GX con. DN
GX con. DN
Programmable Controller
User's Manual
QJ71DN91
DeviceNet Master-Slave Module
GX Configurator-DN
Before using this product, please read this manual and the relevant manuals introduced in this manual
carefully and pay full attention to safety to handle the product correctly.
The instructions given in this manual are concerned with this product only. For the safety instructions of
the programmable controller system, please read the User's Manual of the CPU module used.
In this manual, the safety instructions are ranked as "DANGER" and "CAUTION".
Note that failure to observe a ! CAUTION level instruction may lead to a serious consequence
depending on the circumstances.
Always follow the instructions of both levels to ensure the safety.
Please keep this manual in a safe place for future reference and also pass it on to the end user.
[DESIGN PRECAUTIONS]
! DANGER
• If a communications error occurs on a DeviceNet network, faulty nodes will behave as follows:
(1) The master node (QJ71DN91) holds input data which had been received from slave nodes
before the error occurred.
(2) Whether output signals of a slave node are turned off or held is determined by the slave
node's specifications or the parameters set at the master node. When the QJ71DN91 is
used as a slave node, it holds data that have been input from the master node before the
communication error.
Utilizing communications states of slave nodes, create an interlock circuit on sequential
programs and provide safety mechanism externally so that the system will operate safely.
! CAUTION
• Do not install control wires or communication cables together with the main circuit or power
wires, or bring them close to each other.
Keep a distance of 300 mm (11.8 inch) or more between them.
Failure to do so may cause malfunctions due to noise.
A-1 A-1
[INSTALLATION PRECAUTIONS]
! CAUTION
• Use the programmable controller in an environment that meets the general specifications
contained in the User's Manual of the CPU module used.
Using it in an environment that does not meet them may result in an electric shock, fire,
malfunction, and damage to or deterioration of the product.
• While pressing the installation lever on the lower part of the module, insert the module fixing
projection into the hole in the base unit. Then, securely mount the module.
Incorrect module mounting may cause the module to malfunction, fail or fall off.
Secure the module with screws especially when it is used in an environment where constant
vibrations may occur.
• Tighten the screws within the specified torque range.
If the screws are loose, it may cause falling, short circuits, or malfunction.
If the screws are tightened too much, it may cause damage to the screw and /or the module,
resulting in falling, short circuits or malfunction.
• Before mounting/dismounting the module, be sure to shut off all phases of the external power
supply used by the system. Failure to do so may cause product damage.
• Do not directly touch the conductive area or electric components of the module.
Doing so may cause malfunction or failure in the module.
[WIRING PRECAUTIONS]
! DANGER
• Before installation or wiring, shut off all phases of the external power supply used in the system.
Failure to do so may cause an electric shock, damage to the product or malfunction.
! CAUTION
• Be careful to prevent foreign matter such as dust or wire chips from entering the module.
It may cause a fire, failure or malfunction.
• The top surface of the module is covered with a protective film to prevent foreign matter such as
wiring chips from entering the module during wiring.
Do not remove this film until wiring is complete.
Before starting the system, remove the film to release heat.
• Place the communication cables and power cables connected to the module in a duct or clamp
them.
Otherwise, dangling cables may swing or inadvertently be pulled, resulting in damage to the
module or cables or malfunctions due to poor cable contact.
• Do not pull the cable part when disconnecting the cable from the module. To disconnect a cable
with connector, hold the connector that is plugged into the module. To disconnect a cable
without connector, loosen the screws used for fastening.
Pulling the cable that is still connected to the module may damage the module and/or cable, or
cause a malfunction due to poor contact.
A-2 A-2
[STARTUP/MAINTENANCE PRECAUTIONS]
! DANGER
• Do not touch any terminal unless all phases of the external power supply have been shut off.
Doing so may cause a malfunction.
• Always turn off all phases of the external power supply before cleaning or retightening the
terminal screws.
Failure to do so may result in a malfunction.
• Do not disassemble or remodel the module.
Doing so will cause failure, malfunctions, injuries, or a fire.
• Before mounting/dismounting the module, be sure to shut off all phases of external power supply
used by the system.
Failure to do so may cause module failure or malfunctions.
• Do not mount/dismount the module onto/from a base unit more than 50 times (IEC 61131-2
compliant), after the first use of the product.
Doing so may cause malfunctions.
• Before handling the module, touch a grounded metal object to discharge the static electricity
from the human body.
Failure to do so may cause a failure or malfunctions of the module.
[DISPOSAL PRECAUTION]
! CAUTION
• When disposing of this product, treat it as industrial waste.
A-3 A-3
REVISIONS
*The manual number is given on the bottom left of the back cover.
Print Date *Manual Number Revision
Dec. 2000 SH (NA)-080143-A First Printing
Jun. 2001 SH (NA)-080143-B
Addition
Section 2.3, 2.4
Delete
Section 2.2.1, 2.2.2
Correction
SAFETY PRECAUTIONS, About the Generic Terms and Abbreviations,
Product Configuration, Section 2.2, 2.4, Section 6.2, 6.2.1, 6.2.2, 6.3.3,
6.5
Feb. 2002 SH (NA)-080143-C
Correction
About the Generic Terms and Abbreviations, Section 2.2, Section 6.2.1,
6.2.2
Dec. 2002 SH (NA)-080143-D
Addition
Section 2.5
Correction
Section 2.2, Section 3.3.2, 3.4.1, Section 6.1, 6.2.1, 6.3.2, 6.4, 6.5,
Section 9.2.1, 9.2.2
Feb. 2003 SH (NA)-080143-E
Correction
SAFETY PRECAUTIONS, INTRODUCTION, CONTENTS, Section 6.2.2,
Section 6.3.3, Section 6.4, Section 6.5
May. 2003 SH (NA)-080143-F
Correction
Section 6.3.1
Jun. 2004 SH (NA)-080143-G
Correction
Section 2.2, 2.3, Section 3.3.2, Section 4.2.1, Section 6.3.2, 6.5, 6.6,
Section 7.3.2, Section 8.1, 8.3, Section 9.3
Feb. 2006 SH (NA)-080143-H
Correction
SAFETY PRECAUTIONS, Compliance with the EMC and Low Voltage
Directives, Section 1.1, Section 2.1, 2.3, Section 3.2.1, 3.4, 3.5, Section
4.1, 4.2.1, Chapter 5, Chapter 6 (screen change), Section 6.2.2, Section
7.1, 7.2, 7.3.1, 7.4, 7.5.2, 7.7, Section 8.3, Section 9.3, Appendix 3
Mar. 2006 SH (NA)-080143-I
Addition
Section 2.5, 3.4.1
Correction
Section 3.4.1
A-4 A-4
Print Date *Manual Number Revision
Jan. 2008 SH(NA)-080143-J
Correction
Generic Terms and Abbreviations, Section 1.1, 2.1 to 2.3, 3.4, Chapter 4,
Section 5.1 to 5.4, 5.6, 6.1, 6.2, 6.4, 6.5, Chapter 7 and 8, Section 9.1,
9.2, Appendix 6
Addition
Definitions of Terminology, Section 2.4, 3.2, 6.5.1 to 6.5.17, 7.3.1, 7.4.1,
8.2.1, 8.3.1, 9.1.5, 9.2.3, Appendix 2
Deletion
Section 2.4 to 2.6, Chapter 5
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
© 2000 MITSUBISHI ELECTRIC CORPORATION
A-5 A-5
INTRODUCTION
CONTENTS
SAFETY PRECAUTIONS..............................................................................................................................A- 1
REVISIONS ....................................................................................................................................................A- 4
INTRODUCTION............................................................................................................................................A- 6
CONTENTS....................................................................................................................................................A- 6
Compliance with the EMC and Low Voltage Directives................................................................................A-10
Generic Terms and Abbreviations .................................................................................................................A-10
Definitions of Terminology .............................................................................................................................A-11
Packing List ....................................................................................................................................................A-13
1 OVERVIEW 1- 1 to 1- 3
2 SYSTEM CONFIGURATION 2- 1 to 2- 7
3 SPECIFICATIONS 3- 1 to 3-48
A-6 A-6
3.4.12 Hardware test area.......................................................................................................................... 3-44
3.4.13 Parameter saving area selection area............................................................................................ 3-46
3.4.14 Auto communication start setting area ........................................................................................... 3-46
3.5 Communication Performance .................................................................................................................. 3-47
3.5.1 Transmission delay ........................................................................................................................... 3-47
3.5.2 Communication cycle time................................................................................................................ 3-47
3.5.3 Link scan time.................................................................................................................................... 3-48
4 FUNCTIONS 4- 1 to 4-13
A-7 A-7
6.5.4 Node configuration status monitor.................................................................................................... 6-22
6.5.5 Node communication status monitor ................................................................................................ 6-22
6.5.6 Node communication error status monitor ....................................................................................... 6-23
6.5.7 Node fault status monitor .................................................................................................................. 6-23
6.5.8 Failed node detection setting............................................................................................................ 6-24
6.5.9 Message communication area monitor/test ..................................................................................... 6-25
6.5.10 I/O address area monitor for master function ................................................................................ 6-26
6.5.11 Master function receive data monitor ............................................................................................. 6-27
6.5.12 Master function transmit data monitor/test ..................................................................................... 6-27
6.5.13 Slave function receive data monitor ............................................................................................... 6-28
6.5.14 Slave function transmit data monitor/test ....................................................................................... 6-28
6.5.15 Auto configuration ........................................................................................................................... 6-29
6.5.16 Flash ROM parameter clear ........................................................................................................... 6-30
6.5.17 Parameter backup........................................................................................................................... 6-31
6.6 Flash ROM Setting................................................................................................................................... 6-32
A-8 A-8
9 TROUBLESHOOTING 9- 1 to 9-18
A-9 A-9
Compliance with the EMC and Low Voltage Directives
Unless otherwise specified, this manual uses the following generic terms and
abbreviations to explain the QJ71DN91 DeviceNet master/slave module.
Generic term for the Q00JCPU, Q00CPU, Q01CPU, Q02CPU, Q02HCPU, Q06HCPU,
QCPU (Q mode) Q12HCPU, Q25HCPU, Q12PHCPU, Q25PHCPU, Q12PRHCPU, Q25PRHCPU, Q02UCPU,
Q03UDCPU, Q04UDHCPU, and Q06UDHCPU
A - 10 A - 10
Definitions of Terminology
Terms used in this manual and their definitions are listed below.
Term Definition
Function that allows I/O (input/output) data communications between master and slave
I/O communication function
nodes.
Function that allows reading or writing of slave node’s attribute data in response to a
Message communication
request message. For further details, refer to the DeviceNet common service in the
function
DeviceNet Specifications (Release2.0).
Device that exchanges I/O data with slave nodes which are configured with the master
Master node
function parameters.
Slave node Device that exchanges I/O data with a master node.
Parameters for setting information such as connection type or I/O points, which are used to
Master function exchange I/O data with respective slave nodes when the QJ71DN91 is used as a master
parameters node.
Configured in sequence programs or GX Configurator-DN.
Function that detects slave nodes on the network and automatically creates master function
parameters.
Two options are available: "All configuration" used for detecting all slave nodes on the
Auto configuration
network and "Add configuration" used for detecting the slave nodes added to the network.
This function can reduce programming steps for master function parameter setting.
Executed in sequence programs or GX Configurator-DN.
Parameters provided for changing the number of I/O points for a slave node when the
Slave function parameters QJ71DN91 is used as a slave node.
Configured in sequence programs or GX Configurator-DN.
Auto communication start Setting by which I/O communications automatically start at power-up.
setting Configured in sequence programs or GX Configurator-DN.
Memory inside the QJ71DN91, which stores parameters saved in the following buffer
memory areas:
• Master Function Parameters (Address: 01D4H to 03CFH)
Flash ROM • Slave Function Parameters (Address: 060EH, 060FH)
• Auto Communication Start Setting (Address: 0631H)
Parameters saved on the flash ROM are automatically loaded to the buffer memory when
power is turned ON from OFF or when the CPU module is reset.
Automatic data transfer between the buffer memory and devices of a programmable
Automatic refresh controller CPU.
Configured in Auto refresh setting in GX Configurator-DN.
A - 11 A - 11
Term Definition
Used to specify a method for communicating I/O data between a master and slave nodes.
When the QJ71DN91 is used as a master node, one of the following connection types can
be selected for each slave node.
• Polling
Connection type • Bit strobe
• Change of state
• Cyclic
When the QJ71DN91 is used as a slave node, the polling method is applied to I/O
communications.
A - 12 A - 12
Packing List
A - 13 A - 13
1 OVERVIEW
MELSEC-Q
1 OVERVIEW
1 This manual provides descriptions such as the specifications and parts names of the
QJ71DN91 DeviceNet master/slave module, which is used in combination with a
MELSEC-Q series programmable controller CPU.
For the DeviceNet specifications, refer to the DeviceNet Specifications (Release 2.0)
Volumes 1 and 2.
DeviceNet is a registered trademark of Open DeviceNet Vendor Association, Inc.
POINT
The QJ71DN91 is assumed to be compatible with most of DeviceNet products on
the market. However, the compatibility with products manufactured by other
vendors is not guaranteed.
1.1 Features
*1 0700H
X Master Transmit
Function
Receive
Data area
07FFH
*1
0900H Master
Y Receive
Function
Transmit
Data area
09FFH
2) One of the following connection types can be selected for each slave
node.
• Polling
• Bit strobe
• Change of state
• Cyclic
1-1 1-1
1 OVERVIEW
MELSEC-Q
0B00H *1
Transmit Slave X
Function
Receive
0B3FH Data area
0C00H *1
Receive Slave Y
Function
Transmit
Data area
0C3FH
1-2 1-2
1 OVERVIEW
MELSEC-Q
I/O communication
Master function Slave function Master function
No communication between
DeviceNet slaves
1-3 1-3
2 SYSTEM CONFIGURATION
MELSEC-Q
2 SYSTEM CONFIGURATION
QJ71DN91
Master node
Drop line
QJ71DN91
Slave node
Slave node Terminating resistor
(121Ω, 1/4W)
Slave node
POINT
To minimize the affect of noise, keep DeviceNet cables, power cables, and signal
lines of I/O modules away from each other.
2-1 2-1
2 SYSTEM CONFIGURATION
MELSEC-Q
Remarks
Please inquire to ODVA about the following devices that are required to construct a
DeviceNet network.
• Network power supply unit
• Power supply tap
2 • Tap
• Terminating resistor
• DeviceNet cable
Contact:
Open DeviceNet Vendor Association, Inc.
http://www.odva.org/
2-2 2-2
2 SYSTEM CONFIGURATION
MELSEC-Q
This section describes the systems to which the QJ71DN91 can be applied.
2-3 2-3
2 SYSTEM CONFIGURATION
MELSEC-Q
Software version
*1
GX Developer GX Configurator-DN
Single CPU system Version 7 or later
Q00J/Q00/Q01CPU Version 1.10L or later
Multiple CPU system Version 8 or later
Q12H/Q25HCPU
Multiple CPU system Version 6 or later Version 1.10B or later
2-4 2-4
2 SYSTEM CONFIGURATION
MELSEC-Q
2.3 How to Check the Function Version, Serial No. and Software Version
This section describes how to check the function version and serial No. of the
QJ71DN91 and GX Configurator-DN software version.
(1) Checking the function version and serial No. of the QJ71DN91
(a) Checking at "the SERIAL field of the rating plate" located on the side of the
module
The serial No. and function version of the module is shown in the SERIAL
field of the rating plate.
[Operating procedure]
[Diagnostics] [System monitor] [Product Inf. List]
*1: The Production No. column display is active only when the CPU used is a Universal
model QCPU.
2-5 2-5
2 SYSTEM CONFIGURATION
MELSEC-Q
POINT
The serial No. on the rating plate may be different from the serial No. displayed on
the product information screen of GX Developer.
• The serial No. on the rating plate indicates the management information of the
product.
• The serial No. displayed on the product information screen of GX Developer
indicates the function information of the product.
