0% found this document useful (0 votes)
4 views

KB1250F2

The KB1250 is a 12V 5.0Ah VRLA battery designed for general applications such as UPS and telecommunications, with a design life of 3-5 years. It features AGM technology, operates in a temperature range of -20 to 60ºC, and has various discharge capacities depending on the duration. The battery is suitable for multiple applications including medical equipment, marine equipment, and solar powered systems.

Uploaded by

marcoscardoso.97
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4 views

KB1250F2

The KB1250 is a 12V 5.0Ah VRLA battery designed for general applications such as UPS and telecommunications, with a design life of 3-5 years. It features AGM technology, operates in a temperature range of -20 to 60ºC, and has various discharge capacities depending on the duration. The battery is suitable for multiple applications including medical equipment, marine equipment, and solar powered systems.

Uploaded by

marcoscardoso.97
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

KB1250 12V 5.

0Ah
The KB Standard series consists in VRLA batteries - AGM technology (Absorbent Glass
Mat), with a design life of 3-5 years and it is designed for general applications such
as UPS, telecommunications and electrical applications.

Dimensions and Terminal (Unit: mm (inches))

Performance Characteristics

Nominal Voltage 12V


Dimensions Length (mm / inch) 151 / 5.94
Width (mm / inch) 53 / 2.09 Applications
Height (mm / inch) 93 / 3.66
Total Height (mm / inch) 99 / 3.90 Alarm systems Marine equipment
Approx Weight (Kg / lbs) 1.75 / 3.86 Cable television Medical equipment
Design Life 5 years Communications Equipment Micro processor based office machines
Terminal F2 Control Equipment Portable cine & Video lights
Container Material ABS Computers Solar powered systems
Rated Capacity 5.00Ah / 0.250A (20hr, 1.80V / cell, 25ºC / 77ºF)
Electronic Cash Registers Telecommunications systems
4.65Ah / 0.465A (10hr, 1.80V / cell, 25ºC / 77ºF)
4.20Ah / 0.840A (5hr, 1.75V / cell, 25ºC / 77ºF)
Electric Test Equipment Television & Video recorders
3.04Ah / 3.04A (1hr, 1.60V / cell, 25ºC / 77ºF) Emergency lighting systems Toys
Max. Discharge Current 75A (5s) Fire & Security Uninterruptible power supply systems
Internal Resistance Approx 45mΩ Geophysical equipment Vending machines
Operating Temp. Range Discharge : -20 ~ 60ºC (-4 ~140ºF)
Charge : -10 ~ 60ºC (14 ~ 140ºF)
Storage : -20 ~ 60ºC (-20 ~ 140ºF) Certifications
Nominal Operating Temp. Range 25 ± 3ºC (77 ± 5ºF)
Cycle Use Initial Charging Current less than 1.0A
Voltage: 14.4V ~ 14.7V at 25ºC (77ºF) ISO 9001:2008 ISO 14001:2008
Temp. Coefficient: -30mV/ºC
Standby Use Initial Charging Current less than 1.0A
Voltage: 13.5V ~ 13.8V at 25ºC (77ºF) Discharge Current vs. Discharge Voltage
Temp. Coefficient: -20mV/ºC
Capacity affected by Temperature 40ºC (104ºF) 103%
25ºC (77ºF) 100% Final discharge 1,8 1,75 1,7 1,6
0ºC (32ºF) 86% voltage V/CELL
Self Discharge Fully charged Kaise Standard Series batteries may be Discharge current I ≤ 0,1CA 0.25CA ≥ I >>0.1CA 0.55CA ≥ I> > 0.25CA I > 0.55CA
stored for up to 6 months at 25ºC (77ºF) and then a (A)
freshening charge is required. For higher temperatures the
time interval will be shorter.

Discharge Constant Current (Amperes) at 77ºF (25ºC) Discharge Constant Power (Watts per cell) at 77ºF (25ºC)

Volts/cell 5min 10min 15min 30min 1h 3h 5h 10h 20h Volts/cell 5min 10min 15min 30min 45min 1h 2h 3h 5h
1.80V 11.8 7.99 6.40 4.25 2.60 1.18 0.818 0.465 0.250 1.80V 22.0 15.1 12.2 8.23 6.27 5.09 3.09 2.33 1.63
1.75V 14.0 9.03 7.06 4.54 2.74 1.22 0.840 0.474 0.253 1.75V 25.7 16.9 13.3 8.73 6.63 5.33 3.20 2.40 1.66
1.70V 15.9 9.96 7.64 4.77 2.85 1.26 0.861 0.482 0.257 1.70V 28.9 18.4 14.3 9.12 6.84 5.52 3.31 2.47 1.69
1.65V 17.5 10.7 8.08 4.97 2.97 1.30 0.880 0.489 0.261 1.65V 31.4 19.5 14.9 9.42 7.06 5.72 3.39 2.52 1.72
1.60V 18.4 11.2 8.42 5.11 3.04 1.33 0.898 0.497 0.262 1.60V 32.5 20.1 15.4 9.58 7.15 5.80 3.47 2.56 1.75

(Note) The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.
KB1250 12V 5.0Ah

Charging Characteristics (float use) Cycle Life in Relation to Depth of Discharge

Temperature Effects in Relation to Battery Capacity Effect of Temperature on Long Term Float Life

Self Discharge Characteristics

No supplementary charge required


A (carrry out supplementary charge before use if 100% capacity is required)
Supplementary charge required before use . Optional charging way a below:
B 1. Charged for above 3 days at limited current 0.25 CA and constant voltage 2.25V / cell.
2. Charged fo above 20 hours limited current 0.25CA and constant voltage 2.45V / cell.
3. Charged for 8-10 hours ar limited current 0.05 CA.
Supplementary charge often fail to recover the capacity.
C The battery should never be left standing till this is reached.

IMPORTANT NOTE: The specifications presented herein are subject to revision without notice.

Contacto
[email protected]
PANASONIC EVOLTA EL FUTURO DE LAS PILAS
www.tempelgroup.com
Tempel Group en el mundo
BARCELONA · MADRID · VALENCIA · BILBAO · SEVILLA · LISBOA · PORTO · BUENOS AIRES · LIMA
BARCELONA
SANTIAGO DE CHILE· ·MADRID
BOGOTÁ ·· SÃO
VALENCIA
PAULO ·· MÉXICO
BILBAODF ·· CIUDAD
SEVILLADE PANAMÁ
· LISBOA · PORTO · QUITO
· MONTEVIDEO
www.tempelgroup.com
BUENOS AIRES · SANTIAGO DE CHILE · BOGOTÁ · SÃO PAULO · LIMA · MEXICO DF

You might also like