c.pCO Tips and tricks
c.pCO Tips and tricks
PCO FAQ
l In system menu, releasing the display. pGD1 will now display the subsequent c.pCO's
interface (ordered by ascending pLAN address).
1. Press “ALARM + ENTER” for 3 seconds
2. Enter “SETTINGS” menu
3. Enter “PLAN_SETTINGS” menu
4. Set "Release Term" to YES
5. Set “Update Config" to YES
l Using ST calls in c.mask. Check online documentation for more information about.
Note: Display sharing is possible only if the controllers are connected together through the
pLAN serial network (J11)
c.pCOmini High End doesn't have BMS port. How to use ModBus RTU
Slave?
l Display port can be set as ModBus RTU Slave. As downside, no pGD1 can be used on
this port.
l FieldBus can be set as Modbus RTU Slave. However, this port is electrically designed to
work as a master. Check “Chapther 3 – Communication ports” of c.pCO manual in order to
have all details about this type of connection.