300.000 PRODUCTS/MATERIALS
All equipment and assemblies which fall within the scope of the Pressure Equipment
Directive (PED) 2014/68/EU, must be tested by the manufacturer, and be certified as
compliant with the Directive. Such compliance shall be evidenced by displaying the
appropriate CE Mark on the equipment and assemblies.
Only relevant equipment and assemblies certified as compliant will be permitted under this
specification, and any substitution put forward must also be compliant with the Directive.
Comply with the relevant requirements and recommendations of the Local Authorities
having jurisdiction.
Comply with the pollution prevention guidelines for projects in locations where they are still
enforced by the local Environmental Agency.
Comply with:
o Guidance in the Health and Safety Executive HSG176 on design and construction of
installations for the storage of flammable liquids.
o Code of practice for oil firing BS 5410-1 or BS 5410-2 or BS 5410-3 to suit particular
application.
All relevant equipment to comply with OFTEC requirements for the application.
Diesel oil:
o Standard - BS EN 12285-2
o Type:
Access
o [Manholes]
o [Inspection openings]
Paint and clean tanks in accordance with the tank construction standard and manufacturer's
recommendations.
Accessories
o Level measurement:
o Water detection
o Temperature measurement
Drain valves
Install one piece bronze ball valve with hose end connection at low points in fuel oil piping.
Vent pipes
o Ladder
Bund details
Standard - BS EN 13341.
o Tank material
Construction
[Single skin.]
[Bunded.]
Marking
Accessories
Drain valves
o Install one piece bronze ball valve with hose end connection at low points in fuel oil
piping.
Vent pipes
o Install pressure relief valves in distribution piping between supply and return lines.
Telemetry
Ladder
Bund details
Fuel oil distribution piping and joints and fittings should conform to BS 5410 and the relevant
OFTEC codes.
[Type A]
Standards:
Supply and install a leak detection system in the fuel oil storage/distribution system. Link the
system to an integral alarm system.
Filter screen:
Ancillaries:
o Matching flanges.
o Drain valve.
300.120 CARTRIDGE TYPE STRAINERS:
Duty:
Details:
o Strainer Screen: 60-mesh startup strainer, and perforated stainless-steel basket with
50 percent free area.
Material:
o Meter:
[Brass]
[Cast iron]
o Working chamber:
[Brass]
[Bronze]
o Ancillaries:
Batching unit
Cathodic protection of buried metallic tanks and related piping to be provided in accordance
with BS EN 13636.
Type:
o Gear type
Motor:
o Motor operating conditions
o Surge suppressors
o Motor type
[Induction (asynchronous).]
[IK08.]
Motor efficiency
o [IP55.]
Accessories
o Matching flanges
Audible alarm is not required when there is a BMS interface for the Pumps.
For interface points to the BMS, refer to BMS control diagrams and specs.
[Audible alarm.]
Control panel
o [BACnet]
o [ModBus]
Accessories
o Combined anti-vacuum, automatic air vent and surge protection valve supplied loose
for fitting at top of risers.
310.000 WORKMANSHIP
As appropriate to the particular project, comply where practically possible with the
requirements of the relevant parts of BS EN 12514 for the safety and corresponding tests for
plant, equipment and pipework within an oil supply installation to burners.
The document specifies that the fuel storage system includes a day-tank and a larger storage tank
system for fuel transfer. However, the exact volume of fuel storage is not directly mentioned. The
system includes day-tank instruments for monitoring fuel levels and alarms for over-fill and low-level
conditions.
9.1.3.13 Fuel system for outdoor generator
Fuel oil fill point at street level installed at the wall of adjacent electric substation.
Gear type simplex fuel oil pump sets (1 acting & 1 standby) to transfer fuel to daily tanks
located in the fenced area related to fuel tanks.
The tanks will be FRP above ground tanks surrounded with 1.5 m height fenced area, the
area between fence and tanks are related to fuel dike area.
Two tanks with estimated capacity 42,000 lit based on 8 operation hours per day for 5 days.
A. Day-tank Construction:
Fitted with drain plug, inlet and outlet pipe connectors, and breather pipe
Shall have replaceable paper air filter or breather caps with air filters
C. Day-tank instruments:
Installed on piping system between storage tank and one or more day-tanks for fuel transfer
Pump shall be self-priming type against the specific head shown on the Drawings
E. Day-tank Connections:
Fitted through holes in top of tank and welded all around inside and outside
Connections, except vent connection, shall extend inside tank to within 150 mm of bottom
Seamless black steel pipes of same size as connection and braced to tank walls
A manual valve shall be provided on the fuel supply line to the genset
F. Fuel Lines:
Treated internally with corrosion resistant paint and with joints sealed with PTFE tape
Changes in direction and branching and jointing shall be with regular pipefitting
G. Fuel Lines:
Size of fuel return line from day-tank to main fuel tank shall be to manufacturer's
recommendations
H. Valves Generally:
827.4 kPa (steam working pressure rating) and 1380 kPa cold water non-shock pressure
rating
Galvanized steel
Fuel:
Tanks:
Gear type simplex fuel oil pump sets (1 acting & 1 standby) to transfer fuel to daily tanks
located in the fenced area related to fuel tanks
FRP above ground tanks surrounded with 1.5 m height fenced area, the area between fence
and tanks are related to fuel dike area
Two tanks with estimated capacity 42,000 liters based on 8 operation hours per day for 5
days
9.1.3.13 Fuel System for Fuel Type Fuel oil No. 2 (light diesel oil) for outdoor
Outdoor Generator emergency generators.
Fuel Oil Fill Point Located at street level, installed at the wall of the
adjacent electric substation.
Fuel Oil Pumps Gear type simplex fuel oil pump sets (1 active & 1
standby) to transfer fuel to day-tanks.