KT 24 398 Elec HCL Cable Schedule r2

The document provides detailed specifications and calculations for various types of cables, including their rated current, resistance, and factors affecting their performance under different conditions. It categorizes cables based on size and material, offering derating factors for temperature, depth of laying, and grouping. Additionally, it includes notes on installation conditions and verification requirements for voltage drop and current rating.

Uploaded by

nirmal07.nk
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views5 pages

KT 24 398 Elec HCL Cable Schedule r2

The document provides detailed specifications and calculations for various types of cables, including their rated current, resistance, and factors affecting their performance under different conditions. It categorizes cables based on size and material, offering derating factors for temperature, depth of laying, and grouping. Additionally, it includes notes on installation conditions and verification requirements for voltage drop and current rating.

Uploaded by

nirmal07.nk
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 5

HCL CAMPUS- CALCULATIONS FOR CABLE

PROJECT MANAGEMENT CONSULTANT

TURNKEY CONTRACTOR

MEP DESIGN CONSULTANT

KAUSI TECHNICAL SERVICES PVT LTD.,


Plot No-43, Door No-3/1, Kasi Estate,
4th Street, Jafferkhanpet, Ashok Nagar,
Chennai – 600083.
1.1kV XLPE Armoured / un armoured cables D.F Description Conditions Factor
Rated current(A) 30 degree C 1.10
Cable RAC(Ω/km) X(Ω/km)
In Ground In Air 35 degree C 1.04
Ambient
temperature 40 degree C 1.00
4Cx400 sqmm-Al 0.1 0.0704 418 530 45 degree C 0.95
4Cx300 sqmm-Al 0.128 0.0705 367 455 Rating factor for Variation in 50 degree C 0.90
4Cx240 sqmm-Al 0.16 0.071 326 399 A 20 degree C 1.08
Ambient/Ground temperature
4Cx185 sqmm-Al 0.21 0.0718 282 337 25 degree C 1.03
4Cx150 sqmm-Al 0.264 0.0716 249 292 Ground 30 degree C 1.00
4Cx120 sqmm-Al 0.324 0.0712 223 257 temperature 35 degree C 0.96
4Cx95 sqmm-Al 0.41 0.0724 196 221 40 degree C 0.91
4Cx70 sqmm-Al 0.567 0.074 164 179 Rating factor for variation in 750mm 1.00
4Cx50 sqmm-Al 0.82 0.075 133 142 B depth of laying of cables laid Depth of laying 900mm 0.98
4Cx35 sqmm-Al 1.11 0.0783 113 117 directly in the ground 1050mm 0.97
4Cx25 sqmm-Al 1.54 0.0805 94 96 150 1.00
Thermal
4Cx16 sqmm-Al 2.44 0.0808 73 70 Rating factor for variation in 200 0.89
C resistivity of
4Cx10 sqmm-Al 3.94 0.0837 57 67 thermal resistivity of soil 250 0.81
soil in °C-cm/W
4Cx6 sqmm-Al 5.9 0.0884 43 50 300 0.75
4Cx4 sqmm-Al 9.48 0.0927 34 31 1 1.00
2 0.79
3.5Cx400 sqmm-Al 0.1 0.0704 418 530 no of cables 3 0.69
3.5Cx300 sqmm-Al 0.128 0.0705 367 455 with touching 4 0.62
3.5Cx240 sqmm-Al 0.16 0.071 326 399 Group rating factor for cables 5 0.58
3.5Cx185 sqmm-Al 0.21 0.0718 282 337 D laid directly in ground in 6 0.54
3.5Cx150 sqmm-Al 0.264 0.0716 249 292 horizontal formation 2 0.82
3.5Cx120 sqmm-Al 0.324 0.0712 223 257 no of cables 3 0.75
3.5Cx95 sqmm-Al 0.41 0.0724 196 221 with 150mm 4 0.69
3.5Cx70 sqmm-Al 0.567 0.074 164 179 spacing 5 0.65
3.5Cx50 sqmm-Al 0.82 0.075 133 142 6 0.61
no of cable trays in no of cables in a
