Ficha Técnica - FTA1930 - Mark III+ - Firetrol - 75HP

The document outlines the specifications and features of the Firetrol MarkIII+ Electric Fire Pump Controller, which includes solid state reduced current starting capabilities. It details voltage and power ratings, standards compliance, enclosure specifications, operator interface features, alarm indications, and communication options. The controller is designed for reliable operation in fire protection systems and includes advanced monitoring and logging functionalities.

Uploaded by

Golsatel Peru
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
108 views18 pages

Ficha Técnica - FTA1930 - Mark III+ - Firetrol - 75HP

The document outlines the specifications and features of the Firetrol MarkIII+ Electric Fire Pump Controller, which includes solid state reduced current starting capabilities. It details voltage and power ratings, standards compliance, enclosure specifications, operator interface features, alarm indications, and communication options. The controller is designed for reliable operation in fire protection systems and includes advanced monitoring and logging functionalities.

Uploaded by

Golsatel Peru
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

Submittal FTA1930

Package

MARKIII+ Electric Fire Pump Controller - Solid State Reduced Current Starting

Project Information

Voltage / Power Table

Voltage Min HP Max HP

208 40 60

220 - 240 40 75

380 - 400 - 415 75 125

440 - 480 75 150

600 100 200

DRAWINGS INCLUDED IN THIS PACKAGE ARE FOR STANDARD


CONTROLLERS. ACTUAL “AS BUILT” DRAWINGS MAY DIFFER FROM
THOSE SHOWN HERE.

3362 Apex Peakway


Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability,
for damages resulting from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice.
©2023 Firetrol, Inc., All Rights Reserved.
Publication SBP1930-821 Rev. A
Firetrol MarkIII+ Electric Fire Pump Controller
FTA1930 - Solid State Reduced Current Starting
Specifications

1.0 Main Fire Pump Controller


The main fire pump controller shall be a factory assembled, wired and tested unit.
The controller shall be of the combined manual and automatic type designed for full
voltage starting of the fire pump motor having the horsepower, voltage, phase and
frequency rating shown on the plans and drawings. The controller shall be rated for an
Ambient Temperature Operating Range of 39ºF (4ºC) to 104ºF (40ºC).

1.1 Standards, Listings & Approvals


The controller shall conform to all the requirements of the latest editions of:
NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection
NFPA 70, National Electrical Code.

The controller shall be listed by:


Underwriters Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Con-
trollers Canadian Standards Association CSA-C22.2, Standard for Industrial Control
Equipment (cUL)
CE - Low Voltage Directive

The controller shall be approved by:


Factory Mutual (IEC 62091)
The City of New York for fire pump service

1.2 Enclosure
The controller components shall be housed in a NEMA Type 2 (IEC IP22) drip-proof, wall
mounted enclosure with bottom entry gland plate and lifting lugs.

1.3 Withstand Ratings (Short Circuit Current Ratings)


All controller components shall be front mounted, wired and front accessible for main-
tenance. The available short circuit current ratings are shown below.
Code 200-208V 220-240V 380-415V 440-480 550-600
5-150 HP 5-200 HP 5-350 HP 5-400 HP 5-500 HP
M - Standard 100kA 100kA 100kA 100kA N/A
N - Intermediate 150kA 150kA 150kA 150kA N/A
P - High 200kA 200kA 200kA 200kA N/A
Q - Intermediate N/A N/A N/A N/A 100kA
R - Standard N/A N/A N/A N/A 50kA
200-208V 220-240V 380-415V 440-480
Code 200 HP 250-400 HP 400-500 HP 450-500 HP
M - Standard 50A 50kA 50kA 50kA
N - Intermediate N/A N/A N/A N/A
P - High 100kA 100kA 100kA 100kA
Q - Intermediate N/A N/A N/A N/A
R - Standard N/A N/A N/A N/A

1.4 Power Components


The controller shall include a combination isolating disconnect switch/circuit breaker,
rated for not less than 115% of the motor full load current, mechanically interlocked and
operated with a single, externally mounted handle. The isolating disconnect switch/
circuit breaker shall be mechanically interlocked so that the enclosure door cannot be
opened with the handle in the ON position except by a hidden tool operated bypass
mechanism. The isolating disconnect switch/circuit breaker shall be capable of being
padlocked in the OFF position for installation and maintenance safety, and shall also be
capable of being locked in the ON position without affecting the tripping characteristics
of the circuit breaker.
The controller will include a voltage surge arrestor and Solid State Reduced Current
starting.
The controller shall be equipped with a single handle, manually operated, emergency
start mechanism capable of being latched in the ON position.

1.5 Operator Interface (HMI)


The operator interface shall be a 7.0” LCD capacitive type color touch screen (HMI
technology) powered by an embedded microcomputer with software PLC logic. In-
cluded shall be keypad type push-buttons for START, STOP and TEST.
The screen shall include menus for: Home · Alarms · Configuration · History · Service ·
Manuals · Language.

The HMI shall graphically display the following: Voltage and Amperage of all 3 phas-
es simultaneously using true RMS Technology · Motor Stopped/Running · Starting
Cause · Actuation Mode · Controller Type · Shutdown Mode · Date & Time · Pump
Room Temp. · System Pressure
System pressure shall be capable of being displayed as: PSI, kPa, Bar, Feet of Head or
Meters of Water.

The HMI shall allow programming and display of: Cut In & Cut Out Pressure Settings ·
Minimum Run Timer · Sequential Start Timer · Periodic Test Timer

The HMI allows the user to select the language of the system and download the
manual or view the manual on screen.

1.6 State and Alarm Indication


Visual indication shall be provided for the following:
Power Available • Motor Run • Periodic Test • Manual Start • Deluge Valve Start • Remote
Automatic Start • Remote Manual Start • Emergency Start • Pump On Demand/Auto-
matic Start • Pump Room Temperature • Lockout

The digital display shall visually indicate the following alarms:


• Locked Rotor Current • Fail To Start • Under/Over Current • Under/Over Voltage •
Phase Unbalance • Check Test Solenoid Valve • Weekly Test Cut-In Not Reached •
Transducer Fault • Control Voltage Not Healthy • Motor Trouble • Pump Room Alarm •
Invalid Cut-In • Phase Reversal • Power Loss • Phase Loss L1 / L2 / L3 • Low Water Level •
Pump On Demand • Low Ambient Temp. • Service Required

Audible and visible alarm shall be provided for: Fail To Start

Remote Alarm contacts shall be provided for:


Power Available • Phase Reversal • Motor Run • Common Pump Room Alarm (Overvolt-
age, Undervoltage, Phase Unbalance, Low/High Pump Room Temperature) • Common
Motor Trouble (Overcurrent, Fail To Start, Undercurrent, Ground Fault)

1.7 Pressure and Event Recording


The system shall be capable of logging pressure data and operational events with
time/date stamp. The system shall display operational events for the lifetime of the
controller and display the pressure data in text or graphical form. The controller shall
log the Date/Time of the first start-up and the controller total power on time from
that date. The controller shall log first and last statistics for: First Setup · On Time ·
Start Count · Last Start Time · Min/Max/Average System Pressure · Min/Max/Average
Pump Room Temp. · Jockey Pump On Time/Start Count/Last Start Time · Phase to
Phase Voltages with Date Stamp · Amps Per Phase with Date Stamp

1.8 USB Host Controller


A USB port capable of accepting a USB Flash Memory Disk shall be provided for
downloading pressure and event logs.

1.9 Serial Communications


The controller shall feature Modbus with TCP/IP frame format and shielded female RJ45
connector

2.0 Pressure Sensing / Wet Parts


The controller shall be supplied with a solid state pressure transducer with a range of
0-500 psi calibrated for 0-300 psi (0-20.7 bar) and a run test solenoid valve. The wet
parts shall be externally mounted and include a protective cover. The pressure sens-
ing line connection to the transducer shall be 1/2-inch FNPT. Provisions for a redun-
dant pressure transducer shall be provided.

2.1 Controller Operation


The controller shall be capable of automatic starting via pressure drop, remote start
signal from an automatic device or a deluge valve. The controller can be manually
started via the START push-button, the RUN TEST push-button, or a remote signal from
a manual device. Stopping can be achieved manually with the STOP push-button or
automatically after expiration of minimum run timer or test timer. The minimum run
timer (off delay), sequential start timer (on delay) and periodic test timer shall be field
adjustable and include a visual countdown on the display.

2.2 Manufacturer
The controller shall be a Firetrol brand.

3412 Apex Peakway


Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2022 Firetrol, Inc., All Rights Reserved.
Publication SP1930-60 Rev. C
Product Description FTA1930

MarkIII+ Electric Fire Pump Controllers - Solid State Reduced Current Starting

Standard Features — The following are


included as standard with each con-
troller:
• Voltage surge protector
• Main Disconnect Switch sized for con-
nected motor horsepower and voltage
• Fire pump Circuit Breaker
• Single Handle Isolating Disconnect
Switch/Circuit Breaker mechanism
• Motor contactor
• Single Handle Emergency Manual Run
Mechanism to mechanically close
motor contactor contacts in an emer-
Description—Firetrol® FTA1930 Solid State
gency condition
Reduced Current Starting Fire Pump
• Built-in Start and Stop push-buttons to
Controllers feature soft start, soft stop
bypass automatic start circuits
and system sensing capabilities that not
• Daylight Savings Time Option
only provide for reduced current starting,
• Elapsed Time Meter
but also offer an improved level of hydro
• 7.0” LCD capacitive type color touch
mechanical performance. The controller
screen (HMI technology) software up-
monitors, displays and records fire pump
gradeable operator interface powered
system information.
by an embedded microcomputer with
software PLC logic.
Approvals – Firetrol fire pump controllers • 500 PSI Pressure Transducer (cali-
are listed by Underwriters’ Laboratories, brated for 300 PSI (20.7 Bar))and Test
Inc., in accordance with UL218, Standard Solenoid for fresh water applications,
for Fire Pump Controllers, CSA, Standard externally mounted with protective
for Industrial Control Equipment, and cover
approved by Factory Mutual. They are • Audible alarm buzzer embedded in the
built to meet or exceed the requirements MarkIII+
of the approving authorities as well as • Pump Room Ambient Temperature
NEMA and the latest editions of NFPA 20, Switch, Display and Alarms
Installation of Centrifugal Fire Pumps, • Pressure and Event Recording with
and NFPA 70, National Electrical Code. Date Stamp to System Memory Ac-
cessible VIA The User Interface and
Downloadable to a USB Flash Drive
• Modbus Communications with TCP/IP
frame format and a shielded female
RJ45 connector
• NEMA Type 2 (IEC IP22) enclosure with
bottom entry gland plate and lifting
lugs
• Suitable for use as Service Equipment
• The controller supplies visual indica-
tion of the following: Power Available
• Motor Run • Periodic Test • Manual
Start • Deluge Valve Start • Remote
Automatic Start • Remote Manual
Start • Emergency Start • Pump On
Demand (Automatic Start) • Pump
Room Temp. • Lockout
• The controller displays visual indica-
tion for the following alarm conditions:
Control Voltage Not Healthy • Invalid
Cut-In • Lock Rotor Current • Loss of
Power • Low Ambient Temp. • Low Water
Level • Motor Trouble • Phase Reversal
• Overcurrent • Overvoltage • Phase
Loss L1 / L2 / L3 • Phase Unbalanced •
Pressure Transducer Fault Detected •
Pump On Demand • Pump Room Alarm
• Service Required • Undercurrent •
Undervoltage • Check Test Solenoid •
Weekly Test Cut-In Reached
• Audible and Visible Indication for Fail
To Start.
• DPDT 8A, 250VAC remote alarm con-
tacts are provided for: Power Available
• Phase Reversal • Motor Run
• Common Pump Room Alarm (Over-
voltage / Undervoltage / Phase Unbal-
ance / Low Pump Room Temp. / High
Pump Room Temp)
• Common Motor Trouble (Overcurrent
/ Fail To Start / Undercurrent / Ground
Fault)
• Field Adjustable Timers with Visual
Countdown for Minimum Run (Off De-
lay), Sequential Start (On Delay) and
Weekly Test

