Trductor de Presion Gemu

The GEMÜ 4232 is a travel sensor designed for linear actuators, providing position detection for valves. It is available in standard and special versions for use in potentially explosive areas, compliant with ATEX and IECEx standards. The document includes operating instructions, safety information, installation guidelines, and technical specifications for the sensor.

Uploaded by

David Molero
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
34 views20 pages

Trductor de Presion Gemu

The GEMÜ 4232 is a travel sensor designed for linear actuators, providing position detection for valves. It is available in standard and special versions for use in potentially explosive areas, compliant with ATEX and IECEx standards. The document includes operating instructions, safety information, installation guidelines, and technical specifications for the sensor.

Uploaded by

David Molero
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

GEMÜ 4232

Travel sensor for linear actuators

EN Operating instructions

further information
webcode: GW-4232
All rights including copyrights or industrial property rights are expressly reserved.
Keep the document for future reference.
© GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG
31.05.2021

GEMÜ 4232 2 / 20 www.gemu-group.com


Contents

1 General information .................................................. 4


1.1 Information .......................................................... 4
1.2 Symbols used ...................................................... 4
1.3 Warning notes ..................................................... 4
2 Safety information .................................................... 5
3 Product description ................................................... 5
3.1 Construction ........................................................ 5
3.2 Description ........................................................... 5
3.3 Function ............................................................... 5
4 Intended use ............................................................. 6
4.1 Product without special function X or Z ............ 6
4.2 Product with special function X ......................... 6
4.3 Product with special function Z ......................... 6
5 Order data ................................................................. 7
6 Technical data .......................................................... 8
7 Dimensions ............................................................... 11
8 Manufacturer's information ....................................... 12
8.1 Delivery ................................................................ 12
8.2 Scope of delivery ................................................. 12
8.3 Packaging ............................................................ 12
8.4 Transport ............................................................. 12
8.5 Storage ................................................................. 12
9 Installation ................................................................ 12
9.1 Linear travel sensor mounting kit assembly ..... 12
9.2 Preparations for assembly to the valve ............. 13
9.3 Installing the adapter .......................................... 13
9.4 Installing the travel sensor on the actuator ....... 13
9.5 Connection to the positioner .............................. 14
10 Electrical connection ................................................. 14
10.1 Design with open wires with cable ends (code
0000) .................................................................... 14
10.2 Design with M12 cable connector (code 4001) 14
10.3 Potential equalisation for special version code
X and Z ................................................................. 15
11 Installation instructions for explosion-protected
design ....................................................................... 15
11.1 Installation instructions for special version X
(wiring instructions for intrinsic safety) ............. 15
11.2 Installation instructions for special version Z
(wiring instructions for non-incendive opera-
tion) ...................................................................... 16
12 Disposal .................................................................... 16
13 Returns ..................................................................... 16
14 Declaration of Incorporation according to 2006/42/
EC (Machinery Directive) ........................................... 17
15 EU Declaration of Conformity in accordance with
2014/34/EU (ATEX) ................................................... 18
16 EU Declaration of Conformity in accordance with
2014/34/EU (ATEX) ................................................... 19

www.gemu-group.com 3 / 20 GEMÜ 4232


1 General information

1 General information 1.3 Warning notes


Wherever possible, warning notes are organised according to
1.1 Information
the following scheme:
• The descriptions and instructions apply to the standard ver-
sions. For special versions not described in this document SIGNAL WORD
the basic information contained herein applies in combina-
Possible Type and source of the danger
tion with any additional special documentation.
symbol for the
Possible consequences of non-observance.
• Correct installation, operation, maintenance and repair work specific
ensure faultless operation of the product. danger Measures for avoiding danger.

• Should there be any doubts or misunderstandings, the Ger-


Warning notes are always marked with a signal word and
man version is the authoritative document.
sometimes also with a symbol for the specific danger.
• Contact us at the address on the last page for staff training
The following signal words and danger levels are used:
information.

1.2 Symbols used


DANGER
Imminent danger!
The following symbols are used in this document:
▶ Non-observance can cause death or
Symbol Meaning severe injury.
Tasks to be performed
Response(s) to tasks
– Lists
WARNING
Potentially dangerous situation!
▶ Non-observance can cause death or
severe injury.

CAUTION
Potentially dangerous situation!
▶ Non-observance can cause moderate
to light injury.

NOTICE
Potentially dangerous situation!
▶ Non-observance can cause damage to
property.

The following symbols for the specific dangers can be used


within a warning note:

Symbol Meaning
Danger of explosion

GEMÜ 4232 4 / 20 www.gemu-group.com


3 Product description

2 Safety information 3 Product description


The safety information in this document refers only to an indi-
3.1 Construction
vidual product. Potentially dangerous conditions can arise in
combination with other plant components, which need to be
considered on the basis of a risk analysis. The operator is re- 1
sponsible for the production of the risk analysis and for com- 2
pliance with the resulting precautionary measures and re-
gional safety regulations. 3
The document contains fundamental safety information that
must be observed during commissioning, operation and main-
tenance. Non-compliance with these instructions may cause:
• Personal hazard due to electrical, mechanical and chemical 4
5
effects.
• Hazard to nearby equipment. 6
• Failure of important functions.
• Hazard to the environment due to the leakage of dangerous 7
materials.
The safety information does not take into account:
• Unexpected incidents and events, which may occur during
installation, operation and maintenance. Item Name Materials

• Local safety regulations which must be adhered to by the 1 Cable LIYY


operator and by any additional installation personnel. 2 Cover Depending on design, PP
30% glass fibre rein-
Prior to commissioning: forced, PVDF or PP
1. Transport and store the product correctly. 3 Housing Depending on design, an-
2. Do not paint the bolts and plastic parts of the product. odized aluminium, PVDF
or PP
3. Carry out installation and commissioning using trained
personnel. 4 Threaded piece Depending on design, an-
odized aluminium (SS for
4. Provide adequate training for installation and operating
explosion-protected
personnel.
design), PVDF or PP
5. Ensure that the contents of the document have been fully
understood by the responsible personnel. 5 Bushing with internal lip Bushing PP, lip ring PUR
ring
6. Define the areas of responsibility.
6 Spindle 1.4104
7. Observe the safety data sheets.
7 Mounting kit Material depending on
8. Observe the safety regulations for the media used.
design (specific to valve)

During operation:
3.2 Description
9. Keep this document available at the place of use.
The GEMÜ 4232 travel sensor is intended for the attachment
10. Observe the safety information.
to valves with linear actuators and is used to determine the
11. Operate the product in accordance with this document. valve position. It is used as a travel sensor for the
12. Operate the product in accordance with the specifications. GEMÜ 1434 µPos, GEMÜ 1435 ePos and GEMÜ 1436 cPos in-
13. Maintain the product correctly. telligent positioners, which can be connected using either the
open cable ends or an M12 cable connector (depending on
14. Do not carry out any maintenance work and repairs not de-
the design and/or selection of the controller).
scribed in this document without consulting the manufac-
turer first. 3.3 Function
In cases of uncertainty: GEMÜ 4232 is a travel sensor for detecting the position of
globe and diaphragm valves with linear actuators. It is a po-
15. Consult the nearest GEMÜ sales office.
tentiometer with a passive resistance element (support ma-
terial and a resistance track of conductive plastic) and a pass-
ive wiper.
It serves as a position sensor for the intelligent GEMÜ 1434,
GEMÜ 1435 and GEMÜ 1436 positioners.

www.gemu-group.com 5 / 20 GEMÜ 4232


4 Intended use

4 Intended use 4.3 Product with special function Z


The product with the special version Z order option is inten-
DANGER ded for use in potentially explosive areas of zone 2 with
Danger of explosion gases, mists or vapours and zone 22 with combustible dusts
▶ Danger of death or severe injury. in accordance with EU Directive 2014/34/EU (ATEX).
● Only use the product in potentially ex- The product has the following explosion protection marking:
plosive zones confirmed in the declara-
tion of conformity. ATEX
Gas: II 3G Ex ec nC IIC T4 Gc X
WARNING
Dust: II 3D Ex tc IIIC T80°C Dc X
Improper use of the product
The product has been developed in compliance with the fol-
▶ Risk of severe injury or death.
lowing harmonised standards:
▶ Manufacturer liability and guarantee will be void.
• EN IEC 60079-0:2018
● Only use the product in accordance with the operating
conditions specified in the contract documentation and in • EN IEC 60079-7:2015/A1:2018
this document. • EN IEC 60079-15:2019
The product GEMÜ 4232 is designed for fitting to a GEMÜ • EN 60079-31:2014
valve in order to detect the position of linear actuators elec- Use of the product is permissible in the following ambient
trically. The product works as an analogue travel sensor sys- temperature ranges: -10 °C to +70 °C
tem based on a resistance value (potentiometer) that The explosion-protected design is marked with index Z.
changes linearly with the stroke position. The product is posit-
For use in potentially explosive areas, the following conditions
ively connected with the actuator spindle by means of a
or operation limits must be observed:
mounting kit (spring, operating bush). The measurement sig-
nals (resistance value) can be checked using the electrical Special conditions for use:
connections. • The housing must be installed protected from mechanical
influences.
4.1 Product without special function X or Z
• Connection cables and connectors must be protected from
The product is not intended for use in potentially explosive damage.
areas. RFID chips must not be read out in potentially explosive areas.

4.2 Product with special function X


With the special version X order option, the product is inten-
ded for use in potentially explosive areas in zone 1 with gases,
mists or vapours and zone 21 with combustible dusts in ac-
cordance with EU Directive 2014/34/EU (ATEX).
The product has the following explosion protection marking:

ATEX
Gas: II 2G Ex ib IIB T4 Gb
Dust: II 2D Ex ib IIIC T130 °C Db
Certificate: IBExU20ATEX1045
• EN IEC 60079-0:2018
• EN 60079-11:2012

IECEx
Gas: Ex ib IIB T4 Gb
Dust: Ex ib IIIC T130 °C Db
Certificate: IECEx IBE 20.0027 X
The product has been developed in compliance with the fol-
lowing harmonised standards:
• IEC 60079-0:2017 (edition 7)
• EN 60079-11:2011 (edition 6)
Use of the product is permissible in the following ambient
temperature ranges: -10 °C to +70 °C
The explosion-protected design is marked with index X.

GEMÜ 4232 6 / 20 www.gemu-group.com


5 Order data

5 Order data
The order data provide an overview of standard configurations.
Please check the availability before ordering. Other configurations available on request.
The travel length depends on the necessary mounting kit.
Note: A valve specific mounting kit is required for assembly. For designing the mounting kit, the valve type, nominal size, control
function and actuator size must be stated.

Order codes
1 Type Code 6 Cable length Code
Travel sensor for linear actuators 4232 2 m cable, 3-pin 02M0
5 m cable, 3-pin 05M0
2 Fieldbus Code
10 m cable, 3-pin 10M0
Without 000
20 m cable, 3-pin 20M0
3 Accessory Code
7 Cable connection Code
Accessory Z
Open wires with cable ends 0000
4 Housing material Code M12 cable connector, straight 4001
PP, polypropylene 05
8 Special version Code
Anodized aluminium 14
Without
PVDF, polyvinylidene fluoride 20
ATEX/IECEx ib for zone1/21 X
5 Travel length Code intrinsic safety ignition protection
Potentiometer, 30 mm length 030 ATEX nC,eC/tC for zone 2/22 Z
Potentiometer, 50 mm length 050 Ex eC, nC, tC ignition protection
Potentiometer, 75 mm length 075

Order example
Ordering option Code Description
1 Type 4232 Travel sensor for linear actuators
2 Fieldbus 000 Without
3 Accessory Z Accessory
4 Housing material 14 Anodized aluminium
5 Travel length 030 Potentiometer, 30 mm length
6 Cable length 05M0 5 m cable, 3-pin
7 Cable connection 0000 Open wires with cable ends
8 Special specification Without

www.gemu-group.com 7 / 20 GEMÜ 4232


6 Technical data

6 Technical data
6.1 Temperature
Ambient temperature: -10 — 80 °C
Special version X and Z: -10 to 70 °C

Storage temperature: -10 — 80 °C

6.2 Product compliance


Explosion protection: ATEX (2014/34/EU) and IECEx, order code special version X or Z

