0% found this document useful (0 votes)
14 views31 pages

DeltaV Classic IO

The Classic I/O subsystem is a modular and flexible system designed for easy installation and maintenance in process control applications. It offers reduced capital equipment costs, decreased installation time, and increased productivity through features like plug-and-play capabilities and function keys for correct I/O card installation. The subsystem includes various I/O cards and terminal blocks, ensuring compatibility and ease of use while meeting stringent environmental and safety specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views31 pages

DeltaV Classic IO

The Classic I/O subsystem is a modular and flexible system designed for easy installation and maintenance in process control applications. It offers reduced capital equipment costs, decreased installation time, and increased productivity through features like plug-and-play capabilities and function keys for correct I/O card installation. The subsystem includes various I/O cards and terminal blocks, ensuring compatibility and ease of use while meeting stringent environmental and safety specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 31

Product Data Sheet

Classic I/O
Mar-04—Page 1

TM

Classic I/O
I/O cards plugged
into an 8-wide carrier

Redundant power supplies


and controllers plugged into Additional I/O
2-wide carriers The DeltaV I/O subsystem is easy to install and maintain.

■ Decreases capital equipment costs The Classic I/O subsystem includes:


✔ I/O interface carrier (a DIN rail surface mounted)
on which all I/O related components are
■ Decreases installation time and expense installed.

■ Increases productivity ✔ Bulk AC to 24 VDC power supply for field


devices.

Introduction ✔ An I/O interface consisting of an I/O card and an


I/O terminal block.
Classic I/O is a modular subsystem that offers
flexibility during installation. It’s designed to be ✔ A variety of analog and discrete I/O cards
installed in the field, near your devices. Classic I/O is enclosed in a common form factor that easily
equipped with function and field wiring protection plugs into the I/O interface carrier.
keys to ensure that the correct I/O card is always
plugged into the corresponding terminal block. ✔ A variety of I/O terminal blocks mounted on the
Modularity, protection keys, and plug and play I/O interface carrier that can be pre-wired before
capabilities make DeltaV Classic I/O a smart choice I/O card installation.
for your process control system.
Product Data Sheet
Classic I/O
Mar-04—Page 2

TM

Benefits Decreases installation time and


expense.
Decreases capital equipment costs.
Plug-and-play installation saves money. All
Full system modularity. The Classic I/O subsystem Classic I/O components plug into the I/O interface
was designed with your investment in mind. All carrier. You can install the I/O interface carriers to
components are fully modular and may be installable manage anticipated growth and postpone the I/O
1
under power. You add I/O interface carriers and I/O interfaces until you’re ready to install your additional
interfaces in groups of 8 channels as you need field devices.
them. The modular design enables you to purchase
the exact amount of I/O cards, 8-wide carriers, Phased installation saves time. As soon as you
power/controllers, and 2-wide carriers you need and mount the I/O interface carrier, you’re ready to begin
add more DeltaV I/O as your system grows. installing the field devices. I/O terminal blocks plug
directly onto the I/O interface carrier. There is no
Reduced system footprint. The DeltaV system’s need to have the I/O cards installed.
state-of-the-art form factor design of the I/O
components enables you to mount the I/O interface
carrier in a junction box in the field so you
significantly reduce the footprint of your equipment
and increase valuable control room space for other
uses.
Installation. Save on wiring expenses by installing
Classic I/O in the field, near the actual field devices.
Mounting the controller with the I/O further reduces
your wiring expenditures by eliminating the need for
long runs of multi-cores. The integrated design of
the I/O subsystem can eliminate the need for
marshaling panels. This saves you even more in
your total capital costs.
The provision of in-line fuses and bussed power
saves on installation costs compared with external
fuses and power distribution.

Classic I/O terminal block.

Keys. Classic I/O interfaces and terminal blocks


have I/O function keys. These keys ensure that the
correct I/O card is always plugged into the
corresponding terminal block. It’s incredibly easy to
use and gives you time to do more.

This design enables you to initially install Classic I/O


1
Refer to Zone 2 installation instructions (12P2046) quickly and efficiently. When you need to replace an
and/or Class 1 Division 2 installation instructions I/O card, the function key design ensures that you
(12P1293) for details.
Product Data Sheet
Classic I/O
Mar-04—Page 3

TM

will always install it correctly. This keying system Product Description and Specification
provides a safety measure by preventing the wrong
I/O interface’s being installed. I/O Cards
Increases productivity. A variety of analog and discrete I/O cards is
available to meet your specific requirements. All I/O
Real-time, online equipment additions. Online cards are enclosed in a common form factor that
addition of new I/O interfaces means your process plugs into the I/O interface carrier. The housing is
does not get interrupted. As new equipment is clearly labeled with the enclosed I/O card type.
added, the DeltaV Explorer acknowledges it and Clearly visible LEDs on the top of the I/O card
assigns it basic configuration. display the power, error, and status to the channels
included in the I/O card.
We have met ISA G3 corrosion specifications by the
careful selection of superior electronic components
and the use of conformal coating.
For slow pulse applications (< 125 Hz) any discrete
input card can be used. The most commonly used
discrete input cards for pulse applications are the
discrete input 24 VDC.
If you’re entering the world of smart plants, then you
may be interested in the benefits associated with
HART and FOUNDATION fieldbus I/O. For detailed
information about these products, refer to the
appropriate product data sheet.

A Classic I/O card easily plugs into


an I/O carrier.
Product Data Sheet
Classic I/O
Mar-04—Page 4

TM

The following tables list the specifications for the


Classic I/O:

Common Environmental Specifications for all I/O Interfaces

Category Specifications:

Storage temperature -40 to 85 °C (-40 to 185 °F)

Operating temperature 0 to 60 °C (32 to 140 °F)

Relative humidity 5 to 95% , non-condensing

• ISA-S71.04-1985
Airborne Contaminants
Airborne contaminants Class G3

• Conformal coating

Protection rating IP 20, NEMA 12

• Class 1, Div 2, Groups A,


Hazardous B, C, D, T4 hazardous
area/location* locations, or
• ATEX 3 G IIC T4

Shock 10 g ½-sine wave for 11 ms

1 mm peak-to-peak from 5 to
Vibration 16 Hz;
0.5 g from 16 to 150 Hz

H 10.7 cm (4.2 in.)


Dimensions W 4.1 cm (1.6 in.)
Depth 10.5 cm (4.1 in.)

*Refer to Zone 2 installation instructions (12P2046) and/or Class 1 Division 2 installation instructions (12P1293)
for information on installing in hazardous areas.
Product Data Sheet
Classic I/O
Mar-04—Page 5

TM

Analog I/O Cards

Specifications for AI-Card, 8 channel, 1 to 5 VDC

Number of channels 8

Isolation Each channel is optically isolated from the system at field to system
isolation = 100 VAC (verified by 1700 VDC factory test)

Nominal signal range (span) 1 to 5 VDC

Full signal range 0.19 to 5.64 VDC, with overrange checking

LocalBus current (12 VDC nominal) 100 mA typical, 150 mA maximum


per card

Field circuit power per card 100 mA (used on card)

Input impedance 2 MΩ

Accuracy over temperature range 0.1% of span

Resolution 16 bits

Repeatability 0.05% of span

Rolloff frequency -3 dB at 2.7 Hz;


-20.5 dB at ½ the sampling frequency

Calibration None required

Optional fuse 2.0 A

Hazardous area/location Class 1, Div 2, Groups A, B, C, D, T4 hazardous locations


ATEX 3 G IIC T4

2
Class I, Div 2 Groups A, B, C, D, T4 non-incendive
Field wiring ATEX 3 G IIC T4 -nL
3

2
Non-incendive field circuits are designed such that under normal operating conditions energy is limited. The circuit is not
capable of igniting the surrounding flammable gas or vapor by opening, shorting or grounding the field wiring.
3
Energy-limited field circuits (-nL) are designed such that any spark or thermal effect produced in test conditions is not
capable of causing ignition of given flammable gas or vapor.
Product Data Sheet
Classic I/O
Mar-04—Page 6

TM

Specifications for AI-Card, 8 channel, 4 to 20 mA

Number of channels 8
Isolation Each channel is optically isolated from the system at field to system
isolation = 100 VAC (verified by 1700 VDC factory test)
Nominal signal range (span) 4 to 20 mA
Full signal range 1 to 23 mA, with overrange checking
LocalBus current (12 VDC nominal) 120 mA typical, 150 mA maximum
per card
Field circuit power per card 300 mA maximum at 24 VDC (+10%)
Accuracy over temperature range 0.1% of span
Resolution 16 bits
Repeatability 0.05% of span
Rolloff frequency -3 dB at 2.7 Hz;
-20.5 dB at ½ the sampling frequency
Calibration None required
Optional fuse 2.0 A

Hazardous area/location Class 1, Div 2, Groups A, B, C, D, T4 hazardous locations


ATEX 3 G IIC T4

Field wiring Class 1, Div 2, Groups A, B, C, D, T4


2-wire—non-incendive
4-wire—non-arcing
2-wire— ATEX 3 G IIC T4 -nL
4-wire— ATEX 3 G IIC T4 -nA
Product Data Sheet
Classic I/O
Mar-04—Page 7

TM

Specifications for AO Card, 8 channel, 4 to 20 mA

Number of channels 8
Isolation Each channel is optically isolated from the system at field to system
isolation = 100 VAC (verified by 1700 VDC factory test)
Nominal signal range (span) 4 to 20 mA
Full signal range 1 to 23 mA
LocalBus current (12 VDC nominal) 100 mA typical, 150 mA maximum
per card
Field circuit power per card 300 mA maximum
Accuracy over temperature range 0.25% of span
Resolution 12 bits
Output compliance 20 mA at 21.6 VDC supply into 700 Ω load
Calibration Information stored on card.
Optional fuse 2.0 A

Hazardous area/location Class 1, Div 2, Groups A, B, C, D T4 hazardous locations


ATEX 3 G IIC T4

Field wiring Class I, Div 2, Groups A, B, C, D T4 non-incendive


ATEX 3 G IIC T4 -nL
Product Data Sheet
Classic I/O
Mar-04—Page 8

TM

RTD I/O Card

Specifications for RTD Input Card, 8 channel


RTD channels per card 8
Sensor types 2 wire, 3 wire, or 4 wire: Resistance, Pt100, Pt200, Pt500, Ni120,
Cu10, user defined
LocalBus power rating 12 VDC, 160 mA
Repeatability 0.05% of span
Calibration None required
Resolution 0.03 Degrees C (16 bit)
Wiring 3 and 4 wire sensors
Sensor type 100 ohm platinum
200 ohm platinum
10 ohm copper
Custom RTD available
Units Degrees C
Degrees F
Temperature range -200 to 870 Degrees C
Sensor excitation Constant current source supplied by card
Common mode rejection 100 dB at 60 Hz
Common mode impedance > 10 megohms
Normal mode rejection rolloff 100 dB at 50/60 Hz, -20dB at ½ the sampling frequency
Frequency
Open RTD response time 1 second
Scan time 1 second (filtering is appropriate to realize a true 1 second detection
Environmental conditions
Temperature
Operating 0 to 60 Degrees C
Rate of Change 1 degree C per minute without performance degradation
Storage -40 to 85 degrees C
Relative humidity
Operating 5 to 95% (non-condensing)
Storage 5 to 95% (non-condensing)
Hazardous area/location Class 1, Div 2, Groups A, B,C,D, T4
ATEX 3 G IIC T4

Field wiring Class 1, Div 2, Groups A, B,C,D, T4 non-incendive


ATEX 3 G IIC T4 -nL
Product Data Sheet
Classic I/O
Mar-04—Page 9

TM

RTD, ohms Sensor Type Specifications

25° Reference Temperature


Sensor Type Full Scale Operating Range Accuracy Resolution
Drift
Resistance 0 to 2,000 ohms 0 to 2,000 ohms ± 6.2 ohms ± 0.112 ~0.02 ohms
ohms/°C
Pt100 -200 to 850°C -200 to 850°C ± 0.5° C ± 0.018° C/°C ~0.05° C
Pt200 -200 to 850°C -200 to 850°C ± 0.5° C ± 0.012° C/°C ~0.05° C
Pt500 -200 to 850°C -200 to 850°C ± 3.5° C ± 0.063° C/°C ~0.18° C
Ni120 -70 to 300°C 70 to 300°C ± 0.2° C ± 0.006° C/°C ~0.02° C
Cu10 -30 to 140°C -30 to 140°C ± 1.0° C ± 0.157° C/°C ~0.23° C
User defined 0 to 1000 ohms 0 to 1000 ohms ± 0.4 ohms ± 0.009 ~0.05 ohms
ohms/°C
Product Data Sheet
Classic I/O
Mar-04—Page 10

TM

Thermocouple/ Millivolt I/O Card

Specifications for Thermocouple Input Card, 8 channel

Thermocouple or millivolt channels per card 8


Resolution 16 bit
Isolation Each channel is optically isolated form the system at field-to-system
isolation = 100 VAC (verified by 1700 VDC factory test.)
Channels 1,2,3 and 4 have a safety isolation from channels 5,6,7 and 8 of
100 VAC (verified by 1,700 VDC factory test). Thermocouples attached to
channels 1,2,3 and 4 or 5,6,7 and 8 are not electrically isolated and should
be within +/- 0.7VDC from each other.
Sensor type
mV Low level voltage source
Thermocouple B, E, J, K, N, R, S, T, uncharacterized
LocalBus power rating 12 VDC, 350 mA
Repeatability 0.05% of span
Rolloff frequency
mV -25 dB at 50/60 Hz, -20 dB at ½ the sample frequency
Thermocouple –100 at 50/60 Hz, -200 dB at ½ the sample frequency
Calibration None required
Units Degrees C
Degrees F
Millivolt range -100 to 100 mV
Cold junction compensation Integral terminal block with cold junction compensation. Also, one input
channel may be configured to use external cold junction compensation
Common mode rejection 100 dB at 60 Hz
Common mode impedance > 10 megohms
Normal mode rejection 60 dB at 60 Hz
Open thermocouple response time 1 second
Open circuit detection Yes
Scan time 1 second (filtering is appropriate to realize a true 1 second detection
Environmental conditions
Temperature
Operating 0 to 60 degrees C
Rate of change 1 Degree C per minute without performance degradation
Storage -40 to 85 degrees C
Relative humidity
Operating 5 to 95% (non-condensing)
Storage 5 to 95% (non-condensing)
Hazardous area/location Class 1, Div 2, Groups A, B, C , D, T4 hazardous location
ATEX 3 G IIC T4

Field wiring Class 1, Div 2, Groups A, B, C, D, T4 non-incendive


ATEX 3 G IIC T4 -nL
Product Data Sheet
Classic I/O
Mar-04—Page 11

TM

Thermocouple Sensor Type Specifications

25°
Sensor Type Full Scale Operating Range Temperature Drift Resolution
Reference
Accuracy
Uncharacterized -100 to 100 mV -100 to 100 mV 0.1 mV ± 0.002 mV/ °C ~ 0.003mV
(no linearization,
no cold junction
compensation.)
B 250 to 1810° C 500 to 1810° C ± 2.4° C ± 0.056 ° C/ °C ~ 0.18° C
E -200 to 1000° C -200 to 1000° C ± 0.6° C ± 0.008° C/ °C ~ 0.07° C
J -210 to 1200° C -190 to 1200° C ± 0.8° C ± 0.011° C/ °C ~ 0.05° C
K -270 to 1372° C -200 to 1372° C ± 0.5° C ± 0.016° C/ °C ~ 0.18° C
N -270 to 1300° C -190 to 1300° C ± 1.0° C ± 0.007° C/ °C ~ 0.10° C
R -50 to 1768° C -50 to 1768° C ± 2.1° C ± 0.013° C/ °C ~ 0.14° C
S -50 to 1768° C -40 to 1768° C ± 2.2° C ± 0.067° C/ °C ~ 0.24° C
T -270 to 400° C -200 to 400° C ± 0.7° C ± 0.001° C/ °C ~ 0.04° C
Product Data Sheet
Classic I/O
Mar-04—Page 12

TM

mV Sensor Type Specifications

25°
Operating
Sensor Type Full Scale Reference Temperature Resolution
Range
Accuracy Drift
Low-level voltage -100 to 100 mV -100 to 100 mV 0.1 mV 0.002 mV/° C ~ 0.003 mV°
source

Isolated Input I/O Card


4
Specifications for Isolated Input Card,4 channel

Number of channels 4
Isolation CAN/CSA-C22.2 Installation Cat II, Pollution degree 2
5
No.10101-92
Channel to system - 600 V RMS double insulation
Channel to ground - 600 V RMS double insulation
Channel to channel - 600 V RMS basic insulation
Dielectric strength Channel to system - 3700 V RMS
Channel to channel - 2200 V RMS
ADC Resolution 16 bit
-3dB Filter Frequency 2.7 Hz
DC/50/60 Hz Common Mode Rejection 120 dB
Input Impedance 10 MΩ
Thermocouple Sensor Types B, E, J, K, N, R, S, T, Uncharacterized
RTD Sensor Types PT100, PT200, Ni120, Cu10, Resistance, User defined
mV and V ranges Refer to following Tables.
Input type mix Independently configurable
Ambient temperature -40 to 70°C
Calibration None required
Mounting Assigned slot of I/O carrier
LocalBus power rating 12 VDC, 350 mA, no field power required

4
DeltaV version 7.3 is required for this card.
5
Warning: When hazardous live voltages are present on a channel, adjacent channel wiring must be inaccessible.
Product Data Sheet
Classic I/O
Mar-04—Page 13

TM

Isolated Input Card, Thermocouple and MilliVolt Input Specifications

Item Specification

Linearization error 0.003% Full Scale


Cold Junction Compensation Accuracy 1.0°C
Cold Junction Compensation types Off, local, remote
Cold Junction Compensation range -40 to 85°C
Temperature scale ITS90
Open circuit detection (Thermocouple only) 0.4 mA DC
Detection time 1 second

Isolated Input Thermocouple Sensor Type Specifications

Sensor Types 25°C Reference Temperature Nominal Operating


Full Scale
Accuracy Drift Resolution Range
B 0.8° C 0.116 ° C/ °C 0.09° C 250 to 1810° C 500 to 1810° C
E 0.6° C 0.004° C/ °C 0.05° C -200 to 1000° C -200 to 1000° C
J 0.6° C 0.005° C/ °C 0.06° C -210 to 1200° C -190 to 1200° C
K 0.7° C .013° C/ °C 0.05° C -270 to 1372° C -200 to 1372° C
N 0.8° C .015° C/ °C 0.05° C -270 to 1300° C -190 to 1300° C
R 0.9° C .083° C/ °C 0.06° C -50 to 1768° C 0 to 1768° C
S 0.9° C .095° C/ °C 0.08° C -50 to 1768° C 0 to 1768° C
T 0.3° C .025° C/ °C 0.04° C -270 to 400° C -200 to 400° C
Uncharacterized 0.05 mV .0003 mV/ °C .0031 mV -100 to 100 mV -100 to 100 mV
no linearization or
CJC
Product Data Sheet
Classic I/O
Mar-04—Page 14

TM

Isolated Input Card, RTD, ohms Input Specifications

Item Specification

Measurement configurations 2, 3, and 4 wire

Excitation current 100 µA DC

Temperature scale ITS90

Open sensor detection time 1 second

Short circuit detection time 1 second

Pt 100 and Pt 200 alpha 0.00385

Isolated Input Card, RTD, ohms Input Range Specifications

25°C
Sensor Type Temperature Drift Resolution Sensor Input
Reference
Range
Accuracy
Pt100 ± 0.5° C ± 0.018° C/°C 0.05° C -200 to 850° C
Pt200 ± 0.5° C ± 0.012° C/°C 0.05° C -200 to 850° C
Ni120 ± 0.2° C ± 0.006° C/°C 0.02° C -70 to 300° C
Cu10 ± 1.0° C ± 0.076° C/°C 0.23° C -30 to 140° C
Resistance ± 0.5 ohms ± 0.018 ohms/°C 0.02 ohms 1 to 1000 ohm
Product Data Sheet
Classic I/O
Mar-04—Page 15

TM

Isolated Input Card, Voltage Input Range Specifications

25°C
Sensor Type Sensor Range Temperature Drift Maximum
Reference
Resolution
Accuracy
0-5V 0-5V ± 0.005 V ± 0.0002 V° C 0.00009 V
0 - 10 V 0 - 10 V ± 0.010 V ± 0.0004 V° C 0.00016 V
1-5V 1-5V ± 0.0005 V ± 0.0002 V° C 0.00009 V
1V ±1V ± 0.0025 V ± 0.0002 V° C 0.00015 V
5V ±5V ± 0.005 V ± 0.0002 V° C 0.00017 V
10 V ± 10 V ± 0.010 V ± 0.0004 V° C 0.0003 V
Product Data Sheet
Classic I/O
Mar-04—Page 16

TM

High-Density Discrete I/O Cards


Specifications for DI Card, 32 channel, 24 VDC, Dry Contact
Number of channels 32
Isolation Each channel is optically isolated from the system
at 250 VAC (No channel-to-channel isolation)
Detection level for On > 2 mA
Detection level for Off < 0.25 mA
Input impedance 5K ohm (approximate)
LocalBus current (12 VDC nominal) per 50 mA typical,
card
75 mA maximum
Field circuit power per card 150 mA at 24 VDC
Return Uses common return
Terminal block 32-screw termination block
Hazardous areas/location Class 1 Div 2, Groups A, B, C, D, T4 hazardous location
ATEX 3 G IIC T4

6
Field wiring Class 1, Div 2, Groups A, B, C, D, T4 non-arcing
7
ATEX 3 G IIC T4 -nA

6
Non-arcing field circuits are designed so that ignition does not occur during normal operation.
7
Non-sparking circuits (-nA) are designed to minimize the risk of occurrence of arcs, sparks, or hot spots capable of creating
ignition hazards during normal operation. Normal operation excludes the removal or insertion of field wiring with circuits
energized.
Product Data Sheet
Classic I/O
Mar-04—Page 17

TM

Specifications for DO Card, 32 channel, 24 VDC, High Side


Number of channels 32
Isolation Each channel is optically isolated from the system
at 250 VAC (No channel-to-channel isolation)
Output range 24 VDC ± 10%
Output rating 100 mA per channel
Off-state leakage 0.1 mA maximum
LocalBus current (12 VDC nominal) 100 mA typical,
per card
150 mA maximum
Field circuit power per card 3.2 A at 24 VDC per I/O interface
Return Uses common return
Terminal block 32-screw termination block
Class 1, Div 2, Groups A, B, C, D, T4 hazardous location
Hazardous area/location
ATEX 3 G IIC T4
Class 1, Div 2, Groups A, B, C, D, T4 non-arcing
Field wiring
ATEX 3 G IIC T4 -nA
Product Data Sheet
Classic I/O
Mar-04—Page 18

TM

Discrete I/O Cards


Specifications for DI Card, 8 channel, 24 VDC, Dry Contact
Number of channels 8
Isolation Each channel is optically isolated from the system
at 250 VAC
Detection level for On > 2.2 mA
Detection level for Off < 1 mA
Output Impedance 5 KΩ (approximate)
LocalBus current (12 VDC nominal) 75 mA typical,
per card
100 mA maximum
Field circuit power per card 40 mA at 24 VDC
Optional fuse 2.0 A

Hazardous area/location Class 1, Div 2, Groups A, B, C, D, T4 hazardous location


ATEX 3 G IIC T4

Field wiring Class 1, Div 2, Groups A, B, C, D, T4 non-incendive


ATEX 3 G IIC T4 -nL

Specifications for DI Card, 8 channel, 24 VDC, Isolated


Number of channels 8
Isolation Each channel is optically isolated from the system at 250 VAC and
from other channels at 150 VAC
Detection level for On > 10 VDC
Detection level for Off < 5 VDC
Input impedance 5 mA at 24 V
LocalBus current (12 VDC nominal) 75 mA typical,
per card
100 mA maximum
Field circuit power per card None
Optional fuse 2.0 A

Hazardous area/location Class 1, Div 2, Groups A, B, C, D, T4 hazardous location


ATEX 3 G IIC T4

Field wiring Class 1, Div 2, Groups A, B, C, D, T4 non-arcing


ATEX 3 G IIC T4 -nA
Product Data Sheet
Classic I/O
Mar-04—Page 19

TM

Specifications for DI Card, 8 channel, 120 VAC, Isolated


Number of channels 8
Isolation Each channel is optically isolated from the system at 250 VAC and
from other channels at 150 VAC
Detection level for On 84 to 130 VAC
Detection level for Off 0 to 34 VAC
Input load (contact cleaning) 2 mA at 120 VAC
Input Impedance 60 KΩ
LocalBus current (12 VDC nominal) 75 mA typical,
per card
100 mA maximum
Field circuit power per card None
Optional fuse 2.0 A
Hazardous area/location Class 1, Div 2, Groups A, B, C, D T4 hazardous location
Field wiring Class 1, Div 2, IIC T4 non-arcing
Product Data Sheet
Classic I/O
Mar-04—Page 20

TM

Specifications for DI Card, 8 channel, 120 VAC, Dry Contact


Number of channels 8
Isolation Each channel is optically isolated from the system at 250 VAC
Detection level for On > 1.4 mA
Detection level for Off < 0.56 mA
Output Impedance 60 KΩ
LocalBus current (12 VDC nominal) 75 mA typical,
per card
100 mA maximum
Field circuit power per card 15 mA at 120 VAC
Optional fuse 2.0 A
Hazardous area/location Class 1, Div 2, Groups A, B, C, D T4 hazardous location
Field wiring Class 1, Div 2 IIC T4 non-arcing

Specifications for DI Card, 8 channel, 230 VAC, Isolated


Number of channels 8
Isolation Each channel is optically isolated from the system at 250 VAC
Detection level for On 168 to 250 VAC
Detection level for Off 0 to 68 VAC
Input load (contact cleaning) 1 mA at 230 VAC
Input impedance 238 KΩ
LocalBus current (12 VDC nominal) 75 mA typical,
per card
100 mA maximum
Field circuit power per card None
Optional fuse 2.0 A
Hazardous area/location Class 1, Div 2, Groups A. B, C, D T4 hazardous location
Field wiring Class 1, Div 2 IIC T4 non-arcing
Product Data Sheet
Classic I/O
Mar-04—Page 21

TM

Specifications for DI Card, 8 channel, 230 VAC, Dry Contact


Number of channels 8
Isolation Each channel is optically isolated from the system and from other
channels at 250 VAC
Detection level for On > 0.71 mA
Detection level for Off < 0.28 mA
Output impedance 238 KΩ
LocalBus current (12 VDC nominal) 75 mA typical,
per card
100 mA maximum
Field circuit power per card 7 mA at 230 VAC
Optional fuse 2.0 A
Hazardous area/location Class 1, Div 2, Groups A, B, C, D T4 hazardous location
Field wiring Class 1, Div 2 IIC T4 non-arcing
Product Data Sheet
Classic I/O
Mar-04—Page 22

TM

Specifications for DO Card, 8 channel, 120/230 VAC, Isolated


Number of channels 8
Each channel is optically isolated from system at 250 VAC and from
Isolation
other channels at 150 VAC
Output range 20 to 250 VAC
1.0 A continuous per channel;
Output rating 2.0 A maximum per card up to 60 C° (140 F°)
3.0 A maximum per card up to 50 C° (122 F°)
2 mA maximum at 120 VAC
Off state leakage
4 mA maximum at 230 VAC

LocalBus current (12 VDC nominal) 100 mA typical,


per card 150 mA maximum
Field circuit power per card None
Configurable channel types: Output
Discrete output Output stays in last state submitted by the controller.
Momentary output Output is active for a pre-configured time period (100 ms to 100 s).
Output is active as a percentage of a pre-configured base time
Continuous pulse output
period (100 ms to 100 s). Resolution = 5 ms
Optional fuse 2.0 A
Hazardous area/location Class 1, Div 2, Groups A, B, C, D T4 hazardous location
Field wiring Class 1, Div 2 IIC T4 non-arcing
Product Data Sheet
Classic I/O
Mar-04—Page 23

TM

8
Specifications for DO Card, 8 channel, 120/230 VAC, High Side
Number of channels 8
Isolation Each channel is optically isolated from the system at 250 VAC
Output range 20 to 250 VAC
Output rating 1.0 A continuous per channel;
2.0 A maximum per card up to 60 C° (140 F°)
3.0 A maximum per card up to 50 C° (122 F°)
Off state leakage 2 mA maximum at 120 VAC
4 mA maximum at 230 VAC
LocalBus current (12 VDC nominal) 100 mA typical,
per card
150 mA maximum
Field circuit power per card 3.0 A at 120 VAC or 230 VAC
Configurable channel types: Output
Discrete output Output stays in last state submitted by the controller
Momentary output Output is active for a pre-configured time period (100 ms to 100 s).
Continuous pulse output Output is active as a percentage of a pre-configured base time
period (100 ms to 100 s). Resolution = 5 ms
Optional fuse 2.0 A

Hazardous area/location Class 1, Div 2, Groups A, B, C, D T4 hazardous location

Field wiring Class 1, Div 2 IIC T4 non-arcing

8
High-side means the output signal is switched on the positive leg. Switching on the positive leg avoids current in field
wiring when there is no output signal.
Product Data Sheet
Classic I/O
Mar-04—Page 24

TM

Specifications for DO Card, 8 channel, 24 VDC, Isolated


Number of channels 8
Isolation Each channel is optically isolated from the system at 250 VAC and
from other channels at 150 VAC
Output range 2 VDC to 60 VDC
Output rating 1.5 A
Off state leakage 1.2 mA maximum
LocalBus current (12 VDC nominal) 100 mA typical,
per card
150 mA maximum
Field circuit power per card None
Configurable Channel Types: Output
Discrete output Output stays in last state submitted by the controller.
Momentary output Output is active for a pre-configured time period (100 ms to 100 s).
Continuous pulse output Output is active as a percentage of a pre-configured base time
period (100 ms to 100 s). Resolution = 5 ms
Hazardous area/location Class 1, Div 2, Groups A, B, C, D, T4 hazardous locations
ATEX 3 G IIC T4
Field wiring Class I, Div 2 Groups A, B, C, D, T4 non-arcing
ATEX 3 G IIC T4 -nA
Product Data Sheet
Classic I/O
Mar-04—Page 25

TM

Specifications for DO Card, 8 channel, 24 VDC, High Side


Number of channels 8
Isolation Each channel is optically isolated from the system at 100 VAC
Output range 2 VDC to 60 VDC
Output rating 1.0 A continuous per channel;
3.0 A maximum per I/O Interface
Off state leakage 1.2 mA maximum
LocalBus current (12 VDC nominal) 100 mA typical,
per card
150 mA maximum
Field circuit power per card 3.0 A at 24 VDC per I/O Interface
Configurable channel types: Output
Discrete output Output stays in last state submitted by the controller.
Momentary output Output is active for a pre-configured time period (100 ms to 100 s).
Continuous pulse output Output is active as a percentage of a pre-configured base time
period (100 ms to 100 s). Resolution = 5 ms
Optional fuse 2.0 A
Hazardous area/location Class 1, Div 2, Groups A, B, C, D, T4 hazardous locations
ATEX 3 G IIC T4
Field wiring Class I, Div 2 Groups A, B, C, D, T4 non-arcing
ATEX 3 G IIC T4 -nA
Product Data Sheet
Classic I/O
Mar-04—Page 26

TM

I/O Terminal Blocks


A variety of I/O terminal blocks is available to meet
specific functionality and environmental
requirements. I/O terminal blocks and I/O cards used
together are equipped with function and field wiring
protection keys to ensure that only the I/O card and
I/O terminal block that match functionally can be
plugged into each other.

The terminal block keys can be preset to speed


installation. For field devices that are located in an
intrinsically safe zone, or discrete field devices that
require more than the maximum specified current,
standard mass terminated interfaces are provided
with 10-, 16-, or 24-pin connections to allow mass
termination cable connection to intermediary panels.
The systems integrator usually installs these panels.
The low-level signals are conducted over 0.093 mm²
(28 AWG) ribbon cable or round instrument cable.

For field devices requiring external power, the 4-wire


I/O terminal block is available. This particular I/O
terminal block is used in conjunction with the AI, 4-
20 mA card.

Function
keys

24 pin 10 pin 16 pin


Standard mass terminated interfaces.
Product Data Sheet
Classic I/O
Mar-04—Page 27

TM

The following tables list specifications for I/O and mass termination blocks:

Specifications for I/O Terminal Blocks

Voltage rating Varies for card type


Maximum current Varies for card type
Hazardous • Class 1, Div 2, Groups A, B, C, D
area/location T4 hazardous locations
• ATEX 3 G IIC T4

Specifications for Mass Terminal Blocks

Models 10-pin mass termination block


16-pin mass termination block
24-pin mass termination block
Maximum current 1 A per I/O Channel (16-pin)
1 A per cable (10-pin, 24-pin)
Voltage rating 30 VDC between non-connected
signals
Maximum cable length 4 m. (13.1 ft.)
Key position Set the key position based on I/O card
type.
Factory settings:
10-pin: B6
16-pin: A1
24-pin: A3
Hazardous • Class 1, Div 2, Groups A, B, C, D
area/location T4 hazardous locations
• ATEX 3 G IIC T4
Product Data Sheet
Classic I/O
Mar-04—Page 28

TM

Options

The table below lists Classic I/O and terminal block compatibility:

I/O Card – Terminal Block Compatibility

I/O Card I/O Card Keying Recommended I/O Optional I/O


Terminal Block Terminal Block

AI, 8-channel, 4–20 mA A1 I/O terminal block Fused I/O terminal block 4-wire I/O
terminal block 16-pin mass termination
block (2-wire connection)
AI, 8-channel, 1–5 VDC A3 4-wire I/O terminal block 24-pin mass termination block
AO, 8-channel,4–20 mA A4 I/O terminal block Fused I/O terminal block 16-pin mass
termination block
Isolated Input Card C2 Isolated Input Terminal NA
Block
DI, 8-channel, 24 VDC, B2 I/O terminal block Fused I/O terminal block 16-pin mass
Isolated termination block
DI, 8-channel, 24 VDC, B1 Fused I/O terminal block I/O terminal block
dry contact 16-pin mass termination block
DI, 8-channel, 120 VAC, E4 I/O terminal block Fused I/O terminal block
isolated
DI, 8-channel, 120 VAC, E1 Fused I/O terminal block I/O terminal block
dry contact
DI, 8-channel, 230 VAC, E5 I/O terminal block Fused I/O terminal block
isolated
DI, 8-channel, 230 VAC, E2 Fused I/O terminal block I/O terminal block
dry contact
DO, 8-channel, 120 F4 I/O terminal block Fused I/O terminal block
VAC/230 VAC, isolated
DO, 8-channel, 120 F1 Fused I/O terminal block I/O terminal block
VAC/230 VAC, high side
DO, 8-channel, 24 VDC, B5 I/O terminal block Fused I/O terminal block 16-pin mass
isolated termination block
DO, 8-Channel, 24 VDC, B6 Fused I/O terminal block I/O terminal block
High Side 10-pin mass termination block
16-pin mass termination block
Product Data Sheet
Classic I/O
Mar-04—Page 29

TM

Ordering Information

Model Number Description

VE4001S2T1B1 Discrete Input Card: 8 Channels, 24Vdc, Isolated, Standard I/O Termination Block

VE4001S2T1B2 Discrete Input Card: 8 Channels, 24Vdc, Isolated, Fused I/O Termination Block

VE4001S2T1B3 Discrete Input Card: 8 Channels, 24Vdc, Isolated, 16-Pin Mass I/O Termination Block

VE4001S2T2B1 Discrete Input Card: 8 Channels, 24Vdc, Dry Contact, I/O Termination Block

VE4001S2T2B2 Discrete Input Card: 8 Channels, 24Vdc, Dry Contact, Fused I/O Termination Block

VE4001S2T2B3 Discrete Input Card: 8 Channels, 24Vdc, Dry Contact, 16-Pin Mass I/O Termination Block

VE4001S2T2B4 Discrete Input Card: 32 Channels, 24 Vdc, Dry Contact, Termination Block

VE4001S3T1B1 Discrete Input Card: 8 Channels, 120Vac, Isolated, I/O Termination Block

VE4001S3T1B2 Discrete Input Card: 8 Channels, 120Vac, Isolated, Fused I/O Termination Block

VE4001S3T2B1 Discrete Input Card: 8 Channels, 120Vac, Dry Contact, I/O Termination Block

VE4001S3T2B2 Discrete Input Card: 8 Channels, 120Vac, Dry Contact, Fused I/O Termination Block

VE4001S4T1B1 Discrete Input Card: 8 Channels, 230Vac, Isolated, I/O Termination Block

VE4001S4T1B2 Discrete Input Card: 8 Channels, 230Vac, Isolated, Fused I/O Termination Block

VE4001S4T2B1 Discrete Input Card: 8 Channels, 230Vac, Dry Contact, I/O Termination Block

VE4001S4T2B2 Discrete Input Card: 8 Channels, 230Vac, Dry Contact, Fused I/O Termination Block

VE4002S1T1B1 Discrete Output Card: 8 Channels 24Vdc, Isolated, I/O Termination Block

VE4002S1T1B2 Discrete Output Card: 8 Channels 24Vdc, Isolated, Fused I/O Termination Block

VE4002S1T1B3 Discrete Output Card: 8 Channels 24Vdc, Isolated, 16-Pin Mass I/O Termination Block

VE4002S1T2B1 Discrete Output Card: 8 Channels 24Vdc, High Side, I/O Termination Block

VE4002S1T2B2 Discrete Output Card: 8 Channels 24Vdc, High Side, Fused I/O Termination Block
Product Data Sheet
Classic I/O
Mar-04—Page 30

TM

Ordering Information (continued)

VE4002S1T1B1 Discrete Output Card: 8 Channels 24Vdc, Isolated, I/O Termination Block

VE4002S1T1B2 Discrete Output Card: 8 Channels 24Vdc, Isolated, Fused I/O Termination Block

VE4002S1T1B3 Discrete Output Card: 8 Channels 24Vdc, Isolated, 16-Pin Mass I/O Termination Block

VE4002S1T2B1 Discrete Output Card: 8 Channels 24Vdc, High Side, I/O Termination Block

VE4002S1T2B2 Discrete Output Card: 8 Channels 24Vdc, High Side, Fused I/O Termination Block

VE4002S1T2B3 Discrete Output Card: 8 Channels 24Vdc, High Side, 16-Pin Mass I/O Termination Block

VE4002S1T2B4 Discrete Output Card: 8 Channels 24Vdc, High Side, 10-Pin Mass I/O Termination Block

VE4002S1T2B5 Discrete Output Card, 32 Channels, 24Vdc, High Side, I/O Termination Block

VE4002S2T1B1 Discrete Output Card: 8 Channels 115/230Vac, Isolated, I/O Termination Block

VE4002S2T1B2 Discrete Output Card: 8 Channels 115/230Vac, Isolated, Fused I/O Termination Block

VE4002S2T2B1 Discrete Output Card: 8 Channels 115/230Vac, High Side, I/O Termination Block

VE4002S2T2B2 Discrete Output Card: 8 Channels 115/230Vac, High Side, Fused I/O Termination Block

VE4003S2B1 Analog Input Card: 8 Channels 4-20 mA, HART, I/O Termination Block

VE4003S2B2 Analog Input Card: 8 Channels 4-20 mA, HART, Fused I/O Termination Block

VE4003S2B3 Analog Input Card: 8 Channels 4-20 mA, HART, 4-wire I/O Termination Block

VE4003S2B4 Analog Input Card: 8 Channels 4-20 mA, HART, 16-Pin Mass I/O Termination Block

VE4003S3B3 Analog Input Card: 8 Channels 1-5 Vdc, 4-wire I/O Termination Block

VE4003S3B4 Analog Input Card: 8 Channels 1-5 Vdc, 16-Pin Mass I/O Termination Block

VE4003S3B5 Analog Input Card: 8 Channels 1-5 Vdc, 24-Pin Mass I/O Termination Block

VE4003S4B1 Analog Input Card: 8 Channels, mV Ranges, I/O Termination Block

VE4003S5B1 Analog Input Card: 8 Channels Thermocouple, CJC Termination Block


Product Data Sheet
Classic I/O
Mar-04—Page 31

TM

Ordering Information (continued)

VE4003S6B1 Analog Input Card: 8 Channels RTD, RTD Termination Block

VE4003S7B1 Isolated Input Card , 4 Isolated Channels for T/C, RTD, mv, or volts; Isolated Input terminal
Block
VE4005S2B1 Analog Output Card: 8 Channels 4-20 mA, HART, I/O Termination Block

VE4005S2B2 Analog Output Card: 8 Channels 4-20 mA, HART, Fused I/O Termination Block

VE4005S2B3 Analog Output Card: 8 Channels 4-20 mA, HART, 16-Pin Mass I/O Termination Block

Prerequisites

DeltaV version 7.3 is required for 4-channel isolated card.

To locate a sales office near you, visit our website at: www.EasyDeltaV.com/reach

…or call us at: Asia Pacific: 65.777.8211


Europe, Middle East: 41.41.768.6111
North America, Latin America: +1 800.833.8314 or
+1 512.832.3774

For large power, water, and wastewater applications contact Power and Water Solutions at:
www.emersonprocess-powerwater.com

…or call us at: Asia Pacific: 65.777.8211


Europe, Middle East, Africa: 48.22.630.2443
North America, Latin America: +1 412.963.4000

©Fisher-Rosemount Systems, Inc. 1996—2004 All rights reserved.

DeltaV, the DeltaV design, SureService, the SureService design, SureNet, the SureNet design, and PlantWeb are marks of one of the Emerson Process
Management group of companies. All other marks are property of their respective owners. The contents of this publication are presented for informational
purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warrantees or guarantees, express or implied,
regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on
request. We reserve the right to modify or improve the design or specification of such products at any time without notice.

You might also like