SET key. 9 P8 5 display refresh time 0... 250 s : 10


N. PAR. DEF. REGULATION MIN... MAX.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit 10 r0 2.0 setpoint differential 1... 15 °C/°F
4.
the procedure. 11 r1 -50 minimum setpoint -99 °C/°F... r2
EVCO S.p.A. | EV3271/EV3281 | Instruction sheet ver. 1.0 | Code 1043271E103 | Page 2 of 2 | PT 44/24
12 r2 50.0 maximum setpoint r1... 199 °C/°F N. PAR. DEF. DIGITAL INPUTS MIN... MAX. RoHS 2011/65/CE WEEE 2012/19/EU REACH (EC) Regulation
13 r4 0.0 setpoint offset in energy saving 0... 99 °C/°F 60 i0 5 door switch/multi-purpose input 0 = disabled 1907/2006
14 r5 0 cooling or heating operation 0 = cooling function 1 = compressor EMC 2014/30/UE LVD 2014/35/UE
1 = heating 2 = reserved Power supply 115... 230 VAC (+10 % -15%), 50/60 Hz
15 r6 0.0 setpoint offset in overcool- 0... 99 °C/°F 3 = reserved (±3 Hz), max. 4 VA (EV3271) or 4.9 VA
ing/overheating 4 = reserved (EV3281) insulated
16 r7 30 overcooling/overheating duration 0... 240 min 5 = reserved Earthing methods for the control device None
17 r8 0 DOWN key additional function 0 = disabled 6 = reserved Rated impulse-withstand voltage 2.5 KV
1 = overcooling/overheating 7 = energy saving Over-voltage category II
2 = energy saving 8 = iA alarm Software class and structure A
18 r12 0 position of the r0 differential 0 = asymmetric 9 = device on/off
Analogue inputs 1 for PTC, NTC or Pt 1000 probes (cabinet
1 = symmetric 10= Cth alarm
probe)
11= th alarm
N. PAR. DEF. COMPRESSOR MIN... MAX. PTC probes Sensor type KTY 81-121 (990 Ω @ 25 °C, 77 °F)
61 i1 0 door switch/multi-purpose input 0 = with contact closed
19 C0 0 compressor on delay after pow- 0... 240 min Measurement field From -50 to 150 °C (from -58 to 302 °F)
activation 1 = with contact open
er-on Resolution 0.1 °C (1 °F)
62 i2 30 open door alarm delay -1... 120 min
20 C2 3 compressor off minimum time 0... 240 min NTC probes Sensor type ß3435 (10 KΩ @ 25 °C, 77 °F)
-1 = disabled
0 = protection against mains Measurement field From -40 to 105 °C (from -40 to 221 °F)
voltage fluctuations dis- 63 i3 15 regulation inhibition maximum -1... 120 min
Resolution 0.1 °C (1 °F)
abled time with door open -1 = until the closing
Pt 1000 Measurement field From -99 to 199 °C (from -146 to 390 °F)
21 C3 0 compressor on minimum time 0... 240 s 64 i7 0 multi-purpose input alarm delay -1... 120 min
probes Resolution 0.1 °C (1 °F)
-1 = disabled
22 C4 10 compressor off time during cabi- 0... 240 min Other inputs Input configurable for analogue input (auxil-
if i0 = 10 or 11, compressor
net probe alarm iary probe) or digital input (door
on delay after alarm reset
23 C5 10 compressor on time during cabi- 0... 240 min switch/multi-purpose, dry contact)
65 i10 0 door closed consecutive time for 0... 999 min
net probe alarm Dry contact Contact type 5 VDC, 1.5 mA
energy saving after regulation temperature
24 C6 80.0 threshold for high condensation 0... 199 °C/°F Power supply None
< SP
warning differential = 2 °C/4 °F
0 = disabled Protection None
25 C7 90.0 threshold for high condensation 0... 199 °C/°F
66 i13 180 number of door openings for de- 0... 240 Digital outputs 1 electro-mechanical relay
alarm
frost 0 = disabled Compressor relay (K1) SPST, 16 A res. @ 250 VAC (EV3271)
26 C8 1 high condensation alarm delay 0... 15 min
67 i14 32 door open consecutive time for 0... 240 min SPST, 30 A res. @ 250 VAC (EV3281)
27 C10 0 compressor hours for service 0... 999 h x 100
defrost 0 = disabled Type 1 or Type 2 Actions Type 1
0 = disabled
N. PAR. DEF. ENERGY SAVING (if r5 = 0) MIN... MAX. Additional features of Type 1 or Type 2 ac- C
28 C14 190 mains voltage threshold below 95... 260 V
68 HE2 0 energy saving maximum duration 0... 999 min tions
which the compressor is not the device attempts to switch
N. PAR. DEF. REAL TIME ENERGY SAVING (if MIN... MAX. Displays 3 digits custom display, with function icons
switched on on every 30 s
r5 = 0) Alarm buzzer Incorporated
29 C15 180 mains voltage threshold below 95... 260 V
69 H01 0 energy saving time 0... 23 h Communication ports 1 TTL MODBUS slave port for EVconnect app,
which the compressor is switched if satisfied C17 time
70 H02 0 energy saving duration 0... 24 h EPoCA remote monitoring system or for BMS
off
30 C16 260 mains voltage threshold above 95... 260 V 71 HEd 7 energy saving day 0 = Monday 1 = Tuesday
which the compressor is not if satisfied C17 time 2 = Wednesday
switched on or switched off the device attempts to switch 3 = Thursday 4 = Friday
on every 30 s 5 = Saturday 6 = Sunday
7 = none
31 C17 5 consecutive duration of the per- 0... 60 s
manence of the mains voltage N. PAR. DEF. REAL TIME DEFROST (if d8 = 4) MIN... MAX.
