Air Circuit
Breakers
Dimensions 100
ACB
Product Overview
HG Series
90 º
Equipped with Various Accessories and Highly Convenient Maintenance by Attaching Draw-In/Out
Functional Protection Trip Relay (OCR) Device to the Body
Over Current Relay (Trip Relay)
Apart from the basic protection functions, OCR has reinforced
power monitoring functions such as temperature monitoring,
fault recording and storage etc., enabling stable power supply.
H Type
Standard Cradle Cradle Retrofit
˙L/S/I/G Functions
˙External Power
˙Individual Continuous Power Contact
˙Fault Recording (256) and Waveform (4 Cycles, Check Via
Communication)
˙L/S/I/G Minute Current Adjustment
˙Voltage/Current Harmonics (1 st ~ 63 th) Analysis
˙View 3 Phase Waveform
Air Circuit Breakers 5
VCB
Equipped with Temperature Sensor
Reliable high temperature measurement is possible following the sensor measurement of the heat source (Range of measurement:
-5 ~ 250 degrees)
ACB
Screw PH(+) PS/W M4 L8
MCCB
Measurement Point
RCTU Sensor
Distance = 40 ~ 80 mm Busbar
and applied according to the usage environment and conditions ˙CB Certification (DEKRA, KERI):IEC 60947-1, 2
permitted by the standards. ˙CE Mark
˙CCC Certification
˙Vessel Certification:LR, ABS, KR, BV, GL, NK, RINA, DNV, RS
˙9 Major Vessel Certifications:KR, GL, LR, ABS, BV, NK, RINA, DNV, RS
6 Air Circuit Breakers
Technical Data
External Structure
❶
❶
❷
❷
⓰ ⓫
⓰ ⓫
❸ ⓬
❸ ⓬
❹ ⓭ ⓭
❹
❺
❺
❻ ❻
⓮ ❼
⓮
❽
❾
⓱
❿
VCB
Internal Structure
❶
❷
❸
❹
ACB
❻
❾ ❼
❽
MCCB
⓬
❻ ❶
❹ ⓰
⓮ ⓱
❽ ⓲
❾
⓳
⓴
MS
⓫ ⓲
⓯
※ HG Series air circuit breaker has been designed so that upon closing, the N phase is closed earlier than R, S, T phase and upon opening, the N phase is disconnected last in order to
reduce burden of main contact and to prevent ripple effect of accident of N phase.
8 Air Circuit Breakers
Technical Data
Connection Method
User convenience has been reinforced by allowing each terminal to be rotated 90 degrees directly on site depending on the busbar type
of low voltage switchgear.
Standard Type
Combined Type
※ Terminal change is only possible for HGS/HGN A frame 630 ~ 1,600 A, B frame 2,000 ~ 3,200 A.
Front type is a terminal form that is suitable for switchgear with spatial restrictions.
Horizontal/vertical change above 4,000 A requires separate parts so please contact our company.
In case of B frame, 3,200 A terminal is provided as for the front type provided separately for 2,000/2,500 A.
Front type terminal has to be purchased separately.
Air Circuit Breakers 9
VCB
Convenient Connection Method
As for HG Series air circuit breaker, 4 types of mounting
(Connected, test, isolated, removed) are possible and offer easy
maintenance.
ACB
Connected Position Test Position
As a commonly used status, the main circuit and control circuit are both As a status in which the main circuit is isolated and the control circuit is
connected. connected, the circuit breaker can be turned On/Off with the switchgear
door closed.
MCCB
Isolated Position Removed Position
With the main circuit and control circuit both isolated, the air circuit cannot The air circuit has completely been removed from the cradle.
be turned On/Off.
MS
RELAY
10 Air Circuit Breakers
Technical Data
Various Accessories (Main Unit)
❷,❺
❹,❻
❸,❺
⓲
⓳
⓱ ❾ ❼,❽
⓬ ⓯
⓭ ❶ ❽
VCB
Various Accessories (Cradle)
❶,❷,❸
⓫
❿,❻
ACB
⓫,❼
MCCB
❺
MS
❾
❿
※ 1) 70 kA is DEKRA certified Life time is the limit lifespan and is not the guaranteed lifespan. In case of maintenance,
2) 4,000 AF it is charged. In the event of abnormalities in accessories during use, it can be replaced.
3) In case of MCR and override setting, INST is 50 ms. Quality Assurance:Based on IEC 60947-2’s number of opening/closing within the
warranty period.
D W D
W D W
Air Circuit Breakers 13
VCB
Over Current Relay (OCR)
Function General Feeder Generator (Marine Type)
ACB
STD (Short Time) ● ● ● ● ● ● ● ● ●
INST (Instantaneous) ● ● ● ● ● ● ● ● ●
Pre-Trip Alarm - ● ● ● ● ● - ● ●
Ground Fault Trip ● ● - - ● ● - - -
● ●
Outer CT ZCT Earth
Ground 2) Leakage 3)
ELT Function - - - - - - -
(Ground fault (Below 30 A)
at more than
30 A)
Thermal Function ● ● ● ● ● ● ● ● ●
Field Test - ● ● ● ● ● - ● ●
Fail Safe ● ● ● ● ● ● ● ● ●
Indication
True RMS
MCCB
● ● ● ● ● ● ● ● ●
Detection Method
LED Indication per
- ● ● ● ● ● - ● ●
Trip Type
PTA, L, PTA, L, PTA, L, PTA, L, PTA, L, PTA, L, PTA, L,
Fault LED L 1) L 1)
S/I, G S/I, leakage S/I, leakage S/I, G S/I, G S/I S/I
Real-Time LCD
Indication of Load - ● ● ● ● ● - ● ●
Rate per Phase
Measurement LCD - ● ● ● ● ● - ● ●
Output Contact
Integrated
Instantaneous ● - - - - - - -
Contact (1a)
Individual Continuous
- ● ● ● ● ● - ● 4) ● 4)
Contact (4a)
Operation
MCR - 〇 〇 〇 〇 〇 - 〇 〇 MS
Communication NFC Modbus-RTU Modbus-RTU Modbus-RTU Modbus-RTU Modbus-RTU NFC Modbus-RTU Modbus-RTU
Event/Fault Recording ● ● ● ● ● ● ● ● ●
※ ●:Standard, 〇:Option
1) Indicates reserve before operation during long time delay.
2) ZCT designated by the customer is used.
3) ZCT designated by our company is used.
4) As for marine type, individual continuous contact is 3a.
RELAY
14 Air Circuit Breakers
˙Upstream:ACB HGN/HGS
˙Downstream:MCB HGD, MCCB HGM/HGP
HG-ACB HG-MCCB
Upstream
Item ACB
Downstream
1 3 T T T T T T T T T T T T
2 3 T T T T T T T T T T T T
3 3 T T T T T T T T T T T T
4 3 T T T T T T T T T T T T
5 3 T T T T T T T T T T T T
6 3 T T T T T T T T T T T T
10 3 T T T T T T T T T T T T
HGD63E 13 3 T T T T T T T T T T T T
B, C, D Curve 15 3 T T T T T T T T T T T T
16 3 T T T T T T T T T T T T
20 3 T T T T T T T T T T T T
25 3 T T T T T T T T T T T T
32 3 T T T T T T T T T T T T
40 3 T T T T T T T T T T T T
50 3 T T T T T T T T T T T T
63 3 T T T T T T T T T T T T
1 4.5 T T T T T T T T T T T T
2 4.5 T T T T T T T T T T T T
3 4.5 T T T T T T T T T T T T
4 4.5 T T T T T T T T T T T T
5 4.5 T T T T T T T T T T T T
6 4.5 T T T T T T T T T T T T
MCB
10 4.5 T T T T T T T T T T T T
HGD63S 13 4.5 T T T T T T T T T T T T
B, C, D Curve 15 4.5 T T T T T T T T T T T T
16 4.5 T T T T T T T T T T T T
20 4.5 T T T T T T T T T T T T
25 4.5 T T T T T T T T T T T T
32 4.5 T T T T T T T T T T T T
40 4.5 T T T T T T T T T T T T
50 4.5 T T T T T T T T T T T T
63 4.5 T T T T T T T T T T T T
1 6 T T T T T T T T T T T T
2 6 T T T T T T T T T T T T
3 6 T T T T T T T T T T T T
4 6 T T T T T T T T T T T T
5 6 T T T T T T T T T T T T
HGD63N/M 6 6 T T T T T T T T T T T T
B, C, D Curve 10 6 T T T T T T T T T T T T
13 6 T T T T T T T T T T T T
15 6 T T T T T T T T T T T T
16 6 T T T T T T T T T T T T
20 6 T T T T T T T T T T T T
25 6 T T T T T T T T T T T T
※ T Selective breaking is possible in all sectors, Selective breaking is impossible in this sector.
Air Circuit Breakers 15
VCB
HG-MCB
˙Upstream:ACB HGN/HGS
˙Downstream:MCB HGD, MCCB HGM/HGP
HG-ACB HG-MCCB
Upstream
Item ACB
Downstream
ACB
32 6 T T T T T T T T T T T T
HGD63N/M 40 6 T T T T T T T T T T T T
B, C, D Curve 50 6 T T T T T T T T T T T T
63 6 T T T T T T T T T T T T
1 10 T T T T T T T T T T T T
2 10 T T T T T T T T T T T T
3 10 T T T T T T T T T T T T
4 10 T T T T T T T T T T T T
5 10 T T T T T T T T T T T T
6 10 T T T T T T T T T T T T
10 10 T T T T T T T T T T T T
MCB HGD63H 13 10 T T T T T T T T T T T T
MCCB
B, C, D Curve 15 10 T T T T T T T T T T T T
16 10 T T T T T T T T T T T T
20 10 T T T T T T T T T T T T
25 10 T T T T T T T T T T T T
32 10 T T T T T T T T T T T T
40 10 T T T T T T T T T T T T
50 10 T T T T T T T T T T T T
63 10 T T T T T T T T T T T T
80 10 T T T T T T T T T T T T
HGD125
100 10 T T T T T T T T T T T T
B, C, D Curve
125 10 T T T T T T T T T T T T
16 30 T T T T T T T T T T T T
20 30 T T T T T T T T T T T T
25 30 T T T T T T T T T T T T
32 30 T T T T T T T T T T T T MS
40 30 T T T T T T T T T T T T
HGM100
50 30 T T T T T T T T T T T T
63 30 T T T T T T T T T T T T
75 30 T T T T T T T T T T T T
80 30 T T T T T T T T T T T T
100 30 T T T T T T T T T T T T
MCCB 16 55 T T T T T T T T T T T T
20 55 T T T T T T T T T T T T
25 55 T T T T T T T T T T T T
32 55 T T T T T T T T T T T T
40 55 T T T T T T T T T T T T
RELAY
HGM125 50 55 T T T T T T T T T T T T
63 55 T T T T T T T T T T T T
75 55 T T T T T T T T T T T T
80 55 T T T T T T T T T T T T
100 55 T T T T T T T T T T T T
125 55 T T T T T T T T T T T T
※ T Selective breaking is possible in all sectors, Selective breaking is impossible in this sector.
MCCB Rated Breaking Current:Based on AC 440/460 V, HGM L-Type, HGP X-Type
16 Air Circuit Breakers
˙Upstream:ACB HGN/HGS
˙Downstream:MCB HGD, MCCB HGM/HGP
HG-ACB HG-MCCB
Upstream
Item ACB
Downstream
100 55 T T T T T T T T T T T T
125 55 T T T T T T T T T T T T
150 55 T T T T T T T T T T T T
160 55 T T T T T T T T T T T T
HGM250
175 55 T T T T T T T T T T T T
200 55 T T T T T T T T T T T T
225 55 T T T T T T T T T T T T
250 55 T T T T T T T T T T T T
250 85 T T T T T T T T T T T T
300 85 T T T T T T T T T T T T
HGM400
350 85 T T T T T T T T T T T T
400 85 T T T T T T T T T T T T
500 85 T T T T T T T T T T T
HGM630
630 85 T T T T T T T T T T T
700 85 T T T T T T T T T T
HGM800
800 85 T T T T T T T T T T
16 150 T T T T T T T T T T T T
20 150 T T T T T T T T T T T T
25 150 T T T T T T T T T T T T
32 150 T T T T T T T T T T T T
MCCB 40 150 T T T T T T T T T T T T
HGP125D
50 150 T T T T T T T T T T T T
63 150 T T T T T T T T T T T T
80 150 T T T T T T T T T T T T
100 150 T T T T T T T T T T T T
125 150 T T T T T T T T T T T T
100 150 T T T T T T T T T T T T
125 150 T T T T T T T T T T T T
150 150 T T T T T T T T T T T T
160 150 T T T T T T T T T T T T
HGP250
175 150 T T T T T T T T T T T T
200 150 T T T T T T T T T T T T
225 150 T T T T T T T T T T T T
250 150 T T T T T T T T T T T T
300 150 T T T T T T T T T T T T
HGP400 350 150 T T T T T T T T T T T T
400 150 T T T T T T T T T T T T
500 150 T T T T T T T T T T T
HGP630
630 150 T T T T T T T T T T T
700 150 T T T T T T T T T T
HGP800
800 150 T T T T T T T T T T
※ T Selective breaking is possible in all sectors, Selective breaking is impossible in this sector.
MCCB Rated Breaking Current:Based on AC 440/460 V, HGM L-Type, HGP X-Type
Air Circuit Breakers 17
Accessories
VCB
Over Current Relay (OCR)
External
❷ ❸
❶ ❹
❺
ACB
❼
❽
⓫
❾
⓬ ❿
⓯
⓭ ⓱
MCCB
⓰
⓮
MS
❶ PTA Signal LED ❽ LTD Test Button ⓯ STD Pick Up Setting GFT/STD (Inverse Time Setting).,
❷ LTD Signal LED ❾ Movement Button ⓰ STD Operational Time Setting MCR On/Off Setting Switch
❸ STD/INST Signal LED ❿ Enter Button ⓱ INST Pick Up Setting In (Rated Current) Setting
❹ GFT/ELT Signal LED ⓫ Reset Button ⓲ PTA Pick Up Setting Temporary Test Connection Jack
❺ Com. Signal LED ⓬ Menu Button ⓳ PTA Operational Time Setting Model Name
❻ LCD/NFC Antenna (LN, SN) ⓭ LTD Pick Up Setting GFT/ELT Pick Up Setting Battery
RELAY
※ Self-power functions normally in the case of 10 % for 3 phases and 30 % for a single phase. However, when 200 A ~ 320 A CT is used, it functions normally in case of 50 % for 3 phase
and more than 100 % for single phase.
When using MCR function, mark B8 in the name of order type. Auxiliary contact point is 4a5b.
The lifespan of the battery is usually 10 years so in case it is time for replacement, contact our customer support division and services can be received at a cost.
High/low test function is automatically disabled when a load current is applied.
18 Air Circuit Breakers
Accessories
Over Current Relay (OCR)
Enhancement of Over Current Relay (OCR) Functions
Over current relay (OCR) built in the HG Series air circuit breaker has reinforced power monitoring functions such as temperature
monitoring, fault recording other than the basic protection function, ultimately enabling stable power supply.
Externals
50 Hz 50 51 52 53 54
Frequency
60 Hz 60 61 62 63 64
VCB
Item General Feeder Generator (Marine Type)
H Type N Type A Type P Type
Model Name
GPR-LH GPR-SN GPR-SA GPR-SP
ACB
Externals
MCCB
50 Hz 55 57 58 59
Frequency
60 Hz 65 67 68 69
Accessories
Over Current Relay (OCR)
Appearance and Setting Value
Nominal Switching 5A
Capacity (Resistive Load) 277 VAC
Max. Switching Power
1,385 VA
(Resistive Load)
Rating
Max. Switching Voltage 277 VAC
Max. Switching Current 5A
Max. Switching Capacity 100 mA
(Reference Value) 5 VDC
Protection Functions
VCB
GPR-LA (51, 61)
˙Overload Protection ˙RS-485 Communication/Modbus-RTU
- Long time delay ˙4a DO (Digital Output)
˙Short Circuit Protection - Contact specification
- Short time delay, instantaneous trip
- l²t On/Off optional (for STD)
Nominal Switching 5A
˙Ground Fault Protection Capacity (Resistive Load) 277 VAC
- l²t On/Off optional Max. Switching Power
1,385 VA
ACB
˙Neutral Wire Protection (Resistive Load)
Rating
- 3 Pole:No protection Max. Switching Voltage 277 VAC
- 4 Pole:Non, 50 %, 100 % (×Ir, Isd, Ii) Max. Switching Current 5A
Max. Switching Capacity 100 mA
˙Measurement and Display
(Reference Value) 5 VDC
- 3 Phase current
˙Realization of Protective Coordination by ˙Protection Features
ZSI (Zone Selective Interlocking)
˙Fault Recording
- Records up to 256 fault information
Ir
on fault type, fault phase, fault value,
IP
occurrence time of fault tr
˙Event Recording Tp
- Records up to 200 events of devices,
I2t on
MCCB
records changes in protection trip relay Isd
Ig I2t on
information tsd
tg
˙Pre-Trip Alarm
- Prevent unnecessary overload trip by I2t off Ii
I2t off
setting according to rated current (In)
˙Field Test
- Simulation of long time, short time,
instantaneous
Protection Functions
± 20 % (Ig≤0.4 In)
Grounding
I2t Off 0.05 0.1 0.2 0.3 0.4 0.5
Protection Time Delay (sec) tg
I2t On 0.05 0.1 0.2 0.3 0.4 0.5
@ 1×Ict
Accuracy:± 20 % Min. Trip Time (ms) 20 80 160 260 360 460
(I t Off)
2
Max. Trip Time (ms) 80 140 240 340 440 540
Current Setting (A)
Ip = In×… 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 Non
Pre-Alarm Accuracy:± 15 %
Time Delay (sec) tp 5 10 15 20 40 60 80 120 160
22 Air Circuit Breakers
Accessories
Over Current Relay (OCR)
Appearance and Setting Value
Protection Functions
VCB
GPR-LAZ (53, 63)
˙Overload Protection ˙Field Test
- Long time delay - Simulation of long time, short time,
- Thermal operation instantaneous
˙Short Circuit Protection ˙4a DO (Digital Output)
- Short time delay, instantaneous trip - Contact specification
- l²t On/Off optional (for STD)
˙Earth Leakage Protection Nominal Switching 5A
ACB
- Uses our company’s supply of 1,000:1 ZCT Capacity (Resistive Load) 277 VAC
- GPR’s operation setting is set based on Max. Switching Power
1,385 VA
the primary (Resistive Load)
Rating
˙Neutral Wire Protection Max. Switching Voltage 277 VAC
- 3 Pole:No protection Max. Switching Current 5A
- 4 Pole:Non, 50 %, 100 % (×Ir, Isd, Ii) Max. Switching Capacity 100 mA
(Reference Value) 5 VDC
˙Measurement and Display
- 3 Phase current
˙Protection Features
˙Realization of Protective Coordination by
ZSI (Zone Selective Interlocking)
˙Fault Recording
- Records up to 256 fault information Ir
on fault type, fault phase, fault value, IP
tr
occurrence time of fault
MCCB
Tp
˙Event Recording
- Records up to 200 events of devices, I2t on
Isd
records changes in protection trip relay Ig I2t on
tsd
information tg
Protection Functions
Accessories
Over Current Relay (OCR)
Appearance and Setting Value
˙Fault Recording
- Records up to 256 fault information ˙Protection Features
on fault type, fault phase, fault value,
occurrence time of fault
Ir
˙Event Recording IP
- Records up to 256 events of devices, records tr
changes in protection trip relay information Tp
˙Pre-Trip Alarm I2t on
Isd
- Prevent unnecessary overload trip by Ig I2t on
tsd
setting according to rated current (In) tg
˙Field Test
I2t off Ii
- Simulation of long time, short time, I2t off
instantaneous
Protection Functions
VCB
GPR-SN (57, 67)
˙Overload Protection ˙Protection Features
- Long time delay
˙Short Circuit Protection
- Short time delay, instantaneous trip Ir
- l²t On/Off optional (for STD)
tr
˙Self-Power
˙Equipped with NFC Functions
I2t on
ACB
- Incident information can be received to Isd
the mobile phone tsd
- Introduction of function and app
installation method:Refer to Page 34 Ii
I2t off
˙1a DO (Digital Output)
- Contact specification
Nominal Switching 5A
Capacity (Resistive Load) 277 VAC
Max. Switching Power
1,385 VA
(Resistive Load)
Rating
Max. Switching Voltage 277 VAC
Max. Switching Current 5A
MCCB
Max. Switching Capacity 100 mA
(Reference Value) 5 VDC
Protection Functions
Accessories
Over Current Relay (OCR)
Appearance and Setting Value
Protection Functions
VCB
GPR-SP (59, 69)
˙Overload Protection ˙RS-485 Communication/Modbus-RTU
- Long time delay ˙Need to Connect Voltage Module for
˙Short Circuit Protection Voltage Measurement
- Short time delay, instantaneous trip ˙3a DO (Digital Output)
- l²t On/Off optional (for STD) - Contact specification
˙Neutral Wire Protection
- 3 Pole:No protection
ACB
- 4 Pole:Non, 50 %, 100 % (× Ir, Isd, Ii) Nominal Switching 5A
Capacity (Resistive Load) 277 VAC
˙Over-Voltage/Under-Voltage/Imbalance
Max. Switching Power
Protection (Resistive Load)
1,385 VA
Rating
˙Measurement and Display Max. Switching Voltage 277 VAC
- 3 Phase current/voltage/power/power Max. Switching Current 5A
factor/power quantity/phase/demand Max. Switching Capacity 100 mA
˙Realization of Protective Coordination by (Reference Value) 5 VDC
MCCB
- Records up to 200 events of devices,
Tp
records changes in protection trip relay
I2t on
information Isd
˙Pre-Trip Alarm tsd
- Prevent unnecessary overload trip by
setting according to rated current (In) I2t off Ii
˙Field Test
- Simulation of long time, short time,
instantaneous
Protection Functions
Pre-Alarm Accuracy:± 15 %
Time Delay (sec) tp @ (lp×1.2) 5 10 15 20 40 60 80 120 160
28 Air Circuit Breakers
Accessories
Over Current Relay (OCR)
Operation Characteristics
Tp (S type)
Ip
Ir
tr
Ig2t on
Air Circuit Breakers 29
Ig2t off
Ig
Tg
I I
VCB
t t
I2t on
Instantaneous (INST)
I2t off I∆ n
Isd Standard Current Setting
Tsd - The scale marks the magnification of [In].
- The setting range of current is ∆Ta 9-step method of Non, 2, 3, 4, 6, 8, 10, 12, 15×[In].
I I
- No protection in case [Ii] is set as [Non], the protection does not function.
ACB
t t
Tp (S type)
Ip
Ii
Tp
I I
MCCB
Ground Fault Trip (GFT)
Standard Current Setting
˙L Type
- The numbers indicate scale for the 1 st currnet of OCR [Ict].
- The setting range of current is a 10-step method of Non, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7,
0.8, 1.0×[Ict].
MS
Time Delay Setting
t ˙L Type
- The marking indicates the relay operation based on the time of 120 % of [Ig] in msec
with definite time operation.
- The setting range is a 6-step method of 50, 100, 200, 300, 400, 500 msec.
Ig2t on
- It functions in case of 100 % lct of inverse time in case of lg²t on setting.
Ig2t off
Ig
Tg
I
RELAY
I∆ n
30 Air Circuit Breakers
Accessories
Over Current Relay (OCR)
t
Operation Characteristics
t
t
Tp (S type)
Pre-Trip Alram
Ip (PTA)
I∆ n
Standard Current Setting
Tp ˙L Type
∆T I
- The scale marks the magnification of [In] with inverse time operation.
I
- The setting range of current is a 10-step method of Non, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85,
0.9, 0.95, 1.0 of [In].
˙S Type
- The scale marks the magnification with regards to [Io] with inverse time operation.
t - The setting range of current is a 10-step method of Non, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95,
1.0, 1.05, 1.1×[Io].
VCB
Characteristic Curve
General Feeder
3
Setting Range
Hour
1
❷ Short Time Delay Current 50
40
Setting Range 30
20
❸ Instantaneous Tripping 10
Minute
ACB
8
Current Setting Range 6
5
4
3
❹ Ground Fault Trip Current 2
Setting Range 1
50
40
❺ Pre-Trip Alarm Current
30
20
Setting Range
10
8
6
5
4
3
2
1
0.8
Second
0.6
0.5
0.4
500 ms 500 ms
0.3
0.2
0.1
0.08
0.06
0.05 50 ms 50 ms
0.04
MCCB
0.03
0.02
0.01
0.008
0.006
0.005
7
8
9
10
15
20
30
40
50
60
70
80
90
100
60
70
80
90
100
125
150
200
250
300
400
500
600
700
800
900
1,000
1,500
2,000
2,500
3,000
Percent for rated Primary Current of OCR [lct] Percent for rated Current [In]
Generator
3
Setting Range
Hour
MS
40
Setting Range 30
20
❸ Instantaneous Tripping 10
8
Minute
10
8
6
5
4
3
2
1
0.8
Second
0.6
0.5 500 ms
0.4
0.3
RELAY
0.2
0.1
0.08
0.06 50 ms
0.05
0.04
0.03
0.02
0.01
0.008
0.006
0.005
7
8
9
10
15
20
30
40
50
60
70
80
90
100
125
150
200
250
300
400
500
600
700
800
900
1,000
1,500
2,000
2,500
3,000
Accessories
Measurement
Dimension
46.6 Unit:mm
56.4
42
91.4
75
27.6
29.1
Voltage Module
GPR-LP/LH/SP Trip Relay has to be installed with a voltage module to measure the voltage.
Voltage Input Range:AC 69 ~ 690 V
Voltage Connection
VR VS VT VN
A B C
VN GPR
VT
VS
VR
ACB Terminal
4P 4Wire / 3P 4Wire
VR VS VT VN
A B C N
VN GPR
VT
VS
VR
ACB Terminal
Air Circuit Breakers 33
VCB
Zone Selective Interlocking
Zone Selective Interlocking System
Zone selective interlocking function involves the breaker in the fault sector detecting malfunction for selective protection coordination.
The circuit breaker in the fault sector sends a lock signal to the back-up protection circuit breaker by force to delay the operation and the
circuit breaker in the fault sector operates instantaneously to enable selective protection coordination of the system.
Examples
˙First Fault Occurrence ˙Fault 2 Occurrence
In case fault 1 occurs in selective zone (Zone 3), ACB 3-2 In case a fault occurs at the lower end of ACB 2-1, the circuit
ACB
functions immediately and ACB 3-2 relay triggers a ZSI signal breaker in zone 3 region is unable to detect. Therefore, the relay
in ACB 2-1 relay to maintain a delay so that the circuit breaker of ACB 2-1 is unable to receive any signal from the lower end so,
does not function, preventing the expansion of fault region. immediately, ACB 2-1 functions, triggering a ZSI signal to ACB 1
to prevent the expansion of fault range.
MCCB
ACB 1
OUT
ZONE 1
IN
ZSI Connection
using ZSI.
34 Air Circuit Breakers
Accessories
Over Current Relay (OCR)
System Diagram
R S T N
ACB Trip
ACB
Display
(LCD, LED)
MHT
Trip
Rogowski Relay Operation
CT Measurement
Part Selection
PTA Contact
MCU
LTD Contact
External
Contact STD/INST Contact
GFT Contact
Power
CT Common Contact
Self Power
Trip Relay
ZSI Output +
ZSI Output -
ZSI
ZSI Input +
ZSI Input -
Communication Function
VCB
Circuit Diagrams
GPR-LN
Over-Current
Main Circuit
Protective Device
NCT
k ℓ
ACB
R S T N 21 29 30
NCT NCT
R S T N L 1 2
Over-Current
Protective Device
GPR-LN
Rn Sn Tn Nn Ac MCR MCR
+ _ TN TP
CT4
CT3 TP
CT2
MCCB
MHT
CT1
TN
1a for MCR
Rn Sn Tn Nn 22
GPR-LA
Over-Current
Main Circuit
Protective Device
AC, DC 100-250 V S0-S2
Power
_
NCT +
k ℓ
MS
R S T N 21 23 29 30 19
R S T N L P NCT NCT
1 2 S2
Over-Current
Protective Device
GPR-LA
Rn Sn Tn Nn Ac S/I G/E ZI1 ZI2 ZO
1
ZO
2 COM COM RR+ RR-
MCR MCR
+ _ TN TP S 0
CT4
RELAY
CT3 TP
CT2 MHT
CT1
TN
1a for MCR
Rn Sn Tn Nn 22 24 26 31 32 33 34 35 36 5 6 20
_ _ _ _
+ + + +
IN OUT Communi- Remote
ZSI cation Reset
36 Air Circuit Breakers
Accessories
Over Current Relay (OCR)
System Diagrams
GPR-LAG/LAZ
Over-Current
Main Circuit
Protective Device
AC, DC 100-250 V S0-S2
Power
External CT / ZCT
(Secondary : 5 A)(1,000 : 1) NCT _
+
k ℓ k ℓ
R S T N 21 23 27 28 29 30 19
Over-Current
Protective Device
GPR-LAG / LAZ
Rn Sn Tn Nn Ac S/I G/E ZI1 ZI2 ZO
1
ZO COM COMRR+ RR-
2
MCR MCR
+ _ TN TP S0
CT4
CT3 TP
CT2 MHT
CT1
TN
1a for MCR
Rn Sn Tn Nn 22 24 26 31 32 33 34 35 36 5 6 20
_ _ _ _
+ + + +
IN OUT Communi- Remote
ZSI cation Reset
GPR-LP/LH
Over-Current
Main Circuit
Protective Device
AC, DC 100-250 V S0-S2
3Ø3W/3Ø4W
Power
VM _
NCT +
k ℓ
R S T N 21 23 29 30 VR VS VT VN 19
NCT NCT S2
R S T N L P 1 2 VR VS VT VN
Over-Current
Protective Device
GPR-LP / LH
ZI ZI ZO ZO MCR MCR
Rn Sn Tn Nn Ac S/I G/E 1 2 1 2 COM COM RR+ RR- + _ TN TP S0
CT4
CT3 TP
CT2 MHT
CT1
TN
1a for MCR
Rn Sn Tn Nn 22 24 26 31 32 33 34 35 36 5 6 20
_ _ _ _
+ + + +
IN OUT Communi- Remote
ZSI cation Reset
Air Circuit Breakers 37
VCB
GPR-SN
Over-Current
Main Circuit
Protective Device
R S T 21
ACB
R S T N L
Over-Current
Protective Device
GPR-SN
Rn Sn Tn Nn Ac MCR MCR
+ _ TN TP
CT3 TP
CT2 MHT
CT1
MCCB
TN
1a for MCR
Rn Sn Tn 22
GPR-SA
Over-Current
Main Circuit
Protective Device
AC, DC 100-250 V S0-S2
Power
_
+
MS
R S T 21 23 19
R S T N L P S2
Over-Current
Protective Device
GPR-SA
ZI ZI ZO ZO MCR MCR TN TP S0
Rn Sn Tn Nn Ac S/I G/E 1 2 1 2 COM COM RR+ RR- + _
CT3 TP
RELAY
CT2 MHT
CT1
TN
1a for MCR
Rn Sn Tn 22 24 26 31 32 33 34 35 36 5 6 20
_ _ _ _
+ + + +
IN OUT Communi- Remote
ZSI cation Reset
38 Air Circuit Breakers
Accessories
Over Current Relay (OCR)
System Diagrams
GPR-SP
Over-Current
Main Circuit
Protective Device
AC, DC 100-250 V S0-S2
3Ø3W/3Ø4W
Power
VM _
+
R S T 21 23 VR VS VT 19
R S T N L P VR VS VT S2
Over-Current
Protective Device
GPR-SP
ZI ZO ZO
Rn Sn Tn Nn Ac S/I G/E 1 ZI2 1 2 COM COM RR+ RR- MCR MCR
+ _ TN TP S0
CT3 TP
CT2 MHT
CT1
TN
1a for MCR
Rn Sn Tn 22 24 26 31 32 33 34 35 36 5 6 20
_ _ _ _
+ + + +
IN OUT Communi- Remote
ZSI cation Reset
※ In case of No. 52 62 (GPR-LAG) 53-63 (GPR-LAZ), CT connecting wire 27, 28 must be within 5 m.
The connecting wire of Remote Reset (RR) No. 5 No. 6 circuit must be within 5 m.
Air Circuit Breakers 39
VCB
Time Chart for LTD Inverse Time (General Feeder)
ACB
150 10.43 26.08 41.73 52.16 104.33 208.65 312.98 417.30 521.63 625.95
155 9.55 23.88 38.21 47.77 95.53 191.07 286.60 382.13 477.67 573.20
160 8.79 21.98 35.17 43.96 87.91 175.83 263.74 351.65 439.57 527.48
165 8.12 20.31 32.50 40.62 81.25 162.50 243.75 325.00 406.25 487.50
170 7.54 18.84 30.15 37.69 75.38 150.75 226.13 301.50 376.88 452.25
175 7.02 17.54 28.07 35.08 70.16 140.33 210.49 280.65 350.82 420.98
180 6.55 16.38 26.20 32.76 65.51 131.02 196.53 262.04 327.55 393.06
185 6.13 15.33 24.53 30.67 61.33 122.67 184.00 245.34 306.67 368.01
190 5.76 14.39 23.03 28.78 57.57 115.14 172.71 230.28 287.85 345.42
195 5.42 13.54 21.66 27.08 54.16 108.32 162.48 216.64 270.80 324.96
200 5.11 12.77 20.42 25.53 51.06 102.12 153.18 204.24 255.30 306.36
205 4.82 12.06 19.29 24.12 48.23 96.46 144.70 192.93 241.16 289.39
210 4.56 11.41 18.26 22.82 45.64 91.29 136.93 182.57 228.22 273.86
MCCB
215 4.33 10.82 17.31 21.63 43.27 86.53 129.80 173.07 216.33 259.60
220 4.11 10.27 16.43 20.54 41.08 82.16 123.23 164.31 205.39 246.47
225 3.91 9.76 15.62 19.53 39.06 78.12 117.18 156.23 195.29 234.35
230 3.72 9.30 14.88 18.59 37.19 74.38 111.57 148.76 185.95 223.14
235 3.55 8.86 14.18 17.73 35.46 70.91 106.37 141.82 177.28 212.74
Overload 240 3.38 8.46 13.54 16.92 33.85 67.69 101.54 135.38 169.23 203.07
Rate 245 3.23 8.09 12.94 16.17 32.35 64.69 97.04 129.38 161.73 194.07
(%) 250 3.09 7.74 12.38 15.47 30.95 61.89 92.84 123.78 154.73 185.67
255 2.96 7.41 11.86 14.82 29.64 59.28 88.91 118.55 148.19 177.83
260 2.84 7.10 11.37 14.21 28.41 56.83 85.24 113.65 142.07 170.48
265 2.73 6.82 10.91 13.63 27.27 54.53 81.80 109.06 136.33 163.59
270 2.62 6.55 10.47 13.09 26.19 52.37 78.56 104.75 130.94 157.12
275 2.52 6.29 10.07 12.59 25.17 50.35 75.52 100.69 125.87 151.04
280 2.42 6.05 9.69 12.11 24.22 48.44 72.66 96.87 121.09 145.31
285 2.33 5.83 9.33 11.66 23.32 46.64 69.95 93.27 116.59 139.91
MS
290 2.25 5.62 8.99 11.23 22.47 44.94 67.41 89.87 112.34 134.81
295 2.17 5.42 8.67 10.83 21.67 43.33 65.00 86.66 108.33 129.99
300 2.09 5.23 8.36 10.45 20.91 41.81 62.72 83.62 104.53 125.43
305 2.02 5.05 8.07 10.09 20.19 40.37 60.56 80.74 100.93 121.11
310 1.95 4.88 7.80 9.75 19.50 39.00 58.51 78.01 97.51 117.01
315 1.89 4.71 7.54 9.43 18.85 37.71 56.56 75.42 94.27 113.13
320 1.82 4.56 7.30 9.12 18.24 36.48 54.72 72.95 91.19 109.43
325 1.77 4.41 7.06 8.83 17.65 35.31 52.96 70.61 88.27 105.92
330 1.71 4.27 6.84 8.55 17.10 34.19 51.29 68.38 85.48 102.57
335 1.66 4.14 6.63 8.28 16.56 33.13 49.69 66.26 82.82 99.39
340 1.61 4.01 6.42 8.03 16.06 32.12 48.18 64.23 80.29 96.35
RELAY
345 1.56 3.89 6.23 7.79 15.58 31.15 46.73 62.30 77.88 93.45
350 1.51 3.78 6.05 7.56 15.11 30.23 45.34 60.46 75.57 90.69
355 1.47 3.67 5.87 7.34 14.67 29.35 44.02 58.70 73.37 88.04
360 1.43 3.56 5.70 7.13 14.25 28.50 42.76 57.01 71.26 85.51
365 1.38 3.46 5.54 6.92 13.85 27.70 41.55 55.40 69.24 83.09
370 1.35 3.37 5.39 6.73 13.46 26.93 40.39 53.85 67.31 80.78
375 1.31 3.27 5.24 6.55 13.09 26.19 39.28 52.37 65.46 78.56
40 Air Circuit Breakers
Accessories
Over Current Relay (OCR)
Time Chart for LTD Inverse Time (General Feeder)
Overload 505 0.71 1.77 2.84 3.55 7.10 14.20 21.30 28.40 35.50 42.60
Rate 510 0.70 1.74 2.78 3.48 6.96 13.92 20.88 27.83 34.79 41.75
(%) 515 0.68 1.71 2.73 3.41 6.82 13.64 20.46 27.29 34.11 40.93
520 0.67 1.67 2.68 3.34 6.69 13.38 20.07 26.75 33.44 40.13
525 0.66 1.64 2.62 3.28 6.56 13.12 19.68 26.24 32.80 39.36
530 0.64 1.61 2.57 3.22 6.43 12.87 19.30 25.74 32.17 38.60
535 0.63 1.58 2.52 3.16 6.31 12.62 18.94 25.25 31.56 37.87
540 0.62 1.55 2.48 3.10 6.19 12.39 18.58 24.77 30.97 37.16
545 0.61 1.52 2.43 3.04 6.08 12.16 18.24 24.31 30.39 36.47
550 0.60 1.49 2.39 2.98 5.97 11.93 17.90 23.87 29.83 35.80
555 0.59 1.46 2.34 2.93 5.86 11.72 17.57 23.43 29.29 35.15
560 0.58 1.44 2.30 2.88 5.75 11.50 17.26 23.01 28.76 34.51
565 0.56 1.41 2.26 2.82 5.65 11.30 16.95 22.60 28.24 33.89
570 0.55 1.39 2.22 2.77 5.55 11.10 16.65 22.19 27.74 33.29
575 0.55 1.36 2.18 2.73 5.45 10.90 16.35 21.80 27.26 32.71
580 0.54 1.34 2.14 2.68 5.36 10.71 16.07 21.42 26.78 32.14
585 0.53 1.32 2.11 2.63 5.26 10.53 15.79 21.05 26.32 31.58
590 0.52 1.29 2.07 2.59 5.17 10.35 15.52 20.69 25.87 31.04
595 0.51 1.27 2.03 2.54 5.09 10.17 15.26 20.34 25.43 30.51
600 0.50 1.25 2.00 2.50 5.00 10.00 15.00 20.00 25.00 30.00
605 0.49 1.23 1.97 2.46 4.92 9.83 14.75 19.67 24.58 29.50
610 0.48 1.21 1.93 2.42 4.84 9.67 14.51 19.34 24.18 29.01
615 0.48 1.19 1.90 2.38 4.76 9.51 14.27 19.02 23.78 28.53
620 0.47 1.17 1.87 2.34 4.68 9.36 14.04 18.71 23.39 28.07
625 0.46 1.15 1.84 2.30 4.60 9.21 13.81 18.41 23.01 27.62
630 0.45 1.13 1.81 2.26 4.53 9.06 13.59 18.12 22.65 27.17
635 0.45 1.11 1.78 2.23 4.46 8.91 13.37 17.83 22.29 26.74
640 0.44 1.10 1.75 2.19 4.39 8.77 13.16 17.55 21.93 26.32
Air Circuit Breakers 41
VCB
LTD Time Setting (sec)
Tr
Item
x Ir
0.5 1.25 2 2.5 5 10 15 20 25 30
645 0.43 1.08 1.73 2.16 4.32 8.64 12.96 17.27 21.59 25.91
650 0.43 1.06 1.70 2.13 4.25 8.50 12.75 17.01 21.26 25.51
655 0.42 1.05 1.67 2.09 4.19 8.37 12.56 16.74 20.93 25.12
660 0.41 1.03 1.65 2.06 4.12 8.24 12.37 16.49 20.61 24.73
665 0.41 1.01 1.62 2.03 4.06 8.12 12.18 16.24 20.30 24.36
670 0.40 1.00 1.60 2.00 4.00 8.00 12.00 15.99 19.99 23.99
675 0.39 0.98 1.58 1.97 3.94 7.88 11.82 15.76 19.69 23.63
ACB
680 0.39 0.97 1.55 1.94 3.88 7.76 11.64 15.52 19.40 23.28
685 0.38 0.96 1.53 1.91 3.82 7.65 11.47 15.29 19.12 22.94
690 0.38 0.94 1.51 1.88 3.77 7.54 11.30 15.07 18.84 22.61
695 0.37 0.93 1.49 1.86 3.71 7.43 11.14 14.85 18.57 22.28
700 0.37 0.91 1.46 1.83 3.66 7.32 10.98 14.64 18.30 21.96
705 0.36 0.90 1.44 1.80 3.61 7.21 10.82 14.43 18.04 21.64
710 0.36 0.89 1.42 1.78 3.56 7.11 10.67 14.23 17.78 21.34
715 0.35 0.88 1.40 1.75 3.51 7.01 10.52 14.02 17.53 21.04
720 0.35 0.86 1.38 1.73 3.46 6.91 10.37 13.83 17.29 20.74
725 0.34 0.85 1.36 1.70 3.41 6.82 10.23 13.64 17.05 20.46
730 0.34 0.84 1.34 1.68 3.36 6.72 10.09 13.45 16.81 20.17
735 0.33 0.83 1.33 1.66 3.32 6.63 9.95 13.26 16.58 19.90
740 0.33 0.82 1.31 1.64 3.27 6.54 9.81 13.08 16.36 19.63
MCCB
745 0.32 0.81 1.29 1.61 3.23 6.45 9.68 12.91 16.14 19.36
750 0.32 0.80 1.27 1.59 3.18 6.37 9.55 12.73 15.92 19.10
755 0.31 0.79 1.26 1.57 3.14 6.28 9.42 12.57 15.71 18.85
760 0.31 0.77 1.24 1.55 3.10 6.20 9.30 12.40 15.50 18.60
765 0.31 0.76 1.22 1.53 3.06 6.12 9.18 12.24 15.30 18.35
Overload 770 0.30 0.75 1.21 1.51 3.02 6.04 9.06 12.08 15.10 18.11
Rate 775 0.30 0.74 1.19 1.49 2.98 5.96 8.94 11.92 14.90 17.88
(%) 780 0.29 0.74 1.18 1.47 2.94 5.88 8.82 11.77 14.71 17.65
785 0.29 0.73 1.16 1.45 2.90 5.81 8.71 11.62 14.52 17.42
790 0.29 0.72 1.15 1.43 2.87 5.73 8.60 11.47 14.33 17.20
795 0.28 0.71 1.13 1.42 2.83 5.66 8.49 11.32 14.15 16.98
800 0.28 0.70 1.12 1.40 2.80 5.59 8.39 11.18 13.98 16.77
805 0.28 0.69 1.10 1.38 2.76 5.52 8.28 11.04 13.80 16.56
810 0.27 0.68 1.09 1.36 2.73 5.45 8.18 10.90 13.63 16.36
815 0.27 0.67 1.08 1.35 2.69 5.38 8.08 10.77 13.46 16.15
MS
820 0.27 0.66 1.06 1.33 2.66 5.32 7.98 10.64 13.30 15.96
825 0.26 0.66 1.05 1.31 2.63 5.25 7.88 10.51 13.14 15.76
830 0.26 0.65 1.04 1.30 2.60 5.19 7.79 10.38 12.98 15.57
835 0.26 0.64 1.03 1.28 2.56 5.13 7.69 10.26 12.82 15.38
840 0.25 0.63 1.01 1.27 2.53 5.07 7.60 10.13 12.67 15.20
845 0.25 0.63 1.00 1.25 2.50 5.01 7.51 10.01 12.52 15.02
850 0.25 0.62 0.99 1.24 2.47 4.95 7.42 9.89 12.37 14.84
855 0.24 0.61 0.98 1.22 2.44 4.89 7.33 9.78 12.22 14.67
860 0.24 0.60 0.97 1.21 2.42 4.83 7.25 9.66 12.08 14.50
865 0.24 0.60 0.96 1.19 2.39 4.78 7.16 9.55 11.94 14.33
870 0.24 0.59 0.94 1.18 2.36 4.72 7.08 9.44 11.80 14.16
RELAY
875 0.23 0.58 0.93 1.17 2.33 4.67 7.00 9.33 11.67 14.00
880 0.23 0.58 0.92 1.15 2.31 4.61 6.92 9.23 11.53 13.84
885 0.23 0.57 0.91 1.14 2.28 4.56 6.84 9.12 11.40 13.68
890 0.23 0.56 0.90 1.13 2.25 4.51 6.76 9.02 11.27 13.53
895 0.22 0.56 0.89 1.11 2.23 4.46 6.69 8.92 11.15 13.38
900 0.22 0.55 0.88 1.10 2.20 4.41 6.61 8.82 11.02 13.23
905 0.22 0.55 0.87 1.09 2.18 4.36 6.54 8.72 10.90 13.08
42 Air Circuit Breakers
Accessories
Over Current Relay (OCR)
Time Chart for LTD Inverse Time (General Feeder)
Overload 950 0.20 0.49 0.79 0.99 1.98 3.96 5.93 7.91 9.89 11.87
Rate 955 0.20 0.49 0.78 0.98 1.96 3.91 5.87 7.83 9.78 11.74
(%) 960 0.19 0.48 0.77 0.97 1.94 3.87 5.81 7.75 9.68 11.62
965 0.19 0.48 0.77 0.96 1.92 3.83 5.75 7.67 9.58 11.50
970 0.19 0.47 0.76 0.95 1.90 3.79 5.69 7.59 9.48 11.38
975 0.19 0.47 0.75 0.94 1.88 3.75 5.63 7.51 9.38 11.26
980 0.19 0.46 0.74 0.93 1.86 3.72 5.57 7.43 9.29 11.15
985 0.18 0.46 0.74 0.92 1.84 3.68 5.52 7.36 9.19 11.03
990 0.18 0.46 0.73 0.91 1.82 3.64 5.46 7.28 9.10 10.92
995 0.18 0.45 0.72 0.90 1.80 3.60 5.41 7.21 9.01 10.81
1,000 0.18 0.45 0.71 0.89 1.78 3.57 5.35 7.14 8.92 10.70
Air Circuit Breakers 43
VCB
Time Chart for LTD Inverse Time (Generator)
ACB
135 6.71 10.07 13.42 16.78 20.13 23.49 26.84 33.55 40.26
140 6.02 9.03 12.04 15.05 18.06 21.07 24.08 30.10 36.12
145 5.44 8.17 10.89 13.61 16.33 19.06 21.78 27.22 32.67
150 4.96 7.44 9.92 12.39 14.87 17.35 19.83 24.79 29.75
155 4.54 6.81 9.08 11.35 13.62 15.89 18.16 22.70 27.24
160 4.18 6.27 8.36 10.44 12.53 14.62 16.71 20.89 25.07
165 3.86 5.79 7.72 9.65 11.58 13.51 15.44 19.31 23.17
170 3.58 5.37 7.16 8.95 10.75 12.54 14.33 17.91 21.49
175 3.33 5.00 6.67 8.34 10.00 11.67 13.34 16.67 20.01
180 3.11 4.67 6.23 7.78 9.34 10.90 12.45 15.57 18.68
185 2.91 4.37 5.83 7.29 8.74 10.20 11.66 14.57 17.49
190 2.74 4.10 5.47 6.84 8.21 9.58 10.94 13.68 16.41
195 2.57 3.86 5.15 6.43 7.72 9.01 10.29 12.87 15.44
MCCB
200 2.43 3.64 4.85 6.07 7.28 8.49 9.71 12.13 14.56
205 2.29 3.44 4.58 5.73 6.88 8.02 9.17 11.46 13.75
210 2.17 3.25 4.34 5.42 6.51 7.59 8.68 10.85 13.01
215 2.06 3.08 4.11 5.14 6.17 7.20 8.22 10.28 12.34
220 1.95 2.93 3.90 4.88 5.86 6.83 7.81 9.76 11.71
Overload 225 1.86 2.78 3.71 4.64 5.57 6.50 7.42 9.28 11.14
Rate 230 1.77 2.65 3.53 4.42 5.30 6.19 7.07 8.84 10.60
(%) 235 1.68 2.53 3.37 4.21 5.05 5.90 6.74 8.42 10.11
240 1.61 2.41 3.22 4.02 4.83 5.63 6.43 8.04 9.65
245 1.54 2.31 3.07 3.84 4.61 5.38 6.15 7.69 9.22
250 1.47 2.21 2.94 3.68 4.41 5.15 5.88 7.35 8.82
255 1.41 2.11 2.82 3.52 4.23 4.93 5.63 7.04 8.45
260 1.35 2.03 2.70 3.38 4.05 4.73 5.40 6.75 8.10
265 1.30 1.94 2.59 3.24 3.89 4.53 5.18 6.48 7.77
270 1.24 1.87 2.49 3.11 3.73 4.36 4.98 6.22 7.47
MS
275 1.20 1.79 2.39 2.99 3.59 4.19 4.78 5.98 7.18
280 1.15 1.73 2.30 2.88 3.45 4.03 4.60 5.75 6.91
285 1.11 1.66 2.22 2.77 3.32 3.88 4.43 5.54 6.65
290 1.07 1.60 2.14 2.67 3.20 3.74 4.27 5.34 6.41
295 1.03 1.54 2.06 2.57 3.09 3.60 4.12 5.15 6.18
300 0.99 1.49 1.99 2.48 2.98 3.48 3.97 4.97 5.96
305 0.96 1.44 1.92 2.40 2.88 3.36 3.84 4.80 5.76
310 0.93 1.39 1.85 2.32 2.78 3.24 3.71 4.63 5.56
315 0.90 1.34 1.79 2.24 2.69 3.14 3.58 4.48 5.38
320 0.87 1.30 1.73 2.17 2.60 3.03 3.47 4.33 5.20
325 0.84 1.26 1.68 2.10 2.52 2.94 3.36 4.19 5.03
RELAY
330 0.81 1.22 1.62 2.03 2.44 2.84 3.25 4.06 4.87
335 0.79 1.18 1.57 1.97 2.36 2.76 3.15 3.94 4.72
340 0.76 1.14 1.53 1.91 2.29 2.67 3.05 3.82 4.58
345 0.74 1.11 1.48 1.85 2.22 2.59 2.96 3.70 4.44
350 0.72 1.08 1.44 1.80 2.15 2.51 2.87 3.59 4.31
355 0.70 1.05 1.39 1.74 2.09 2.44 2.79 3.49 4.18
360 0.68 1.02 1.35 1.69 2.03 2.37 2.71 3.39 4.06
44 Air Circuit Breakers
Accessories
Over Current Relay (OCR)
Time Chart for LTD Inverse Time (Generator)
Overload 490 0.36 0.54 0.72 0.90 1.08 1.26 1.44 1.79 2.15
Rate 495 0.35 0.53 0.70 0.88 1.05 1.23 1.41 1.76 2.11
(%) 500 0.34 0.52 0.69 0.86 1.03 1.21 1.38 1.72 2.07
505 0.34 0.51 0.67 0.84 1.01 1.18 1.35 1.69 2.02
510 0.33 0.50 0.66 0.83 0.99 1.16 1.32 1.65 1.98
515 0.32 0.49 0.65 0.81 0.97 1.13 1.30 1.62 1.94
520 0.32 0.48 0.64 0.79 0.95 1.11 1.27 1.59 1.91
525 0.31 0.47 0.62 0.78 0.94 1.09 1.25 1.56 1.87
530 0.31 0.46 0.61 0.76 0.92 1.07 1.22 1.53 1.83
535 0.30 0.45 0.60 0.75 0.90 1.05 1.20 1.50 1.80
540 0.29 0.44 0.59 0.74 0.88 1.03 1.18 1.47 1.77
545 0.29 0.43 0.58 0.72 0.87 1.01 1.16 1.44 1.73
550 0.28 0.43 0.57 0.71 0.85 0.99 1.13 1.42 1.70
555 0.28 0.42 0.56 0.70 0.84 0.97 1.11 1.39 1.67
560 0.27 0.41 0.55 0.68 0.82 0.96 1.09 1.37 1.64
565 0.27 0.40 0.54 0.67 0.81 0.94 1.07 1.34 1.61
570 0.26 0.40 0.53 0.66 0.79 0.92 1.05 1.32 1.58
575 0.26 0.39 0.52 0.65 0.78 0.91 1.04 1.30 1.55
580 0.25 0.38 0.51 0.64 0.76 0.89 1.02 1.27 1.53
585 0.25 0.38 0.50 0.63 0.75 0.88 1.00 1.25 1.50
590 0.25 0.37 0.49 0.61 0.74 0.86 0.98 1.23 1.48
595 0.24 0.36 0.48 0.60 0.73 0.85 0.97 1.21 1.45
600 0.24 0.36 0.48 0.59 0.71 0.83 0.95 1.19 1.43
605 0.23 0.35 0.47 0.58 0.70 0.82 0.93 1.17 1.40
610 0.23 0.34 0.46 0.57 0.69 0.80 0.92 1.15 1.38
615 0.23 0.34 0.45 0.56 0.68 0.79 0.90 1.13 1.36
620 0.22 0.33 0.44 0.56 0.67 0.78 0.89 1.11 1.33
625 0.22 0.33 0.44 0.55 0.66 0.77 0.87 1.09 1.31
Air Circuit Breakers 45
VCB
LTD Time Setting (sec)
Tr
Item
x Ir
10 15 20 25 30 35 40 50 60
630 0.22 0.32 0.43 0.54 0.65 0.75 0.86 1.08 1.29
635 0.21 0.32 0.42 0.53 0.64 0.74 0.85 1.06 1.27
640 0.21 0.31 0.42 0.52 0.63 0.73 0.83 1.04 1.25
645 0.21 0.31 0.41 0.51 0.62 0.72 0.82 1.03 1.23
650 0.20 0.30 0.40 0.51 0.61 0.71 0.81 1.01 1.21
655 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.99 1.19
660 0.20 0.29 0.39 0.49 0.59 0.69 0.78 0.98 1.18
ACB
665 0.19 0.29 0.39 0.48 0.58 0.68 0.77 0.96 1.16
670 0.19 0.29 0.38 0.48 0.57 0.67 0.76 0.95 1.14
675 0.19 0.28 0.37 0.47 0.56 0.66 0.75 0.94 1.12
680 0.18 0.28 0.37 0.46 0.55 0.65 0.74 0.92 1.11
685 0.18 0.27 0.36 0.45 0.55 0.64 0.73 0.91 1.09
690 0.18 0.27 0.36 0.45 0.54 0.63 0.72 0.90 1.07
695 0.18 0.26 0.35 0.44 0.53 0.62 0.71 0.88 1.06
700 0.17 0.26 0.35 0.43 0.52 0.61 0.70 0.87 1.04
705 0.17 0.26 0.34 0.43 0.51 0.60 0.69 0.86 1.03
710 0.17 0.25 0.34 0.42 0.51 0.59 0.68 0.84 1.01
715 0.17 0.25 0.33 0.42 0.50 0.58 0.67 0.83 1.00
720 0.16 0.25 0.33 0.41 0.49 0.58 0.66 0.82 0.99
725 0.16 0.24 0.32 0.41 0.49 0.57 0.65 0.81 0.97
MCCB
730 0.16 0.24 0.32 0.40 0.48 0.56 0.64 0.80 0.96
735 0.16 0.24 0.32 0.39 0.47 0.55 0.63 0.79 0.95
740 0.16 0.23 0.31 0.39 0.47 0.54 0.62 0.78 0.93
745 0.15 0.23 0.31 0.38 0.46 0.54 0.61 0.77 0.92
750 0.15 0.23 0.30 0.38 0.45 0.53 0.61 0.76 0.91
Overload 755 0.15 0.22 0.30 0.37 0.45 0.52 0.60 0.75 0.90
Rate 760 0.15 0.22 0.29 0.37 0.44 0.52 0.59 0.74 0.88
(%) 765 0.15 0.22 0.29 0.36 0.44 0.51 0.58 0.73 0.87
770 0.14 0.22 0.29 0.36 0.43 0.50 0.57 0.72 0.86
775 0.14 0.21 0.28 0.35 0.42 0.50 0.57 0.71 0.85
780 0.14 0.21 0.28 0.35 0.42 0.49 0.56 0.70 0.84
785 0.14 0.21 0.28 0.34 0.41 0.48 0.55 0.69 0.83
790 0.14 0.20 0.27 0.34 0.41 0.48 0.54 0.68 0.82
795 0.13 0.20 0.27 0.34 0.40 0.47 0.54 0.67 0.81
800 0.13 0.20 0.27 0.33 0.40 0.46 0.53 0.66 0.80
MS
805 0.13 0.20 0.26 0.33 0.39 0.46 0.52 0.66 0.79
810 0.13 0.19 0.26 0.32 0.39 0.45 0.52 0.65 0.78
815 0.13 0.19 0.26 0.32 0.38 0.45 0.51 0.64 0.77
820 0.13 0.19 0.25 0.32 0.38 0.44 0.51 0.63 0.76
825 0.12 0.19 0.25 0.31 0.37 0.44 0.50 0.62 0.75
830 0.12 0.18 0.25 0.31 0.37 0.43 0.49 0.62 0.74
835 0.12 0.18 0.24 0.30 0.37 0.43 0.49 0.61 0.73
840 0.12 0.18 0.24 0.30 0.36 0.42 0.48 0.60 0.72
845 0.12 0.18 0.24 0.30 0.36 0.42 0.48 0.59 0.71
850 0.12 0.18 0.24 0.29 0.35 0.41 0.47 0.59 0.71
855 0.12 0.17 0.23 0.29 0.35 0.41 0.46 0.58 0.70
RELAY
860 0.11 0.17 0.23 0.29 0.34 0.40 0.46 0.57 0.69
865 0.11 0.17 0.23 0.28 0.34 0.40 0.45 0.57 0.68
870 0.11 0.17 0.22 0.28 0.34 0.39 0.45 0.56 0.67
875 0.11 0.17 0.22 0.28 0.33 0.39 0.44 0.55 0.67
880 0.11 0.16 0.22 0.27 0.33 0.38 0.44 0.55 0.66
885 0.11 0.16 0.22 0.27 0.33 0.38 0.43 0.54 0.65
890 0.11 0.16 0.21 0.27 0.32 0.38 0.43 0.54 0.64
46 Air Circuit Breakers
Accessories
Over Current Relay (OCR)
Time Chart for LTD Inverse Time (Generator)
Overload 935 0.10 0.15 0.19 0.24 0.29 0.34 0.39 0.49 0.58
Rate 940 0.10 0.14 0.19 0.24 0.29 0.34 0.38 0.48 0.58
(%) 945 0.09 0.14 0.19 0.24 0.28 0.33 0.38 0.47 0.57
950 0.09 0.14 0.19 0.23 0.28 0.33 0.38 0.47 0.56
955 0.09 0.14 0.19 0.23 0.28 0.33 0.37 0.46 0.56
960 0.09 0.14 0.18 0.23 0.28 0.32 0.37 0.46 0.55
965 0.09 0.14 0.18 0.23 0.27 0.32 0.36 0.46 0.55
970 0.09 0.14 0.18 0.23 0.27 0.32 0.36 0.45 0.54
975 0.09 0.13 0.18 0.22 0.27 0.31 0.36 0.45 0.54
980 0.09 0.13 0.18 0.22 0.26 0.31 0.35 0.44 0.53
985 0.09 0.13 0.17 0.22 0.26 0.31 0.35 0.44 0.52
Air Circuit Breakers 47
VCB
Time Chart for STD Inverse Time (General Feeder)
Tsd STD Time Setting (ms) Inland Type Tsd STD Time Setting (ms) Inland Type
Item Item
x In 50 100 200 300 400 500 x In 50 100 200 300 400 500
100 5,000 10,000 20,000 30,000 40,000 50,000 630 126 252 504 756 1,008 12,60
110 4,132 8,264 16,529 24,793 33,058 41,322 640 122 244 488 732 977 1,221
120 3,472 6,944 13,889 20,833 27,778 34,722 650 118 237 473 710 947 1,183
130 2,959 5,917 11,834 17,751 23,669 29,586 660 115 230 459 689 918 1,148
140 2,551 5,102 10,204 15,306 20,408 25,510 670 111 223 446 668 891 1,114
150 2,222 4,444 8,889 13,333 17,778 22,222 680 108 216 433 649 865 1,081
160 1,953 3,906 7,813 11,719 15,625 19,531 690 105 210 420 630 840 1,050
ACB
170 1,730 3,460 6,920 10,381 13,841 17,301 700 102 204 408 612 816 1,020
180 1,543 3,086 6,173 9,259 12,346 15,432 710 99 198 397 595 793 992
190 1,385 2,770 5,540 8,310 11,080 13,850 720 96 193 386 579 772 965
200 1,250 2,500 5,000 7,500 10,000 12,500 730 94 188 375 563 751 938
210 1,134 2,268 4,535 6,803 9,070 11,338 740 91 183 365 548 730 913
220 1,033 2,066 4,132 6,198 8,264 10,331 750 89 178 356 533 711 889
230 945 1,890 3,781 5,671 7,561 9,452 760 87 173 346 519 693 866
240 868 1,736 3,472 5,208 6,944 8,681 770 84 169 337 506 675 843
250 800 1,600 3,200 4,800 6,400 8,000 780 82 164 329 493 657 822
260 740 1,479 2,959 4,438 5,917 7,396 790 80 160 320 481 641 801
270 686 1,372 2,743 4,115 5,487 6,859 800 78 156 313 469 625 781
280 638 1,276 2,551 3,827 5,102 6,378 Overload 810 76 152 305 457 610 762
Rate
290 595 1,189 2,378 3,567 4,756 5,945 820 74 149 297 446 595 744
MCCB
(%)
300 556 1,111 2,222 3,333 4,444 5,556 830 73 145 290 435 581 726
310 520 1,041 2,081 3,122 4,162 5,203 840 71 142 283 425 567 709
320 488 977 1,953 2,930 3,906 4,883 850 69 138 277 415 554 692
330 459 918 1,837 2,755 3,673 4,591 860 68 135 270 406 541 676
340 433 865 1,730 2,595 3,460 4,325 870 66 132 264 396 528 661
Overload 350 408 816 1,633 2,449 3,265 4,082 880 65 129 258 387 517 646
Rate 360 386 772 1,543 2,315 3,086 3,858 890 63 126 252 379 505 631
(%) 370 365 730 1,461 2,191 2,922 3,652 900 62 123 247 370 494 617
380 346 693 1,385 2,078 2,770 3,463 910 60 121 242 362 483 604
390 329 657 1,315 1,972 2,630 3,287 920 59 118 236 354 473 591
400 313 625 1,250 1,875 2,500 3,125 930 58 116 231 347 462 578
410 297 595 1,190 1,785 2,380 2,974 940 57 113 226 340 453 566
420 283 567 1,134 1,701 2,268 2,834 950 55 111 222 332 443 554
960 54 109 217 326 434 543
MS
430 270 541 1,082 1,622 21,63 2,704
440 258 517 1,033 1,550 2,066 2,583 970 53 106 213 319 425 531
450 247 494 988 1,481 1,975 2,469 980 52 104 208 312 416 521
460 236 473 945 1,418 1,890 2,363 990 51 102 204 306 408 510
470 226 453 905 13,58 1,811 2,263 1,000 50 100 200 300 400 500
480 217 434 868 1,302 1,736 2,170
490 208 416 833 1,249 1,666 2,082
500 200 400 800 1,200 1,600 2,000
510 192 384 769 1,153 1,538 1,922
520 185 370 740 1,109 1,479 1,849
530 178 356 712 1,068 1,424 1,780
540 171 343 686 1,029 1,372 1,715
550 165 331 661 992 1,322 1,653
RELAY
Accessories
Over Current Relay (OCR)
Time Chart for STD Inverse Time (Generator)
VCB
Time Chart for GFT Inverse Time (General Feeder)
ACB
17 1,730 3,460 6,920 10,381 13,841 17,301 70 102 204 408 612 816 1,020
18 1,543 3,086 6,173 9,259 12,346 15,432 71 99 198 397 595 793 992
19 1,385 2,770 5,540 8,310 11,080 13,850 72 96 193 386 579 772 965
20 1,250 2,500 5,000 7,500 10,000 12,500 73 94 188 375 563 751 938
21 1,134 2,268 4,535 6,803 9,070 11,338 74 91 183 365 548 730 913
22 1,033 2,066 4,132 6,198 8,264 10,331 75 89 178 356 533 711 889
23 945 1,890 3,781 5,671 7,561 9,452 76 87 173 346 519 693 866
24 868 1,736 3,472 5,208 6,944 8,681 77 84 169 337 506 675 843
25 800 1,600 3,200 4,800 6,400 8,000 78 82 164 329 493 657 822
26 740 1,479 2,959 4,438 5,917 7,396 79 80 160 320 481 641 801
27 686 1,372 2,743 4,115 5,487 6,859 80 78 156 313 469 625 781
Detection
28 638 1,276 2,551 3,827 5,102 6,378 Setting 81 76 152 305 457 610 762
29 595 1,189 2,378 3,567 4,756 5,945 Current 82 74 149 297 446 595 744
MCCB
(%)
30 556 1,111 2,222 3,333 4,444 5,556 83 73 145 290 435 581 726
31 520 1,041 2,081 3,122 4,162 5,203 84 71 142 283 425 567 709
32 488 977 1,953 2,930 3,906 4,883 85 69 138 277 415 554 692
33 459 918 1,837 2,755 3,673 4,591 86 68 135 270 406 541 676
34 433 865 1,730 2,595 3,460 4,325 87 66 132 264 396 528 661
Detection 35 408 816 1,633 2,449 3,265 4,082 88 65 129 258 387 517 646
Setting
36 386 772 1,543 2,315 3,086 3,858 89 63 126 252 379 505 631
Current
(%) 37 365 730 1,461 2,191 2,922 3,652 90 62 123 247 370 494 617
38 346 693 1,385 2,078 2,770 3,463 91 60 121 242 362 483 604
39 329 657 1,315 1,972 2,630 3,287 92 59 118 236 354 473 591
40 313 625 1,250 1,875 2,500 3,125 93 58 116 231 347 462 578
41 297 595 1,190 1,785 2,380 2,974 94 57 113 226 340 453 566
42 283 567 1,134 1,701 2,268 2,834 95 55 111 222 332 443 554
43 270 541 1,082 1,622 2,163 2,704 96 54 109 217 326 434 543
44 258 517 1,033 1,550 2,066 2,583 97 53 106 213 319 425 531
MS
45 247 494 988 1,481 1,975 2,469 98 52 104 208 312 416 521
46 236 473 945 1,418 1,890 2,363 99 51 102 204 306 408 510
47 226 453 905 1,358 1,811 2,263 100 50 100 200 300 400 500
48 217 434 868 1,302 1,736 2,170
49 208 416 833 1,249 1,666 2,082
50 200 400 800 1,200 1,600 2,000
51 192 384 769 1,153 1,538 1,922
52 185 370 740 1,109 1,479 1,849
53 178 356 712 1,068 1,424 1,780
54 171 343 686 1,029 1,372 1715
55 165 331 661 992 1,322 1,653
RELAY
Accessories
Over Current Relay (OCR)
Time Chart for PTA Inverse Time (Generator)
VCB
PTA Time Setting (sec)
Tp
Item
x Ip
1 5 10 15 20 25 30 35 40
102 1.38 6.92 13.84 20.76 27.68 34.60 41.52 48.44 55.36
103 1.36 6.79 13.57 20.36 27.15 33.93 40.72 47.51 54.29
104 1.33 6.66 13.31 19.97 26.63 33.28 39.94 46.60 53.25
105 1.31 6.53 13.06 19.59 26.12 32.65 39.18 45.71 52.24
106 1.28 6.41 12.82 19.22 25.63 32.04 38.45 44.86 51.26
107 1.26 6.29 12.58 18.87 25.16 31.44 37.73 44.02 50.31
108 1.23 6.17 12.35 18.52 24.69 30.86 37.04 43.21 49.38
ACB
109 1.21 6.06 12.12 18.18 24.24 30.30 36.36 42.42 48.48
110 1.19 5.95 11.90 17.85 23.80 29.75 35.70 41.65 47.60
111 1.17 5.84 11.69 17.53 23.37 29.22 35.06 40.91 46.75
112 1.15 5.74 11.48 17.22 22.96 28.70 34.44 40.18 45.92
113 1.13 5.64 11.28 16.92 22.55 28.19 33.83 39.47 45.11
114 1.11 5.54 11.08 16.62 22.16 27.70 33.24 38.78 44.32
115 1.09 5.44 10.89 16.33 21.78 27.22 32.67 38.11 43.55
116 1.07 5.35 10.70 16.05 21.40 26.75 32.10 37.46 42.81
117 1.05 5.26 10.52 15.78 21.04 26.30 31.56 36.82 42.08
118 1.03 5.17 10.34 15.51 20.68 25.85 31.03 36.20 41.37
119 1.02 5.08 10.17 15.25 20.34 25.42 30.51 35.59 40.68
120 1.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00 40.00
121 0.98 4.92 9.84 14.75 19.67 24.59 29.51 34.42 39.34
MCCB
122 0.97 4.84 9.67 14.51 19.35 24.19 29.02 33.86 38.70
123 0.95 4.76 9.52 14.28 19.04 23.80 28.55 33.31 38.07
124 0.94 4.68 9.37 14.05 18.73 23.41 28.10 32.78 37.46
125 0.92 4.61 9.22 13.82 18.43 23.04 27.65 32.26 36.86
126 0.91 4.54 9.07 13.61 18.14 22.68 27.21 31.75 36.28
Detection 127 0.89 4.46 8.93 13.39 17.86 22.32 26.78 31.25 35.71
Setting
128 0.88 4.39 8.79 13.18 17.58 21.97 26.37 30.76 35.16
Current
(%) 129 0.87 4.33 8.65 12.98 17.31 21.63 25.96 30.29 34.61
130 0.85 4.26 8.52 12.78 17.04 21.30 25.56 29.82 34.08
131 0.84 4.20 8.39 12.59 16.78 20.98 25.17 29.37 33.56
132 0.83 4.13 8.26 12.40 16.53 20.66 24.79 28.93 33.06
133 0.81 4.07 8.14 12.21 16.28 20.35 24.42 28.49 32.56
134 0.80 4.01 8.02 12.03 16.04 20.05 24.06 28.07 32.08
135 0.79 3.95 7.90 11.85 15.80 19.75 23.70 27.65 31.60
136 0.78 3.89 7.79 11.68 15.57 19.46 23.36 27.25 31.14
MS
137 0.77 3.84 7.67 11.51 15.34 19.18 23.02 26.85 30.69
138 0.76 3.78 7.56 11.34 15.12 18.90 22.68 26.47 30.25
139 0.75 3.73 7.45 11.18 14.91 18.63 22.36 26.09 29.81
140 0.73 3.67 7.35 11.02 14.69 18.37 22.04 25.71 29.39
141 0.72 3.62 7.24 10.86 14.49 18.11 21.73 25.35 28.97
142 0.71 3.57 7.14 10.71 14.28 17.85 21.42 25.00 28.57
143 0.70 3.52 7.04 10.56 14.08 17.60 21.13 24.65 28.17
144 0.69 3.47 6.94 10.42 13.89 17.36 20.83 24.31 27.78
145 0.68 3.42 6.85 10.27 13.70 17.12 20.55 23.97 27.40
146 0.68 3.38 6.76 10.13 13.51 16.89 20.27 23.64 27.02
147 0.67 3.33 6.66 10.00 13.33 16.66 19.99 23.32 26.66
RELAY
148 0.66 3.29 6.57 9.86 13.15 16.44 19.72 23.01 26.30
149 0.65 3.24 6.49 9.73 12.97 16.22 19.46 22.70 25.94
150 0.64 3.20 6.40 9.60 12.80 16.00 19.20 22.40 25.60
151 0.63 3.16 6.32 9.47 12.63 15.79 18.95 22.10 25.26
152 0.62 3.12 6.23 9.35 12.47 15.58 18.70 21.81 24.93
153 0.62 3.08 6.15 9.23 12.30 15.38 18.45 21.53 24.61
154 0.61 3.04 6.07 9.11 12.14 15.18 18.22 21.25 24.29
52 Air Circuit Breakers
Accessories
Over Current Relay (OCR)
Time Chart for PTA Inverse Time (Generator)
Accessories
VCB
Spring Charging Geared Motor
˙Manual charging method and geared motor charging method Connection Diagram
using external power source for charging the spring in the
circuit breaker. Power
˙As for the geared motor charging method, if power is applied
to the control power terminal number (1), (2), spring charge is
1
possible at 85 ~ 110 % power of the operating voltage range.
15
Ordering Method
ACB
Order Name Placed Detailed M
Name of Accessory
upon Outgoing Specification
M1 AC/DC 110 V
M2 AC/DC 220 V
AC 380 V
M3
(Under Development) 2 16
Spring Charging
Geared Motor AC 440 V
M4
(Under Development)
M7 DC 24 V
M8 DC 48 V
M9 DC 125 V
MCCB
Ratings
˙Spring charging switch delivers (15, 16) the charged status when mechanism spring charge is complete.
˙Read to close switch delivers (15, 16) only when the circuit breaker is open and simultaneously only when the mechanism spring
charge is complete.
˙Order name of spring charging switch:B6, Order name of ready to close switch:BT
˙Two accessories cannot be ordered simultaneously.
54 Air Circuit Breakers
Accessories
Closing Coil (CC)
˙A control device which closes a circuit breaker remotely from Connection Diagram
outside.
˙The circuit breaker is closed by applying power of at least more
Power
than 150 ms within the range of 85 ~ 110 % of the rated control PB
(Close)
voltage to the control power terminal number (3) and (4).
˙Add C1 ~ C9 in the order form when ordering the main unit. 3
Ordering Method
C8 DC 48 V
C9 DC 125 V
Closing Coil
Air Circuit Breakers 55
VCB
Trip Coil (TC)
˙A control device which trips a circuit breaker remotely. Connection Diagram
˙The circuit breaker is tripped by applying power of at least more
than 150 ms within the range of 70 ~ 110 % of the rated control Power
voltage to the control power terminal number (7) and (8).
˙Add S1 ~ S9 in the order form when ordering the main unit.
PB(Open)
˙It can be purchased separately. 7
Ordering Method
ACB
Order Name Placed Detailed
Name of Accessory
upon Outgoing Specification
TC
S1 AC/DC 110 V
S2 AC/DC 220 V
S3 AC 380 V
Trip Coil S4 AC 440 V
S7 DC 24 V 8
S8 DC 48 V
S9 DC 125 V
MCCB
Ratings Wire Ratings
MS
Trip Coil
RELAY
56 Air Circuit Breakers
Accessories
Secondary Trip Coil
˙It is a control device which trips a circuit breaker remotely from Connection Diagram
outside and dual remote trip is possible with an additional
installation of trip coil. Power Power
˙The circuit breaker is tripped by applying power of at least
PB(Open)
PB(Open)
more than 150 ms within the range of 70 ~ 110 % of the rated
control voltage by applying power to the control power terminal 7 9
8 10
Wire Ratings
VCB
Trip Coil Supervision
˙A control device which trips a circuit breaker remotely from outside. Connection Diagram
˙The circuit breaker is tripped by applying power of at least more
than 150 ms within the range of 70 ~ 110 % of the rated control
Power
voltage by applying power to the control power terminal
number (7) and (8).
PB(Open)
Supervision
˙When using trip coil supervision, auxiliary contact is 4a3b and 7 59
ACB
by using the additional 1a1b (Order code AA). (Possibility of
contact damage) However, if it is compulsory, select 1a contact
within 4a3b for use. TC
MCCB
Order Name Placed Detailed Item DC (V) AC (V)
Name of Accessory
upon Outgoing Specification 24 -
T1 AC/DC 110 V Rated Voltage (Vn) 100 ~ 130 100 ~ 130
T2 AC/DC 220 V 200 ~ 250 200 ~ 250
T3 AC 380 V Operating Limits (Vn) 0.7 ~ 1.1
Trip Coil Supervision T4 AC 440 V Power Consumption (VA) Inrush (300), Steady-State (10)
T7 DC 24 V Trip Time (ms) 40
T8 DC 48 V
T9 DC 125 V
Wire Ratings
Accessories
UVT Coil
˙Under-voltage trip device is a device that automatically trips Connection Diagram
the circuit breaker if the load voltage drops to below 70 % of the
standard or to prevent accidents at the load part during a black out. Power
PB(Open)
time delay type for use. As for instantaneous type, directly 9
connect to control power terminal number (9), (10) for use and
as for time delay type, the Time Delay Controller can be used.
˙The circuit breaker trips when the load voltage at the UVT coil
becomes less than 35 %, becomes an interlocked state that
cannot be closed and when load voltage of 85% is applied,
normal closing is possible. UVT
Wire Ratings
UVT Coil
Air Circuit Breakers 59
VCB
UVT Time Delay Controller
˙Under-voltage trip device is a device that automatically trips Connection Diagram
the circuit breaker if the load voltage drops to below operating
voltage or to prevent accidents at the load part during a black out. COM
U1
Power
˙This device is capable of delaying (0.5, 1.0, 1.5, 3 sec). a
b
U2
PB(Open)
C1
T2
Controller
UVT
C2
the cradle and the external rail and it can also be mounted at T1
9
the position desired by the customer.
˙Add V1 ~ V9 in the order form when ordering the main unit.
Time Delay Controller will be included in the package.
˙When purchasing the UVT time delay controller only, place the
ACB
order for the separate product, HGNS UT1 ~ UT9.
UVT
˙DC 24 V and DC 48 V are only available in instantaneous type.
˙In the event the UVT Time Delay Controller and RCTU are
purchased simultaneously, the front mounting can be installed
in the front for 1 option designated by the customer.
The remaining 1 shall be installed by designating a position in 10
MCCB
Separate Sales
Accessory upon Outgoing Specification
(HGNS-)
Dimension
MS
UVT Time Delay Controller
Unit:mm
121.4
105
91.4
75
RELAY
Accessories
AUX Switch
˙It is an output contact to remotely monitor the On/Off state of Connection
the ACB.
˙As for HGS Type, 3a3b is provided and as for HGN Type, 5a5b is 41 43 45 47 49 51 53 55 57 59
provided as standard without separate indication in the order form.
˙AUX switch can be expanded up to 6a6b maximum.
- How to order HGS 5a5b:Add A5 in the order form.
- How to order HGS/HGN 6a6b:Add AA in the order form.
Applicable Load Resistance Lamp Inductor Motor Wire Specification AWG Insulation Level (V)
AC 125 V 5A 0.7 A 4A 1.3 A Specification 20 300
AC 250 V 5A 0.5 A 4A 0.8 A
AUX Switch
Air Circuit Breakers 61
VCB
Counter OCR Manual/Auto Reset & Alarm Switch Reset
˙It is a device that displays the number of operations, indicating ˙It is a device that interlocks the closing of the circuit breaker
On/Off operation of the circuit breaker in 1 cycle. until the electric line is restored after the user has completely
˙It is a primary component so separate order is unnecessary. removed the fault factor when a circuit breaker tripped by OCR
due to overload or fault current in the electric line. (BR)
˙BR:When the circuit breaker functions due to OCR, it interlocks
to prevent closing of circuit breaker and is reset manually.
˙BA:When the circuit breaker functions due to OCR, the circuit
breaker’s status is indicated as output contact 2a other
than the interlock feature and this output contact is reset
manually.
ACB
˙BH:When the circuit breaker functions due to OCR, the circuit
breaker’s status is indicated as output contact high
capacity switch other than the interlock feature and this
output contact is reset manually.
˙As a product mounted in the main unit, add BR/BA/BH in the
order form when ordering the main unit.
Ordering Method
MCCB
OCR Manual Reset BR Interlock Manual Reset
MS
Counter
62 Air Circuit Breakers
Accessories
Position Switch
˙This switch, mounted at the side of the cradle, displays the Position Switch
position of ACB during draw-out.
˙The position of Inserted/Isolated/Test/Connected can be
displayed.
˙Only one switch is applicable and it can only be mounted at the
right side of the cradle.
˙It can be purchased separately.
Ordering Method
Operating Sequence of
Position Switch Operation Circuit Connection Diagram Dimension
Unit:mm
61 64 71 74 81 84
61 64 71 74 81 84 63.5
Insert
Isol TestInsert Connect
Isol Test Connect
Connect
Connect
Test
Test 62 63 65 66 72 73 75 76 82 83 85 86
Test 62 63 65 66 Isolation
Connection 72 73 75 76 82 83 85 86
Isol
Isol Position Position
Test Postion
Connection Isolation
61-62 a Position
71-72 a Position
81-82 a Postion
Insert 61-63 b 71-73 b a
61-62 81-83
71-72 ba 81-82 a
Insert 64-65 a 61-63
74-75 a b 71-73 b
INSERT 81-83 b
64-66 b 74-76 b a
64-65 POSITION
74-75 a INSERT
67-68 a 64-66
77-78 a b 74-76 ab
91-92 POSITION
67-69 b 77-79 b a
67-68 91-93
77-78 ba 91-92 a
67-69 b 77-79 b 91-93 b
Air Circuit Breakers 63
VCB
Lifting Lug Dummy ACB
˙It is a component that is used for transporting the circuit ˙The dummy ACB is applied as emergency in case of a long-
breaker. term black out for repair when a malfunction has occurred in a
˙It can be hung to the handle at the side of the cradle, side of the device when using the ACB. It is a frame used to conduct ACB’s
arc shield and the main unit and the product can be moved by function temporarily.
a crane or a person. ˙As the circuit breaker is closed, the primary power must be
˙When handling all the products, use the crane and in case of removed in the electric line when connecting the Dummy ACB.
transporting independently using only the crane in case of ˙Each frame is provided in the maximum rated current.
products below 3,200 A, the products must be transported in ˙It can be ordered separately. Make a separate inquiry when
accordance with the safety regulations. placing the order.
˙As a product sold separately, place an order for HGNS AL.
ACB
Ordering Method
MCCB
Lifting Lug
MS
RELAY
64 Air Circuit Breakers
Accessories
Mechanical Interlock
˙MI is a device that mechanically interlocks the closing and
tripping of each circuit breaker by connecting 2 or 3 circuit
breakers.
˙The MI is operated by a combination of the MI unit and the
components of the interlock that is installed inside the main unit.
˙The MI unit is a separate product and it is a device that is mounted
additionally after the ACB has to be installed in the panel.
˙When placing the order for the main unit, add B0 in the order
from and only the component inside the interlock is mounted
inside the main unit for release and as for the external
mounting kit, place an additional order as a separate product.
˙MI wire should be connected under 2 m between ACBs. Mechanical
Interlock
˙In order to install, a square hole of 100×200 (mm) is required.
Ordering Method
A & B & C & D Frame Draw-Out (Fixed) Type C Frame 3P Draw-Out 3 Way MI +
HGNS DWB1 HGNS DWB2C3
2 Way MI (External Mounting Kit Only) Interlock Part (B0)
A & B & C & D Frame Draw-Out (Fixed) Type C Frame 4P Draw-Out 3 Way MI +
HGNS DWB2 HGNS DWB2C4
3 Way MI (External Mounting Kit Only) Interlock Part (B0)
HGNS B0DD3 D Frame 3P Interlock Part (B0) HGNS FWB1A A Frame Fixed Type 2 Way MI + Interlock Part (B0)
HGNS B0DD4 D Frame 4P Interlock Part (B0) HGNS FWB2A A Frame Fixed Type 3 Way MI + Interlock Part (B0)
A Frame Interlock Part (B0) + HGNS FWB1B B Frame Fixed Type 2 Way MI + Interlock Part (B0)
Mechanical HGNS B0FA
Fixed Type of Installation Bracket HGNS FWB2B B Frame Fixed Type 3 Way MI + Interlock Part (B0)
Interlock Mechanical
Interlock
B Frame Interlock Part (B0) + C Frame 3P Fixed Type 2 Way MI +
HGNS B0FB HGNS FWB1C3
Fixed Type of Installation Bracket Interlock Part (B0)
HGNS DWB1A A Frame Draw-Out Type 2 Way MI + Interlock Part (B0) D Frame 4P Fixed Type 2 Way MI +
HGNS FWB1D4
HGNS DWB2A A Frame Draw-Out Type 3 Way MI + Interlock Part (B0) Interlock Part (B0)
HGNS DWB1B B Frame Draw-Out Type 2 Way MI + Interlock Part (B0) D Frame 3P Fixed Type 3 Way MI +
HGNS FWB2D3
HGNS DWB2B B Frame Draw-Out Type 3 Way MI + Interlock Part (B0) Interlock Part (B0)
HGNS DWB1C3 C Frame 3P Draw-Out 2 Way MI + Interlock Part (B0) D Frame 4P Fixed Type 3 Way MI +
HGNS FWB2D4
HGNS DWB1C4 C Frame 4P Draw-Out 2 Way MI + Interlock Part (B0) Interlock Part (B0)
Air Circuit Breakers 65
VCB
Key Lock Key Lock & Key Interlock
˙It is a device that maintains the interlock condition to prevent ˙3 circuit breakers mounted with the key lock device for
electric/manual closing when the circuit breaker is open. preventing On can be used to make up the system. Only 2
˙When the key has been used to unlock, the electric/manual On/ circuit breakers can be allowed to close using 2 keys and the
Off operation is possible. When the key has been removed from remaining 1 unit can be interlocked to provide stable load.
the circuit breaker, it becomes interlocked. When the key has
been used to lock, the Off button has to be pressed to turn the
key to the lock position.
˙As a product mounted on the main unit, add AB in the order Circuit Breaker 3 cannot be closed
form when placing an order for the main unit. Power 1 Power 2
Circuit Breaker 1 Circuit Breaker 2
ACB
Bus-Tie
Circuit Breaker 3
Load 1 Load 2
MCCB
Bus-Tie
Circuit Breaker 3
Load 1 Load 2
Bus-Tie
Circuit Breaker 3 MS
Load 1 Load 2
Accessories
On/Off Button Lock DR Device Unit & Position Pad Lock
˙It is a safety device that prevents manual On/Off operation ˙As for the draw-out type of circuit breaker, DR device is mounted
caused by the user’s mistaken. The buttons are covered with a on the main unit.
plastic cover to prevent arbitrary operation of manual close/trip ˙DR device is comprised of a groove for inserting draw-out
button and padlock is used. handle, draw-out push button, position indicator and a padlock
˙As a product mounted on the main unit, add AM in the order device.
form when placing an order for the main unit. ˙As for the padlock device, it is provided as a standard safety
˙Padlock is not provided by our company. (Ø5 ~ Ø8) device that prevents arbitrary draw-out by using a padlock in
the connection/test/isolated position but the padlock is not
provided by our company. (Ø5 ~ Ø8)
˙It can be purchased separately.
VCB
Auto Connection Type & Manual Control Short “b” Contact
Plug Type
˙As for the method of connecting the control power, auto ˙When the circuit breaker is moved from the Connected
connection type in which the control power is automatically position to the Test position, the auxiliary contact AUX “b” is
connected/isolated when the main unit is drawn out and disconnected to maintain the external control circuit in normal,
manual connection type in which the user directly inserts the ultimately maintaining an accurate sequence operation.
connector with the control power connected to the main unit As for the number of shorting “b” contact, it corresponds to the
are available. number of AUX “b” (5b).
˙Fixed type is provided with manual control plug type as ˙Upon outgoing, only 1b (51, 52) is mounted and as for the
standard so that type of connection terminal of the main power remaining 4b, it is sealed together with the manual pack so it
can be designated without separate indication. can be mounted as much as needed for use.
ACB
˙When completely removing the manual connection type of ˙As a product mounted on the main unit, add AK in the order
product from the cradle, the main unit has to be separated after form when placing an order for the main unit.
removing the connector.
˙As a product mounted on the cradle, select A for automatic Indication of Contact Status
connection type and J for manual connection type. (When AUX “b” and Short “b” are Connected)
ACB Operating
ACB Close ACB Open
(AUX “b” Off) (AUX “b” On)
ACB Position
OFF
OFF ON
ON
Connected Position
MCCB
(Short “b” Off) AUX
AUX "b"
"b" OFF
OFF Short
Short "b"
"b" AUX
AUX "b"
"b" ON
ON Short
Short "b"
"b"
MS
RELAY
68 Air Circuit Breakers
Accessories
Miss-Insertion Preventor
˙Although the external size is equivalent, in case the rating does Part’s Mounting Position per Rated Current
not conform when the main unit of the circuit breaker (ACB)
is inserted in the cradle in the composition of another circuit
breaker, this device prevents it from being inserted.
˙It is comprised based on the CT rated current.
˙Each component is mounted on the main unit and cradle
respectively. Add AW in the main unit and cradle’s order form
1
respectively when placing the order. 2
3
4
5
1 A
6
2 B
Ordering Method
3 C
7
4 D
5 E
6 F
7 G
7 G
4 D
5 E
6 F
Miss-Insertion Preventer
Air Circuit Breakers 69
VCB
Phase Insulation Barrier Safety Shutter & Shutter Lock
˙Phase insulation barrier is a part installed between phases that ˙It is a safety device that prevents the contact between the
prevents short circuit between phases in advance by closing the conductor part and the front part when the main unit of the
arc which may occur between phases. circuit breaker mounted on the cradle is drawn out.
˙2 ea are mounted for 3P Type and 3 ea are mounted for 4P Type ˙The structure automatically opens and closes when the circuit
and as they are sold individually, select the required quantity breaker is drawn out and it comes with a shutter lock device
when placing the order. that prevents it from opening when the shutter is closed in the
˙As a product sold separately, place an order in HGNS P BAR. event the main unit is drawn out. The padlock is not provided
by our company. (Ø5 ~ Ø8)
˙As for the shutter, the power side and load side operates
separately, each equipped with an operation device and they
ACB
can be locked individually.
˙As a product mounted on the cradle, add AE in the order form
when placing the order for the cradle.
Ordering Method
MCCB
HGNS AEB3 B Frame, 2,000 ~ 4,000 A, 3P
MS
Safety Shutter &
Shutter Lock
RELAY
70 Air Circuit Breakers
Accessories
Fixing Block Control Terminal Protection Cover
˙It is a safety device for reinforcement in order to prevent ˙It is a safety cover that is placed on the connection terminal to
abnormal operation caused by vibration. prevent contact with external foreign substances or physical
˙It is capable of simultaneously fixing the main unit and the contact after the control power has been connected to the
cradle and reinforcing the cradles and panel supporters. automatic connection type of terminal.
˙Each component is mounted on the main unit and the cradle. ˙It cannot be applied to fixed type ACB and draw-out type ACB
Add AF in the respective order form of the main unit and cradle with manual connection terminal.
when placing the order. ˙As a product mounted on the cradle, add BC when placing an
order for the draw-out type with automatic connection type.
Fixing Block
Air Circuit Breakers 71
VCB
Terminal Bus Bar (Draw-Out Type)
˙HG-Series ACB is compatible with various type of terminal bus bar such as vertical, horizontal, front and others depending on the type
of bus bar of the customer’s equipment and the terminal can be changed to A frame (630 ~ 1,600 A) and B frame (630 ~ 3,200 A).
˙The front type of terminal bus bar is released separately from the main unit and cradle so it needs to be installed at site. In addition,
the front type of terminal bus bar requires separate order so refer to the following table when placing the order.
˙As for the front type of terminal bus bar that is provided separately for the B frame 2,000/2,500 A, 3,200 A terminal is provided.
˙Front type of terminal bus bar is sold separately.
ACB
(Upper) Vertical Type (Upper) Horizontal Type (Upper) Vertical Type Vertical Type Horizontal Type Front Type
+ + +
(Lower) Horizontal Type (Lower) Vertical Type (Lower) Front Type
MCCB
(Upper) Horizontal Type (Upper) Front Type (Upper) Front Type
+ + +
(Lower) Front Type (Lower) Vertical Type (Lower) Horizontal Type
MS
Ordering Method
HGNS HVA3 Up-Down Horizontal Type/Up-Down Vertical Type 6 ea (A Frame, 630 ~ 1,600 A, 3P)
HGNS HVA4 Up-Down Horizontal Type/Up-Down Vertical Type 8 ea (A Frame, 630 ~ 1,600 A, 4P)
HGNS HVB3 Up-Down Horizontal Type/Up-Down Vertical Type 6 ea (B Frame, 2,000 ~ 3,200 A, 3P)
HGNS HVB4 Up-Down Horizontal Type/Up-Down Vertical Type 8 ea (B Frame, 2,000 ~ 3,200 A, 4P)
HGNS FRA3 Up-Down Front Type 6 ea (A Frame, 630 ~ 1,600 A, 3P)
Connection Terminal HGNS FRA4 Up-Down Front Type 8 ea (A Frame, 630 ~ 1,600 A, 4P)
RELAY
(Draw-Out Type) HGNS FRB3 Up-Down Front Type 6 ea (B Frame, 2,000 ~ 3,200 A, 3P)
HGNS FRB4 Up-Down Front Type 8 ea (B Frame, 2,000 ~ 3,200 A, 4P)
HGNS FHVA3 Up-Down Front Type 3 ea + Horizontal Type/Vertical Type 3 ea (A Frame, 630 ~ 1,600 A, 3P)
HGNS FHVA4 Up-Down Front Type 4 ea + Horizontal Type/Vertical Type 4 ea (A Frame, 630 ~ 1,600 A, 4P)
HGNS FHVB3 Up-Down Front Type 3 ea + Horizontal Type/Vertical Type 3 ea (B Frame, 2,000 ~ 3,200 A, 3P)
HGNS FHVB4 Up-Down Front Type 4 ea + Horizontal Type/Vertical Type 4 ea (B Frame, 2,000 ~ 3,200 A, 4P)
72 Air Circuit Breakers
Accessories
Arc Shield
˙Arc which occurs while breaking the circuit breaker is Ordering Method
extinguished through the arc chamber within the main unit or
as the residual arc is discharged to the external upper part, the Order Name Order Name for
Name of
Placed upon Separate Sales Detailed Specification
Accessory
basic distance required for insulation has to be maintained. Outgoing (HGNS-)
Arc Shield
Air Circuit Breakers 73
VCB
RCTU Temperature Monitoring Device Module
˙This product is a module that closes and prevents the ACB ˙This product detects the bus bar temperature of the ACB
remotely by using communication. through the temperature sensor installed on the temporary
˙This product uses Modbus/RS-485 communication. location of ACB and displays it.
˙Close/Open control of ACB assures its reliability through SBO ˙Up to 3 temperature sensor can be installed and it can trigger
(Select Before Operation) function. the designated temperature alarm through a separate
˙It can be used together with the temperature monitoring device temperature contact.
module and as for the detailed rating, refer to the table in Page 98. ˙It supports Modbus/RS–485 communication and the each
channel’s temperature value and the maximum temperature
value out of the channel are transmitted through
Contact Specification
communication.
ACB
For ACB Control Applicable Range ˙The alarm for operating temperature value can be set through
Contact Ratings 10 A 240 VAC, 30 VDC communication.
Max Switching Power 10 A 240 VAC, 30 VDC ˙The temperature value of each channel can be checked
through the Segment LED mounted at the front and once it
Dimension reaches the temperature alarm set by the user, the temperature
value of the relevant channel is displayed.
105
˙As a product sold separately, it can be installed in the ACB and
7(Panel Protrusion) 70
the internal panel. As a module that can be used together with
the remote breaking module, refer to the table on Page 98.
˙This product is an optional product of remote breaking module
and it is only sold as a combination type with the remote
91.4
75
60
MCCB
breaking module.
121.4
33
2-Ø4.2 (Use M4 X 25L Screw) 77 Contact Specification
MS
RELAY
74 Air Circuit Breakers
Accessories
Temperature Sensor Unit
˙Detailed specification of Remote Control Temperature Unit (RCTU) Contact Specification
- RCTU is equipped with a contact that enables remote
Item Applicable Range
insertion/disconnection of ACB using communication.
Contact Ratings 10 A 240 VAC, 30 VDC
Through the 4 temperature channels, the temperature of ACB ACB Control
Max Switching Power 2,400 VA, 300 W
is measured.
Temperature Contact Ratings 10 A 120 VAC/5 A 240 VAC 5 A 30 VDC
- RCTU supports RS-485/Modbus-RTU communication. Alarm Max Switching Power 1,200 VA, 150 W
- Insertion/disconnection control of ACB assures its reliability
through SBO (Select Before Operation) function.
- If the temperature rises over the value set by the user through
communication, it can be checked through the alarm
contacting point (Additional connection required).
- The temperature of ACB can be checked through the Segment
LED at the front.
- RCTU can be installed in the ACB’s cradle or panel.
- RCU module is equipped with the same function other than
LED
the temperature monitoring function in the RCTU module.
Terminal Block
VCB
Block Diagram
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
ACB
IR Sensor IR Sensor IR Sensor
NTC No 3 No 2 No 1 RS 485
Sensor
B G Y R B G Y R B G Y R - +
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
MCCB
MS
RELAY
76 Air Circuit Breakers
Accessories
Temperature Sensor
˙The temperature sensor is mounted on the designated position Communication Specification
as standard but another location can be designated by the user. ˙RS-485 (Modbus-RTU)
˙It is sold separately. ˙Baud Rate:9,600, 19,200, 38,400 bps (Default:9,600)
˙Data Bits:8 bits
Ordering Method ˙Parity:None
˙Stop Bits:1 bits
Order Name for
Name of Detailed
Separate Sales
Accessory Specification
(HGNS-) Address Setting:1 ~ 240
Physical Medium
˙Shielded Twister Pair cable used
VCB
IR (Infrared Sensor) Specification (Option)
ACB
Sense on Bolt or Busbar RCTU Sensor
Busbar
Busbar
RCTU Sensor
Distance = 40 ~ 80 mm
* How to Install
Distance = 40 ~ 80 mm
MCCB
Cable Length 3 m
Field of View
50 % at Half Energy Points Optical Axis - 3.5 0 + 3.5 Degree Sensor View Direction
Field of View 6 11 Degree 50 % Energy Points
IR Sensor Measurement
˙IR temperature sensor has to be installed with sufficient insulation distance from the measuring point.
˙The recommended distance between the measuring point and the temperature sensor is 50 ~ 80 mm.
˙The measuring point must be a surface without reflection due to the characteristics of the IR sensor and black matte painting is
recommended at the measuring point.
MS
Caution
1. As for the IR sensor, the measurement value differs depending on the reflection rate of the metal surface. Measuring point with surfaced painted with matte black
or varnish other than metallic varnishing must be measured.
2. As for the surface to be measured and the IR distance, the size of measurement area differs depending on the D:S Ratio. This sensor has a ratio of 8:1.
RELAY
78 Air Circuit Breakers
Accessories
Temperature Sensor
Control Contact Connection
HGN
ACB Information Pin
CC TC
3 7
4 8
ACB Close/Open
ACB Information ACB Position
Control
RCTU
Terminal 11 13 5 7 3 1
3 7 45 47 49 55 57 61 71
ACB
Circuit CC TC
4 8 46 48 50 56 58 62 63 72 73
RCTU
Terminal 12 14 6 8 4 2
VCB
OCR Portable Checker
˙OCR Portable Checker (Hereinafter referred to as the Checker)
executes the relay test operation of the OCR (Hereinafter
referred to as the OCR) (Long time/short time delay/
instantaneous/ground fault).
˙It is possible to set the current size and phases using button for
the OCR test.
˙The relay test factors can be set through the front LCD and the
operating time can be checked.
˙It is equipped with a battery so it can be used without a
separate external power.
ACB
˙As for the cable connector of the checker, connect when the
control power of OCR is off when inserting the OCR.
˙As a product sold separately, place an order for HGNS OCC.
˙HGNS OCC is a product with a calibration certificate issued by a
specializing institute.
Ratings
MCCB
Battery Alkaline 9 V:3 ea
Trip Time Measurement 0 ~ 999.999 sec
Test Output 0.3 Ict ~ 17 Ict
Output Precision ± 20 % (1 Ict ~ 17 Ict)
Size (mm) 193.40 (H) × 110.60 (W) × 44.60 (D)
❶ ❷ ❸ ❹ ❸ ❹
110.60
❶
MS
193.40
❺
❺ ❻
44.60
❶ UP Move Menu and Increase Setting Value ❶ LCD Indicates Menu, Setting Current, Trip Time
❷ DOWN Move Menu and Decrease Setting Value ❷ Key Pad Move Menu and Setting
❸ FUNC Move to the Previous Menu and Return to the Setup Screen ❸ Signal Output Terminal OCR Connection Terminal
Save the Setting and Move the Number of Digits of ❹ Power Switch Power On/Off
❹ ENTER
Setting Current ❺ Adapter Terminal Control Terminal of Checker
❺ START Generate Waveform
❻ STOP Stop Waveform
80 Air Circuit Breakers
Accessories
OCR Checker
Multi-functional OCR checker is test equipment that can inspect Rating Specification
the OCR operation in unloaded status and the OCR status can be Control Power AC/DC 85 ~ 270 V (50/60 Hz)
inspected through communication.
Output Channel:4 (R, S, T, N)
Output Test Output:0.4 ~ 17 Ict
˙Control Power:AC/DC 85 ~ 270 V (50/60 Hz) Precision:± 3 %
˙Specification
Communication:RS 485
Input
- Dimension:411 (L) × 321 (W) × 165 (H) Touch-Screen of HMI
- Weight:8 kg Size 411×321×165 mm, 8 kg
˙Key Functions
- I nspection of LTD, STD, INST, GFT operation and operating time
- Inspection of PTA operation (Pre Trip Alarm)
- Touch LCD
Air Circuit Breakers 81
VCB
NCT (Neutral CT)
˙It is a separate mounting type of current transform installed Ordering Method
in the N phase in case of protecting the earth fault by using
Name of Order Name for
3-pole air circuit breaker with earth fault protection features in Accessory Separate Sales (HGNS-)
Detailed Specification
ACB
HGNS NCT_N NCT N = 2,500 A/Inner Diameter 135
power (k), 30 (ℓ) to the 3-pole circuit breaker. HGNS NCT_P NCT P = 3,200 A/Inner Diameter 135
HGNS NCT_Q NCT Q = 4,000 A/Inner Diameter 200
HGNS NCT_S NCT S = 5,000 A/Inner Diameter 200
HGNS NCT_X NCT×= 6,300 A/Inner Diameter 200
Externals
Unit:mm
150 W
K 4- 4-
Ø1 Ø1
MCCB
4 4
Ø80
175
Sec. M5
35 00
Ø1 Ø2
300
240
300
300
240
300
97
25
80
107 100
75 SUS 2T
30
30
30 240 40 30 240 40
17.5
300 300
10
MS
RELAY
82 Air Circuit Breakers
Accessories
CTD-Condenser Trip Device
˙In case of using AC/DC power for trip control of the circuit
breaker, it is a device that can electrically trip the circuit breaker
once by using the power charged in the CTD when the supply of
control voltage has been stopped due to black-out and others.
˙It is a product sold separately.
PB(Open)
7
Ratings
Item Details
YC
Rated Input Voltage AC 110 V AC 220 V
Normal Charging Voltage DC 145 V DC 290 V
Normal Current Capacity DC 2 A
Rated Frequency 50/60 Hz
Delay Circuit Time Within 1.5 sec 8
Unit:mm
72 130 1 6
7
R1
6
-Ø
2
SA RY R2 R3
22
72
SW C1 NL
2
80 5
3 4
90
˙AC Input Power NO. 1, 2 ˙DC Normal Power NO. 6 (+), 5 (-)
˙CTD Trip Power NO. 7 (+), 5 (-) ˙Delay Contact NO. 3, 4
Air Circuit Breakers 83
VCB
Test Jumper
˙It is a device that enables the main unit to be operated
independently by separating the automatic connection type of
main unit from the cradle.
˙As a product sold separately, place an order for HGNS AJ when
ordering.
ACB
190
Draw-In/Out Handle 770
MCCB
˙In case the standard handle is uncomfortable when drawing
the circuit breaker in and out, Long Type Handle and Universal
Joint Handle which are sold separately can be used.
˙As a product sold separately, place an order of HGNS LHANDLE
or HGNS UHANDLE.
190
190
750
770
Type
MS
620
190
190
770 750
400
Ordering Method
RELAY
620
Accessories
Door Flange Dust Cover
˙It is an auxiliary device mounted on the cutting part of the panel ˙It is a device installed to protect against dust and moisture
door at the front protrusion mounting type of ACB. mounted on the cutting part of the panel door at the front
˙The door flange of our company is IP30. protrusion mounting type of ACB.
˙As for the cutting dimension of the panel, refer to the external ˙The dust cover of our company is IP52.
drawing. ˙The cover can be locked in the test and connected position.
˙As for the panel cutting dimension, it is equivalent for both the ˙The cutting dimension of the panel must be referred to.
draw-out and fixed type and it is the same even if the dust cover ˙As a product sold separately, place an order for HGNS DC.
is installed.
˙As a product sold separately, place an order for HGNS AG.
Unit:mm Unit:mm
Operaing
Panel Center
292
196 196 R5
R5 4-
103.5 100 103.5 4- 292 292
4- 2
Ø5 42.5 103.5 100 103.5 42.5 Ø5. 103.5 100
.2 4-
122.5
20
122.5
15
345
115
290
229
115
345
4
-Ø
122.5
12
4
-Ø
7.5
122.5
12
68.6 15
7.5
Bottom
20
33.1
7.5 25.6
Operaing
Panel Center
196 196 R5
4- 292
292 103.5 100
4-
Ø5 42.5 103.5 100 103.5 42.5 5 .2
.2 4 -Ø
20
122.5
15
290
229
115
345
Door Flange
4
-Ø
122.5
12
68.6 15
7.5
20
Bottom
Bottom
Dust Cover
33.1
7.5
25.6
Air Circuit Breakers 85
VCB
ATS & Controller
Features
˙Stable Transfer System
By applying Hyundai air circuit breaker equipped with the
highest rated breaking capacity in Korea, it has outstanding
protective features with regards to electric power system, 4
making it optimal for places in which stable power supply is
compulsory (Communication base station, computer center,
hospital, plant equipment and other important facilities).
˙Unmanned Working System
Unmanned power transfer is possible by applying automatic
ACB
power control device in the ACB equipped with mechanical
interlock device.
˙Various Modes ACB1
Various modes is possible as it is equipped with 4 selection 3
MCCB
ACB is more compact and lightweight so it can easily be
3 ACB2
installed in the ATS switchgear and occupies less space.
˙ATS Configuration and Interlock
- ACB1:“Normal” power (Power company side)
- ACB2:“Stand-by” power (Power generator side)
- 3:Mechanical interlock device unit
- 4:ATS unit
Each ACB should meet the following specifications.
- Geared charge type of mechanism (Control power of AC 220 V)
- TC (Control power of AC 220 V)
- CC (Control power of AC 220 V)
- Trip device for overload or short protection (2a contact)
MS
Transfer System’s Interlock Conditions
ACB1 ACB2
Open Open
Close Open
Open Close
RELAY
ACB1 ACB2
※ As a product sold separately, place an order for HGNS ATS when placing an order.
However, M1 has to be ordered separately and B0, BA must be added when placing an
order for the product.
86 Air Circuit Breakers
Accessories
ATS & Controller
Characteristics per Mode
There are 4 selection modes.
˙Stop/Manu Mode
220/240 V 50/60 Hz t1
This mode offers On/Off functions using ACB Manual from the 1
2 4
8
N UN = 0
power company side and generator side. N UN R UR 0.5 15
0.1 30
˙Auto Mode
ON/I ON/I
This mode is for automatically controlling the ACB depending 0.5 s 0.5 s
˙N Mode (Forced Operation of Power Company Power) Fault Fault 0.1 240
UN = I R
This mode turns off the ACB at the generator side and turns on
Reset
the ACB at the power company side by force. Stop Auto
˙R Mode (Forced Operation of Generator Power) Manu
This mode turns off the ACB at the power company side and
turns on the ACB at the generator side by force.
N R
Operation Characteristics
T1 (ms) T2 (ms)
Status
0.1-30 500 250 0.1-240 500 250
I (On)
UR (Stand-by Power)
○ (Off)
I (On)
KR (Re-Inspection)
○ (Off)
I (On)
QN (Normal
Power Cut-Off)
○ (Off)
I (On)
QR (Stand-by
Power Cut-Off)
○ (Off)
Air Circuit Breakers 87
VCB
System Operation
N R
4-Position Switch
ACB1 and ACB2 “Normal”
Off (N Position, UN Supplied)
Manual Trip Power ON
I O
ACB
ACB2 Trip
Voltage Un Lost (More than setting value of 1 t)
Auto Mode
or when Auto Switching Command is Received
t > 0.5 s
ACB1 Trip
Reset 1s
ACB1 Input
t > 0.5 s
Reset Complete
Operation Stopped
ACB2 Input Complete
MCCB
N R I O
I O
When Voltage on Exists for t > t2 or
when Auto Switch Command is Stopped
R Mode (“Stand-by” Power Forced ON)
ACB2 Trip
MS
ACB1 Input
ACB1 Trip
ACB2 Input
N R
RELAY
Accessories
ATS & Controller
Circuit Diagram of the System [ HGS/HGN Type ]
1
STOP
2 1
Power Company ON 1
Control Circuit Terminal Block
B1
A1
A1
AUX.SW.
1
1
Control Circuit Terminal Block
1 2 TC M CC
COMMON 2
Control Circuit Terminal Block
2 3
STOP 7
5 6
AUTO 37
7
53
8
43
54 44 38 8 2 4
※ 1) The standard model is a SW mounting type on controller. (Control terminal type is not a standard model)
Auto Power Switch System’s Auxiliary Device Circuit Diagram applied with 2 ACBs
45
R S T R S T
12
MCCB at MCCB at 46
Power Company Generator 11
47
Side Side 10
48
9
55
Controller IVE 56
8
7
N R 57
6
58
5
4
3
2
1
20
1
3 19
18
7
17
19
16
20
15
37
14
38
13
ATS Terminal Block
45
12
46
11
47
10
48
9
Power Company Side ACB 55
56
8
7
57
6
58
5
4
3
2
Generator Side ACB 1
Air Circuit Breakers 89
VCB
“Stand-by” Circuit Breaker’s Auxiliary Device
37 38 OCR DO
53 43 37 7 1 3
43 44 Auxiliary a Switch Terminal
ACB
Spring 53 54 Auxiliary b Switch Terminal
Charge
“OFF”SW TC Voltage Trip
B1
A1
A1
AUX.SW.
Charging Motor
OCR Alarm SW.
M
Latch Release (Close)
AUX. SW.
CC
54 44 38 8 2 4
MCCB
ATS Panel Remote Circuit Diagram
1
PB (Close) Power is supplied from ATS controller so
3
ATS Controller at Power Company Normal PB (Open) power should not be applied from outside. 1)
7
Control Voltage (AC 220 V) ACB 19
20 OCR Control Power AC/DC 100 ~ 250 S0-S2
N R
ATS Terminal Block
37
38 OCR + OCGR “1a” Contact
45
46
47
48
55
AUX. SW. 2a-2b
MS
56
57
58
1
PB (Close) Power is supplied from ATS controller so
Stand-by 3
PB (Open) power should not be applied from outside. 1)
7
ACB 19
20 OCR Control Power AC/DC 100 ~ 250 S0-S2
ATS Terminal Block
37
38 OCR + OCGR “1a” Contact
45
46
RELAY
47
48 AUX. SW. 2a-2b
55
ATS Controller at Generator Side 56
Control Voltage (AC 220 V) 57
58
※ 1) Upon remote operation, as for the Open/Close power, the power is supplied from the ATS control device so do not input a separate control power supply. (Terminal number “1”, “7”, “16”)
90 Air Circuit Breakers
Accessories
ATS & Controller
Dimensions [ ATS HGN A Frame ]
Unit:mm
HGN06 ~ 16 A [ Front ] [ Vertical Type ] [ Horizontal Type ]
40 470
89 220 89
20.5 128 36 154
27.5
245
46.3
46.3
39.9 79 39.9 79
50 94.1 50
15
159.1
343
20.1
15
1,810
420.9
455.9
1,440
615
50 94.1 50
15
159.1
343
20.1
15
357.05
374.55
250
Unit:mm
HGN20 A [ Front ] [ Vertical Type ]
40 89
128 36 154
20.5
27.5
245
46.3
39.9 79
75 69.1 75
343
20.1
1,810
395.9
1,440
615
75 69.1 75
343
20.1
344.6
250
※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 91
VCB
Dimensions [ ATS HGN B Frame ]
Unit:mm
HGN20 ~ 25 B [ Front ] [ Vertical Type ] [ Horizontal Type ]
140
40 89 89
128 36 154
27.5
20.5
245
ACB
75 68.1 75
20 20
163.1
343
20.1
1,810
396.9
451.9
1,440
615
75 68.1 75
20 20
163.1
343
20.1
345.05
372.55
MCCB
250
Unit:mm
HGN32 B [ Front ] [ Vertical Type ] [ Horizontal Type ]
140
40 89 89
128 36 154
27.5
20.5
245
MS
20
90 53.1 90
123.1
343
20
20.1
1,810
615
381.9
1,440
615
20
90 53.1 90
163.1
343
20
20.1
RELAY
372.55
337.55
250
※ The drawing dimension of this page may be subject to change without prior notice.
92 Air Circuit Breakers
Accessories
ATS & Controller
Dimensions [ ATS HGN B Frame ]
Unit:mm
HGN40 B [ Front ] [ Vertical Type ] [ Horizontal Type ]
140
40
128 36 154 89 89
27.5
20.5
245
15
125
40 128 40
15
343
68
15
125
20.1
1,810
15
407
297
1,440
15
615
68 125
40 128 40
15
343
15
125
20.1
15
362.55
295.05
250
※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 93
VCB
Dimensions [ ATS HGN C Frame ]
Unit:mm
HGN40 ~ 50 C, [ Front ] [ Vertical Type ] [ Horizontal Type ]
3P
240
40 89 89
128 36 154
20.5
27.5
245
ACB
20
110 86.1 110
125 69.1 125
20
343
20
20
20.1
1,810
295.9
308.9
1,440
615
20
110 86.1 110
125 69.1 125
20
343
20
20
20.1
301.1
294.5
MCCB
250
Unit:mm
HGN40 ~ 50 C, [ Front ] [ Vertical Type ] [ Horizontal Type ]
4P 440
40 128 36 154 89 89
20.5
27.5
245
MS
125 69.1 125
20
20
1,810
20.1
295.9
308.9
1,440
615
20
20
20.1
RELAY
301.1
294.5
250
※ The drawing dimension of this page may be subject to change without prior notice.
94 Air Circuit Breakers
Accessories
ATS & Controller
Dimensions [ ATS HGN D Frame ]
Unit:mm
HGN40 D, 3P [ Front ] [ Vertical Type ] [ Horizontal Type ]
440
40 128 36 154 89 89
27.5
245 20.5
20
110 83.1 110
125 68.1 125
20
343
20
20
1,810
19.1
311.9
295.9
1,440
615
20
110 83.1 110
20
343
20
20
19.1
302.5
294.5
250
Unit:mm
HGN40 D, 4P [ Front ] [ Vertical Type ] [ Horizontal Type ]
40 128 36 154 89 89
20.5
27.5
245
20
343
20
1,810
20
19.1
311.9
295.9
1,440
615
20
110 83.1 110
125 69.1 125
20
343
20
20
19.1
294.5
302.5
250
※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 95
VCB
Unit:mm
HGN50 ~ 63 D, [ Front ] [ Vertical Type ] [ Horizontal Type ]
3P 440
40 128 36 154
89 89
20.5
27.5
245
ACB
68.1 150
20
110 83.1 110
20
343
20
1,810
20
150
19.1
311.9
246.9
1,440
615
68.1 150
20
110 83.1 110
20
343
20
20
150
19.1
302.5
MCCB
250
270
Unit:mm
HGN50 ~ 63 D, [ Front ] [ Vertical Type ] [ Horizontal Type ]
4P 40 128 36 154 89 89
20.5
27.5
245
MS
68.1 150
20
110 83.1 110
20
343
20
1,810
20
150
19.1
311.9
246.9
1,440
615
150
20
110 83.1 110
20
343
68.1
20
150
20
19.1
RELAY
302.5
250
270
※ The drawing dimension of this page may be subject to change without prior notice.
96 Air Circuit Breakers
Accessories
Order Code
Order Form
Name of Accessory Detailed Specification Release Form Page
Mounted Sold Separately
- HGNS HVA3 Up-Down Horizontal/Up-Down Vertical (A Frame, 06 ~ 16A 3P)
- HGNS HVA4 Up-Down Horizontal/Up-Down Vertical (A Frame, 06 ~ 16A 4P)
- HGNS HVB3 Up-Down Horizontal/Up-Down Vertical (B Frame, 06 ~ 32B 3P)
- HGNS HVB4 Up-Down Horizontal/Up-Down Vertical (B Frame, 06 ~ 32B 4P)
- HGNS FRA3 Up-Down Front 6 ea (A Frame, 06 ~ 16A 3P)
Terminal Bus Bar 1) - HGNS FRA4 Up-Down Front 8 ea (A Frame, 06 ~ 16A 4P)
Sold Separately -
(Draw-Out Type) - HGNS FRB3 Up-Down Front 6 ea (B Frame, 06 ~ 32B 3P)
- HGNS FRB4 Up-Down Front 8 ea (B Frame, 06 ~ 32B 4P)
- HGNS FHVA3 Up-Down Front 3 ea + Horizontal/Vertical 3 ea 06 ~ 16A 3P
- HGNS FHVA4 Up-Down Front 4 ea + Horizontal/Vertical 4 ea 06 ~ 16A 4P
- HGNS FHVB3 Up-Down Front 3 ea + Horizontal/Vertical 3 ea 06 ~ 32B 3P
- HGNS FHVB4 Up-Down Front 4 ea + Horizontal/Vertical 4 ea 06 ~ 32B 4P
- HGNS FRA3F Up-Down Front 6 ea (A Frame, 06 ~ 16A 3P) + Additional Spacer 6
- HGNS FRA4F Up-Down Front 8 ea (A Frame, 06 ~ 16A 4P) + Additional Spacer 8
- HGNS FRB3F Up-Down Front 6 ea (B Frame, 06 ~ 32B 3P) + Additional Spacer 6
Terminal Bus Bar 2) - HGNS FRB4F Up-Down Front 8 ea (B Frame, 06 ~ 32B 4P) + Additional Spacer 8
(Fixed Type) Sold Separately -
- HGNS FHVA3F Up-Down Front 3 ea + Horizontal/Vertical 3 ea 06 ~ 16A 3P + Additional Spacer 3
- HGNS FHVA4F Up-Down Front 4 ea + Horizontal/Vertical 4 ea 06 ~ 16A 4P + Additional Spacer 4
- HGNS FHVB3F Up-Down Front 3 ea + Horizontal/Vertical 3 ea 06 ~ 32B 3P + Additional Spacer 3
- HGNS FHVB4F Up-Down Front 4 ea + Horizontal/Vertical 4 ea 06 ~ 32B 4P + Additional Spacer 4
Automatic
Connection Control Automatic Connection Control Terminal Cover (Cannot be Mounted on Mounted upon Release
BC HGNS BC -
Terminal Protection Fixed Type, Manual Connection Type) and Sold Separately
Cover
※ 1) Only the terminal bus bar (Draw-out type) A frame 630 ~ 1,600A/B frame 2,000 ~ 3,200 A-draw-out type can be ordered.
2) Only the terminal bus bar (Fixed type) A frame 630 ~ 1,600A/B frame 2,000 ~ 3,200 A-fixed type can be ordered.
3) Contact us when placing an order for set order required for installation.
4) UVT time delay type of controller is mounted outside the main unit or the cradle.
Air Circuit Breakers 97
VCB
Order Form
Name of Accessory Detailed Specification Release Form Page
Mounted Sold Separately
ACB
HGNS AED3 40D3 ~ 63D3
HGNS AED4 40D4 ~ 63D4
MCCB
AV HGNS AV Isolated 2C Mounted upon Release
Position Switch 5) -
P4 HGNS P4 Test 2C, Connected 2C and Sold Separately
Arc Shield AX
HGNS AXB4 20B4 ~ 40B4 Mounted upon Release
and Sold Separately
- MS
HGNS AXC3 32C3 ~ 50C3
HGNS AXC4 32C4 ~ 50C4
HGNS AXD3 40D3 ~ 63D3
HGNS AXD4 40D4 ~ 63D4
- HGNS DWB1 Drawout (Fixed)/Wire Type 2 Way MI
- HGNS DWB2 Drawout (Fixed)/Wire Type 3 Way MI
- HGNS FWB1 Fixed/Wire Type 2 Way MI
- HGNS FWB2 Fixed/Wire Type 3 Way MI
Mech Interlock 6) Sold Separately -
- HGNS DWB1A A Frame, Draw-Out Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS DWB2A A Frame, Draw-Out Type, Wire Type 3 Way MI + Interlock Parts (B0)
RELAY
- HGNS DWB1B B Frame, Draw-Out Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS DWB2B B Frame, Draw-Out Type, Wire Type 3 Way MI + Interlock Parts (B0)
※ 5) Position switch cannot be used together and can only be mounted at the right side of the cradle.
6) Mechanical interlock is a wire type. The MI unit is mounted outside the main unit or on the cradle and the interlock part is mounted inside the main unit.
98 Air Circuit Breakers
Accessories
Order Code
Order Form
Name of Accessory Detailed Specification Release Form Page
Mounted Sold Separately
- HGNS DWB1C3 C Frame 3P, Draw-Out Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS DWB1C4 C Frame 4P, Draw-Out Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS DWB2C3 C Frame 3P, Draw-Out Type, Wire Type 3 Way MI + Interlock Parts (B0)
- HGNS DWB2C4 C Frame 4P, Draw-Out Type, Wire Type 3 Way MI + Interlock Parts (B0)
- HGNS FWB1A A Frame, Fixed Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS FWB2A A Frame, Fixed Type, Wire Type 3 Way MI + Interlock Parts (B0)
Sold Separately -
- HGNS FWB1B B Frame, Fixed Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS FWB2B B Frame, Fixed Type, Wire Type 3 Way MI + Interlock Parts (B0)
- HGNS FWB1C3 C Frame, 3P, Fixed Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS FWB1C4 C Frame, 4P, Fixed Type, Wire Type 2 Way MI + Interlock Parts (B0)
Mech Interlock 6)
- HGNS FWB2C3 C Frame, 3P, Fixed Type, Wire Type 3 Way MI + Interlock Parts (B0)
- HGNS FWB2C4 C Frame, 4P, Fixed Type, Wire Type 3 Way MI + Interlock Parts (B0)
HGNS B0DA A Frame, Interlock Parts (B0)
HGNS B0DB B Frame, Interlock Parts (B0)
HGNS B0DC3 C Frame, 3P Interlock Parts (B0)
HGNS B0DC4 C Frame, 4P Interlock Parts (B0) Mounted upon Release
BO -
HGNS B0FA A Frame, Interlock Parts (B0) + Fixed Bracket and Sold Separately
ATS Controller UNIT (ATS Controller + 2 Way M/I + Wiring Assemble) for Mounted upon Release
ATS Controller B6B7 HGNS ATS -
Draw Out and Sold Separately
Lifting LUG - HGNS AL 2 ea = 1 set, C Frame 5,000 A is Provided as Standard Sold Separately -
※6) Mechanical interlock is a wire type. The MI unit is mounted outside the main unit or on the cradle and the interlock part is mounted inside the main unit.
Air Circuit Breakers 99
VCB
Order Form
Name of Accessory Detailed Specification Release Form Page
Mounted Sold Separately
On/Off Button Lock AM HGNS AM On/Off Button Cover Lock Sold Separately -
Door Lock (On/Off) - HGNS DL_CO Pannel Door Lock for On/Off (In Case of On) In Course of Development Sold Separately -
Door Lock Pannel Door Lock for Position (In Case of Test or Connected)
- HGNS DL_PO Sold Separately -
(Position) > In Course of Development
ACB
- HGNS UHANDLE Universal Join Head Draw In-Out Handle
Draw In-Out Handle Sold Separately -
- HGNS THANDLE T Grip Long Type Draw In-Out Handle
- HGNS HANDLE Standard Draw In-Out Handle
MCCB
MS
RELAY
100 Air Circuit Breakers
Dimensions
HGS/HGN Fixed Type 630 ~ 2,000 A (HGS06 ~ 16/HGN06 ~ 20 A Frame) Unit:mm
Front
296 381
404.4
404.4
270
270
176.7 261.7
353.4 438.4
3P 4P
Vertical Type
8 313.4 8 398.4
85 85 85 85 85
15 15
40
40
14
14
186.8
152.5
186.8
152.5
4 4
Ø1 Ø1
20
20
109
109
35 13
35 13 3-Ø
2-Ø
50
75
50
50
15 15
25
144
330
144
330
75
50
132
132
33
33
60 49 186.8 60 49 186.8
295.8 43.6 295.8 43.6
※ The drawing dimension of this page may be subject to change without prior notice.
As for the HGN fixed type A type 2,000 A, only the vertical terminal can be applicable.
Air Circuit Breakers 101
VCB
Unit:mm
8 313.4 8 398.4
85 85 85 85 85
50 50
8 313.4 8 398.4
85 85 85 85 85
50 50
40
40
14
14
40152.5
186.8
152.5
186.8
4
Ø1
40
14
14
152.5
186.8
152.5
186.8
4
Ø1
ACB
20
20
109
109
20
20
109
109
35 13
2-Ø
15
35 13
50
2-Ø
15
50 25
15
129
144
330
15
25
129
15144
330
132
33
MCCB
15
60 49 186.8
132
295.8 43.6
33
60 49 186.8
295.8 43.6
40
14
14
152.5
152.5
109 152.5 186.8
186.8
40
40
14
14
152.5
186.8
186.8
20
20
109
MS
20
20
109
109
11
2-Ø
11
50
25
2-Ø15
446
330
50
25
15
446
330
RELAY
33
60 49 186.8
38
295.8 15
252.4
33
60 49 186.8
38
295.8 15
252.4
※ The drawing dimension of this page may be subject to change without prior notice.
102 Air Circuit Breakers
Dimensions
HGS/HGN Draw-Out Type 630 ~ 2,000 A (HGS06 ~ 16/HGN06 ~ 20 A Frame) Unit:mm
Front
440 525
416 501
440 525
416 501
Ø1
Ø1
2.1
2.1
438(Manual Control Plug Type)
Plug Type)
Connection
Ø1
ControlControl
2.1
2.1
Connection
438(Manual
460(Auto
278.3
438(Manual
460(Auto
278.3
270 270
164 164 164 249
270 270
328 413
164 164 164 249
3P
328 413 4P
3P 4P
Vertical Type
85 85 85 85 85
15 15 85
85 85 85 85
15 15
28.828.8
28.8
28.8
250250
250
368.4
368.4
250
368.4
368.4
Ø1 Ø1
Ø1 4 Ø1 4
4 4
210 59 210 85
210 59 210 85
[[ HGS/HGN 630~~1,600
HGS/HGN 630 1,600AA] ] [ HGN 2,000 A ]
[ HGN 2,000 A ]
(Test) 26.5 60 (Test) 26.5 60
(Test) 26.5 60 Arc Shield Surface (Test) 26.5 60 Arc Shield Surface
Arc Shield Surface
(Option) Arc Shield Surface
(Isol)
(Isol)11.5
11.5 20.4
20.4 (Option) (Isol)
(Isol) 11.5
11.5 20.420.4 (Option)
(Option)
13Ø1
3 3
3535 35 -Ø13 -Ø1
2-Ø2-
35 3
119.3
119.3 66 119.3 6
119.3 6 3
50
25 50
144 50
50
50
465.875
75
50
75
75
465.8
465.8
465.8
FixingBlock
Fixing Block 1515 Fixing
Fixing BlockBlock 15 15
25
(Option)
(Option) (Option)
(Option)
144
330
330
144
144
330
330
50
132 50
75
75
ØØ13 15
15 Ø13 Ø15 15
132
13
132
13
132
50 250 50 250
50 250 50 250
33.1
33.1
15
15
328.8
33.1
328.8
33.1
15
15
328.8 328.8
352.8 352.8
352.8 352.8
39.6 381.6 39.6 381.6
39.6 381.6 39.6 381.6
421.2 421.2
421.2 421.2
※ The drawing dimension of this page may be subject to change without prior notice.
As for the HGN draw-out type A type 2,000 A, only the vertical terminal can be applicable.
Air Circuit Breakers 103
VCB
Unit:mm
28.8
28.828.8
28.8
250
250 250
368.4
368.4
250
368.4
368.4
Ø1 Ø1
4 4
Ø1 Ø1
4 4
210 59 210 85
ACB
(Test) 26.5 60 210 59 210 85
Arc Shield Surface
(Isol) 11.5 20.4 (Option)
(Test) 26.5 60 Arc Shield Surface
(Isol) 11.5 20.4 (Option)
119.3 6 35 13
2-Ø
15
119.3 6 35 13
2-Ø
50
465.8
Fixing Block
15
15
25
(Option)
129
144
50
330
465.8
Fixing Block
15
(Option) 25
129
144
330
15
Ø13 15
132
15
50 250 15
Ø13
132
33.1
15
328.8
MCCB
352.8
50 250
39.6 381.6
33.1
15
328.8
421.2
352.8
39.6 381.6
421.2
28.8
85 85 85 85 85
50 50
28.8
28.8
250
250
368.4
368.4
Ø1 Ø1
250
250
4 4
368.4
368.4
210 59 210 85
Ø1 Ø1
(Test) 26.5 60
4
20.4 Arc Shield Surface
4
MS
(Isol) 11.5 (Option)
210 59 210 85
(Test) 26.5 60
20.4 Arc Shield Surface 1
(Isol) 11.5 1
119.3 6 (Option) 2-Ø
50
25
Fixing Block
465.8
15 1
446
(Option) 1
2-Ø
330
119.3 6
50
25
328.8
Fixing Block
465.8
15
446
(Option) Ø13 15
330
39.6 50 250
38
33.1
15
328.8
329.6 15
RELAY
15
352.8 Ø13
39.6 50 250
38
33.1
15
329.6 15
352.8
※ The drawing dimension of this page may be subject to change without prior notice.
104 Air Circuit Breakers
Dimensions
HGS/HGN Fixed Type 2,000 (630) ~ 3,200 A (HGS/HGN20 (06) ~ 32 B Frame) Unit:mm
Front
367 482
404.4
404.4
270
270 212.2 327.2
424.4 539.4
3P 4P
Vertical Type
8 384.4 8 499.4
115 115 115 115 115
20 20
40
40
14
14
186.8
152.5
186.8
152.5
20
20
109
109
35 13 35 13
3-Ø 3-Ø
75
50
90
50
75
90
15 15
144
144
330
330
75
90
132
132
33
33
60 49 186.8 60 49 186.8
295.8 43. 6 295.8 43.6
※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 105
VCB
Unit:mm
Horizontal Type
Model Name Detail“A”
8 384.4 8 499.4 HGN20 (06) ~ 25 75
115 115 115 115 115
90 90 HGN32 90
8 384.4 8 499.4
115 115 115 115 115
90 90
40
40
14
14
186.8
152.5
186.8
152.5
40
40
14
14
186.8
152.5
109186.8
152.5
20
20
109
ACB
20
20
109
109
35 13 35 13
[ 2,000 ~ 2,500 A ] 3-Ø [ 3,200 A ] 3-Ø
90
50
75
50
35 13 35 13
-Ø 3-Ø
153 15
330
144
330
144
90
50
75
50
15 15
330
144
330
144
20
20
132
132
33
33
60 49 60 49
MCCB
186.8 186.8
20
20
132
132
33
60 49 186.8 60 49 186.8
295.8 43.6 295.8 43.6
8 384.4 8 499.4
Front Type 115 115 115 115 115
75 75
8 384.4 8 499.4
115 115 115 115 115
40
40
75 75
14
14
152.5
152.5
186.8
186.8
40
40
14
14
152.5
152.5
109186.8
109186.8
20
20
MS
20
20
109
109
11
3-Ø
75
50
11
3-Ø
15
484
330
75
50
15
484
330
33
60 49 186.8
38
20
RELAY
295.8
33
257.4
60 49 186.8
38
295.8 20
257.4
※ The drawing dimension of this page may be subject to change without prior notice.
106 Air Circuit Breakers
Dimensions
HGS/HGN Draw-Out Type 2,000 (630) ~ 3,200 A (HGS/HGN20 (06) ~ 32 B Frame) Unit:mm
Front
511 626
487 602
511 626
487 602
438(Manual Control Plug Type)
Ø1
Ø1
2.1
2.1
438(Manual Control Plug Type)
Ø1
Ø1
2.1
2.1
278.3
278.3
278.3
278.3
270 270
199.5 199.5 199.5 314.5
270 270
199.5 399 199.5 199.5 514
314.5
399 514
3P 4P
3P 4P
28.8
28.8
250
250
250
250
368.4
368.4
368.4
368.4
ØØ114 Ø1 Ø
4 14
4
13
35 13
35
3-Ø 119.3 6 3-Ø
119.3 6 3 35 13
119.3 6
35
3-Ø
1
119.3 6 3-Ø
90
90
50
75 75
50 75
50
465.8
Fixing Block
465.8
Fixing Block
90
90
50
(Option) 15
75
(Option) 15
143
465.8
330
330
Fixing Block
143
465.8
Fixing Block
(Option) 15 (Option) 15
143
330
330
143
90
75 75
132.5
Ø13 15
90
Ø13 15
132.5
132.5
Ø13 15 Ø13 15
132.5
50 250 50 250
15
33.1
328.8
15
33.1
328.8
50 352.8
250 50 352.8 250
39.6 383.6328.8
15
39.6 383.6
33.1
15
33.1
328.8
423.2 423.2
352.8 352.8
39.6 383.6 39.6 383.6
423.2 423.2
※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 107
VCB
Unit:mm
Horizontal Type
115 115 115 115 115
Model Name Detail“A”
A A
HGN20 (06) ~ 25 75
28.8
28.8
28.8
28.8
250
250
368. 4
368. 4
Ø1 Ø1
4 4
250
250
368. 4
368. 4
210 94.5 210 115
Ø1 Ø1
4 4
ACB
[ 2,000 ~ 2,500 A ] [ 3,200 A ]
(Test) 26.5 60 (Test) 26.5 60
210 Arc Shield Surface 94.5 210 Arc Shield Surface
115
(Isol) 11.5 20.4 (Option) (Isol) 11.5 20.4 (Option)
20
20
50
75
50
90
465.8
465.8
Fixing Block Fixing Block
3515 13 35 13
119.3(Option)
6 3-Ø 119.3(Option) 15 3-Ø
143
6
124
330
330
143
124
20
20
50
75
50
90
465.8
465.8
Fixing Block Fixing Block
15
20
20
132.5
Ø13 15
(Option) Ø13 15 15
132.5
(Option)
143
124
330
330
143
124
50 250 50 250
33.1
33.1
15
15
MCCB
328.8 328.8
20
20
132.5
15 15
132.5
15
328.8 328.8 15
352.8 352.8
39.6 383.6 39.6 383.6
Front Type
423.2 423.2
115 115 115 115 115
75 75
28.8
28.8
28.8
250
250
368.4
368.4
Ø1 Ø1
4 4
250
250
368.4
368.4
MS
Ø1 Ø1
4 4
(Test) 26.5 60 Arc Shield Surface
20.4 (Option)
(Isol) 11.5
210 94.5 210 115
Fixing Block
50
75
445.5
(Option) 15 11
330
119.3 6 3-Ø
328.8
465.8
Fixing Block
50
75
445.5
Ø13
(Option) 15
15
330
39.6 50 250
15
33.1
328.8 20
329.6
15
37.5
352.8 Ø13
RELAY
39.6 50 250
15
33.1
329.6 20
37.5
352.8
※ The drawing dimension of this page may be subject to change without prior notice.
108 Air Circuit Breakers
Dimensions
HGN Fixed Type 4,000 A (HGN40 B Frame) Unit:mm
Front
367 482
367 482
404.4 404.4
404.4 404.4
270
270
212.2 327.2
424.4 270 539.4
270
212.2 327.2
3P
424.4 4P
539.4
3P 4P
40
14
14
109 186.8 186.8
20152.5 152.5
109 109 186.8 186.8
20152.5 152.5
40
40
14
14
20
20
109
[ 4,000 A ]
35 13
[ 4,000 A ] 5-Ø
35 13
5-Ø
25x4=100
125
125
25x4=100
125
15
125
330
169
44
15
330
60 49 186.8
295.8 87
57
33
60 49 186.8
295.8 87
※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 109
VCB
Unit:mm
Horizontal Type
405 520
152.5 152.5 140 140 140
100 100
40
40
14
14
186.8
152.5
186.8
152.5
20
20
ACB
109
109
384.4 8 499.4 8
[ 4,000 A ]
3
Ø1
35 3-
25x3=75
100
40
15
330
144
15
10
MCCB
15
132
33
60 49 186.8
295.8 58.6
MS
RELAY
※ The drawing dimension of this page may be subject to change without prior notice.
110 Air Circuit Breakers
Dimensions
HGN Draw-Out Type 4,000 A (HGN40 B Frame) Unit:mm
Front
511 626
487 602
511 626
487 602
Type) Plug Type)
Ø1
2.1
2.1
438(Manual Control Plug Type)
ConnectionControl
Ø1
Ø1
2.1
2.1
460(Auto438(Manual
460(Auto438(Manual
278.3
278.3
278.3
278.3
270 270
199.5 199.5 199.5 314.5
399 514
270 270
3P
199.5 199.5 199.5
4P 314.5
399 514
3P 4P
15 10 15 15 10 15
28.8
28.8
250
250
368.4
368.4
Ø1 Ø1
250
250
368.4
368.4
4 4
Ø1
210 94.5 Ø1210 115
4 4
119.3 6 13
35 5-Ø
25x4=100
25x4=100 125
125
119.3 6
Fixing Block 15
465.8
125
(Option)
125
330
193
68
Fixing Block 15
465.8
(Option)
330
193
68
125
Ø13 15
107.5
125
50 250 Ø13 15
107.5
33.1
15
328.8
50 352.8 250
39.6 425.6
33.1
15
328.8
465.2352.8
39.6 425.6
465.2
※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 111
VCB
Unit:mm
Horizontal Type
405 520
152. 5 152. 5 140 140 140
100 100
28.8
28.8
250
250
368.4
368.4
Ø1 Ø1
4 4
ACB
210 94.5 210 115
[ 4,000 A ]
(Test) 26.5 60
Arc Shield Surface
(Isol) 11.5 20.4 (Option)
3
Ø1
35 3-
119.3 6
15
25x3=75
10
100
15
Fixing Block 15
465.8
168
(Option)
330
MCCB
40
Ø13 15
132.5
50 250
33.1
15
328.8
352.8
39.6 399.6
439.2
MS
RELAY
※ The drawing dimension of this page may be subject to change without prior notice.
112 Air Circuit Breakers
Dimensions
HGN Fixed Type 4,000 (3,200) ~ 5,000 A (HGN40 (30) ~ 50 C Frame) Unit:mm
Front
592 762
592 762
404.4
404.4
404.4
404.4
270 270
472.7 176.7 557.7 261.7
649.4 819.4
270 270
472.7 176.7 557.7 261.7
3P 4P
649.4 819.4
3P 4P
Vertical Type
8 609.4 8 779.4
190.5 190.5 190.5 190.5 190.5
20 70 20 148 20 70 20 148
8 609.4 8 779.4
190.5 190.5 190.5 190.5 190.5
20 70 20 148 20 70 20 148
40
40
14
14
186.8
152.5
152.5
186.8
40
40
14
14
186.8
152.5
152.5
186.8
20
20
109
109
20
20
109
109
13
35 5-Ø
13
25x4=100 25x4=100
35 5-Ø
125
125
15
194
69
330
125
125
15
125
107194
69
330
33
125
60 49 186.8
44.5
107
295.8 63.6
33
60 49 186.8
44.5
295.8 63.6
※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 113
VCB
Unit:mm
Horizontal Type
8 609.4 8 779.4
190.5 190.5 190.5 190.5 190.5
40
14
14
186.8
152.5
152.5
186.8
ACB
20
20
109
109
13
35 5-Ø
20
25x4=100
110
125
70
15
20
330
196
86
110
MCCB
106
51
33
60 49 186.8
295.8 63.6
MS
RELAY
※ The drawing dimension of this page may be subject to change without prior notice.
114 Air Circuit Breakers
Dimensions
HGN Draw-Out Type 4,000 (3,200) ~ 5,000 A (HGN40 (30) ~ 50 C Frame) Unit:mm
Front
736 906
712 882
736 906
712 882
Type)
Type)
Type) Plug Type)
Ø1
2.1
460(Auto Connection
2.1
460(Auto Connection
Plug Control
Plug Control
Type)
Type)
Ø1
Ø1
438(Manual
2.1
438(Manual
460(Auto Connection
278.3
2.1
278.3
460(Auto Connection
438(Manual Control
438(Manual Control
278.3
278.3
270 270
460 164 545 249
624 794
270 270
460 164 545 249
624 794
Vertical Type
24
24
368.4
368.4
175
4
175
4
Ø1 Ø1
175 50 103.8
175 50 103.8
368.4
368.4
4 4
460 Ø1 164 545 Ø1 249
260 260 345 345
50
50
13
(Test) 26.5 60 Arc Shield Surface 35 5-Ø
20.4 (Option)
(Isol) 11.5
119.3 6
25x4=100
13
125
125
35 5-Ø
Fixing Block
465.8
119.3 6(Option) 15
194
330
12569
25x4=100
125
Fixing Block
465.8
69125
(Option) 15
194
330
107
Ø13 15
12544.5
50 175
33.1
328.8
15
107
Ø13 15
352.8
44.5
39.6 401.6
50 175
441.2
33.1
328.8
15
352.8
39.6 401.6
441.2
※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 115
VCB
Unit:mm
Horizontal Type
103.8
103.8
368.4
368.4
175
175
4
Ø1
14
Ø
ACB
50
50
13
35 5-Ø
20
119.3 6
25x4=100
110
125
70
Fixing Block
465.8
(Option) 15
20
196
330
86
MCCB
110
Ø13 15
106
51
50 175
33.1
328.8
15
352.8
39.6 401.6
441.2
MS
RELAY
※ The drawing dimension of this page may be subject to change without prior notice.
116 Air Circuit Breakers
Dimensions
HGN Fixed Type 4,000 ~ 6,300 A (HGN40 ~ 63 D Frame) Unit:mm
Front
734 964
734 964
404.4
404.4
404.4
404.4
270 12 270 12
559.2 192.2 8 674.2 307.2 8
791.4 1,021.4
270 12 270 12
559.2 3P 192.2 8 674.2 4P 307.2 8
791.4 1,021.4
3P 4P
40
14
152.5
152.5
186.8
186.8
40
40
14
20
20
152.5
152.5
186.8
109
186.8
109
20
20
109
109
13
35 5-Ø
150
25x5=125
150
13
35 5-Ø
194
69 150 150 69
330
25x5=12515
15
150
107
194
330
15
33
15
60 49 186.8
19.5
295.8 68.6
150
107
33
60 49 186.8
19.5
295.8 68.6
※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 117
VCB
Unit:mm
Horizontal Type
40
14
14
152.5
152.5
186.8
186.8
ACB
20
109
109
13
35 5-Ø
20
25x5=125
110
70
150
20
194
84
15
330
110
107
52
33
60 49 186.8
MCCB
295.8 68.6
MS
RELAY
※ The drawing dimension of this page may be subject to change without prior notice.
118 Air Circuit Breakers
Dimensions
HGN Draw-Out Type 4,000 A (HGN40 D Frame) Unit:mm
Front
878.2 1,108.2
854.2 1,084.2
878.2 1,108.2
Type)
Control Plug Type)
Type)
Control Plug Type)
854.2 1,084.2
Ø1
Ø1
460(Auto Connection
460(Auto Connection
2.1
2.1
Type)
Plug Type)
Type)
Plug Type)
Ø1
Ø1
278.3
278.3
438(Manual
438(Manual
460(Auto Connection
460(Auto Connection
2.1
2.1
438(Manual Control
438(Manual Control
270 270
278.3
278.3
566.6 199.6 681.6 314.6
766.2 996.2
270 270
566.6 199.6 681.6 314.6
766.2 996.2
Vertical Type
241 241 241 241 241
103.8
103.8
175 50103.8175
4 4
Ø1 Ø1
175 50
368.4
368.4
50
13
(Test) 26.5 60 Arc Shield Surface 35 5-Ø
20.4 (Option)
(Isol) 11.5
119.3 6
25x4=100
125
13
125
35 5-Ø
465.8
Fixing Block 15
193.1
119.3 6
125 45 68.1125 12568.1
330
(Option)
25x4=100
125
465.8
Fixing Block 15
193.1
330
(Option)
107
50 175
Ø1
33.1
328.8 3
15
352.8
107
39.6 406.6
45
50 175 446.2
Ø1
33.1
328.8 3
15
352.8
39.6 406.6
446.2
※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 119
VCB
Unit:mm
Horizontal Type
103.8
103.8
368.4
368.4
175
175
4 4
Ø1 Ø1
50
50
566.6 199.6
ACB
681.6 314.6
330 330 445 445
13
35 5-Ø
119.3 6
25x4=100
110
125
70
465.8
Fixing Block 15
20
193.1
83.1
330
(Option)
110
MCCB
106
52.5
50 175
Ø1
33.1
328.8 3
15
352.8
39.6 406.6
446.2
MS
RELAY
※ The drawing dimension of this page may be subject to change without prior notice.
120 Air Circuit Breakers
Dimensions
HGN Draw-Out Type 5,000 ~ 6,300 A (HGN50 ~ 63 D Frame) Unit:mm
Front
878.2 1,108.2
854.2 1,084.2
Control Plug Type)
Connection Type)
878.2 1,108.2
Ø1
2.1
2.1
Plug Type)
460(AutoType)
Plug Type)
460(AutoType)
278.3
278.3
Ø1
438(Manual
Ø1
438(Manual
460(Auto Connection
460(Auto Connection
2.1
2.1
438(Manual Control
438(Manual Control
270 270
278.3
278.3
566.6 199.6 681.6 314.6
766.2 996.2
270 270
566.6 199.6 681.6 314.6
766.2 996.2
Vertical Type
241 241 241 241 241
103.8
103.8
103.8 175
4 4
Ø1 Ø1
103.8
50
50
175
4 4
330 Ø1 330 445 Ø1 445
50
50
13
35 5-Ø
(Test) 26.5 60 Arc Shield Surface
20.4 (Option)
(Isol) 11.5 119.3 6
25x5=125
150
150
13
35 5-Ø
465.8
Fixing Block
193.1
15068.1
119.3 6 15
330
(Option)
25x5=125
150
465.8
68.1150
Fixing Block
193.1
15
330
107
(Option)
50 175
Ø1
33.1
328.8 3
150
15
20
352.8
107
39.6 406.6
50 175 446.2
Ø1
33.1
328.8 3
15
20
352.8
39.6 406.6
446.2
※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 121
VCB
Unit:mm
Horizontal Type
103.8
103.8
368.4
368.4
175
175
4 4
Ø1 Ø1
50
50
ACB
566.6 199.6 681.6 314.6
330 330 445 445
13
35 5-Ø
119.3 6
25x5=125
110
70
150
465.8
Fixing Block
20
193.1
83.1
15
330
(Option)
110
MCCB
106
52.5
50 175
Ø1
33.1
328.8 3
15
352.8
39.6 406.6
446.2
MS
RELAY
※ The drawing dimension of this page may be subject to change without prior notice.
122 Air Circuit Breakers
Dimensions
Panel Cutting Dimension of HGS/HGN Fixed Type Unit:mm
Panel Door Cut-Out (For Dust Cover) Panel Door Cut-Out (For Door Flange)
Operating
Operating Panel Center Operating
Panel Center Operating Panel Center
Panel Center
196 196 - R5 292
196 4 196 R5 5
292 4- 103.5 100 103.5 -R
4292
4- 5.
2 R5
Ø5 42.5 103.5 4 100 292
103.5 42.5 Ø .2
103.5 100 103.5 4-
.2 -Ø 4-103.5 42.5 Ø5
5.2 42.5 103.5 100
4-
122.5
20
122.5
122.5
20
15
122.5
15
144
330
115
345
290
229
115
345
330
115
345
290
229
115
345
75
4
-Ø
122.5
4
4
12
-Ø
-Ø
122.5
132
122.5
4
12
12
7.5
-Ø
122.5
68.6 15
12
7.5
7.5
68.6 15
Bottom
20
7.5
33
Bottom Bottom
20
33
Bottom 7.5 95 188
25.6
33.1
25.6
Panel Door Rear Panel (IP
33.1
7.5
25.6
Panel Door
Operating Operating
Panel Center Panel Center
ACB Center ACB Center
2 5 292
0 103.5 4-
R R5 A A
103.5 100 103.5 4-
122.5
122.5
144
330
115
345
144
330
115
345
B
75
75
4
4
-Ø
-Ø
122.5
12
33 122.5
12
132
7.5
132
7.5
7.5
25.6
Model Name A B C
HGN 06A3 ~ 20A3, HGS 06A3 ~ 16A3 283 355 25
HGN 06A4 ~ 20A4, HGS 06A4 ~ 16A4 368 355 25
HGN 06B3 ~ 40B3, HGS 20B3 ~ 32B3 354 355 25
HGN 06B4 ~ 40B4, HGS 20B4 ~ 32B4 469 355 25
HGN 32C3 ~ 50C3 579 355 25
HGN 32C4 ~ 50C4 749 355 25
※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 123
VCB
Panel Cutting Dimension of HGS/HGN Draw-Out Type Unit:mm
Panel Door Cut-Out (For Dust Cover) Panel Door Cut-Out (For Door Flange)
20
122.5
122.5
122.5
122.5
15
15
ACB
290
229
115
345
115
345
330
290
229
115
345
115
345
330
4
4
4
4
-Ø
-Ø
-Ø
-Ø
122.5
122.5
122.5
122.5
12
12
12
12
Rear panel R
68.6 15
68.6 15
7.5
7.5
7.5
7.5
(IP30) (
20
20
33.1
7.5 7.5
33.1
7.5 7.5
25.6
25.6
33.1
25.6
25.6
Panel Door Panel Door
25 25 323 323
MCCB
Operating (Test) 26.5 60
Operating Panel Center
(Test) 26.5 60 (Isol) 11.5 20.4
Panel Center
(Isol) 11.5 20.4
292
R5 ACB Center
292 103.5 100 103.5 4-
R5 ACB Center
100 103.5 4- A
A
122.5
122.5
115
330345
330
B
115
345
B
4
-Ø
122.5
4
12
-Ø
MS
Rear panel
122.5
7.5
12
Bottom Bottom
31
32
4
7.5
33.1
25.6
Panel Door 4
7.5
33.1
25.6
Panel Door
25 323
25 323
Model Name A B C
HGN 06A3 ~ 20A3, HGS 06A3 ~ 16A3 329 268 70
RELAY
※ The drawing dimension of this page may be subject to change without prior notice.
124 Air Circuit Breakers
Circuit Diagrams
PB(Open)
PB(Open)
PB(Open)
PB(Open)
K L K L (Close)
Supervision
R S T N 21 23 27 28 29 30 VR VS VT VN 19 37 39 37 39 1 15 3 7 7 59 7 9
Spring
Charge
Off SW.
Over-Current
Protective Device
M CC TC TC TC2
Rn Sn Tn Nn Ac S/I G/E ZI
1
ZI
2
ZO ZO
1 2 COM COM RR+ RR- MCR MCR
+ - TN TP S0 TC
CT4
CT3 TP
CT2 MHT
CT1
TN
1a for MCR
Rn Sn Tn Nn 22 24 26 31 32 33 34 35 36 5 6 20 38 40 38 40 2 16 4 8 8 8 10
+ - + - + - + -
IN OUT Communi- Remote
ZSI cation Reset
※ This circuit diagram is equipped with the 'GPR-LA' type of OCR and please refer to page 35 to 38 for other types of OCR.
Air Circuit Breakers 125
VCB
UVT Coil + Auxiliary Position External Auxiliary
UVT Time Delay Device Contact Switch Contact (MOC)
U1
COM
a
Power
U2
Power b
Time Delay
C1
T2
UVT
PB(Open)
PB(Open)
C2
T1
9 9 41 43 45 47 49 51 53 55 57 59 61 64 67 101 71 74 77 81 84 91 94 121 123 125 127 129 131 133 135 137 139 141 143 145 147 149 151 153 155 157 159
Used for Short "b" contact (Option)
Used for SHT Supervision (Option)
ACB
Used for MCR (Option)
UVT UVT
10 10 42 44 46 48 50 52 54 56 58 60 62 63 65 66 68 69 102 103 72 73 75 76 78 79 82 83 85 86 92 93 95 96 122 124 126 128 130 132 134 136 138 140 142 144 146 148 150 152 154 156 158 160
MOC1 MOC2
MCCB
101-103 OFF
20 22 24 26 28 30 32 34 36 38 40 VS VN 2 4 8 10 16 42 44 46 48 50 52 54 56 58 60
MS
OCR
OCR Contact
POW ELT N-CT ZSI COM Temp V Input
COM L S/I P/T G/E
19 21 23 27 29 31 33 35 37 39 VR VT
20 22 24 26 28 30 32 34 36 38 40 VS VN
1 3 7 9 15 41 43 45 47 49 51 53 55 57 59
RELAY
2 4 8 10 16 42 44 46 48 50 52 54 56 58 60
Order Code
HGN Type
HGN 12 A 3 J M2
Manual Connection +
K
Horizontal Type
Manual Connection +
M
Vertical Type
Manual Connection +
N Upper:Horizontal/
Lower:Vertical
Manual Connection +
Q Upper Side:Vertical/
Lower Side:Horizontal
Manual Connection +
R 2) Front Type/Mounting Type
Selected by Customer
※ 1) A frame, 2,000 A is only available for vertical terminal bus bar arrangement.
2) P, G, R type of fixed terminal bus bar arrangement should be ordered per terminal and mounted personally.
(Refer to the additional components). Applicable frames are A06 ~ 16, B06 ~ 32.
3) Charging motor AC 380 V, AC 440 V are currently under development.
4) CT for Over-Current
- A/W Frame:200 ~ 2,000 A
- B/X Frame:400 ~ 4,000 A
- C/Y Frame:3,200 ~ 5,000 A
- D/Z Frame:4,000 ~ 6,300 A
5) When applying OCR high-end type P, H type, place an order for voltage module (HGNS VM) additionally for mounting.
Air Circuit Breakers 127
VCB
C2 S2 61 K AB
ACB
C7 DC 24 V S7 DC 24 V 52 GPR-LAG H 800 A U4 AC 440 V V4 AC 440 V
C8 DC 48 V S8 DC 48 V 53 GPR-LAZ J 1,000 A U7 DC 24 V V9 DC 125 V
C9 DC 125 V S9 DC 125 V 54 GPR-LP 5)
K 1,250 A U8 DC 48 V
55 GPR-LH 5) L 1,600 A U9 DC 125 V Position S/W
Trip Supervision Coil 60 Hz M 2,000 A AQ Test 1C, Connected 1C
T1 AC/DC 110 V 60 GPR-LN N 2,500 A Secondary Trip Coil AR Connected 2C
T2 AC/DC 220 V 61 GPR-LA P 3,200 A S1 AC/DC 110 V AS Test 2C
T3 AC 380 V 62 GPR-LAG Q 4,000 A S2 AC/DC 220 V AT Isolated 1C, Inserted 1C
T4 AC 440 V 63 GPR-LAZ S 5,000 A S3 AC 380 V AU Inserted 2C
T7 DC 24 V 64 GPR-LP 5) X 6,300 A S4 AC 440 V AV Isolated 2C
T8 DC 48 V 65 GPR-LH 5) S7 DC 24 V P4 Test 2C, Connected 2C
MCCB
T9 DC 125 V S8 DC 48 V PT Test 4C
Generator S9 DC 125 V Isolated 1C, Test 1C,
PS
50 Hz Connected 2C
- Mechanical interlock device (B0), external auxiliary contact (MC) and fixing block (AF) cannot be used together. ATS Production
- BC:The control terminal’s safety cover is only available for the auto connection.
Emergency Power
- AK:Short “b” is only available for auto connection and is attached to 51, 52. It can be attached as much as BAB7
Transfer
the number of “B” contact so upon additional mounting, place a separate order (HGNS ~ ).
- AG:O riginally, it is attached separately but upon release, the front cover is inserted when shipped.
- MR:AE, AG, AF, AM are attached as a standard option, so the relevant accessories are not marked separately.
MR Marine Switchgear
- AA and BA (BH) cannot be attached at the same time.
- UVT and Secondary Trip Coil cannot be attached at the same time.
128 Air Circuit Breakers
Order Code
When Placing an Order for the Cradle
DHN 12 A 3 A H AE
Control
Frame Category & Terminal Bus Bar
Model Name Rated Frame No. of Poles Terminal Accessories
Neutral Pole Arrangement
Connection
Air Circuit 16 DHN06 ~ 16A (W) 630 ~ 1,600 A 3/4P 3 3 Pole H Horizontal Type
Auto Safety
DHN Breakers A Standard RSTN A AE
20 DHN20A (W) 1)
4 4 Pole Connection V Vertical Type Shutter
Cradle Reverse Phase NRST
※ 1) A frame, 2,000 A is only available for vertical terminal bus bar arrangement.
2) P type of fixed terminal bus bar arrangement should be ordered per terminal and mounted personally. (Refer to the additional components).
Applicable frames are A06 ~ 16, B06 ~ 32.
Air Circuit Breakers 129
VCB
ACB
MCCB
MS
RELAY
130 Air Circuit Breakers
Order Code
HGS Type
HGS 12 A 3 J M2
Upper Side:Vertical/
L
Lower Side:Horizontal
Draw-Out Type
(Combined with Cradle)
Auto Connection +
B
Horizontal Type
Auto Connection +
C
Vertical Type
Auto Connection +
D Upper Side:Horizontal/
Lower Side:Vertical
Auto Connection +
E Upper Side:Vertical/
Lower Side:Horizontal
Auto Connection +
G 1) Front Type/Mounting Type
Selected by Customer
Manual Connection +
K
Horizontal Type
Manual Connection +
M
Vertical Type
Manual Connection +
N Upper Side:Horizontal/
Lower Side:Vertical
Manual Connection +
Q Upper Side:Vertical/
Lower Side:Horizontal
Manual Connection +
R 1) Front Type/Mounting Type
Selected by Customer
※ 1) P, G, R type of fixed terminal bus bar arrangement should be ordered per terminal
and mounted personally. (Refer to the additional components).
2) Charging motor AC 380 V, AC 440 V are currently under development.
3) O, V can only be applicable to frame A.
- B frame can be applied above 400 A of CT.
4) When applying LP type of OCR, place an order for the voltage module (HGNS VM)
additional for mounting.
Air Circuit Breakers 131
VCB
C2 S2 61 K AB
ACB
C7 DC 24 V S7 DC 24 V 52 GPR-LAG H 800 A U7 DC 24 V V4 AC 440 V
C8 DC 48 V S8 DC 48 V 53 GPR-LAZ J 1,000 A U8 DC 48 V V9 DC 125 V
C9 DC 125 V S9 DC 125 V 54 GPR-LP 4)
K 1,250 A U9 DC 125 V
60 Hz L 1,600 A Position S/W
60 GPR-LN M 2,000 A Secondary Trip Coil Test 1C,
AQ
61 GPR-LA N 2,500 A S1 AC/DC 110 V Connected 1C
S8 DC 48 V AU Inserted 2C
MCCB
S9 DC 125 V AV Isolated 2C
Test 2C,
P4
Connected 2C
On/Off Button Lock
AM
Device PT Test 4C
Inserted 1C,
Auxiliary Switch
A5 PQ Isolated 1C, Test 1C,
- U□ is only applicable when instantaneous type and only the UVT coil is installed. (Additional 5a 5b)
Connected 1C
When using time delay type, place a separate order for the time delay type of controller
Inserted 2C,
(HGNS ~ ) and install externally. Key Lock Device
AB P8 Isolated 2C, Test 2C,
- V□ is only applicable when time delay type is applied and the UVT coil is installed (Prevent ON)
Connected 2C
in the main unit while the time delay type of controller is installed at the side of Inserted 1C,
B8 OCR MCR
the cradle. In case of dimension issues, place an order for HGNS V□ for separate PR Isolated 1C, Test 3C,
installation. OCR Manual Reset Connected 3C
BR
- B0:The mechanical interlock device has to be ordered separately and when B0 is
marked, only the components interlocked inside the main unit are assembled for
Function
MS
Auto Connection
release. (Refer to additional components). OCR Manual Reset &
BA BC Control Terminal’s
- When S□ Secondary trip is applied, UVT coil cannot be applied at the same time. Alarm S/W 2a
Safety Cover
- When using T□ trip coil monitoring contact, it becomes 4a4b and when using MCR
CR Manual Reset + AE Safety Shutter
function of B8 OCR, it can be used as 4a5b. When both functions are applied, 3a4b can BH High Capacity Alarm
be possible. S/W 1a AX Arc Shield
- In the order code for the main unit only (A/J/Fixed type), combination with cradle Closing Preparation AF Fixing Block
accessories is not possible and the cradle accessory arrangement is only possible Contact (B6 and BT
when purchased with cradle arrangement. For the independent release of the main cannot be Applied
BT
unit, place a separate order (HGNS ~ ) (refer to additional components). Simultaneously
- Position switch cannot be overlapped for use and can only be attached only at the (Overlapping
right side of cradle. In case a combination other than the combination indicate is Mounting)
required, make an inquiry separately. B6 Spring Charge Switch
- Mechanical interlock device (B0), external auxiliary contact (MC) and fixing block (AF)
AG Door Flange
cannot be used together.
RELAY
- BC:The control terminal’s safety cover is only available for the auto connection. Auxiliary Switch
A5
- AK:Short “b” is only available for auto connection and is attached to 51, 52. It can be (5 ~ 5b)
attached as much as the number of “B” contact so upon additional mounting,
place a separate order (HGNS ~ ).
- AG:O riginally, it is attached separately but upon release, the front cover is inserted
when shipped.
- AA and BA (BH) cannot be attached at the same time.
- UVT and Secondary Trip Coil cannot be attached at the same time.
132 Air Circuit Breakers
Order Code
When Placing an Order for the Cradle
DHS 12 A 3 A H AE
Control
Frame Category & Terminal Bus Bar
Model Name Rated Frame No. of Poles Terminal Accessories
Neutral Pole Arrangement
Connection
Air Circuit 10 DHS06 ~ 10A (W) 630 ~ 1,600 A 3/4P 3 3 Pole H Horizontal Type
Auto Safety
DHS Breakers A Standard RSTN A AE
16 DHS12 ~ 16A (W) 4 4 Pole Connection V Vertical Type Shutter
Cradle Reverse Phase NRST
※ 1) P type of fixed terminal bus bar arrangement should be ordered per terminal and mounted personally. (Refer to the additional components).
Applicable frames are A06 ~ 16, B06 ~ 32.
Air Circuit Breakers 133
VCB
Internal Resistance and Power Consumption
ACB
A Frame 1,000 15 45 30 90 C Frame 4,000 8 384 11 528
HGN 20 1,250 15 70 30 141 HGN 40 ~ 50 5,000 8 600 11 825
1,600 15 115 30 230 4,000 6 288 9 432
D Frame
2,000 13 156 27 324 HGN 5,000 6 450 9 675
40 ~ 63
6,300 5 595 7 833
※T
he abovementioned power consumption is the total power consumption of the
circuit breaker based on 50/60 Hz, 3/4 pole.
The inner resistance value is the resistance value per pole.
Power Factor = 1.0
Tightening Torque
MCCB
Main Circuit
Tightening Torque Control Circuit
M10 : 270 ± 32 kgf-cm Tightening Torque
M12 : 480 ± 57 kgf-cm M3.5 : 8.8 ± 1.1 kgf-cm
Detail
Detail
Insulation Voltage MS
When designing the switchboard, maintain the insulation
distance in accordance with the table below.
A
Item A B
Fixed Type 150 50
Draw-Out Type without Arc Shield 150 50
B B
Draw-Out Type with Arc Shield 0 50
RELAY
e)
anc
Dist
Minimum Insulation Distance at Charging Side tion
n sula
D (I
Insulating Voltage Minimum Insulation Distance(mm)
Below 600 V 8
Above 600 V, below 1,000 V 14
134 Air Circuit Breakers
Applicable
Model Rating ACB
Motion
Name Current Terminal
Standard
※ The ambient temperature is based on the external temperature of the circuit breaker and the motion that can be applicable to the circuit breaker is applied.
The motion is based on copper material with no separate painting.
The maximum allowable temperature of the motion is below 100 ℃.
Calibration of Rating Current Following Altitude Item Altitude 2,000 m 3,000 m 4,000 m 5,000 m
ACB is designed to be used at altitudes below 2,000 m. Withstand Voltage (V) 3,500 3,150 2,500 2,100
Average Insulating Voltage (V) 1,000 900 700 600
When used at above 2,000 m, change the ratings depending on
Max. Operation Voltage (V) 690 590 520 460
the surrounding environment condition for use. Current Calibration Coefficient 1×In 0.99×In 0.96×In 0.94×In
Air Circuit Breakers 135
VCB
Derating Table (HGN)
4
3
2
Switchboard Composition
1
Connection Type
Rated Current 2)
~ 800 A 1,000 A
ACB
Ventilated Switchboard Board 4 800↓
(IP31) 3)
3 800↓ 800↓ 1,000
Ta 1) = 30 ~ 40 ℃
H 2 800↓ 800↓ 800↓ 1,000 1,000
4 800↓
H
3 800↓ 800↓ 1,000
Ta = 40 ~ 50 ℃
D 2 800↓ 800↓ 800↓ 1,000 1,000
W
1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000
4 800↓
MCCB
D 3 800↓ 800↓ 1,000
W
Ta = 50 ~ 60 ℃
Area of Intake Ventilator:350 cm2 2 800↓ 800↓ 800↓ 1,000 1,000
Area of Exhaust Ventilator:350 cm2
1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000
4 800↓
Panel Dimensions
D
(mm):W×H×D 800×2,300×900
W
Area of Outlet Vents (IP31) 350 cm2
※ 1) The ambient temperature, Ta refers to the external temperature of the panel (IEC 60439-1).
2) The rated current satisfies the temperature condition in accordance with the temperature test regulation of IEC 60947-1, 2. When installed within the panel, the derating of
RELAY
4
3
2
Switchboard Composition
1
Connection Type
Rated Current 2)
1,250 A 1,600 A 2,000 A
3 1,250 2,000
Ta 1) = 30 ~ 40 ℃
H 2 1,250 1,250 1,600 2,000 2,000
4
H
3 1,250 1,900
Ta = 40 ~ 50 ℃
D 2 1,250 1,250 1,600 2,000 2,000
W
1 1,250 1,250 1,250 1,250 1,600 1,600 1,600
4
D
W 3 1,250 1,800
Ta = 50 ~ 60 ℃
Area of Intake Ventilator:350 cm2 2 1,250 1,250 1,470 1,900 1,900
Area of Exhaust Ventilator:350 cm2
1 1,250 1,250 1,250 1,250 1,520 1,600 1,600
Non-Ventilated Switchboard 4
(IP41/54) 4)
3 1,250 1,750
Ta 1) = 30 ~ 40 ℃
2 1,250 1,250 1,600 1,850 1,850
3 1,250 1,650
H Ta = 40 ~ 50 ℃
2 1,250 1,250 1,500 1,750 1,750
H 4
3 1,250 1,550
D
W
Ta = 50 ~ 60 ℃
2 1,250 1,250 1,400 1,650 1,650
Panel Dimensions
D (mm):W×H×D 800×2,300×900
W
Area of Outlet Vents (IP31) 350 cm2
※ 1) The ambient temperature, Ta refers to the external temperature of the panel (IEC 60439-1).
2) The rated current satisfies the temperature condition in accordance with the temperature test regulation of IEC 60947-1, 2. When installed within the panel, the derating of
additional current and recommended motion specification must be used.
3) The ventilation structure has to been designed to reduce the temperature of the product installed in the panel.
4) Forced ventilation device must be added in order to reduce the temperature inside the panel in an enclosed structure.
The load rate under the derating table above must be used below 70 % of the rated current. In case it is smaller than the designated bus bar size, it causes an increase in
temperature due to the reduced area of the bus bar. In order to protect the load, the current load rate must be reduced to a safe range.
Air Circuit Breakers 137
VCB
4
3
2
Switchboard Composition
1
Connection Type
Model Name HGN 06 ~ 20B HGN 25B HGN 32B HGN 40B
Rated Current 2)
2,000 A 2,500 A 3,200 A 4,000 A
ACB
Ventilated Switchboard (IP31) 3) 4
3 2,000↓
Ta 1) = 30 ~ 40 ℃
H 2 2,000↓ 2,000↓ 2,000↓ 2,375 2,500 3,040 3,200 3,320 3,700
4
H
3 2,000↓
Ta = 40 ~ 50 ℃
D 2 2,000↓ 2,000↓ 2,000↓ 2,250 2,380 2,880 3,100 3,160 3,500
W
1
MCCB
D
W 3 2,000↓
Ta = 50 ~ 60 ℃
Area of Intake Ventilator:350 cm2 2 2,000↓ 2,000↓ 2,000↓ 2,100 2,250 2,690 2,900 2,960 3,280
Area of Exhaust Ventilator:350 cm2
1
Non-Ventilated Switchboard 4
(IP41/54) 4)
3 2,000↓
Ta 1) = 30 ~ 40 ℃
2 2,000↓ 2,000↓ 2,000↓ 2,125 2,275 2,650 2,850 3,040 3,320
3 1,900↓
H Ta = 40 ~ 50 ℃
2 1,900↓ 1,960↓ 1,960↓ 2,000 2,150 2,550 2,700 2,880 3,120
1
MS
H 4
3 1,780↓
D
W
Ta = 50 ~ 60 ℃
2 1,800↓ 1,920↓ 1,920↓ 1,900 2,020 2,370 2,530 2,720 2,960
Panel Dimensions
D (mm):W×H×D 800×2,300×900
W
Area of Outlet Vents (IP31) 350 cm2
4
3
2
Switchboard Composition
1
Connection Type
Model Name HGN 40C HGN 50C HGN 40D HGN 50D HGN 63D
Rated Current 2)
4,000 A 5,000 A 4,000 A 5,000 A 6,300 A
3
Ta 1) = 30 ~ 40 ℃
H 2 3,900 4,000 4,550 4,850 4,000 4,000 4,700 5,000 5,550 5,850
4
H
3
Ta = 40 ~ 50 ℃
D 2 3,850 3,900 4,350 4,650 4,000 4,000 4,450 4,850 5,380 5,670
W
1
4
D
W 3
Ta = 50 ~ 60 ℃
Area of Intake Ventilator:350 cm2 2 3,800 3,850 4,100 4,400 4,000 4,000 4,200 4,600 5,080 5,350
Area of Exhaust Ventilator:350 cm2
1
Non-Ventilated Switchboard 4
(IP41/54) 4)
3
Ta 1) = 30 ~ 40 ℃
2 3,800 3,900 4,200 4,500 4,000 4,000 4,350 4,650 5,050 5,290
3
H Ta = 40 ~ 50 ℃
2 3,650 3,800 3,950 4,250 4,000 4,000 4,100 4,400 4,780 5,040
H 4
3
D
W
Ta = 50 ~ 60 ℃
2 3,550 3,650 3,750 4,050 3,840 3,950 3,850 4,150 4,490 4,730
Panel Dimensions
D (mm):W×H×D 1,000×2,300×900 1,400×2,300×1,500
W
Area of Outlet Vents (IP31) 500 cm 2
500 cm2
※ 1) The ambient temperature, Ta refers to the external temperature of the panel (IEC 60439-1).
2) The rated current satisfies the temperature condition in accordance with the temperature test regulation of IEC 60947-1, 2. When installed within the panel, the derating of
additional current and recommended motion specification must be used.
3) The ventilation structure has to been designed to reduce the temperature of the product installed in the panel.
4) Forced ventilation device must be added in order to reduce the temperature inside the panel in an enclosed structure.
The load rate under the derating table above must be used below 70% of the rated current. In case it is smaller than the designated bus bar size, it causes an increase in
temperature due to the reduced area of the bus bar. In order to protect the load, the current load rate must be reduced to a safe range.
Air Circuit Breakers 139
VCB
Derating Table (HGS)
4
3
2
Switchboard Composition
1
Connection Type
Rated Current 2)
~ 800 A 1,000 A 1,250 A
ACB
Ventilated Switchboard (IP31) 3) 4 800↓
1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000 1,250 1,250 1,250 1,250
4 800↓
H
3 800↓ 800↓ 1,000 1,250
Ta = 40 ~ 50 ℃
D 2 800↓ 800↓ 800↓ 1,000 1,000 1,250 1,250
W
1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000 1,250 1,250 1,250 1,250
4 800↓
MCCB
D
W 3 800↓ 800↓ 1,000 1,050
Ta = 50 ~ 60 ℃
Area of Intake Ventilator:350 cm2 2 800↓ 800↓ 800↓ 1,000 1,000 1,200 1,150
Area of Exhaust Ventilator:350 cm2
1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000 1,250 1,250 1,250 1,250
1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000 1,250 1,250 1,250 1,250
4 800↓
1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000 1,250 1,250 1,150 1,150
MS
H 4 800↓
1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 975 950 1,250 1,250 1,150 1,050
Panel Dimensions
D (mm):W×H×D 800×2,300×900
W
Area of Outlet Vents (IP31) 350 cm2
4
3
2
Switchboard Composition
1
Connection Type
Model Name HGS 16A HGS 20B HGS 25B HGS 32B
Rated Current 2)
1,600 A 2,000 A 2,500 A 3,200 A
3 2,000
Ta 1) = 30 ~ 40 ℃
H 2 1,600 2,000 2,000 2,000 2,375 2,500 2,880 3,100
4
H
3 1,900
Ta = 40 ~ 50 ℃
D 2 1,520 1,900 2,000 2,000 2,250 2,380 2,690 2,900
W
1 1,600 1,600 1,600
4
D
W 3 1,800
Ta = 50 ~ 60 ℃
Area of Intake Ventilator:350 cm2 2 1,450 1,800 1,950 1,900 2,100 2,250 2,500 2,700
Area of Exhaust Ventilator:350 cm2
1 1,520 1,600 1,520
Non-Ventilated Switchboard 4
(IP41/54) 4)
3 1,750
Ta 1) = 30 ~ 40 ℃
2 1,520 1,750 1,850 1,850 2,125 2,275 2,550 2,700
3 1,650
H Ta = 40 ~ 50 ℃
2 1,450 1,650 1,750 1,750 2,000 2,150 2,370 2,530
H 4
3 1,550
D
W
Ta = 50 ~ 60 ℃
2 1,370 1,550 1,650 1,650 1,900 2,020 2,200 2,370
Panel Dimensions
D (mm):W×H×D 800×2,300×900 800×2,300×900
W
Area of Outlet Vents (IP31) 350 cm 2
350 cm2
※ 1) The ambient temperature, Ta refers to the external temperature of the panel (IEC 60439-1).
2) The rated current satisfies the temperature condition in accordance with the temperature test regulation of IEC 60947-1, 2. When installed within the panel, the derating of
additional current and recommended motion specification must be used.
3) The ventilation structure has to been designed to reduce the temperature of the product installed in the panel.
4) Forced ventilation device must be added in order to reduce the temperature inside the panel in an enclosed structure.
The load rate under the derating table above must be used below 70 % of the rated current. In case it is smaller than the designated bus bar size, it causes an increase in
temperature due to the reduced area of the bus bar. In order to protect the load, the current load rate must be reduced to a safe range.
Air Circuit Breakers 141
VCB
Standard Operation Conditions
The following regulated value has been set in accordance with IEC 62271-100 (IEC 62271-1).
| Ambient Temperature | -5 ~ +40 °C The surrounding environment may affect the insulation
(Daily average temperature of below 35 °C) performance and durability of the circuit break so the
| Altitude | Below 2,000 m above sea level operation conditions must be checked clearly before
| Relative Humidity | Below 85 % (Below daily average of 85 %) application.
ACB
In case of operating in high ambient temperature In case of operating in places with high
exceeding 40 °C, use according to the derating humidity and frequent rain, the insulation or
calibrated depending on the ambient electrical performance may drop.
temperature indicated in the catalogue.
In case of storing and using in places with a lot When storing circuit breaker without
of dust and humidity, the use of a dust cover electric circuit:-25 °C ~ 85 °C
or dehumidifier is recommended. Excessive When storing circuit breaker with
MCCB
impact and vibration may cause damage in the electric circuit:-15 °C ~ 70 °C
operation mechanism. After storing in low temperature, store for more
than 8 hours in room temperature then store in an
open location for the type with charging motor.
In case there is a lot of corrosive gas, it must be In case of highland with high altitude, the
stored in an enclosed protective structure to insulation performance drops so please apply
minimize damage. the highest rating product after checking the
insulation performance calibration coefficient.
MS
The HG-Series air circuit breaker has been designed/manufactured to operate in a standard operating environment designated by the
IEC standard and in case of operating the circuit breaker in the following special environment, contact our company.
˙In case the altitude above sea level and the ambient ˙In case the relative humidity exceeds the standard operating
temperature exceeds the standard operating environment environment
˙In case of a region with a lot of sea wind or salinity ˙In case of a region with a lot of humidity and frequent rainfall
RELAY
˙In case of a region with snow and freezing ˙In case of a region with a lot of dust, vapor, corrosive and
˙In case of a region of frequent shock and vibration combustible gas, wet steam
˙In other special environment that exceeds the standard
environment
※ Special operating environment and condition may cause damage in the product (Increase in resistance at main circuit, rust, change in coating).
142 Air Circuit Breakers
Normal Condition
I/In ≤ 80 % 24/24 Hours -
(Recommended)
Periodic
80 < I/In ≤ 90 % 24/24 Hours -
Inspection
Change in Plastic
Additional
I/In = 100 % 24/24 Hours Insulation
Exhaust
Material Color
※ In the event indicating the characteristic number is not required, mark the said area with ‘X’.
Protection Degree
Numeral
First Characteristic Numeral (Particulate) Second Characteristic Numeral (Liquid)
VCB
Product Installation Condition
˙In order to prevent burning of products caused by electrical fault and to enhance structural safety of the panel when installing the
product in areas with concerns of vibration, mount the fixing block and install the terminal supporting position like the figure.
˙In particular, when executing short-time/short-circuit panel testing, it must be installed for structural safety.
˙For the support dimension of the product, refer to the drawing.
˙In the event of switchboard (Panel) development test (Short-time, short-circuit), the bus bar inside the panel must be supported firmly
according to the following conditions.
Unit:mm
B
A
ACB
Ø12.1
150 150
119.3 6 119.3 6
278.3
Fixing Fixing
Block Block
278.3
278.3
Front
MCCB
70
250
278.3
278.3
278.3
250
MS
Model Name A B
HGS 06 ~ 16A 3P, HGN 06 ~ 20A 3P 416 440
HGS 06 ~ 16A 4P, HGN 06 ~ 20A 4P 501 525
RELAY
Inspection Item
Inspection Form Inspection Period
Main Review Item Details and Countermeasures
Visual examination must be executed and there must be no foreign substance inside.
Foreign Substance Every 6 months
Blow away the foreign substance using compressed air.
Gap Execute visual examination and there must be no cracks or gaps. Replace, repair
Circuit breaker must be closed manually to inspect the operation area during normal
Operation Once a year
status.
General Regular Apply an adequate amount of grease on each pin, axle and bearing.
Inspection Excessive greasing may cause dust and stain from building up.
Greasing Every 6 months
Electrical grease:HITALWBE 28G
Lubiricant grease:Kamro Chemical/CHEMAX HHI 5000#1.
Spring Type The status of the spring must be checked to inspect the damaged area. Replace, repair
Screw/Bolt Type Tighten loose areas using screw or bolt. Every 6 months
Stain on the There must be no dust or stain at the fastening area. Wipe the area well using clean
All the time
Fastening Bolt Area cloth dipped in alcohol.
Total operation frequency:3,000 times Non-current 2,500 time, current 500 time
Paid inspection is
required (Precision
Open/close within the range of rated inspection)
Open/closing frequency:500 times
Below 2,500 AF current
Inspection period:
Open/close in over-load (Around 6 times At least 6 months
Open/closing frequency:25 times after exceeding the
the rated current) area
Mechanical Durability opening/closing
Warranty Lifespan Immediately upon breaking Prevent short-circuit/earth fault frequency
Inspection Precision inspection
Open/close frequency: 2,000 times Non-current 1,500 time, current 500 time
once a year is
recommended
Open/close within the range of rated
Open/close cycle:500 times
current
Contact our company
Above 3,200 AF
to determine is
Open/close in over-load (Around 6 times replacement is
Open/close cycle:25 times
the rated current) area required
Immediately upon breaking Prevent short-circuit/earth fault
Contact with Foreign In case foreign substance has melted onto the grid’s side plate, replace the ionized Replace,
Arc Chamber (Grid)
Substance pieces inside the arc chamber and others. contact our company
In case the main contact has been worn off and is rough, the surface must be
managed neatly.
Damage of
Main Contact At all times
Main Contact
However, in case there is foreign substance on the contact, precision diagnosis is
required to determine if replacement is necessary through our company’s paid service.
Caution
1. In the event the contact or part is replaced, turn the circuit breaker off and replace after drawing out the disconnected position to isolated.
2. Execute the inspection work after checking whether the remaining heat in the conduction part has been dissipated. It may cause burns.
3. When rubbing the contact tip, ensure that the sludge does not enter the circuit breaker’s mechanical device. After rubbing, wipe the contact tip neatly.
Air Circuit Breakers 145
VCB
Assembly & Disassembly
Loosen the screw for arc chamber assembly. Then, remove the arc chamber. (Level the circuit breaker).
In order to assemble the arc chamber, check the square nut, place the arc chamber in the original position and tighten the fixing screw
(M6).
ACB
Square Nut
(M6)
MCCB
Caution
When replacing the contact or part, turn the circuit breaker off and exchange after drawing out from isolated position.
In addition, execute the inspection work after checking whether the remaining heat in the conduction part has been dissipated.
It may cause burns.
When removing the arc chamber, the square nut for bolt fastening must be removed together.
In the event of on-off operation without removing the square nut, the nut may flow into the pole due to impact.
It may cause malfunction.
When rubbing the contact tip, ensure that the sludge does not enter the circuit breaker’s mechanical device.
After rubbing, wipe the contact tip neatly.
MS
RELAY
146 Air Circuit Breakers
⓳ ⓲
❺ ❹ ❸ ❷ ❶
⓮
⓯
⓱
❻ ⓴
❼
❽ ⓰
❾
❿ ⓯
VCB
Approvals & Certificates
●:Acquired
ACB ◎:In Progress (Expected)
Mark
ACB
HGS08 A Frame ● ● ●
HGS10 A Frame ● ● ●
HGS12 A Frame ● ● ●
HGS16 A Frame ● ● ●
HGS20 B Frame ● ● ●
HGS25 B Frame ● ● ●
HGS32 B Frame ● ● ●
HGN06 A Frame ● ● ● ●
HGN08 A Frame ● ● ● ●
HGN10 A Frame ● ● ● ●
HGN12 A Frame ● ● ● ●
MCCB
HGN16 A Frame ● ● ● ◎ ●
HGN20 A Frame ● ● ● ●
HGN06 B Frame ● ● ● ●
HGN08 B Frame ● ● ● ●
HGN10 B Frame ● ● ● ●
HGN12 B Frame ● ● ● ●
HGN16 B Frame ● ● ● ●
HGN20 B Frame ● ● ● ◎ ●
HGN25 B Frame ● ● ● ●
HGN32 B Frame ● ● ● ◎ ●
HGN40 B Frame ● ● ● ●
HGN32 C Frame ● ● ● ●
HGN40 C Frame ● ● ● ●
HGN50 C Frame ● ● ● ● MS
HGN40 D Frame ● ●
HGN50 D Frame ● ●
HGN63 D Frame ● ●
RELAY
148 Air Circuit Breakers
Mark