Code X marking: Intrinsic safety (Ex i) ignition protection


ATEX
Gas: II 2G Ex ib IIB T4 Gb
Dust: II 2D Ex ib IIIC T130 °C Db
Certificate: IBExU20ATEX1045
IECEx
Gas: Ex ib IIB T4 Gb
Dust: Ex ib IIIC T130 °C Db
Certificate: IECEx IBE 20.0027 X
Operation in potentially explosive areas only in conjunction with a safety barrier complying with
ATEX which is designed for operating passive resistor elements or potentiometers and for which
separate operating instructions apply.
In addition, the supplied limit resistor must be installed in the wiper cable between the safety barrier
and travel sensor.

Code Z marking: Increased safety (Ex e) ignition protection in combination with non-incendive (Ex n) and (dust)
protection by enclosure (Ex t)
ATEX
Gas: II 3G Ex ec nC IIC T4 Gc X
Dust: II 3D Ex tc IIIC T80°C Dc X

Potential equalisation: Special version code X and Z


The travel sensor must be integrated into the system's potential equalization via the pre-assembled
earthing kit.
The potential equalization connection's maximum permissible resistance limit value is defined as R
≤ 100 Ω.
During the plant-specific maintenance cycle, the potential equalization connection must be checked
to ensure that it has been connected correctly and that the maximum resistance limit value has not
been exceeded.

GEMÜ 4232 8 / 20 www.gemu-group.com


6 Technical data

6.3 Mechanical data


Protection class: IP 64 in accordance with EN 60529 – housing material anodized aluminium (code
14)
IP 65 in accordance with EN 60529 – housing material PVDF, PP (code 20)
Weight: Travel sensor length Material
Aluminium (code 14) PP (code 05
PVDF (code 20)
Standard Special version Standard
(code X and Z)
30 mm (Code 030) 110 170 140
50 mm (Code 050) 125 180 150
75 mm (Code 075) 140 190 160

Weight in g
Weight specifications include 2 m of cable with open ends and cable ends.
Additional weight in each case:
25 g per additional metre of cable
20 g with M12 cable connector (cable connection code 4001)

Service life: 10 x 106 operations

Installation position: Optional

Min. stroke: Dependent on the connected device

Max. stroke: Travel sensor version


Code 030 Code 050 Code 075
30 mm 50.2 mm 74.4 mm

www.gemu-group.com 9 / 20 GEMÜ 4232


6 Technical data

6.4 Electrical data


Duty cycle: Continuous duty

Electrical connection: Open wires with multicore cable ends (code 0000)
M12 cable plug A-coded, straight, 5-pin, plastic (code 4001)

Supply voltage Uv: max. 42 V DC


(does not apply to code X special version – the intrinsically safe characteristic values apply here)
The travel sensor is generally supplied by the connected positioners (GEMÜ 1434, 1435 or 1436).

Travel sensor: Travel sensor version


Code 030 Code 050 Code 075
Linearity: ± 0.2 % ± 0.25 % ± 0.1 %
Repeatability: > 10 µm > 10 µm > 10 µm
Nominal resist- 3 kΩ 5 kΩ 5 kΩ
ance:

Safety-relevant values: Special version code X


A)
Ui = 30 V
li = 100 mA
Pi = 700 mW
These values refer to the two supply cables (white and green wires), which need to be protected
with a two-channel safety barrier.
B)
Ui = 16 V
li = 200 mA
Pi = 600 mW
These values refer to the wiper cable (brown wire), which needs to be protected with a single-chan-
nel safety barrier. The supplied limit resistor must also be wired.

GEMÜ 4232 10 / 20 www.gemu-group.com


7 Dimensions

7 Dimensions
7.1 Housing material aluminium
ø 39,0*
ø 23,5
h

SW 27
10

* Only explosion-protected designs


M16x1 (special version X and Z)

Travel sensor h
length (code) Standard ATEX design (code
Z)
030 62.2 67.2
050 84.2 89.2
075 109.2 114.2

Dimensions in mm

7.2 Housing material PVDF or PP


h
10

M16x1
Ø30

Travel sensor h
length (code)
030 69.6
050 91.6
075 116.6

Dimensions in mm

www.gemu-group.com 11 / 20 GEMÜ 4232


8 Manufacturer's information

8 Manufacturer's information 8.5 Storage


1. Store the product free from dust and moisture in its ori-
8.1 Delivery
ginal packaging.
● Check that all parts are present and check for any damage 2. Avoid UV rays and direct sunlight.
immediately upon receipt.
3. Do not exceed the maximum storage temperature (see
The product's performance is tested at the factory. The scope chapter "Technical data").
of delivery is apparent from the dispatch documents and the
4. Do not store solvents, chemicals, acids, fuels or similar
design from the order number.
fluids in the same room as GEMÜ products and their spare
8.2 Scope of delivery parts.

9 Installation
1
9.1 Linear travel sensor mounting kit assembly

CAUTION
5
Pretensioned spring!
2 ▶ Damage to the device.
● Slowly release the tension in the spring.
3
CAUTION
4 Do not scratch the spindle!
Item Name ▶ A damaged spindle surface may cause failure of the
travel sensor.
1 Travel sensor
2 Spindle Item Name
Items 3–6 are not included in the travel sensor's 1 Travel sensor
scope of supply, but are part of a mounting kit that 2 Spindle
needs to be ordered separately.
3 Spring
3 Spring
4 Operating bush
4 Operating bush
5 Guide bush*
5 Guide bush*
6 Threaded adapter**
6 Threaded adapter* (not pictured)
*Enclosed depending on design
*Enclosed depending on design
**If a threaded adapter is included, it must be screwed into
GEMÜ 4232 is assembled using a mounting kit 4243S01Z... the actuator top of the process valve
consisting of a spring, an operating bush and a threaded ad-
apter. The mounting kit is specific to the valve and must be
ordered separately.
1
8.3 Packaging
The product is packaged in a cardboard box which can be re- 5 1
cycled as paper.
1 2 5
8.4 Transport
3 2
1. Only transport the product by suitable means. Do not drop.
Handle carefully.
3
2 4
2. After the installation dispose of transport packaging ma- 4
terial according to relevant local or national disposal regu-
lations / environmental protection laws. 1. Pull the spindle 2 out of the travel sensor 1.
2. If included, push the guide bush 5 taper over the spindle 2
first.
3. Push the spring 3 over the spindle 2 and secure with the
operating bush 4.
4. Tighten the operating bush 4 by turning it clockwise.

GEMÜ 4232 12 / 20 www.gemu-group.com


9 Installation

• Push in the spindle until it pushes against the spring and 9.4 Installing the travel sensor on the actuator
then slowly release the pressure on the spring.
NOTICE
9.2 Preparations for assembly to the valve
Wrong mounting kit
1. Move the actuator to the open position. ▶ If the travel sensor cannot be pushed in all the way, the
2. Remove optical position indicator 2 and / or protective cap spring is blocking the path because the mounting kit is
1 from the actuator top. too long.
▶ If you cannot feel any initial spring tension, the mounting
1 kit is too short.
2
9.4.1 Installing the travel sensor with plastic housing

1 CAUTION
Travel sensor failure!
A
▶ With threaded adapter: Tightening on the (round) travel
sensor housing can cause the travel sensor to fail. Only
use the intended adapter spanner flat for tightening.
9.3 Installing the adapter
With some mounting kits it is necessary to install an adapter
as well. This adapter is enclosed with the required mounting
kits. Valves with a normally open and double-acting control
function (code 2+3) also include additional O-rings (1+2) (see
“Installing the adapter for metal housings (housing material
code 14)“, page 13).
9.3.1 Installing the adapter for plastic housings (housing
material code 05 and 20)

CAUTION
Tightening with tools can cause the travel sensor to fail!

1. Move the actuator into the OPEN position.


2. Guide the assembled travel sensor as far as it will go into
the actuator opening and screw it in clockwise against the
initial spring tension.
3. Without threaded adapter: Gently tighten the travel sensor
1. Gently screw the adapter onto the travel sensor by hand on the round housing by hand (until you feel resistance).
(until you feel resistance). Then continue turning it another 30–40°.
2. Then continue turning it another 30–40°. With threaded adapter: Carefully tighten the travel sensor
on the adapter spanner flat with a suitable WAF 27 open-
3. Check the correct function and recovery.
ended spanner
Press in the spindle as far as possible by hand, then slowly
(tighten with a max. torque of 2.5 Nm – if no torque can
release the spring until the travel sensor spindle is in the
be measured, turn for max. another 90° once you feel res-
initial position. If the spring is not fully released, the ad-
istance).
apter needs to be undone anti-clockwise and the proced-
ure repeated until the spindle is safely and fully pushed
out of the spring.
9.3.2 Installing the adapter for metal housings (housing
material code 14)
1
3

1. Move the actuator to the closed position.


2. If enclosed: Place O-rings 1 and 2 into adapter 3.
3. Screw adapter 3 into the actuator opening as far as it will
go and tighten.

www.gemu-group.com 13 / 20 GEMÜ 4232


10 Electrical connection

9.4.2 Installing the travel sensor with metal housing 10 Electrical connection
10.1 Design with open wires with cable ends (code
0000)

WH
SW27
BN

GN

80
GN BN WH

This design is suitable for connecting to the GEMÜ 1435 posi-


tioner (except the GEMÜ 1435 design with M12 cable con-
1. Move the actuator into the OPEN position.
nector).
2. Guide the assembled travel sensor into the actuator open-
ing or the adapter as far as it will go and working against 10.2 Design with M12 cable connector (code 4001)
the initial spring tension, screw it into place clockwise.
M12 cable connector
3. Tighten the travel sensor using a suitable WAF 27 open- A-coded, straight, 5-pin, plastic
ended spanner.
1- WH 2
9.5 Connection to the positioner
2 - BN 3 5 1
Connect the travel sensor with the GEMÜ 1434, GEMÜ 1435 or
GEMÜ 1436 positioner (see “Electrical connection“, page 14). 4
3 - GN
For use in potentially explosive areas, observe the following
installation instructions (see “Installation instructions for ex-
plosion-protected design“, page 15).
This design is suitable for connecting to the GEMÜ 1434,
1436 or 1435 positioner with the M12 cable connector design.

NOTICE
▶ For special versions X and Z:
The M12 connector must only be connected in the safe
area (outside the potentially explosive zone). The en-
closed M12 cable connector is only intended for connec-
tion to the positioner (the positioners (GEMÜ 1434, 1435
and 1436) are not explosion-protected and must only be
installed outside of the potentially explosive zone).

NOTICE
▶ For special version X:
The electrical connection of the travel sensor to the posi-
tioner must be routed via safety barriers (a limit resistor
must also be wired) (see “Installation instructions for spe-
cial version X (wiring instructions for intrinsic safety)“,
page 15).
In order to wire the safety barriers appropriately, the con-
nection cable for the travel sensor can be cut to length at
the point at which the safety barriers are being installed
(generally a DIN rail) and the end piece including the fitted
M12 cable connector can be used to continue wiring from
the safety barriers to the installation position for the posi-
tioner.

GEMÜ 4232 14 / 20 www.gemu-group.com


11 Installation instructions for explosion-protected design

10.3 Potential equalisation for special version code X 11 Installation instructions for explosion-protected
and Z design
NOTICE DANGER
▶ For safe use in potentially explosive areas, the product Danger of explosion
must be integrated into the system's potential equalisa- ▶ Risk of severe injury or death.
tion. ● Only versions that have been approved
according to their technical data may
be used in potentially explosive envir-
onments.
The standard version of the product (without special function
X or Z) must not be used in potentially explosive zones.
1. Danger from sparking. Never disconnect the connection
cables when live.
2. Do not connect or disconnect the device until the power
has been switched off or the area has been classified as
non-hazardous.

WARNING
1. Connect a suitable cable lug (M4) and cable to the marked
earthing connection Danger of explosion
▶ Non-observance can cause death or
2. Integrate the GEMÜ 4232 into the system's potential
severe injury.
equalisation.
▶ Non-observance will also void the
The potential equalisation connection's maximum permissible
manufacturer's liability and any war-
resistance limit value is R ≤ 100 Ohm.
ranty claims.
Check that the potential equalisation connection is set up cor- ● GEMÜ 1434, GEMÜ 1435 or GEMÜ
rectly and that the resistance limit value is not exceeded as 1436 must not be installed or operated
part of the plant-specific maintenance cycle. in potentially explosive zones.

11.1 Installation instructions for special version X


(wiring instructions for intrinsic safety)

DANGER
Danger of explosion
▶ Risk of severe injury or death.
● The travel sensor with special function
X may only be used in potentially ex-
plosive zones in combination with
compliant safety barriers.
These safety barriers need to have
been designed specifically for use with
passive resistor elements or poten-
tiometers and must have their own op-
erating instructions. The supplied limit
resistor must also be wired.

NOTICE
▶ The correct use of safety barriers creates an intrinsically
safe electric circuit between the travel sensor and the
safety barriers; the travel sensor cable can be labelled ac-
cordingly on the system side.
Installation standard IEC 60079-14 for potentially explos-
ive areas must be observed here.
The limit resistor kit supplied with the product comprises a
mounting rail module, a component holder, a lateral separator
plate and a specified fixed resistor.

www.gemu-group.com 15 / 20 GEMÜ 4232


12 Disposal

The kit must be assembled as illustrated below and must be 11.2 Installation instructions for special version Z
mounted close to the safety barriers, outside the potentially (wiring instructions for non-incendive operation)
explosive area, and wired in accordance with the following
wiring diagram. Special conditions for use
• The housing must be installed protected from mechanical
influences.
• Connection cables and connectors must be protected from
damage.
RFID chips must not be read out in potentially explosive areas.

12 Disposal
1. Pay attention to adhered residual material and gas diffu-
sion from penetrated media.
2. Dispose of all parts in accordance with the disposal regu-
lations/environmental protection laws.

13 Returns
Legal regulations for the protection of the environment and
personnel require that the completed and signed return deliv-
ery note is included with the dispatch documents. Returned
goods can be processed only when this note is completed. If
Electrical installation in accordance with the following wiring
no return delivery note is included with the product, GEMÜ
diagram:
cannot process credits or repair work but will dispose of the
goods at the operator's expense.
Safe area EX area
Safety barrier A Potentiometer 4232
1. Clean the product.
Item no.: 99014203
2. Request a return delivery note from GEMÜ.
3. Complete the return delivery note.
4. Send the product with a completed return delivery note to
Connection to
GEMÜ 1434 μPos, Safety barrier B GEMÜ.
GEMÜ 1435 ePos, Article no.: 99014207
GEMÜ 1436 cPos
RS

Basic wiring example, Ensure that the travel sensor is


the relevant safety connected to the potential equalization.
regulations in the area of
application must be followed.

● Connect the travel sensor 4232 to GEMÜ 1434, GEMÜ


1435 or GEMÜ 1436 positioners via suitable (compliant)
safety barriers.
The limit resistor Rs supplied with the product must be
connected in the brown wiper cable between the safety
barrier and travel sensor.
Ensure that the potential equalization of the safety barri-
ers is not connected in a way that is interference-prone.

NOTICE
▶ The safety barriers shown are an example. Other safety
barriers with similar properties that comply with the in-
trinsically safe characteristic values can be used on-site.
Special conditions for use
• The housing must be installed protected against mechan-
ical influences.
• Connection cables and connectors must be protected from
damage.
RFID chips must not be read out in potentially explosive areas.

GEMÜ 4232 16 / 20 www.gemu-group.com


14 Declaration of Incorporation according to 2006/42/EC (Machinery Directive)

14 Declaration of Incorporation according to 2006/42/EC (Machinery Directive)

Declaration of Incorporation
according to the EC Machinery Directive 2006/42/EC, Annex II, 1.B for partly
completed machinery

We, GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG


Fritz-Müller-Straße 6-8
74653 Ingelfingen-Criesbach, Germany
declare that the following product
Make: GEMÜ Travel sensor for linear actuators
Project number: 4232
Commercial name: GEMÜ 4232
meets the following essential requirements of the Machinery Directive 2006/42/EC:
1.3, 1.3.7, 1.5.1, 1.5.2, 1.5.16, 1.6.1, 2.2.1, 3.2.2, 3.3.4, 3.4, 3.4.3
We also declare that the specific technical documentation has been compiled in accordance with part B of Annex VII.
The manufacturer or his authorised representative undertake to transmit, in response to a reasoned request by the national au-
thorities, relevant information on the partly completed machinery. This transmission takes place:
Electronically
Authorised documentation officer GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG
Fritz-Müller-Straße 6-8
74653 Ingelfingen, Germany
This does not affect the industrial property rights!
Important note! The partly completed machinery may be put into service only if it was determined, where appropriate, that the
machinery into which the partly completed machinery is to be installed meets the provisions of this Directive.

2020-12-11

Joachim Brien
Head of Technical Department

www.gemu-group.com 17 / 20 GEMÜ 4232


15 EU Declaration of Conformity in accordance with 2014/34/EU (ATEX)

15 EU Declaration of Conformity in accordance with 2014/34/EU (ATEX)

EU Declaration of Conformity
in accordance with 2014/34/EU (ATEX)

We, GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG


Fritz-Müller-Straße 6-8
74653 Ingelfingen-Criesbach, Germany
declare that the product listed below complies with the requirements of directive 2014/34/EU for intended use in potentially ex-
plosive areas.
Description of the product: GEMÜ 4232 Code X special version (4232000Z14... ...X)

Explosion protection designation: Gas: II 2G Ex ib IIB T4 Gb


Dust: II 2D Ex ib IIIC T130 °C Db
Certificate: IBExU20ATEX1045

Explanations: For special conditions or operation limits see chapter "Correct use" in the operating
instructions.

The Essential Safety and Health Requirements are met by compliance with the standards listed below that are applicable for the
above mentioned product:
• EN IEC 60079-0:2018
• EN 60079-11:2012

2021-05-12

Joachim Brien
Head of Technical Department

GEMÜ 4232 18 / 20 www.gemu-group.com


16 EU Declaration of Conformity in accordance with 2014/34/EU (ATEX)

16 EU Declaration of Conformity in accordance with 2014/34/EU (ATEX)

EU Declaration of Conformity
in accordance with 2014/34/EU (ATEX)

We, GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG


Fritz-Müller-Straße 6-8
74653 Ingelfingen-Criesbach, Germany
declare that the product listed below complies with the requirements of directive 2014/34/EU for intended use in potentially ex-
plosive areas.
Description of the product: GEMÜ 4232 Code Z special version (4232000Z14... ...Z)

Explosion protection designation: Gas: II 3G Ex ec nC IIC T4 Gc X


Dust: II 3D Ex tc IIIC T80°C Dc X

Explanations: For special conditions or operation limits see chapter "Correct use" in the operating
instructions.

The Essential Safety and Health Requirements are met by compliance with the standards listed below that are applicable for the
above mentioned product:
• EN IEC 60079-0:2018
• EN IEC 60079-7:2015/A1:2018
• EN IEC 60079-15:2019
• EN 60079-31:2014

2021-05-11

Joachim Brien
Head of Technical Department

www.gemu-group.com 19 / 20 GEMÜ 4232


Subject to alteration
GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG

*88760848*
Fritz-Müller-Straße 6–8, 74653 Ingelfingen-Criesbach, Germany 05.2021 | 88760848
Phone +49 (0) 7940 1230 · [email protected]
www.gemu-group.com