3.5Cx35 sqmm-Al 1.11 0.0783 113 117
a tier tray
3.5Cx25 sqmm-Al 1.54 0.0805 94 96 1 0.95
Group rating factor for cables 2 0.90
1
3Cx400 sqmm-Al 0.1 0.0704 418 530 laid inside concrete trench 3 0.88
3Cx300 sqmm-Al 0.128 0.0705 367 455 with removable covers, on 6 0.85
3Cx240 sqmm-Al 0.16 0.071 326 399 cable trays where air 1 0.90
3Cx185 sqmm-Al 0.21 0.0718 282 337 E circulation is restricted. The 2 0.85
2
3Cx150 sqmm-Al 0.264 0.0716 249 292 cables spaced by one cable 3 0.83
3Cx120 sqmm-Al 0.324 0.0712 223 257 diameter and trays in tiers by 6 0.81
3Cx95 sqmm-Al 0.41 0.0724 196 221 300mm. The clearance of the 1 0.88
cable from the wall is 25mm
3Cx70 sqmm-Al 0.567 0.074 164 179 2 0.83
3
3Cx50 sqmm-Al 0.82 0.075 133 142 3 0.81
3Cx35 sqmm-Al 1.11 0.0783 113 117 6 0.79
no of cable trays in no of cables in a
3Cx25 sqmm-Al 1.54 0.0805 94 96
a tier tray
3Cx16 sqmm-Al 2.44 0.0808 73 70 1 1.00
3Cx10 sqmm-Al 3.94 0.0837 57 67 2 0.84
1
3Cx6 sqmm-Al 5.9 0.0884 43 50 Group rating factor for cables 3 0.80
3Cx4 sqmm-Al 9.48 0.0927 34 31 laid on cable trays exposed to 6 0.75
air.The cables touching and 1 1.00
F
1Cx400 sqmm-Al 0.1 0.0873 431 596 trays in tiers by 300mm. The 2 0.80
2
1Cx300 sqmm-Al 0.128 0.0881 376 501 clearance of the cable from 3 0.76
1Cx240 sqmm-Al 0.16 0.09 332 433 the wall is 25mm 6 0.71
1Cx185 sqmm-Al 0.21 0.0932 286 360 1 1.00
1Cx150 sqmm-Al 0.264 0.0941 253 309 2 0.78
3
1Cx120 sqmm-Al 0.324 0.0968 225 268 3 0.74
1Cx95 sqmm-Al 0.41 0.1 198 230 6 0.70
1Cx70 sqmm-Al 0.567 0.102 166 187 1 1.00
1Cx50 sqmm-Al 0.82 0.108 135 150 Rating factor for cables laid 2 0.88
1Cx35 sqmm-Al 1.11 0.114 114 121 direct in single way no of cables 3 0.82
G
1Cx25 sqmm-Al 1.54 0.12 96 98 ducts/pipes in horizontal with touching 4 0.77
1Cx16 sqmm-Al 2.44 0.125 76 73 formation 5 0.74
1Cx10 sqmm-Al 3.94 0.134 59 53 6 0.71
1Cx6 sqmm-Al 5.9 0.123 44 39
1Cx4 sqmm-Al 9.48 0.132 36 31
Notes:
4Cx400 sqmm-Cu 0.0602 0.0704 1) When Cable laid directly in ground, choose derating factors A,B,C & D as per above
4Cx300 sqmm-Cu 0.0769 0.0705 462 480 table and derating factors E, F&G shall remain '1'
4Cx240 sqmm-Cu 0.0965 0.071 414 426
4Cx185 sqmm-Cu 0.127 0.0718 360 366 2) When Cable laid in concrete trench, choose derating factors A & E as per above table
4Cx150 sqmm-Cu 0.159 0.0716 324 318 and derating factors B,C,D,F & G shall remain '1'
4Cx120 sqmm-Cu 0.196 0.0712 288 276
4Cx95 sqmm-Cu 0.247 0.0724 252 240 3) When Cable laid on cable trays exposed to air, choose derating factors A & F as per
4Cx70 sqmm-Cu 0.343 0.074 210 198 above table and derating factors B,C,D,E & G shall remain '1'
4Cx50 sqmm-Cu 0.495 0.075 174 162
4Cx35 sqmm-Cu 0.671 0.0783 144 132 4) When Cable laid in ducts/pipes, choose derating factors A & G as per above table and
4Cx25 sqmm-Cu 0.93 0.0805 119 108 derating factors B,C,D,E & F shall remain '1'
4Cx16 sqmm-Cu 1.47 0.0808 92 79
4Cx10 sqmm-Cu 2.34 0.0837 72 62 5) Verification gives "OK" only if Voltage drop is less than 3% and current rating is 20% extra
4Cx6 sqmm-Cu 3.94 0.0884 54 47
4Cx4 sqmm-Cu 5.9 0.0927 43 36 6) "No of Typ. Load feeders" is filled when cable sizing is to be done for typical

3.5Cx400 sqmm-Cu 0.0602 0.0704 510 546


3.5Cx300 sqmm-Cu 0.0769 0.0705 462 480 Eg: AHUs-4nos of 7.5kW in same AHU room
3.5Cx240 sqmm-Cu 0.0965 0.071 414 426 Other wise the value is '1'
3.5Cx185 sqmm-Cu 0.127 0.0718 360 366
3.5Cx150 sqmm-Cu 0.159 0.0716 324 318
3.5Cx120 sqmm-Cu 0.196 0.0712 288 276
3.5Cx95 sqmm-Cu 0.247 0.0724 252 240
3.5Cx70 sqmm-Cu 0.343 0.074 210 198
3.5Cx50 sqmm-Cu 0.495 0.075 174 162
3.5Cx35 sqmm-Cu 0.671 0.0783 144 132
3.5Cx25 sqmm-Cu 0.93 0.0805 119 108

3Cx400 sqmm-Cu 0.0602 0.0704 510 546


3Cx300 sqmm-Cu 0.0769 0.0705 462 480
3Cx240 sqmm-Cu 0.0965 0.071 414 426
3Cx185 sqmm-Cu 0.127 0.0718 360 366
3Cx150 sqmm-Cu 0.159 0.0716 324 318
3Cx120 sqmm-Cu 0.196 0.0712 288 276
3Cx95 sqmm-Cu 0.247 0.0724 252 240
3Cx70 sqmm-Cu 0.343 0.074 210 198
3Cx50 sqmm-Cu 0.495 0.075 174 162
3Cx35 sqmm-Cu 0.671 0.0783 144 132
3Cx25 sqmm-Cu 0.93 0.0805 119 108
3Cx16 sqmm-Cu 1.47 0.0808 92 79
3Cx10 sqmm-Cu 2.34 0.0837 72 62
3Cx6 sqmm-Cu 3.94 0.0884 54 47
3Cx4 sqmm-Cu 5.9 0.0927 43 36

1Cx400 sqmm-Cu 0.0602 0.0873 480 660


1Cx300 sqmm-Cu 0.0769 0.0881 450 570
1Cx240 sqmm-Cu 0.0965 0.09 414 510
1Cx185 sqmm-Cu 0.127 0.0932 366 444
1Cx150 sqmm-Cu 0.159 0.0941 336 384
1Cx120 sqmm-Cu 0.196 0.0968 300 336
1Cx95 sqmm-Cu 0.247 0.1 364 294
1Cx70 sqmm-Cu 0.343 0.102 228 246
1Cx50 sqmm-Cu 0.495 0.108 186 198
1Cx35 sqmm-Cu 0.671 0.114 156 156
1Cx25 sqmm-Cu 0.93 0.12 132 132
1Cx16 sqmm-Cu 1.47 0.125 102 98
1Cx10 sqmm-Cu 2.34 0.134 78 72
1Cx6 sqmm-Cu 3.94 0.123 59 53
1Cx4 sqmm-Cu 5.9 0.132 47 42

6c 4sqmm Flexi cable 5.9 0.0927 43 36


1C 3.22 SQMM UNIVYIN 5.35 0.132 43 41
1C 8.76SQMM UNIVYIN 1.97 0.125 87 85
HCL CAMPUS
Title : CABLE SIZING CALCULATION Date :
Building : HCL CAMPUS DESIGNED CHECKED SHEET Rev.
Doc No:
Rated Demand Breaker Total
De-rating Factors when laid in Derated Connec Load Uprating VALIDATION
"R" "X" current Connected factor / System Load Size cable Voltage Cumulativ
Cable size in Laying of Net current length No. of ted Power for Breaker H/Load
Sr.No. From To Ω/ Ω/ of Temp Ground TrenchTray Duct Load Overall Voltage Current in Amps carrying Drop in e Voltage Voltage Current
Sq. mm Cables D.F. of cable (mtrs) Runs Load factor Breaker size current
km km cable A B C D E F G (kW ) Diversity in kV (Amp) recommend current % Drop in % Drop rating
(amp) (kW ) (Cos Ø) Selection
(amp) Factor ed (Amp)
630A FEEDER @ PUMP 3.5Cx300 sqmm-Al In Air 0.13 0.07 455 1 1 1 1 1 0.84 1 0.84 382.20 22 217.20 1 1.0 217.2 0.8 0.415 377.7 1.5 564.3 630 382.20 0.50 0.50 1.01 OK OK
SS1, MPCC-5 PANEL-1

1 PUMP PANEL-1 PUMP-1 3.5Cx95 sqmm-Al In Air 0.41 0.07 221 1 1 1 1 1 0.84 1 0.84 185.64 333 60.00 1 1.0 60.0 0.8 0.415 104.3 1.5 155.9 250 185.64 5.39 5.39 1.78 NOT OK OK

2 PUMP PANEL-1 PUMP-2 3.5Cx95 sqmm-Al In Air 0.41 0.07 221 1 1 1 1 1 0.84 1 0.84 185.64 390 60.00 1 1.0 60.0 0.8 0.415 104.3 1.5 155.9 250 185.64 6.31 6.31 1.78 NOT OK OK

3 PUMP PANEL-1 PUMP-3 3.5Cx185 sqmm-Al In Air 0.21 0.07 337 1 1 1 1 1 0.84 1 0.84 283.08 649 60.00 1 1.0 60.0 0.8 0.415 104.3 1.5 155.9 250 283.08 5.97 5.97 2.71 NOT OK OK

400A FEEDER @ PUMP 3.5Cx120 sqmm-Al In Air 0.32 0.07 257 1 1 1 1 1 0.84 1 0.84 215.88 50 120.00 1 1.0 120.0 0.8 0.415 208.7 1.5 311.8 400 215.88 1.31 1.31 1.03 OK OK
SS2 PANEL-2

4 PUMP PANEL-2 PUMP-4 3.5Cx150 sqmm-Al In Air 0.26 0.07 292 1 1 1 1 1 0.84 1 0.84 245.28 429 60.00 1 1.0 60.0 0.8 0.415 104.3 1.5 155.9 250 245.28 4.75 4.75 2.35 OK OK

5 PUMP PANEL-2 PUMP-5 3.5Cx95 sqmm-Al In Air 0.41 0.07 221 1 1 1 1 1 0.84 1 0.84 185.64 223 60.00 1 1.0 60.0 0.8 0.415 104.3 1.5 155.9 250 185.64 3.61 3.61 1.78 OK OK

320KVA DG DG PANEL 3.5Cx185 sqmm-Al In Air 0.21 0.07 337 1 1 1 1 1 0.84 1 0.84 283.08 48 150.00 1 1.0 150.0 0.8 0.415 260.9 1.5 389.7 630 283.08 1.10 1.10 1.09 OK OK