FOR MODEL # INFORMATION SEE


PUBLICATION SD1000-60
FOR OPTIONS AND MODIFICATIONS SEE
PUBLICATION OP1000-71

3412 Apex Peakway


Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2022 Firetrol, Inc., All Rights Reserved.
Publication PD1930-60 Rev. D
General Starting FTA1930
Configuration

MarkIII+ Electric Fire Pump Controllers - Solid State Reduced Current Starting

Circuit
Switch Breaker
Mechanically Interlocked in

200-600 VAC 3Ø
Power Supply
Voltage and Current
Sensing

Aux Run Contacts = 1M

Running 1M (Bypass)
Digital 1M 1**
Manual Emergency Run
Soft Operator mechanically linked
Starter to contact carrier of contactor

FS*1 0 sec
Aux Contact = 1CR
starter reaches full speed (FS).
Fire Pump
Default = 5 sec. Control Relays
**Indicates number of auxiliary
contacts supplied with contactor. CR4 CR5
General Starting Configuration

Soft starting
Legend:
Peak Inrush Current (DOL) FLA : Full Load Amperage / Full Load Current
FLT : Full-Load Torque / Rated Torque at FLA, Vn, and Full-Load Speed
Vn : Nominal Voltage / Rated Voltage

Locked Rotor Current (DOL)

600 300
100% Vn

500

Motor Torque (%)


Motor Current (%)

400 Adjustable 200


Voltage ramp current limit * 100% Vn

300 Voltage ramp

200 Tn 100 Accelerating


Torque ramp
Torque ramp Torque

In 100
Resistive Torque (Pump)

20 40 60 80 100 20 40 60 80 100
Motor speed (%)N n Motor speed (%)N n
*Low current limit may cause the motor to not accelerate or even stall; not respecting the 10 seconds ramp code requirement.

Starting Method: Soft Start / Soft Stop


Starting voltage per winding: Reduced
Typical voltage applied at motor starting (%Vn): 30-50% Adjust.
Peak inrush current at starting (1): Negligible
Peak inrush current at transition (1): Negligible
Starting current (% FLA) (2): 250 - 450%
Transition current (% FLA) (3): N/A
Starting Torque (% FLT) (4): 10-100% (Adjust. on Torque Ramp Mode)
Motor type(5): Standard
Number of wire connections: 3

1) A transient peak occurs when starting the motor while at rest or when disconnecting and reconnecting the motor during a transition. This transient lasts no more
than 1/2 cycle.
2) The starting current (locked rotor current) is the Root Mean Square current value the motor takes from the power source at start and fades while the motor is
accelerating to full speed. The larger the load on the motor, the slower the acceleration and the higher the current.
3) The transition current depends on the moment the transition occurs and the speed of the motor. A early transition will lead to increased current as the motor has
not reached full speed for the load and voltage. A late transition suggests that the motor will be running at reduced voltage when the load is almost the same as
full load. This causes the motor efficiency to drop and the temperature to rise in the motor stator windings. The motor can withstand this for a short period of
time but it is not recommended to run the motor with reduced voltage for more than 5 seconds.
4) Generally, the torque developed by the induction motor at any speed is approximately proportional to the square of the voltage and inversely proportional to the
square of the frequency. The locked rotor torque and breakdown torque are decreased when the voltage is unbalanced. If the voltage imbalance is severe, the
torque may be inadequate for the application.
5) Induction motors are inherently capable of developing transient current and torque considerably in excess of rated current and torque when exposed to an out
of phase bus transfer or momentary voltage interruption and re-closing on the same power supply. This transient torque can range from 2 to 20 times the rated
torque and is related to many factors including: motor design, operating conditions, switching time, rotating system inertias and torsional spring constants, the
number of motors on the bus and more.

This information is provided as a general information document. Consult an electrical engineer on your specific application.

3412 Apex Peakway


Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2021 Firetrol, Inc., All Rights Reserved.
Publication GS1930-10 Rev. C
Model Number FTA1000 - FTA1930
Selection Guide
MarkIII+ Electric Fire Pump Controllers

FTA1000, 1250, 1300, 1350, 1800, 1930


ELECTRIC FIRE PUMP CONTROLLERS
Example: FTA1300-AM75HH-xx

Starting Method
1000 - Across-the-line (direct on line)
1250 - Part Winding (50%-50% windings)
1300 - Wye-delta (star-delta), open transition Modifications
1350 - Wye-delta (star-delta), closed See Publication
transition OP1000-71
1800 - Autotransformer
1930 - Digital Solid-state soft start/stop

Start/Stop Options
A - Automatic/Manual start with manual
Three Phase Voltage
stop only (default). Field configurable
A - 220-240 Volt, 60 Hertz (230 V)
to automatic start with timed permis-
AZ - 220-230 Volt, 50 Hertz
sive stop after minimum run time and
B - 440-480 Volt, 60 Hertz (460 V)
manual start with manual stop only.
BZ - 415 Volt, 50 Hertz
C - For Manual only operation of Foam
C - 550-600 Volt, 60 Hertz (575 V)
Controllers (use option -LK3)
F - 380 Volt, 60 Hertz
FZ - 380 Volt, 50 Hertz
FF - 400 Volt, 60 Hertz
Short Circuit Current Rating FX - 400 Volt, 50 Hertz
H - 208 Volt, 60 Hertz
Code 200-208V 220-240V 380-415V 440-480V 550-600V HH - 200 Volt, 60 Hertz
5-150 HP 5-200 HP 5-350 HP 5-400 HP 5-500 HP
M - Standard 100kA 100kA 100kA 100kA N/A
N - Intermediate 150kA 150kA 150kA 150kA N/A
P - High 200kA 200kA 200kA 200kA N/A
Q - Intermediate N/A N/A N/A N/A 100kA Horsepower Rating
R - Standard N/A N/A N/A N/A 50kA 03 - 3 HP 100 - 100 HP
200-208V 220-240V 380-415V 440-480V 05 - 5 HP 125 - 125 HP
Code 200 HP 250-400 HP 400-500 HP 450-500 HP 07 - 7 1/2 HP 150 - 150 HP
M - Standard 50A 50kA 50kA 50kA 10 - 10 HP 200 - 200 HP
N - Intermediate N/A N/A N/A N/A 15 - 15 HP 250 - 250 HP
P - High 100kA 100kA 100kA 100kA 20 - 20 HP 300 - 300 HP
Q - Intermediate N/A N/A N/A N/A 25 - 25 HP 350 - 350 HP
R - Standard N/A N/A N/A N/A 30 - 30 HP 400 - 400 HP
For controller options and modifications see Publication 40 - 40 HP 450 - 450 HP
OP10000-71. 50 - 50 HP 500 - 500 HP
60 - 60 HP
75 - 75 HP

3412 Apex Peakway


Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2021 Firetrol, Inc., All Rights Reserved.
Publication SD1000-60 Rev.C
Options & FTA1000 - FTA1930
Modifications
MarkIII+ Electric Fire Pump Controllers
SPECIAL ENCLOSURES
Option Description
--- Enclosure, NEMA Type 2 (IEC IP22), Painted Steel (Standard)
-E Enclosure, NEMA Type 4 (IEC IP65), Painted Steel
-F Enclosure, NEMA Type 4X (IEC IP66), #304 Stainless Steel, Brushed Finish
-FD Enclosure, NEMA Type 4X (IEC IP66), #316 Stainless Steel, Brushed Finish
-FDB Enclosure, NEMA Type 4X (IEC IP66), #316 Stainless Steel, Seam Welded, Brushed Finish
-FDP Enclosure, NEMA Type 4X (IEC IP66), #316 Stainless Steel, Painted Finish
-FXP Enclosure, NEMA Type 4X (IEC IP66), #304 Stainless Steel, Painted Finish
-G Enclosure, NEMA Type 12 (IEC IP54), Painted Steel
-T Enclosure, NEMA Type 3R (IEC IP24), Painted Steel
-U Enclosure, NEMA Type 3 (IEC IP54), Painted Steel

CIRCUIT BREAKER OPTION*


Option Description
Standard Short Circuit Current Rating
-M 200-208V 220-240V 380-415V 440-480V 550-600V 200-208V 220-240V 380-415V 440-480V
-R 5-150 HP 5-200 HP 5-350 HP 5-400 HP 5-500 HP 200 HP 250-400 HP 400-500 HP 450-500 HP
100kA (M) 100kA (M) 100kA (M) 100kA (M) 50kA (R) 50kA (M) 50kA (M) 50kA (M) 50kA (M)
Intermediate Short Circuit Current Rating
-N 200-208V 220-240V 380-415V 440-480V 550-600V 200-208V 220-240V 380-415V 440-480V
-Q 5-150 HP 5-200 HP 5-350 HP 5-400 HP 5-500 HP 200 HP 250-400 HP 400-500 HP 450-500 HP
150kA (N) 150kA (N) 150kA (N) 150kA (N) 100kA (Q) N/A N/A N/A N/A
High Short Circuit Current Rating
-P 200-208V 220-240V 380-415V 440-480V 550-600V 200-208V 220-240V 380-415V 440-480V
5-150 HP 5-200 HP 5-350 HP 5-400 HP 5-500 HP 200 HP 250-400 HP 400-500 HP 450-500 HP
200kA 200kA 200kA 200kA NA 100kA 100kA 100kA 100kA

ANTI-CONDENSATION SPACE HEATERS


Option Description
None
-J Space Heater, 120V Externally Powered with Circuit Breaker & Thermostat
-K Space Heater, 120V Externally Powered with Circuit Breaker & Humidistat
-M Space Heater, 240V Externally Powered with Circuit Breaker & Thermostat
-N Space Heater, 240V Externally Powered with Circuit Breaker & Humidistat
-JKP Space Heater, 120V Externally Powered with Circuit Breaker, Thermostat
and Humidistat in Parallel
-MNP Space Heater, 240V Externally Powered with Circuit Breaker, Thermostat
and Humidistat in Parallel

PRESSURE TRANSDUCERS, SOLENOID VALVES, PLUMBING


Option Description
--- Wetted Parts including Pressure Sensor and Test Solenoid, 300 PSI (20.4 Bar) Fresh Water
-B1 Wetted Parts including Pressure Sensor and Test Solenoid, 500 PSI (34.5 Bar)
Fresh Water (For Factory Calibration Purposes Only)
-C1 Wetted Parts including Pressure Sensor and Test Solenoid, 300 PSI (20.4 Bar), Sea Water
-D1 Wetted Parts including Pressure Sensor and Test Solenoid, 500 PSI (34.5 Bar), Sea Water
-SP1 Low Suction Pressure Transducer, Fresh Water, 0-300 PSI (20.4 Bar) with Visible Indication
and Output Contacts
-SP2 Low Suction Pressure Transducer, Sea Water, 0-300 PSI (20.4 Bar) with Visible Indication
and Output Contacts
FOAM PUMP APPLICATIONS
Option Description
Required For Foam
-LR1 Low Foam Level External Input, Visible Indications and Alarm Contacts, Additive with
Provisions for Proof Pressure Switch Connection, With Lockout and Remote Alarm Indication
For Interlock On (Locked Out)
Required For Foam
-LK1 Foam Pump Application With Pressure Transducer and Run Test Solenoid Valve (Auto. Start)
-LK2 Foam Pump Application With Pressure Transducer and Run Test Solenoid Valve, Stainless Steel (Auto. Start)
-LK3 Foam Pump Application Without Pressure Transducer and Run Test Solenoid Valve (Manual Start)
Optional For Foam
-DVC Operation, Dump Valve Control

ALARMS
Option Description
-AC Extra Alarm Output Contacts, Pump Operating (2 Form-C)
-AM Alarm Output Contacts, Fail to Start
-AV Alarm Output Contacts, Low Pump Room Temperature
-AW Alarm Output Contacts, Reservoir Low
-AY1 Configurable Low Suction Pressure, Visible/Output Contacts with External Digital Input
-BW1 Extra Alarm Output Contacts, Phase Failure/Phase Reversal
-BY1 Alarm Output Contacts, Overcurrent
-CTS1 Configurable Low Suction Pressure, Visible/Output Contacts with Suction Pressure Transducer
-EH1 Alarm Output Contacts, Main Relief Valve Open
-EK Alarm Output Contacts, Flow Meter Open
-JR Visible Indicator, Jockey Pump Operating
-JT Alarm, Audible/Visible, Jockey Pump Trouble
-KH Alarm Output Contacts, Common Alarm
-P1 Alarm, Audible/Visible, Built-In 120V Supervisory System (Includes Visible Supervisory Voltage
Normal Indication and Audible Pump Operating, Phase Failure and Phase Reversal Indication
-PE Alarm Output Contacts, Low System Pressure (Pump on Demand)
-PT Alarm, Audible/Visible, Built-In 240V Supervisory System (Includes Visible Supervisory Voltage
Normal Indication and Audible Pump Operating, Phase Failure and Phase Reversal Indication

MISCELLANEOUS
Option Description
-ED2 Normal Source Load Shedding with Adjustable Time Delay to Remove Non-Critical
Loads Before Starting
-EL Series Pumping Operation, High Zone Controller
-EM Series Pumping Operation, Mid Zone Controller
-EN Series Pumping Operation, Low Zone Controller
-IEC Marking, CE with External Wet Parts (Requires NEMA Type 12 (IP54) Enclosure as Minimum)
-MZN Neutral Lug, Service Entrance, Non-Insulated Bonded to Enclosure
-OSP Seismic Certification compliant to OSHPD (CA) for rigid base or wall mount only
-PK Terminal Blocks, Extra Remote Start
-PY Output Contacts, Motor Space Heater, Externally Powered
-S Tropicalization
-SEI Seismic Certification compliant to CBC 2019, IBC 2018 for rigid base or wall mount only
-USBX Data Port, External USB
-Y55 Controller Temperature Rating, 55°C (131°F) Ambient Temperature
-ZPM1 Data Port, RS-485 Modbus RTU
-XCR Export Packaging (Wooden Crating to Conform to IPPC Standards)

3412 Apex Peakway


Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2022 Firetrol, Inc., All Rights Reserved.
Publication OP1000-71 Rev. J
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: FTA1350/FTA1800/FTA1930


BUILT TO THE LATEST EDITION OF THE NFPA20 & NFPA70
A
DRAWN BY ACD 07/02/24 ELECTRIC FIRE PUMP CONTROLLER DRAWING NUMBER
CDL
A
© Firetrol, Inc. Not for construction.
NYC
Dpt of Building
THIRD ANGLE DD1000-821 /E
FINAL Approved
PROJECTION DWG REV. 1
Subject to change without notice. FC 07/02/24
APPROVAL SHEET 1 OF 1

33 1/4" [846]

B 1/2" [12] 19" [483] 30" [762] B

28 1/2" [724]
14" [356]
Ø7/8" [Ø23] X2
Ø3/8" [Ø10] X4

C C

See Notes

D D

55 1/8" [1400]

54" [1372]
51 7/8" [1318]
E E

Voltage / Power Table

Voltage Min HP Max HP 27" [685]


F F
21 1/4" [541]
208 40 60 27 5/8" [702]

220 - 240 40 75
1" [25] Adjustable Feet

380 - 400 - 415 75 125

G 440 - 480 75 150 G

600 100 200


Sensing Line Connection - 1/2 " F.NPT
34" [864]
32" [813]

Drain - 3/8 " M.TUBE Ø1/2" [Ø13] X4 7" [178]


1" [25]

H H
Notes:
- Standard NEMA: NEMA 2 9 1/8" [233]
Normal Power
- Standard paint : textured red RAL 3002. 7" [178] and Motor
12" [305]
- All dimensions are in inches [millimeters]. Leads
Entrance
- Center of screen: 47-5/8" [1208] from bottom.
- Bottom conduit entrance through removable gland plate recommended.
I - Use watertight conduit and connector only. I
- Protect equipment against drilling chips. 1 1/4" [31] 3 1/2" [89] 4" [102]
- Door swing equal to door width. 1" [25]

0 1 2 3 4 5 6 7 8
Copyright © 2024 Firetrol Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Firetrol Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Firetrol Inc.
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: FTA1930


DRAWN BY ACD 28/02/23
ELECTRIC FIRE PUMP CONTROLLER BUILT TO THE LATEST EDITION OF THE NFPA20 & NFPA70
CDL
A DRAWING NUMBER A
REDUCED VOLTAGE / SOFT STARTER NYC WS19308
-00 /E
© Firetrol, Inc. Not for construction. FINAL
Dpt of Building
Approved DWG REV. 0
Subject to change without notice. FC 28/02/23
APPROVAL SHEET 1 OF 2

IS1
1L3
B 1L2 B
1L1

To I/O
Electric Board
4
To J45 MMB1 UP
CB1 ST1 (P.2 / F4) (P.2 / E2)
C 2 C

I/O

D J14 J8 J5 D

COM

COM

COM

COM
3L1

DI0

DI1

DI2

DI3
3L2 -

+
3L3
To
J2/J3/J4 (P.2/F8) (D1)
3L1 3L2

1M
E E
H1 H2

3L3
XTR4
3L2
3L1 44 X2 X1
230

17
F CR5 F
50 47
49 (P.2/H2)
46
CR4
CR5
3L1 (P.2/E8)
48
CT3 68 Black
69 White
G G
CT2 66 Black
CL1 LI1 LI2 +24V CL2
67 White To J76 (P.2/F6)

CT1 64 Black
65 White Legend
R1B 1M Contactor
AB Alarm Bell
R1C RUN / TRIP
CB Circuit Breaker
H NO (Programmable)
CR Control Relay
H
R1A
CT Current Transformer
EB Electric I/O Board
195 NC IS Isolating Switch
1M** SSS1 (P.2/H7) 198
R2B
J Jumper
R2C OVERLOAD / FAILURE LS Limit Switch
NO (Fail Safe) PT Pressure Transducer
R2A SA Surge Arrester

I ATS22....6S SSS
ST
Soft Starter
Shunt Trip I
T1 T2 T3 SV Solenoid Valve

M
MMB Main Board
XTR Transformer

0 1 2 3 4 5 6 7 8
Copyright © 2023 Firetrol Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Firetrol Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Firetrol Inc.
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: FTA1930


DRAWN BY ACD 28/02/23
ELECTRIC FIRE PUMP CONTROLLER BUILT TO THE LATEST EDITION OF THE NFPA20 & NFPA70
CDL
A DRAWING NUMBER A
REDUCED VOLTAGE / SOFT STARTER NYC WS19308
-00 /E
© Firetrol, Inc. Not for construction. FINAL
Dpt of Building
Approved DWG REV. 0
Subject to change without notice. FC 28/02/23
APPROVAL SHEET 2 OF 2

B B

C C

SV1
XTR1
1
LS1** LS1-1 X1 H2

Brown
D LS1-2 24VAC D
3L2

Blue
X2 H1
3 3L1
Sensing Line
Connection To
3L1-2-3
PT1 To ST1
To
(P.1 / D1)

E
(P.1 / C8)
(P.1 / C1)
CR4 CR5 CT1-2-3
(P.1 / G2)
To E
To 3L1 CR4
MMB1 (P.1 / G2)

CR4-1
CR4-2

CR5-1
CR5-2
SV1-1
SV1-2
I/O
White
Black

3L3

3L2
3L2

3L1
3L1
Red

4
2

1
3

67
69
68

66
65
64
7 5 3 1

24V OUT

24VAC
24V IN
UP DOWN 8 6 4 2 2 1 2 1 2 1
F F
LS1
AI4

AI3

AI2

AI1

NO

NO
NC

NC
AB

SV

ST
L3 L2 L1

C
IGF I3 I2 I1
+

+
-

J76 J53 J4 J3 J2
J14 J15 J16 J17 J54 J46 J43 J45 J44 J47 J36 J38
CR4 CR5

I/O Electric Board EB1


G J40 J42 J37 J39 J41 J55 G
TB1 TB2 TB3 TB4 TB5 TB6
J25
NO

NO

NO

NO

NO

NO
NC

NC

NC

NC

NC

NC

2 2 2 2 2 2
C

C
NO

NO

NO

NO

NO

NO
NC

NC

NC

NC

NC

NC

1 1 1 1 1 1
C

IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8

H H
47
46

195
198
J1* J2*
ve e

m
n

le
ble

Re Phas
l
Ru

rsa

ub

e
al

l
to
t
Ala

ve
ou
ila

(P.1/F5)
alv
nu

Au

(P.1/H3)
Tro

Le
tor

ck
va

eV
Ma
r

om

te
Lo
we

ter
Mo

rA

mo

lug
tor

ote

Wa
Ro
Po
we

Re

De
Mo

w
Re
mp
al
Po

Lo
rm

Pu
No

I I

* Remove jumper to use this feature


** Contact closes when emergency start is in "ON" position
0 1 2 3 4 5 6 7 8
Copyright © 2023 Firetrol Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Firetrol Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Firetrol Inc.
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: FTA1000


BUILT TO THE LATEST EDITION OF THE NFPA20 & NFPA70
A
DRAWN BY ACD 28/02/23 ELECTRIC FIRE PUMP CONTROLLER DRAWING NUMBER
CDL
A
© Firetrol, Inc. Not for construction.
NYC
Dpt of Building
FC10008
-00 /E
FINAL Approved DWG REV. 0
Subject to change without notice. FC 28/02/23
APPROVAL SHEET 1 OF 1

COPPER CONDUCTORS for Isolating Switch (IS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
B
Bending
5 " (127 mm) 8 " (203 mm)
Power Terminals B
Space
3 Phases
HP 5 7.5 10 15 20 25 30 40 50 60 Bonding Incoming Power
Voltage
Ground
208 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 3/0) 1x (3/0 to 250) 1x (4/0 to 250)

220 to 240 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250)
L1 L2 L3
380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0) IS1
C C
440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0)

Bending
Space 12 " (305 mm) 16 " (406 mm)

HP 75 100 125 150 200 250 300 350 400 450 500
Voltage
D D
208 2x (1/0 to 500) 2x (2/0 to 500) 2x (4/0 to 500) 2x (250 to 500) 3x (4/0 to 500) -------- -------- -------- -------- -------- --------

220 to 240 1x (250) 2x (2/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (350 to 500) 3x (250 to 500) -------- -------- -------- -------- --------

380 to 416 1x (1/0 to 3/0) 1x (3/0 to 250) 1x (250) 2x (1/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (400 to 500) 3x (250 to 500) 3x (300 to 500) --------

440 to 480 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250) 1x (4/0 to 250) 2x (1/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 3x (250 to 500)

E 600 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250) 1x (250) 2x (2/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (350 to 500) E
Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

ALUMINUM CONDUCTORS for Isolating Switch (IS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
Bending
Space 5 " (127 mm) 8 " (203 mm) 10 " (254 mm)
F F
HP 5 7.5 10 15 20 25 30 40 50 60
Voltage
1x (300) ** or
208 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 1/0) 1x (1/0) 1x (3/0) 1x (4/0 to 250)
1x (250) 90°C *
220 to 240 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (1/0)

G 440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) G

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0)

Bending
Space 12 " (305 mm) 16 " (406 mm)

HP 75 100 125 150 200 250 300 350 400 450 500
Voltage

H 208 2x (2/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 3x (300 to 500) -------- -------- -------- -------- -------- -------- H
1x (350) ** Notes:
220 to 240 2x (3/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (500) 3x (400 to 500) -------- -------- -------- -------- --------
N/A 1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada)
1x (350) ** 3x (300 to 500)**
380 to 416 1x (3/0) 1x (250 to 350) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (500)
2x (500) 90°C *
3x (350 to 500) 3x (400 to 500) -------- or local code.
N/A
1x (300 to 350)** 2 - Controller suitable for service entrance in USA.
440 to 480 1x (1/0 to 3/0) 1x (3/0) 1x (250) 2x (3/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (400 to 500) 2x (500) 2x (500) 90°C * 3x (350 to 500)
1x (250) 90°C * 3 - For more accurate motor connections refer to motor manufacturer or
600 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (4/0 to 250) 1x (350 to 500) 2x (3/0 to 500) 2x (4/0 to 250) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 2x (500) motor nameplate.
I
4 - Controller is phase sensitive. Incoming lines must be connected in ABC I
Bending sequence.
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

Drawing for information only.


* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C. Manufacturer reserves the right to modify this drawing without notice.
** Consult Factory Contact manufacturer for "As Built" drawing.

0 1 2 3 4 5 6 7 8
Copyright © 2023 Firetrol Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Firetrol Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Firetrol Inc.
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: FTA1000/FTA1800/FTA1930


BUILT TO THE LATEST EDITION OF THE NFPA20 & NFPA70
A
DRAWN BY ACD 28/02/23 ELECTRIC FIRE PUMP CONTROLLER DRAWING NUMBER
CDL
A
© Firetrol, Inc. Not for construction.
NYC
Dpt of Building
FC10008
-01 /E
FINAL Approved DWG REV. 0
Subject to change without notice. FC 28/02/23
APPROVAL SHEET 1 OF 1

COPPER CONDUCTORS for Motor Connection (1M).


Field Wiring According to Bending Space (AWG or MCM). Terminals T1 - T2 - T3
HP
B 5 7.5 10 15 20 25 30 40 50 60 B
Voltage
208 1x (10 to 2) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (4 to 2) 1x (3 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (3/0) 1x (4/0 to 300) Motor Terminals
220 to 240 1x (10 to 2) 1x (10 to 2) 1x (8 to 2) 1x (6 to 2) 1x (4 to 2) 1x (4 to 2/0) 1x (3 to 2/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (3/0)

380 to 416 1x (10 to 2) 1x (10 to 2) 1x (10 to 2) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 1/0) 1x (4 to 2) 1x (3 to 2/0) 1x (1 to 2/0) 1M


T1 T2 T3
440 to 480 1x (10 to 2) 1x (10 to 2) 1x (10 to 2) 1x (10 to 2) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2) 1x (4 to 2/0) 1x (3 to 2/0)
C C
600 1x (10 to 2) 1x (10 to 2) 1x (10 to 2) 1x (10 to 2) 1x (10 to 2) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2) 1x (4 to 2/0)

HP M
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 1x (300) 2x (2/0 to 300) 2x (4/0 to 300) 2x (250 to 300) 2x (400 to 600) -------- -------- -------- -------- -------- -------- Models:FTA1000/FTA1800/FTA1930

220 to 240 1x (250 to 300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (350 to 500) 2x (500 to 600) -------- -------- -------- -------- --------
D D
380 to 416 1x (1/0 to 3/0) 1x (3/0) 1x (250 to 300) 1x (300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (300) 2x (400 to 500) 2x (500 to 600) 2x (600)

440 to 480 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 1x (4/0 to 300) 2x (1/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (300) 2x (350 to 500) 2x (400 to 600) 2x (500 to 600)

600 1x (3 to 1/0) 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 1x (250 to 300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (250 to 300) 2x (300) 2x (350 to 500)

E E

ALUMINUM CONDUCTORS for Contactor (1M).


Field Wiring According to Bending Space (AWG or MCM). Terminals T1 - T2 - T3
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
208 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 2/0) ** 1x (1 to 2/0) ** 1x (1/0 to 2/0) ** 1x (2/0) 90°C * Consult Factory 1x (300)

F 220 to 240 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (4 to 2/0) ** 1x (3 to 2/0) ** 1x (2 to 2/0) ** 1x (1 to 2/0) ** 1x (2/0) 1x (3/0) 90°C * Consult Factory F

380 to 416 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 2/0) ** 1x (1 to1/0) 1x (1/0)

440 to 480 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 1/0) 1x (1 to 1/0)

600 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (4 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 1/0)

HP
G 75 100 125 150 200 250 300 350 400 450 500 G
Voltage
208 1x (300) 90°C * 2x (4/0 to 300) 2x (300) 2x (300) 90°C * 2x (600) -------- -------- -------- -------- -------- --------

220 to 240 1x (300) 90°C * 2x (3/0 to 300) 2x (250 to 300) 2x (300) 2x (500) 2x (600) -------- -------- -------- -------- --------

380 to 416 1x (3/0) Consult Factory 1x (300) 90°C * Consult Factory 2x (4/0 to 300) 2x (300) Consult Factory 2x (600) 2x (600) 90°C * 2x (600) 90°C * --------

440 to 480 1x (1/0) 1x (3/0) Consult Factory 1x (300) 2x (3/0 to 300) 2x (250 to 300) 2x (300) 2x (300) 90°C * 2x (500) 2x (600) 2x (600) 90°C *
H H
600 1x (1 to 1/0) Consult Factory 1x (3/0) 90°C * Consult Factory 1x (300) 90°C * 2x (3/0 to 300) 2x (4/0 to 300) 2x (300) 2x (300) 90°C * 2x (300) 90°C * Consult Factory
Notes:
1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada)
* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C.
or local code.
** Option V659 required.
2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or
motor nameplate.
I
4 - Controller is phase sensitive. Incoming lines must be connected in ABC I
sequence.

Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

0 1 2 3 4 5 6 7 8
Copyright © 2023 Firetrol Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Firetrol Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Firetrol Inc.
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: FTA1000


BUILT TO THE LATEST EDITION OF THE NFPA20 & NFPA70
A
DRAWN BY ACD 28/02/23 ELECTRIC FIRE PUMP CONTROLLER DRAWING NUMBER
CDL
A
© Firetrol, Inc. Not for construction.
NYC
Dpt of Building
FC10008
-03 /E
FINAL Approved DWG REV. 0
Subject to change without notice. FC 28/02/23
APPROVAL SHEET 1 OF 1

Field Connections Alarm Contacts


Terminals Wire Size: Terminals Wire Size:
B 24 - 12 AWG 24 - 12 AWG B
0.5 Nm 0.5 Nm
I/O Electric Board
I/O Electric Board
Normally Opened

IN 1
Remote Manual NO
Closes to alarm
Normally Closed C
Opens to alarm

IN 2
Lockout NC
Motor Run TB1
Normally Opened NO
C C

Controller Terminal Strip


Closes to alarm

IN 3
Remote Auto J1* Normally Closed C
Opens to alarm NC
Deluge Valve

IN 4
J2*
J25 Normally Opened
Closes to alarm NO

IN 5
Low Water Level Normally Closed C
Opens to alarm NC
IN 6 Power Available TB2
Normally Opened NO
Closes to alarm
D Normally Closed C D
IN 7

Opens to alarm NC

Normally Opened
IN 8

Closes to alarm NO
Normally Closed C

Network Connections
Opens to alarm NC
Normal Power TB3
Phase Reversal Normally Opened NO
Closes to alarm
Terminals Wire Size: Normally Closed C
E Shielded Female Connector RJ45 Opens to alarm NC
E

Located on Main Board Normally Opened


Closes to alarm NO

Modbus TCP/IP RJ45 Normally Closed


Opens to alarm
C
NC
Pump Room Alarm** TB4
Normally Opened NO
Closes to alarm
Normally Closed C
Opens to alarm NC
F F
Normally Opened
Closes to alarm NO
Normally Closed C
Opens to alarm NC
Motor Trouble** TB5
Normally Opened NO
Closes to alarm
Normally Closed C
Opens to alarm NC
G G
Normally Opened
NO
Closes to alarm
Normally Closed C
Opens to alarm NC
(Field
Programmable***) TB6
Normally Opened NO
Closes to alarm
Normally Closed C
Opens to alarm NC

H H

I I

* Remove jumper to use this feature


** Re-assignable
*** Not available on Model FTA1930

0 1 2 3 4 5 6 7 8
Copyright © 2023 Firetrol Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Firetrol Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Firetrol Inc.