The function information of the product is updated when a new function is
added.
[Operating procedure]
GX Developer "Help" Product information
Software version
2-6 2-6
2 SYSTEM CONFIGURATION
MELSEC-Q
2-7 2-7
3 SPECIFICATIONS
MELSEC-Q
3 SPECIFICATIONS
This chapter provides the performance specifications of the QJ71DN91, I/O signals
used with a programmable controller CPU, and buffer memory specifications.
For the general specifications for the QJ71DN91, refer to the User’s Manual
(Hardware) of the CPU module used.
Item Specification
Node type DeviceNet master (Group 2 only client)
Node No. 0 to 63
Master connections I/O connection 63 (polling, bit strobe, change of state, cyclic)
function
I/O Send Max. 4096 points (512 bytes), max. 256 bytes per node
Communication communication Receive Max. 4096 points (512 bytes), max. 256 bytes per node
data size Message Send Max. 240 bytes
communication Receive Max. 240 bytes
Communication specifications
Communication speed Selectable from 125 kbps, 250 kbps and 500kbps.
Maximum trunk line distance Drop line length
Communication Combination
Thick Thin
speed of thick and Maximum Total
cables cables
Maximum cable length * thin cables
125 kbaud 500 m 156 m
250 kbaud 250 m 100 m See 3.1.1 6m 78 m
500 kbaud 100 m 39 m
Current consumption required on the network 0.03 A
Number of writes to flash ROM Max. 100000 times
No. of occupied I/O points 32 points (I/O allocation: Intelligent 32 points)
5 V DC internal current consumption 0.17 A
Weight 0.11 kg
* : The maximum cable length complies with the DeviceNet Specifications (Release 2.0) Volumes 1 and 2.
3-1 3-1
3 SPECIFICATIONS
MELSEC-Q
3.1.1 Maximum trunk line distance when using thick and thin cables
The maximum transmission distance in the case of using thick and thin cables is
shown below.
Table 3.2 Maximum trunk line distance when using thick and thin cables
3-2 3-2
3 SPECIFICATIONS
MELSEC-Q
3-3 3-3
3 SPECIFICATIONS
MELSEC-Q
This section explains the input/output signals that the QJ71DN91 sends to or receives
from a programmable controller CPU.
The I/O signal assignments shown are based on the case where the start I/O No. of
the QJ71DN91 is "0000" (mounted to slot 0 of a main base unit).
Device X denotes an input signal from the QJ71DN91 to the programmable controller
CPU.
Device Y denotes an output signal from the programmable controller CPU to the
QJ71DN91.
Table 3.5 lists the I/O signals used for the programmable controller CPU.
Table 3.5 I/O signal list
QJ71DN91 Programmable controller CPU Programmable controller CPU QJ71DN91
Availability Availability
Input No. Signal name Master Slave Output No. Signal name Master Slave
function function function function
X00 Watchdog Timer Error Y00
X01 I/O Communicating Y01
X02 Message Communication Completion — Y02
X03 Error Set Signal for Master Function — Y03
X04 Slave Down Signal — Y04
X05 Message Communication Error Signal — Y05
X06 Saving Parameters to Flash ROM Y06
X07 Parameters Saved to Flash ROM Y07
X08 Error Set Signal for Slave Function — Y08 Use prohibited — —
X09 Use prohibited — — Y09
X0A H/W Test in Progress For hardware test Y0A
X0B H/W Test Completion For hardware test Y0B
X0C H/W Test Error Detection For hardware test Y0C
X0D Y0D
Use prohibited — —
X0E Y0E
X0F Module Ready Y0F
X10 Y10
X11 Y11 I/O Communication Request
Use prohibited — —
X12 Y12 Message Communication Request —
X13 Y13 Error Reset Request for Master Function —
X14 Auto-Configuring — Y14 Use prohibited — —
X15 Auto Configuration Completion — Y15 Auto Configuration Request —
X16 Y16 Use prohibited — —
Request for Saving Parameters to Flash
X17 Y17
ROM
X18 Y18 Error Reset Request for Slave Function —
X19 Y19
X1A Use prohibited — — Y1A
X1B Y1B
X1C Y1C Use prohibited — —
X1D Y1D
X1E Y1E
X1F Y1F
IMPORTANT
Do not set any "use-prohibited" signal to ON.
Doing so may cause malfunctions of the programmable controller system.
3-4 3-4
3 SPECIFICATIONS
MELSEC-Q
This section describes the ON/OFF timings and conditions of the I/O signals used for
the master function.
Module Ready(X0F)
Parameter
check
3-5 3-5
3 SPECIFICATIONS
MELSEC-Q
Parameter
check
POINT
(1) I/O Communicating (X01) is not set to ON even if I/O Communication Request
(Y11) is turned ON with the following output signals set to ON,
• Auto Configuration Request (Y15)
• Request for Saving Parameters to Flash ROM (Y17)
Turn OFF the output signals, and set I/O Communication Request (Y11) to ON
from OFF.
(2) To stop I/O communication, set I/O Communication Request (Y11) and after
200ms or more has elapsed, reset it.
3-6 3-6
3 SPECIFICATIONS
MELSEC-Q
Parameter
check
Parameter
check
3-7 3-7
3 SPECIFICATIONS
MELSEC-Q
POINT
For message communications, the master function parameters must be set.
If the master function parameters have not been set, a message connection is
opened using message group 1.
Message Communication
Request (Y12)
Message Communication
Completion (X02)
3-8 3-8
3 SPECIFICATIONS
MELSEC-Q
(4) Error Set Signal for Master Function (X03), Error Reset Request for
Master Function (Y13)
These signals are used for notification of an error occurred during master
function execution and for error code resetting.
(a) When a master function error occurs, the error information is stored in Error
Information for Master Function (address: 01B1H), and Error Set Signal for
Master Function (X03) is set to ON.
When the error is corrected, Error Set Signal for Master Function is set to
OFF. (While I/O communication is stopped, however, it is not set to OFF.)
(b) After the error is removed, setting Error Reset Request for Master Function
(Y13) to ON clears the error code in Error Information for Master Function
(address: 01B1H).
Error Reset Request
for Master Function (Y13)
POINT
(1) The I/O communication status of each slave node can be confirmed at Node
Communication Status (address: 01BCH to 01BFH).
(2) Reserved nodes are recognized as failed nodes.
To prevent a reserved node from being detected as a failed node, turn ON the
corresponding bit in Failed Node Detection Setting (address: 01CCH to 01CFH).
3-9 3-9
3 SPECIFICATIONS
MELSEC-Q
(c) If the parameter check has failed, the ERR. LED lights up and Error Set
Signal for Master Function (X03) or Error Set Signal for Slave Function
(X08) is set to ON.
For details of Error Set Signal for Master Function (X03), refer to Section
(4).
For details of Error Set Signal for Slave Function (X08), refer to Section
3.3.3 (4).
(d) Upon completion of parameter saving to the flash ROM, Parameters Saved
to Flash ROM (X07) is set to ON.
(e) When Request for Saving Parameters to Flash ROM (Y17) is set to OFF,
Saving Parameters to Flash ROM (X06) and Parameters Saved to Flash
ROM (X07) are set to OFF.
Saving Parameters
to Flash ROM (X06)
Parameters Saved
to Flash ROM (X07)
Parameters
(MOV/TO Parameter
instruction) check
3 - 10 3 - 10
3 SPECIFICATIONS
MELSEC-Q
Saving Parameters
to Flash ROM (X06) OFF
Parameters Saved
to Flash ROM (X07) OFF
POINT
(1) Even if Request for Saving Parameters to Flash ROM (Y17) is set to ON while
I/O Communicating (X01) is ON, Parameters Saved to Flash ROM (X07) is not
set to ON. Set I/O Communication Request (Y11) to ON, and after confirming
that I/O Communicating (X01) is OFF, set Request for Saving Parameters to
Flash ROM (Y17) to OFF and then ON.
(2) Even if Request for Saving Parameters to Flash ROM (Y17) is set to ON while
the following output signal is ON, Parameters Saved to Flash ROM (X07) is not
set to ON.
• I/O Communication Request (Y11)
• Auto Configuration Request (Y15)
Set the output signal to OFF, and then set Request for Saving Parameters to
Flash ROM (Y17) to OFF and then ON.
(3) Since there is a restriction on the number of writes to Flash ROM, execute
Request for Saving Parameters to Flash ROM (Y17) only when parameters are
newly created or changed.
3 - 11 3 - 11
3 SPECIFICATIONS
MELSEC-Q
Auto-Configuring (X14)
POINT
Auto Configuration Completion (X15) is not set to ON even if Auto Configuration
Request (Y15) is set to ON while the following output signals are ON.
• I/O Communication Request (Y11)
• Request for Saving Parameters to Flash ROM (Y17)
Turn the output signals to OFF, and set Auto Configuration Request (Y15) to ON
from OFF again.
(9) H/W Test in Progress (X0A), H/W Test Completion (X0B), H/W
Test Error Detection (X0C)
The hardware test status is indicated.
For the hardware test, refer to Section 5.4.
(a) Turning ON the module with the mode set to 9 starts the hardware test, and
H/W Test in Progress (X0A) is set to ON.
(b) Upon normal completion of the hardware test, H/W Test Completion (X0B)
is set to ON.
(c) If a failure occurs in the hardware test, H/W Test Error Detection (X0C) is
set to ON. At this time, H/W Test Completion (X0B) is not set to ON.
3 - 12 3 - 12
3 SPECIFICATIONS
MELSEC-Q
This section describes the ON/OFF timings and conditions of the I/O signals used for
the slave function.
Parameter
check
3 - 13 3 - 13
3 SPECIFICATIONS
MELSEC-Q
Parameter
check
POINT
(1) I/O Communicating (X01) is not set to ON even if I/O Communication Request
(Y11) is turned ON with the following output signals set to ON,
• Auto Configuration Request (Y15)
• Request for Saving Parameters to Flash ROM (Y17)
Turn OFF the output signals, and set I/O Communication Request (Y11) to ON
from OFF.
(2) To stop I/O communication, set I/O Communication Request (Y11) and after
200ms or more has elapsed, reset it.
3 - 14 3 - 14
3 SPECIFICATIONS
MELSEC-Q
Parameter
check
Parameter
check
3 - 15 3 - 15
3 SPECIFICATIONS
MELSEC-Q
(4) Error Set Signal for Slave Function (X08), Error Reset Request for
Slave Function (Y18)
These signals are used for notification of an error occurred during slave function
execution and for error code resetting.
(a) When a slave function error occurs, the error information is stored in Error
Information for Slave Function (address: 0601H), and Error Set Signal for
Slave Function (X08) is set to ON.
When the error is corrected, Error Set Signal for Slave Function (X08) is set
to OFF. (While I/O communication is stopped, however, it is not set to
OFF.)
(b) After the error is removed, setting Error Reset Request for Slave Function
(Y18) to ON clears the error code in Error Information for Slave Function
(address: 0601H).
Error Reset Request
for Slave Function (Y18)
Error Information
for Slave Function Error code
(0601H)(MOV/FROM cleared
instruction)
3 - 16 3 - 16
3 SPECIFICATIONS
MELSEC-Q
3 - 17 3 - 17
3 SPECIFICATIONS
MELSEC-Q
3 - 18 3 - 18
3 SPECIFICATIONS
MELSEC-Q
*1: Indicates whether or not data can be read or written from sequence programs.
R: Read only, R/W: Read/Write
*2: Can be saved to a flash ROM.
Parameters in the buffer memory are cleared when power is turned off or when the CPU module is
reset, unless they are saved to a flash ROM.
3 - 19 3 - 19
3 SPECIFICATIONS
MELSEC-Q
This area is used for the message communication of the master function.
For the execution timing, refer to Section 3.3.2 (3).
(d) Resetting
Table 3.10 Reset
Buffer memory address
Item Description
(Hex.)
0110H Command No. 0201H =Reset
Slave node No. (slave Low byte: Node No. of the slave node (MAC ID)
0111H
MAC ID), class ID High byte: Class ID of the object
0112H Instance ID Instance ID of the object
3 - 20 3 - 20
3 SPECIFICATIONS
MELSEC-Q
3 - 21 3 - 21
3 SPECIFICATIONS
MELSEC-Q
(d) Resetting
Table 3.15 Reset
Buffer memory
Item Description
address (Hex.)
0120H Command No. 0201H =Reset
Normal completion: 0000H
0121H Execution error code
Failed: Execution error code (Refer to Section 9.2.2.)
Slave node No. (slave Low byte: Node No. of the slave node (MAC ID)
0122H
MAC ID), class ID High byte: Class ID of the object
0123H Instance ID Instance ID of the object
3 - 22 3 - 22
3 SPECIFICATIONS
MELSEC-Q
•••
01A7H
•••
01A7H
3 - 23 3 - 23
3 SPECIFICATIONS
MELSEC-Q
*1: Refer to the manual of each slave node for actual failures and troubleshooting.
*2: Refer to the manual of each slave node for the meaning of each error code.
1) Slave status
The ON/OFF status of each bit notifies of a slave node error as shown
below.
3 - 24 3 - 24
3 SPECIFICATIONS
MELSEC-Q
This area stores the communication status, error information, etc. of the master
function.
1) When "No start" is set for Auto Communication Start Setting (address:
0631H)
Upon power-up, the status automatically changes from Offline (00H) to
Stop (40H).
When I/O Communication Request (Y11) is set to ON, the status
changes to Operate (C0H).
2) When "Start" is set for Auto Communication Start Setting (address:
0631H)
Upon power-up, the status automatically changes from Offline (00H) to
Operate (C0H).
3) When a reset message is received through the network
The status automatically returns to Offline (00H), and then changes to
Operate (C0H).
3 - 25 3 - 25
3 SPECIFICATIONS
MELSEC-Q
Always
OFF
Parameter error
Always OFF
Network has a serious
problem and communication
is not available.
If the corresponding bit is ON, any
of these errors may have occurred.
3 - 26 3 - 26
3 SPECIFICATIONS
MELSEC-Q
POINT
If errors occur at multiple nodes, the error information of the node with the smallest
node No. (MAC ID) is stored.
(5) Operation Setting Area for Bus Off Error (address: 0632H/1586)
Set whether or not to reset the QJ71DN91’s CAN chip (communication chip) to
resume the communication in the event of a bus off error,
Setting "1" in this area enables communication resumption without resetting the
CPU module.
This setting must be done before I/O communication (before setting I/O
Communication Request (Y11) to ON).
Even if "1" is set in this area after occurrence of a bus off error, the CAN chip is
not reset.
0: Stop communication without resetting the CAN chip (Default)
1: Resume communication by resetting the CAN chip
*: When any value other than 0 and 1 is set, the CAN chip is not reset.
3 - 27 3 - 27
3 SPECIFICATIONS
MELSEC-Q
3 - 28 3 - 28
3 SPECIFICATIONS
MELSEC-Q
3 - 29 3 - 29
3 SPECIFICATIONS
MELSEC-Q
POINT
When any of the bits in this area turns ON, Slave Down Signal (X04) is set to ON.
3 - 30 3 - 30
3 SPECIFICATIONS
MELSEC-Q
POINT
For a node that is set as a reserved node with a master function parameter, turn
ON the corresponding bit of Failed Node Detection Setting. If it remains OFF, it is
recognized as a failed node even if it is just a reserved node.
3 - 31 3 - 31
3 SPECIFICATIONS
MELSEC-Q
3 - 32 3 - 32
3 SPECIFICATIONS
MELSEC-Q
Buffer memory
Item Description
address (Hex.)
Set an action for watchdog timeout of the slave node.
0000H: Equivalent to the following Timeout (Default)
0001H: Timeout
The connection is placed in timeout status.
Not recovered until an operator stops the communication and then
resumes it.
01DEH Watchdog timeout action 0002H: Auto Delete
The connection is automatically deleted. At this time the
1st slave communication stops once, and then resumes automatically.
node The output is cleared once.
0003H: Auto Reset
The communication continues while the connection is maintained.
The output is not cleared.
Set a production inhibit time.
Setting varies depending on the connection type. For details, refer to Table
01DFH Production inhibit time 3.25. (Setting range: 0 to 65535 ms (FFFFH))*1
0000H: 10ms (Default)
Other than 0000H: Set value –1 (ms)
01E0H to
Settings for 2nd to 63rd slave nodes Same as those for 1st slave node
03CFH
*1: When setting a value of 32768 or more, set it in hexadecimal.
POINT
When changing master function parameters, set default values for the areas after
the changed area.
(Example) When changing the number of slave nodes that perform I/O
communication, set default values in the areas for the 5th and 6th slave
nodes.
3 - 33 3 - 33
3 SPECIFICATIONS
MELSEC-Q
Table 3.25 Details of the expected packet rate and production inhibit time
Expected packet rate Production inhibit time
(1) Set a communication watchdog timer value for the (1) Set a minimum transmit interval of the slave node,
slave node. When the communication between the which is the minimum time during which the slave
master node and the slave node stops for the node can prepare transmit data. The master node
duration represented by "set value 4," the slave transmits a polling request to the slave node when
node executes the operation specified by the this time or longer has elapsed.*1
Watchdog Timeout Action.
Polling
(2) When the specified expected packet rate value is not equal to 1 (not equal to 0 ms), the expected packet rate
must be equal to or greater than the production inhibit time.
(3) When the set value = 1, i.e., when the expected (3) When the set value = 1, i.e. when the production
packet rate = 0 ms, the watchdog timer monitoring inhibit time = 0 ms, the master node transmits a
function is disabled. polling request to the slave node at intervals of the
module scan.
(1) Set a communication watchdog timer value for the (1) Set a minimum transmit interval of the slave node,
slave node. When the communication between the which is the minimum time during which the slave
master node and the slave node stops for the can prepare transmit data. The master node
duration represented by "set value 4," the slave transmits a bit strobe request to the slave node
node executes the operation specified by the when this time or longer has elapsed.*1
Watchdog Timeout Action.
Bit strobe*2
(2) When the specified expected packet rate value is not equal to 1 (not equal to 0 ms), the expected packet rate
must be equal to or greater than the production inhibit time.
(3) When the set value = 1, i.e., when the expected (3) When the set value = 1, i.e. when the production
packet rate = 0 ms, the watchdog timer monitoring inhibit time = 0 ms, the master node transmits a bit
function is disabled. strobe request to the slave node at intervals of the
module scan.
(1) Set a communication watchdog timer value for the (1) Set a minimum time during which the slave node can
slave node. When the communication between the receive data. The master node transmits output
master node and the slave node stops for the data to the slave node at this time intervals. (The
duration represented by "set value 4," the slave master node also transmits data to the slave node
node executes the operation specified by the when output data changes.)*1
Change of state Watchdog Timeout Action.
(2) When the specified expected packet rate value is not equal to 1 (not equal to 0 ms), the expected packet rate
must be equal to or greater than the production inhibit time.
(3) When the set value = 1, i.e., when the expected (3) When the set value = 1, i.e. when the production
packet rate = 0 ms, the watchdog timer monitoring inhibit time = 0 ms, the master node transmits data
function is disabled. to the slave node only when output data changes.
(1) Specify an interval of data transmissions from the (1) Specify an interval of data transmissions from the
slave node to the master node. master node to the slave node.*1
(2) When the specified expected packet rate value is not equal to 1 (not equal to 0 ms), the expected packet rate
Cyclic
must be equal to or greater than the production inhibit time.
(3) Setting of the set value = 1, i.e., the expected packet (3) Setting of the set value = 1, i.e., the production
rate = 0 ms is inhibited. inhibit time = 0 ms is inhibited.
*1: If the setting of the production inhibit time is shorter than the scan time of the module, the master node transmits data to the slave node
at the intervals of the module’s scan.
*2: The setting of the production inhibit time must be the same in all bit strobe connections.
3 - 34 3 - 34
3 SPECIFICATIONS
MELSEC-Q
3 - 35 3 - 35
3 SPECIFICATIONS
MELSEC-Q
3 - 36 3 - 36
3 SPECIFICATIONS
MELSEC-Q
Communication data for the master function are stored in this area.
0709H Empty 1st byte module Input data of the 3rd node
3 - 37 3 - 37
3 SPECIFICATIONS
MELSEC-Q
0909H Empty 1st byte module Output data of the 3rd node
3 - 38 3 - 38
3 SPECIFICATIONS
MELSEC-Q
(3) I/O Address Area for Master Function (address: 0500H to 05FBH
/1280 to 1531)
This area stores the start addresses and sizes (number of words) of Master
Function Receive Data (address: 0700H to 07FFH/1792 to 2047) and Master
Function Transmit Data (address: 0900H to 09FFH/2304 to 2559) for each node.
This area can be used to check the start address of each node.
Input data start address of
0500H
1st slave node
Input data size of 1st slave
0501H
node (No. of words)
0502H Output data start address of
1st slave node
Output data size of 1st slave
0503H
node (No. of words)
0504H Input data start address of
2nd slave node
3 - 39 3 - 39
3 SPECIFICATIONS
MELSEC-Q
This area stores the communication status, error information, etc. of the slave function.
(a) When "No start" is set for Auto Communication Start Setting (address:
0631H)
Upon power-up, the status automatically changes from Offline (0000H) to
Stop (0040H).
When I/O Communication Request (Y11) is set to ON, the status changes
to Operate (00C0H).
Note that, until receiving an I/O communication request from the master
node, the module is placed in Ready status (0080H).
(b) When "Start" is set for Auto Communication Start Setting (address: 0631H)
Upon power-up, the status automatically changes from Offline (0000H) to
Operate (00C0H).
Note that, until receiving an I/O communication request from the master
node, the module is placed in Stop status (0040H).
3 - 40 3 - 40
3 SPECIFICATIONS
MELSEC-Q
3 - 41 3 - 41
3 SPECIFICATIONS
MELSEC-Q
Communication data for the slave function are stored in this area.
POINT
When the QJ71DN91 is used as a master node, set an even number of byte
modules. If an odd number is set and when word modules and double-word
modules are set at the same time, these word and double-word data cannot be
sent or received normally.
3 - 42 3 - 42
3 SPECIFICATIONS
MELSEC-Q
3 - 43 3 - 43
3 SPECIFICATIONS
MELSEC-Q
3 - 44 3 - 44
3 SPECIFICATIONS
MELSEC-Q
3 - 45 3 - 45
3 SPECIFICATIONS
MELSEC-Q
This area is used to save parameters in the buffer memory to a flash ROM.
For the execution timing, refer to Section 7.3 (3) and 8.2 (2).
b15 to b3 b2 b1 b0
Not used
3 - 46 3 - 46
3 SPECIFICATIONS
MELSEC-Q
The communication cycle time is an interval from the time a polling or bit strobe
request is sent to a slave node until another request is sent to the same node.
The calculation formulas for the communication cycle time of each slave node are
shown below.
(1) LS<PIT: LC = LS + PIT [ms]
(2) LS>PIT: LC = LS [ms]
LC: Communication cycle time [ms]
LS: Link scan time [ms] (Refer to Section 3.5.3.)
PIT: Production inhibit time [ms] (Refer to Section 3.4.5.)
3 - 47 3 - 47
3 SPECIFICATIONS
MELSEC-Q
The link scan time represents a time during which the QJ71DN91 waits for responses
from all nodes after sending a polling request or bit-strobe requests.
The following shows the link scan time calculation formulas.
LS = (TIn + TOn + 0.097) + 0.222 BR + 1.0 [ms]
LS: Link scan time [ms]
TIn: Transmission time for data received from the n-th slave. [ms] (Refer
to (1) below.)
TOn: Transmission time for data sent to the n-th slave. [ms] (Refer to (2)
below.)
: Indicates that the values in the parentheses "( )" must be added up
for all of the slave nodes. (Except for reserved nodes)
BR: Coefficient corresponding to the baud rate
500kbaud = 1, 250kbaud = 2, 125kbaud = 4
(b) When the length of the data received from the n-th slave is 9 bytes or more
TIn = (BT + BTa 8 + 0.190) a + {BT + BTa (b + 1) + 0.450} [ms]
BT, BTa: Coefficient corresponding to the baud rate (See *1.)
a: Result obtained by dividing the receive data length by 7
(Truncate the fractional part.)
b: Remainder obtained by dividing the receive data length by
7
(b) When the length of the data sent to the n-th slave is 9 bytes or more
TOn = (BT + BTa 8 + 0.130) c + {BT + BTa (d + 1) + 1.2} [ms]
BT, BTa: Coefficient corresponding to the baud rate (See *1.)
c: Result obtained by dividing the transmit data length by 7
(Truncate the fractional part.)
d: Remainder obtained by dividing the transmit data length by 7
3 - 48 3 - 48
4 FUNCTIONS
MELSEC-Q
4 FUNCTIONS
This function allows I/O data communication with respective slave nodes (up to 63
nodes), using the buffer memory of the QJ71DN91.
Communications of 512 bytes of inputs (up to 256 bytes per node) and 512 bytes of
outputs (up to 256 bytes per node) are available.
Master node Slave node
Programmable controller CPU QJ71DN91
I/O Communication
SET Y11 Request
4
0700H
X MasterFunction
Transmit
Receive Data
area
07FFH
0900H
Y Receive
Master Function
Transmit Data
area
09FFH
(b) Data transfer between the buffer memory and programmable controller
CPU devices
Reference
Transfer method Description
section
Auto refresh Configure the auto refresh settings in GX Configurator-DN. 7.4.1
MOV or FROM/TO instruction Configure the settings in sequence programs. 7.4.2
4-1 4-1
4 FUNCTIONS
MELSEC-Q
Auto Configuration
Request (Y15) OFF 3)
Request for Saving
Parameters to Flash
ROM (Y17) OFF 3)
4) 7)
I/O Communication
Request (Y11)
5)
I/O Communicating
(X01)
6)
Error Set Signal for
Master Function (X03)
4-2 4-2
4 FUNCTIONS
MELSEC-Q
5)
I/O Communication
Request (Y11)
I/O Communicating 3)
(X01)
4)
Error Set Signal for
Master Function (X03)
4-3 4-3
4 FUNCTIONS
MELSEC-Q
(a) Polling
Polling is a communication method by which the following steps 1) to 6) are
repeated to slave nodes.
1) The master node sends output data.
2) Step 1) triggers input data transmission from the slave node.
3) The master node sends output data.
4) Step 3) triggers input data transmission from the slave node.
5) The master node sends output data.
6) Step 5) triggers input data transmission from the slave node.
Master node
1)
4) 6)
3) 5)
2)
Slave node
4-4 4-4
4 FUNCTIONS
MELSEC-Q
Master node
4)
1) 3)
2)
Slave node
4-5 4-5
4 FUNCTIONS
MELSEC-Q
Master node
1) 2)
Slave node
4-6 4-6
4 FUNCTIONS
MELSEC-Q
(d) Cyclic
Cyclic is a communication method by which the following steps 1) and 2)
are repeated to each slave node at fixed intervals.
1) Data of the master node are sent to the slave node.
2) Data of the slave node are sent to the master node.
The cycle of cyclic transmission can be specified for each slave node.
Specify it to the following parameter items:
Cycle of transmission from master node: Production inhibit time
Cycle of transmission from slave node: Expected packet rate
The cyclic communication does not have a concept of communication
cycle.
Master node
1) 2)
Slave node
4-7 4-7
4 FUNCTIONS
MELSEC-Q
The QJ71DN91 can read or write attribute data of slave nodes using its own buffer
memory.
For details of other message communications, refer to DeviceNet Common Service
in DeviceNet Specifications (Release 2.0).
At one time, 240 bytes of message data can be transferred.
For the execution timing, refer to Section 3.3.2 (3).
(1) Get Attribute
Programmable controller CPU QJ71DN91 Slave node (MAC ID)
0110H Class
1) Message 2)
TO Comm.
Command area Instance
011FH
2) Message Comm. Attribute
SET Y12 Request
Attribute
Instance
Attribute
0120H
6) Message 3)
FROM Comm.
X02 X05 Result area
012FH Class
0130H
Message Instance
Comm.
Data area Attribute
01A7H
4) Message
communication Instance
complete
FROM Attribute
X02 X05 5)
Message Comm. Attribute
Completion Attribute
0110H Class
1) Message 3)
TO Comm.
Command area Instance
011FH
Attribute
0130H
2) Message
Attribute
TO Comm.
Data area
01A7H
3) Message Comm.
SET Y12 Request
Class
0120H Instance
Message
Comm.
Attribute
Result area
012FH
4) Message
communication Instance
Next complete Attribute
processing
X02 X05 5) Attribute
Message Comm.
Completion
Class
Instance
Attribute
Attribute
Instance
Attribute
4-9 4-9
4 FUNCTIONS
MELSEC-Q
Slave 2) Instance
information
storage area Attribute
Attribute
0120H
5) Message Attribute
FROM Comm.
X02 X05 Result area
012FH
0130H
Message
Comm. Class
Data area
01A7H Instance
3) Message Attribute
communication
complete Attribute
FROM
X02 X05 4) Attribute
Message Comm.
Completion
Instance
Attribute
4 - 10 4 - 10
4 FUNCTIONS
MELSEC-Q
This function allows I/O data communication with the master node, using the buffer
memory of the QJ71DN91.
Communications of 128 input bytes and 128 output bytes are available.
The polling method is used as the connection type.
0B00H
Transmit Slave X
Function
Receive
Data area
0B3FH
0C00H Slave
Receive Y
Function
Transmit
Data area
0C3FH
(b) Data transfer between the buffer memory and programmable controller
CPU devices
Reference
Transfer method Description
section
Auto refresh Configure the auto refresh settings in GX Configurator-DN. 8.3.1
MOV or FROM/TO instruction Configure the settings in sequence programs. 8.3.2
4 - 11 4 - 11
4 FUNCTIONS
MELSEC-Q
Auto Configuration
Request (Y15) OFF 3)
Request for Saving
Parameters to Flash
OFF 3)
ROM (Y17)
4) 7)
I/O Communication
Request (Y11)
5)
I/O Communicating
(X01)
6)
Error Set Signal for
Slave Function (X08)
4 - 12 4 - 12
4 FUNCTIONS
MELSEC-Q
5)
I/O Communication
Request (Y11)
3)
I/O Communicating
(X01)
4)
Error Set Signal for
Slave Function (X08)
4 - 13 4 - 13
5 SETUP AND PREPARATION
MELSEC-Q
This chapter describes the procedures to be followed before starting the system that
includes the QJ71DN91.
Start
Not use
Use GX Configurator-DN?
Use
5
Auto configuration (See Section 7.3.1 (1).) *1 Auto configuration (See Section 7.3.1 (1).) *1
Execute auto configuration. Not needed when setting Create sequence program for executing auto
parameters for master function manually. configuration. Not needed when setting parameters for
master function manually.
Parameters for master function (See Section 7.3.1 (2).) Parameters for master function (See Section 7.3.2 (2).)
Set parameters for master function. Create sequence program for setting master function
parameters.
Auto communication start setting (See Section 7.3.1 (1), (2).) Auto communication start setting (See Section 7.3.2 (3).)
Set auto communication start setting. Not needed when starting Create sequence program for auto communication
I/O communication by I/O Communication Request (Y11). start setting. Not needed when starting I/O
communication by I/O Communication Request (Y11).
Saving parameters to flash ROM (See Section 7.3.1 (3).) Saving parameters to flash ROM (See Section 7.3.2 (3).)
Save parameters to flash ROM. Create sequence program for saving parameters to
flash ROM.
Refresh setting (See Section 7.4.1.) Refresh setting (See Section 7.4.2.)
Configure auto refresh settings. Write intelligent Create sequence program for refresh.
function module parameters to CPU module.
Programming for control (See Section 7.4.1.) Programming for control (See Section 7.4.2.)
Create sequence program for control. After writing it to Create sequence program for control. After writing it to
programmable controller, reset CPU module. programmable controller, reset CPU module.
Failed Failed
Test run Test run
OK OK
Set Request for Saving Parameters to Flash ROM
(Y17) to ON to save parameters to flash ROM.
Operation
*1: Check that power supplies to slave nodes and network are ON and the wiring is correct.
5-1 5-1
5 SETUP AND PREPARATION
MELSEC-Q
Start
Not use
Use GX Configurator-DN?
Use
Parameters for slave function (See Section 8.2.1 (1).) Parameters for slave function (See Section 8.2.2 (1).)
Set parameters for slave function. Create sequence program for setting parameters for
Not needed unless I/O points for slave function are slave function. Not needed unless I/O points for slave
changed. function are changed.
Auto communication start setting (See Section 8.2.1 (1).) Auto communication start setting (See Section 8.2.2 (2).)
Saving parameters to flash ROM (See Section 8.2.1 (2).) Saving parameters to flash ROM (See Section 8.2.2 (2).)
Save parameters to flash ROM. Create sequence program for saving parameters to
flash ROM.
Refresh setting (See Section 8.3.1.) Refresh setting (See Section 8.3.2.)
Configure auto refresh settings. Write intelligent Create sequence program for refresh.
function module parameters to CPU module.
Programming for control (See Section 8.3.1.) Programming for control (See Section 8.3.2.)
Create sequence program for control. After writing it to Create sequence program for control. After writing it to
programmable controller, reset CPU module. programmable controller, reset CPU module.
Failed Failed
Test run Test run
OK OK
Set Request for Saving Parameters to Flash ROM
(Y17) to ON to save parameters to flash ROM.
Operation
5-2 5-2
5 SETUP AND PREPARATION
MELSEC-Q
Refer to Chapter 7 for programming for the master function, and Chapter 8 for
programming for the slave function.
Start
Not use
Use GX Configurator-DN?
Use
Create sequence program for control. After writing it to Create sequence program for control. After writing it to
programmable controller, reset CPU module. programmable controller, reset CPU module.
Failed Failed
Test run Test run
OK OK
Set Request for Saving Parameters to Flash ROM
(Y17) to ON to save parameters to flash ROM.
Operation
*1: Check that power supplies to slave nodes and network are ON and the wiring is correct.
5-3 5-3
5 SETUP AND PREPARATION
MELSEC-Q
(1) Do not drop the module casing or connector, or do not subject it to strong
impact.
(2) Do not remove the printed-circuit board of the module from its case.
Doing so may cause a failure.
(3) Be careful to prevent foreign matter such as wire chips from entering the
module.
It may cause a fire, failure or malfunction.
(4) The top surface of the module is covered with a protective film to prevent
foreign matter such as wiring chips from entering the module during wiring.
Do not remove this film until wiring is complete.
Before starting the system, remove the film to release heat.
(5) Tighten the fixing screws within the following torque ranges.
A loose screw may cause a short circuit, failure or malfunctions.
Screw Tightening torque range
*1
Module fixing screw (usually not required) (M3) 0.36 to 0.48 N•m
DeviceNet connector screw 0.353 to 0.480 N• m
DeviceNet connector wiring screw 0.608 to 0.823 N• m
*1: The module can be easily mounted to a base unit, using the hook on the upper part of
the module. However, it is recommended to secure it with the module fixing screws
when used in an environment where constant vibrations may occur.
(6) Be sure to insert the module fixing projection into the hole in the base unit.
Then, securely mount the module.
Incorrect module mounting may cause the module to malfunction, fail or fall
off.
For more details on the installation environment, refer to the User's Manual of your
programmable controller CPU.
5-4 5-4
5 SETUP AND PREPARATION
MELSEC-Q
This section describes the part names, LED indications, and respective switch settings
of the QJ71DN91.
QJ71DN91
RUN MS
NS
ERR.
NODE ADDRESS
5 6
4
2 3
7 8
X10
9
01
Node No.
5 6 switches
4
2 3
X1
7 8
MODE/DR 9
0 : M/125 01
1 : M/250
2 : M/500 M 78 9
4 56
AB E
3 : S/125 O
Mode
CD
4 : S/250 D
23
switch
5 : S/500 E
F01
6 : D/125
7 : D/250
8 : D/500
DeviceNet
connector
QJ71DN91
5-5 5-5
5 SETUP AND PREPARATION
MELSEC-Q
The following explains the names of the LEDs on the QJ71DN91 and their
indications in mode 0 to 8.
For the LED indications in mode 9 to C, refer to Section 5.4 Hardware Test or 5.6
Communication Test.
5-6 5-6
5 SETUP AND PREPARATION
MELSEC-Q
X10 Do not change the node No. during module operation since it
is recognized when the module is powered ON or reset.
0
5
If changed, the ERR. LED will flash.
2 3
X1
0
Setting range: 0 to 63 (The Err. LED will flash if any other than
these is set.)
* The node No. must be unique.
POINT
(1) If the module is used as both a master and slave node, the same node No. is
applied to the master and slave functions.
(2) Since lower numbers have priority over higher numbers, set a lower number to
a master node.
D (factory default).
E 0
1 Operates as a master node, at communication speed of 250k baud.
2 Operates as a master node, at communication speed of 500k baud.
3 Slave function Operates as a slave node, at communication speed of 125k baud.
4 Operates as a slave node, at communication speed of 250k baud.
5 Operates as a slave node, at communication speed of 500k baud.
6 Master and slave Operates as a master and slave node, at communication speed of 125k baud.
7 functions * Operates as a master and slave node, at communication speed of 250k baud.
8 Operates as a master and slave node, at communication speed of 500k baud.
9 Hardware test Performs the ROM/RAM check and self-loopback test.
A Communication Performs the transmit/receive test, at communication speed of 125k baud.
B test Performs the transmit/receive test, at communication speed of 250k baud.
C Performs the transmit/receive test, at communication speed of 500k baud.
D to F Use prohibited -
* Select a mode between 6 and 8 when using both the master and slave functions.
5-7 5-7
5 SETUP AND PREPARATION
MELSEC-Q
The hardware test checks whether or not the module operates normally in stand-
alone condition. It performs ROM check, RAM check, self-loopback test, etc.
Be sure to perform the hardware test before building a system.
For the test related to DeviceNet communications, refer to Section 5.6
Communication Test and perform it after wiring.
NS
ERR.
NS
ERR.
NS
ERR.
Failed
Test result?
Normal completion
End Check error code in Hardware Test Result
Area (address: 062FH), and take corrective
actions.
5-8 5-8
5 SETUP AND PREPARATION
MELSEC-Q
5.5 Wiring
V+ (red)
CAN_H (white)
CAN_L (blue)
V- (black)
V+
CAN_H
Shield (drain wire)
CAN_L
V-
FG V+ V- FG V+ V- FG V+ V-
Power supply Power supply Power supply
unit unit unit
5-9 5-9
5 SETUP AND PREPARATION
MELSEC-Q
The transmission and reception tests are performed after connecting the QJ71DN91
and other DeviceNet devices with DeviceNet cables.
There is no restriction on the node No. setting of the communication target.
NS
ERR.
When completed normally, MS LED stays
ON green.
RUN MS
NS
ERR.
When failed, MS LED turns OFF and ERR.
LED turns ON.
RUN MS
NS
ERR.
Failed
Test result?
Normal completion
End Check error code in Hardware Test Result
Area (address: 062FH), and take corrective
actions.
5 - 10 5 - 10
5 SETUP AND PREPARATION
MELSEC-Q
Follow the procedure below to determine the position to install the network power
supply unit.
1) Calculate the current consumption of each node on the network.
2) Measure the total length of the network.
3) Referring to Tables 5.4 and 5.5, find a maximum current value corresponding to
the network length and the cable type used.
4) If the current value calculated at step 1) is less than the one obtained at step 3),
any of the positions described on the next page can be used.
5) If the current value calculated at step 1) exceeds the one obtained at step 3),
install the network power supply unit near the center of the network referring to the
next page, and check if power can be supplied to all nodes.
6) As a result of step 5), if power cannot be supplied to all nodes, increase the
number of network power supply units.
POINT
Use a network power supply unit of which the current capacity is more than the
required total current consumption.
If the current capacity is insufficient, use of multiple power supplies is possible.
However, use power supply taps in such a case.
5 - 11 5 - 11
5 SETUP AND PREPARATION
MELSEC-Q
5.7.2 Network power supply unit position and current capacity calculation
This section describes where to install the network power supply unit and how to
calculate the current capacity.
(1) Connecting the network power supply unit to one end of the network
When the network is 200m long in total and uses thick cables, the current
capacity can be calculated as shown below.
Network power
supply unit
Terminating Terminating
resistor resistor
Master node Slave node Slave node Slave node Slave node
0.1A 0.15A 0.05A 0.25A 0.1A
200m
(2) Connecting the network power supply unit to the center of the
network
When the network uses thick cables, the current capacity can be calculated as
shown below.
In this case, the network power supply unit can supply twice the current
compared to when it is connected to the end of the network.
Network power
supply unit
Terminating Terminating
resistor resistor
Master node Slave node Slave node Slave node Slave node Slave node
0.1A 0.25A 0.2A 0.15A 0.25A 0.15A
120m 120m
Power supply distance on the left side = Power supply distance on the right side
= 120m
Total current capacity of the left side = 0.1A + 0.25A + 0.2A = 0.55A
Total current capacity of the right side = 0.15A + 0.25A + 0.15A = 0.55A
Max. current capacity available for thick cable length of 120m (See Table 5.4.) =
approx. 2.56A
(Straight-line approximation between 100m and 150m)
Therefore, this configuration allows power supply to all nodes.
5 - 12 5 - 12
5 SETUP AND PREPARATION
MELSEC-Q
Network power
supply unit
Terminating Terminating
resistor resistor
Master node Slave node Slave node Slave node Slave node Slave node
1.1A 1.25A 0.5A 0.25A 0.25A 0.85A
120m 120m
Power supply distance on the left side = Power supply distance on the right side
= 120m
Total current capacity of the left side = 1.1A + 1.25A + 0.5A = 2.85A
Total current capacity of the right side = 0.25A + 0.25A + 0.85A = 1.35A
Max. current capacity available for thick cable length of 120m (See Table 5.4.) =
approx. 2.56A
(Straight-line approximation between 100m and 150m)
Network power
supply unit
Terminating Terminating
resistor resistor
Master node Slave node Slave node Slave node Slave node Slave node
1.1A 1.25A 0.5A 0.25A 0.25A 0.85A
100m 140m
As a result of shifting the network power supply unit, it is able to supply power to
all nodes.
5 - 13 5 - 13
5 SETUP AND PREPARATION
MELSEC-Q
Network power
supply unit
Terminating Terminating
resistor resistor
Slave node
0.1A
200m
Table 5.6 Maximum current capacity for each drop line length
Drop line length (m) 0.30 0.90 1.50 2.25 3.00 4.50 6.00
Max. current (A) 3.00 3.00 3.00 2.00 1.50 1.00 0.75
5 - 14 5 - 14
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
6-1 6-1
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
For how to install or uninstall the utility package, refer to "Method of installing the
MELSOFT Series" included in the utility package.
6-2 6-2
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
6-3 6-3
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
This section explains the operating environment of the personal computer that runs GX
Configurator-DN.
Item Description
Installation (Add-in) target*1 Add-in to GX Developer Version 4 (English version) or later*2
®
Computer Windows -based personal computer
CPU Refer to the following table "Operating system and performance required for personal
Required memory computer".
Hard disk For installation 65 MB or more
space*3 For operation 10 MB or more
Display 800 600 dots or more resolution*4
® ®
Microsoft Windows 95 Operating System (English version)
® ®
Microsoft Windows 98 Operating System (English version)
® ®
Microsoft Windows Millennium Edition Operating System (English version)
® ®
Microsoft Windows NT Workstation Operating System Version 4.0 (English version)
® ®
Microsoft Windows 2000 Professional Operating System (English version)
® ®
Microsoft Windows XP Professional Operating System (English version)
Operating system ® ®
Microsoft Windows XP Home Edition Operating System (English version)
® ®
Microsoft Windows Vista Home Basic Operating System (English version)
® ®
Microsoft Windows Vista Home Premium Operating System (English version)
® ®
Microsoft Windows Vista Business Operating System (English version)
® ®
Microsoft Windows Vista Ultimate Operating System (English version)
® ®
Microsoft Windows Vista Enterprise Operating System (English version)
*1: Install GX Configurator-DN in GX Developer Version 4 or higher in the same language.
GX Developer (English version) and GX Configurator-DN (Japanese version) cannot be used in combination, and GX
Developer (Japanese version) and GX Configurator-DN (English version) cannot be used in combination.
*2: GX Configurator-DN is not applicable to GX Developer Version 3 or earlier.
®
*3: At least 15GB is required for Windows Vista .
®
*4: Resolution of 1024 768 dots or more is recommended for Windows Vista .
6-4 6-4
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
POINT
• The functions shown below are not available for Windows XP and Windows
R
®
Vista .
If any of the following functions is attempted, this product may not operate
normally.
Start of application in Windows compatible mode
R
6-5 6-5
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
Back
Space Deletes the character where the cursor is positioned.
Page
up Moves the cursor one page up.
Page
Down Moves the cursor one page down.
6-6 6-6
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
6-7 6-7
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
<Text files>
(a) A text file can be created by clicking the Make text file button on the initial
setting, Auto refresh setting, or Monitor/Test screen.
The text files can be utilized to create user documents.
GX Developer/
GX Configurator-DN Disk
Project Project
1)
A A
2)
B Personal
B
4) computer
QCPU 3) 5) QJ71DN91
QJ71DN91
Q25HCPU RUN MS
NS
MODE ERR.
RUN
ERR.
USER NODE ADDRESS
X10
5 A: Intelligent function module parameters
BOOT 0
5
B: Flash ROM data.
X1
C: Data saved by "Make text file"
A
0
B
M
O
4
D
E 0
USB
RS-232
QJ71DN91
Figure 6.1 Correlation chart for data created with the utility package
6-8 6-8
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
6-9 6-9
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
1)
[Online] - [Monitor/Test] [Tools] - [Flash ROM setting]
6 - 10 6 - 10
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Starting the Intelligent function module utility from GX Developer, activate the
screen for selecting a module to set parameters.
From this screen, the screen for configuring auto refresh of the QJ71DN91, and
the screen for selecting a module to be monitored/tested can be started.
[Operating procedure]
[Tools] [Intelligent function utility] [Start]
[Setting screen]
[Explanation of items]
(1) Activation of other screens
(a) Auto refresh setting screen
"Start I/O No.* " "Module type" "Module model name"
Auto refresh
6 - 11 6 - 11
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
POINT
(1) Saving intelligent function module parameters in a file
Since intelligent function module parameters cannot be saved in a file by the
project saving operation of GX Developer, save them on the shown module
selection screen.
(2) Reading/writing intelligent function module parameters from/to a
programmable controller using GX Developer
(a) Intelligent function module parameters can be read from and written into
a programmable controller after having been saved in a file.
(b) Set a target programmable controller CPU in GX Developer:
[Online] [Transfer setup].
(3) Checking the required utility
While the start I/O is displayed on the Intelligent function module utility setting
screen, "*" may be displayed for the model name.
This means that the required utility has not been installed or the utility cannot
be started from GX Developer.
Check the required utility, selecting [Tools] - [Intelligent function utility] - [Utility
list...] in GX Developer.
6 - 12 6 - 12
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Configure the QJ71DN91's buffer memory for automatic refresh.
This auto refresh setting eliminates the need for reading and writing by sequence
programs.
[Operating procedure]
"Start I/O No.* " "Module type" "Module model name" Auto refresh
* Enter the start I/O No. in hexadecimal.
[Setting screen]
POINT
Do not edit or write any data that were set by GX Configurator-DN Version 1.15R or
later with or to GX Configurator-DN Version 1.14Q or earlier.
Doing so will corrupt the set data.
If a numerical value is entered accidentally, press Cancel .
6 - 13 6 - 13
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Master Function Communication Status 01B0H
Error Information for Master Function 01B1H
3.4.3
Bus Error Counter 01B2H
Bus Off Counter 01B3H
Node Configuration Status 01B4H to 01B7H
Node Communication Status, Node Communication Error
01BCH to 01C3H
Status 3.4.4
Node Fault Status 01C4H to 01C7H
Failed Node Detection Disable Status 01CCH to 01CFH
Present Link Scan Time 05FCH
Minimum Link Scan Time 05FDH 3.4.7
Maximum Link Scan Time 05FEH
Slave Function Communication Status 0600H
3.4.8
Error Information for Slave Function 0601H
I/O Address Area for Master Function 0500H to 05FBH
Master Function Receive Data 0700H to 07FFH 3.4.6
Master Function Transmit Data 0900H to 09FFH
Slave Function Receive Data 0B00H to 0B3FH
3.4.10
Slave Function Transmit Data 0C00H to 0C3FH
[Explanation of items]
(1) Items
Module side Buffer size: Displays the buffer memory size of the setting item.
Module side Transfer word count: Displays the number of words to be transferred.
Transfer direction: " " indicates that data are written from the programmable
controller CPU to the buffer memory.
" " indicates that data are loaded from the buffer memory to
the programmable controller CPU.
PLC side Device: Enter a CPU module side device that is to be automatically
refreshed.
Applicable devices are X, Y, M, L, B, T, C, ST, D, W, R, and
ZR.
When using bit devices X, Y, M, L or B, set a number that can
be divided by 16 points (examples: X10, Y120, M16, etc.)
Also, buffer memory data are stored in a 16-point area,
starting from the specified device number. For example, if X10
is entered, data are stored in X10 to X1F.
6 - 14 6 - 14
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
POINT
• The auto refresh settings are stored in an intelligent function module parameter
file.
The auto refresh settings become effective by turning the power OFF and then
ON or resetting the CPU module after writing the intelligent function module
parameters to the CPU module.
• The auto refresh settings cannot be changed from sequence programs.
However, processing equivalent to auto refresh can be added using the
FROM/TO instruction in the sequence program.
6 - 15 6 - 15
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
6.5 Monitoring/Test
[Purpose]
Start buffer memory monitoring/testing and I/O signal monitoring/testing from this
screen.
[Operating procedure]
"Select monitor/test module" screen "Start I/O No. " "Module type"
"Module model name" Monitor/test
* Enter the start I/O No. in hexadecimal.
The screen can also be started from System monitor of GX Developer Version 6
or later.
Refer to the GX Developer Operating Manual for details.
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Model Name 0620H to 0624H
Node Number 0625H 3.4.11
Mode Switch Number 0626H
Bus Error Counter 01B2H
3.4.3
Bus Off Counter 01B3H
H/W Test Item Area 062EH
3.4.12
H/W Test Result Area 062FH
Master Function Communication Status 01B0H
3.4.3
Error Information for Master Function 01B1H
Present Link Scan Time (Units: ms) 05FCH
Minimum Link Scan Time (Units: ms) 05FDH 3.4.7
Maximum Link Scan Time (Units: ms) 05FEH
Slave Function Communication Status 0600H
3.4.8
Error Information for Slave Function 0601H
6 - 16 6 - 16
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
Reference
Item Buffer memory address (Hex.)
section
X/Y Monitor/Test 6.5.1
Parameter Area Monitor/Test 6.5.2
Save Parameters to Flash ROM 6.5.3
Node Configuration Status Monitor 6.5.4
Node Communication Status Monitor 6.5.5
Node Communication Error Status Monitor 6.5.6
Node Fault Status Monitor 6.5.7
Failed Node Detection Setting 6.5.8
Message Communication Area Monitor/Test – 6.5.9
I/O Address Area Monitor for Master Function 6.5.10
Master Function Receive Data Monitor 6.5.11
Master Function Transmit Data Monitor/Test 6.5.12
Slave Function Receive Data Monitor 6.5.13
Slave Function Transmit Data Monitor/Test 6.5.14
Auto Configuration 6.5.15
Flash ROM Parameter Clear 6.5.16
Parameter Backup 6.5.17
6 - 17 6 - 17
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Explanation of items]
(1) Items
Setting item: Displays I/O signals and buffer memory names.
Current value: Monitors the I/O signal states and present buffer memory values.
Setting value: Enter or select values to be written into the buffer memory for test
operation.
Read from module Reads parameters from the flash ROM of the
QJ71DN91.
Save file Saves parameters on the hard disk, etc.
Current value display Displays the current value of the item selected. (This is
used to check the text that cannot be displayed in the
current value field. However, in this utility package, all
items can be displayed in the display fields).
Make text file Creates a file containing the screen data in text file
format.
Start monitor / Selects whether or not to monitor current values.
Stop monitor
Execute test Performs a test on the selected items. To select more
than one item, select them while holding down the
Ctrl key.
Close Closes the screen that is currently open and returns to
the previous screen.
REMARK
The "Execute test" operation is explained below, using an example of writing data to
"Failed Node Detection Setting".
(1) Change the setting value for "Node 1" to "Do not detect".
Nothing is written to the QJ71DN91 at this point.
6 - 18 6 - 18
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Monitor I/O signals and tests output signals.
[Operating procedure]
Monitor/Test screen X/Y Monitor/Test
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
X00: Watchdog Timer Error 3.3.2 (1)
3.3.2 (2)
X01: I/O Communicating
3.3.3 (2)
X02: Message Communication Completion 3.3.2 (3)
X03: Error Set Signal for Master Function 3.3.2 (4)
X04: Slave Down Signal 3.3.2 (5)
X05: Message Communication Error Signal 3.3.2 (3)
X06: Saving Parameters to Flash ROM
3.3.2 (6)
X07: Parameters Saved to Flash ROM
X08: Error Set Signal for Slave Function 3.3.3 (4)
X0A: H/W Test in Progress
X0B: H/W Test Completion – 3.3.2 (9)
X0C: H/W Test Error Detection
X0F: Module Ready 3.3.2 (7)
X14: Auto-Configuring
3.3.2 (8)
X15: Auto Configuration Completion
3.3.2 (2)
Y11 : I/O Communication Request
3.3.3 (2)
Y12: Message Communication Request 3.3.2 (3)
Y13: Error Reset Request for Master Function 3.3.2 (4)
Y15: Auto Configuration Request 3.3.2 (8)
Y17: Request for Saving Parameters to Flash ROM 3.3.2 (6)
Y18: Error Reset Request for Slave Function 3.3.3 (4)
6 - 19 6 - 19
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Configure parameters for master function, parameters for slave function, and
auto communication start settings.
For auto configuration of the parameters for master function, refer to Section
6.5.15.
For saving parameters to the flash ROM, refer to Section 6.5.3.
[Operating procedure]
Monitor/Test screen Param. Area Mon.
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Parameters for Master Function 01D4H to 03CFH 3.4.5
Parameters for Slave Function 060EH, 060FH 3.4.9
Auto Communication Start Setting 0631H 3.4.14
6 - 20 6 - 20
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Save parameters to the flash ROM.
Follow the instructions shown in the Setting item column.
[Operating procedure]
Monitor/Test screen Flash ROM Save
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
1. Stop I/O Communication.
2. Select Parameter Saving Area. 3.3.2 (6)
3. Save Parameters to Flash ROM. – 7.3.1 (3)
4. Confirm Parameter Saving to Flash ROM. 8.2.1 (2)
5. Turn Off Parameter Saving Request.
6 - 21 6 - 21
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Monitor the parameter setting status of each slave node.
[Operating procedure]
Monitor/Test screen Config. Status Mon.
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Node 0 to Node 63 01B4H to 01B7H 3.4.4 (1)
[Purpose]
Monitor the I/O communication status of each slave node.
[Operating procedure]
Monitor/Test screen Comm. Status Mon.
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Node 0 to Node 63 01BCH to 01BFH 3.4.4 (2)
6 - 22 6 - 22
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Monitor the I/O communication error status of each slave node.
[Operating procedure]
Monitor/Test screen Comm. Err. Status Mon.
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Node 0 to Node 63 01C0H to 01C3H 3.4.4 (3)
[Purpose]
Monitor the communication fault status of each slave node.
[Operating procedure]
Monitor/Test screen Fault Status Mon.
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Node 0 to Node 63 01C4H to 01C7H 3.4.4 (4)
6 - 23 6 - 23
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Test whether or not to detect a failed node.
[Operating procedure]
Monitor/Test screen Failed Node Detection Setting
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Node 0 to Node 63 01CCH to 01CFH 3.4.4 (5)
6 - 24 6 - 24
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Test the message communication area.
For the execution timing, refer to Section 3.3.2 (3).
[Operating procedure]
Monitor/Test screen Msg. Comm. Area
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Message Communication Command 0110H to 011FH
Message Communication Result 0120H to 012FH 3.4.2
Message Communication Data 0130H to 01A7H
6 - 25 6 - 25
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Monitor the start address and size (words) for each slave node in Master
Function Receive Data (address: 0700H to 07FFH) and Master Function Transmit
Data (address: 0900H to 09FFH).
[Operating procedure]
Monitor/Test screen Address Area For Master
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
1st Slave, Input Data Start Address 0500H
1st Slave, Input Data Size (Words) 0501H
1st Slave, Output Data Start Address 0502H 3.4.6 (3)
1st Slave, Output Data Size (Words) 0503H
2nd to 63rd Slaves 0504H to 05FBH
6 - 26 6 - 26
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Monitor the data received from each slave node.
[Operating procedure]
Monitor/Test screen Master Receive Data
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Master Function Receive Data 0700H to 07FFH 3.4.6 (1)
[Purpose]
Test the data to be sent to each slave node.
[Operating procedure]
Monitor/Test screen Master Transmit Data
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Master Function Transmit Data 0900H to 09FFH 3.4.6 (2)
6 - 27 6 - 27
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Monitor the data received from the master node.
[Operating procedure]
Monitor/Test screen Slave Receive Data
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Slave Function Receive Data 0B00H to 0B3FH 3.4.10 (1)
[Purpose]
Test the data to be sent to the master node.
[Operating procedure]
Monitor/Test screen Slave Transmit Data
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Slave Function Transmit Data 0C00H to 0C3FH 3.4.10 (2)
6 - 28 6 - 28
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Using the auto configuration, set the parameters for master function.
Follow the instructions shown in the Setting item column.
[Operating procedure]
Scroll down on the Monitor/Test screen.
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
1. Stop I/O Communication.
2. Set Auto Configuration Operation.
3.3.2 (8)
3. Execute Auto Configuration. –
7.3.1 (1)
4. Confirm Auto-Configured Parameters.
5. Save Parameters to Flash ROM.
6 - 29 6 - 29
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Clear the parameters from the flash ROM.
Follow the instructions shown in the Setting item column.
[Operating procedure]
Scroll down on the Monitor/Test screen.
[Setting screen]
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
7.3.1 (4)
Flash ROM Parameter Clear –
8.2.1 (3)
6 - 30 6 - 30
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Read the parameters saved in the QJ71DN91’s flash ROM, and save them in the
personal computer.
Or, read the parameters saved in the personal computer, and save them in the
QJ71DN91’s flash ROM.
Follow the instructions shown in the Setting item column.
[Operating procedure]
Scroll down on the Monitor/Test screen.
[Setting screen]
Param. Backup
[Setting items]
Reference
Item Buffer memory address (Hex.)
section
Parameter Saving Area Selection 0630H 3.4.13
Parameters for Master Function 01D4H to 03CFH 3.4.5
Parameters for Slave Function 060EH, 060FH 3.4.9
Auto Communication Start Setting 0631H 3.4.14
6 - 31 6 - 31
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Purpose]
Edit the flash ROM settings offline.
Edited parameters can be written to the module from the "Parameter Backup"
screen under "Monitor/Test".
[Operating procedure]
Flash ROM setting screen "Module type" "Module model name" Select
[Setting screen]
Param. Backup
6 - 32 6 - 32
6 UTILITY PACKAGE (GX Configurator-DN)
MELSEC-Q
[Explanation of items]
(1) Items
Setting item: Displays parameter names.
Setting value: Enter or select values to be set in the flash ROM.
6 - 33 6 - 33
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
•
•
•
•
•
•
(2) Reading receive data and writing transmit data must be performed when there is
no error in the module and the module is in the ready status.
Module error Module ready
7
X0 X0F
Program for communication
3) Create a program that detects the communication status of each node and
performs interlock. Also, create an error handling program.
Module error Module ready Node communication status
X0 X0F
FROM H0 H1BC K4MO K4
M0
Node No. 0 error handling program
M1
Node No. 1 error handling program
M0
Node No. 0 normal processing program
M1
Node No. 1 normal processing program
7-1 7-1
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
(4) When handling transmit/receive data of multiple words, pay attention to the
following:
Consistency of 1-word or 2-word (for double-word modules) is guaranteed for
transmit/receive data.
When data of three words or more are handled, new and old data may be mixed
in units of one word.
Therefore, confirm correct data transfer using a method such as providing a
handshake area at each end of transmit/receive data areas, as shown in the
following example.
Programmable controller CPU QJ71DN91 master QJ71DN91 slave Programmable controller CPU
7
3) \
Sets Transmit request flag.
Transmit
request
flag: 903H
\ 7) \
Resets Transmit request flag.
Transmit complete Transmit
flag: 703H request
flag: 903H
4) 5)
\ \ \
Reads receive data from Slave
Receive complete Receive completion Slave function Receive data function receive data area.
flag: B03H notification receive data
flag: C03H :B00H
6) \
Sets Receive completion
Receive notification flag.
completion
notification
flag
:C03H
\ \
Resets Receive completion
Receive complete Receive
notification flag.
flag: B03H completion
notification
flag
:C03H
7-2 7-2
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
7-3 7-3
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
The explanation of the programs in this chapter is based on the following system.
24V power supply 1st slave node 2nd slave node 4th slave node
(Node No.1, polling) (Node No.2, polling) (Node No.3, bit strobe)
Omron CompoBus/D Omron CompoBus/D Rockwell Automation
8-point input 8-point output Flex I/O DeviceNet adapter
(DRT1-ID08) (DRT1-OD08) + 16-point input
(1794ADN+IB16)*3
*1: The QJ71DN91 (master node) is installed to slot 0 of the base unit, with the start I/O No. set to
"0000H".
*2: The QJ71DN91 (slave node) is installed to slot 1 of the base unit, with the start I/O No. set to
"0020H".
*3: Rockwell Automation’s Flex I/O DeviceNet adapter has input data of two bytes for its status. It
also has 2-byte input data and 2-byte output data.
(2) Settings
(a) Settings of the master node (QJ71DN91 (master node))
For communication with the 1st to 4th slave nodes, set the information such
as connection type and I/O points as the parameters for master function.
(Refer to Section 7.3.)
Item Setting
Node No. (Node No. switches) 0 (00)
Communication speed (Mode switch) 125kbaud (Mode 0)
Receive data X100 to X16F
Transmit data Y100 to Y14F
7-4 7-4
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
7-5 7-5
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
(3) Communications
The following shows the relation among the programmable controller CPU,
master node’s buffer memory, and a slave node.
Programmable controller CPU QJ71DN91 master node Remote I/O (node No. 1)
8-point input
Receive data
FROM
X100 to X107 Node No. 1 I00 to I07
700H
Input 00 to input 07
701H
QJ71DN91 slave node (node No. 4)
FROM 702H Node No. 4
X110 to X14F 8-byte transfer
703H
704H C00H
Node No. 3 status
705H C01H Transmit data
FROM
X160 to X16F 706H
Node No. 3
C02H
C03H
Transmit data
TO B00H
Y100 to Y107 900H Node No. 2
B01H Receive data
901H
B02H
TO 902H Node No. 4
Y110 to Y14F B03H
903H
Remote I/O (node No. 3)
904H 16-point input
Node No. 3
905H
Status
I00 to I15
Input 00 to input 15
Dummy output
O00 to O07
Output 00 to output 07
7-6 7-6
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
7-7 7-7
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
1)
MOV/TO
Auto Configuration Operation Setting (03F0H) instruction
6) 8)
MOV/TO
Parameters for Master Function (01D4H to 03CFH) instruction
1) Set a type of auto configuration and the maximum detection node No.
in Auto Configuration Operation Setting (address: 03F0H).
(Example) When the auto configuration type is "All configuration" and
the maximum detection node No. is 4, set 0004H.
2) Set I/O Communication Request (Y11) and Request for Saving
Parameters to Flash ROM (Y17) to OFF.
3) Set Auto Configuration Request (Y15) to ON.
4) Auto configuration is started, and Auto-Configuring (X14) is set to ON.
Up to approx. 60 seconds are needed for completion of auto
configuration.
5) Upon completion of auto configuration, Auto Configuration Completion
(X15) is set to ON.
6) Parameters saved in each slave node are loaded and stored in
Parameters for Master Function (address: 01D4H to 03CFH).
The parameter settings loaded from the slave nodes are stored in
order of node No.
7) When Auto Configuration Request (Y15) is set to OFF, Auto-
Configuring (X14) and Auto Configuration Completion (X15) are set to
OFF.
8) Check Parameters for Master Function (address: 01D4H to 03CFH).
Confirm that the settings such as node No., connection type, I/O points
are correct. Correct values if any incorrect setting is identified.
7-8 7-8
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
4) 8)
Request for Saving Parameters to Flash ROM (Y17)
5)
Saving Parameters to Flash ROM (X06)
7)
Parameters Saved to Flash ROM (X07)
6)
Error Set Signal for Master Function (X03)
MOV/FROM
Error Information for Master Function (01B1H) instruction
2)
Parameter Area Select Bit (0630H) MOV/TO
instruction
1)
MOV/TO Parameter
Parameters instruction check
Flash ROM
POINT
(1) Pre-determine the slave node settings (e.g. connection type) before executing
auto configuration.
(2) Check that the power of the slave nodes and the network is ON and the wiring
is correct.
(a) The setting items for auto configuration are shown below.
2)
1)
7 - 10 7 - 10
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
1)
2)
3)
4)
1) When the current value for "Y11: I/O Communication Request" is "I/O
Comm. Request", set "I/O Comm. Stop Request".
Select "I/O Comm. Stop Request" Execute test button
2) When the current value for "X01: I/O Communicating" is "I/O
Communicating", set "I/O Comm. Request" for "Y11: I/O
Communication Request".
Select "I/O Comm. Request" Execute test button
Then, set "I/O Comm. Stop Request" for "Y11: I/O Communication
Request".
Select "I/O Comm. Stop Request" Execute test button
Check that the current value for "X01: I/O Communicating" was
changed to "I/O Comm. Stop".
7 - 11 7 - 11
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
3) When the current value for "Y17: Request for Saving Parameters to
Flash ROM" is "Save Request", set "OFF" for it.
Select "OFF" Execute test button
4) Click the Close button.
1)
2)
7 - 12 7 - 12
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
1)
2)
3)
4)
5)
7 - 13 7 - 13
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
1)
2)
3)
4)
7 - 14 7 - 14
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
POINT
(1) Slave node settings detected by auto configuration are stored in order of node
No.
(2) When changing parameters for master function, set default values in the areas
after the parameter-set areas.
(Example) When changing the number of slave nodes that can perform I/O
communication from 6 to 4, set default values in the areas for 5th
and 6th slave nodes.
7 - 15 7 - 15
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
1)
2)
3)
1) Set parameters for 1st to 4th slave nodes. (For the setting details, refer
to Section 7.3 (1).)
Select a value in a Setting value field Execute test button
Repeat this if more than one parameter must be set.
2) To start I/O communication automatically at power-up, set "Start" for
"Auto Communication Start Setting".
Select "Start" Execute test button
3) Click the Close button.
7 - 16 7 - 16
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
POINT
When changing parameters for master function, set default values in the areas after
the parameter-set areas.
(Example) When changing the number of slave nodes that can perform I/O
communication from 6 to 4, set default values in the areas for 5th and
6th slave nodes.
7 - 17 7 - 17
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
1)
2)
3)
1) When the current value for "Y11: I/O Communication Request" is "I/O
Comm. Request", set "I/O Comm. Stop Request".
Select "I/O Comm. Stop Request" Execute test button
2) When the current value for "X01: I/O Communicating" is "I/O
Communicating", set "I/O Comm. Request" for "Y11: I/O
Communication Request".
Select "I/O Comm. Request" Execute test button
Then, set "I/O Comm. Stop Request" for "Y11: I/O Communication
Request".
Select "I/O Comm. Stop Request" Execute test button
Check that the current value for "X01: I/O Communicating" was
changed to "I/O Comm. Stop".
3) When the current value for "Y15: Auto Configuration Request" is
"Config. Request", set "OFF" for "Y15: Auto Configuration Request".
Select "OFF" Execute test button
7 - 18 7 - 18
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
4)
5)
6)
7)
8)
9)
10)
7 - 19 7 - 19
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
POINT
Since the number of writes to flash ROM is limited, use Request for Saving
Parameters to Flash ROM (Y17) only when creating or changing parameters.
7 - 20 7 - 20
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
1)
2)
3)
4)
5)
6)
5) After completion of clearing the flash ROM parameters, set "OFF" for
"Request for Saving Parameters to Flash ROM".
Select "OFF" Execute test button
6) Click the Close button.
7 - 22 7 - 22
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
*1: Check that the settings such as node No., connection type, and I/O points are correct.
Correct values if any incorrect setting is identified. (For the setting details, refer to Section 7.3 (1).)
POINT
(1) Pre-determine the slave node settings (e.g. connection type) before executing
auto configuration.
(2) Check that the power of the slave nodes and the network is ON and the wiring
is correct.
(3) Slave node settings detected by auto configuration are stored in order of node
No.
(4) When changing parameters for master function, set default values in the areas
after the parameter-set areas.
(Example) When changing the number of slave nodes that can perform I/O
communication from 6 to 4, set default values in the areas for 5th
and 6th slave nodes.
7 - 23 7 - 23
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
7 - 24 7 - 24
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
POINT
When changing parameters for master function, set default values in the areas after
the parameter-set areas.
(Example) When changing the number of slave nodes that can perform I/O
communication from 6 to 4, set default values in the areas for 5th and
6th slave nodes.
7 - 25 7 - 25
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
POINT
(1) Save the parameters in the buffer memory to a flash ROM. Otherwise, they are
cleared when the power is turned OFF or the CPU module is reset.
(2) Since the number of writes to flash ROM is limited, use Request for Saving
Parameters to Flash ROM (Y17) only when creating or changing parameters.
7 - 26 7 - 26
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
1)
2)
3)
7 - 27 7 - 27
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
POINT
To ensure consistency of transmit/receive data of multiple words, take a measure
such as providing a handshake area at the end of transmit/receive data to check
the data transfer.
For the program example, refer to Section 7.1 (4).
7 - 28 7 - 28
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
7 - 29 7 - 29
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
POINT
To ensure consistency of transmit/receive data of multiple words, take a measure
such as providing a handshake area at the end of transmit/receive data to check
the data transfer.
For the program example, refer to Section 7.1 (4).
7 - 30 7 - 30
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
7 - 31 7 - 31
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
Get Attribute
Instance ID = 1
Attribute ID = 7
7 - 32 7 - 32
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
Set Attribute
Instance ID = 1
7 - 33 7 - 33
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
This section explains an example of a sequence program that obtains the error
information for the master function.
Error code
7 - 34 7 - 34
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
If transmit/receive data of each slave node may change depending on the system,
reserve the data storage devices for each slave node in advance.
Using the information in I/O Address Area for Master Function (address: 0500H to
05FBH) and executing the FROM or TO instruction will eliminate the need for modifying
the sequence program even if the transmit/receive data length is changed.
The figure below shows an example in which the transmit/receive data storage devices
of each node are allocated in units of 64 points, in the same system configuration
described in Section 7.2.
In this example, the devices are allocated as follows: 64 points from X200 for storing
receive data of node No.1, 64 points from X240 for storing receive data of node No.2,
and so on.
The information in I/O Address Area for Master Function (address: 0500H to 05FBH) is
stored in D1000 to D1251, and the FROM or TO instruction is executed using the start
buffer memory address of this information and the data length.
Programmable controller CPU QJ71DN91 master node Remote I/O (node No. 1)
8-point input
Receive data
Receive FROM I00 to I07
X200 to X207 700H Node No. 1
data area for 701H Input 00 to input 07
X208 to X23F FROM
node No.1 (For future 702H
(64 points)
Node No. 4 QJ71DN91 slave node
expansion) 703H
(node No. 4)
Receive 704H
705H 8-byte transfer
data area for X240 to X27F Node No. 3 status
Transmit data
Transmit TO 900H Node No. 2 Remote I/O (node No. 3)
data area for Y200 to X23F 901H 16-point input
node No.1 (For future TO 902H Node No. 4
expansion)
(64 points) 903H Status
Transmit Y240 to X247 904H I00 to I15
data area for 905H Node No. 3 Input 00 to input 15
Y248 to X27F
node No.2 (For future
(64 points) expansion) Dummy output
Transmit
data area for Y280 to X2BF
node No.4
Remote I/O (node No. 2)
(64 points) TO
Y2C0 to X2CF 8-point input
Transmit
data area for Y2D0 to X2FF
(For future O00 to O07
node No.3 expansion) Output 00 to output 07
(64 points)
500H
D1000 to D1251
I/O address I/O address
information FROM area for
to
Based on this master
information,
execute FROM/TO
function
instructions.
5FBH
7 - 35 7 - 35
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
MELSEC-Q
7 - 36 7 - 36
8 PROGRAMMING FOR EXECUTING THE SLAVE FUNCTION
MELSEC-Q
The explanation of the programs in this chapter is based on the system shown in
Section 7.2.
Note that the transmit/receive data of the QJ71DN91 (slave node) are assigned to the
following devices.
Item Device
Receive data X200 to X23F
Transmit data Y200 to Y23F
POINT
To change I/O points for slave function, parameters for slave function must be set.
However, for the I/O points of the QJ71DN91 (slave node) shown in Chapter 7,
parameters for slave function need not be set because default values are used.
(1) Settings
The following table shows the slave function parameters that are to be set in the
program example.
For details of the slave function parameters, refer to Section 3.4.9.
For saving parameters to a flash ROM, refer to (2) in this section.
Buffer memory
Item Set value
address (Hex.)
8 060EH Slave Function Receive-Bytes (Input Size) Setting Area K16 (16 bytes)
060FH Slave Function Transmit-Bytes (Output Size) Setting Area K16 (16 bytes)
8-1 8-1
8 PROGRAMMING FOR EXECUTING THE SLAVE FUNCTION
MELSEC-Q
Flash ROM
1)
2)
3)
1) Enter "16" for "Slave Function Input Sizes Setting Area" and "Slave
Function Output Sizes Setting Area".
Select "16" Execute test button
2) To start I/O communication automatically at power-up, set "Start" for
"Auto Communication Start Setting".
Select "Start" Execute test button
3) Click the Close button.
(b) Saving the parameters to the flash ROM (Refer to (2) in this section.)
8-3 8-3
8 PROGRAMMING FOR EXECUTING THE SLAVE FUNCTION
MELSEC-Q
1)
2)
3)
1) When the current value for "Y11: I/O Communication Request" is "I/O
Comm. Request", set "I/O Comm. Stop Request".
Select "I/O Comm. Stop Request" Execute test button
2) When the current value for "X01: I/O Communicating" is "I/O
Communicating", set "I/O Comm. Request" for "Y11: I/O
Communication Request".
Select "I/O Comm. Request" Execute test button
Then, set "I/O Comm. Stop Request" for "Y11: I/O Communication
Request".
Select "I/O Comm. Stop Request" Execute test button
Check that the current value for "X01: I/O Communicating" was
changed to "I/O Comm. Stop".
3) When the current value for "Y15: Auto Configuration Request" is
"Config. Request", set "OFF" for "Y15: Auto Configuration Request".
Select "OFF" Execute test button
8-4 8-4
8 PROGRAMMING FOR EXECUTING THE SLAVE FUNCTION
MELSEC-Q
4)
5)
6)
7)
8)
9)
10)
8-5 8-5
8 PROGRAMMING FOR EXECUTING THE SLAVE FUNCTION
MELSEC-Q
POINT
Since the number of writes to flash ROM is limited, use Request for Saving
Parameters to Flash ROM (Y17) only when creating or changing parameters.
8-6 8-6
8 PROGRAMMING FOR EXECUTING THE SLAVE FUNCTION
MELSEC-Q
8-7 8-7
8 PROGRAMMING FOR EXECUTING THE SLAVE FUNCTION
MELSEC-Q
Parameter saving
Parameter Area Select Bit
Slave/Auto Comm.
Auto Communication Start Setting
Start
Writes parameters to buffer memory.
Sets Request for Saving Parameters
to Flash ROM to ON.
Saving parameters to flash ROM
POINT
(1) Save the parameters in the buffer memory to a flash ROM. Otherwise, they are
cleared when the power is turned OFF or the CPU module is reset.
(2) Since the number of writes to flash ROM is limited, use Request for Saving
Parameters to Flash ROM (Y17) only when creating or changing parameters.
8-8 8-8
8 PROGRAMMING FOR EXECUTING THE SLAVE FUNCTION
MELSEC-Q
1)
2)
8-9 8-9
8 PROGRAMMING FOR EXECUTING THE SLAVE FUNCTION
MELSEC-Q
POINT
To ensure consistency of transmit/receive data of multiple words, take a measure
such as providing a handshake area at the end of transmit/receive data to check
the data transfer.
For the program example, refer to Section 7.1 (4).
8 - 10 8 - 10
8 PROGRAMMING FOR EXECUTING THE SLAVE FUNCTION
MELSEC-Q
POINT
To ensure consistency of transmit/receive data of multiple words, take a measure
such as providing a handshake area at the end of transmit/receive data to check
the data transfer.
For the program example, refer to Section 7.1 (4).
8 - 11 8 - 11
8 PROGRAMMING FOR EXECUTING THE SLAVE FUNCTION
MELSEC-Q
This section explains an example of a sequence program that obtains the error
information for the slave function.
8 - 12 8 - 12
9 TROUBLESHOOTING
MELSEC-Q
9 TROUBLESHOOTING
This chapter describes the errors that may occur while using the QJ71DN91 as well as
their troubleshooting procedures.
This chapter contains the following information:
Section 9.1 Problem Identification
Troubleshooting procedures are shown according to symptoms.
Section 9.2 Error Codes
Troubleshooting procedures are shown according to error codes.
9-1 9-1
9 TROUBLESHOOTING
MELSEC-Q
This section explains checking procedures and actions to be taken when a problem
occurs.
Problem occurred
Yes
Yes
9-2 9-2
9 TROUBLESHOOTING
MELSEC-Q
9.1.2 When unable to communicate with all slave nodes (when using master function)
Yes
Yes
Yes
Same communication
speed set for all nodes? No Set same communication speed for all nodes.
Yes
Yes
Is there
a slave node having same node No. as Yes Eliminate node No. duplication.
QJ71DN91?
No
Yes
Yes
I/O Communication
No Set I/O Communication Request (Y11) to ON.
Request (Y11) set to ON?
Yes
No
9-3 9-3
9 TROUBLESHOOTING
MELSEC-Q
9.1.3 When unable to communicate with a specific slave node (when using master function)
Yes
Is DeviceNet
cable connected to the slave no No Connect DeviceNet cable securely.
securely?
Yes
Is comm. speed same as other nodes? No Set the same communication speed.
Yes
Yes
Is the
slave node set with parameters? No
Yes
Is the
parameter for node No. same as the No
actual one?
Yes
No
Specified
connection type matched with the slave No
node spec?
Yes
UCMM support
and message group matched with the No
slave node spec?
Yes
Value set
for watchdog timeout action matched with No
the slave node spec?
Yes
I/O configuration
parameters matched with the actual No
configuration?
Yes
No
No
Have the parameters been written? No Configure and write correct parameters.
Yes
Yes Take corrective actions according
Is there an error code?
to the error code.
No
Check the entire network condition
such as noise or installation.
9-4 9-4
9 TROUBLESHOOTING
MELSEC-Q
9.1.4 When unable to communicate with master node (when using slave function)
Yes
Is DeviceNet
Connect DeviceNet cable securely.
cable connected to QJ71DN91's No
connector securely
Yes
Yes
Same communication speed No Set same communication speed for all nodes.
set for all nodes?
Yes
Yes
Is there
a slave node having same node No. as Yes Eliminate node No. duplication.
QJ71DN91?
No
Yes
Yes
I/O Communication Request (Y11) No Set I/O Communication Request (Y11) to ON.
set to ON?
Yes
No
9-5 9-5
9 TROUBLESHOOTING
MELSEC-Q
9-6 9-6
9 TROUBLESHOOTING
MELSEC-Q
9-7 9-7
9 TROUBLESHOOTING
MELSEC-Q
A communication error code is stored in the high byte of Error Information for Master
Function (address: 01B1H) or Error Information for Slave Function (address: 0601H).
Read it when Error Set Signal for Master Function (X03) or Error Set Signal for Slave
Function (X08) is set to ON, and check the error details.
Communication error codes can be checked in System monitor of GX Developer.
(Refer to Section 9.3.)
(1) When the error-detected node No. (low byte of error information) is FFH
Error Detectability
Detected
code Description Action Master Slave
in:
(Hex.) function function
• Set the node No. within the range of 0 to
The node No. (MAC ID) value is out of
63.
36H QJ71DN91 range.
• Set the mode switch to any other than D
The mode switch value is out of range.
to F.
The node No. (MAC ID) is duplicated on
39H QJ71DN91 • Set a unique node No.
the network.
E0H QJ71DN91 Power is not supplied to the network. • Supply power to the network (DC24V).
Other modules cannot be identified on
E1H QJ71DN91 • Connect other modules to the network.
the network.
The node No. switches or mode switch • Restore the setting of the node No.
F0H QJ71DN91
has been changed during operation. switches or mode switch.
9-8 9-8
9 TROUBLESHOOTING
MELSEC-Q
(2) When the error-detected node No. (low byte of error information) is FEH
Error Detectability
Detected
code Description Action Master Slave
in:
(Hex.) function function
Zero (0) is set for both the input and • Set the input and output points according
02H QJ71DN91
output points of a slave node. to the slave node specifications.
The low byte of the slave node No. in the
03H QJ71DN91 • Set it within the range of 0 to 63.
buffer memory is out of range.
The high byte of the slave node No. in • Set it within the range of 01H to 04H, or to
04H QJ71DN91
the buffer memory is out of range. 80H.
The connection type in the buffer
05H QJ71DN91 • Set 0001H, 0002H, 0004H, or 0008H.
memory is out of range.
The same node No. has already been
06H QJ71DN91 set for a slave node in the buffer • Set unique node numbers for all nodes.
memory.
07H QJ71DN91 No slave node has been set. • Set at least one slave node.
The total input data length of all slave
08H QJ71DN91 • Reduce it to 512 bytes or less.
nodes is too long.
The total output data length of all slave
09H QJ71DN91 • Reduce it to 512 bytes or less.
nodes is too long.
The parameter value for the watchdog
0AH QJ71DN91 • Set 0000H, 0001H, 0002H, or 0003H.
timeout action is invalid.
The expected packet rate value in the • Change the setting so that the expected
0BH QJ71DN91 buffer memory is smaller than the packet rate value is greater than or equal
production inhibit time value. to the production inhibit time value.
• Save the parameters again.
Flash ROM checksum error (Parameters
0CH QJ71DN91 • Do not turn OFF the power or reset while
for Master Function area)
saving the parameters.
• Save the parameters again.
Flash ROM checksum error (Parameters
0DH QJ71DN91 • Do not turn OFF the power or reset while
for Slave Function area)
saving the parameters.
• Save the parameters again.
Flash ROM checksum error (Auto
0EH QJ71DN91 • Do not turn OFF the power or reset while
Communication Start Setting area)
saving the parameters.
• Clear all parameters again.
0FH QJ71DN91 Flash ROM all clear error • Do not turn OFF the power or reset while
clearing the parameters.
The number of input points per slave • Correct the number of input points per
10H QJ71DN91
node exceeds 256 bytes. slave node to 256 bytes or less.
The number of output points per slave • Correct the number of output points per
11H QJ71DN91
node exceeds 256 bytes. slave node to 256 bytes or less.
The production inhibit time value was set • Set the production inhibit time value to a
15H QJ71DN91
to 0 ms (set value 1) in cyclic. value other than 0 ms.
All slave nodes are set as reserved • Set the parameters according to the slave
16H QJ71DN91
nodes by parameters. nodes connected to the network.
The number of slave function receive
80H QJ71DN91 • Set it within the range of 0 to 128 bytes.
bytes is out of range.
The number of slave function transmit
81H QJ71DN91 • Set it within the range of 0 to 128 bytes.
bytes is out of range.
Both of the slave function transmit and • Set either of the transmit or receive bytes
82H QJ71DN91
receive bytes are set to 0. to any other than 0.
9-9 9-9
9 TROUBLESHOOTING
MELSEC-Q
Error Detectability
Detected
code Description Action Master Slave
in:
(Hex.) function function
• Set I/O points of slave nodes in
Parameters for Master Function.
When using both the master and slave
• Set transmit/receive bytes in Parameters
A0H QJ71DN91 functions, the number of I/O points is set
for Slave Function.
to 0 for both of them.
(Either of master or slave function values
must be set.)
9 - 10 9 - 10
9 TROUBLESHOOTING
MELSEC-Q
(3) When the error-detected node No. (low byte of error information) is other than
FFH and FEH
Error Detectability
Detected
code Description Action Master Slave
in:
(Hex.) function function
A network problem was detected after • Check that the cables are connected
01H QJ71DN91
communication was started. correctly.
• Check the entire network and slave node
states for MAC ID and baud rate setting,
1EH QJ71DN91 The slave node did not respond.
a failed slave node, or disconnection of a
terminating resistor.
• Read the communication error
A slave node responded with a non-
20H Slave node information, and take an appropriate
prescribed error.
action according to the error information.
• Read the communication error
A slave node responded with an error
23H Slave node information, and take an appropriate
when establishing a connection.
action according to the error information.
The input data size set with a parameter
• Check the slave node manual and set the
24H QJ71DN91 is different from the size for the actual
correct input data size.
slave node.
The output data size set with a
• Check the slave node manual and set the
25H QJ71DN91 parameter is different from the size for
correct output data size.
the actual slave node.
• Check the slave node manual, and
prevent any data of the function not
Response data of the function that is not supported by the QJ71DN91 from being
26H QJ71DN91 supported by the QJ71DN91 was sent from the slave node.
received. • Check the entire network and slave node
states for any fault such as disconnection
of a terminating resistor.
• Check the entire network and slave node
The connection is already in the
27H Slave node states for any fault such as disconnection
specified mode.
of a terminating resistor.
• Check the entire network and slave node
Unexpected invalid data was received
28H QJ71DN91 states for any fault such as disconnection
when the connection was established.
of a terminating resistor.
Connection has already been • Wait for a while, and reset the slave node
29H Slave node
established with that slave node. if the connection cannot be established.
The data length of a polling response is
• Check the entire network and slave node
different from the length of the data that
2AH QJ71DN91 states for any fault such as disconnection
was read from the slave node when a
of a terminating resistor.
connection was established.
When a polling response was divided • Check the entire network and slave node
2BH QJ71DN91 into several data units, the first data unit states for any fault such as disconnection
was received twice. of a terminating resistor.
When a polling response was divided • Check the entire network and slave node
2CH QJ71DN91 into several data blocks, data of an states for any fault such as disconnection
unexpected number was received. of a terminating resistor.
When a polling response was divided
• Check the entire network and slave node
into several data blocks, the second data
2DH QJ71DN91 states for any fault such as disconnection
block or later was received before the
of a terminating resistor.
first one.
9 - 11 9 - 11
9 TROUBLESHOOTING
MELSEC-Q
Error Detectability
Detected
code Description Action Master Slave
in:
(Hex.) function function
• The same node No. is set for two or more
slave nodes. Correct the duplicated
Two or more identical node numbers parameter settings.
3BH QJ71DN91
(MAC IDs) were detected in parameters. • A slave node having the same node No.
as that of this node exists in the
parameters.
• Check if the connection type value is
correct.
47H QJ71DN91 Incorrect connection type was specified.
• Read the communication error
information, and take appropriate actions.
• Check the entire network and slave node
The polling connection in the slave states for any fault such as disconnection
80H QJ71DN91
function has timed out. of a terminating resistor.
• Check the master node status.
A connection other than for explicit • Do not allocate any I/O connection other
81H QJ71DN91
messages and polling was allocated. than for polling.
The number of bytes received by polling
• Set the master node’s I/O points that
82H QJ71DN91 is greater than the max. number of
match the settings of the QJ71DN91.
receive points.
9 - 12 9 - 12
9 TROUBLESHOOTING
MELSEC-Q
9.2.2 Execution error codes of message communication (for the master function only)
9 - 13 9 - 13
9 TROUBLESHOOTING
MELSEC-Q
Error
Detected
code Description Action
in:
(Dec.)
• Check whether or not the specified MAC ID, class ID,
instance ID and attribute ID are correct.
The requested service cannot be executed in the
16 Slave node • Referring to the slave node manual, check the
current device status.
condition under which the slave node notifies this
error, and take an appropriate action.
• Check the entire network and slave node states for
17 QJ71DN91 Slave node did not respond. any fault such as slave node failure, or disconnection
of a terminating resistor.
• Check whether or not the specified MAC ID, class ID,
instance ID and attribute ID are correct.
• In the case of set attribute, verify that the specified
Sufficient data was not provided to execute the
19 Slave node data is sufficient and the data length is correct.
specified operation.
• Referring to the slave node manual, check the
condition under which the slave node notifies this
error, and take an appropriate action.
• Check whether or not the specified MAC ID, class ID,
instance ID and attribute ID are correct.
20 Slave node The specified attribute is not supported. • Referring to the slave node manual, check the
condition under which the slave node notifies this
error, and take an appropriate action.
• Reduce the data returned from the slave node to 240
21 Slave node The service provided excessive data.
bytes or less.
• Check whether or not the specified MAC ID, class ID,
instance ID and attribute ID are correct.
The specified object does not exist in the slave
22 Slave node • Referring to the slave node manual, check the
node.
condition under which the slave node notifies this
error, and take an appropriate action.
• Check the entire network and slave node states for
50 QJ71DN91 The response data format is invalid. any fault such as disconnection of a terminating
resistor.
55 QJ71DN91 The specified slave node No. is other than 0 to 63. • Specify a node No. in the range of 0 to 63.
• Check the entire network and slave node states for
57 QJ71DN91 The divided data were received in incorrect order. any fault such as disconnection of a terminating
resistor.
The data length set in the buffer memory is 241 or
257 QJ71DN91 • Set the data length to 240 bytes or less.
more.
An invalid value was set as a command No. in the
• Set 0001H, 0101H, 0102H, 0201H, or FE**H as a
258 QJ71DN91 Message Communication Command area of the
command No.
buffer memory.
300 QJ71DN91 The own node is set offline. • Set Y11 to ON to set the own node online.
301 QJ71DN91 An error occurred during data queuing. • Perform a hardware test to check for hardware failure.
• Check the entire network and slave node states for
302 QJ71DN91 A timeout occurred while waiting for a response. any fault such as disconnection of a terminating
resistor.
• Check the entire network and slave node states for
303 QJ71DN91 An invalid response was obtained. any fault such as disconnection of a terminating
resistor.
The specified node No. is currently set for a • Set a node No. that is not being used for a reserved
304 QJ71DN91
reserved node. node.
• Send messages to address any other than the own
305 QJ71DN91 The message was sent to the own node.
node.
9 - 14 9 - 14
9 TROUBLESHOOTING
MELSEC-Q
Error
Detected
code Description Action
in:
(Dec.)
• Check whether the parameter value for the message
306 QJ71DN91 Failed to open a message connection.
group is set correctly or not.
• Verify that the transmit message can be responded by
317 Slave node The response data length is too long.
the slave node.
9 - 15 9 - 15
9 TROUBLESHOOTING
MELSEC-Q
9.2.3 General DeviceNet error codes of message communication (for the master function
only)
Error code
Error name Description
Hex. Dec.
0000H to 0001H 0 to 1 Reserved Reserved by DeviceNet.
The requested service could not be executed because there was no
0002H 2 Resource unavailable
space in the required resource.
0003H to 0007H 3 to 7 Reserved Reserved by DeviceNet.
The requested service is not supported. Or, the requested service is not
0008H 8 Service not supported
defined by the specified object class/instance.
0009H 9 Invalid attribute value The requested service had an error in the attribute data.
000AH 10 Reserved Reserved by DeviceNet.
The specified object has already been changed into the requested
000BH 11 Already in requested mode/state
mode/status.
The specified object was not in the state that could execute the requested
000CH 12 Object state conflict
service.
000DH 13 Reserved Reserved by DeviceNet.
000EH 14 Attribute not settable The requested setup service specified an unchangeable attribute.
000FH 15 Privilege violation The service requester did not have the access privilege.
The specified device was not in the state that could execute the
0010H 16 Device state conflict
requested service.
The response data length exceeded the data length that can be
0011H 17 Reply data too large
processed.
0012H 18 Reserved Reserved by DeviceNet.
The requested service did not provide sufficient data to execute
0013H 19 Not enough data
processing.
0014H 20 Attribute not supported The requested service specified an undefined attribute.
0015H 21 Too much data The requested service includes invalid data.
0016H 22 Object does not exist The requested service specified an unimplemented object.
0017H 23 Reserved Reserved by DeviceNet.
The attribute data of this object had not been saved before this service
0018H 24 No stored attribute data
was requested.
The attribute data of this object was not saved due to an error that
0019H 25 Store operation failure
occurred during the save operation.
001AH to 001EH 26 to 30 Reserved Reserved by DeviceNet.
A vender-specific error occurred. A specific error occurred is indicated in
the "Additional error code" area (0134H) of the error response. This error
001FH 31 Vendor specific error
code can be used only when the error codes shown in this table and
object class definitions do not apply to the corresponding error.
The requested service had a parameter error. This code can be used
only when the parameter satisfies neither the requirements of the
0020H 32 Invalid parameter
DeviceNet specifications nor the requirements defined by application
object specifications.
0021H to 0027H 33 to 39 Future extensions Reserved by DeviceNet.
An unimplemented class/instance/attribute was specified for the member
0028H 40 Invalid Member ID
ID of the requested service.
0029H 41 Member not settable The requested setup service specified an unchangeable member.
002AH to 00CFH 42 to 207 Reserved Reserved by DeviceNet.
This error code range is used to indicate errors specific to the object
class. The code in this range can be used only when any error code in
00D0H to 00FFH 208 to 255 Reserved for Object Class and service errors this table does not correctly explain the error that occurred. Using the
"Additional error code" area (0134H), the "General DeviceNet error code"
area (0133H) can be explained in detail.
9 - 16 9 - 16
9 TROUBLESHOOTING
MELSEC-Q
Error codes and LED status can be checked by selecting the detailed information of
the QJ71DN91 from System monitor of GX Developer.
050220000000000-B
Function version B
Serial No. (first 5 digits) 05022
9 - 17 9 - 17
9 TROUBLESHOOTING
MELSEC-Q
9 - 18 9 - 18
APPENDIXES
MELSEC-Q
APPENDIXES
QJ71DN91
RUN MS
NS
ERR.
NODE ADDRESS
5 6
4
2 3
7 8
X10
9
01
5 6
4
2 3
X1
7 8
98 (3.86)
MODE/DR 9
0 : M/125 01
1 : M/250
2 : M/500 M 78 9
4 56
AB E
3 : S/125 O
CD
4 : S/250 D
23
5 : S/500 E
F01
6 : D/125
7 : D/250
8 : D/500
QJ71DN91
(Unit: mm)
App
App - 1 App - 1
APPENDIXES
MELSEC-Q
The table below lists new functions of the QJ71DN91 and serial No. and software
version of the products that support each function.
The following table lists the differences between the QJ71DN91 and the
AJ71DN91/A1SJ71DN91.
Model name
QJ71DN91 AJ71DN91/A1SJ71DN91
Function
DeviceNet master function and DeviceNet
DeviceNet master/slave function DeviceNet master function only
slave function
Number of I/O points of the DeviceNet
Input 4096 points, output 4096 points Input 2048 points, output 2048 points
master function
Auto configuration function Available Not available
Auto refresh function with programmable
Available (requires GX Configurator-DN) Not available
controller CPU
Constant scan Available Not available
Hardware test/communication test function Available Not available
3 methods
2 methods
• Setting with sequence programs
Parameter setting method • Setting with sequence programs
• Setting with GX Configurator-DN
• Setting with configuration software
• Setting with the auto configuration function
App
App - 2 App - 2
APPENDIXES
MELSEC-Q
Buffer memory
Item Description Set value
address (Hex.)
Specify a value to make the link scan time constant.
01D7H Constant scan
(Setting range: 0 to 65535ms (FFFFH))
[ th slave node]
Buffer memory
Item Description Set value
address (Hex.)
Low byte: Node No. of th slave node (MAC ID)
00H to 3FH (0 to 63)
High byte: 01H Node that supports UCMM and uses any of
message groups 3, 2, and 1.
01D8H + ( - 1) 8 Node No. and message group 03H Node that supports UCMM and uses message
group 1
04H Node that does not support UCMM (Group 2 only
server)
80H Reserved node
Select a connection type for I/O communication.
0001H = Polling
01D9H + ( - 1) 8 Connection type 0002H = Bit strobe
0004H = Change of state
0008H = Cyclic
Low byte: Number of input byte modules
01DAH + ( - 1) 8 Number of byte modules High byte: Number of output byte modules (set in hexadecimal)
Eight bit modules (8 points) are counted as one byte module.
Low byte: Number of input word modules
01DBH + ( - 1) 8 Number of word modules
High byte: Number of output word modules (set in hexadecimal)
Low byte: Number of input double-word modules
Number of double-word
01DCH + ( - 1) 8 High byte: Number of output double-word modules (set in
modules
hexadecimal)
Set an expected packet rate for the slave node.
(Setting range: 0 to 65535 ms (FFFFH))
01DDH + ( - 1) 8 Expected packet rate
0000H: 200ms (Default)
Other than 0000H: Set value – 1 (ms)
Set an action for watchdog timeout of the slave node.
0000H: Equivalent to the following Timeout (Default)
01DEH + ( - 1) 8 Watchdog timeout action 0001H: Timeout
0002H: Auto Delete
0003H: Auto Reset
Set a production inhibit time.
(Setting range: 0 to 65535ms (FFFFH))
01DFH + ( - 1) 8 Production inhibit time
0000H: 10ms (Default)
Other than 0000H: Set value –1 (ms)
When setting parameters, use a copy of this sheet.
App - 3 App - 3
APPENDIXES
MELSEC-Q
Buffer memory
Item Description Set value
address (Hex.)
Slave function receive-bytes Set a size of I/O data that can be received for the slave function.
060EH
(input size) setting area (Setting range: 0 to 128 bytes, Default: 8 bytes)
Slave function transmit-bytes Set a size of I/O data that can be sent for the slave function.
060FH
(output size) setting area (Setting range: 0 to 128 bytes, Default: 8 bytes)
App - 4 App - 4
APPENDIXES
MELSEC-Q
The following table lists an example of parameter setting for communicating with slave
nodes from various manufacturers. For more details on the parameter settings, please
contact each manufacturer.
Set value (values in parentheses are for the case of setting with sequence programs) Remarks
No. of byte No. of word No. of double- Watch-
Expected Production
Name of Connection modules modules word modules dog Message
Model Name Packet Inhibit UCMM
manufacturer type Timeout group
Output Input Output Input Output Input Rate Time
Action
DeviceNet
00H to 00H to 200ms Timeout 10ms
QJ71DN91 master/slave Polling (H1) 00H 00H 00H 00H Yes 3
80H 80H (K201) (H1) (H0)
Mitsubishi module
Electric A500 Series
Corporation inverter 1000ms Timeout 10ms
FR-A5ND Polling (H1) 04H 04H 00H 00H 00H 00H Yes 3
DeviceNet (K1001) (H1) (K11)
option
1000ms 10ms
Polling (H1)
(K1001) (K11)
1000ms 10ms
Flex I/O Bit strobe (H2)
(K1001) Timeout (K11)
1794ADN DeviceNet 00H 02H 00H 00H 00H 00H Yes 3
Rockwell Change-of- 0ms (H1) 0ms
adapter
Automation state (H4) (H0) (H0)
Japan Co., 30ms 25ms
Cyclic (H8)
Ltd. (K31) (K26)
Flex I/O input
1794-IB16 — 02H 02H 00H 00H 00H 00H — — — — —
module
1794- Flex I/O output
— 02H 02H 00H 00H 00H 00H — — — — —
OB16 module
DRT1- CompoBus/D Polling (H1)/ 1000ms Timeout 10ms
00H 01H 00H 00H 00H 00H No —
ID08 8-point input bit strobe (H2) (K1001) (H1) (K11)
DRT1- CompoBus/D Polling (H1)/ 1000ms Timeout 10ms
00H 02H 00H 00H 00H 00H No —
ID16 16-point input bit strobe (H2) (K1001) (H1) (K11)
DRT1- CompoBus/D 1000ms Timeout 10ms
Polling (H1) 01H 00H 00H 00H 00H 00H No —
OD08 8-point output (K1001) (H1) (K11)
Omron DRT1- CompoBus/D 1000ms Timeout 10ms
Polling (H1) 02H 00H 00H 00H 00H 00H No —
Corporation OD16 16-point output (K1001) (H1) (K11)
CompoBus/D
DRT1- Polling (H1)/ 1000ms Timeout 10ms
4-point analog 00H 00H 00H 04H 00H 00H No —
AD04 bit strobe (H2) (K1001) (H1) (K11)
input
CompoBus/D
DRT1- 1000ms Timeout 10ms
2-point analog Polling (H1) 00H 00H 02H 00H 00H 00H No —
DA02 (K1001) (H1) (K11)
output
DeviceNet
SX5D- 1000ms Timeout 10ms
16-point digital Polling (H1) 00H 02H 00H 00H 00H 00H No —
SBN16S (K1001) (H1) (K11)
input
DeviceNet
SX5D- 1000ms Timeout 10ms
IDEC (Izumi) 16-point digital Polling (H1) 02H 00H 00H 00H 00H 00H No —
SBT16K (K1001) (H1) (K11)
Corporation output
DeviceNet
SX5D- 8-point digital 1000ms Timeout 10ms
Polling (H1) 01H 01H 00H 00H 00H 00H No —
SBM16K input/8-point (K1001) (H1) (K11)
digital output
App - 5 App - 5
APPENDIXES
MELSEC-Q
The following shows the EDS file of the QJ71DN91. The EDS file is stored in the CD-
ROM of GX Configurator-DN.
$ Mitsubishi Master/Slave EDS file
$ File Description Section
[File]
DescText="QJ71DN91 EDS file";
CreateDate=08-28-2000; $ created
CreateTime=12:00:00;
ModDate=08-28-2000; $ last change
ModTime=12:00:00;
Revision=1.1; $ Revision of EDS
$ Device Description Section
[Device]
VendCode=0xA1;
VendName="MITSUBISHI ELECTRIC CORPORATION";
ProdType=0x0C; $ Communication Adapter Device
ProdTypeStr="Communication Adapter"; $ Communication Adapter Device
ProdCode=4;
MajRev=1;
MinRev=1;
ProdName="QJ71DN91";
Catalog="";
$ I/O Characteristics Section
[IO_Info]
Default=0x0001; $ Poll Only
PollInfo=0x0001,
1, $ Default Input = Input1
1; $ Default Output = Output1
$ Input Connections
Input1= $ Input(Producing)
8, $ 8 byte
0, $ 0 bits are significant
0x0001, $ Poll Only Connection
"Input Data", $ Name
6, $ Path Size
"20 04 24 64 30 03", $ Assembly Object Instance 100
"Data"; $ Help
$ Output Connections
Output1= $ Output(Consuming)
8, $ 8 byte
0, $ 0 bits are significant
0x0001, $ Poll Only Connection
"Output Data", $ Name
6, $ Path Size
"20 04 24 65 30 03", $ Assembly Object Instance 101
"Data"; $ Help
[ParamClass]
MaxInst=0;
Descriptor=0x00;
CfgAssembly=0;
App - 6 App - 6
APPENDIXES
MELSEC-Q
MEMO
App - 7 App - 7
INDEX
Ind
[A] [F]
Add configuration .......................................... 3-35 Failed node detection setting ........................3-31
All configuration............................................. 3-35 Flash ROM setting .........................................6-32
Auto-configuring (X14) .................................. 3-12 Functions of the utility package .......................6-1
Auto configuration .........................................A-11 Function version...................................... 2-5,9-17
Auto configuration completion (X15) ............ 3-12
Auto communication start setting ................. 3-46 [G]
Auto configuration operation setting ............. 3-35 General DeviceNet error codes.....................9-16
Auto configuration request (Y15) .................. 3-12 GX Configurator-DN ................................ 2-4, 6-1
Auto refresh ................................................... 6-13 GX Developer ..................................................2-4
[B] [H]
Bit strobe.......................................................... 4-5 Hardware test...................................................5-8
Buffer memory list ......................................... 3-17 Hardware test item area ................................3-44
Bus error counter........................................... 3-27 Hardware test result area ..............................3-45
Bus off counter .............................................. 3-27 H/W test completion (X0B) ............................3-12
H/W test error detection (X0C) ......................3-12
[C] H/W test in progress (X0A)............................3-12
Change of state ............................................... 4-6
Checking the LEDs ......................................... 9-2 [I]
Communication error codes............................ 9-8 I/O address area for master function.............3-39
Communication test ...................................... 5-10 I/O communicating (X01)....................... 3-5, 3-13
Cyclic ............................................................... 4-7 I/O communication request (Y11) ......... 3-5, 3-13
I/O signal list.....................................................3-4
[D]
Differences from the AJ71DN91/A1SJ71DN91 [L]
.....................................................................App-2 LED indications ................................................5-6
Link scan time ................................................3-48
[E] List of communication parameters of slave nodes
EDS file........................................................App-6 from various manufacturers........................ App-5
Error codes ...................................................... 9-8
Error information for master function ............ 3-27 [M]
Error information for slave function............... 3-40 Master function (I/O communication function)
Error reset request for master function (Y13) ................................................................ 4-1, 7-35
......................................................................... 3-9 Master function communication status..........3-25
Error reset request for slave function (Y18) Master function receive data .........................3-37
....................................................................... 3-16 Master function transmit data ........................3-38
Error set signal for master function (X03)....... 3-9 Maximum link scan time ................................3-39
Error set signal for slave function (X08) ....... 3-16 Message communication command .............3-20
Execution error codes of message communication Message communication completion (X02)....3-8
....................................................................... 9-13 Message communication data ......................3-23
Expected packet rate .................................... 3-34 Message communication error signal (X05)
External dimensions....................................App-1 ..........................................................................3-8
Message communication function......... 4-8, 7-31
Message communication request (Y12) .........3-8
Index - 1 Index - 1
[M] Slave function receive data ...........................3-42
Message communication result .................... 3-21 Slave function receive-bytes setting area .....3-41
Ind Minimum link scan time................................. 3-39 Slave function transmit data ..........................3-42
Mode switch..................................................... 5-8 Slave function transmit-bytes setting area....3-41
Mode switch No. .......................................... 3-43 Starting the intelligent function module utility
Model name................................................... 3-43 ........................................................................6-11
Module ready (X0F) ...................................... 3-11 System configuration .......................................2-1
Monitoring...................................................... 6-16
[T]
[N] Test.................................................................6-16
Node communication error status................. 3-30 Transmission delay........................................3-47
Node communication status ......................... 3-29
Node configuration status ............................. 3-29 [W]
Node fault status ........................................... 3-30 Watchdog timer error (X00) .............................3-5
Node No. ..................................................... 3-43 When unable to communicate with all slave nodes
Node No. switches .......................................... 5-7 ..........................................................................9-3
When unable to communicate with a specific slave
[O] node..................................................................9-4
Obtaining error information (master function) When unable to communicate with master node
....................................................................... 7-34 ..........................................................................9-5
Obtaining error information (slave function) Wiring ...............................................................5-9
....................................................................... 8-12
ODVA............................................................... 2-2
Operation overview ......................................... 6-9
Operation setting area for bus off error ........ 3-27
[P]
Parameters saved to flash ROM (X07) ........ 3-10
Parameter saving area selection area.......... 3-46
Parameters for the master function ....... 3-32, 7-9
Parameters for the slave function.......... 3-41, 8-1
Performance specifications............................. 3-1
Polling .............................................................. 4-4
Precautions for network power supply ......... 5-11
Present link scan time ................................... 3-39
Production inhibit time................................... 3-34
Programming precautions............................... 7-1
[R]
Request for saving parameters to flash ROM
(Y17) .............................................................. 3-10
[S]
Saving parameters to flash ROM (X06) ....... 3-10
Slave function (I/O communication function)
................................................................ 4-11, 8-9
Slave function communication status ........... 3-40
Index - 2 Index - 2
WARRANTY
Please confirm the following product warranty details before using this product.
3. Overseas service
Overseas, repairs shall be accepted by Mitsubishi's local overseas FA Center. Note that the repair conditions at each FA
Center may differ.
6. Product application
(1) In using the Mitsubishi MELSEC programmable controller, the usage conditions shall be that the application will not
lead to a major accident even if any problem or fault should occur in the programmable controller device, and that
backup and fail-safe functions are systematically provided outside of the device for any problem or fault.
(2) The Mitsubishi programmable controller has been designed and manufactured for applications in general industries,
etc. Thus, applications in which the public could be affected such as in nuclear power plants and other power plants
operated by respective power companies, and applications in which a special quality assurance system is required,
such as for Railway companies or Public service purposes shall be excluded from the programmable controller
applications.
In addition, applications in which human life or property that could be greatly affected, such as in aircraft, medical
applications, incineration and fuel devices, manned transportation, equipment for recreation and amusement, and
safety devices, shall also be excluded from the programmable controller range of applications.
However, in certain cases, some applications may be possible, providing the user consults their local Mitsubishi
representative outlining the special requirements of the project, and providing that all parties concerned agree to the
special circumstances, solely at the users discretion.
Microsoft, Windows, Windows NT, and Windows Vista are registered trademarks of Microsoft Corporation in
the United States and other countries.
Pentium is a registered trademark of Intel Corporation in the United States and other countries.
Other company and product names herein are either trademarks or registered trademarks of their respective
owners.
SPREAD
Copyright (c) 1996 FarPoint Technologies, Inc.
SH(NA)-080143-J
MITSUBISHI ELECTRIC
MITSUBISHI
ELECTRIC Mitsubishi Electric Europe B.V. /// FA - European Business Group /// Gothaer Straße 8 /// D-40880 Ratingen /// Germany
FACTORY AUTOMATION Tel.: +49(0)2102-4860 /// Fax: +49(0)2102-4861120 /// [email protected] /// www.mitsubishi-automation.com