The document outlines the electrical load schedule for a bungalow commercial building, detailing branch load descriptions, circuit protection, and wire specifications. It specifies installation requirements in accordance with the Philippine Electrical Code, including conduit sizes, wire types, and outlet heights. Additionally, it emphasizes that all electrical work must be supervised by a licensed professional engineer.

Uploaded by

mark anjo luyun
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2 views

Project_solana

The document outlines the electrical load schedule for a bungalow commercial building, detailing branch load descriptions, circuit protection, and wire specifications. It specifies installation requirements in accordance with the Philippine Electrical Code, including conduit sizes, wire types, and outlet heights. Additionally, it emphasizes that all electrical work must be supervised by a licensed professional engineer.

Uploaded by

mark anjo luyun
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

S¹ MPB MPB

SCHEDULE OF LOADS TYPICAL PANEL BOARD

a a BRANCH LOAD DESCRIPTION NO.


VA VOLTS AMPERES
CIRCUIT PROTECTION
SIZE OF CONDUIT
CKT. NO. OF LOADS SIZE OF WIRE
2 AT P AF

1 LIGHTING OUTLET 4 400 230 1.77 15 2P 50 2 - 2.00 MM² THHN WIRE 20 MM² ø PVC PIPE.

2 CONVENIENCE OUTLET 4 720 230 3.13 20 2P 50 2 - 3.5 MM² THHN WIRE 20 MM² ø PVC PIPE.

TOTAL COMPUTED LOAD 1120 230 4.9 20 2P 50 2 - 5.5.0 MM² & 1 - 3.5MM² THHN WIRE 25 MM² ø PVC PIPE.

1
a a
PROTECTION COMPUTATIONS:
ITFL = total ampere load x 80% (demand factor)
ITFL = 4.9 x 80%
ITFL = 3.92 A
SIZE OF MAIN WIRE & CONDUIT:
USE: 2- 5.5 mm² THHN & 1- 3.5 mm² THHN (GRND) in 25 mm dia. PVC pipe, 20AT/50AF, 2pole

LIGHTNING LAYOUT POWER LAYOUT

1. AN ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISION


OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE APPLICABLE s¹a 1 Gang Switch SERVICE ENTRANCE CAP
ORDINANCE OF THE LOCAL GOVERNMENT AND THE REQUIREMENTS OF THE SERVICE ENTRANCE CAP
LOCAL POWER AND TELEPHONE COMPANIES.

2. ALL WIRING SHALL BE INSTALLED IN STANDARD CONDUIT PIPES RUN EMBEDDED LIGHTNING OUTLET
INSIDE THE CONCRETE AND HALLOW STRUCTURES, SLABS, COLUMNS AND/ OR
RUN CONCEALED BETWEEN DOUBLE WALL WOODED PARTITIONS AND INSIDE THE
CEILING SPACES. WATT HOUR-METER
3. UNLESS OTHERWISE INDICATED ON THE PLANS, THE MINIMUM SIZE OF WIRE AND
CONVENIENCE OUTLET
CONDUIT TO BE USED SHALL BE 2.00mm², AND 20 mm Ø PVC RESPECTIVELY.

4. ALL LIGHTNING AND CONVENIENCE OUTLET CIRCUIT HOMERUNS SHALL BE MPB BREAKER
WIRED WITH NOT LESS THAN 3.5mm² IN SIZE. ALL 15 AND 20 AMPERE CIRCUIT MAIN PANEL BOARD - MPB
HOMERUNS TO PANELBOARD MORE THAN 30 METERS IN LENGTH SHALL BE
WIRED WITH NOT LESS 5.5mm² IN SIZE, UNLESS OTHERWISE INDICATED ON THE
PLANS.
GROUND
5. ALL NON- CURRENT CARRYING METAL PARTS OF THE EQUIPMENT IN THE
SYSTEM SHALL BE PROPERLY GROUNDED IN ACCORDANCE WITH THE
1 CIRCUIT HOMERUN
PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE.

6. ALL MATERIALS SHALL BE NEW AND OF THE APPROVED TYPE FOR THE LOCATION
AND PURPOSE.
ELECTRICAL SYMBOLS USE 2 - 5.5 mm² THHN Wire in 25mm dia. PVC pipe

7. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATION AND


OTHER APPURTENANCES FOR THE ELECTRICAL INSTALLATION SHALL BE USED.
PULL BOX OFF PROPER SIZES AND DIMENSIONS SHALL BE PROVIDED ALTHOUGH 20 A

NOT INDICATED IN THE PLAN.

CKT 1 CKT 2
8. ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTS ABOVE 15 A 20 A

THE FINISHED FLOOR LEVEL.


UNLESS OTHERWISE NOTED:
WALL SWITCHES 1400mm above finished floor line USE:1 - 3.5 mm² THHN (GRND)
SITE
CONVENIENCE OUTLETS 400mm above finished
floor line
PANEL BOARD AT CONVENIENT HEIGHT
WALL LAMP AT CONVENIENT HEIGHT

9. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OD


SERVICE ENTRANCE FOR CONNECTION TO POWER COMPANY SERVICE POINT.

10. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE
SUPERVISION OF DULY LICENSED ELECTRICAL ENGINEER OR REGISTERED
SINGLE LINE DIAGRAM
MASTER ELECTRICIAN.

GENERAL NOTES AND


SPECIFICATIONS VICINITY MAP

PREPARED BY: PROJECT NAME: CONCURRED BY: SHEET CONTENTS: SHEET NO.

DELFIN F. MADDARA BUNGALOW COMMERCIAL BLDG. MR. EDUARDO E. ESPERANZA AS SHOWN


1
PROFESSIONAL ELECTRICAL ENGINEER

PRC REG. NO. : 3202

PTR NO.: 3522725


VALIDITY: 11-22-2027

DATE ISSUED: 01-02-2025


TIN NO.: 140-195-328

PLACE ISSUED: TUGUEGARAO CITY LOCATION: PUROK 3, BRGY. NANGALISAN, SOLANA, CAGAYAN OWNER