1MRK504166-BEN_en_T_Product Guide, Transformer Protection RET670 Version 2.2
1MRK504166-BEN_en_T_Product Guide, Transformer Protection RET670 Version 2.2
The software and hardware described in this document is furnished under a license and may be used or disclosed
only in accordance with the terms of such license.
This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit (https://
www.openssl.org/). This product includes cryptographic software written/developed by: Eric Young
([email protected]) and Tim Hudson ([email protected]).
Trademarks
ABB is a registered trademark of ABB Asea Brown Boveri Ltd. Manufactured by/for a Hitachi Energy company. All
other brand or product names mentioned in this document may be trademarks or registered trademarks of their
respective holders.
Warranty
Please inquire about the terms of warranty from your nearest Hitachi Energy representative.
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product description and are
not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment
addressed in this manual must satisfy themselves that each intended application is suitable and acceptable,
including that any applicable safety or other operational requirements are complied with. In particular, any risks in
applications where a system failure and/or product failure would create a risk for harm to property or persons
(including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying
the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or
mitigate such risks.
This document has been carefully checked by Hitachi Energy, but deviations cannot be completely ruled out. In case
any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit
contractual commitments, in no event shall Hitachi Energy be responsible or liable for any loss or damage resulting
from the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities on the approximation of the
laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the
result of tests conducted by Hitachi Energy in accordance with the product standard EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is
designed in accordance with the international standards of the IEC 60255 series.
Transformer protection RET670 1MRK504166-BEN T
Version 2.2
Contents
5
Transformer protection RET670 1MRK504166-BEN T
Version 2.2 Issued: June 2023
Revision: T
B 2017-10 2.2.1 Ethernet ports with RJ45 connector added. enhancements/updates made to
ZMFPDIS and ZMFCPDIS.
E 2018-07 2.2.2 LDCM galvanic X.21 added. Function PTRSTHR added. Ordering section
updated.
F 2018-11 2.2.2 Technical data updated for PSM, EF4PTOC and T2WPDIF/T3WPDIF.
Corrections/enhancements made to OC4PTOC, TRPTTR, UV2PTUV and
OV2PTOV. Case dimensions updated.
Q 2021-06 2.2.5 Added note to Disturbance report and IEC 60870-5-103 protocol
R 2022-07 2.2.5.4 Introduced RIA600, which is a software implementation of the IED LHMI
panel.
T 2023-06 2.2.6 SNMP support, support for 12 MUs, IEC 61850 Ed2.1, new variants of single
mode SFP added. Functions C1RADR, C2RADR, C3RADR, GOOSEACRCV,
SNMPSERVERCONF, and SNMPUSERCONF added. Functions LDRGFC,
INTERRSIG, SETGRPS, TERMINALID, ZMFPDIS, ZMFCPDIS, PPLPHIZ,
PPL2PHIZ, PSPPPAM, OC4PTOC, EF4PTOC, NS4PTOC, LCPTTR,
LFPTTR, BRCPTOC, VRPVOC, APPTEF, OEXPVPH, VDCPTDV,
SCCFPVOC, SCUCPTOC, SCPDPTDV, SCUVPTOV, CVGAPC, SCSWI,
SXSWI, TCMYLTC, TCLYLTC, VSGAPC, SMPPTRC, BTIGAPC, IB16,
ITBGAPC, CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU,
SSCBR, SPGAPC, SP16GAPC, IEC61850-8-1, LD0LLN0, GOOSEACRCV,
AP_1, AP_FRONT, FLTMMXU, LDCMTRN, and MVGAPC updated. Ordering
section updated.
2. New features
GUID-B3343A2F-393A-4DDF-972B-30F6E619FB43 v1
The following are the new features added/updated in the
current release:
• SNMP support added
• Three new variants of single mode SFP added
• Support for IEC 61850 Ed2.1
• Support for 12 merging units
• Improvements to high speed line distance protection
• Improvements related to apparatus control functions
• Enhancements and corrections
M11788-3 v11
Communication via optical connections ensures immunity template in the graphical configuration tool. An alternative
against disturbances. for Autotransformers is also available as a configuration
SEMOD51222-5 v9 template. Analog and tripping IO has been pre-defined for
Four packages have been defined for the following basic use on the, as standard supplied one binary input
applications: module and one binary output module. Add binary I/O as
required for your application at ordering. Other signals need
• Back-up (A10)
to be applied as required for each application.
• Voltage and tap changer controll (A25)
• Single/Multi breaker, 2 winding differential (B30) For details on included basic functions, refer to chapter
• Multi breaker, 3 winding differential (B40) "Basic IED functions"
Optional functions are not configured but a maximum
configuration with all optional functions are available as
*)
WA1 WA2
RET670 B30 - 2-winding transformer in single / multiple circuit breaker assembly 12AI
(24AI) (9I + 3U, (9I + 3U))
W1_QA2
W1_CT1 Control
Control
50BF 3I> BF 52PD PD 3 Control
CC RBRF CC PDSC SSSSCBR
SCBR
SCBR
87N IdN/I
87T 3Id/I>
REF PDIF
T2W PDIF
W2_NCT
51N 4(IN>)
W2
EF4 PTOC 3 Control
Control
Control MET Isqi
SSSSCBR
SCBR
SCBR C MSQI
87N IdN/I
REF PDIF
W2_CT
50BF 3I> BF 52PD PD 51 4(3I>) 49 θ> MET I
CC RBRF CC PDSC OC4 PTOC TR PTTR C MMXU
W2_VT
MET Usqi MET U 51N_67N 4(IN>) U>/I< MET P/Q
V MSQI V MMXU EF4 PTOC FUF SPVC CV MMXN
*)
S CSWI S XSWI TR8 ATCC VD SPVC VHM MHAI VR PVOC ZCLC PSCH
SDE PSDE STB PTOC
* ) Optional component if a multiple circuit breaker assembly is required. An additional TRM (9I + 3U) is required.
IEC05000849-8-en.vsdx
IEC05000849 V9 EN-US
WA1 WA2
RET670 B40 - 3 winding transformer in multi breaker arrangement 24AI
(9I+3U, 9I+3U)
W1_QA2
W1_CT1
50BF 3I> BF 52PD PD 3 Control
Control
Control
CC RBRF CC PDSC SSSSCBR
SCBR
SCBR
W2 T3W PDIF
W2_NCT 3 Control
Control
Control MET Isqi
87N IdN/I
REF PDIF SSSSCBR
SCBR
SCBR C MSQI
3 Control 67N IN> 50STB 3I>STB 3 Control 90 ↑↓ 60 Ud> VTHD UTHD 51V 2(I>/U<) 85
S CSWI SDE PSDE STB PTOC S XSWI TR8 ATCC VD SPVC VHM MHAI VR PVOC ZCLC PSCH
IEC05000851-8-en.vsdx
IEC05000851 V9 EN-US
WA1
WA2
W1_QA1 63 71
S SIMG S SIML
W1_CT
50BF 3I>BF 52PD PD 51 4(3I>) 50 3I>> 50N IN>>
CC RBRF CC PDSC OC4 PTOC PH PIOC EF PIOC
3 Control
Control
Control MET I MET Isqi 51N 4(IN>)
SSSSCBR
SCBR
SCBR C MMXU C MSQI EF4 PTOC
W1
W3
W2
W2_QA1
WA1
46 Iub> 50 3I> MET P/Q 71 DELTAI 7V_78V DELTAU 7 DELTA MET W/Varh U>/I<
BRC PTOC BR PTOC CV MMXN DELI SPVC DELV SPVC DEL SPVC ETP MMTR FLT MMXU FUF SPVC
87 Id> 27 3U< 3 Control 87N IdN/I 67N IN> 87V Ud> MET U MET UN
HZ PDIF LOV PTUV Q CBAY REF PDIF SDE PSDE VDC PTDV V MMXU V MSQI
Optional Functions
67NT IO> → TEF ITHD ITHD 32 P> 37 P< 26/49HS 3Ihp>T 46I2 4(I2>) 24 U/f> 59 2(3U>)
AP PTEF CHM MHAI GOP PDOP GUP PDUP LOL SPTR NS4 PTOC OEX PVPH OV2 PTOV PMU REP
51TF 59N 2(U0>) 81 df/dt<> 81 f> 81 f< 50STB 3I>STB 27 2(3U<) VTHD UTHD 60 Ud>
PTR STHR ROV2 PTOV SA PFRC SA PTOF SA PTUF STB PTOC UV2 PTUV VHM MHAI VD SPVC
51V 2(I>/U<)
VR PVOC
IEC07000191-8-en.vsdx
IEC07000191 V9 EN-US
84 ↑↓ DFR/SER DR 84 ↑↓
TCM YLTC DRP RDRE TCM YLTC
W1 MET UN MET U W1
VN MMXU V MMXU
TRF1 TRF2
W2 W2
MET U MET UN
V MMXU VN MMXU
TRF1_W2_VT
MET I MET Isqi MET P/Q 90 ↑↓
C MMXU C MSQI CV MMXN TR8 ATCC
TRF1_W2_CT
TRF2_W2_VT
90 ↑↓ MET P/Q MET Isqi MET I
TR8 ATCC CV MMXN C MSQI C MMXU
TRF2_W2_CT
TRF1_W2_QA1 TRF2_W2_QA1
QA11
BRC PTOC CCS SPVC DELI SPVC DEL SPVC DELV SPVC ETP MMTR FLT MMXU LOV PTUV Q CBAY
Optional Functions
ITHD ITHD 50N IN>> 51N_67N 4(IN>) 46I2 4(I2>) 51_67 4(3I>) 59 2(3U>) 50 3I>>
50 3I>
EF PIOC NS4 PTOC OC4 PTOC OV2 PTOV PH PIOC PMU REP
BR PTOC CHM MHAI EF4 PTOC
51TF 3 Control 59N 2(U0>) 3 Control 3 Control 67N IN> 3 Control 27 2(3U<) 60 Ud>
PTR STHR Q CRSV ROV2 PTOV S CILO S CSWI SDE PSDE S XSWI UV2 PTUV VD SPVC
VTHD UTHD
VHM MHAI
IEC07000192-5-en.vsdx
IEC07000192 V8 EN-US
4. Available functions
GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v2
IEC 61850 or
ANSI Function description Transformer
function name
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Differential protection
Impedance protection
IEC 61850 or
ANSI Function description Transformer
function name
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
IEC 61850 or
ANSI Function description Transformer
function name
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Current protection
NS4PTOC 46I2 Directional negative phase 0-8 2-C42 2-C42 3-C43 2-C19
sequence overcurrent
protection, four steps
IEC 61850 or
ANSI Function description Transformer
function name
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Voltage protection
Unbalance protection
Frequency protection
Multipurpose protection
General calculation
1) 67 requires voltage
2) 67N requires voltage
IEC 61850 or
ANSI Function description Transformer
function name
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Control
SMBRREC 79 Autorecloser 1
IEC 61850 or
ANSI Function description Transformer
function name
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Logic
AND, GATE, INV, Basic configurable logic 40-420 40-420 40-420 40-420 40-420
LLD, OR, blocks (see Table 3)
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR
IEC 61850 or
ANSI Function description Transformer
function name
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
IEC 61850 or
ANSI Function description Transformer
function name
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Monitoring
IEC 61850 or
ANSI Function description Transformer
function name
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
PTRSTHR 51TF Through fault monitoring 0-2 2-M22 2-M22 2-M22 2-M22
IEC 61850 or
ANSI Function description Transformer
function name
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Metering
AND 280
GATE 40
INV 420
LLD 40
OR 298
PULSETIMER 40
RSMEMORY 40
SRMEMORY 40
TIMERSET 60
XOR 40
SCILO Interlocking 30
BB_ES 6
A1A2_BS 4
A1A2_DC 6
ABC_BC 2
BH_CONN 2
BH_LINE_A 2
BH_LINE_B 2
DB_BUS_A 3
DB_BUS_B 3
DB_LINE 3
ABC_LINE 6
AB_TRAFO 4
RESIN2 59
ANDQT 120
INDCOMBSPQT 20
INDEXTSPQT 20
INVALIDQT 22
INVERTERQT 120
ORQT 120
PULSETIMERQT 40
RSMEMORYQT 40
SRMEMORYQT 40
TIMERSETQT 40
XORQT 40
AND 220
GATE 49
INV 220
LLD 49
OR 220
PULSETIMER 89
RSMEMORY 40
SLGAPC 74
SRMEMORY 130
TIMERSET 113
VSGAPC 120
XOR 89
Communication GUID-C1FB7B84-2F43-4F15-9264-F33832C8036B v2
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
Station communication
RS485GEN RS485 1 1 1 1 1
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
RSTP IEC 62439-3 Rapid spanning 0-1 1-P25 1-P25 1-P25 1-P25
tree protocol
SNMPSERVERCONF SNMPServerConfiguration 1 1 1 1 1
SNMPUSERCONF SNMPUserConfiguration 2 2 2 2 2
AP_1-AP_6 AccessPoint_ABS 1 1 1 1 1
ROUTE_1-ROUTE_6 Route_ABS1-Route_ABS6 1 1 1 1 1
Remote communication
BinSignRec1_1 Binary signal transfer, receive 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6
BinSignRec1_2
BinSignReceive2
RET670 (A10)
RET670 (B30)
RET670 (B40)
RET670 (A25)
RET670
(Customized)
LDCMRecBinStat1 Receive binary status from 6/3 6/3 6/3 6/3 6/3
LDCMRecBinStat3 remote LDCM
Scheme communication
PMUCONF Configuration parameters for IEC/IEEE 60255-118 (C37.118) 2011 and IEEE1344 1
protocol
PMUREPORT Protocol reporting via IEEE 1344 and IEC/IEEE 60255-118 (C37.118) 1
PHASORREPORT1 Protocol reporting of phasor data via IEEE 1344 and IEC/IEEE 60255-118 1
(C37.118), phasors 1-8
PHASORREPORT2 Protocol reporting of phasor data via IEEE 1344 and IEC/IEEE 60255-118 1
(C37.118), phasors 9-16
PHASORREPORT3 Protocol reporting of phasor data via IEEE 1344 and IEC/IEEE 60255-118 1
(C37.118), phasors 17-24
ANALOGREPORT1 Protocol reporting of analog data via IEEE 1344 and IEC/IEEE 60255-118 1
(C37.118), analogs 1-8
BINARYREPORT1 Protocol reporting of binary data via IEEE 1344 and IEC/IEEE 60255-118 1
(C37.118), binary 1-8
PMUSTATUS Diagnostics for IEC/IEEE 60255-118 (C37.118) 2011 and IEEE1344 protocol 1
PMUCONF Configuration parameters for IEC/IEEE 60255-118 (C37.118) 2011 and IEEE1344 1
protocol
PMUREPORT Protocol reporting via IEEE 1344 and IEC/IEEE 60255-118 (C37.118) 2
PHASORREPORT1 Protocol reporting of phasor data via IEEE 1344 and IEC/IEEE 60255-118 2
(C37.118), phasors 1-8
PHASORREPORT2 Protocol reporting of phasor data via IEEE 1344 and IEC/IEEE 60255-118 2
(C37.118), phasors 9-16
PHASORREPORT3 Protocol reporting of phasor data via IEEE 1344 and IEC/IEEE 60255-118 2
(C37.118), phasors 17-24
PHASORREPORT4 Protocol reporting of phasor data via IEEE 1344 and IEC/IEEE 60255-118 2
(C37.118), phasors 24-32
ANALOGREPORT1 Protocol reporting of analog data via IEEE 1344 and IEC/IEEE 60255-118 2
(C37.118), analogs 1-8
ANALOGREPORT2 Protocol reporting of analog data via IEEE 1344 and IEC/IEEE 60255-118 2
(C37.118), analogs 9-16
ANALOGREPORT3 Protocol reporting of analog data via IEEE 1344 and IEC/IEEE 60255-118 2
(C37.118), analogs 17-24
BINARYREPORT1 Protocol reporting of binary data via IEEE 1344 and IEC/IEEE 60255-118 2
(C37.118), binary 1-8
BINARYREPORT2 Protocol reporting of binary data via IEEE 1344 and IEC/IEEE 60255-118 2
(C37.118), binary 9-16
BINARYREPORT3 Protocol reporting of binary data via IEEE 1344 and IEC/IEEE 60255-118 2
(C37.118), binary 17-24
PMUSTATUS Diagnostics for IEC/IEEE 60255-118 (C37.118) 2011 and IEEE1344 protocol 1
INTERRSIG
Self supervision with internal event list
SELFSUPEVLST
5. Differential protection
Two-winding applications
Transformer differential protection T2WPDIF/
two-winding power
T3WPDIF M16104-3 v19
transformer
The Transformer differential protection is provided with
xx05000048.vsd
internal CT ratio matching, vector group compensation and IEC05000048 V1 EN-US
two-winding power
transformer with two
High impedance differential protection, single phase
circuit breakers and HZPDIF M13071-3 v14
xx05000053.vsd
IEC05000053 V1 EN-US
Restricted earth-fault protection, low impedance
Autotransformer with
two circuit breakers
REFPDIF M13047-3 v20
Figure 5. CT group arrangement for differential The REFPDIF function is a percentage biased function with
protection
an additional zero sequence current directional comparison
criterion. This gives excellent sensitivity and stability during
The setting facilities cover the application of the differential
through faults.
protection to all types of power transformers and auto-
transformers with or without load tap changer as well as REFPDIF can also protect autotransformers. Five currents
shunt reactors and local feeders within the station. An are measured at the most complicated configuration as
adaptive stabilizing feature is included for heavy through- shown in Figure 6.
fault currents. By introducing the load tap changer position,
the differential protection pick-up can be set to optimum CT CT
YNdx
sensitivity thus covering internal faults with low fault current CT CB CB
level. Y d
CB CB
Autotransformer
Stabilization is included for inrush and overexcitation
CT
currents respectively, cross-blocking is also available. IED
currents. IEC05000058-2-en.vsd
IEC05000058-2 V1 EN-US
Self-adaptive differential protection for two-winding A sensitive differential protection element based on the
power transformers PSTPDIF GUID-C313E571-F589-4D45-B832-FB60B3509C02 v3
theory of negative-sequence current component is included.
