Pub111 103 00 - 1117
Pub111 103 00 - 1117
1. General
The actuators shall be suitable for use on a nominal _volt, _ phase, _Hz power supply and are to
incorporate motor, integral reversing starter, local control facilities and terminals for remote control and
indication connections housed within a self-contained, sealed enclosure.
As a minimum the actuators should meet the requirements set out in EN15714-2 and ISA SP96.02.
Standard actuator commissioning of torque levels and position limits shall be carried out through physical
adjustment of a mechanical switch mechanism interface. The switch mechanism shall include switches
to adequately control the integral motor of the actuator.
An alternative switch mechanism may be offered, providing full digital feedback of torque and position
to the control interface. This digital switch mechanism should ensure that commissioning becomes a
non-intrusive process that maintains the integrity of the enclosure whilst including as few as possible
moving parts.
In order to maintain the integrity of the enclosure configuration of the indication contacts etc. shall be
carried out without the removal of any actuator covers. It should be possible to configure the actuator
with the local controls however an alternative method of configuration should also be provided using an
Infrared or Bluetooth® wireless interface. When applicable, supplementary configuration tools must meet
the enclosure protection and certification levels of the actuators. In addition, provision shall be made for
the protection of configured actuator settings by a means independent of access to the commissioning
method. Provision shall be made to disable Bluetooth® communications or only allow a Bluetooth®
connection initiated by an Infra-Red command for maximum security.
The actuator shall include a device to ensure that the motor runs with the correct rotation for the required
direction of valve travel irrespective of the connection sequence of the power supply.
2. Actuator Sizing
The actuator shall be sized to guarantee valve closure at the specified differential pressure and
temperature. The safety margin of motor power available for seating and unseating the valve shall be
sufficient to ensure torque switch trip at maximum valve torque with the supply voltage 10% below
nominal. For linear operating valves, the operating speed shall be such as to give valve closing and
opening at approximately 10-12 inches per minute unless otherwise stated in the data sheet. For 90 °
valve types the operating time will be specified.
One actuator frame size (matching external dimensions) shall be available covering output speeds from
9 to 192 rpm for a given torque range, to avoid over sizing and unnecessary weight load on the valve
stem, flange and yoke assembly. An increase of actuator size caused by higher actuator output speed
is not acceptable to avoid weight over sizing of actuators. Actuators must be selected to provide sufficient
torque required for safe valve operation. Actuator rated output torque must be available at 90 % of
nominal build voltage.
In order to enable proper sizing of applicable electric equipment, actuator supplier has to disclose load
value (Amps) at rated actuator torque. A locked rotor current figure must also be provided to ensure
maximum potential starting conditions can be accommodated. Actuator shall be capable of opening and
closing the valve against full differential pressure within specified time on valve data sheet.
3. Environmental
Actuators shall be suitable for indoor and outdoor use. The actuator shall be capable of functioning in
an ambient temperature ranging from -30°C (-22°F) to 70°C (140°F), up to 100% relative humidity.
Actuators shall be built with suitable alternative seals, lubrication and bearings should a lower ambient
temperature range be required.
Actuators shall be O-ring sealed, watertight to IP68 8m for 96hrs, NEMA 4 & 6. The motor and all other
internal electrical elements of the actuator shall be protected from ingress of moisture and dust when
the terminal cover is removed for site cabling. If required, the actuator manufacturer should ensure the
ingress protection rating of the actuator is maintained whilst the terminal compartment is removed.
The actuator shall be able to complete 10 operations during submersion.
5. Motor
The motor shall be an integral part of the actuator, designed specifically for valve actuator applications.
It shall be a low inertia high torque design, capable of delivering rated torque when power is turned on.
All motors shall be of high starting torque type to facilitate 'unseating' of the valve. Each motor shall have
a rating plate marked in accordance with IEC 34.1 as far as applicable.
Standard isolating duty actuators shall include class F insulated motors with a class B temperature rise
giving a time rating of 15 minutes at 40°C (104°F) at an average load of at least 33% of maximum valve
torque. Temperature shall be limited by 2 thermostats embedded in the motor stator windings and
integrated into its control. Electrical and mechanical disconnection of the motor should be possible
without draining the lubricant from the actuator gearcase.
7. Gearing
The actuator gearing shall be totally enclosed in an oil-filled gearcase suitable for operation at any
angle. Grease lubrication is not permissible. All drive gearing and components must be of metal
construction and incorporate a lost-motion hammer blow feature. To ensure immediate drive output
response, modulating duty actuators should not include a hammer blow feature. For rising spindle
valves the output shaft shall be hollow to accept a rising stem, and incorporate thrust bearings of the
ball or roller type at the base of the actuator. The design should be such as to permit the opening of
the gearcase for inspection or disassembled without releasing the stem thrust or taking the valve out
of service. For 90° operating type of valves drive gearing shall be self-locking to prevent the valve back-
driving the actuator.
8. Hand Operation
A handwheel shall be provided for emergency operation, engaged when the motor is declutched by a
lever or similar means, the drive being restored to electrical operation automatically by starting the motor.
The handwheel or selection lever shall not move on restoration of motor drive. Provision shall be made
for the hand/auto selection lever to be locked in both hand and auto positions. It should be possible to
select hand operation while the actuator is running or start the actuator motor while the hand/auto
selection lever is locked in hand without damage to the drive train.
Clockwise operation of the handwheel shall provide closing movement of the valve unless otherwise
stated in the data sheet. For linear valve types the actuator handwheel drive must be mechanically
independent of the motor drive and should be such as to permit valve operation in a reasonable time
with a manual force not exceeding 400N through stroke and 800N for seating/unseating of the valve.
It must be possible to deliver the actuator rated torque to the valve through the handwheel mechanism.
Position limit indication shall remain active in manual operation as well as motor operation, thus allowing
a signal to be provided when the set position has been reached. Intermediate position shall remain
available during manual operation provided this feature is supplied within the selected actuator.
9. Drive Interface
The actuator shall be furnished with a drive bushing easily detachable for machining to suit the valve
stem or gearbox input shaft. The drive bush shall be positioned in a detachable base of the actuator.
Thrust bearings shall be sealed for life and the base shall be capable of withstanding five times the rated
thrust of the actuator.
The actuator shall have an appropriate mounting flange according to ISO 5210 or MSS SP-102.
The actuator shall incorporate local controls for electrical operation and configuration purposes. This
shall consist of a selector switch for Open/Close and a Local/Stop/Remote mode selector switch,
lockable in any one of the following three positions: local control only, stop (no electrical operation),
remote control plus local stop only. It shall be possible to select maintained or non-maintained local
control.
The local controls shall be arranged so that the direction of valve travel can be reversed without the
necessity of stopping the actuator.
The local controls and display shall be rotatable through increments of 90 degrees to suit valve and
actuator orientation.Should the required actuators be mounted in a difficult or inaccessible location, it
shall be possible to separate the control module (including motor switchgear) from the actuator body. A
remote mounting kit shall include a wall bracket and the required electrical plug and socket connections,
suitable for distances up to 100 m cable length.
All field wiring connections and the main actuator power supply must be wired to a multi pin plug and
socket for customer connection. Terminal compartment shall provide sufficient space to accommodate
the maximum possible number of incoming wires. A minimum of three cable entries must be provided
for motor power cable and digital/analogue inputs and outputs. Each cable entry shall be properly sealed
by cable glands during site installation. Cable glands shall be chosen by contractor, responsible for
wiring during commissioning phase.
Each actuator shall provide an adequately sized internal and external connection for grounding.
Measurement of torque shall be from direct measurement of reactive force on the motor shaft. Methods
of determining torque-using data derived from the motor such as motor speed, current, flux etc are not
acceptable.
A means for automatic “torque switch bypass” to inhibit torque off during valve unseating shall be
provided.
The electrical circuit diagram of the actuator should not vary with valve type remaining identical
regardless of whether the valve is to open or close on torque or position limit.
Four potential free contacts shall be provided which can be selected to indicate any position of the valve.
Provision shall be made for the selection of a normally closed or normally open contact form. Contacts
shall maintain and update position indication during handwheel operation if the main power supply is
maintained.
The contacts shall be rated for 5mA to 5A, 120V AC, 30V DC.
As an alternative to providing valve position indication any of the four above contacts shall be selectable
to signal one of the following:
Provision shall be made in the design for an additional eight contacts having the same functionality.
A configurable monitor relay shall be provided as standard, which can be used to indicate either
Availability or Fault. The relay should be a spring return type with a Normally Open / Normally Closed
contact pre-wired to the terminal bung.
The Monitor (availability or fault) relay, being energized from the control transformer will de-energise
under any one or more the following conditions:
Provision shall be made in the design for the addition of a contactless transmitter to give a 4-20mA
analogue signal corresponding to valve travel and / or torque for remote indication when required. The
transmitter will auto range to the set limits.
The actuator display shall include a dedicated numeric/symbol digital position indicator displaying valve
position from fully open to fully close in 0.1% increments. Valve closed and open positions shall be
indicated by symbols showing valve position in relation to the pipework to ensure that valve status is
clearly interpreted. With mains power connected, the display shall be backlit to enhance contrast at all
ambient light levels and shall be legible from a distance of at least 5m (16ft).
Red, green, and yellow LEDs corresponding to open, closed and intermediate valve positions shall be
included on the actuator display when power is switched on. The yellow LED should also be fully
programmable for on/off, blinker and alarm indication. The digital display shall be maintained and
updated during handwheel operation.
The actuator display shall include a large segment element with two lines of text information, alarm and
configuration icons. The text display shall be selectable between English and other languages such as:
Spanish, German, French, and Italian. Provision shall be made to upload a different language without
removal of any covers or using specialized tools not provided as standard with the actuator.
Data logger menus should as a minimum be able to display on the local LCD the following information:
• Maximum temperature
• Minimum temperature
• Total starts
• Maximum opening torque
• Maximum closing torque
• Motor running time
• Average torque
• Open contactor starts
• Close contactor starts
• Maximum powered on time
• Number of power ups
The main display shall be capable of indicating 3 different home-screens of the following configuration:
The reversing starter, control transformer and local controls shall be integral with the valve actuator,
suitably housed to prevent breathing and condensation. The starter shall be mechanically and electrically
interlocked suitable for isolating duty. Alternative solid state contacts (thyristors) shall be available for
modulating duty. All starters shall be rated appropriately for the respective motor size. The controls
supply transformer shall be fed from two of the incoming three phases and incorporate overload
protection. It shall have the necessary tapping and be adequately rated to provide power for the following
functions:
The necessary control, wiring and terminals shall be provided integral to the actuator enclosure. Open
and close external interlocks shall be made available to inhibit local and remote valve opening / closing
control. It shall be possible to configure the interlocks to be active in remote control only.
Remote control signals fed from an internal 24V DC (or 110VAC) supply and/or from an external supply
between 20V and 60 VDC or 40V and 120VAC, to be suitable for any one or more of the following
methods of control:
It shall be possible to reverse valve travel without the necessity of stopping the actuator. The motor
starter shall be protected from excessive current surges during rapid travel reversal. The internal circuits
associated with the remote control and monitoring functions are to be designed to withstand simulated
lightning impulses of up to 2kV.
Provision shall be made for operation by distributed control system utilising the following fieldbus
systems:
• Profibus
• Modbus
• Foundation Fieldbus
• HART
Facilities shall be provided for monitoring actuator operation and availability as follows:
Integral data logger to record and store the following operational data:
• Maximum and minimum temperature
• Motor running time
• Opening contactor starts
• Closing contactor starts
• Total open/closed operations
• Maximum recorded opening and closing torque values
• Maximum power on time
• Number of power up events
The data logger shall record and store the aforementioned data on a non-volatile memory medium to
ensure power failure does not impact on data integrity.
Data logger information shall be accessed via optional non-intrusive Bluetooth® communication and
data displayed on the local LCD. Optional secure Bluetooth® tools shall be available for downloading
datalog and actuator configuration files from the actuators and subsequently uploading to a PC. The
actuator manufacturer shall supply PC software to enable actuator configuration files and data log files
to be viewed/edited and analysed.
Internal wiring shall be tropical grade PVC insulated stranded cable of appropriate size for the control
and 3-phase power. Each wire shall be clearly identified at each end. The terminals shall be fixed in a
terminal block of high tracking resistance compound.
The terminal compartment shall be separated from the inner electrical components of the actuator by
means of a plug and socket arrangement and shall accommodate all field wiring connections to the
actuator. The terminal compartment shall be provided with a minimum of 3 threaded cable entries with
provision for an additional 2 extra conduit entries.
All wiring supplied as part of the actuator to be contained within the main enclosure for physical and
environmental protection. External conduit connections between components are not acceptable
unless they are provided from the actuator manufacturer as an approved option. A detailed wiring
diagram and terminal plan shall be provided with every unit. The terminal plan shall be suitable for the
contractor to inscribe cable core identification alongside terminal numbers.
Each actuator shall be supplied with a start-up kit comprising installation instruction manual, electrical
wiring diagram and cover seals to make good any site losses during the commissioning period.
Each actuator must be performance tested and individual test certificates shall be supplied free of
charge. The test equipment should simulate a typical valve load, and the following parameters should
be recorded.
In addition, the test certificate should record details of specification such as gear ratios for both manual
and automatic and second stage gearing if provided, drive closing direction, wiring diagram number.