C 421EB Sentri
C 421EB Sentri
SENTRI
The Sentri provides a total solution and coordination with 40 trip
levels from 100 mA up to 1200 A. This versatile relay can be used
in both solidly grounded and resistance grounded systems.
Too often, systems are protected with just one relay on the main
service breaker, which leads to power interruption of the entire
service. Consequently, in an effort to minimize disruptions, the
protection on the main breaker is often set to maximum pickup
and delay settings, or worse, disconnected entirely. This can lead
to substantial equipment damage, due to increased clearing time.
Minimizing damage, downtime and maintaining service, I-Gard
provides the Sentri relay with integral zone selective instantaneous
protection to protect systems, at LV and MV system levels, with
optimized coordination. Maximum protection with minimum service
disruption.
unparalleled protection
In addition to ground fault, the Sentri
relay provides three optical sensor
inputs. Optical inputs monitor for arc
flash upon which the relay trips with
under 1ms. Three separate trip relays
correspond to the three flash sensor
inputs. These three relays are a
combination of solid state technology
which can achieve trip speeds of less
than 1ms as well as dry contact relays
used as a backup.
Sentri light sensors Ground fault protection & arc flash mitigation built into 1 relay
To be used on solidly grounded or resistance grounded systems
0.1 A to 1200 A trip settings
Can connect to 3 self-monitoring arc flash sensors
Less than 1ms trip time on arc flash
Solid state relays with mechanical relay backup
I-Gard mGARD-SYM Pre-trip relay for indication prior to main relay tripping
1 A and 5 A CT inputs as well as ZSCS inputs for sensitive protection
Monitor current with mGARD-SYM display
Modbus capability with mGARD-SYM display
ZSIP Zone Selective Instantaneous Protection
The Sentri can be used to monitor
leakage current and provide
indication when that current
exceeds a pre-set level.
The relay can also be connected
to an mGARD-SYM remote
indicator (with Modbus
connectivity) for remote indication,
test, reset, and setup.
Where continuity of service is
essential, selective ground fault
protection should be used. A
selective ground fault protection
system is one in which each
disconnecting means is equipped
with a ground fault relay so that
only the one nearest the ground
fault will be tripped. Selective
ground fault protection systems Figure #1: Three level ZSIP
may be either time coordinated
protection (TCP), zone selective
instantaneous protection (ZSIP) or
a combination of both.