1 DG PANEL PUMP-1 3.5Cx120 sqmm-Al In Air 0.32 0.07 257 1 1 1 1 1 0.84 1 0.84 215.88 690 30.00 1 1.0 30.0 0.8 0.415 52.2 1.5 77.9 125 215.88 4.54 4.54 4.14 OK OK

2 DG PANEL PUMP-2 4Cx25 sqmm-Al In Air 1.54 0.08 96 1 1 1 1 1 0.84 1 0.84 80.64 140 30.00 1 1.0 30.0 0.8 0.415 52.2 1.5 77.9 125 80.64 3.90 3.90 1.55 OK OK

3 DG PANEL PUMP-3 4Cx25 sqmm-Al In Air 1.54 0.08 96 1 1 1 1 1 0.84 1 0.84 80.64 190 30.00 1 1.0 30.0 0.8 0.415 52.2 1.5 77.9 125 80.64 5.30 5.30 1.55 NOT OK OK

4 DG PANEL PUMP-4 3.5Cx70 sqmm-Al In Air 0.57 0.07 179 1 1 1 1 1 0.84 1 0.84 150.36 466 30.00 1 1.0 30.0 0.8 0.415 52.2 1.5 77.9 125 150.36 5.05 5.05 2.88 NOT OK OK

5 DG PANEL PUMP-5 3.5Cx120 sqmm-Al In Air 0.32 0.07 257 1 1 1 1 1 0.84 1 0.84 215.88 718 30.00 1 1.0 30.0 0.8 0.415 52.2 1.5 77.9 125 215.88 4.72 4.72 4.14 OK OK

SS1 SS2 3Cx240 sqmm-Al In Air 0.16 0.07 399 1 1 1 1 1 0.84 1 0.84 335.16 370 850.00 2 1.0 850.0 0.8 33 18.6 1.5 2208.3 126 670.32 0.24 0.24 36.06 OK OK
HCL CAMPUS
Title : CABLE SCHEDULE
Building : HCL CAMPUS

No.of CONNECT CONNECTED LOAD TOTAL CABLE TOTAL CABLE


Sl.No FROM TO CABLE DESCRIPTION ED LOAD CABLE LENGTH LENGTH (10%
Runs (CL) TERMINATION
(CL) MARGIN)

630A FEEDER @ SS1, PUMP PANEL-1 3.5Cx300 sqmm-Al 1 217 217 22 24 2


MPCC-5
1 PUMP PANEL-1 PUMP-1 3.5Cx95 sqmm-Al 1 60 60 333 366 2
2 PUMP PANEL-1 PUMP-2 3.5Cx95 sqmm-Al 1 60 60 390 429 2
3 PUMP PANEL-1 PUMP-3 3.5Cx185 sqmm-Al 1 60 60 649 714 2
400A FEEDER @ SS2 PUMP PANEL-2 3.5Cx120 sqmm-Al 1 120 120 50 55 2
4 PUMP PANEL-2 PUMP-4 3.5Cx150 sqmm-Al 1 60 60 429 472 2
5 PUMP PANEL-2 PUMP-5 3.5Cx95 sqmm-Al 1 60 60 223 245 2
320KVA DG DG PANEL 3.5Cx185 sqmm-Al 1 150 150 48 53 2
1 DG PANEL PUMP-1 3.5Cx120 sqmm-Al 1 30 30 690 759 2
2 DG PANEL PUMP-2 4Cx25 sqmm-Al 1 30 30 140 154 2
3 DG PANEL PUMP-3 4Cx25 sqmm-Al 1 30 30 190 209 2
4 DG PANEL PUMP-4 3.5Cx70 sqmm-Al 1 30 30 466 513 2
5 DG PANEL PUMP-5 3.5Cx120 sqmm-Al 1 30 30 718 790 2
SS1 SS2 3Cx240 sqmm-Al 2 850 850 370 814 4
CABLE LENGTH TERMINATION
120sqmm 1458 6
150sqmm 429 2
185sqmm 697 4
240sqmm 814 2
300sqmm 22 2
70sqmm 466 2
95sqmm 946 6
25sqmm 330 4