ProblemSet1
ProblemSet1
Problem 1.6
A ferromagnetic core with a relative permeability of 1500 is shown in Figure P1-3. The dimensions are
as shown in the diagram, and the depth of the core is 5 cm. The air gaps on the left and right sides of
the core are 0.050 and 0.070 cm, respectively. Because of fringing effects, the effective area of the air
gaps is 5 percent larger than their physical size. If there are 300 turns in the coil wrapped around the
center leg of the core and if the current in the coil is 1.0 A, what is the flux in each of the left, center,
and right legs of the core? What is the flux density in each air gap?
Solution 1.6
This core can be divided up into five regions. Let R1 be the reluctance of the left-hand
portion of the core, R 2 be the reluctance of the left-hand air gap, R 3 be the reluctance
of the right-hand portion of the core, R 4 be the reluctance of the right-hand air gap, and
R 5 be the reluctance of the center leg of the core. Then the total reluctance of the core
is
RTOT R5
R1 R2 R3 R4
R1 R 2 R3 R 4
l1 1.11 m
R1 168 kA t/Wb
r 0 A1 1500 4 10 H/m 0.07 m 0.05 m
7
l2 0.0007 m
R2 152 kA t/Wb
0 A2 4 10 H/m 0.07 m 0.05 m 1.05
7
l3 1.11 m
R3 168 kA t/Wb
r 0 A3 1500 4 10 H/m 0.07 m 0.05 m
7
l4 0.0005 m
R4 108 kA t/Wb
0 A4 4 10 H/m 0.07 m 0.05 m 1.05
7
l5 0.37 m
R5 56.1 kA t/Wb
r 0 A5 1500 4 10 H/m 0.07 m 0.05 m
7
The total flux in the core is equal to the flux in the center leg:
F 300 t 1.0 A
center TOT 0.00147 Wb
RTOT 204 kA t/Wb
The fluxes in the left and right legs can be found by the “flux divider rule”, which is
analogous to the current divider rule.
R3 R 4 168 108
left TOT 0.00147 Wb 0.00068 Wb
R1 R 2 R3 R 4 168 152 168 108
R1 R2 168 152
right TOT 0.00147 Wb 0.00079 Wb
R1 R 2 R3 R 4 168 152 168 108
The flux density in the air gaps can be determined from the equation BA :
left 0.00068 Wb
Bleft 0.185 T
Aeff 0.07 cm 0.05 cm 1.05
right 0.00079 Wb
Bright 0.215 T
Aeff 0.07 cm 0.05 cm 1.05
Problem 1.14
A two-legged magnetic core with an air gap is shown in Figure P1-11. The depth of the core is
5 cm, the length of the air gap in the core is 0.05 cm, and the number of turns on the coil is
1000. The magnetization curve of the core material is shown in Figure P1-9. Assume a 5
percent increase in effective air-gap area to account for fringing. How much current is required
to produce an air-gap flux density of 0.5 T? What are the flux densities of the four sides of the
core at that current? What is the total flux present in the air gap?
192
Solution 1.14
192
Bag 0.5 T
H ag 398 kA t/m
0 4 107 H/m
The magnetizing intensity required to produce a flux density of 0.524 T in the right-hand leg of
the core can be found from Figure P1-9 to be
H right 410 A t/m
The magnetizing intensity required to produce a flux density of 0.262 T in the top, left, and
bottom legs of the core can be found from Figure P1-9 to be
H top H left H bottom 240 A t/m
Problem 1.16
Sketch the voltage present at the terminals of the coil.
Solution 1.16
By Lenz’ Law, an increasing flux in the direction shown on the core will produce a voltage that
tends to oppose the increase. This voltage will be the same polarity as the direction shown on
the core, so it will be positive. The induced voltage in the core is given by the equation
d
eind N
dt
so the voltage in the windings will be
Time d eind
N
dt
0<t<2s 0.010 Wb 2.50 V
500 t
2s
2<t<5s 0.020 Wb -3.33 V
500 t
3s
5<t<7s 0.010 Wb 2.50 V
500 t
2s
7<t<8s 0.010 Wb 5.00 V
500 t
1s
Problem 2.6
A 1000-VA 230/115-V transformer has been tested to determine its equivalent circuit.
The results of the tests are shown below.
(a) Find the equivalent circuit of this transformer referred to the low-voltage side of
the transformer.
(b) Find the transformer’s voltage regulation at rated conditions and (1) 0.8 PF
lagging, (2) 1.0 PF, (3) 0.8 PF leading.
(c) Determine the transformer’s efficiency at rated conditions and 0.8 PF lagging.
Solution 2.6
To convert the equivalent circuit to the secondary side, divide each series
impedance by the square of the turns ratio (a = 230/115 = 2). Note that the
excitation branch elements are already on the secondary side. The resulting
equivalent circuit is shown below:
REQ,S 0.126 X EQ,S j 0.476
RC , S 3383 X M , S 1099
(b) To find the required voltage regulation, we will use the equivalent circuit of the
transformer referred to the secondary side. The rated secondary current is
1000 VA
IS 8.70 A
115 V
We will now calculate the primary voltage referred to the secondary side and use
the voltage regulation equation for each power factor.
(1) 0.8 PF Lagging:
VP VS Z EQ I S 1150 V 0.126 j 0.476 8.7 36.87 A
VP 118.41.3 V
118.4-115
VR 100% 2.96%
115
(2) 1.0 PF:
VP VS Z EQ I S 1150 V 0.126 j 0.476 8.70.0 A
V 116.22.04 V
P
116.2-115
VR 100% 1.04%
115
(3) 0.8 PF Leading:
VP VS Z EQ I S 1150 V 0.126 j 0.476 8.736.87 A
VP 113.52.0 V
113.5-115
VR 100% 1.3%
115
(c) At rated conditions and 0.8 PF lagging, the output power of this transformer is
POUT VS I S cos 115 V 8.7 A 0.8 800 W
V
2
118.4 V
2
P
Pcore 4.1 W
RC 3383
(a) Find the equivalent circuit referred to the low-voltage side of this transformer.
(b) Calculate the voltage regulation of this transformer for a full-load current at power
factor of 0.8 lagging.
(c) Calculate the copper and core losses in transformer at the conditions in (b).
(d) Assume that the primary voltage of this transformer is a constant 15 kV, and plot the
secondary voltage as a function of load current for currents from no-load to full-load.
Repeat this process for power factors of 0.8 lagging, 1.0, and 0.8 leading.
Solution 2.8
(a) The base impedance of this transformer referred to the primary (low-voltage) side
is
V 2 15 kV
2
(b) If the load on the secondary side of the transformer is 150 MVA at 0.8 PF lagging,
and the referred secondary voltage is 15 kV, then the referred secondary current
is
I S
PLOAD 150 MVA
12,500 A
VS PF 15 kV 0.8
I S 12,500 36.87 A
The voltage on the primary side of the transformer is
VP VS I S Z EQ,P
VP 15,0000 V 12,500 36.87 A 0.018 j 0.075 157552.23 V
% M-file: prob2_8.m
% M-file to calculate and plot the secondary voltage
% of a transformer as a function of load for power
% factors of 0.8 lagging, 1.0, and 0.8 leading.
% These calculations are done using an equivalent
% circuit referred to the primary side.
Problem 2.24
Figure P2-4 shows a one-line diagram of a power system consisting of a three-phase 480-V 60-
Hz generator supplying two loads through a transmission line with a pair of transformers at
either end.
Solution 2.24
This problem can best be solved using the per-unit system of measurements. The power
system can be divided into three regions by the two transformers. If the per-unit base
quantities in Region 1 (left of transformer 1) are chosen to be S base1 = 1000 kVA and VL ,base1 =
480 V, then the base quantities in Regions 2 (between the transformers) and 3 (right or
transformer 2) will be as shown below.
(a) To get the per-unit, per-phase equivalent circuit, we must convert each
impedance in the system to per-unit on the base of the region in which it is
located. The impedance of transformer T1 is already in per-unit to the proper
base, so we don’t have to do anything to it:
R1,pu 0.010
X 1,pu 0.040
( R, X , Z ) pu on base 2 ( R, X , Z ) pu on base 1
Vbase 1 Sbase 2
2
(2-60)
Vbase 2 2 Sbase 1
R2,pu 0.020
8314 V 1000 kVA
2
0.040
8314 V2 500 kVA
X 2,pu 0.085
8314 V2 1000 kVA 0.170
8314 V2 500 kVA
The per-unit impedance of the transmission line is
Z line 1.5 j10
Z line,pu 0.00723 j 0.0482
Z base2 207.4
T1 Line T2
1.513
+
10° - L1 L2
j1.134
-j3.36
(b) With the switch opened, the equivalent impedance of this circuit is
Z EQ 0.010 j 0.040 0.00723 j 0.0482 0.040 j 0.170 1.513 j1.134
Z EQ 1.5702 j1.3922 2.09941.6
(c) With the switch closed, the equivalent impedance of this circuit is
The power supplied to the two loads is the power supplied to the resistive
component of the parallel combination of the two loads: 2.358 pu.
PLoad,pu I 2 RLoad 0.409 2.358 0.394
2
Load 2 improved the power factor of the system, increasing the load voltage and the
total power supplied to the loads, while simultaneously decreasing the current in the
transmission line and the transmission line losses. This problem is a good example of
the advantages of power factor correction in power systems.
Problem 7.4
A dc machine has 8 poles and a rated current of 120 A. How much current will flow in each
path at rated conditions if the armature is (a) simplex lap-wound, (b) duplex lap-wound, (c)
simplex wave-wound?
Solution 7.4
An eight-pole, 25-kW, 120-V dc generator has a duplex lap-wound armature which has 64 coils
with 10 turns per coil. Its rated speed is 3600 r/min.
(a) How much flux per pole is required to produce the rated voltage in this generator
at no-load conditions?
(b) What is the current per path in the armature of this generator at the rated load?
(c) What is the induced torque in this machine at the rated load?
(d) How many brushes must this motor have? How wide must each one be?
(e) If the resistance of this winding is 0.011 per turn, what is the armature resistance
RA of this machine?
Solution 7.7
ZP
(a) E A K
2 a
In this machine, the number of current paths is
a mP 2 8 16
The total resistance per path is RP 40 0.011 0.44 . Since there are 16
parallel paths through the machine, the armature resistance of the generator is
0.44
RA 0.0275
16 paths
Problem 7.8
Figure P7-2 shows a small two-pole dc motor with eight rotor coils and 10 turns per
coil. The flux per pole in this machine is 0.006 Wb.
FIGURE P7-2
The machine in Problem 7-8.
(a) If this motor is connected to a 12-V dc car battery, what will the no-load speed of
the motor be?
(b) If the positive terminal of the battery is connected to the rightmost brush on the
motor, which way will it rotate?
(c) If this motor is loaded down so that it consumes 600 W from the battery, what will
the induced torque of the motor be? (Ignore any internal resistance in the motor.)
Solution
(a) At no load, VT E A K . If K is known, then the speed of the motor can be
found. The constant K is given by
ZP
K
2 a
On the average, about 6 of the 8 coils are under the pole faces at any given time,
so the average number of active conductors is
Z = (6 coils)(4 turns/coil)(2 conductors/turn) = 48 conductors
There are two poles and two current paths, so
ZP 48 cond 2 poles
K 7.64
2 a 2 2 paths
1 r 60 s
nm 262 rad/s 2500 r/min
2 rad 1 min
(b) If the positive terminal of the battery is connected to the rightmost brush, current
will flow into the page under the South pole face, producing a CW torque CW
rotation.
(c) If the motor consumes 600 W from the battery, the current flow is
P 600 W
I 50 A
VB 12 V