outside the thresholds C15 and 72 Hd1 h- 1st daily defrost time h- = disabled
C16 due to the compressor being 73 Hd2 h- 2nd daily defrost time h- = disabled
switched off 74 Hd3 h- 3rd daily defrost time h- = disabled
32 C18 5 consecutive number of failed 0... oo 75 Hd4 h- 4th daily defrost time h- = disabled
compressor starts due to the 0 = protection against mains 76 Hd5 h- 5th daily defrost time h- = disabled
mains voltage outside the voltage fluctuations dis- 77 Hd6 h- 6th daily defrost time h- = disabled
thresholds C14 and C16 such as abled N. PAR. DEF. SAFETIES MIN... MAX.
to cause the forced start-up of oo = the device never makes 78 POF 0 enable ON/STAND-BY key 0 = no 1 = yes
the compressor the forced start-up of 79 PAS -19 password -99... 999
the compressor 80 PA1 426 level 1 password -99... 999
the interruption of the power 81 PA2 824 level 2 password -99... 999
supply resets the count
N. PAR. DEF. REAL TIME CLOCK MIN... MAX.
N. PAR. DEF. DEFROST (if r5 = 0) MIN... MAX.
82 Hr0 0 enable clock 0 = no 1 = yes
33 d0 8 automatic defrost interval 0... 99 h
N. PAR. DEF. DATA-LOGGING EVLINK MIN... MAX.
0 = only manual
83 bLE 1 serial port configuration for con- 0 = free
if d8 = 3, maximum interval
nectivity 1 = forced for EVconnect or
34 d2 8.0 threshold for defrost end -99... 99 °C/°F
EPoCA
35 d3 30 defrost duration 0... 99 min 2-99 = EPoCA local network
se P4 = 1, maximum duration address
36 d4 0 enable defrost at power-on 0 = no 1 = yes 84 rE0 15 data-logger sampling interval 0... 240 min
37 d5 0 defrost dealy after power-on 0... 99 min 85 rE1 3 recorded temperature 0 = none 1 = cabinet
38 d6 2 value displayed during defrost 0 = cabinet temperature 2 = auxiliary 3 = all
1 = display locked N. PAR. DEF. MODBUS MIN... MAX.
2 = dEF label
86 LA 247 MODBUS address 1... 247
39 d7 2 dripping time 0... 15 min
87 Lb 2 MODBUS baud rate 0 = 2,400 baud
40 d8 0 defrost interval counting mode 0 = device on hours 1 = 4,800 baud
1 = compressor on hours 2 = 9,600 baud
2 = hours evaporator tem- 3 = 19,200 baud
perature < d9 parity even
3 = adaptive
4 = real time 8 ALARMS
41 d9 0.0 evaporation threshold for auto- -99... 99 °C/°F
matic defrost interval counting COD. DESCRIPTION RESET REMEDIES
42 d11 0 enable defrost timeout alarm 0 = no 1 = yes Pr1 cabinet probe alarm automatic - check P0
43 d18 40 adaptive defrost interval 0... 999 min Pr2 auxiliary probe alarm automatic - check probe integrity
if compressor on + evapora- - check electrical connection
tor temperature < d22 rtc clock alarm manual set date, time and day of the week
0 = only manual
COn forced compressor start manual - touch a key
44 d19 3.0 threshold for adaptive defrost 0... 40 °C/°F alarm - check C18
(relative to optimal evaporation optimal evaporation tempera-
LU compressor alarm not on or manual, au- - touch a key
temperature) ture - d19
off due to low mains voltage tomatic after - check C14 and C15
45 d20 180 compressor on consecutive time 0... 999 min 30 s
for defrost 0 = disabled
HU compressor alarm not on or manual, au- - touch a key
46 d21 200 compressor on consecutive time 0... 500 min off due to high mains volt- tomatic after - check C16
for defrost after power-on and if (cabinet temperature - set- age 30 s
overcooling point) > 10°C/20 °F
AL low temperature alarm automatic check AA, A1 and A2
0 = disabled
AH high temperature alarm automatic check AA, A4 and A5
47 d22 -2.0 evaporation threshold for adap- -10... 10 °C/°F
id open door alarm automatic check i0 e i1
tive defrost interval counting optimal evaporation tempera-
PF power failure alarm manual - touch a key
(relative to optimal evaporation ture + d22
- check electrical connection
temperature)
COH high condensation warning automatic check C6
N. PAR. DEF. ALARMS MIN... MAX.
CSd high condensation alarm manual - switch the device off and on
48 AA 0 select value for high/low temper- 0 = cabinet temperature
- check C7
ature alarms 1 = auxiliary temperature
iA multi-purpose input alarm automatic check i0 and i1
49 A1 -10.0 threshold for low temperature -99... 99 °C/°F
Cth compressor thermal switch automatic check i0 and i1
alarm
alarm
50 A2 1 low temperature alarm type 0 = disabled
th global thermal switch alarm manual - switch the device off and on
1 = relative to setpoint
- check i0 and i1
2 = absolute
dFd defrost timeout alarm manual - touch a key
51 A4 10.0 threshold for high temperature -99... 99 °C/°F
- check d2, d3 and d11
alarm
52 A5 1 high temperature alarm type 0 = disabled
9 TECHNICAL SPECIFICATIONS
1 = relative to setpoint
2 = absolute
Purpose of the control device Function controller
53 A6 12 high temperature alarm delay af- 0... 99 min x 10
Construction of the control device Built-in electronic device
ter power-on
Container Black, self-extinguishing
54 A7 15 high/low temperature alarms de- 0... 240 min
Category of heat and fire resistance D
lay
Measurements
55 A8 15 high temperature alarm delay af- 0... 240 min
75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x 75.0 x 33.0 x 81.5 mm (2 15/16 x 1 5/16 x
ter defrost
2 5/16 in) with fixed screw terminal blocks 3 3/16 in) with removable screw terminal
56 A9 15 high temperature alarm delay af- 0... 240 min
blocks
ter door closing
Mounting methods for the control device To be fitted to a panel, snap-in brackets pro-
57 A10 10 power failure duration for alarm 0... 240 min
vided N.B.
recording
Degree of protection provided by the cover- IP65 (front) The device must be disposed of according to local regulations governing the collection
58 A11 2.0 high/low temperature alarms re- 1... 15 °C/°F
ing of electrical and electronic waste.
set differential
Connection method
59 A13 0 enable alarm buzzer 0 = no 1 = yes
Fixed screw terminal blocks Removable screw terminal Micro-MaTch connector This document and the solutions contained therein are the intellectual property of EVCO and thus pro-
for wires up to 2,5 mm² blocks for wires up to tected by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an absolute ban on the full
2,5 mm²; by request or partial reproduction and disclosure of the content other than with the express approval of EVCO. The
Maximum permitted length for connection cables customer (manufacturer, installer or end-user) assumes all responsibility for the configuration of the de-
Power supply: 10 m (32.8 ft) Analogue inputs: 10 m (32.8 ft) vice. EVCO accepts no liability for any possible errors in this document and reserves the right to make
Digital inputs: 10 m (32.8 ft) Digital outputs: 10 m (32.8 ft) any changes, at any time without prejudice to the essential functional and safety features of the equip-
Operating temperature From 0 to 55 °C (from 32 to 131 °F) ment.
Storage temperature From -25 to 70 °C (from -13 to 158 °F)
Operating humidity Relative humidity without condensate from EVCO S.p.A.
10 to 90% Via Feltre 81, 32036 Sedico (BL) ITALY
Pollution status of the control device 2 telefono 0437 8422 | fax 0437 83648

Conformity email [email protected] | web www.evco.it