C-03_paper
C-03_paper
Abstract. In ammonia reactor system, a feed-effluent heat exchanger (FEHE) is typically installed to
utilize reaction-generated heat to heat the reactor’s feed. Utilizing energy from exothermic reaction
to the incoming feed stream is often called “autothermal operation”. Despite the advantage of
FEHE, there is a risk of utilizing FEHE in a reactor system such as instability of process
temperature or known as hysteresis. Hysteresis phenomena in chemical process could cause
operational problems, for example it could damage the integrity of the equipment’s material. This
paper aims to evaluate the dynamic behavior of a single-bed ammonia reactor with FEHE,
particularly to propose a way to prevent instability within the system. The dynamic simulation of the
single-bed ammonia reactor with FEHE was performed with Aspen HYSYS v8.8. The result of the
simulation result shows that hysteresis phenomenon in the ammonia reactor system occurs when
the feed’s temperature is below a certain value. If the feed temperature reaches that value, the
temperature of the reactor’s outlet oscillates. One of the solution to keep the feed temperature
above that critical value is by installing a trim heater within the system. Based on the simulation,
trim heater installation within the system is able to prevent hysteresis in the system evaluated.
*
Corresponding author: [email protected]
N2 75.6 %
H2 16.3 %
NH3 8.1 %
Total Volume 30 m3
Length 6.11 m
Fig. 3. Simulation scheme of autothermal single-bed ammonia
reactor system with Aspen HYSYS v8.8. Diameter 2.50 m
Wall Thickness 5.00 × 10-3 m
Reactor feed is consisted of nitrogen, hydrogen Void Fraction 0.40
and slightly amount of ammonia which specification is
shown in table 1. Feed stream split into two part, one Reaction equilibrium and kinetics parameter are
part which consist of 75% from total reactor feed shown in equation (1) and table 4 respectively.
amount is transferred to FEHE to be heated by reactor
effluent and the other goes directly to the reactor after (1)
mixed with heated stream from FEHE. Specification of
heat exchanger used as FEHE is shown in table 2.
Table 4. Reaction Kinetics Parameters.
Table 1. Ammonia reactor system feed stream specification.
Parameters Forward Reverse
Temperature 250°C N2 Order 1.0 0
Pressure 163.5 bar H2 Order 1.5 -1.5
Mass Flow 200 ton/hr NH3 Order -1.0 1.0
Composition A 23.62 3.40 × 1013
E 87090 kJ/kmol 198464 kJ/kmol
Fig. 5. Ammonia reactor feed-outlet temperature profile.
A = Arrhenius Constant
E = Activation Energy Based on study case result in figure 4, there are
three main information that could be obtained. First,
from feed-outlet temperature profile generated by
3 Result and Discussion forward step (line 3), the reaction was activated when
the feed temperature is above 290°C. Therefore, when
3.1 Instability phenomenon of single-bed doing the start-up, feed temperature must be set above
ammonia reactor 290°C to initiate the reaction. This temperature is
often refered as “ignition temperature”. Second, from
The stability behavior of the ammonia reactor could
feed-outlet temperature profile generated by backward
be represented by outlet-feed temperature profile.
step (line 1), it is shown that the reaction extinguished
Feed temperature is varied to obtain outlet
when feed temperature is below 230°C. The
temperature by using study case feature in Aspen
temperature value when the reactor extinguished
HYSYS in forward step and backward step. Varying
often reffered as “extinction temperature”. In
reactor inlet temperature is also performed to identify
correlation of reaction’s conversion profile shown in
the feed-outlet temperature profile. Feed-outlet
figure 5, it is better to keep feed temperature low as
temperature profile is shown in figure 4. Relation
the conversion is higher in lower temperature and
between reactor conversion and feed temperature also
conserving the energy for heating the feed stream.
shown in figure 5. This relation was generated by
However, feed temperature must remain above the
varying reactor inlet temperature in such way to get
extinction temperature to make sure the reactor not
the value of feed temperature and reactor conversion.
extinguished. Third, from feed-outlet temperature
profile generated by varying reactor inlet temperature
(line 2), it is shown that there is a transition zone
between ingnition temperature and extinction
temperature. When reactor operated in the “upper
outlet temperature” of the trasition zone, once feed
temperature goes below the extiction temperature, the
outlet temperature would dramatically fall to “lower
outlet temperature”. After that moment, increasing
the feed temperature back to its original value could
not restore outlet temperature directly to “upper
outlet temperature” path. However, the outlet
temperature would follow “lower outlet temperature”
path until feed temperature reach the ignition
temperature. This transition zone that has non-
Fig. 4. Ammonia reactor feed-outlet temperature profile. revesible behavior could result instability of the
process, known as hysteresis.
Furthermore, hysteresis phenomenon could be
identified from dynamic simulation. Feed temperature
was set at 250°C in steady operation condition and
then suddenly dropped down to several temperatures
around the extinction temperature which value is
230°C, reffered as TE. The temperature drops
performed with a step function after the reactor
operated in 1200 seconds. In this simulation, the final
feed temperature would be TE + 5°C, TE and TE - 5°C.
Result of dynamic simulations to identify the
instability behavior are presented in figure 6.
Reactor still in stable condition when feed
temperature dropped from 250°C to TE + 5°C (235°C)
as shown in figure 6(a), although the outlet
temperature was slightly oscillating in the beginning
of temperature drop. Instability phenomenons could
be observed when feed temperature dropped to TE and
TE - 5°C, as shown in figure 6(b) and 6(c) respectively.
After temperature have been dropped, outlet
temperature was roughly oscillating in range of 300 –
570 °C before finally extinguished the reaction. As
shown in the figure 6(b) and 6(c), the obvious
difference of these two instability phenomena is the
duration of outlet temperature oscillating behavior.
Reactor with final temperature of TE had experienced
ocsillating behavior for roughly 9000 seconds, while
the other one was only 5000 seconds.
Huge difference of oscillating temperature could
damage equipment material because of temperature (b)
sudden change that could decrease equipment material
integrity. Unstable operation condition could also
cause problem to the next process; the uncertainty of
the outlet stream specification from the reactor system
may cause problems to the further process.
P-28
Feed
(a)
FEHE
Effluent
Feed
(a)
TRIM HEATER REACTOR
(b)
Fig. 7. Trim heater installation scenario (a) at feed stream line, Fig. 8. Trim heater installation simulation schemes, (a) trim
(b) at reactor inlet stream line heater before the reactor and (b) trim heater before FEHE.
4 CONCLUSION
Reactor that implemented autothermal configuration,
like ammonia reactor, is at risk to become unstable
when the reactor is operating. The instability often
appears as hysteresis, the oscillation of operating
parameter that could lead reactor to extinguish.
Hysteresis could be occurred when reactor inlet
temperature reached certain value that made
conversion of the reactor fall down. Hysteresis in
single-bed ammonia reactor could be prevented by
installing trim heater before stream entered the
reactor or in the reactor system feed stream, before
entering FEHE.
REFERENCES