c.pCO Tips and tricks

The document provides FAQs regarding the c.pCO product, including how to manage pGD1 display sharing, connect the display to c.pCOmini, and details about ModBus RTU Slave usage. It also addresses filesystem operation issues when the application is running and specifies that c.pCO uses Big Endian for ModBus. For further assistance, users are directed to contact support or visit the Carel website.

Uploaded by

sychnew
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views3 pages

c.pCO Tips and tricks

The document provides FAQs regarding the c.pCO product, including how to manage pGD1 display sharing, connect the display to c.pCOmini, and details about ModBus RTU Slave usage. It also addresses filesystem operation issues when the application is running and specifies that c.pCO uses Big Endian for ModBus. For further assistance, users are directed to contact support or visit the Carel website.

Uploaded by

sychnew
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

C.

PCO FAQ

Product Document version Document date

c.pCO 1.0.5 06/11/2019

How is managed pGD1 display sharing between controllers connected


in pLAN?
There are two possible ways:

l In system menu, releasing the display. pGD1 will now display the subsequent c.pCO's
interface (ordered by ascending pLAN address).
1. Press “ALARM + ENTER” for 3 seconds
2. Enter “SETTINGS” menu
3. Enter “PLAN_SETTINGS” menu
4. Set "Release Term" to YES
5. Set “Update Config" to YES

l Using ST calls in c.mask. Check online documentation for more information about.

Example: calling “SetKeySwitch(135);” registers key combination UP+DOWN


to be used as switch. Now when pressing this 2 buttons, the switch is made.
Always use a combination of 2 or more buttons.

Note: Display sharing is possible only if the controllers are connected together through the
pLAN serial network (J11)

For any issue contact [email protected] or visit www.carel.com 1/3


c.pCO FAQ Version How to connect pGD1 display to c.pCOmini? - 06/11/2019

How to connect pGD1 display to c.pCOmini?


Check the below schema:

c.pCO refuses to execute operations on filesystem (copy/delete/move,


both by USB or FTP). Why?
When application is running, operative system gives priority to it and allocates the majority of the
resources to it. In order to speed up other features, stop the application, when possible. You can
do that by selecting APPLICATION > STOP APPLICATION from system menu.

c.pCOmini High End doesn't have BMS port. How to use ModBus RTU
Slave?
l Display port can be set as ModBus RTU Slave. As downside, no pGD1 can be used on
this port.
l FieldBus can be set as Modbus RTU Slave. However, this port is electrically designed to
work as a master. Check “Chapther 3 – Communication ports” of c.pCO manual in order to
have all details about this type of connection.

For any issue contact [email protected] or visit www.carel.com 2/3


c.pCO FAQ Version What is c.pCO ModBus endianness? - 06/11/2019

What is c.pCO ModBus endianness?


c.pCO uses Big Endian.

For any issue contact [email protected] or visit www.carel.com 3/3