The PSTPDIF function can be used as a differential
protection for any two-winding three-phase power
transformers. It is especially suitable for the differential
protection of phase-shifting transformers (PST), which is
also called phase-angle regulating transformers (PAR). This
function is similar to the standard transformer differential
This element offers the best possible coverage of power lines and cables in complex network configurations,
transformer winding(s) turn-to-turn faults. such as parallel lines, multi-terminal lines.
X
Forward
operation
Forward
operation
R
Reverse
operation
Reverse
operation
en05000034.vsd
IEC05000034 V1 EN-US
Built-in adaptive load compensation algorithm prevents Phase selection, quadrilateral characteristic with
overreaching of zone 1 at load exporting end at phase-to- fixed angle FDPSPDIS M13139-3 v9
earth faults on heavily loaded power lines. The operation of transmission networks today is in many
cases close to the stability limit. Due to environmental
The distance protection zones can operate independently of considerations, the rate of expansion and reinforcement of
each other in directional (forward or reverse) or non- the power system is reduced, for example, difficulties to get
directional mode. This makes them suitable, together with permission to build new power lines. The ability to
different communication schemes, for the protection of accurately and reliably classify the different types of fault,
so that single pole tripping and autoreclosing can be used
The extensive output signals from the phase selection gives Reverse
operation
also important information about faulty phase(s), which can
be used for fault analysis.
currents and the residual current and, compare them with Figure 10. Typical quadrilateral distance protection zone with Phase
the set values. selection, quadrilateral characteristic with settable angle
function FRPSPDIS activated
The independent measurement of impedance for each fault
Full-scheme distance measuring, Mho characteristic
loop together with a sensitive and reliable built in phase
ZMHPDIS SEMOD175459-4 v12 selection makes the function suitable in applications with
The numerical mho line distance protection is an up to five
single phase auto-reclosing.
(depending on product variant) zone full scheme protection
of short circuit and earth faults. The distance protection zones can operate, independent of
each other, in directional (forward or reverse) or non-
The full scheme technique provides back-up protection of
directional mode. This makes them suitable, together with
power lines with high sensitivity and low requirement on
different communication schemes, for the protection of
remote end communication.
power lines and cables in complex network configurations,
The zones have fully independent measuring and settings, such as parallel lines, multi-terminal lines.
which gives high flexibility for all types of lines.
Directional impedance element for Mho characteristic
Built-in selectable zone timer logic is also provided in the
ZDMRDIR
function. SEMOD175532-4 v2
The phase-to-earth impedance elements can be optionally
The function can be used as under impedance back-up supervised by a phase unselective directional function
protection for transformers and generators. (phase unselective, because it is based on symmetrical
components).
The phase selection function is design to accurately select to enlarge the resistive setting of both the phase selection
the proper fault loop(s) in the distance function dependent and the measuring zones without interfering with the load.
on the fault type.
The extensive output signals from the phase selection gives
The heavy load transfer that is common in many also important information about faulty phase(s) which can
transmission networks may in some cases interfere with the be used for fault analysis.
distance protection zone reach and cause unwanted
operation. Therefore the function has a built in algorithm for A current-based phase selection is also included. The
load encroachment, which gives the possibility to enlarge measuring elements continuously measure three phase
the resistive setting of the measuring zones without currents and the residual current and, compare them with
interfering with the load. the set values.
Phase selection, quadrilateral characteristic with During phase-to-earth faults on heavily loaded power lines
settable angle FRPSPDIS GUID-09D0E480-C003-424E-BECD-A82BCB0052CD v1
there is an adaptive load compensation algorithm that
The operation of transmission networks today is in many prevents overreaching of the distance zones in the load
cases close to the stability limit. Due to environmental exporting end, improving the selectivity of the function. This
considerations, the rate of expansion and reinforcement of also reduces underreach in the importing end.
the power system is reduced for example, difficulties to get
permission to build new power lines. The ability to The ZMFPDIS function is also equipped with the parallel
accurately and reliably classify the different types of fault, line mutual coupling compensation feature based on the
so that single pole tripping and autoreclosing can be used parallel line residual current.
plays an important role in this matter. The phase selection
function is designed to accurately select the proper fault
High speed distance protection for series comp.
loop in the distance function dependent on the fault type.
lines, quad and mho characteristic ZMFCPDIS
GUID-C5C1ADD8-50A5-4485-848C-77D2222B56DC v10
The heavy load transfer that is common in many The high speed distance protection (ZMFCPDIS) provides a
transmission networks may make fault resistance coverage sub-cycle, down towards a half-cycle operate time. Its
difficult to achieve. Therefore, the function has a built in seven zone, full scheme protection concept is entirely
algorithm for load encroachment, which gives the possibility suitable in applications with single-phase autoreclosing.
High speed distance protection ZMFCPDIS is fundamentally reliable fault clearance can be achieved for faults during
the same function as ZMFPDIS but provides more flexibility power swing.
in zone settings to suit more complex applications, such as
series compensated lines. In operation for series It is still possible to inhibit the ZMBURPSB function for
compensated networks, the parameters of the directional earth-fault currents during a power swing without activating
function are altered to handle voltage reversal. power swing unblocking functionality.
Two current channels I3P1 and I3P2 are available in During a cross-country fault, both fault locations are in front
OOSPPAM function to allow the direct connection of two of the distance protection. The measured residual current
groups of three-phase currents; that may be needed for very magnitude can be quite small. The PPL2PHIZ function has
powerful generators, with stator windings split into two built-in logic that can detect such a condition and properly
groups per phase, when each group is equipped with release the preferred phase-to-earth loop.
current transformers. The protection function performs a
simple summation of the currents of the two channels I3P1
Underimpedance protection for generators and
and I3P2.
transformers ZGVPDIS GUID-5D0E6F04-8B60-4F12-8DA6-7043BE09A3CC v7
The under impedance protection (ZGVPDIS) function is a
Phase preference logic PPLPHIZ SEMOD153619-5 v3
three zone full scheme impedance protection using offset
The optional phase preference logic (PPLPHIZ) is used with mho characteristics for detecting faults in the generator,
the ZMQPDIS and FDPSPDIS distance protection. The generator-transformer and transmission system. The three
main purpose of this function is to provide a selective zones have fully independent measuring loops and settings.
tripping for cross-country faults in isolated or high The functionality also comprises an under voltage seal-in
impedance-earthed networks. feature to ensure issuing of a trip even if the current
transformer goes into saturation and, in addition, the
positive-sequence-based load encroachment feature for the
Phase preference logic PPL2PHIZ GUID-39785DEB-E5D7-447C-977B-9E940CA8E774 v3 second and the third impedance zone. Built-in
The Phase preference logic function (PPL2PHIZ) is used
compensation for the unit step-up transformer vector group
with the high speed distance protection, quad and mho
connection is available.
characteristic (ZMFPDIS). It is intended to be used in
isolated or high impedance earthed networks where there is
a requirement to operate on only one of the faulty lines Automatic switch onto fault logic, voltage and current
during a cross-country fault. It can be used without based ZCVPSOF M13829-3 v4
preference to restrain operation for single earth faults with a Automatic switch onto fault logic (ZCVPSOF) is a function
delayed zero-sequence current release for cable networks that gives an instantaneous trip at closing of breaker onto a
earthed using a resistor. fault. A dead line detection check is provided to activate the
function when the line is dead.
For cross-country faults, the logic selects either the leading
or lagging phase-to-earth loop for measurement. It initiates
operation on the preferred phase based on the selected 7. Wide area measurement system
phase preference scheme. A number of different phase
preference schemes are available.
Synchrophasor report, 24 phasors GUID-7539462D-A3D6-492D-9926-E67C5B7C72D9 v2
block contains parameters for PMU performance class and The Instantaneous residual overcurrent protection
reporting rate, the IDCODE and Global PMU ID, format of (EFPIOC) has a low transient overreach and short tripping
the data streamed through the protocol, the type of reported times to allow use for instantaneous earth-fault protection,
synchrophasors, as well as settings for reporting analog and with the reach limited to less than typical eighty percent of
digital signals. the transformer impedance at minimum source impedance.
EFPIOC can be configured to measure the residual current
The message generated by the PMUREPORT function from the three-phase current inputs or the current from a
block is set in accordance with the IEC/IEEE 60255-118 separate current input.
(C37.118) and/or IEEE 1344 standards.
There are settings for Phasor type (positive sequence, Directional residual overcurrent protection, four
negative sequence or zero sequence in case of 3-phase steps EF4PTOC M13667-3 v20
phasor and L1, L2 or L3 in case of single phase phasor), EF4PTOC has an inverse or definite time delay independent
PMU's Service class (Protection or Measurement), Phasor for each step.
representation (polar or rectangular) and the data types for
All IEC and ANSI time-delayed characteristics are available
phasor data, analog data and frequency data.
together with an optional user-defined characteristic.
Synchrophasor data can be reported to up to 8 clients over
EF4PTOC can be set to be directional or non-directional
TCP and/or 6 UDP group clients for multicast or unicast
independently for each step.
transmission of phasor data from the IED. More information
regarding synchrophasor communication structure and IDir, UPol and IPol can be independently selected to be
TCP/UDP configuration is available in Application Manual either zero sequence or negative sequence.
under section IEC/IEEE 60255-118 (C37.118) Phasor
Measurement Data Streaming Protocol Configuration. A second harmonic blocking can be set individually for each
step.
Multiple PMU functionality can be configured in the IED,
which can stream out same or different data at different The residual current can be calculated by summing the
reporting rates or different performance (service) classes. three-phase currents or taking the input from the neutral CT.
Directional phase overcurrent protection, four steps All IEC and ANSI time delayed characteristics are available
OC4PTOC M12846-3 v18 together with an optional user defined characteristic.
Directional phase overcurrent protection, four steps
(OC4PTOC) has an inverse or definite time delay for each The directional function is voltage polarized.
step.
NS4PTOC can be set directional or non-directional
All IEC and ANSI inverse time characteristics are available independently for each of the steps.
together with an optional user defined time characteristic.
The directional function needs voltage as it is voltage Sensitive directional residual overcurrent and power
polarized with memory. The function can be set to be protection SDEPSDE SEMOD171438-5 v6
directional or non-directional independently for each of the In isolated networks or in networks with high impedance
steps. earthing, the earth fault current is significantly smaller than
the short circuit currents. In addition to this, the magnitude
use either the residual current or residual power component Breaker failure protection (CCRBRF) ensures a fast backup
3U0·3I0·cos j, for operating quantity with maintained short tripping of the surrounding breakers in case the own
circuit capacity. There is also available one nondirectional breaker fails to open. CCRBRF measurement criterion can
3I0 step and one 3U0 overvoltage tripping step. be current based, CB position based or an adaptive
combination of these two conditions.
No specific sensitive current input is needed. Sensitive
directional residual overcurrent and power protection A current based check with extremely short reset time is
(SDEPSDE) can be set as low 0.25% of IBase. used as check criterion to achieve high security against
inadvertent operation.
Thermal overload protection, one time constant CB position check criteria can be used where the fault
LCPTTR/LFPTTR M12020-4 v14
current through the breaker is small.
The increasing utilization of the power system closer to the
thermal limits has generated a need of a thermal overload CCRBRF provides three different options to select how t1
protection for power lines. and t2 timers are run:
1. By external start signals which is internally latched
A thermal overload will often not be detected by other 2. Follow external start signal only
protection functions and the introduction of the thermal 3. Follow external start signal and the selected
overload protection can allow the protected circuit to FunctionMode
operate closer to the thermal limits.
CCRBRF can be single- or three- phase initiated to allow its
The three-phase current measuring protection has an I2t use with single phase tripping applications. For the three-
characteristic with settable time constant and a thermal phase application of the CCRBRF the current criteria can be
memory. The temperature is displayed in either Celsius or set to operate only if “2 elements operates out of three
Fahrenheit, depending on whether the function used is phases and neutral” for example; two phases or one phase
Thermal overload protection (LCPTTR) (Celsius) or plus the residual current start. This gives a higher security
(LFPTTR) (Fahrenheit). to the backup trip command.
An alarm level gives early warning to allow operators to take The CCRBRF function can be programmed to give a single-
action well before the line is tripped. or three- phase retrip to its own breaker to avoid
unnecessary tripping of surrounding breakers at an
Estimated time to trip before operation, and estimated time incorrect initiation due to mistakes during testing.
to reclose after operation are presented.
Two warning levels are available. This enables actions in Overcurrent protection with binary release BRPTOC
GUID-17DA02BB-B0C0-4AE9-8441-DDA4082A776B v4
the power system to be done before dangerous Overcurrent protection with binary release (BRPTOC) is a
temperatures are reached. If the temperature continues to simple, non-directional three-phase overcurrent protection
increase to the trip value, the protection initiates a trip of the function with definite time delay. A single step is available
protected transformer. within the function. The current pickup level and definite
time delay can be set independently. It is possible to
The estimated time to trip before operation is presented. release the function operation via a binary signal. If the
binary signal is not connected, the function will
automatically operate in a continuous mode of operation. The overcurrent protection feature has a settable current
Several function instances are available. level that can be used either with definite time or inverse
time characteristic. Additionally, it can be voltage controlled/
From the measured three-phase currents, various types of restrained.
measurement modes such as DFT, Peak, and Peak-to-peak
can be selected for the BRPTOC operation. One undervoltage step with definite time characteristic is
also available within the function in order to provide
Peak and Peak-to-Peak measurement mode allow this functionality for overcurrent protection with undervoltage
function to be used as instantaneous over-current protection seal-in.
as well. If required by application, short time delay can also
be applied.
Capacitor bank protection CBPGAPC GUID-D55CEBF7-9377-4E36-BD8B-533609048A1E v3
BRPTOC can be used for different line and transformer Shunt Capacitor Banks (SCB) are used in a power system
protection applications. If required, it can also be used to to provide reactive power compensation and power factor
supervise on-load tap-changer operation. correction. They are as well used as integral parts of Static
Var Compensators (SVC) or Harmonic Filters installations.
Capacitor bank protection (CBPGAPC) function is specially
Pole discordance protection CCPDSC M13269-3 v15 designed to provide protection and supervision features for
An open phase can cause negative and zero sequence
SCBs.
currents which cause thermal stress on rotating machines
and can cause unwanted operation of zero sequence or
negative sequence current functions. Negative sequence time overcurrent protection for
machines NS2PTOC
Normally the own breaker is tripped to correct such a GUID-DBF3EC07-D947-4483-ABD1-4F7D29F48D61 v7
Negative-sequence time overcurrent protection for
situation. If the situation persists the surrounding breakers machines (NS2PTOC) is intended primarily for the
should be tripped to clear the unsymmetrical load situation. protection of generators against possible overheating of the
rotor caused by negative sequence current in the stator
The Pole discordance protection function (CCPDSC)
current.
operates based on information from auxiliary contacts of the
circuit breaker for the three phases with additional criteria The negative sequence currents in a generator may, among
from unsymmetrical phase currents when required. others, be caused by:
• Unbalanced loads
Directional over/underpower protection GOPPDOP/
• Line to line faults
GUPPDUP SEMOD175421-4 v7 • Line to earth faults
The directional over-/under-power protection (GOPPDOP/
• Broken conductors
GUPPDUP) can be used wherever a high/low active,
• Malfunction of one or more poles of a circuit breaker or a
reactive or apparent power protection or alarming is
disconnector
required. The functions can alternatively be used to check
NS2PTOC can also be used as a backup protection, that is,
the direction of active or reactive power flow in the power
to protect the generator in case line protections or circuit
system. There are a number of applications where such
breakers fail to clear unbalanced system faults.
functionality is needed. Some of them are:
To provide an effective protection for the generator for
• detection of reversed active power flow
external unbalanced conditions, NS2PTOC is able to
• detection of high reactive power flow
directly measure the negative sequence current. NS2PTOC
Each function has two steps with definite time delay.
also has a time delay characteristic which matches the
2
Broken conductor check BRCPTOC heating characteristic of the generator I 2 t = K as defined
SEMOD171446-5 v2
The main purpose of the function Broken conductor check in standard IEEE C50.13.
(BRCPTOC) is the detection of broken conductors on
protected power lines and cables (series faults). Detection where:
can be used to give alarm only or trip the line breaker. I2 is negative sequence current expressed in
per unit of the rated generator current
t is operating time in seconds
Voltage-restrained time overcurrent protection
VRPVOC K is a constant which depends of the
GUID-935E1CE8-601F-40E2-8D22-2FF68420FADF v7
generators size and design
Voltage-restrained time overcurrent protection (VRPVOC)
function can be used as generator backup protection NS2PTOC has a wide range of K settings and the sensitivity
against short-circuits. and capability of detecting and tripping for negative
The function is suitable to be used in distribution and in A reset delay ensures operation for intermittent earth faults.
meshed HV sub-transmission networks using high-
impedance grounding. In meshed systems a directional
permissive scheme is required in order to ensure selective Overexcitation protection OEXPVPH M13319-3 v9
tripping of a faulty line. Alternatively, the function can be When the laminated core of a power transformer or
used solely for signaling of the earth-fault location to the generator is subjected to a magnetic flux density beyond its
SCADA system when the power network is allowed to design limits, stray flux will flow into non-laminated
operate for a longer time with an earth-fault being present. components that are not designed to carry flux. This will
cause eddy currents to flow. These eddy currents can cause
excessive heating and severe damage to insulation and
9. Voltage protection adjacent parts in a relatively short time. The function has
settable inverse operating curves and independent alarm
stages.
Two-step undervoltage protection UV2PTUV M13789-3 v14
Undervoltages can occur in the power system during faults
or abnormal conditions. The two-step undervoltage Voltage differential protection VDCPTDV SEMOD153862-5 v8
protection function (UV2PTUV) can be used to open circuit A voltage differential monitoring function is available. It
breakers to prepare for system restoration at power outages compares the voltages from two three phase sets of voltage
or as a long-time delayed back-up to the primary protection. transformers and has one sensitive alarm step and one trip
step.
UV2PTUV has two voltage steps, each with inverse or
definite time delay.
Loss of voltage check LOVPTUV SEMOD171457-5 v8
It has a high reset ratio to allow settings close to the system Loss of voltage check (LOVPTUV ) is suitable for use in
service voltage. networks with an automatic system restoration function.
LOVPTUV issues a three-pole trip command to the circuit
breaker, if all three phase voltages fall below the set value shunt capacitor bank(SCB) from the unbalance due to
for a time longer than the set time and the circuit breaker internal faults in elements or units. The SCPDPTOV
remains closed. function can be applied to grounded and ungrounded
capacitor bank configurations, where the three-phase bus
The operation of LOVPTUV is supervised by the fuse failure and tap voltage measurements are available.
supervision FUFSPVC.
The main features of the function are,
• It can be applied for both single WYE and double WYE,
10. Unbalance protection grounded and ungrounded capacitor bank configurations.
• Continuous monitoring of voltage ratio to overcome the
Cascading failure protection for shunt capacitor bank natural unbalance.
SCCFPVOC • The voltage ratio can be settable or can be triggered
GUID-718C2B4C-6AFA-48E8-B322-0B1D845218D5 v1
Cascading failures are series faults in shunt capacitor banks remotely to be updated it with continuously calculated
involving more than one capacitor unit (or even more than values.
one rack). Cascading failures in shunt capacitor bank • Binary signal indication, when the percentage variation of
(SCCFPVOC) function provides protection against calculated voltage and stored voltage ratios exceeds the
cascading faults and has the following protection modes to settable limit.
detect the unbalances. • Function provides phase segregated warning, alarm and
• Two step, negative sequence based voltage restrained trip signals along with a general warning, alarm and trip
over-current protection signal based on independent set levels.
• Two step, zero sequence based voltage restrained over- • Reliable warning and alarm signals are generated,
current protection stability of alarm and the warning signal is ensured with
settable time delay.
• Two timer modes for trip signal-Definite time and
Current unbalance protection for shunt capacitor programmable IDMT delay curve.
bank SCUCPTOC GUID-29D8914A-371B-4E3B-A522-E5013EED5486 v1 • Unwanted operation of the function, for example,
The current unbalance protection for shunt capacitor bank capacitor bank de-energization can be inhibited by
(SCUCPTOC) function is used to protect the shunt capacitor activating a binary signal.
bank(SCB) from the unbalance due to internal faults in
elements or units. It is applicable for protecting the following
shunt capacitor bank configurations, only when CT’s Voltage unbalance protection for shunt capacitor
available to measure the unbalance current from the bank SCUVPTOV GUID-D9BA5FF8-1A61-46BB-B705-51C9C40ED5D5 v1
• Minimum bus voltage check for secure operation measurement and requires two phase-phase or three
• Function has warning, alarm and trip levels phase-neutral voltages to be connected.
• Function trip signal can be delayed by definite timer or
based on a programmable curve and warning and alarm
have definite time delays
12. Multipurpose protection
11. Frequency protection General current and voltage protection CVGAPC M13083-3 v6
The protection module is recommended as a general
backup protection with many possible application areas due
Underfrequency protection SAPTUF M13349-3 v13
to its flexible measuring and setting facilities.
Underfrequency occurs as a result of a lack of generation in
the network. The built-in overcurrent protection feature has two settable
current levels. Both of them can be used either with definite
Underfrequency protection (SAPTUF) measures frequency time or inverse time characteristic. The overcurrent
with high accuracy, and is used for load shedding systems, protection steps can be made directional with selectable
remedial action schemes, gas turbine startup and so on. voltage polarizing quantity. Additionally they can be voltage
Separate definite time delays are provided for operate and and/or current controlled/restrained. 2nd harmonic
restore. restraining facility is available as well. At too low polarizing
voltage the overcurrent feature can be either blocked, made
SAPTUF is provided with undervoltage blocking. non directional or ordered to use voltage memory in
accordance with a parameter setting.
The operation is based on positive sequence voltage
measurement and requires two phase-phase or three Additionally two overvoltage and two undervoltage steps,
phase-neutral voltages to be connected. either with definite time or inverse time characteristic, are
available within each function.
Overfrequency protection SAPTOF M14953-3 v12 The general function suits applications with
Overfrequency protection function (SAPTOF) is applicable
underimpedance and voltage controlled overcurrent
in all situations, where reliable detection of high
solutions. The general function can also be utilized for
fundamental power system frequency is needed.
generator transformer protection applications where
Overfrequency occurs because of sudden load drops or positive, negative or zero sequence components of current
shunt faults in the power network. Close to the generating and voltage quantities are typically required.
plant, generator governor problems can also cause over
frequency.
13. General calculation
SAPTOF measures frequency with high accuracy, and is
used mainly for generation shedding and remedial action Multipurpose filter SMAIHPAC GUID-EB0B11C3-FF79-4B8D-A335-649623E832F9 v3
schemes. It is also used as a frequency stage initiating load The multi-purpose filter function block (SMAIHPAC) is
restoring. A definite time delay is provided for operate. arranged as a three-phase filter. It has very much the same
user interface (e.g. inputs and outputs) as the standard pre-
SAPTOF is provided with an undervoltage blocking.
processing function block SMAI. However the main
The operation is based on positive sequence voltage difference is that it can be used to extract any frequency
measurement and requires two phase-phase or three component from the input signal. Thus it can, for example,
phase-neutral voltages to be connected. be used to build sub-synchronous resonance protection for
synchronous generator.
transformer cores with the neutral point current on a functions that need to be blocked in case of faults in the
separate input taken from another set of cores on the voltage circuit.
current transformer.
A detection of a difference indicates a fault in the circuit and Voltage based delta supervision DELVSPVC
GUID-6188C4C1-E1D5-421A-B496-96676287EBB2 v2
is used as alarm or to block protection functions expected to Delta supervision function is used to quickly detect (sudden)
give inadvertent tripping. changes in the network. This can, for example, be used to
detect faults in the power system networks and islanding in
grid networks. Voltage based delta supervision
Fuse failure supervision FUFSPVC SEMOD113820-4 v13 (DELVSPVC) is needed at the grid interconnection point.
The aim of the fuse failure supervision function (FUFSPVC)
is to block voltage measuring functions at failures in the
secondary circuits between the voltage transformer and the Current based delta supervision DELISPVC
GUID-30A00AE0-8D3A-4CE8-9379-8D1A0A6078E3 v2
IED in order to avoid inadvertent operations that otherwise Delta supervision function is used to quickly detect (sudden)
might occur. changes in the network. This can, for example, be used to
detect disturbances in the power system network. Current
The fuse failure supervision function basically has three based delta supervision (DELISPVC) provides selectivity
different detection methods, negative sequence and zero between load change and the fault.
sequence based detection and an additional delta voltage
and delta current detection. Present power system has many power electronic devices
or FACTS devices, which injects a large number of
The negative sequence detection algorithm is harmonics into the system. The function has additional
recommended for IEDs used in isolated or high-impedance features of 2nd harmonic blocking and 3rd harmonic start
earthed networks. It is based on the negative-sequence level adaption. The 2nd harmonic blocking secures the
quantities. operation during the transformer charging, when high inrush
currents are supplied into the system.
The zero sequence detection is recommended for IEDs
used in directly or low impedance earthed networks. It is
based on the zero sequence measuring quantities. Delta supervision of real input DELSPVC
GUID-8FAD2CCF-091F-4CDB-8ABF-1BDC874A8403 v2
Delta supervision functions are used to quickly detect
The selection of different operation modes is possible by a (sudden) changes in the power system. Real input delta
setting parameter in order to take into account the particular supervision (DELSPVC) function is a general delta function.
earthing of the network. It is used to detect the change measured qualities over a
settable time period, such as:
A criterion based on delta current and delta voltage
• Power
measurements can be added to the fuse failure supervision
• Reactive power
function in order to detect a three phase fuse failure, which
• Temperature
in practice is more associated with voltage transformer
• Frequency
switching during station operations.
• Power factor
Manual closing as well as automatic reclosing can be • Direct with normal security
checked by the function and can have different settings. • SBO (Select-Before-Operate) with enhanced security
For systems, which can run asynchronously, a Normal security means that only the command is evaluated
synchronizing feature is also provided. The main purpose of and the resulting position is not supervised. Enhanced
the synchronizing feature is to provide controlled closing of security means that the command is evaluated with an
circuit breakers when two asynchronous systems are in additional supervision of the status value of the control
phase and can be connected. The synchronizing feature object. The command sequence with enhanced security is
evaluates voltage difference, phase angle difference, slip always terminated by a CommandTermination service
frequency and frequency rate of change before issuing a primitive and an AddCause telling if the command was
controlled closing of the circuit breaker. Breaker closing successful or if something went wrong.
time is a setting.
Control operation can be performed from the local HMI with
authority control if so defined.
Autorecloser SMBRREC M12390-3 v17
The auto recloser (SMBRREC) function provides:
• high-speed and/or delayed auto reclosing Interlocking M13531-3 v5
• single and/or three phase auto reclosing The interlocking function blocks the possibility to operate
• support for single or multi-breaker applications. primary switching devices, for instance when a disconnector
is under load, in order to prevent material damage and/or
The auto recloser can be used for delayed busbar accidental human injury.
restoration.
Each apparatus control function has interlocking modules
Up to five reclosing shots can be performed. The first shot included for different switchyard arrangements, where each
can be single-, two-, and /or three-phase depending on the function handles interlocking of one bay. The interlocking
type of the fault and the selected auto reclosing mode. function is distributed to each IED and is not dependent on
any central function. For the station-wide interlocking, the
Several auto reclosing functions can be provided for multi- IEDs communicate via the system-wide interbay bus (IEC
breaker arrangements. A priority circuit allows one circuit 61850-8-1) or by using hard wired binary inputs/outputs.
breaker to reclose first and the second will only close if the The interlocking conditions depend on the circuit
fault proved to be transient. configuration and apparatus position status at any given
time.
Each auto reclosing function can be configured to co-
operate with the synchrocheck function. For easy and safe implementation of the interlocking
function, the IED is delivered with standardized and tested
Apparatus control APC software interlocking modules containing logic for the
The apparatus control functions are used for control and
M13444-3 v16
interlocking conditions. The interlocking conditions can be
supervision of circuit breakers, disconnectors and earthing altered, to meet the customer’s specific requirements, by
switches within a bay. Permission to operate is given after adding configurable logic by means of PCM600 tool.
evaluation of conditions from other functions such as
interlocking, synchrocheck, operator place selection and Switch controller SCSWI
external or internal blockings. The Switch controller (SCSWI) initializes and supervises all
M13486-3 v11
switches via binary output boards and to supervise the Automatic voltage control for tap changer, single control
switching operation and position. (TR1ATCC), Automatic voltage control for tap changer,
parallel control (TR8ATCC), Tap changer control and
supervision, 6 binary inputs (TCMYLTC) and Tap changer
Reservation function QCRSV M13506-3 v5
control and supervision, 32 binary inputs (TCLYLTC) are
The purpose of the reservation (QCRSV) function is used for control of power transformers with an on-load tap
primarily to transfer interlocking information between IEDs changer. The functions provide automatic regulation of the
in a safe way and to prevent double operation in a bay, voltage on the secondary side of transformers or
switchyard part, or complete substation. alternatively on a load point further out in the network.
Local remote LOCREM/Local remote control Selector mini switch VSGAPC SEMOD158756-5 v11
LOCREMCTRL M17086-3 v12
The Selector mini switch (VSGAPC) function block is a
The signals from the local HMI or from an external local/ multipurpose function used for a variety of applications, as a
remote switch are connected via the function blocks local general purpose switch.
remote (LOCREM) and local remote control
(LOCREMCTRL) to the Bay control (QCBAY) function block. VSGAPC can be controlled from a symbol on the single line
The parameter ControlMode in function block LOCREM is diagram (SLD) on the local HMI or from binary inputs.
set to choose if the switch signals are coming from the local
Generic communication function for double point Phase segregated scheme communication logic for
indication DPGAPC SEMOD55850-5 v8
distance protection ZPCPSCH SEMOD141686-4 v4
Generic communication function for double point indication Communication between line ends is used to achieve fault
(DPGAPC) function block is used to send double point clearance for all faults on a power line. All possible types of
position indications to other systems, equipment or communication schemes for example, permissive
functions in the substation through IEC 61850-8-1 or other underreach, permissive overreach and blocking schemes
communication protocols. It is especially intended to be are available. To manage problems with simultaneous faults
used in the interlocking station-wide logics. on parallel power lines phase segregated communication is
needed. This will then replace the standard Scheme
communication logic for distance or Overcurrent protection
Single point generic control 8 signals SPC8GAPC SEMOD176462-4 v11 (ZCPSCH) on important lines where three communication
The Single point generic control 8 signals (SPC8GAPC)
channels (in each subsystem) are available for the distance
function block is a collection of 8 single point commands
protection communication.
that can be used for direct commands for example reset of
LEDs or putting IED in "ChangeLock" state from remote. In The main purpose of the Phase segregated scheme
this way, simple commands can be sent directly to the IED communication logic for distance protection (ZPCPSCH)
outputs, without confirmation. Confirmation (status) of the function is to supplement the distance protection function
result of the commands is supposed to be achieved by other such that:
means, such as binary inputs and SPGAPC function blocks.
The commands can be pulsed or steady with a settable • fast clearance of faults is also achieved at the line end for
pulse time. which the faults are on the part of the line not covered by
its underreaching zone.
• correct phase selection can be maintained to support
Automation bits, command function for DNP3.0 single-pole tripping for faults occurring anywhere on the
AUTOBITS SEMOD158591-5 v9 entire length of a double circuit line.
Automation bits function for DNP3 (AUTOBITS) is used
To accomplish this, three separate communication
within PCM600 to get into the configuration of the
channels, that is, one per phase, each capable of
commands coming through the DNP3 protocol. The
transmitting a signal in each direction is required.
AUTOBITS function plays the same role as functions
GOOSEBINRCV (for IEC 61850) and MULTICMDRCV (for ZPCPSCH can be completed with the current reversal and
LON). WEI logic for phase segregated communication, when found
necessary in Blocking and Permissive overreaching
schemes.
Single command, 16 inputs SINGLECMD M12446-6 v7
The IEDs can receive commands either from a substation
automation system or from the local HMI. The command Current reversal and weak-end infeed logic for
function block has outputs that can be used, for example, to distance protection ZCRWPSCH M13896-3 v15
control high voltage apparatuses or for other user defined The ZCRWPSCH function provides the current reversal and
functionality. weak end infeed logic functions that supplement the
standard scheme communication logic. It is not suitable for
standalone use as it requires inputs from the distance
16. Scheme communication
protection functions and the scheme communications
function included within the terminal.
Scheme communication logic for distance or
On detection of a current reversal, the current reversal logic
overcurrent protection ZCPSCH M13860-3 v12
provides an output to block the sending of the teleprotection
To achieve instantaneous fault clearance for all line faults,
signal to the remote end, and to block the permissive
scheme communication logic is provided. All types of
tripping at the local end. This blocking condition is
communication schemes for permissive underreaching,
maintained long enough to ensure that no unwanted
permissive overreaching, blocking, delta based blocking,
operation will occur as a result of the current reversal.
unblocking and intertrip are available.
On verification of a weak end infeed condition, the weak
The built-in communication module (LDCM) can be used for
end infeed logic provides an output for sending the received
scheme communication signaling when included.
teleprotection signal back to the remote sending end and
other output(s) for local tripping. For terminals equipped for
single- and two-pole tripping, outputs for the faulted
phase(s) are provided. Undervoltage detectors are used to
detect the faulted phase(s).
The weak-end infeed logic is used in cases where the If parallel lines are connected to common busbars at both
apparent power behind the protection can be too low to terminals, overreaching permissive communication schemes
activate the distance protection function. When activated, can trip unselectively due to fault current reversal. This
received carrier signal together with local undervoltage unwanted tripping affects the healthy line when a fault is
criteria and no reverse zone operation gives an cleared on the other line. This lack of security can result in
instantaneous trip. The received signal is also echoed back a total loss of interconnection between the two buses. To
to accelerate the sending end. avoid this type of disturbance, a fault current reversal logic
(transient blocking logic) can be used.
M13928-8 v5
Local acceleration logic ZCLCPSCH Permissive communication schemes for residual overcurrent
M13823-3 v7
To achieve fast clearing of faults on the whole line, when no protection can basically operate only when the protection in
communication channel is available, local acceleration logic the remote IED can detect the fault. The detection requires
(ZCLCPSCH) can be used. This logic enables fast fault a sufficient minimum residual fault current, out from this
clearing and re-closing during certain conditions, but IED. The fault current can be too low due to an opened
naturally, it can not fully replace a communication channel. breaker or high-positive and/or zero-sequence source
impedance behind this IED. To overcome these conditions,
The logic can be controlled either by the autorecloser (zone weak-end infeed (WEI) echo logic is used. The weak-end
extension) or by the loss-of-load current (loss-of-load infeed echo is limited to 200 ms to avoid channel lockup.
acceleration).
17. Logic
Scheme communication logic for residual
overcurrent protection ECPSCH M13918-4 v11
To achieve fast fault clearance of earth faults on the part of Tripping logic SMPPTRC M12275-3 v16
the line not covered by the instantaneous step of the A function block for protection tripping and general start
residual overcurrent protection, the directional residual indication is always provided as a basic function for each
overcurrent protection can be supported with a logic that circuit breaker. It provides a settable pulse prolongation
uses communication channels. time to ensure a trip pulse of sufficient length, as well as all
functionality necessary for correct co-operation with
In the directional scheme, information of the fault current autoreclosing functions.
direction must be transmitted to the other line end. With
directional comparison, a short operate time of the The trip function block includes a settable latch function for
protection including a channel transmission time, can be the trip signal and circuit breaker lockout.
achieved. This short operate time enables rapid
The trip function can collect start and directional signals
autoreclosing function after the fault clearance.
from different application functions. The aggregated start
The communication logic module for directional residual and directional signals are mapped to the IEC 61850 logical
current protection enables blocking as well as permissive node data model.
under/overreaching, and unblocking schemes. The logic can
The function also captures and reports the magnitude, angle
also be supported by additional logic for weak-end infeed
of the voltage and current of each phase and neutral at the
and current reversal, included in Current reversal and weak-
instant of fault to IEC 61850, LHMI, signal monitoring tool
end infeed logic for residual overcurrent protection
triggered by TRINx signal activation.
(ECRWPSCH) function.
The purpose of this functionality is to provide general start The OR function block has up to six inputs and two
and directional information for the IEC 61850 trip logic data outputs. One of the outputs is inverted.
model SMPPTRC. • PULSETIMER function block can be used, for example,
for pulse extensions or limiting of operation of outputs,
settable pulse time.
Trip matrix logic TMAGAPC M15321-3 v14 • RSMEMORY function block is a flip-flop that can reset or
The trip matrix logic (TMAGAPC) function is used to route
set an output from two inputs respectively. Each block
trip signals and other logical output signals to different
has two outputs where one is inverted. The memory
output contacts on the IED.
setting controls if, after a power interruption, the flip-flop
The trip matrix logic function has 3 output signals and these resets or returns to the state it had before the power
outputs can be connected to physical tripping outputs interruption. RESET input has priority.
according to the specific application needs for settable • SRMEMORY function block is a flip-flop that can set or
pulse or steady output. reset an output from two inputs respectively. Each block
has two outputs where one is inverted. The memory
setting controls if, after a power interruption, the flip-flop
Group alarm logic function ALMCALH GUID-16E60E27-F7A8-416D-8648-8174AAC49BB5 v4
resets or returns to the state it had before the power
The group alarm logic function (ALMCALH) is used to route interruption. The SET input has priority.
several alarm signals to a common indication, LED and/or • TIMERSET function has pick-up and drop-out delayed
contact, in the IED. outputs related to the input signal. The timer has a
settable time delay.
• XOR is used to generate combinatory expressions with
Group warning logic function WRNCALH GUID-F7D9A012-3AD4-4D86-BE97-DF2A99BE5383 v4
The group warning logic function (WRNCALH) is used to boolean variables. XOR has two inputs and two outputs.
route several warning signals to a common indication, LED One of the outputs is inverted. The output signal OUT is 1
and/or contact, in the IED. if the input signals are different and 0 if they are the
same.
route several indication signals to a common indication, The configurable logic blocks QT propagate the time stamp
LED and/or contact, in the IED. and the quality of the input signals (have suffix QT at the
end of their function name).
Basic configurable logic blocks The function blocks assist the user to adapt the IEDs'
M11396-4 v20
The basic configurable logic blocks do not propagate the configuration to the specific application needs. The list
time stamp and quality of signals (have no suffix QT at the below shows a summary of the function blocks and their
end of their function name). A number of logic blocks and features.
timers are always available as basic for the user to adapt
• ANDQT AND function block. The function also propagates
the configuration to the specific application needs. The list
the time stamp and the quality of input signals. Each
below shows a summary of the function blocks and their
block has four inputs and two outputs where one is
features.
inverted.
The logic blocks are available as a part of an extension • INDCOMBSPQT combines single input signals to group
logic package. The list below is a summary of the function signal. Single position input is copied to value part of
blocks and their features. SP_OUT output. TIME input is copied to time part of
SP_OUT output. Quality input bits are copied to the
• AND function block. The AND function is used to form corresponding quality part of SP_OUT output.
general combinatory expressions with boolean variables. • INDEXTSPQT extracts individual signals from a group
The AND function block has up to four inputs and two signal input. The value part of single position input is
outputs. One of the outputs is inverted. copied to SI_OUT output. The time part of single position
• GATE function block is used for whether or not a signal input is copied to TIME output. The quality bits in the
should be able to pass from the input to the output. common part and the indication part of inputs signal are
• INVERTER function block that inverts the input signal to copied to the corresponding quality output.
the output. • INVALIDQT function which sets quality invalid of outputs
• LLD function block. Loop delay used to delay the output according to a "valid" input. Inputs are copied to outputs.
signal one execution cycle. If input VALID is 0, or if its quality invalid bit is set, all
• OR function block. The OR function is used to form outputs invalid quality bit will be set to invalid. The time
general combinatory expressions with boolean variables. stamp of an output will be set to the latest time stamp of
INPUT and VALID inputs.
• INVERTERQT function block that inverts the input signal • Applicable to long time integration (≤999 999.9 seconds).
and propagates the time stamp and the quality of the • Supervision of limit transgression conditions and overflow.
input signal. • Possibility to define a warning or alarm with the resolution
• ORQT OR function block that also propagates the time of 10 milliseconds.
stamp and the quality of the input signals. Each block has • Retaining of the integration value.
six inputs and two outputs where one is inverted. • Possibilities for blocking and reset.
• PULSETIMERQT Pulse timer function block can be used, • Reporting of the integrated time.
for example, for pulse extensions or limiting of operation
of outputs. The function also propagates the time stamp Boolean to integer conversion, 16 bit B16I SEMOD175725-4 v5
and the quality of the input signal. Boolean to integer conversion, 16 bit (B16I) is used to
• RSMEMORYQT function block is a flip-flop that can reset transform a set of 16 boolean (logical) signals into an
or set an output from two inputs respectively. Each block integer.
has two outputs where one is inverted. The memory
setting controls if the block after a power interruption
Boolean to integer conversion with logical node
should return to the state before the interruption, or be
representation, 16 bit BTIGAPC
reset. The function also propagates the time stamp and Boolean to integer conversion with logical node
SEMOD175781-4 v8
the quality of the input signal. representation, 16 bit (BTIGAPC) is used to transform a set
• SRMEMORYQT function block is a flip-flop that can set or of 16 boolean (logical) signals into an integer. The block
reset an output from two inputs respectively. Each block input will freeze the output at the last value.
has two outputs where one is inverted. The memory
setting controls if the block after a power interruption
should return to the state before the interruption, or be Integer to Boolean 16 conversion IB16 SEMOD158373-5 v7
reset. The function also propagates the time stamp and Integer to boolean 16 conversion function (IB16) is used to
the quality of the input signal. transform an integer into a set of 16 boolean (logical)
• TIMERSETQT function has pick-up and drop-out delayed signals.
outputs related to the input signal. The timer has a
settable time delay. The function also propagates the time
Integer to boolean conversion with logical node
stamp and the quality of the input signal.
representation, 16 bit ITBGAPC
• XORQT XOR function block. The function also SEMOD158421-5 v10
Integer to boolean conversion with logic node
propagates the time stamp and the quality of the input
representation function (ITBGAPC) is used to transform an
signals. Each block has two outputs where one is
integer which is transmitted over IEC 61850 and received by
inverted.
the function to 16 boolean (logic) output signals.
Extension logic package GUID-144BAAA3-A5EF-49AF-8876-93CC5F3D0234 v1
The logic extension block package includes additional trip Comparator for integer inputs INTCOMP GUID-A93564FA-0017-4939-A9C1-095DA0FD9832 v1
matrix logic and configurable logic blocks. The function gives the possibility to monitor the level of
integer values in the system relative to each other or to a
fixed value. It is a basic arithmetic function that can be used
Fixed signal function block FXDSIGN M15322-3 v16
for monitoring, supervision, interlocking and other logics.
The Fixed signals function (FXDSIGN) has nine pre-set
(fixed) output signals that can be used in the configuration
of an IED, either for forcing the unused inputs in other Comparator for real inputs REALCOMP GUID-E17A88D7-D095-4F36-9CD5-64EBFD2A1DEA v1
function blocks to a certain level/value, or for creating The function gives the possibility to monitor the level of real
certain logic. Boolean, integer, floating point, string types of value signals in the system relative to each other or to a
signals are available. fixed value. It is a basic arithmetic function that can be used
for monitoring, supervision, interlocking and other logics.
One FXDSIGN function block is included in all IEDs.
The Disturbance recorder acquires sampled data from output signals can be used as conditions in the configurable
selected analog and binary signals connected to the logic or for alarming purpose.
Disturbance recorder function (maximum 40 analog and 352
binary signals). The binary signals available are the same
Insulation supervision for gas medium function
as for the event recorder function.
SSIMG GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v8
The function is characterized by great flexibility and is not Insulation supervision for gas medium (SSIMG ) is used for
dependent on the operation of protection functions. It can monitoring the circuit breaker condition. Binary information
record disturbances not detected by protection functions. based on the gas pressure in the circuit breaker can be
Up to ten seconds of data before the trigger instant can be used as input to the function. In addition, the function can
saved in the disturbance file. be used with an analog value of gas pressure and
temperature of the insulation medium and binary inputs. The
The disturbance recorder information for up to 200 SSIMG function generates alarms based on the received
disturbances are saved in the IED and the local HMI is used information.
to view the list of recordings .
• Applicable to very long time accumulation (≤ 99999.9 faults, the fault-current magnitude is higher as the allowed
hours) overload current range. At low fault current magnitudes
• Supervision of limit transgression conditions and rollover/ which are below the overload capability of the transformer,
overflow mechanical effects are considered less important unless the
• Possibility to define a warning and alarm with the frequency of fault occurrence is high. Since through fault
resolution of 0.1 hours current magnitudes are typically closer to the extreme
• Retain any saved accumulation value at a restart design capabilities of the transformer, mechanical effects
• Possibilities for blocking and reset are more significant than thermal effects.
• Possibility for manual addition of accumulated time
• Reporting of the accumulated time For other power system objects, for example, an over-head
line, this function can be used to make a log of primary
Estimation of transformer winding insulation life quantities of a protected line.
LOLSPTR GUID-CDE89397-8E99-4873-9701-FF642101A308 v2
Estimation of transformer winding insulation life (LOLSPTR)
Current harmonic monitoring CHMMHAI
is used to calculate transformer winding hot spot GUID-CD97D6CF-7343-416B-82D3-8352FFF9D73E v2
Current harmonic monitoring function CHMMHAI is used to
temperature using the empirical formulae. It is also used to
monitor the current part of the power quality of a system. It
estimate transformer loss of life from the winding hot spot
calculates the total harmonic distortion (THD) with respect
temperature value. The transformer winding insulation is
to fundamental signal amplitude, and the total demand
degraded when the winding hot spot temperature exceeds
distortion (TDD) with respect to maximum demand load
certain limit. LOLSPTR gives warning and alarm signals
current. These indices indicate the current signal quality
when the winding hot spot temperature reaches a set value.
factor.
Hot spot temperature calculation requires top oil
Additionally, the function is used to calculate the numerical
temperature at a given time. This value can either be a
multiple of rated frequency harmonics amplitude and
measured value taken through sensors or the one
harmonic distortion up to 9 th order. It helps the user to know
calculated by the function. This decision is made based on
the predominant harmonic frequencies order and their
the top oil temperature sensor quality. Top oil temperature
amplitudes present in the system. The function also
calculation is done using the method explained in IEC
calculates the crest factor to indicate the effectiveness of
60076-7 standard.
the signal. All calculations in the harmonic monitoring
Inputs required for hot spot temperature calculation are: function are based on IEEE 1459 and IEEE 519-2014
• Transformer oil time constant standards.
• Winding time constant
The current harmonic function monitors the harmonic
• Loss ratio at different tap positions
distortion and demand distortion values constantly.
• Ambient temperature around the transformer
Whenever these value crosses their set limit levels, a
The oil and winding time constants can be calculated by the warning signal will be initiated. If the warning signal persists
function based on transformer parameters if the inputs are continuously for the set time, an alarm signal will be
not available from the transformer manufacturer. generated.
The voltage harmonic function monitors the harmonic input is low, then the outputs are shown as default for the
distortion value constantly. Whenever these value crosses corresponding disturbance recorded.
their set limit levels, a warning signal will be initiated. If the
warning signal persists continuously for the set time, an
alarm signal will be generated.
19. Metering
Fault current and voltage monitoring FLTMMXU Pulse-counter logic PCFCNT M13394-3 v7
GUID-FD0A598B-7E78-4F49-B927-21D099DD91D4 v1
The fault current and voltage monitoring function monitors Pulse-counter logic (PCFCNT) function counts externally
and reports the voltage and current values on occurrence of generated binary pulses, for instance pulses coming from
a trip event. an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary
FLTMMXU function monitors and reports the following input module and then read by the PCFCNT function. A
values: scaled service value is available over the station bus. The
• Maximum peak current of individual phases during the trip special Binary input module with enhanced pulse counting
event capabilities must be ordered to achieve this functionality.
• Maximum RMS current of individual phases during the trip
event
Function for energy calculation and demand handling
• Maximum RMS current of all phases during the trip event
ETPMMTR
• Fundamental DFT current magnitude and angle of GUID-6898E29B-DA70-421C-837C-1BBED8C63A7A v3
Power system measurement (CVMMXN) can be used to
individual phases at the instant of triggering the function
measure active as well as reactive power values. Function
via input TRIGFLUI
for energy calculation and demand handling (ETPMMTR)
• Fundamental DFT neutral current magnitude and angle at
uses measured active and reactive power as input and
the instant of triggering the function via input TRIGFLUI
calculates the accumulated active and reactive energy
• Fundamental DFT voltage magnitude and angle of
pulses, in forward and reverse direction. Energy values can
individual phases at the instant of triggering the function
be read or generated as pulses. Maximum demand power
via input TRIGFLUI
values are also calculated by the function. This function
• Fundamental DFT neutral voltage magnitude and angle at
includes zero point clamping to remove noise from the input
the instant of triggering the function via input TRIGFLUI
signal. As output of this function: periodic energy
calculations, integration of energy values, calculation of
Fault locator LMBRFLO M13970-3 v14
energy pulses, alarm signals for limit violation of energy
The accurate fault locator is an essential component to values and maximum power demand, can be found.
minimize the outages after a persistent fault and/or to pin-
point a weak spot on the line. The values of active and reactive energies are calculated
from the input power values by integrating them over a
The fault locator is an impedance measuring function giving selected time tEnergy. The integration of active and reactive
the distance to the fault in km, miles or % of line length. The energy values will happen in both forward and reverse
main advantage is the high accuracy achieved by directions. These energy values are available as output
compensating for load current and for the mutual zero- signals and also as pulse outputs. Integration of energy
sequence effect on double circuit lines. values can be controlled by inputs (STARTACC and
STOPACC) and EnaAcc setting and it can be reset to initial
The compensation includes setting of the remote and local values with RSTACC input.
sources and calculation of the distribution of fault currents
from each side. This distribution of fault current, together The maximum demand for active and reactive powers are
with recorded load (pre-fault) currents, is used to exactly calculated for the set time interval tEnergy and these values
calculate the fault position. The fault can be recalculated are updated every minute through output channels. The
with new source data at the actual fault to further increase active and reactive maximum power demand values are
the accuracy. calculated for both forward and reverse direction and these
values can be reset with RSTDMD input.
Especially on heavily loaded long lines, where the source
voltage angles can be up to 35-40 degrees apart, the
accuracy can be still maintained with the advanced
compensation included in fault locator.
22. Ethernet
Device 1 Device 1
IEC13000239 V4 EN-US
AP1 AP2 AP3 AP1 AP2 AP3
Figure 11. Local human-machine interface SFP_301 SFP_302 SFP_303
SFP_301
A
SFP_302
B SFP_303
single line diagram and provide an interface for controlling Figure 12. Access points, non redundant (left) and redundant
communication (right)
switchgear.
• Navigation buttons and five user defined command DHCP is available for the front port, and a device connected
buttons to shortcuts in the HMI tree or simple commands. to it can thereby obtain an automatically assigned IP-
• 15 user defined three-color LEDs. address.
• Communication port for PCM600.
Access points diagnostics
The LHMI is used for setting, monitoring and controlling. GUID-20F64A6D-AA8C-47D7-AA7D-4810996B2FF2 v4
The access point diagnostics function blocks (RCHLCCH,
SCHLCCH and FRONTSTATUS) supervise communication.
21. Basic IED functions SCHLCCH is used for communication over the rear Ethernet
ports, RCHLCCH is used for redundant communications
over the rear Ethernet ports and FRONTSTATUS is used for
Time synchronization M11344-3 v12 communication over the front port. All access point function
The time synchronization function is used to select a blocks include output signal for denial of service. To get this
common source of absolute time for the synchronization of denial of service, that is reported on the communication, the
the IED when it is a part of a protection system. This makes DOSALARM output from these blocks must be connected to
it possible to compare events and disturbance data between a communication function.
all IEDs within a station automation system and in between
sub-stations. A common source shall be used for IED and
merging unit when IEC/UCA 61850-9-2LE process bus
communication is used.
PRP IEC 62439-3 redundant communication Figure 13. Route from source to destination through gateway
Redundant communication according to IEC 62439-3 PRP-0
and IEC 62439-3 PRP-1 parallel redundancy protocol (PRP)
is available as an option when ordering IEDs. PRP 23. Station communication
according to IEC 62439-3 uses two optical/Galvanic (RJ45)
Ethernet ports.
Communication protocols M14815-3 v16
HSR IEC 62439-3 High-availability seamless redundancy Each IED is provided with several communication interfaces
Redundant station bus communication according to IEC enabling it to connect to one or many substation level
62439-3 Edition 2 High-availability seamless redundancy systems or equipment, either on the Substation Automation
(HSR) is available as an option when ordering IEDs. (SA) bus or Substation Monitoring (SM) bus.
Redundant station bus communication according to IEC
62439-3 uses two optical/Galvanic (RJ45) Ethernet ports. Available communication protocols are:
The HSR ring supports the connection of up to 30 relays. If • IEC 61850-8-1 communication protocol
more than 30 relays are to be connected, it is recommended • IEC/UCA 61850-9-2LE communication protocol
to split the network into several rings to guarantee the • LON communication protocol
performance for real-time applications. • SPA communication protocol
• IEC 60870-5-103 communication protocol
GUID-D87005A3-826E-4EB4-9B3D-9C6222CFEF6C v2
• DNP 3.0 communication protocol
Rapid spanning tree protocol RSTP • Syslog (RFC 5424) standard
Rapid Spanning Tree Protocol (RSTP) is a network protocol Several protocols can be combined in the same IED.
built for loop-free network topology and redundancy/backup
connections between switches.
The LPHD.PhyHealth reflects the physical
• Support for RSTP is available on the Station level network
health of the IED. The status is set to Alarm
communication. when there is an internal failure in the IED or
• RSTP is only available on the Access Point (AP) 1 or Warning if any active communication link fails.
Access Point (AP) 3. AP1 uses port 1 and port 2; AP3
uses port 3 and port 4.
• RSTP can be configured using Ethernet configuration Simple network management protocol SNMP GUID-B03C5450-3659-4D62-B439-EAEB93F3D402 v1
Tool (ECT) and PST in PCM600. Simple Network Management Protocol (SNMP) is an
internet standard protocol to get and set data of the
connected network devices. It uses UDP protocol for
Routes GUID-95F9C7BA-92F8-489F-AD0A-047410B5E66F v2
communication.
A route is a specified path for data to travel between the
source device in a subnetwork to the destination device in a Here it is used to provide information of the hardware
different subnetwork. A route consists of a destination devices, software and attached network interface to the
address and the address of the gateway to be used when SNMP manager.
sending data to the destination device, see Figure 13.
The SNMP agent supports the following,
objects (Object Identifiers) are supported. ALSVS reports the status of sampled value communication
3. User profiles can be configured from the PCM600 tool to a client according to IEC 61850.
and only these users are supported for SNMP
There should be one instance of ALSVS in an IED for each
communication.
sampled value data stream that the IED receives. Each
4. Traps are not supported.
ALSVS reports the status of one receiving sampled value
IEC 61850-8-1 communication protocol data stream.
M14787-3 v18
IEC 61850 Ed. 1, Ed. 2 or Ed. 2.1 can be chosen by a
The attributes St and SimSt are supported as well as the
setting in PCM600. The IED is equipped with up to six
setting SvCBRef, according to IEC 61850-7-4 Edition 2 and
(order dependent) optical Ethernet rear ports for IEC
Edition 2.1.
61850-8-1 station bus communication. The IEC 61850-8-1
communication is also possible from the electrical Ethernet
front port. IEC 61850-8-1 protocol allows intelligent ALSVS is not defined in IEC 61850 Edition 1
and is only supported in Edition 2 and Edition
electrical devices (IEDs) from different vendors to exchange
2.1 mode.
information and simplifies system engineering. IED-to-IED
communication using GOOSE and client-server
communication over MMS are supported. Disturbance IEC/UCA 61850-9-2LE communication protocol
GUID-C3AA21B4-730F-4327-943A-3C77102A80A0 v4
recording file (COMTRADE) uploading can be done over Optical Ethernet port communication standard IEC/UCA
MMS or FTP. 61850-9-2LE for process bus is supported. IEC/UCA
61850-9-2LE allows Non Conventional Instrument
The front port is only intended for PCM600 Transformers (NCIT) with Merging Units (MUs) or stand-
communication, maintenance, training and test alone MUs to exchange information with the IED, and
purposes due to risk of interference during simplifies SA engineering. IEC/UCA 61850-9-2LE uses the
normal operation. same port as IEC 61850-8-1.
There should be one instance of ALGOS in an IED for each IEC 60870-5-103 communication protocol SEMOD120137-5 v6
data set that the IED receives from other IEDs. Each A single glass or plastic port is provided for the IEC
ALGOS reports the status of the receiving GOOSE 60870-5-103 standard. This allows design of simple
communication. substation automation systems including equipment from
different vendors. Disturbance files uploading is provided.
All attributes, both mandatory and optional, according to
IEC 61850-7-4 Edition 2, Edition 2.1 are supported.
IED must be configured with COMTRADE1999
format for disturbance recorder communication
ALGOS is not defined in IEC 61850 Edition 1 with IEC 60870-5-103 protocol.
and is only supported in Edition 2 and Edition
2.1 mode.
Measurands for IEC 60870-5-103 I103MEAS
GUID-A0BD7E4D-9357-4258-BB05-A2AEC005F7E4 v1
103MEAS is a function block that reports all valid measuring
types depending on the connected signals. The set of
connected inputs will control which ASDUs (Application
Service Data Units) are generated.
Measurands user-defined signals for IEC 60870-5-103 Function commands for IEC 60870-5-103 I103CMD
GUID-F6BA286D-BC6B-4110-81C8-78B1D5245F99 v1
I103MEASUSR GUID-7BF8125C-5A6E-41FD-9533-94C3C04F7A77 v1
I103CMD is a command function block in control direction
I103MEASUSR is a function block with user-defined input with pre-defined output signals. The signals are in steady
measurands in monitor direction. These function blocks state, not pulsed, and stored in the IED in case of restart.
include the FunctionType parameter for each block in the
private range, and the Information number parameter for
IED commands for IEC 60870-5-103 I103IEDCMD
each block. GUID-4CCA77FF-343E-4CC1-92E4-F00B8BCD6ABE v1
I103IEDCMD is a command block in control direction with
defined IED functions. All outputs are pulsed and they are
Function status auto-recloser for IEC 60870-5-103 NOT stored. Pulse-time is a hidden parameter.
I103AR GUID-C74C8A27-FCFE-4323-BAEE-F94239AC51D8 v1
I103AR is a function block with defined functions for
Function commands user-defined for IEC 60870-5-103
autorecloser indications in monitor direction. This block
I103USRCMD
includes the FunctionType parameter, and the information GUID-5A7B2247-2E1E-4353-AC5E-596E6FC33F3F v1
I103USRCMD is a command block in control direction with
number parameter is defined for each output signal.
user-defined output signals. These function blocks include
the FunctionType parameter for each block in the private
Function status earth-fault for IEC 60870-5-103 range, and the Information number parameter for each
I103EF GUID-542D6178-2E5F-4057-A266-F4FCEC3CBE79 v1
output signal.
I103EF is a function block with defined functions for earth
fault indications in monitor direction. This block includes the
Function commands generic for IEC 60870-5-103
FunctionType parameter; the information number parameter
I103GENCMD
is defined for each output signal. GUID-7C9D05B4-53B6-44A6-B635-1A7FFEEE5400 v1
I103GENCMD is used for transmitting generic commands
over IEC 60870-5-103. The function has two output signals,
Function status fault protection for IEC 60870-5-103 CMD_OFF and CMD_ON, that can be used to implement
I103FLTPROT GUID-C0C54B65-8F56-4E7B-A8DC-38582CAFB4AB v1
double-point command schemes.
I103FLTPROT is used for fault indications in monitor
direction. Each input on the function block is specific for a The I103GENCMD component can be configured as either 2
certain fault type and therefore must be connected to a pulsed ON/OFF or 2 steady ON/OFF outputs. The ON
correspondent signal present in the configuration. For output is pulsed with a command with value 2, while the
example: 68_TRGEN represents the General Trip of the OFF output is pulsed with a command with value 1. If in
device and must be connected to the general trip signal steady mode is ON asserted and OFF deasserted with
SMPPTRC_TRIP or equivalent. command 2 and vice versa with command 1.
IED status for IEC 60870-5-103 I103IED IED commands with position and select for IEC
GUID-BA671CCE-A19F-414B-AE8A-8514F5F5DB61 v1
I103IED is a function block with defined IED functions in 60870-5-103 I103POSCMD GUID-658C58A6-8B78-4740-BA83-195990308953 v1
monitor direction. This block uses the parameter I103POSCMD has double-point position indicators that are
FunctionType; the information number parameter is defined getting the position value as an integer (for example, from
for each input signal. the POSITION output of the SCSWI function block) and
sending it over IEC 60870-5-103 (1=OPEN; 2=CLOSE). The
standard does not define the use of values 0 and 3.
Supervison status for IEC 60870-5-103 I103SUPERV
GUID-2C84C469-1A3D-4619-9EED-8CDBCAFBF279 v1
However, when connected to a switching device, these
I103SUPERV is a function block with defined functions for values are transmitted.
supervision indications in monitor direction. This block
includes the FunctionType parameter; the information The BLOCK input will block only the signals in monitoring
number parameter is defined for each output signal. direction (the position information), not the commands via
IEC 60870-5-103. The SELECT input is used to indicate
that the monitored apparatus has been selected (in a select-
Status for user-defined signals for IEC 60870-5-103 before-operate type of control).
I103USRDEF GUID-9C4261B2-3F0A-4FC0-8426-2FDA505530F6 v1
I103USRDEF comprises function blocks with user-defined
input signals in monitor direction. These function blocks DNP3.0 communication protocol SEMOD153688-5 v3
include the FunctionType parameter for each block in the An electrical RS485 serial port, optical serial ports on the
private range, and the information number parameter for serial communication module (SLM), optical Ethernet ports
each input signal. are available for DNP3.0 communication. DNP3.0 Level 2
communication with unsolicited events, time synchronization
to station HMI and gateway, and as interface for horizontal The external galvanic data communication converter
peer-to-peer communication (over LON only). G.703/G.703E1 makes an optical-to-galvanic conversion for
connection to a multiplexer. These units are designed for 64
kbit/s resp 2Mbit/s operation. The converter is delivered
24. Remote communication with 19” rack mounting accessories.
analog mode, the IED can send and receive up to 3 analog The binary input module has 16 optically isolated inputs and
signals and up to 8 binary signals. In binary mode, the is available in two versions, one standard and one with
LDCM can send and receive only binary data (up to 192 enhanced pulse counting capabilities on the inputs to be
binary signals). used with the pulse counter function. The binary inputs are
freely programmable and can be used for the input of logical
The IED can be equipped with up to two short range, signals to any of the functions. They can also be included in
medium range or long range LDCMs. the disturbance recording and event-recording functions.
This enables extensive monitoring and evaluation of
operation of the IED and for all associated electrical circuits.
Line data communication module, short, medium and
long range LDCM SEMOD168481-4 v11 Binary output module BOM
The line data communication module (LDCM) is used for M6938-3 v4
The binary output module has 24 independent output relays
communication between the IEDs situated at a distance
and is used for trip output or any signaling purpose.
<110 km/68 miles or from the IED to the optical-to-electrical
converter with G.703 or G.703E1 interface located at a Static binary output module SOM
SEMOD174196-4 v5
distance < 3 km/1.9 miles away. The LDCM module sends The static binary output module has six fast heavy-duty
and receives data to and from another LDCM module. The static outputs and six change over output relays for use in
IEEE/ANSI C37.94 standard format is used. applications with high speed requirements.
required binary input information. The IRIG-B time synchronizing module is used for accurate
time synchronizing of the IED from a station clock.
mA input module MIM
The milli-ampere input module is used to interface
M15020-3 v4
The Pulse Per Second (PPS) input is supported.
transducer signals in the –20 to +20 mA range from for
Electrical (BNC) and optical connection (ST) for 0XX and
example OLTC position, temperature or pressure
12X IRIG-B support.
transducers. The module has six independent, galvanically
separated channels. Transformer input module TRM
M14875-3 v10
The transformer input module is used to galvanically
Optical Ethernet module
M16073-3 v11 separate and adapt the secondary currents and voltages
The optical Ethernet module (OEM) provides two additional
generated by the measuring transformers. The module has
optical Ethernet ports. The port connectors are:
twelve inputs in different combinations of currents and
• SFP Optical LC (single mode and multi mode)
voltage inputs.
• Galvanic RJ45
Ring lug or compression type connectors can be ordered.
Ethernet ports can be configured as two separate or in
redundant mode PRP or HSR. High impedance resistor unit
M16727-3 v2
The high impedance resistor unit, with resistors for pick-up
Serial and LON communication module (SLM) for SPA/IEC
value setting and a voltage dependent resistor, is available
60870-5-103, LON and DNP 3.0
M14933-3 v6 in a single phase unit and a three phase unit. Both are
The Serial and LON communication module (SLM) is used
mounted on a 1/1 19 inch apparatus plate with compression
for SPA, IEC 60870-5-103, DNP3 and LON communication.
type terminals.
SLM has two optical communication ports for plastic/plastic,
plastic/glass or glass/glass fiber cables. One port is used
for serial communication (SPA, IEC 60870-5-103 or DNP3 Layout and dimensions IP14539-1 v1
port) and the other port is used for LON communication.
Dimensions
IP14826-1
M15243-4 v1
v7
Line data communication module LDCM
M16075-3 v7
Each module has one optical port, one for each remote end
to which the IED communicates.
slaves. No special control signal is needed in this case. Figure 14. Case with rear cover
IEC06000182 V3 EN-US
IEC08000165 V4 EN-US
Figure 15. Case with rear cover and 19” rack mounting kit
Case size A B C D E F G H I
(mm)/
(inches)
6U, 1/2 x 19” 265.9/ 223.7/ 247.5/ 255.0/ 205.8/ 190.5/ 466.5/ 232.5/ 482.6/
10.47 8.81 9.74 10.04 8.10 7.50 18.36 9.15 19
6U, 3/4 x 19” 265.9/ 335.9/ 247.5/ 255.0/ 318.0/ 190.5/ 466.5/ 232.5/ 482.6/
10.47 13.23 9.74 10.04 12.52 7.50 18.36 9.15 19
6U, 1/1 x 19” 265.9/ 448.0/ 247.5/ 255.0/ 430.1/ 190.5/ 466.5/ 232.5/ 482.6/
10.47 17.65 9.74 10.04 16.86 7.50 18.36 9.15 19
The G and H dimensions are defined by the 19” rack mounting kit.
Mounting alternatives
M16079-3 v14
• 19” rack mounting kit
• Flush mounting kit with cut-out dimensions:
– 1/2 case size (h) 254.3 mm/10.01” (w) 210.1 mm/8.27”
– 3/4 case size (h) 254.3 mm/10.01” (w) 322.4 mm/12.69”
– 1/1 case size (h) 254.3 mm/10.01” (w) 434.7 mm/17.11”
• Wall mounting kit
See ordering for details about available mounting
alternatives.
The latest versions of the connection diagrams can be IEEE Synchrophasor certificate IEC/IEEE 60255-118-1:2018,
issued by IEEE SA Test report no.: 2020004393
downloaded from
http://www.hitachienergy.com/protection-control. * Valid for IEDs produced at factory in Sweden.
G3 Compliance Certificate
Sulphur dioxide test for contacts IEC 60068-2-42: 2003
and connections IEC 60068-2-43: 2003
Hydrogen sulphide test for IEC 60068-2-60: 2015
contacts and connections
Flowing mixed gas corrosion test
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Analog inputs
M16988-1 v11 IP15842-1 v1
Table 12. TRM - Energizing quantities, rated values and limits for protection transformer
Description Value
Frequency
Current inputs
Rated current Ir 1 or 5 A
Note! All current and voltage data are specified as RMS values at rated frequency
Table 13. TRM - Energizing quantities, rated values and limits for measuring transformer
Description Value
Frequency
Current inputs
Rated current Ir 1A 5A
Table 13. TRM - Energizing quantities, rated values and limits for measuring transformer , continued
Description Value
Voltage inputs *)
Note! All current and voltage data are specified as RMS values at rated frequency
M6389-1 v5
Power consumption -
each mA board £2W
each mA input £ 0.1 W
Auxiliary DC voltage
M12286-1 v9 IP15843-1 v3
Binary inputs 16 -
Power consumption
24/30 V, 50 mA max. 0.05 W/input -
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
M50609-2 v10
Table 17. BIM - Binary input module with enhanced pulse counting capabilities
Binary inputs 16 -
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
Binary inputs 8 -
Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
M12318-1 v13
Table 19. IOM - Binary input/output module contact data (reference standard: IEC 61810-1)
Function or quantity Trip and signal relays Fast signal relays (parallel reed relay)
0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
M12584-1 v13
Table 20. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-1)
Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
Test voltage across open contact, 1 min 250 V rms 250 V rms
Breaking capacity for AC, cos j > 0.4 250 V/8.0 A 250 V/8.0 A
SEMOD175395-2 v13
Table 21. SOM - Static Output Module data (reference standard: IEC 61810-1): Heavy duty static binary outputs
Number of outputs 6
Table 21. SOM - Static Output Module data (reference standard: IEC 61810-1): Heavy duty static binary outputs, continued
Table 22. SOM - Static Output module data (reference standard: IEC 61810-1): Electromechanical relay outputs
Number of outputs 6
Table 22. SOM - Static Output module data (reference standard: IEC 61810-1): Electromechanical relay outputs, continued
M12441-1 v13
Table 23. BOM - Binary output module contact data (reference standard: IEC 61810-1)
Binary outputs 24
Table 23. BOM - Binary output module contact data (reference standard: IEC 61810-1), continued
GUID-61AA4AEF-D09C-4BA6-9142-B5CA857C0574 v2
Number of outputs 1
Influencing factors
M16705-1 v18 IP15846-1 v1
90-250 V DC ± 20%
Interruption
interval
0–50 ms No restart
Frequency dependence for distance protection operate value fr ±2.5 Hz for 50 Hz ±2.0%/Hz
fr ±3.0 Hz for 60 Hz
Harmonic frequency dependence (20% content) 2nd, 3rd and 5th harmonic of fr ±2.0%
Harmonic frequency dependence for distance protection (10% 2nd, 3rd and 5th harmonic of fr ±10.0%
content)
Harmonic frequency dependence for high impedance differential 2nd, 3rd and 5th harmonic of fr ±10.0%
protection (10% content)
Harmonic frequency dependence for overcurrent protection 2nd, 3rd and 5th harmonic of fr ±3.0%
100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Level 3
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Level 4
Surge immunity test 2-4 kV, 1.2/50ms high energy IEC 60255-26, Zone A
1-2 kV, BOM and IRF outputs IEC 60255-26, Zone B
Conducted common mode immunity test 30-3 V, 15-150 Hz IEC 61000-4-16, Level 4
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Level 5
100 A/m, cont.
Pulse magnetic field immunity test 1000 A/m IEC 61000–4–9, Level 5
Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Level 5
Description Value
Description Value
Altitude up to 2000 m
Change of temperature test Test Nb for 5 cycles at -25°C to +70°C IEC 60068-2-14
Damp heat test, steady state Test Ca for 56 days at +40°C and humidity 93% IEC 60068-2-78
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55°C and humidity 93 to 95% (1 cycle = IEC 60068-2-30
24 hours)
Test According to
Vibration endurance test Class I: Rack, flush and wall mount IEC 60255-21-1
Shock response test Class I: Rack, flush and wall mount IEC 60255-21-2
Shock withstand test Class I: Rack, flush and wall mount IEC 60255-21-2
Bump test Class I: Rack, flush and wall mount IEC 60255-21-2
Unrestrained differential current limit (100-5000)% ofIBase on high voltage ±1.0% of set value
winding
*Note: Data obtained with single three-phase input current group. The operate and reset times for T2WPDIF/T3WPDIF are valid for an static
output from SOM.
**Note: Data obtained with two three-phase input current groups. The rated symmetrical currents are applied on both sides as pre- and after-fault
currents. The fault is performed by increasing one phase current to double on one side and decreasing same phase current to zero on the other
side.
M13062-1 v24
M13081-1 v13
1) The value U 2 Trip/ R should always be lower than Stabilizing resistor thermal rating to allow continuous activation during testing. If this value is exceeded, testing should be done
with a transient faults. Typical value for the thermal rating of the resistor is 100W.
GUID-0BD8D3C9-620A-426C-BDB5-DAA0E4F8247F v5
Independent time delay, zero sequence current at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±35 ms
whichever is greater
Independent time delay, low voltage operation at 2 x Uset to 0 (0.000-60.000) s ±0.2% or ±35 ms
whichever is greater
Reset time delay for startup signal at 0 to 2 x Uset (0.000-60.000) s ±0.2% or ±35 ms
whichever is greater
Technical data
GUID-53E95B58-DE9E-4585-92FC-A03C87527E96 v2
Table 38. Self-adaptive differential protection for 2-winding power transformers PSTPDIF
Time delay for differential current alarm, (0.000-60.000) s ±0.2% or ±25 ms whichever is greater
tAlarmDelay
Definite time delay Ph-Ph and (0.000-60.000) s ±0.2% or ±40 ms whichever is greater
Ph-E operation
SEMOD173239-2 v10
Table 40. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS
Table 40. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS , continued
M16024-1 v12
Table 41. Phase selection, quadrilateral characteristic with fixed angle FDPSPDIS
SEMOD173242-2 v14
Definite time delay Ph-Ph and (0.000-60.000) s ±0.2% or ±60 ms whichever is greater
Ph-E operation
SEMOD173249-2 v8
Table 43. Full-scheme distance protection, quadrilateral for earth faults ZMMPDIS
Definite time delay Ph-Ph and (0.000-60.000) s ±0.2% or ±40 ms whichever is greater
Ph-E operation
SEMOD153649-2 v8
GUID-7617A215-AE7C-47CC-B189-4914F530F717 v8
Table 45. Distance measuring zone, quadrilateral characteristic, separate settings ZMRPDIS, ZMRAPDIS
Table 45. Distance measuring zone, quadrilateral characteristic, separate settings ZMRPDIS, ZMRAPDIS , continued
GUID-9E13C38A-3B6D-402B-98A6-6CDA20632CE7 v5
Table 46. Phase selection, quadrilateral characteristic with settable angle FRPSPDIS
GUID-6C2EF52A-8166-4A23-9861-38931682AA7D v8
Resistance determining the load (0.01 - 5000.00) Pseudo continuous ramp: Ramp of shots:
impedance area - forward ohm/p ±2.0% of set value ±5.0% of set value
Conditions: Conditions:
Tested at ArgLd = 30 degrees Tested at ArgLd = 30 degrees
Definite time delay to trip, Ph-E (0.000-60.000) s ±0.2% of set value or ±35 ms whichever is greater
and Ph-Ph operation
GUID-E65CE996-C0CE-4620-8E01-A96896E62802 v1
Power swing detection operate time (0.000-60.000) s ±0.2% or ±10 ms whichever is greater
Second swing reclaim operate time (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
SEMOD171935-5 v5
Permitted maximum operating time (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
difference between higher and lower
zone
Delay for operation of underreach zone (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
with detected difference in operating
time
Conditional timer for sending the CS at (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
power swings
Conditional timer for tripping at power (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
swings
Timer for blocking the overreaching (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater
zones trip
GUID-88E02516-1BFE-4075-BEEB-027484814697 v2
SEMOD175136-2 v9
GUID-BACA37F7-E945-40BC-BF9D-A65BFC96CA91 v9
Independent time delay for residual (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater
current at 0 to 2 x Iset, tIN
Independent time delay for residual (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater
voltage at 0.8 x Uset to 1.2 x Uset, tUN
Independent dropoff-delay for residual (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater
voltage at 1.2 x Uset to 0.8 x Uset,
tOffUN
GUID-42119BFF-1756-431C-A5A1-0AB637213E96 v3
Table 53. Phase preference logic PPL2PHIZ technical dataPhase preference logic PPLPHIZ technical data
Table 53. Phase preference logic PPL2PHIZ technical dataPhase preference logic PPLPHIZ technical data, continued
Independent time delay for residual (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater
current at 0 to 2 x Iset, tIN
Independent time delay for residual (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater
voltage at 0.8 to 1.2 x Uset, tUN
Independent dropoff-delay for residual (0.000 - 60.000) s ±0.2% or ±25 ms whichever is greater
voltage at 1.2 to 0.8 x Uset, tOffUN
M16043-1 v14
Time delay to operate for the switch (0.03-120.00) s ±0.2% or ±30 ms whichever is greater
onto fault function
Delay time for activation of dead line (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
detection
Drop-off delay time of switch onto fault (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
function
GUID-E8104D00-3183-4F55-89F9-A74B14BFE6FE v7
Number of zones 3 -
Table 56. Protocol reporting via IEEE 1344 and IEC/IEEE 60255-118 (C37.118) PMUREPORT
Signal magnitude:
Voltage phasor (0.1–1.2) x Ur
Current phasor (0.5–2.0) x Ir
Interfering signal:
Magnitude 10% of fundamental signal
Minimum frequency 0.1 x fr
Maximum frequency 1000 Hz
M12342-1 v23
Minimum operate time for inverse (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
curves , step 1-4
Inverse time characteristics, see 16 curve types See table 209, table 210 and table 211
table 209, table 210 and table 211
Table 58. Directional phase overcurrent protection, four steps OC4PTOC , continued
M12340-2 v10
M15223-1 v19
Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir
Independent time delay at 0 to 2 x Iset, step (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
1-4
Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms whichever is greater
step 1-4
Definite Reset Time 0.000 ≤ tReset ≤ 60.000, ±0.2% or ±40 ms whichever is greater
2.0 x Iset to (0 - 0.8) x Iset
Operate time for Iset = 1% (ANSI) 0.01 ≤ k ≤ 15.00, ±10.0% or ±40 ms whichever is greater
0.0 x Iset to (2.0 - 20.0) x Iset
Reset time for Iset = 1% (ANSI) 0.01 ≤ k ≤ 15.00, ±12.0% or ±160 ms whichever is greater.
2.0 x Iset to (0 - 0.4) x Iset
Table 60. Directional residual overcurrent protection, four steps EF4PTOC , continued
Operate time for Iset = 1% (IEC) 0.01 ≤ k ≤ 15.00, ±8.0% or ±100 ms whichever is greater
0.0 x Iset to (2.0 - 20.0) x Iset
Reset time for Iset = 1% (IEC) 0.000 ≤ tReset ≤ 60.000, ±0.2% or ±50 ms whichever is greater
2.0 x Iset to (0 - 0.4) x Iset
Operate time for Iset = 1% (RI&RD) 0.01 ≤ k ≤ 15.00, ±2.0% or ±40 ms whichever is greater
0.0 x Iset to (2.0 - 20.0) x Iset
Reset time for Iset = 1% (RI&RD) 0.000 ≤ tReset ≤ 60.000, ±0.2% or ±50 ms whichever is greater
2.0 x Iset to (0 - 0.4) x Iset
Inverse time characteristics, see Table 209, 16 curve types See Table 209, Table 210 and Table 211
Table 210 and Table 211
*Note: Operate time and reset time are only valid if harmonic blocking is turned off for a step.
GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v8
Table 61. Four step directional negative phase sequence overcurrent protection NS4PTOC
Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms whichever is greater
step 1 - 4
Definite Reset Time 0.000 ≤ tReset ≤ 60.000, ±0.2% or ±40 ms whichever is greater
2.0 x Iset to (0 - 0.8) x Iset
Operate time for Iset = 1% (ANSI) 0.01 ≤ k ≤ 15.00, ±10.0% or ±40 ms whichever is greater
0.0 x Iset to (2.0 - 20.0) x Iset
Table 61. Four step directional negative phase sequence overcurrent protection NS4PTOC , continued
Reset time for Iset = 1% (ANSI) 0.01 ≤ k ≤ 15.00, ±12.0% or ±160 ms whichever is greater.
2.0 x Iset to (0 - 0.4) x Iset
Operate time for Iset = 1% (IEC) 0.01 ≤ k ≤ 15.00, ±8.0% or ±100 ms whichever is greater
0.0 x Iset to (2.0 - 20.0) x Iset
Reset time for Iset = 1% (IEC) 0.000 ≤ tReset ≤ 60.000, ±0.2% or ±50 ms whichever is greater
2.0 x Iset to (0 - 0.4) x Iset
Operate time for Iset = 1% (RI&RD) 0.01 ≤ k ≤ 15.00, ±2.0% or ±40 ms whichever is greater
0.0 x Iset to (2.0 - 20.0) x Iset
Reset time for Iset = 1% (RI&RD) 0.000 ≤ tReset ≤ 60.000, ±0.2% or ±50 ms whichever is greater
2.0 x Iset to (0 - 0.4) x Iset
Inverse time characteristics, see table 16 curve types See table 209, table 210 and table 211
209, table 210 and table 211
Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir
SEMOD173350-2 v17
Table 62. Sensitive directional residual overcurrent and power protection SDEPSDE
Table 62. Sensitive directional residual overcurrent and power protection SDEPSDE, continued
Independent time delay for non-directional (0.000 – 60.000) s ±0.2% or ± 75 ms whichever is greater
residual overvoltage at 0.8 x Uset to 1.2 x Uset
Independent time delay for non-directional (0.000 – 60.000) s ±0.2% or ± 75 ms whichever is greater
residual overcurrent at 0 to 2 x Iset
Independent time delay for directional (0.000 – 60.000) s ±0.2% or ± 170 ms whichever is greater
residual overcurrent at 0 to 2 x Iset
Inverse time characteristics, see table 212, 16 curve types See Table 212, Table 213 and Table 214
Table 213 and Table 214
M12352-1 v16
Operate time: Time constant t = (1–1000) IEC 60255-149, ±5.0% or 250 ms whichever is greater
minutes
I , Ip
2 2
t < σ ln
2 TTrip , TAmb 2
I , T √ I ref
ref
EQUATION13000039 V3 EN-US (Equation 1)
M13266-2 v10
Operate time: Time constant τ = (0.10–500.00) IEC 60255-149, ±5.0% or 250 ms whichever is greater
minutes
∑ I 2 , I p2 ⌡
t < σ √ ln 2
I , ITrip 2
EQUATION1356 V3 EN-US (Equation 2)
Alarm level 1 and 2 (50–99)% of heat content ±2.0% of heat content trip
operate value
Reset level temperature (10–95)% of heat content trip ±2.0% of heat content trip
M12353-1 v16
Phase current level for blocking of contact function (5-200)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir
Time delay for retrip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Time delay for backup trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Time delay for backup trip at multi-phase start at 0 (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
to 2 x Iset
Additional time delay for a second backup trip at 0 (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
to 2 x Iset
Time delay for alarm for faulty circuit breaker (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
M12350-1 v13
M13279-1 v10
SEMOD175152-2 v11
S r = 1.732 × U r × I r
Independent time delay to operate for Step 1 (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
and Step 2 at 2 x Sr to 0.5 x Sr and k=0.000
SEMOD175159-2 v9
Independent time delay to operate for Step 1 (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
and Step 2 at 0.5 x Sr to 2 x Sr and k=0.000
SEMOD175200-2 v10
GUID-6A7DA510-E145-4C5B-A7DC-97BC4258E621 v10
Inverse time characteristic According to IEC 60871-1 (2005) and ±20% or ±200 ms whichever is greater
IEEE/ANSI C37.99 (2000)
GUID-E5718F80-556D-4852-A8F2-90E0F578D763 v10
Table 72. Negative sequence time overcurrent protection for machines NS2PTOC
I 22t = K
Reset time, inverse characteristic, Reset Multiplier = 0.01-20.00 ±10.0% or ±40 ms whichever is greater
step 1 - 2
I 22t = K
Minimum operate time for inverse (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
time characteristic, step 1 - 2
Maximum trip delay at 0.5 x Iset to 2 x (0.00-6000.00) s ±0.2% or ±35 ms whichever is greater
Iset, step 1 - 2
Independent time delay at 0.5 x Iset to (0.00-6000.00) s ±0.2% or ±35 ms whichever is greater
2 x Iset, step 1 - 2
Independent time delay for Alarm at (0.00-6000.00) s ±0.2% or ±35 ms whichever is greater
0.5 x Iset to 2 x Iset
GUID-754FFD93-04C7-4129-B658-32F17F272211 v5
Peak to peak:
±0.2% or ±25 ms whichever is greater
Peak:
±0.2% or ±20 ms whichever is greater
Peak to peak:
Min.= 10 ms
Max. =25 ms
Peak:
Min.= 5 ms
Max. = 20 ms
Peak to peak:
Min.= 5 ms
Max. =20 ms
Peak:
Min.= 5 ms
Max. = 15 ms
Peak to peak:
Min.= 5 ms
Max. =15 ms
Peak:
Min.= 5 ms
Max. = 10 ms
Peak to peak:
5 ms typically at 0 to 2 x Iset
Peak:
1 ms typically at 0 to 2 x Iset
GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v9
Max. = 30 ms
Max. = 30 ms
Independent time delay to operate, (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
overcurrent at 0 to 2 x Iset
Inverse time characteristics, 13 curve types See tables 209 and 210
see tables 209 and 210
Minimum operate time for inverse time (0.00 - 60.00) s ±0.2% or ±35 ms whichever is greater
characteristics
Max. = 30 ms
Independent time delay to operate, (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
undervoltage at 2 x Uset to 0
Overcurrent: -
Critical impulse time 10 ms typically at 0 to 2 x Iset
Impulse margin time 20 ms typically
Undervoltage: -
Critical impulse time 10ms typically at 2 x Uset to 0
Impulse margin time 15 ms typically
GUID-BCCA5F2D-9FF7-4188-9B5D-DA05E8E80CC0 v2
Table 75. Average Power Transient Earth Fault Protection APPTEF , continued
Minimum time delay to declare EF direction (0.04-2.00) s ±0.2% or ±25 ms whichever is greater
"tStart"
Minimum trip time delay "tTrip" (0.00-20.00) s ±0.2% or ±25 ms whichever is greater
Intermittent trip time delay "tTripInterm" (0.00-20.00) s ±0.2% or ±25 ms whichever is greater
Minimum pulse length duration for trip and/or (0.02-1.00) s ±0.2% or ±10 ms whichever is greater
start outputs "tPulseMin"
Operate 3Io current level for cross country (20-1000)% of lBase ±1.0% of Ir at I ≤ Ir
fault detection "CrossCntry_IN>" ±1.0% of I at I > Ir
Time delay to activate cross country fault (0.02-1.00) s ±0.2% or ±25 ms whichever is greater
detection "tCC" at 0 to 2 x Iset
Drop off time delay to de-activate cross Fixed 0.2 s ±0.2% or ±25 ms whichever is greater
country fault detection at 2 x Iset to 0
Time delay to activate circulating current (5.0-60.0) s ±0.2% or ±25 ms whichever is greater
detection "tCircIN" at 0 to 2 x Iset
Drop off time delay to de-activate circulating Fixed 0.5 s ±0.2% or ±25 ms whichever is greater
current detection at 2 x Iset to 0
Definite time delay, step 1 at 1.2 x Uset to (0.00-6000.00) s ±0.2% or ±40ms whichever is greater
0
Definite time delay, step 2 at 1.2 x Uset to (0.000-60.000) s ±0.2% or ±40ms whichever is greater
0
M13304-1 v16
Definite time delay, low step (step 1) at 0 to (0.00 - 6000.00) s ±0.2% or ±45 ms whichever is greater
1.2 x Uset
Definite time delay, high step (step 2) at 0 (0.000-60.000) s ±0.2% or ±45 ms whichever is greater
to 1.2 x Uset
M13317-2 v16
Definite time delay low step (step 1) at 0 (0.00–6000.00) s ± 0.2% or ± 45 ms whichever is greater
to 1.2 x Uset
Definite time delay high step (step 2) at 0 (0.000–60.000) s ± 0.2% or ± 45 ms whichever is greater
to 1.2 x Uset
M13338-2 v13
Curve type IEEE or customer defined ±5.0 % or ±45 ms, whichever is greater
(0.18 × k )
IEEE : t =
( M - 1) 2
where M = (E/f)/(Ur/fr)
Minimum time delay for inverse (0.000–60.000) s ±1.0% or ±45 ms, whichever is greater
function
Maximum time delay for inverse (0.00–9000.00) s ±1.0% or ±45 ms, whichever is greater
function
SEMOD166919-2 v8
Independent time delay for voltage differential (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
alarm at 0.8 x UDAlarm to 1.2 x UDAlarm
Independent time delay for voltage differential (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
trip at 0.8 x UDTrip to 1.2 x UDTrip
Independent time delay for voltage differential (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
reset at 1.2 x UDTrip to 0.8 x UDTrip
SEMOD175210-2 v7
Pulse timer when disconnecting all three (0.050–60.000) s ±0.2% or ±15 ms whichever is greater
phases
Time delay for enabling the functions after (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
restoration
Operate time delay when disconnecting all (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
three phases
Time delay to block when all three phase (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
voltages are not low
Independent time delay at 0 to 2 x Iset (0.00-60.00) s ±0.2% or ±45 ms, whichever is greater
GUID-E6D094FC-3059-4B7A-B171-485B48B9EBC5 v1
Independent time delay at 0 to 2 x Iset (0.00-60.00) s ±0.2% or ±65 ms, whichever is greater
Reset time delay at to 2 x Iset to 0 (0.00 - 60.00) s ±0.2% or ±45 ms, whichever is greater
Minimum operate time for inverse curve (0.00 - 60.00) s ±0.2% or ±65 ms, whichever is greater
GUID-42E90A81-B44D-42C1-B9B5-CD4CDB6E376C v2
Table 84. Phase voltage differential based capacitor bank unbalanced protection SCPDPTDV
Minimum Operate Time for Inverse Curve (0.00-60.00) s ±0.2% or ±70 ms whichever is greater
GUID-47B33B7C-0F5E-4731-A7A8-FF1BDA5D5F41 v1
Independent time delay at 0 to 2 x Uset (0.00-60.00) s ±0.2% or ±65 ms, whichever is greater
Reset time delay at to 2 x Uset to 0 (0.00-60.00) s ±0.2% or ±45 ms, whichever is greater
Minimum operate time for inverse curve (0.00-60.00) s ±0.2% or ±65 ms, whichever is greater
Exponent
é U - UMin ù
t=ê × ( tMax - tMin) + tMin
ëUNom - UMin úû
U = U measured
EQUATION1182 V2 EN-US
Note: The stated accuracy is valid for the voltage range 50 V – 250 V secondary.
1) The settings and test conditions are in accordance with IEC 60255-181 standard (section 6.2 – 6.7).
M14964-1 v14
Note: The stated accuracy is valid for the voltage range 50 V – 250 V secondary.
1) The settings and test conditions are in accordance with IEC 60255-181 standard (section 6.2 – 6.7).
M14976-1 v11
Operate value, start function, at Positive gradient: from 0.05 to 10.00 Hz/s ** ±10.0 mHz/s
symmetrical three phase voltage *, Negative gradient: from -0.05 to -10.00 Hz/s **
StartFreqGrad or Gs per IEC
60255-181 standard
* The settings and test conditions are in accordance with IEC 60255-181 standard (section 6.2 – 6.7).
** The value ±0.05 Hz/s is used as minimum pickup value for frequency gradient.
Note! The stated accuracy is valid for phase-to-earth voltage range from 50 V to 250 V secondary. During testing three phase-to-earth voltages
with magnitude of 110/sqrt(3)=63.5 V were always used.
Independent time delay, overcurrent at 0 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
to 2 x Iset, step 1 - 2
Independent time delay, undercurrent at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
2 x Iset to 0, step 1 - 2
Overcurrent (non-directional):
Undercurrent:
Overcurrent:
Inverse time characteristics, see table 16 curve types See table 209, 210 and table 211
209, 210 and table 211
Overcurrent:
Minimum operate time for inverse curves, (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
step 1 - 2
Independent time delay, overvoltage at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
0.8 x Uset to 1.2 x Uset, step 1 - 2
Independent time delay, undervoltage at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
1.2 x Uset to 0.8 x Uset, step 1 - 2
Overvoltage:
Undervoltage:
Overvoltage:
Inverse time characteristics, see table 4 curve types See table 217
217
Undervoltage:
Inverse time characteristics, see table 3 curve types See table 218
218
High and low voltage limit, voltage (1.0 - 200.0)% of UBase ±1.0% of Ur at U ≤ Ur
dependent operation, step 1 - 2 ±1.0% of U at U > Ur
Overcurrent:
Undercurrent:
Overvoltage:
Undervoltage:
M16069-1 v13
GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v5
Max. = 15 ms
Max. = 30 ms
Operate value, alarm for pilot fuse failure (10.0-80.0)% of UBase ±0.5% of Ur
Max. = 15 ms
Max. = 30 ms
GUID-DAECF9F5-1D0B-43FC-AD29-8F96E05DD0DA v4
DelU> (2.0 - 500.0)% of UBase Instantaneous 1 cycle & Instantaneous 2 cycle mode:±20%
of Ur at U ≤ Ur±20% of U at U > Ur
RMS & DFT Mag mode:±10% of Ur at U ≤ Ur±10% of U at U
> Ur
Operate time for changeat Ur to (Ur + 2 x DelU>)at Instantaneous 1 cycle & Instantaneous 2 cycle mode -
Ur to (Ur + 5 x DelU>) <20msRMS & DFT Mag mode - <30ms
Operate time for jump from Zero degrees to Vector shift mode - <60ms
'AngStVal' + 2 degrees
GUID-ED3FE722-1F29-4340-94E9-6C907C4474F2 v3
DelI> (10.0 - 500.0)% of IBase Instantaneous 1 cycle & Instantaneous 2 cycle mode:
±20% of Ir at I ≤ Ir±20% of I at I > Ir
RMS & DFT Mag mode:
±10% of Ir at I ≤ Ir±10% of I at I > Ir
Operate time for changeat Ir to (Ir + 2 x DelI>)at Ir to Instantaneous 1 cycle & Instantaneous 2 cycle mode -
(Ir + 5 x DelI>) <20ms
RMS & DFT Mag mode - <30ms
Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur
Frequency difference limit between bus and line for synchrocheck (0.003-1.000) Hz ±2.5 mHz
Phase angle difference limit between bus and line for synchrocheck (5.0-90.0) degrees ±2.0 degrees
Voltage difference limit between bus and line for synchronizing and (0.02-0.5) p.u ±0.5% of Ur
synchrocheck
Time delay output for synchrocheck when angle difference between bus (0.000-60.000) s ±0.2% or ±35 ms whichever is
and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 degrees greater
Maximum closing angle between bus and line for synchronizing (15-30) degrees ±2.0 degrees
tMaxSynch, which resets synchronizing function if no close has been (0.000-6000.00) s ±0.2% or ±35 ms whichever is
made before set time greater
Time delay for energizing check when voltage jumps from 0 to 90% of (0.000-60.000) s ±0.2% or ±100 ms whichever is
Urated greater
Operate time for synchrocheck function when angle difference between Min. = 15 ms –
bus and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 Max. = 30 ms
degrees
Operate time for energizing function when voltage jumps from 0 to 90% Min. = 70 ms –
of Urated Max. = 90 ms
M12379-1 v14
Dead time:
shot 1 “t1 1Ph” (0.000-120.000) s ±0.2% or ±35 ms
shot 1 “t1 2Ph” whichever is greater
shot 1 “t1 3Ph “
shot 1 “t1 3PhHS”
Extend three-phase dead time duration “tExtended t1” (0.000-60.000) s ±0.2% or ±35 ms
whichever is greater
Minimum time that circuit breaker must be closed before new sequence is allowed (0.00-6000.00) s ±0.2% or ±35 ms
“tCBClosedMin” whichever is greater
Wait time for the slave to close when WAIT input has reset “tSlaveDeadTime” (0.100-60.000) s ±0.2% or ±35 ms
whichever is greater
Maximum wait time for release from master “tWaitForMaster” (0.00-6000.00) s ±0.2% or ±15 ms
whichever is greater
Wait time after close command before proceeding to next shot “tAutoContWait” (0.000-60.000) s ±0.2% or ±45 ms
whichever is greater
Maximum wait time for fulfilled synchrocheck conditions “tSync” (0.00-6000.00) s ±0.2% or ±45 ms
whichever is greater
Delay time before indicating successful reclosing “tSuccessful” (0.000-60.000) s ±0.2% or ±50 ms
whichever is greater
Maximum wait time for circuit breaker closing before indicating unsuccessful “tUnsucCl” (0.00-6000.00) s ±0.2% or ±45 ms
whichever is greater
SEMOD175215-2 v16
Time delay for lower command when fast step down mode is activated (1.0–100.0) s -
Time delay (long) for automatic control commands (3–1000) s ±0.2% or ±600 ms
whichever is greater
Time delay (short) for automatic control commands (1–1000) s ±0.2% or ±600 ms
whichever is greater
Duration time for the reverse action block signal (30–6000) s ±0.2% or ±600 ms
whichever is greater
Level for number of counted raise/lower within one hour (0–30) operations/hour -
Alarm level of active power in forward and reverse direction at (-9999.99–9999.99) MW ±1.0% of Sr
(10-200)% of Sr and (85-120)% of UBase
Alarm level of reactive power in forward and reverse direction at (-9999.99–9999.99) MVAr ±1.0% of Sr
(10-200)% of Sr and (85-120)% of UBase
Time delay for alarms from power supervision (1–6000) s ±0.2% or ±600 ms
whichever is greater
Time after position change before the value is accepted (1–60) s ±0.2% or ±200 ms
whichever is greater
Table 98. Scheme communication logic for distance or overcurrent protection ZCPSCH
Security timer for loss of guard (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
signal detection
SEMOD166936-2 v8
Table 99. Phase segregated scheme communication logic for distance protection ZPCPSCH
M16039-1 v16
Table 100. Current reversal and weak-end infeed logic for distance protection ZCRWPSCH
Operate time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
logic
Delay time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
SEMOD166938-2 v7
Table 101. Current reversal and weak-end infeed logic for phase segregated communication ZPCWPSCH
Operate time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Delay time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
M16049-1 v10
Table 102. Scheme communication logic for residual overcurrent protection ECPSCH
GUID-CC9A02C2-AAE8-4B8C-A091-D4ED584A2EA7 v1
Delay time on pick-up for current release (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
Delay time on drop-off for current release (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
Delay time on pick-up for MinCurr value (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
M16051-2 v11
Table 104. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH
Operate time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
logic
Delay time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
Minimum trip pulse length, tTripMin (0.000 - 60.000) s ±0.2% or ±15 ms whichever is greater
3-pole trip delay, tWaitForPHS (0.020 - 0.500) s ±0.2% or ±15 ms whichever is greater
GUID-1E1A829D-1F26-433A-8813-1F5A6F225418 v1
3 ms 8 ms 100 ms
SMAGAPC 12 - -
3 ms 8 ms 100 ms
STARTCOMB 32 - -
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v3
3 ms 8 ms 100 ms
TMAGAPC 6 6 -
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v2
3 ms 8 ms 100 ms
ALMCALH - - 5
GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v2
3 ms 8 ms 100 ms
WRNCALH - - 5
GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v2
3 ms 8 ms 100 ms
INDCALH - 5 -
GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3
3 ms 8 ms 100 ms
AND 60 60 160
GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v3
3 ms 8 ms 100 ms
GATE 10 10 20
GUID-0EC4192A-EF03-47C0-AEC1-09B68B411A98 v3
3 ms 8 ms 100 ms
INV 90 90 240
GUID-B2E6F510-8766-4381-9618-CE02ED71FFB6 v2
3 ms 8 ms 100 ms
LLD 10 10 20
GUID-35A795D7-A6BD-4669-A023-43C497DBFB01 v4
3 ms 8 ms 100 ms
OR 78 60 160
GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v2
3 ms 8 ms 100 ms
GUID-BE6FD540-E96E-4F15-B2A2-12FFAE6C51DB v2
3 ms 8 ms 100 ms
RSMEMORY 10 10 20
GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v2
3 ms 8 ms 100 ms
SRMEMORY 10 10 20
GUID-C6C98FE0-F559-45EE-B853-464516775417 v3
3 ms 8 ms 100 ms
GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v2
3 ms 8 ms 100 ms
XOR 10 10 20
GUID-23D4121A-4C9A-4072-BBE3-6DB076EDAB79 v1
3 ms 8 ms 100 ms
ANDQT - 20 100
GUID-27DF23C0-A0B2-4BB0-80B5-FC7B7F7FE448 v1
3 ms 8 ms 100 ms
INDCOMBSPQT - 10 10
GUID-C1E61AE5-22CF-4198-97CF-8C8043EE96D2 v1
3 ms 8 ms 100 ms
INDEXTSPQT - 10 10
GUID-77FEBE9B-0882-4E85-8B1A-7671807BFC02 v2
3 ms 8 ms 100 ms
INVALIDQT 10 6 6
GUID-F25B94C6-9CC9-48A0-A7A3-47627D2B56E2 v1
3 ms 8 ms 100 ms
INVERTERQT - 20 100
GUID-88B27B3C-26D2-47AF-9878-CC19018171B1 v1
3 ms 8 ms 100 ms
ORQT - 20 100
GUID-61263951-53A8-4113-82B5-3DB3BF0D9449 v1
3 ms 8 ms 100 ms
GUID-94C803B4-6C5A-4072-AB5C-20DDE98C9A70 v1
3 ms 8 ms 100 ms
RSMEMORYQT - 10 30
GUID-341562FB-6149-495B-8A63-200DF16A5590 v1
3 ms 8 ms 100 ms
SRMEMORYQT - 10 30
GUID-B6231B97-05ED-40E8-B735-1E1A50FDB85F v1
3 ms 8 ms 100 ms
GUID-1C381E02-6B9E-44DC-828F-8B3EA7EDAA54 v1
3 ms 8 ms 100 ms
XORQT - 10 30
GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v8
3 ms 8 ms 100 ms
SLGAPC 10 10 54
VSGAPC 10 10 100
AND 80 40 100
OR 80 40 100
PULSETIMER 20 20 49
GATE — — 49
TIMERSET 34 30 49
XOR 10 10 69
LLD — — 49
SRMEMORY 10 10 110
INV 80 40 100
RSMEMORY 10 10 20
GUID-65A2876A-F779-41C4-ACD7-7662D1E7F1F2 v4
3 ms 8 ms 100 ms
B16I 6 4 8
GUID-3820F464-D296-4CAD-8491-F3F997359D79 v2
3 ms 8 ms 100 ms
BTIGAPC 4 4 8
GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v3
3 ms 8 ms 100 ms
IB16 12 4 8
GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2
3 ms 8 ms 100 ms
ITBGAPC 4 4 8
GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4
Table 138. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
3 ms 8 ms 100 ms
TEIGAPC 4 4 4
GUID-CEA332FF-838D-42B7-AEFC-C1E87809825E v4
3 ms 8 ms 100 ms
INTCOMP 10 10 10
GUID-3FDD7677-1D86-42AD-A545-B66081C49B47 v4
3 ms 8 ms 100 ms
REALCOMP 10 10 10
GUID-A05B5CAE-209B-4564-9125-D45EC28CDB95 v1
3 ms 8 ms 100 ms
HOLDMINMAX - - 20
3 ms 8 ms 100 ms
INT_REAL - - 20
3 ms 8 ms 100 ms
CONST_INT - - 10
3 ms 8 ms 100 ms
INTSEL - - 5
3 ms 8 ms 100 ms
LIMITER - - 20
3 ms 8 ms 100 ms
ABS - - 20
3 ms 8 ms 100 ms
POL_REC - - 20
3 ms 8 ms 100 ms
RAD_DEG - - 20
3 ms 8 ms 100 ms
CONST_REAL - - 10
3 ms 8 ms 100 ms
REALSEL - - 5
3 ms 8 ms 100 ms
STOREINT - - 10
3 ms 8 ms 100 ms
STOREREAL - - 10
3 ms 8 ms 100 ms
DEG_RAD - - 20
GUID-5E04B3F9-E1B7-4974-9C0B-DE9CD4A2408F v6
Phase angle at symmetrical load (0.1-4.0) × Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir
±0.5 degrees at 0.5 × Ir < I ≤ 4.0 × Ir
GUID-374C2AF0-D647-4159-8D3A-71190FE3CFE0 v5
GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6
GUID-9B8A7FA5-9C98-4CBD-A162-7112869CF030 v5
GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v6
M16080-1 v5
M12760-1 v14
Maximum number of events in the Event list 5000, first in - first out -
GUID-F034B396-6600-49EF-B0A5-8ED96766A6A0 v10
Pressure alarm level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater
Pressure lockout level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater
Time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250 ms whichever is greater
Reset time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250 ms whichever is greater
Time delay for pressure lockout (0.000-60.000) s ±0.2% or ±250 ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250 ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250 ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250 ms whichever is greater
GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v9
Oil alarm level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater
Oil lockout level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater
Time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for oil lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Table 164. Insulation supervision for liquid medium function SSIML , continued
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
GUID-B6799420-D726-460E-B02F-C7D4F1937432 v10
Independent time delay for spring charging (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
time alarm
Independent time delay for gas pressure (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
alarm
Independent time delay for gas pressure (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
lockout
GUID-F6B6ED6B-2488-483C-B068-3F4631F34DC8 v1
Operate level , Warning level 1 and 2 (50 - 700)°C/°F of hot spot ±2.0% of hot spot temperature
temperature
Operate time, Warning level 1 and 2 (50 - 700)°C/°F of hot spot ±200 ms typically
temperature
M12700-1 v5
Function Value
Resolution 1 ms
M13765-1 v6
Function Value
M12702-1 v6
Function Value
Resolution 1 ms
M13747-1 v7
Function Value
M12384-1 v10
Function Value
GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1
Time limit for alarm supervision, tAlarm (0 - 99999.9) hours ±0.1% of set value
Time limit for warning supervision, tWarning (0 - 99999.9) hours ±0.1% of set value
GUID-3763D0D6-AD44-4C9B-91E4-050C0B63C7EA v1
GUID-09EC65AC-C60B-4256-A601-FE2CC90D26EC v4
Fundamental Harmonic
Frequency (0.95 to 1.05) X fr 2nd order to 9th order (0.1 - 0.5) X Ir ±2 mHz
Total Demand (0.2 to 2) X Ir 2nd order to 9th order (0.1 - 0.5) X Ir ±5.0% at I ≤ Ir
Distortion (TDD) ±5.0% of ITDD at I > Ir
Total Harmonic (0.2 to 2) X Ir 2nd order to 9th order (0.1 - 0.5) X Ir ±5.0%
Distortion (ITHD)
Note: The column header Fundamental gives the accuracy of fundamental measurement, which is also assessed in the presence of Harmonics.
This is to check the accuracy of filters in detecting the fundamental component even in case of a distorted signal.
GUID-2068BBA0-9026-48D0-9DEB-301BCB3C600C v4
Fundamental Harmonic
Frequency (0.95 to 1.05) X fr 2nd order to 9th order (0.1 - 0.5) X UF ±2 mHz
Fundamental Harmonic
Harmonic (10 to 150) V 2nd order to 9th order (0.1 - 0.5) X UF ±4.0% of UH
Amplitude
Total Harmonic (10 to 150) V 2nd order to 9th order (0.1 - 0.5) X UF ±3.0%
Distortion (VTHD)
Note: The column header Fundamental gives the accuracy of fundamental measurement, which is also assessed in the presence of Harmonics.
This is to check the accuracy of filters in detecting the fundamental component even in case of a distorted signal.
UF - Applied Voltage Fundamental
UH - Applied Voltage Harmonic (of respective harmonics)
U - Actual Voltage = RMS (UF and UH)
GUID-74F6F38A-8DF9-4343-910D-4E0594C6E21F v2
M14987-1 v8
Metering M13404-2 v5
SEMOD153707-2 v7
Table 180. Function for energy calculation and demand handling ETPMMTR
Function Value
Protocol DNP3.0
Protocol LON
Protocol SPA
GUID-E8B5405C-241C-4DC2-8AB1-3FA77343A4DE v2
Function Value
M11927-1 v2
Function Value
Protocol LON
M11901-1 v2
Function Value
Protocol SPA
M11921-1 v4
Function Value
M12589-1 v6
SEMOD117441-2 v7
SEMOD158710-2 v3
SEMOD55310-2 v16
Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for communication using
any protocol
1) For distances above approximately 60% of maximum specified fiber length special care needs to be taken and fiber used should have an attenuation <0.25 dB/km
Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for communication using
any protocol
GUID-8651FF22-C007-4D53-B7E3-686A30F37CB6 v8
Function Value
GUID-D4AFB582-036A-4A98-88A5-40884091AFD7 v1
Function Value
Performance measurements Recovery time from single link failure for 9 IEDs + 1 switch is < 45 ms and for 39 IEDs + 1 switch is < 185 ms in
ring topology
GUID-48F45DA2-B92E-4977-B9B8-C2FCE8091624 v1
Type of LDCM Short range (SR) Medium range (MR) Long range (LR)
Multi-mode fiber
glass 50/125 µm
Transmission rate / Data rate 2 Mbit/s / 64 kbit/s 2 Mbit/s / 64 kbit/s 2 Mbit/s / 64 kbit/s
Insulation 1 kV
Hardware
IED
M11778-1 v8 SEMOD53385-1 v1
M12327-1 v6
Table 196. Water and dust protection level according to IEC 60529
M11777-1 v8
Electrical safety
GUID-1CF5B10A-CF8B-407D-8D87-F4B48B43C2B2 v3 GUID-2825B541-DD31-4DAF-B5B3-97555F81A1C2 v1
Pollution degree 2 (normally only non-conductive pollution occurs except that occasionally a temporary
conductivity caused by condensation is to be expected)
Connection system
SEMOD53376-2 v6 SEMOD53371-1 v1
Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm 2 (AWG12)
M12583-1 v8
Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)
GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3
GUID-4876834C-CABB-400B-B84B-215F65D8AF92 v3
Data Value
M12331-1 v9
Function Value
Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled ± 1.0 ms typically
measurement values
Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically
GUID-8AEB81D0-1731-46DF-A206-D2E758823575 v2
Supported types of clock Boundary Clock (BC), Ordinary Clock (OC), Transparent Clock (TC)
SEMOD55660-2 v3
SEMOD55693-2 v5
Function Value
Accuracy +/-1μs
SEMOD141136-2 v10
Electrical connector:
Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp
Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
Optical connector:
I = Imeasured/Iset
Reset time for Iset = 10%, 195%, 400% of
IBase
I = Imeasured/Iset
Reset time for Iset = 10%, 195%, 400% of
IBase
GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v6
Table 212. ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection
Reset characteristic:
tr
t = ×k
(I 2
-1)
EQUATION1250-SMALL V1 EN-US
I = Imeasured/Iset
Table 213. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection
I = Imeasured/Iset
TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN-US
I = Imeasured/Iset
Table 214. RI and RD type inverse time characteristics for Sensitive directional residual overcurrent and power protection
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN-US
I = Imeasured/Iset
GUID-2AE8C92E-5DA8-487F-927D-8E553EE29240 v3
Table 215. ANSI Inverse time characteristics for Voltage restrained time overcurrent protection
Reset characteristic:
tr
t = ×k
(I 2
-1)
EQUATION1250-SMALL V1 EN-US
I = Imeasured/Iset
Table 216. IEC Inverse time characteristics for Voltage restrained time overcurrent protection
I = Imeasured/Iset
SEMOD116978-2 v11
U> = Uset
U = Umeasured
k 480
t 2.0
0.035
U Un
32 0.5
Un
IECEQUATION2423 V2 EN-US
k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è U> ø
IECEQUATION2421 V1 EN-US
U< = Uset
U = Umeasured
k × 480
t = + 0.055
2.0
æ 32 × U < -U - 0.5 ö
ç ÷
è U < ø
EQUATION1432-SMALL V1 EN-US
U< = Uset
U = Umeasured
U< = Uset
U = Umeasured
U> = Uset
U = Umeasured
k ⋅ 480
t = + 0.035
2.0
32 ⋅ U − U > − 0.5
U >
EQUATION1437-SMALL V2 EN-US
k ⋅ 480
t = + 0.035
3.0
32 ⋅ U − U > − 0.5
U >
EQUATION1438-SMALL V2 EN-US
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the selection tables, as given in the example below.
The selected qty of each table must be filled in, if no selection is possible the code is 0
Example of a complete code: RET670* 2.2 - F00X00 - A00022403000000110 - B42251450002000200000000000 - C880088832266003622162030028 - D33322020 -
T3333 - E1066600 - F9 - S6 - G000 - H06100014044 - K02021110 - L1100000 - M18142330 - P1112220000000011010 - B1X0 - AC - CA - B - A3X0 -
CD1D1ARGN1N1XXXXXXX - KKKXXHKKLAGXSX
Impedance protection -
B 0 0 0 -
Current protection -
C 00 00 1 0 0 0 -
Station communication -
P 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -
Product RET670*
Product version 2.2
Configuration alternative
RET670 Transformer protection F00
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
A 0 0 0 0 0 0 0 0 0 0 0
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
B 0 0 0
Alternative 6 High speed distance protection for series compensated lines, quadrilateral and mho
High speed distance protection for series comp. lines, quad and ZMFCPDIS 1MRK005907-RH 15 0-2 1)
mho characteristic
Optional with alternative 1
Directional impedance element for mho characteristic ZDMRDIR 1MRK005907-HA 8 0-2
Optional with alternative 3
Phase selection, quadrilateral characteristic with fixed angle FDPSPDIS 1MRK005907-CA 3 0-2
Optional with alternatives 1, 2 and 4
Additional distance protection directional function for earth faults ZDARDIR 1MRK005907-KA 9 0-1
Faulty phase identification with load encroachment FMPSPDIS 1MRK005907-MA 11 0-2
Optional with alternatives 1, 2, 3 and 4
Phase preference logic PPLPHIZ 1MRK005908-DF 16 0-1
Optional with alternatives 5 and 6
Phase preference logic PPL2PHIZ 1MRK005908-DG 17 0-2
Optional with any alternative
Power swing detection, blocking and unblocking ZMBURPSB 1MRK005907-UB 18 0-1
Automatic switch onto fault logic, voltage and current based ZCVPSOF 1MRK005908-AA 19 0-2
Power swing logic PSLPSCH 1MRK005907-VA 20 0-1
PoleSlip/Out-of-step protection PSPPPAM 1MRK005908-CB 21 0-1
Out-of-step protection OOSPPAM 1MRK005908-GA 22 0-1
Underimpedance protection for generators and transformers ZGVPDIS 1MRK005907-TC 26 0-2
1) If qty ZMFPDIS > 1 then either IEC 61850 9-2 process bus communication with 8 MUs or LDCM can be ordered but not both.
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
C 00 00 1 0 0 0
Position 1 2 3 4 5 6 7 8
D 0 1 0
Position 1 2 3 4
T
Position 1 2 3 4
E 00
Position 1
F
Position 1
S
Position 1 2 3
G
Position 1 2 3 4 5 6 7 8 9 10 11
H 0 0
Position 1 2 3 4 5 6 7 8
K 0
Current reversal and weak-end infeed logic for phase segregated ZPCWPSCH 1MRK005920-DB 4 0-2
communication
Local acceleration logic ZCLCPSCH 1MRK005920-EA 5 0-1
Scheme communication logic for residual overcurrent protection ECPSCH 1MRK005920-FB 6 0-1
Current reversal and weak-end infeed logic for residual ECRWPSCH 1MRK005920-GA 7 0-1
overcurrent protection
1) Only one of ZCPSCH/ZPCPSCH can be selected.
2) Only one of ZCRWPSCH/ZPCWPSCH can be selected.
Position 1 2 3 4 5
L 00 0 00
Position 1 2 3 4 5 6 7
M 0
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
P 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Mounting details with IP40 of protection from the front Ordering no Selection Notes and rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12 1MRK002420-BB A
19" rack mounting kit for 3/4 x 19" case or 3xRHGS6 1MRK002420-BA B
19" rack mounting kit for 1/1 x 19" case 1MRK002420-CA C
Wall mounting kit 1MRK002420-DA D 1)
Human machine hardware interface Case size Ordering no Selection Notes and rules
Medium size - graphic display, IEC keypad symbols 1/2 x 19", IEC 1MRK000028-AA B
3/4 x 19”, IEC 1MRK000028-CA
1/1 x 19”, IEC 1MRK000028-BA
Medium size - graphic display, ANSI keypad symbols 1/2 x 19", ANSI 1MRK000028-AB C
3/4 x 19”, ANSI 1MRK000028-CB
1/1 x 19”, ANSI 1MRK000028-BB
Front with status LEDs, Ethernet port, IEC symbols 1/2 x 19", IEC 1MRK000031-AA F
3/4 x 19”, IEC 1MRK000031-CA
1/1 x 19”, IEC 1MRK000031-BA
Front with status LEDs, Ethernet port, ANSI symbols 1/2 x 19", ANSI 1MRK000031-AB G
3/4 x 19”, ANSI 1MRK000031-CB
1/1 x 19”, ANSI 1MRK000031-BB
Selected
P40/X401
P41/X411
No Transformer input module included X0 X0 1)
When ordering I/O modules, observe the maximum quantities according to the tables below.
Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but can also
be freely placed.
Note: The maximum quantity of I/O modules depends on the type of connection terminals.
Case sizes BIM IOM BOM/ MIM Maximum in case
SOM
1/1 x 19” rack casing, 14 6 4 6 14 *)
one (1) TRM
1/1 x 19” rack casing, 11 6 4 6 11 *)
two (2) TRM
3/4 x 19” rack casing, 8 6 4 6 8 *)
one (1) TRM
3/4 x 19” rack casing, 5 5 4 5 5 *)
two (2) TRM
1/2 x 19” rack casing, 3 3 3 1 3 **)
one (1) TRM
*) Including a combination of maximum four modules of type BOM or SOM and six modules of type MIM.
**) Max 2 SOM possible
P4/X41
P5/X51
P6/X61
P7/X71
P8/X81
P9/X91
P10/X101
P11/X111
P12/X121
P13/X131
P14/X141
P15/X151
P16/X161
(front view/rear
view)
Table 261. Station communication, remote end serial communication and time synchronization selection
P30:2/X302
P30:3/X303
P30:4/X304
P30:5/X305
P30:6/X306
P30:6:1/X3061
P30:6:2/X3062
P31:1/X311
P31:2/X312
P31:3/X313
P32:2/X322
P32:3/X323
LDCM mode
1)
Table 261. Station communication, remote end serial communication and time synchronization selection, continued
Station communication, remote end Ordering no Selection Notes and rules
serial communication and time
synchronization
GPS time module 1MRK002282-AB S S S S
IRIG-B time synchronization module, 1MRK002305-AA F F F F
with PPS
Selected
1) The maximum number and type of LDCM modules supported depend on the total amount of I/O and communication modules in the IED.
2) Ethernet SFP is basic in P30:1. P30:6:1 and P30:6:2 require the Optical Ethernet module in P30:6.
3) RS485 not allowed in slot P31:2
4) Max 2 LDCMs can be ordered. Always place LDCM modules on the same board to support redundant communication: in P30:5 and P30:6, P31:2 and P31:3 or P32:2 and P32:3.
5) Default if no LDCM is selected
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: RET670 *2.2-A10X00-A02H03-B1A12-AC-CA-B-A3X0-CDAB1RGN1N1XXXXXXX-KKKKXHKKLAGFSX. Using the code of each position #1-11
specified as RET670*1-2 2-3 3-4 4-5 6-7 7-8-9 9 9 9-10 10 10 10-11 11 11
Product version Configuration alternatives Software options
# 1 - 2 - 3 -
RET670* 2.2 - - -
Binary input/output modules Station communication, remote end serial communication and time
synchronization
10 - 11
-
Position
Product version #1 Notes and rules
Version no. 2.2
Selection for position #1 2.2
High speed distance protection, quad and mho characteristic 1MRK004001-XA B35
Stub protection 1MRK004001-VH B26 4)
Four step directional negative phase sequence overcurrent protection - 2 blocks 1MRK004001-UK C42 8)
Four step directional negative phase sequence overcurrent protection - 3 blocks 1MRK004001-UL C43 9)
Selection for
position #3
1) All fields in the ordering form do not need to be filled in.
2) Only for B40; 2 blocks already included for B40
3) Only for B30/B40
4) Only for B30/B40/A10
5) Only for B30/B40. 1 block already included in B30. 2 blocks already included in B40.
6) Only for B30/B40/A25
7) Only for A25
8) Only for A10/B30
9) Only for B40
10) Only for A10/B30; 1 block already included in B30
11) Only for A25/B40; 1 block already included in B40
12) Only for B30
13) Only for A10/B40
14) Only for B30
1 block already included in B30
15) Only for B40; 1 block already included in B40
16) Only for A25; 2 blocks already included in A25
17) Only for B40/A25; 2 blocks already included in A25
18) Options P23, P24 and P25 require two SFPs placed in pairs.
19) This functionality requires accurate time synchronization, therefore either ‘Precision Time Protocol (PTP) Time synch or GTM or IRIG-B will be required.
Selection for B1
position #4
1) Additional 2nd languages are continuously being added. Please get in touch with local Hitachi Energy sales contact.
Mounting details with IP40 of protection from the front Ordering no #6 Notes and rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12 1MRK002420-BB A 1)
19" rack mounting kit for 3/4 x 19" case or 3xRHGS6 1MRK002420-BA B
19" rack mounting kit for 1/1 x 19" case 1MRK002420-CA C
Wall mounting kit 1MRK002420-DA D 2)
Human machine hardware interface Case size Ordering no #8 Notes and rules
Medium size - graphic display, IEC keypad symbols 1/2 x 19", IEC 1MRK000028-AA B 1)
P41/X411
P3/X31
P4/X41
P5/X51
P6/X61
P7/X71
P8/X81
P9/X91
P10/X101
P11/X111
P12/X121
P13/X131
1)
P30:1/X301
P30:2/X302
P30:3/X303
P30:4/X304
P30:5/X305
P30:6/X306
P30:6:1/X3061
P30:6:2/X3062
P31:1/X311
P31:2/X312
P31:3/X313
P32:2/X322
P32:3/X323
LDCM mode
1)
Accessories IP15151-1 v1
Test switch
SEMOD111888-5 v15
The test system COMBITEST intended for use with the Two winding transformer with external neutral on current
IEDs is described in 1MRK512001-BEN and 1MRK001024- circuits. Two pcs can be used in applications for three
CA. Please refer to the website: winding transformers in single or multi-breaker arrangement
www.hitachienergy.com/protection-control for detailed (ordering number RK926 315-BH).
information.
Three winding transformer with internal neutral on current
Due to the high flexibility of our product and the wide variety circuits (ordering number RK926 315-BX).
of applications possible the test switches needs to be
selected for each specific application. The normally open "In test mode" contact 29-30 on the
RTXP test switches should be connected to the input of the
Select your suitable test switch based on the available test function block to allow activation of functions
contacts arrangements shown in the reference individually during testing.
documentation.
Test switches type RTXP 24 is ordered separately. Please
However our proposals for suitable variants are: refer to Section Related documents for references to
corresponding documents.
Two winding transformer with internal neutral on current
circuits. Two pcs can be used in applications for three RHGS 6 Case or RHGS 12 Case with mounted RTXP 24
winding transformers in single or multi-breaker arrangement and the on/off switch for DC-supply are ordered separately.
(ordering number RK926 315-BD) Please refer to Section Related documents for references to
corresponding documents.
Protection cover
M15040-3 v9
Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK002420-AE
Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK002420-AC
Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity: 1MRK002420-AB
Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK002420-AA
High impedance resistor unit with resistor and voltage dependent resistor 20-100V, 1ph Quantity: 1 2 3 RK 795 101-MA
High impedance resistor unit with resistor and voltage dependent resistor 20-100V, 3ph Quantity: RK 795 101-MB
High impedance resistor unit with resistor and voltage dependent resistor 100-400V, 1ph Quantity: 1 2 3 RK 795 101-CB
High impedance resistor unit with resistor and voltage dependent resistor 100-400V, 3ph Quantity: RK 795 101-DC
Combiflex
IP15161-1 v1
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
SEMOD130267-5 v9
Mounting kit
Side-by-side mounting kit Quantity: 1MRK000420-Z
SEMOD131414-4 v5
The IED Connect USB flash drive contains user documentation, Connectivity packages and LED label templates.
Specify quantity of IED Connect USB flash drive requested. Quantity: 1MRK002700-AA
User documentation
Specify the number of printed manuals requested
Application manual IEC Quantity: 1MRK504163-UEN
Communication protocol manual, IEC 61850 Edition 2 and Edition 2.1 IEC Quantity: 1MRK511393-UEN
For our reference and statistics we would be pleased to be provided with the following application data: