现代开关HGN样本书

The document provides an overview of the HG Series Air Circuit Breakers (ACB), detailing their characteristics, technical data, model selection, and various accessories. It highlights the ACB's high breaking capacity, customizable features, and advanced protection functionalities, including temperature monitoring and fault recording. Additionally, it outlines installation methods, maintenance procedures, and acquired standards and certifications for the product.

Uploaded by

rico8370
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views148 pages

现代开关HGN样本书

The document provides an overview of the HG Series Air Circuit Breakers (ACB), detailing their characteristics, technical data, model selection, and various accessories. It highlights the ACB's high breaking capacity, customizable features, and advanced protection functionalities, including temperature monitoring and fault recording. Additionally, it outlines installation methods, maintenance procedures, and acquired standards and certifications for the product.

Uploaded by

rico8370
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 148

HG

Air Circuit
Breakers

Overview and Characteristics  4

Technical Data External Structure 6


Internal Structure 7
Connection Method 8
Accessories 10

Model Selection Table  12

Accessories Protection Trip Relay (OCR) 17


Accessories 53

Dimensions  100

Circuit Diagram  124

Order Code  126

Installation and Environment  133

Maintenance Inspection List  144

Acquired Standards  147

ACB
Product Overview

HG Series

Air Circuit Breakers


Maximized customer’s range of selection and level of
satisfaction with model dualization and compact size.
Characteristics

Multi Retrofit Certifications


Bus bar terminal
can be changed to
horizontal/vertical

90 º

Customized Retrofit ACB can be Provided


Vertical Type Horizontal Type New products can be developed to be
compatible/installed according to the distance of
cradle phase/pole/land and terminal size of the
ACB that has been installed previously

Maximum Breaking Capacity Type per Rating


150 kA (At 500 V, HGN D Frame) 2 Frames, HGS 1,600/3,200 A
4 Frames, HGN 2,000/4,000/5,000/6,300 A

Rated Impulse Withstand 100 % N Phase Current Flow


Voltage (Uimp):12 kV Capacity for all Types

A Frame [85 kA] B Frame [100 kA]


630 ~ 1,600 A (HGS) / 630 ~ 2,000 A (HGN) 2,000 ~ 3,200 A (HGS) / 630 ~ 4,000 A (HGN)

C Frame [100 kA] D Frame [150 kA]


3,200 ~ 5,000 A (HGN) 4,000 ~ 6,300 A (HGN)
4 Air Circuit Breakers

Overview and Characteristics


Air Circuit Breaker (ACB)
Capable of Responding to Various Customer Applications Bus Bar Terminal can be Changed to Horizontal/Vertical
HG Series air circuit breaker is equipped with high breaking Connection method can be changed flexibly according to the
capacity and highly functional OCR, making various customer customer’s panel structure
applications on industrial building, computer center, device ˙HGS/HGN A frame 630 ~ 1,600 A
industries and others possible. With all models designed with 100 % ˙HGS/HGN B frame 630 ~ 3,200 A
n phase current flow capacity, the equipment is safely protected
against abnormal phenomenon such as harmonics and others.

Equipped with Various Accessories and Highly Convenient Maintenance by Attaching Draw-In/Out
Functional Protection Trip Relay (OCR) Device to the Body
Over Current Relay (Trip Relay)
Apart from the basic protection functions, OCR has reinforced
power monitoring functions such as temperature monitoring,
fault recording and storage etc., enabling stable power supply.

N Type Customized Retrofit ACB


˙Overcurrent Protection (L/S/I/G) New products can be developed to be compatible/installed
˙World’s First NFC Function Applied according to the distance of cradle phase/pole/land and terminal
˙Fault Recording (10) and Waveform (4 Cycles, Check Via size of the ACB that has been installed previously
Communication) can be Transmitted to Mobile Phone App ˙Economic:No need for busbar and external box replacement,
minimum construction period, uninterruptable replacement in
A Type case of body retrofit
˙Overcurrent Protection (L/S/I/G) ˙Stability:Lifespan can be extended through the latest relay
˙Self Power performance and by providing breaking performance of high
˙Individual Continuous Power Contact breaking product
˙Fault Recording (256) and Waveform (4 Cycles, Check Via ˙Compatibility:Stable usage through control terminal bar,
Communication) bus bar structure and plug-in compatible devices
˙Communication (MODBUS), External Grounding CT/Earth ˙Technical Support:Customer satisfaction through inspection
Leakage ZCT can be used of various accessories of old panels

P Type Re-Design of External Terminal

˙Overcurrent Protection (L/S/I/G)


˙External Power
˙Individual Continuous Power Contact
˙Fault Recording (256) and Waveform (4 Cycles, Check Via
Communication)
˙Over-Voltage/Under-Voltage, Power, Power Factor, Energy
Display

H Type
Standard Cradle Cradle Retrofit
˙L/S/I/G Functions
˙External Power
˙Individual Continuous Power Contact
˙Fault Recording (256) and Waveform (4 Cycles, Check Via
Communication)
˙L/S/I/G Minute Current Adjustment
˙Voltage/Current Harmonics (1 st ~ 63 th) Analysis
˙View 3 Phase Waveform
Air Circuit Breakers 5

VCB
Equipped with Temperature Sensor
Reliable high temperature measurement is possible following the sensor measurement of the heat source (Range of measurement:
-5 ~ 250 degrees)

Example of IR Sensor Application Installation of IR Sensor

When Installed Directly


on ACB

ACB
Screw PH(+) PS/W M4 L8

Mouting Bolt ACB Terminal


Sensor (Important Item : Black Colored)
Supporter Plate 3 m in Length

Matte Black Coating Applied on

MCCB
Measurement Point
RCTU Sensor

Distance = 40 ~ 80 mm Busbar

* How to Install ˙IR temperature sensor has to be installed with sufficient


insulation distance from the point to be measured
˙The recommended distance between the measurement point
Address Setting:1 ~ 240 and temperature sensor is 50 ~ 80 mm.
On ˙The measurement point has to be a surface without reflection
due to the characteristics of the IR sensor and matte black
1 2 3 4 5 6 7 8 painting is recommended for the measurement point.

Baud Rate Setting


Caution
On Set Description
Off Off 9,600
1. The measurement value of the IR sensor differs depending on the
reflection rate of the metal surface. Surfaces coated with matte black or
MS
1 2 Off On 19,200
surface with varnish excluding metallic varnish must be measured.
On Off 38,400 2. The size of measurement point differs depending on the D:S Ratio for the
surface to be measured and the IR distance. This sensor has a ratio of 8:1.

Applied Standards and Certifications


HG Series air circuit breaker has acquired testing/certifications Acquired Standards and Certifications
from IEC 60947-1, 2 certified testing institute and can be installed ˙KS Certification:KS C 4620
RELAY

and applied according to the usage environment and conditions ˙CB Certification (DEKRA, KERI):IEC 60947-1, 2
permitted by the standards. ˙CE Mark
˙CCC Certification
˙Vessel Certification:LR, ABS, KR, BV, GL, NK, RINA, DNV, RS
˙9 Major Vessel Certifications:KR, GL, LR, ABS, BV, NK, RINA, DNV, RS
6 Air Circuit Breakers

Technical Data
External Structure




⓰ ⓫
⓰ ⓫
❸ ⓬
❸ ⓬
❹ ⓭ ⓭



❻ ❻
⓮ ❼




Fixed Type Draw-In/Out Type (Including Cradle)

Cradle Front Cradle Rear

❶ Control Circuit Terminal ❼ Position Padlock ⓭ Manual Charging Handle


❷ Front Cover ❽ Position Lock Release Button ⓮ Rating Nameplate
❸ Close/Open Indicator ❾ Draw-In/Out Handle Insertion Hole ⓯ Terminal Busbar
❹ Close Button ❿ Position Indicator ⓰ OCR & Alarm S/W Reset Button
❺ Overcurrent Relay Device ⓫ Counter ⓱ Draw-In/Out Guide Rail
❻ Open Button ⓬ Charged/Discharged Indicator
Air Circuit Breakers 7

VCB
Internal Structure




ACB

❾ ❼

MCCB

❻ ❶
❹ ⓰
⓮ ⓱
❽ ⓲



MS
⓫ ⓲

❶ DI Grid ❼ MHT Device ⓭ Control Terminal ⓳ Current Transformer(CT)


❷ CO Unit ❽ OCR ⓮ Manual Charging Handle Terminal Clip
RELAY

❸ Counter ❾ Mechanism ⓯ Closing Spring Cradle


❹ AUX Switch ❿ DR Device ⓰ Moving Contact
❺ Motor ⓫ Cover ⓱ Fixed Contact
❻ Closing/Trip/UVT Coil ⓬C
 ontrol Terminal Protection Cover ⓲ Terminal

※ HG Series air circuit breaker has been designed so that upon closing, the N phase is closed earlier than R, S, T phase and upon opening, the N phase is disconnected last in order to
reduce burden of main contact and to prevent ripple effect of accident of N phase.
8 Air Circuit Breakers

Technical Data
Connection Method
User convenience has been reinforced by allowing each terminal to be rotated 90 degrees directly on site depending on the busbar type
of low voltage switchgear.

Standard Type

Vertical Type Horizontal Type Front Type

Combined Type

(Upper) Vertical Type + (Upper) Horizontal Type + (Upper) Vertical Type +


(Lower) Horizontal Type (Lower) Vertical Type (Lower) Front Type

(Upper) Horizontal Type + (Upper) Front Type + (Upper) Front Type +


(Lower) Front Type (Lower) Vertical Type (Lower) Horizontal Type

※ Terminal change is only possible for HGS/HGN A frame 630 ~ 1,600 A, B frame 2,000 ~ 3,200 A.
Front type is a terminal form that is suitable for switchgear with spatial restrictions.
Horizontal/vertical change above 4,000 A requires separate parts so please contact our company.
In case of B frame, 3,200 A terminal is provided as for the front type provided separately for 2,000/2,500 A.
Front type terminal has to be purchased separately.
Air Circuit Breakers 9

VCB
Convenient Connection Method
As for HG Series air circuit breaker, 4 types of mounting
(Connected, test, isolated, removed) are possible and offer easy
maintenance.

Sliding Body Type (In Case of Draw-In/Out Type)

ACB
Connected Position Test Position

As a commonly used status, the main circuit and control circuit are both As a status in which the main circuit is isolated and the control circuit is
connected. connected, the circuit breaker can be turned On/Off with the switchgear
door closed.

MCCB
Isolated Position Removed Position

With the main circuit and control circuit both isolated, the air circuit cannot The air circuit has completely been removed from the cradle.
be turned On/Off.

MS
RELAY
10 Air Circuit Breakers

Technical Data
Various Accessories (Main Unit)

❷,❺
❹,❻
❸,❺


⓱ ❾ ❼,❽

⓬ ⓯

⓭ ❶ ❽

Accessories for Circuit Breaker

❶ Spring Charge Geared Motor ❾ Lifting Lug ⓱ Counter


❷ Closing Coil ❿ Mechanical Interlock ⓲ OCR & Alarm S/W Reset Button
❸ Trip Coil ⓫ Phase Insulation Barrier ⓳ Test Jumper
❹ Secondary Trip Coil ⓬ On/Off Button Lock Draw-In/Out Handle
❺ Trip Coil Supervision ⓭ OCR Portable Checker Position Pad Lock
❻ UVT Coil ⓮ Key Lock Door Flange
❼ AUX Switch ⓯ Miss-Insertion Preventer Dust Cover
❽ Condenser Trip Device (CTD) ⓰ Fixing Block
Air Circuit Breakers 11

VCB
Various Accessories (Cradle)

❶,❷,❸


❿,❻

ACB
⓫,❼

MCCB

MS

Accessories for Cradle

❶ UVT Time Delay Controller ❺ Position Switch ❿ Safety Shutter


❷ Remote Closing Prevention Module ❻ Mechanical Interlock ⓫ Arc Shield
❸ Temperature Monitoring Device ❼ Phase Insulation Barrier ⓬ Control Terminal Protection Cover
RELAY

Module ❽ Mechanical Operated Cell Switch


❹ Short “b” Contact ❾ Miss-Insertion Preventer
12 Air Circuit Breakers

Model Selection Table


Rating and Specification
Model Name HGS HGN

Item A Frame B Frame A Frame B Frame C Frame D Frame


06:630 20:2,000 06:630 06:630 32:3,200 40:4,000
08:800 25:2,500 08:800 08:800 40:4,000 50:5,000
10:1,000 32:3,200 10:1,000 10:1,000 50:5,000 63:6,300
12:1,250 12:1,250 12:1,250
Rated Current
Based on 40 ℃ A 16:1,600 16:1,600 16:1,600
[In max]
20:2,000 20:2,000
25:2,500
32:3,200
40:4,000
Rated Operational Voltage [Ue] V 690 690
Rated Insulation Voltage [Ui] V 1,000 1,000
Frequency Hz 50/60 50/60
No. of Poles P 3, 4 3, 4
Current Setting Range (…× In max) A 0.4 ~ 1.0 0.4 ~ 1.0
Rated Current of Neutral Pole (N) (… %×In) A 100 % 100 % 100 % 100 % 100 % 100 %
Rated Breaking Capacity [Icu] [Sym]
IEC 60947-2 690/600/550 V 50 70 1) (KS:65) 65 85 85 100
Category “B” AC 500/480/460 V kA 65 85 85 100 100 150
KS C 4620 415/380/230/220 V 65 85 85 100 100 150
Rated Service Short-Circuit Breaking Capacity [Ics] …%×Icu kA 100 % 100 % 100 % 100 % 100 % 100 %
Rated Closing Current [Icm] [Peak]
IEC 60947-2 690/600/550 V 105 154 143 187 187 220
Category “B” AC 500/480/460 V kA 143 187 187 220 220 330
KS C 4620 415/380/230/220 V 143 187 187 220 220 330
Rated Short-Time withstand Voltage [Icw] (Without Inst)
1 Second 50 70 65 85 85 100
2 Seconds kA 35 65 42 75 75 85
3 Seconds 28 50 35 65 65 75
Rated Impulse withstand Voltage [Uimp] kV 12 12
Total Breaking-Time ms 40 3) 40 3)
Closing Operational Time
Motor Charging Time (sec) max. 10 10
Rated Trip Time (ms) max. 80 80
Lifecycle (Cycles)
Without Maintenance 20,000 20,000 20,000 20,000 10,000 5,000
Mechanical
With Maintenance 30,000 30,000 30,000 30,000 15,000 10,000
20:5,000
Without Maintenance 5,000 5,000 5,000 2,000 2,000
25 ~ 40:3,000
Electrical
20:10,000
With Maintenance 10,000 10,000 10,000 5,000 5,000
25 ~ 40:8,000
Weight
Draw-Out Type 63 87 63 87 (107) 2) 145 169
3 Pole
Fixed Type 34 44 34 44 (61) 2) 76 108
kg
Draw-Out Type 74 103 74 103 (140) 2) 173 214
4 Pole
Fixed Type 44 55 44 55 (80) 2) 81 137
(W×H×D)
Draw-Out Type 328×460×368.4 399×460×368.4 328×460×368.4 399×460×368.4 624×460×368.4 766×460×368.4
3 Pole
Fixed Type 337.4×404.4×295.8 408.4×404.4×295.8 337.4×404.4×295.8 408.4×404.4×295.8 633.4×404.4×295.8 775.4×404.4×295.8
mm
Draw-Out Type 413×460×368.4 514×460×368.4 413×460×368.4 514×460×368.4 794×460×368.4 996×460×368.4
4 Pole
Fixed Type 422.4×404.4×295.8 523.4×404.4×295.8 422.4×404.4×295.8 523.4×404.4×295.8 803.4×404.4×295.8 1,005×404.4×295.8

※ 1) 70 kA is DEKRA certified Life time is the limit lifespan and is not the guaranteed lifespan. In case of maintenance,
2) 4,000 AF it is charged. In the event of abnormalities in accessories during use, it can be replaced.
3) In case of MCR and override setting, INST is 50 ms. Quality Assurance:Based on IEC 60947-2’s number of opening/closing within the
warranty period.

Fixed Type Draw-Out Type


H

D W D
W D W
Air Circuit Breakers 13

VCB
Over Current Relay (OCR)
Function General Feeder Generator (Marine Type)

N Type A Type P Type H Type N Type A Type P Type


Model Name
GPR-LN GPR-LA GPR-LAG GPR-LAZ GPR-LP GPR-LH GPR-SN GPR-SA GPR-SP
Frequency
50 Hz 50 51 52 53 54 55 57 58 59
60 Hz 60 61 62 63 64 65 67 68 69
Control Power
External Power - ● ● ● ● ● - ● ●
Self-Power ● ● ● ● ● ● ● ● ●
Protection Function
LTD (Long Time) ● ● ● ● ● ● ● ● ●

ACB
STD (Short Time) ● ● ● ● ● ● ● ● ●
INST (Instantaneous) ● ● ● ● ● ● ● ● ●
Pre-Trip Alarm - ● ● ● ● ● - ● ●
Ground Fault Trip ● ● - - ● ● - - -

● ●
Outer CT ZCT Earth
Ground 2) Leakage 3)
ELT Function - - - - - - -
(Ground fault (Below 30 A)
at more than
30 A)

Thermal Function ● ● ● ● ● ● ● ● ●
Field Test - ● ● ● ● ● - ● ●
Fail Safe ● ● ● ● ● ● ● ● ●
Indication
True RMS

MCCB
● ● ● ● ● ● ● ● ●
Detection Method
LED Indication per
- ● ● ● ● ● - ● ●
Trip Type
PTA, L, PTA, L, PTA, L, PTA, L, PTA, L, PTA, L, PTA, L,
Fault LED L 1) L 1)
S/I, G S/I, leakage S/I, leakage S/I, G S/I, G S/I S/I
Real-Time LCD
Indication of Load - ● ● ● ● ● - ● ●
Rate per Phase
Measurement LCD - ● ● ● ● ● - ● ●
Output Contact
Integrated
Instantaneous ● - - - - - - -
Contact (1a)
Individual Continuous
- ● ● ● ● ● - ● 4) ● 4)
Contact (4a)
Operation
MCR - 〇 〇 〇 〇 〇 - 〇 〇 MS
Communication NFC Modbus-RTU Modbus-RTU Modbus-RTU Modbus-RTU Modbus-RTU NFC Modbus-RTU Modbus-RTU
Event/Fault Recording ● ● ● ● ● ● ● ● ●

※ ●:Standard, 〇:Option
1) Indicates reserve before operation during long time delay.
2) ZCT designated by the customer is used.
3) ZCT designated by our company is used.
4) As for marine type, individual continuous contact is 3a.
RELAY
14 Air Circuit Breakers

Model Selection Table


Selective Breaking Method of Protection Coordination HG-MCB

˙Upstream:ACB HGN/HGS
˙Downstream:MCB HGD, MCCB HGM/HGP

HG-ACB HG-MCCB

Upstream

Item ACB
Downstream

Model HGS/HGN A Frame HGS/HGN B Frame HGN C Frame


Name 630 800 1,000 1,250 1,600 2,000 2,000 2,500 3,200 4,000 4,000 5,000
Rated
Current
Rated Breaking Current
(A) 85 85 85 85 85 85 100 100 100 100 100 100
[Icu] (kA rms)

1 3 T T T T T T T T T T T T
2 3 T T T T T T T T T T T T
3 3 T T T T T T T T T T T T
4 3 T T T T T T T T T T T T
5 3 T T T T T T T T T T T T
6 3 T T T T T T T T T T T T
10 3 T T T T T T T T T T T T

HGD63E 13 3 T T T T T T T T T T T T
B, C, D Curve 15 3 T T T T T T T T T T T T
16 3 T T T T T T T T T T T T
20 3 T T T T T T T T T T T T
25 3 T T T T T T T T T T T T
32 3 T T T T T T T T T T T T
40 3 T T T T T T T T T T T T
50 3 T T T T T T T T T T T T
63 3 T T T T T T T T T T T T
1 4.5 T T T T T T T T T T T T
2 4.5 T T T T T T T T T T T T
3 4.5 T T T T T T T T T T T T
4 4.5 T T T T T T T T T T T T
5 4.5 T T T T T T T T T T T T
6 4.5 T T T T T T T T T T T T
MCB
10 4.5 T T T T T T T T T T T T

HGD63S 13 4.5 T T T T T T T T T T T T
B, C, D Curve 15 4.5 T T T T T T T T T T T T
16 4.5 T T T T T T T T T T T T
20 4.5 T T T T T T T T T T T T
25 4.5 T T T T T T T T T T T T
32 4.5 T T T T T T T T T T T T
40 4.5 T T T T T T T T T T T T
50 4.5 T T T T T T T T T T T T
63 4.5 T T T T T T T T T T T T
1 6 T T T T T T T T T T T T
2 6 T T T T T T T T T T T T
3 6 T T T T T T T T T T T T
4 6 T T T T T T T T T T T T
5 6 T T T T T T T T T T T T

HGD63N/M 6 6 T T T T T T T T T T T T
B, C, D Curve 10 6 T T T T T T T T T T T T
13 6 T T T T T T T T T T T T
15 6 T T T T T T T T T T T T
16 6 T T T T T T T T T T T T
20 6 T T T T T T T T T T T T
25 6 T T T T T T T T T T T T

※ T Selective breaking is possible in all sectors, Selective breaking is impossible in this sector.
Air Circuit Breakers 15

VCB
HG-MCB

˙Upstream:ACB HGN/HGS
˙Downstream:MCB HGD, MCCB HGM/HGP

HG-ACB HG-MCCB

Upstream

Item ACB
Downstream

Model HGS/HGN A Frame HGS/HGN B Frame HGN C Frame


Name 630 800 1,000 1,250 1,600 2,000 2,000 2,500 3,200 4,000 4,000 5,000
Rated
Current
Rated Breaking Current
(A) 85 85 85 85 85 85 100 100 100 100 100 100
[Icu] (kA rms)

ACB
32 6 T T T T T T T T T T T T
HGD63N/M 40 6 T T T T T T T T T T T T
B, C, D Curve 50 6 T T T T T T T T T T T T
63 6 T T T T T T T T T T T T
1 10 T T T T T T T T T T T T
2 10 T T T T T T T T T T T T
3 10 T T T T T T T T T T T T
4 10 T T T T T T T T T T T T
5 10 T T T T T T T T T T T T
6 10 T T T T T T T T T T T T
10 10 T T T T T T T T T T T T
MCB HGD63H 13 10 T T T T T T T T T T T T

MCCB
B, C, D Curve 15 10 T T T T T T T T T T T T
16 10 T T T T T T T T T T T T
20 10 T T T T T T T T T T T T
25 10 T T T T T T T T T T T T
32 10 T T T T T T T T T T T T
40 10 T T T T T T T T T T T T
50 10 T T T T T T T T T T T T
63 10 T T T T T T T T T T T T
80 10 T T T T T T T T T T T T
HGD125
100 10 T T T T T T T T T T T T
B, C, D Curve
125 10 T T T T T T T T T T T T
16 30 T T T T T T T T T T T T
20 30 T T T T T T T T T T T T
25 30 T T T T T T T T T T T T
32 30 T T T T T T T T T T T T MS
40 30 T T T T T T T T T T T T
HGM100
50 30 T T T T T T T T T T T T
63 30 T T T T T T T T T T T T
75 30 T T T T T T T T T T T T
80 30 T T T T T T T T T T T T
100 30 T T T T T T T T T T T T
MCCB 16 55 T T T T T T T T T T T T
20 55 T T T T T T T T T T T T
25 55 T T T T T T T T T T T T
32 55 T T T T T T T T T T T T
40 55 T T T T T T T T T T T T
RELAY

HGM125 50 55 T T T T T T T T T T T T
63 55 T T T T T T T T T T T T
75 55 T T T T T T T T T T T T
80 55 T T T T T T T T T T T T
100 55 T T T T T T T T T T T T
125 55 T T T T T T T T T T T T

※ T Selective breaking is possible in all sectors, Selective breaking is impossible in this sector.
MCCB Rated Breaking Current:Based on AC 440/460 V, HGM L-Type, HGP X-Type
16 Air Circuit Breakers

Model Selection Table


Selective Breaking Method of Protection Coordination HG-MCB

˙Upstream:ACB HGN/HGS
˙Downstream:MCB HGD, MCCB HGM/HGP

HG-ACB HG-MCCB

Upstream

Item ACB
Downstream

Model HGS/HGN A Frame HGS/HGN B Frame HGN C Frame


Name 630 800 1,000 1,250 1,600 2,000 2,000 2,500 3,200 4,000 4,000 5,000
Rated
Current
Rated Breaking Current
(A) 85 85 85 85 85 85 100 100 100 100 100 100
[Icu] (kA rms)

100 55 T T T T T T T T T T T T
125 55 T T T T T T T T T T T T
150 55 T T T T T T T T T T T T
160 55 T T T T T T T T T T T T
HGM250
175 55 T T T T T T T T T T T T
200 55 T T T T T T T T T T T T
225 55 T T T T T T T T T T T T
250 55 T T T T T T T T T T T T
250 85 T T T T T T T T T T T T
300 85 T T T T T T T T T T T T
HGM400
350 85 T T T T T T T T T T T T
400 85 T T T T T T T T T T T T
500 85 T T T T T T T T T T T
HGM630
630 85 T T T T T T T T T T T
700 85 T T T T T T T T T T
HGM800
800 85 T T T T T T T T T T
16 150 T T T T T T T T T T T T
20 150 T T T T T T T T T T T T
25 150 T T T T T T T T T T T T
32 150 T T T T T T T T T T T T
MCCB 40 150 T T T T T T T T T T T T
HGP125D
50 150 T T T T T T T T T T T T
63 150 T T T T T T T T T T T T
80 150 T T T T T T T T T T T T
100 150 T T T T T T T T T T T T
125 150 T T T T T T T T T T T T
100 150 T T T T T T T T T T T T
125 150 T T T T T T T T T T T T
150 150 T T T T T T T T T T T T
160 150 T T T T T T T T T T T T
HGP250
175 150 T T T T T T T T T T T T
200 150 T T T T T T T T T T T T
225 150 T T T T T T T T T T T T
250 150 T T T T T T T T T T T T
300 150 T T T T T T T T T T T T
HGP400 350 150 T T T T T T T T T T T T
400 150 T T T T T T T T T T T T
500 150 T T T T T T T T T T T
HGP630
630 150 T T T T T T T T T T T
700 150 T T T T T T T T T T
HGP800
800 150 T T T T T T T T T T

※ T Selective breaking is possible in all sectors, Selective breaking is impossible in this sector.
MCCB Rated Breaking Current:Based on AC 440/460 V, HGM L-Type, HGP X-Type
Air Circuit Breakers 17

Accessories

VCB
Over Current Relay (OCR)
External

❷ ❸
❶ ❹

ACB



⓬ ❿


⓭ ⓱

MCCB

MS

❶ PTA Signal LED ❽ LTD Test Button ⓯ STD Pick Up Setting GFT/STD (Inverse Time Setting).,
❷ LTD Signal LED ❾ Movement Button ⓰ STD Operational Time Setting MCR On/Off Setting Switch
❸ STD/INST Signal LED ❿ Enter Button ⓱ INST Pick Up Setting In (Rated Current) Setting
❹ GFT/ELT Signal LED ⓫ Reset Button ⓲ PTA Pick Up Setting Temporary Test Connection Jack
❺ Com. Signal LED ⓬ Menu Button ⓳ PTA Operational Time Setting Model Name
❻ LCD/NFC Antenna (LN, SN) ⓭ LTD Pick Up Setting GFT/ELT Pick Up Setting Battery
RELAY

❼ STD/INST Test Button ⓮ LTD Operational Time Setting G


 FT/ELT Operational Time Setting

※ Self-power functions normally in the case of 10 % for 3 phases and 30 % for a single phase. However, when 200 A ~ 320 A CT is used, it functions normally in case of 50 % for 3 phase
and more than 100 % for single phase.
When using MCR function, mark B8 in the name of order type. Auxiliary contact point is 4a5b.
The lifespan of the battery is usually 10 years so in case it is time for replacement, contact our customer support division and services can be received at a cost.
High/low test function is automatically disabled when a load current is applied.
18 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
Enhancement of Over Current Relay (OCR) Functions
Over current relay (OCR) built in the HG Series air circuit breaker has reinforced power monitoring functions such as temperature
monitoring, fault recording other than the basic protection function, ultimately enabling stable power supply.

Item General Feeder


N Type A Type P Type
Model Name
GPR-LN GPR-LA GPR-LAG (Outer CT Ground) GPR-LAZ (Outer CT Earth Leakage) GPR-LP

Externals

50 Hz 50 51 52 53 54
Frequency
60 Hz 60 61 62 63 64

˙L/S/I/G ˙L/S/I/G ˙L/S/I Uses Dedicated ˙L/S/I Uses Dedicated ˙L/S/I/G


˙Thermal ˙Thermal Outer CT Ground if Outer CT if ZCT Earth ˙Thermal
˙Self-Power ˙Self-Power Outer CT Ground (More Leakage (Below 30 A) > ˙Self-Power
˙Fail Safe ˙Fail Safe than 30 A) > 5 A at 1,000:1 A ˙Fail Safe
˙Integrated ˙Communication Secondary) ˙Thermal ˙Communication
Instantaneous Contact (Modbus) ˙Thermal ˙Self-Power (Modbus)
˙10 ea Fault ˙External Power ˙Self-Power ˙Fail Safe ˙External Power
Recording (Check Via ˙ZSI ˙Fail Safe ˙Communication ˙ZSI
Communication) ˙Remote Reset Function ˙Communication (Modbus) ˙Remote Reset Function
˙Last Fault’s Waveform ˙Individual Continuous (Modbus) ˙External Power ˙Individual Continuous
Recording (4 Cycles, Contact:LTD, STD/INST, ˙External Power ˙ZSI Contact:LTD, STD/INST,
Check Via GFT, PTA ˙ZSI ˙Remote Reset Function GFT, PTA
Communication) ˙256 ea Fault Recording ˙Remote Reset Function ˙Individual Continuous ˙256 ea Fault Recording
˙Last Fault’s Waveform ˙Individual Continuous Contact:LTD, STD/INST, ˙Last Fault’s Waveform
Recording (4 Cycles, Contact:LTD, STD/INST, GFT, PTA Recording (4 Cycles,
Check Via GFT, PTA ˙256 ea Fault Recording Check Via
Communication) ˙256 ea Fault Recording ˙Last Fault’s Waveform Communication)
˙200 ea Event ˙Last Fault’s Waveform Recording (4 Cycles, ˙200 ea Event
Main Functions Recording (Check Via Recording (4 Cycles, Check Via Recording (Check Via
Communication) Check Via Communication) Communication)
Communication) ˙200 ea Event ˙Over-Voltage/
˙200 ea Event Recording (Check Via Under-Voltage
Recording (Check Via Communication) ˙Imbalance Type
Communication) (Voltage/Current)
˙Reverse Power
˙3 Phase Voltage/Current
RMS/Vector
˙Power (P, Q, S), Power
Factor (3 Phase)
˙Energy (Normal/Reverse
Direction)
˙Demand
Air Circuit Breakers 19

VCB
Item General Feeder Generator (Marine Type)
H Type N Type A Type P Type
Model Name
GPR-LH GPR-SN GPR-SA GPR-SP

ACB
Externals

MCCB
50 Hz 55 57 58 59
Frequency
60 Hz 65 67 68 69

˙L/S/I/G ˙L/S/I ˙L/S/I ˙L/S/I


˙Thermal ˙Minute Current Adjustment ˙Minute Current Adjustment ˙Thermal
˙IDMTL ˙Thermal ˙Thermal ˙Self-Power
˙Self-Power ˙Self-Power ˙Self-Power ˙Fail Safe
˙Fail Safe ˙Fail Safe ˙Fail Safe ˙Communication (Modbus)
˙Communication (Modbus) ˙Integrated Instantaneous ˙Communication (Modbus) ˙External Power
˙External Power Contact ˙External Power ˙ZSI
˙ZSI ˙10 ea Fault Recording ˙ZSI ˙Remote Reset Function
˙Remote Reset Function (Check Via Communication) ˙Remote Reset Function ˙Individual Continuous Contact:
˙Individual Continuous Contact: ˙Last Fault’s Waveform ˙Individual Continuous Contact: LTD, STD/INST, PTA
LTD, STD/INST, GFT, PTA
˙256 ea Fault Recording
Recording (4 Cycles, Check Via
Communication)
LTD, STD/INST, PTA
˙256 ea Fault Recording
˙256 ea Fault Recording
˙Last Fault’s Waveform
MS
˙Last Fault’s Waveform ˙Last Fault’s Waveform Recording (4 Cycles, Check Via
Recording (4 Cycles, Check Via Recording (4 Cycles, Check Via Communication)
Communication) Communication) ˙200 ea Event Recording
˙200 ea Event Recording ˙200 ea Event Recording (Check Via Communication)
˙Over-Voltage/Under-Voltage (Check Via Communication) ˙Over-Voltage/Under-Voltage
˙Imbalance Type (Voltage/Current) ˙Imbalance Type
Main Functions ˙Reverse Power (Voltage/Current)
˙3 Phase Voltage/Current RMS/ ˙Reverse Power/Over-Power
Vector ˙3 Phase Voltage/Current RMS/
˙Power (P, Q, S), Power Factor Vector
(3 Phase) ˙Power (P, Q, S), Power Factor
˙Energy (Normal/Reverse (3 Phase)
Direction) ˙Energy (Normal/Reverse
˙Frequency, Demand Direction)
˙Minute Current Adjustment ˙Demand
RELAY

at Long Time, Short Time, ˙Minute Current Adjustment


Instantaneous, Ground Setting at Long Time, Short time,
˙Voltage/Current Harmonics Instantaneous, Ground Setting
(1 st ~ 63 th)
˙View 3 Phase Waveform
˙THD, TDD
20 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
Appearance and Setting Value

GPR-LN (50, 60)


˙Overload Protection ˙Protection Features
- Long time delay
˙Short Circuit Protection
- Short time delay, instantaneous trip Ir
- l²t On/Off optional (for STD)
tr
˙Ground Fault Protection
- l²t On/Off optional
˙Neutral Wire Protection I2t on
Isd
Ig I2t on
- 3P:No protection for neutral wire tsd
tg
- 4P:100 % × In
- LTD, STD, INST protection Ii
I2t off
˙Self-Power I2t off

˙Equipped with NFC Functions


- Incident information can be received to
the mobile phone
- Introduction of function and app
installation method:Refer to Page 34
˙1a DO (Digital Output)
- Contact specification

Nominal Switching 5A
Capacity (Resistive Load) 277 VAC
Max. Switching Power
1,385 VA
(Resistive Load)
Rating
Max. Switching Voltage 277 VAC
Max. Switching Current 5A
Max. Switching Capacity 100 mA
(Reference Value) 5 VDC

Protection Functions

In = Ict×… 0.5 0.63 0.7 0.8 0.9 1


Current Setting (A)
Ir = In×… 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1 Non
LTD Protection Time Delay (sec) tr @ (1.5×Ir) 10.4 26.1 41.7 52 104 208 312 417 521 626
Accuracy:± 15 % or tr @ (6.0×Ir) 0.5 1.25 2 2.5 5 10 15 20 25 30
Below 100 ms tr @ (7.2×Ir) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
Current Setting (A)
Isd = In×… 1 1.5 2 2.5 3 4 6 8 10 Non
Accuracy:± 15 %
I2t Off 0.05 0.1 0.2 0.3 0.4 0.5
STD Protection tsd
Time Delay (sec) I2t On 0.05 0.1 0.2 0.3 0.4 0.5
@ 10×In Min. Trip Time (ms) 20 80 160 260 360 460
(I2t Off)
Max. Trip Time (ms) 80 140 240 340 440 540
Instantaneous Current Setting (A) Ii = In×… 2 3 4 6 8 10 12 15 Non
Protection Tripping Time Below 50 ms
Grounding Pick-Up Setting (A)
Accuracy: ± 15 % (Ig>0.4 In) Ig = Ict×… 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1 Non
± 20 % (Ig≤0.4 In)
Grounding
I2t Off 0.05 0.1 0.2 0.3 0.4 0.5
Protection Time Delay (sec) tg
I2t On 0.05 0.1 0.2 0.3 0.4 0.5
@ 1×Ict
Accuracy:± 20 % Min. Trip Time (ms) 20 80 160 260 360 460
(I t Off)
2
Max. Trip Time (ms) 80 140 240 340 440 540
Air Circuit Breakers 21

VCB
GPR-LA (51, 61)
˙Overload Protection ˙RS-485 Communication/Modbus-RTU
- Long time delay ˙4a DO (Digital Output)
˙Short Circuit Protection - Contact specification
- Short time delay, instantaneous trip
- l²t On/Off optional (for STD)
Nominal Switching 5A
˙Ground Fault Protection Capacity (Resistive Load) 277 VAC
- l²t On/Off optional Max. Switching Power
1,385 VA

ACB
˙Neutral Wire Protection (Resistive Load)
Rating
- 3 Pole:No protection Max. Switching Voltage 277 VAC
- 4 Pole:Non, 50 %, 100 % (×Ir, Isd, Ii) Max. Switching Current 5A
Max. Switching Capacity 100 mA
˙Measurement and Display
(Reference Value) 5 VDC
- 3 Phase current
˙Realization of Protective Coordination by ˙Protection Features
ZSI (Zone Selective Interlocking)
˙Fault Recording
- Records up to 256 fault information
Ir
on fault type, fault phase, fault value,
IP
occurrence time of fault tr
˙Event Recording Tp
- Records up to 200 events of devices,
I2t on

MCCB
records changes in protection trip relay Isd
Ig I2t on
information tsd
tg
˙Pre-Trip Alarm
- Prevent unnecessary overload trip by I2t off Ii
I2t off
setting according to rated current (In)
˙Field Test
- Simulation of long time, short time,
instantaneous

Protection Functions

In = Ict×… 0.5 0.63 0.7 0.8 0.9 1


Current Setting (A)
Ir = In×… 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1 Non MS
LTD Protection Time Delay (sec) tr @ (1.5×Ir) 10.4 26.1 41.7 52 104 208 312 417 521 626
Accuracy:± 15 % or tr @ (6.0×Ir) 0.5 1.25 2 2.5 5 10 15 20 25 30
Below 100 ms tr @ (7.2×Ir) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
Current Setting (A)
Isd = In×… 1 1.5 2 2.5 3 4 6 8 10 Non
Accuracy:± 15 %
I2t Off 0.05 0.1 0.2 0.3 0.4 0.5
STD Protection tsd
Time Delay (sec) I2t On 0.05 0.1 0.2 0.3 0.4 0.5
@ 10×In Min. Trip Time (ms) 20 80 160 260 360 460
(I2t Off)
Max. Trip Time (ms) 80 140 240 340 440 540
Instantaneous Current Setting (A) Ii = In×… 2 3 4 6 8 10 12 15 Non
Protection Tripping Time Below 50 ms
Grounding Pick-Up Setting (A)
Accuracy: ± 15 % (Ig>0.4 In) Ig = Ict×… 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1 Non
RELAY

± 20 % (Ig≤0.4 In)
Grounding
I2t Off 0.05 0.1 0.2 0.3 0.4 0.5
Protection Time Delay (sec) tg
I2t On 0.05 0.1 0.2 0.3 0.4 0.5
@ 1×Ict
Accuracy:± 20 % Min. Trip Time (ms) 20 80 160 260 360 460
(I t Off)
2
Max. Trip Time (ms) 80 140 240 340 440 540
Current Setting (A)
Ip = In×… 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 Non
Pre-Alarm Accuracy:± 15 %
Time Delay (sec) tp 5 10 15 20 40 60 80 120 160
22 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
Appearance and Setting Value

GPR-LAG (52, 62)


˙Overload Protection ˙Pre-Trip Alarm
- Long time delay - Prevent unnecessary overload trip by
- Thermal operation setting according to rated current (In)
˙Short Circuit Protection ