Consulting - Specifying Engineer _ Seismic codes for nonstructural engineering

The document discusses the importance of seismic design for mechanical, electrical, and plumbing (MEP) components in buildings, emphasizing that their proper attachment is crucial for safety during earthquakes. It outlines the role of building codes, specifically the International Building Code and ASCE 7, in determining seismic design categories and requirements for MEP systems. The authors provide guidance on best practices for MEP engineers to ensure systems function effectively before, during, and after seismic events.

Uploaded by

xianren2
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3 views

Consulting - Specifying Engineer _ Seismic codes for nonstructural engineering

The document discusses the importance of seismic design for mechanical, electrical, and plumbing (MEP) components in buildings, emphasizing that their proper attachment is crucial for safety during earthquakes. It outlines the role of building codes, specifically the International Building Code and ASCE 7, in determining seismic design categories and requirements for MEP systems. The authors provide guidance on best practices for MEP engineers to ensure systems function effectively before, during, and after seismic events.

Uploaded by

xianren2
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

GET THE LATEST UPDATES ON THE CORONAVIRUS IMPACT ON ENGINEERS.

CLICK HERE

Seismic codes for nonstructural engineering


Mechanical, electrical, and plumbing components are not always taken into account
when the thought of earthquakes comes up, but proper attachment to the structure
can be just as important as proper attachment of a beam or column.
BY BEAU M. SANDERS, PE, SE; AND URIAH J. WOLFE, PE, SE, LEED AP; GRAEF, MILWAUKEE
MARCH 8, 2011

While most people know that earthquakes can cause buildings, bridges, and other structures to crack,
distort, and even fail, mechanical, electrical, and plumbing system failures often get overlooked. People fear
earthquakes because they can be injured from falling structural elements like columns or beams or
architectural components like brick facades or windows. But what about the lights overhead, the rooftop
units, pipes, or storage tanks? These nonstructural components can injure people when their supports and
attachments fail.

The number-one goal of a building code is to protect people. The building code that governs the majority of
the United States is the International Building Code (IBC), which is published by the International Code
By using this website, you agree to our use of cookies. This may include personalization of content and ads, and tra c analytics. Review our
Council (ICC). IBC Chapter 16, as well as Chapters 11-13 and 15-23 of American Society of Civil Engineers X
Privacy Policy for more information.
(ASCE) 7—Minimum Design Loads for Buildings and Other Structures address seismic design Although the
(ASCE) 7 Minimum Design Loads for Buildings and Other Structures, address seismic design. Although the
main purpose of the IBC is to safeguard against major structural failures and loss of life, this does not imply
that damage should be limited or the function of the building be maintained. Buildings and other structures
that support the mechanical, electrical, or plumbing (MEP) components are divided into occupancy
categories (IBC Table 1604.5), which are used to determine the level of seismic loads and detailing required.

Essential facilities such as hospitals, police and re stations, power plants, or water treatment facilities are
examples of higher level occupancy categories (III or IV), which can require a higher level of analysis, design,
and detailing than a lower occupancy category building in the same region of the country. Essential facilities
like these require immediate occupancy or continued use after an earthquake, which can require continued
function of MEP components after an earthquake as well. Life safety systems such as re sprinkler systems
and essential electrical systems require seismic bracing to stay in service.

To determine the level of analysis, design, and detailing that will be required for the structural, architectural,
and MEP components, the structural engineer will need to calculate the seismic design category. This
calculation takes into account the location of the building near a fault, the occupancy category of the
building (as previously mentioned), and the soil characteristics of the site. Seismic design categories A, B, or
C are deemed low to moderate, whereas categories D, E, or F are deemed high to severe. Structures located
in California, for example, will typically fall into a high to severe category, while structures located in
Wisconsin will fall into low to moderate. Once the seismic design category has been determined, the analysis
and design begins. The design of MEP supports and anchorages is covered in ASCE sections 13.3, 13.4, and
13.6.

Below is a partial list of some important items that should be considered and shown by MEP engineers on
the construction documents. The list is culled from three very useful documents produced by the Federal
Emergency Management Agency (FEMA)—412, 413, 414—as well as from the authors’ personal experience.
The FEMA documents are only guides; in all instances local building codes, such as the IBC, control the
design.

The most important thing to remember when detailing and installing seismic restraints for any type of
MEP equipment is to make sure building structures are capable of supporting the seismic bracing
loads. This should be veri ed by a trained professional, such as a licensed structural engineer of
record.
The general design concept, including size of bracing and anchorage sizes, should be shown on
construction documents. Ask the local building o cial if the bracing connections and sizes need to be
stamped by a licensed engineer.
Raceways, conduits, ducts, and cable trays: There are a
number of different ways to support raceways, but
different bracing systems should not be mixed. Each run
of conduits or cable trays must have at least one
transverse support at each end of the run and at least
one longitudinal support anywhere on the run. Seismic
bracing is not required per ASCE 7 if the ducts or piping
are supported 12 in. on center or less or if the area of
Bythe duct
using is lessyou
this website, than
agree6tosq
ourft.
useFigure 1 shows
of cookies. This mayan example
include personalization of content and ads, and tra c analytics. Review our X
Privacy Policy for more information.
of conduit bracing for a larger diameter conduit.
of conduit bracing for a larger diameter conduit.

Rigid oor-mounted equipment: Do not shim, or attach directly to the steel structure or concrete
structure. Do not use oversize holes. Where continuous angles are used on either side of the
equipment, provide a minimum of four bolts (two to the structure and two the equipment) per side.
Where angles are used at each corner, a minimum of three bolts per connection shall be used (two to
the structure and one to the equipment or vice versa). Welding to the equipment or existing steel
structure is an acceptable connection. Figure 2 shows examples of acceptable and unacceptable rigid
oor-mounted attachment con gurations.
Talk to the structural engineer of record to understand
the type of construction being used. Certain fasteners
cannot be used with certain types of construction.
Anchors: When choosing an anchor, a designer must
take into account the particular application. When using
anchors for safety-related applications, such as sprinkler
systems, heavy suspended pipes, etc., anchors must be
IBC approved and designed per the American Concrete
Institute (ACI) 318 Appendix D, and should be designed
by a licensed structural engineer of record. Some
anchors should not be used with vibratory loads. ASCE 7
does not allow for expansion anchors to be used in
mechanical equipment rated over 10 hp unless they
have vibration isolators. Contact an anchor supplier to
determine the proper product for your application.
Approved construction documents may require special
inspection or eld testing per IBC Chapter 17.
Special inspection: Special inspection may be required for certain installations. As mentioned above,
the installation of anchors will need to be periodically inspected in seismic design categories C, D, E, or
F. Some examples of systems that require this inspection are electrical equipment for emergency
standby power; piping systems intended to carry ammable, combustible, or highly toxic content; and
HVAC ductwork that will contain hazardous materials. Special inspection also will be required for
isolator units and energy dissipation devices that are part of the seismic isolation system.
Power-actuated fasteners: Used to directly fasten equipment for permanent installation, these are
typically not used for equipment weighing more than 40 lbs or for equipment not allowed by code for
tension applications in seismic design categories D, E, or F per ASCE 7.
Suspended equipment: Attachment should be located
just above the center of gravity to minimize swinging. It
should be a rigid attachment with brackets to the
equipment using double nuts and washers. Equipment
weighing less than 75 lbs does not require special
seismic requirements per ASCE 7. See Figure 3 for an
example of suspended equipment with seismic bracing.
Housekeeping pads must be designed for the equipment weight and the seismic loads.
Isolators: Talk to your equipment representative about whether an isolator is required. The three main
types are open, housed, and restrained. Never use housed vibration isolators for seismic applications
By using this website, you agree to our use of cookies. This may include personalization of content and ads, and tra c analytics. Review our X
as they cannot resist uplift. Never use open vibration isolators without snubbers or bumpers.
Privacy Policy for more information.
Installation is critical when installing isolators; if an isolator is installed incorrectly vibration will cause
Installation is critical when installing isolators; if an isolator is installed incorrectly, vibration will cause
it to malfunction or become a noise problem. See Figure 4 for an installed example of vibration
isolators. There are a number of proprietary products on the market today that help with vibration
isolation. Ask your equipment representative which product would be most appropriate for your
speci c job.

Earthquakes are major physical occurrences that can have


devastating effects on both existing infrastructure and human
life. Due to advancement through research and better code
development, structural engineers are better able to design
buildings to withstand earthquakes and signi cantly reduce
loss of life and destruction of property. Unfortunately, MEP
components are not always taken into account when
earthquakes are considered, but properly attaching the
components to the structure can be just as important as
properly attaching beams or columns. With careful
communication and coordination with the structural engineer
of record as well as a rm grasp of existing building codes, an
MEP engineer can design a system that functions properly
before, during, and after an earthquake.

Sanders is a structural project manager for GRAEF. He has 6


years of experience in the design of healthcare, commercial,
governmental, industrial, and educational structures. Wolfe is a
structural project manager and an associate for GRAEF. He
has 12 years of experience in the design of commercial,
industrial, and governmental structures.

References:
American Concrete Institute: Building Code Requirements for Structural Concrete, 2005.

American Society of Civil Engineers: Minimum Design Loads for Buildings and Other Structures (ASCE 7),
2005.

Federal Emergency Management Agency: Installing Seismic Restraints for Mechanical Equipment (FEMA
412), 2004.

Federal Emergency Management Agency: Installing Seismic Restraints for Electrical Equipment (FEMA 413),
2004.

Federal Emergency Management Agency: Installing Seismic Restraints for Duct and Pipe (FEMA 414), 2004.

International Code Council: International Building Code, 2006.

Lindeberg, Michael and McMullin, Kurt: Seismic Design of Building Structures—A Professional’s Introduction to
Earthquake Forces and Design Details, 2008.
By using this website, you agree to our use of cookies. This may include personalization of content and ads, and tra c analytics. Review our X
Privacy Policy for more information.
Related Articles
Solving Seismic Design Challenges for Fire-Sprinkler Systems at JFK
Protecting nonstructural systems in earthquakes