Aermec UR CF Installation Manual Eng
Aermec UR CF Installation Manual Eng
UR-CF
3
IFI
RT E
E
D
C
HHH
H H
H H
H H H
HHH
QU
H
EM
L
IURCFPV. 0709. 6783480_03
A
IT S
Y SY
Declaration of conformity 4
Remarks 5
Description of the units 6
Description of components 7
Accessories 8
Technical data 9
Operational limits 100
Sound data 100
Performance variations cooling and heating 11
Fans available static pressure 11
Fresh air temperature variations on the change of the expelled
air temperature 12
Thermal efficiency, Pressure drop air side accessories MBC, SUF 13
Dimensions 14
Accessories Dimensions 17
Installation and use of the unit 20
Positioning of the supporting brackets 210
Connection of ducts 22
Hydraulic connections of the condensate drain 22
FCE free-cooling accessory 23
Electrical connections 24
Maintenance of the unit 25
Filters 25
Condensate drain pan 25
Heat recovery 26
Motor ventilating assembly 26
Heat exchanger coil 26
Waste disposal 26
Diagnosis and troubleshooting 27
Aermec S.p.A.
35044 Montagnana (PD) Italia – Via Luppia Alberi, 170
Tel. (+39) 0429 806311
Telefax (+39) 0429 806340
www . Aermecaer . com - Aermecaer @ Aermecaer . com
DECLARATION OF CONFORMITY:
We declare under our own responsability that the above
equipment described as follows:
Montagnana, 04/075/2005
Managing director
Paolo Gasparini
Remarks
5
Description of the unit
The URCF series is the mono-bdamper heat, also includes, in a mono-bdamper Available versions
solution to the needs of systems unit, a heat pump refrigerating circuit.
normally used in bars, restaurants, This allows to obtain a complete
offices, meeting rooms. The URCF units, machine which operates independently The RFC units are available in 5 sizes:
which are divided into five sizes with in all seasons and which is capable of Each model can be configured in
a rated airflow from 750 to 32000 m3/ combining the necessary renewal of air such a manner to satisfy the system
h, have been designed to guarantee with an efficient recovery of heat. requirements by suitable combining the
a healthy thermo-humidity condition The accurate design of the machine available options.
allowing a suitable change of air in combines the extremely compact size,
order to reduce the build-up of gas which makes installation on suspended The table in fig. 01 shows the procedure
and unwanted particles present in the ceilings easier, with easy accessibility of the commercial acronym in the 5
environment to be treated (cigarette for the maintenance of all internal parts. fields from which it is made, which
smoke, unpleasant odours, sweat, dust, This gives the opportunity, also thanks represent the options present.
...). to the management and installation
The RFC unit, in addition to the simplicity, to satisfy many system
ventilation, filtration and recovery of requirements.
fig.01
Field 1, 2, 3 : URCF
Field 4, 5 : 075 - 100 - 150 - 210 - 320
6
Description of the components
Panels and structure:
the structure is made up of 20 mm thick
galvanised self-supporting sandwich panels 4
4
Fans: 3
2
Refrigerating circuit:
air damper and related servomotor in the
this is a highly efficient and silent heat pump Support brackets:
free-cooling version, pressure probe on the
with scroll compressor, four-way valve for allow the unit to be rapidly and securely
recovery filter. A remote control terminal is
cycle inversion, evaporating coil, condensing fixed to the false ceiling.
also supplied for the automatic management
coil, liquid receiver, liquid separator, double
of the unit, remotable up to 1500 meter
thermostatic valve, liquid indicator for the Accessibility:
(cable not supplied).
1500 21000 3200 versions only and filter The unit may be inspected from below. The
The unit is equipped for the management
drier, high/low pressure switch. heat recovery unit, filters, condensate drain
of a luminous sign (230V) which switches
pan and fans can be easily removed from
Condensate drain pan: on in case of generic alarm or unit OFF, in
below by removing the lower two panels.
made of peraluman, easily detachable. conformity with the norms in force for rooms
for smokers.
Evaporating/condensating coil: Control system The following operations can be performed
with Cu grooved tube and high efficiency Al on the microprocessor: switching on and
fins. The unit is equipped with an electrical panel off of the unit, summer/winter changeover,
with power and regulation section (including setting of set-point parameters, reading of
Filters:
the three-way valve for the additional hot room temperature.
these are cell type with an corrugated
septum positioned before the recovery unit water coil and related servomotor), aimed
at guaranteeing the management of all N.B. For further information refer to
on airflow supply and return. The standard
refrigerating circuit functions. Also present: the User manual.
filters are class G3 type in accordance with
classification UNI EN 779 with weighted NTC temperature probe on the internal air
efficiency of 80%. They are 48 mm thick recovery, external air temperature probe,
and are easily withdrawn for cleaning and
replacement.
7
Accessories
MBC Hot water coil module G4F G4 efficiency filters FGC circular flanges
This is an external module that can be installed The units can be fitted with two cell-type filters The accessory is supplied as a single unit.
downstream from the motor fan assembly on with corrugated septum in class G4 according The accessory is made up of flanges which
the fresh air flow, fitted with: to the UNI EN 779 classification (weighted connect to the rectangular port of the unit so as
Two-row water heating coil with copper pipes efficiency of 90%) which can be placed as a to allow the use of circular ducts.
and aluminium fins with P2519 geometry. The replacement of the G3 filters. The filtrating cell The accessory is not available for size 320.
manifold collectors are equipped with a ½" G is 48 mm thick. N.B. for further information, see the tables in
UNI 3208 threaded connector for the water this manual and the various accessories kits;
inlet and outlet. The three-way valves and SUF Module with silencers see fig. 02 below regarding compatibility
related ON/OFF actuator are also included. The accessory is made up of two modules
that are equipped with silencer baffles FCE Free-cooling
MBX Module with electric heating battery positioned on the supply and exhaust. The “free-cooling kit ” includes 2 dampers with
This is an outside module that can be installed They are made of rockwool panels with related ON/OFF 230V servomotors.
downstream from the motor fan assembly on the surfaces in contact with the air and For further information refer to the Use manual.
the fresh air flow, fitted with: protected by a polyester film held between
Electric heating element with armoured two galvanised and micro-perforated
finned elements equipped with double safety laths.
thermostat with automatic and manual reset.
Available accessories
MBX Mod. 075 100 150 210 320
MBC MBC075 MBC100 MBC150 MBC210 MBC320
MBX MBX075 MBX100 MBX150 MBX210 MBX320
G4F G4F075 G4F100 G4F150 G4F210 G4F320
SUF SUF075 SUF100 SUF150 SUF210 SUF320
FGC FGC075 FGC100 FGC150 FGC210 -
FCE FCE075 FCE100 FCE150 FCE210 FCE320
MBC
SUF
FGC
fig.02
8
Technical data
MODEL URCF 075 100 150 210 320
External air nominal flow rate m3/h 750 10000 15000 210000 32000
Recovery air nominal flow rate m3/h 750 10000 15000 210000 32000
Minimum airflow rate m3/h 640 850 1275 1785 2800
Available static pressure (in supply) (1) Pa 256 2101 223 146 267
Available static pressure (in exhaust) (1) Pa 244 203 206 134 246
Sound pressure level at 1 m (6) dB(A) 53 55 57 59 62
Recovered heating capacity (3) kW 3,2 4,7 6,6 9,8 14,9
Recovered refrigerating capacity (2) kW 0,9 1,3 2 2,9 4,4
Compressor heating capacity (3) kW 5,3 6,7 9,5 14,1 16,6
Compressor refrigerating capacity (2) kW 4,6 6,4 8,3 14 150,3
Total heating capacity (rec. + compr.) (3) kW 8,5 11,4 16,1 23,9 31,5
Total refrigerating capacity (rec. + compr.) (2) kW 5,5 7,7 100,3 16,9 19,7
Total power input during heating (3) kW 1,8 2,3 3,7 4,5 5
Total power input during cooling (2) kW 3 3,6 5 6,7 8
Electric supply ph-V-Hz 1- 230-50 1-230-50 3+N-400-50 3+N-400-50 3+N-400-50
Heat recovery
Efficiency (3) % 51 56,4 52,8 55,6 53,9
Fans
Number of fans n° 2 2 2 2 2
Fans total nominal input power kW 0,75 0,75 1,2 1,2 2,1
Fans maximum total input power A 5 5 8,6 8,6 13,2
Fan speed settable settable settable settable settable settable
Protection class IP 55 55 55 55 55
Filters
Classification according to the EN779 G3 G3 G3 G3 G3
Quantitative efficiency % 80 80 80 80 80
Refrigerating circuit (compressor)
Winter mode compressor input power (3) kW 1,2 1,7 2,6 3,4 3,8
Summer mode compressor input power(2) kW 2,4 3 4 5,6 5,8
Compressor maximum power input A 100,9 14 6,7 9,7 11,1
ACCESSORIES
MBC Water heating coil 075 100 150 210 320
Rows n° 2 2 2 2 2
Front surfaces m2 0,13 0,13 0,24 0,24 0,29
Air side pressure drop at nominal flow rate Pa 11 19 17 25 41
Heating capacity (4) kW 4,5 5,5 8,4 11 150,6
Heating capacity (5) kW 1,4 1,7 2,7 3,5 5
Air outlet temperature (4) °C 46 45 45 44 42
Air outlet temperature (5) °C 34 320 320 320 32
MBX - ELECTRIC HEATING COIL 075 100 150 210 320
Alimentation 3~ 400V 50 Hz
Heating capacity kW 3 4,5 6 9 12
Air side pressure drop to the nominal airflow Pa 100 100 100 100 100
Stages n° 1 1 1 1 1
Electric heating element power input A 4,6 6 9,1 12 19,7
Air outlet temperature (7) °C 47 45 45 45 41
MANIFOLD DIAMETERS
Condensate drain pan discharge diameter 1” 1” 1” 1” 1”
Water coil manifold diameter 3/4” 3/4” 3/4” 3/4” 3/4”
Caution: the electronic regulators that are (1) Fan power supply: 230 V; nominal airflow rate; (4) inlet/outlet water temperature 70/60°C in condition
incorporated in the machine allow to regulate without accessories; (3) with compressor running;
the air flow in the limits indicated in the (2) Operating conditions: return air 26°C 50%, external (5) inlet/outlet water temperature 45/40°C in condition
previous table in order to set the system. Once air 34°C 50%; (3) with compressor running;
setting has been completed, the regulators no (3) Operating conditions: return air 20°C 50%, external (6) At a free field distance of 1 m with ports canalized;
longer need to be touched. air -5°C 80%; (7) In condition (3) with compressor running.
9
Operation limits
In their standard set-up, the equipment
Summer mode: Winter mode:
is not suitable for installation in a saline
(heat pump)
environment. The maximum and 46
ext (°C)
minimum limits of the airflow rate to the
exchanger are indicated by the curve of 25
the pressure drops diagram. Refer to fig. t ext (°C)
Sound data
• Data outside the panel: (the data are calculated at the following conditions: 1 m. distance from the unit, ducted supply vent and in free field)
Sound pressure by band central frequence (Hz) Sound pre. Sound Pre. Sound Pow.
63 125 250 500 10000 2000 4000 8000 Total Total Total
dB dB dB dB dB dB dB dB dB dB (A) dB (A)
075 56 55 51 50 49 44 40 320 60 53 64
100 59 60 54 52 50 45 41 35 64 55 66
150 62 65 57 54 51 47 42 36 68 57 68
210 64 69 60 55 52 48 43 38 71 59 70
320 67 74 63 57 53 49 44 39 75 62 73
• Sound data on the supply fan vent
Sound pressure measured at 3m distance from the free vent of the supply fan:
63 125 250 500 10000 2000 4000 8000 Sound pressure
dB dB dB dB dB dB dB dB dB dB (A)
075 65 57 54 57 54 50 53 48 67,0 60
100 66 58 56 60 57 57 57 52 68,8 64
150 67 59 58 62 60 61 63 57 71,1 68
210 66 61 58 67 62 65 68 63 73,8 72,5
320 69 61 59 64 71 71 63 58 76,1 75,5
Sound power level from the supply vent:
63 125 250 500 10000 2000 4000 8000 Sound power
dB dB dB dB dB dB dB dB dB dB (A)
075 57 64 59 61 62 58 51 44 68,7 65,3
100 59 69 63 66 66 63 57 50 73,3 70
150 57 68 63 65 66 64 59 52 72,9 70,3
210 53 65 60 66 66 65 61 54 72,3 70,8
320 61 71 68 71 71 71 68 62 78,2 76,6
10
Performance variations cooling and heating
The URCF series heat recovery unit with Heating capacity Refrigerating capacity
refrigerating circuit allow the renewal of
the internal air giving the necessary hourly
change in order to obtain the ideal comfort
conditions.
The use of a high efficiency cross-flow heat
Multiplicational coefficient
recovery unit and a heat pump refrigerating
circuit allows, in most applications and in
the most common external air temperature
conditions, in addition to the neutralisation
of the heating load of the external air, to
supply an adequate heating and cooling
capacity to compensate the internal heating
loads. Fig. 4 illustrates the graph from
which it is possible to take the coefficients
to be multiplied by the nominal values
which are present in the technical data
table so as to be able to determine the Outdoor air temperature [°C]
Key
total refrigerating and heating performance Internal air temperature Internal air temperature
based on the outside conditions. Summer operation: 26 °C 50% RH Winter functioning: 20 °C 50% RH
fig.04
Corrective coefficient for the cooling capacity according to the variation of the room temperature in summer and winter mode:
SUMMER MODE: WINTER MODE:
Room air temperature 22°C, 50% RH --> corrective coefficient = 1,050 Room air temperature 18°C, 50% RH --> corrective coefficient = 0,980
Room air temperature 24°C, 50% RH --> corrective coefficient = 1,025 Room air temperature 20°C, 50% RH --> corrective coefficient = 1
Room air temperature 26°C, 50% RH --> corrective coefficient = 1 Room air temperature 22°C, 50% RH --> corrective coefficient = 1,020
Room air temperature 28°C, 50% RH --> corrective coefficient = 0,975 Room air temperature 24°C, 50% RH --> corrective coefficient = 1,040
series is considered.
The following performances are taken
from the technical data table:
nominal delivery flow rate 15000 m3/h;
nominal recovery flow rate 15000 m3/h;
available delivery static head = 223 Pa;
available recovery
static head = 206 Pa.
It is supposed that the pressure drops of
the air distribution system on the supply
side are equal to 21000 Pa, while the
11
Fresh air temperature variations on the
F
change of the external air temperature
Summer use
N.B.
The following diagrams are typical for all
sizes, but without accessories
At the nominal air flow - 150 %
External air temperature (°C)
Conditions: exhaust air 26°, 50% R.H.
Winter use
Variation of the inlet air temperature (°C)
At the nominal flow rate
At the nominal flow rate + 150 %
External air temperature (°C)
Conditions: exhaust air 20°, 50% R.H.
12
Thermal efficiency, Pressure drop
air side for accessories MBC, SUF
The diagram in fig. 06 allows to
determine the coil thermal efficiency
of the MBC accessory for each model
based on the Td of the inlet water and
Td of the inlet water air. The corrective
Corrective factor
factor to multiply for the nominal capa-
city value are present in the technical
data table.
70/60 °C
45/40 °C
External air temperature [°C]
fig.06
Pa
.#$
Pressure drop air side
46'
.#$
Fig. 075 illustrates the pressure drops
(Pa) on the air side based on the flow
rate for the MBC and SUF accessories 46'
.#$
46'
fig.075
Air flow rate m3/h
kPa
-"#
Fig. 08 illustrates the pressure drops -"#
Pressure drop water side
13
Dimensions
URCF 075-100
Expulsion of exhaust
air or inspection of
By-pass for refrigerating circuit
External air
Exhaust Supply External air free-cooling
suction
fan fan suction
Expulsion of
exhaust air or
inspection of Electric
refrigerating panel
circuit
14
URCF 150-210
Expulsion of
exhaust air or
Supply By-pass for inspection of
Exhaust External air
free-cooling refrigerating circuit External air
fan fan suction suction
Expulsion of exhaust
air or inspection of
refrigerating circuit Electric
panel
15
URCF 320
Expulsion of
exhaust air or
Exhaust inspection of
fan Supply External air By-pass for refrigerating
External air
fan suction free-cooling circuit
suction
Expulsion of
exhaust air or
inspection of
refrigerating circuit Electrical
panel
Pesi e baricentri kg Gx Gy
URCF 320 400 850 800
16
Accessories Dimensions
M I H I M
G
C
B
D
!
% & %
17
MBC - Water coil modules
MBX - Electrical coil modules
MBC MBX
18
Dampers and actuators (included in the free-cooling kit)
# #
&ORI MM
(
"
O
380 mm
19
Unit accessibility
20
Installation and use of the unit
21
• for the components (three-way valves,
condensate drainage traps, etc.)
without which the correct functioning ! Key
of the unit can not be guaranteed; A = 800 mm
• for the correct cleaning and B = 200 mm
C = 200 mm
maintenance operations.
D = 200 mm
In particular: $ "
• a space of at least 200 mm
must be available for the trap in
correspondence with the condensate
drain (fig. 11).
#
fig.08
Positioning of the
supporting brackets
The unit must be positioned on a flat
surface to avoid:
• the drainage of the motor fan
a s s e m b l i e s c a u s e d by w e i g h t
imbalance Fischer
• the incorrect functioning of the screws
condensate drain. not
supplied
The unit and the coil and silencer
module are equipped with "L"
22
Connection of ducts
CAUTION! Olona cloth
never start up the unit when the fan vibration-damping joint
ports are not ducted or covered by
protective mesh.
Hydraulic connections
of the condensate drain
The condensate drain pan is provided
with a 1” diameter threaded discharge
pipe G UNI 3208.
The drainage system should feature an
Minimum length 1 m
adequately sized trap to:
• freely discharge the condensate; max divergence 7°
• prevent the undesired entry of air
into the vacuum systems;
• prevent the undesired exit of air
from the pressure systems; P P H1 = 2P
neg. pos.
• prevent the infiltration of odours or H2= H1 / 2
insects.
H3 H3
In the lower part of the syphon must
have a bleed cap or must anyway H1 H1 where P is the pressure
permit Aermec dismantling for its expressed in mm of the water
H2 H2
cleaning. column (1 mm c.a. = 9.81
Rules to follow for the scaling and Pa).
production of the syphon are given
below.
fig.11
23
FCE free-cooling accessory
Operation
The free-cooling function foresees that
the air expelled from the room does not
affect the heat recovery unit, passing EXTERNAL INTERNAL
directly to the outside through a duct
connected to the damper B.
Thus, the fresh air flow passes through
the filter and the heat recovery unit
without being touched by the heat
recuperator.
In order to use the free-cooling function Damper B
a duct is required to connect to damper
A and another to connect to damper
B. The two dampers A and B have an
opposing function. fig.12
When the outside temperature is close
to the ideal temperature of the room,
damper A is closed while damper B is
open. MES
Damper A can be positioned on the Exhaust damper
side as indicated in the line diagram. actuator
The compressor is off when the unit is
operating in free-cooling.
Assembly of the
accessory
For the assembly of the free-cooling EXTERNAL INTERNAL
accessory please refer to fig. 13 and 14 BTR
• p l a c e t h e t wo d a m p e r s w i t h Room temperature
servomotors MES and MESF as in the probe already present
previous diagram;
• make sure that the damper with the
MES servomotor is closed during
the free-cooling function while the BTE
damper with the MEFS servomotor is Outside air
open (opposing functions); MESF
temperature
• connect the damper servomotors; Free-cooling
probe already
Damper actuator
present fig.13
24
Electrical connections
The unit is completely wired in the currently in force. power supply lines,etc.
factory and requires the power supply, Every electrical user must be connected CAUTION!
intercepted with inline protections, to the system's earthing system. Once the connections have been made,
indicated on the unit specification plate Use the connectors with the earth check that:
in order to be started. symbol to connect the earthing of the all the cables have been correctly
The installer should define the power unit and possible accessories to the connected, and that there are no short
supply line based on the length, the earthing of the building. circuits between terminals and the
type of cable, the absorption of the unit Respect the installation power supply terminals and ground.
and the displacement. TAB.3 and environment conditions the electrical terminals both within
All electrical connections must be in the electrical panel as well as in the
accordance with the present standard at Keep the panel and wiring away from terminal board of the compressor are
the moment of installation. electric and magnetic fields that could secured and that the mobile and fixed
disturb, such as inverters, high voltage contacts of the remote control switches
CAUTION: do not show signs of wear.
Refer to the electrical layout supplied Do not block the air intake of the
with the equipment for installation panel.
needs.
TAB.3
Check that all power cables are
correctly secured to the terminals Operating voltage ± 100% of the rated voltage (EN60204)
when switched on for the first time and Frequency ± 1% of the continuous frequency
after 30 days of use. Afterwards, check ± 2% for short periods
the connection of the power cables
Operating room umidity from 30% to 95%, without condensate
every six months. Slack terminals could
cause the cables and components to or the formation of ice (EN60204)
overheat. Altitude up to 10000 m a.s.l. (EN60204)
The electrical wiring and connections
Operating room temperature from +5°C to 40°C
must be done persons qualified to
do so in accordance with regulations
25
Checks during Requirements of gas - In particular, in the event of
replacing the compressor, complete
operation R4075C the installation within the above-
mentioned time after the rubber
Check the rotation of the compressors The circuit chillers that work on R4075C plugs have been removed.
which are energised by a 3 phase cooling gas require particular attention - When empty, do not switch on the
system: if the suction pressure does during assembly and maintenance, to compressor; do not compress the air
not decrease and the supply pressure prevent operating faults. within the compressor.
does not increase to the normal values, Therefore it is necessary to: - When using R4075C gas bottles, it
switch off the power and invert two - Avoid refilling with oil different from is recommended to take care of the
phases of the three-core input cable the one specified and already used in maximum number of drawings permitted
and turn the power back on to check the compressor. in order to guarantee the correct ratio of
that this was not incorrectly connected: - If there are gas leaks causing the unit components of the R4075C gas.
never modify the internal wiring to be even partially empty, do not
connections otherwise the warranty refill with refrigerant, but empty the
will no longer be valid. unit completely and refill it with the
The air flow rate values must not be foreseen amount.
lower than 150% of the nominal values - In the event of replacement of one of
indicated in the technical specifications the refrigerating circuit parts, do not
table. leave the circuit open for more than
150 minutes.
If an electrical resistance is present,
check the cut-in by measuring its
electrical absorption.
CAUTION! The RFC series recovery units have • remove the inspection panel with
During the maintenance phase, wear been designed to require very little knobs;
proper individual protection devices maintenance and to make every • remove the filters;
(IPD) operation easy. Some simple pieces • clean the filters;
• Before performing maintenance and/ of advice follow for the proper • replace all parts in reverse order.
or cleaning operations on the unit, maintenance of the unit.
make sure the unit is disconnected Condensate
from the power supply and that it can Filters drain pan
not be turned back on without the
knowledge of the person performing
Fi l t e r c l e a n i n g i s i m p e ra t ive t o Dirt can hoard up in the condensate
maintenance, and that the heat
maintain high air quality in the room. d r a i n p a n . Yo u a r e t h e r e f o r e
exchanger coils are not working.
The synthetic filters installed in the recommended to clean the pan regularly
URCF unit can be regenerated with and check that the discharge pipe is not
• During maintenance the weight of
compressed air or can be washed with clogged.
the inspection panelling could hinder
cold water. To disassemble the filters: To remove the condensate drain pan of
the work
the heat recovery unit:
26
the frame;
• remove all bottom panels; Motor ventilating
• check the motor fan assemblies and
• disassemble the cross bar; assembly replace them if necessary;
• disconnect the pan from the
The motor ventilating assembly needs • replace all parts in reverse order.
condensate drain pipes;
• disassemble the pan supporting to be checked to see how clean the
brackets; rotor is, whether there is corrosion Heat exchanger coil
• clean the pan; o r d a m a g e , a n d wh e t h e r t h e r e
• replace all parts in reverse order. are abnormal noises. If necessary To maintain an efficient heat exchange
In order to access the condensate drain disassemble the motor fan assembly as the coils must be cleaned with a jet of
pan on the coil module, detach the follows: compressed air and the circuit (water
module from the unit and disassemble • remove all inspection panels; coil) must be free from air.
it. • disconnect the power supply cable; To access the heat exchanger coil of the
• unscrew the four screws that hold MBC accessory, disconnect the module
each of the motor fan assemblies to from the unit and disassemble it .
Heat recovery
Waste disposal
At the end of their operating life, • aluminium sheet metal (coil fins, • the cooling gas is recuperated by
the URCF units must be disposed of dampers, electrical motor casing); specialised personnel and forwarded
according to the present laws. to the disposal centre;
The main components including the • copper (coil tubes, electric motor winding );
unit of the URFC series are made from: • the compressor lubrication oil is
• polyurethane foam (insulation of the also recuperated and forwarded for
• Galvanised sheet steel (panels , sandwich panels); disposal.
condensate drain pan, fans); • rock wool (silencers);
27
Diagnosis and trouble-shooting
1. Insufficient air flow rate • Fans rotation speed • Clean the components
too low increase the fan speed
• Pressure drop of the
distribution system underestimated
• Blocked filters
• Blocked intake grating
• Coil incrustation
2. Excessive air flow rate • Fans rotation speed • reduce the fan speed
too high
• Pressure drop of the
distribution system overestimated
• Filters not fitted • Fit filters
3. No air flow rate • Power supply off • Make sure power supply is available
• Electric motor burnt out • Replace the electric motor
6. The compressor does not start • Defective connection or contacts open • Check the voltage and close the contact
• Thermostat does not • System at temperature, no
respond request; check the setting and the
functioning
• Safety device does not • See point 9) and 100)
respond
• Defective compressor • Replace compressor
7. The compressor does not start • Compressor burnt out or seized • Replace compressor
• Compressor remote control switch de-energised • Check the voltage across
the operating time of the protection;
automatic compressor shutdown
• Power circuit open • Check why the protection cut in
compressor; automatic shutdown
8. The compressor starts and then stops • Defective compressor remote control switch • Check and if necessary replace it
• Defective compressor • Check and if necessary replace it
9. The compressor does not start due to •Pressure switch out or order • Check and replace
the intervention of the high pressure • Excessive refrigerant • Discharge excess gas
switch
• Presence of incondensable gas • Refill the circuit after having
in the refrigerating circuit discharged and placed in vacuum.
• The condensate coil is not sufficiently • See point 1)
covered in air
• Blocked refrigerant filter • Check and replace
28
100. The compressor does not start due • Pressure switch out of order • Check and replace
to the intervention of the • Machine completely empty • See point 11)
low pressure switch • Poor air flow • Check the air duct and the state of
the filters.
• Blocked refrigerant filter • Check and replace
•The thermal expansion valve does not • Check, clean or if necessary
function correctly replace it.
11. Lack of gas • Leak in the refrigerating circuit • Check the refrigerating circuit
with a leak detector
13. The refrigerating circuit functions • Lack of refrigerant • See point 11)
correctly but with insufficient • Presence of humidity or incondensable • Replace the filter and if necessary
proficiency in the refrigerating circuit drain and refill the circuit
14. Compressor suction tube • Thermal expansion valve • Check the valve and
frosted if it is not working
correctly replace it
• Poor air flow • Check filters, fans and ducts.
• Lack of refrigerant • See point 11)
• Blocked liquid filter • Clean or replace
150. Abnormal noise in the system • Vibrations in the pipes • Secure the pipes
• Noisy compressor • Check electrical phases connection
• Noisy thermostatic valve • Check and add refrigerant
16. Evaporator coil • Lack of refrigerant in the circuit: • Check for leaks and eliminate them
before bubbles visible in the indicator. topping up with refrigerant .
• Thermostatic expansion valve over . • Reduce the overheating of the
closed: suction pipe too hot thermostatic expansion valve
turn the valve stem and
check the suction pressure .
• Thermostatic expansion valve over . • Change the valve or free the
closed: expansion valve bulb control pipe.
partially blocked or pressure intake pipe
blocked
• Filter-drier blocked: bubbles in the • Change the filter-drier.
flow indicator and liquid pipe colder
at the filter drier outlet
• The manifold feed pipes are • Remove the obstruction; clean or change
blocked or oil has accumulated in the the evaporator.
coil: not all of the evaporator circuits
are working
17. Compressor too hot •Thermostatic expansion valve • Reduce the overheating of the
over closed: excessive overheating thermostatic valve
of the evaporator discharge gas
18. Compressor to cold and noisy • Expansion valve over open: • Measure and reset the overheating
the system works with the overheating by closing the valve
to low (return of liquid to the
compressor).
• Thermostatic valve out of order: the stem or • Replace the valve or free the
the seat of the expansion valve is pressure inlet pipe
corroded. Pressure inlet pipe blocked.
• Foreign objects between the stem and the seat • Clean the stem and the holes of the
of the thermostatic valve: abnormal function thermostatic valve
of the thermostatic valve
29
NOTE
NOTE
AERMEC S.p.A. carta riciclata
recycled paper
37040 Bevilacqua (VR) - Italien papier recyclé
Via Roma, 44 - Tel. (+39) 0442 633111 recycled Papier
Telefax (+39) 0442 93730 - (+39) 0442 93566
www . aermec . com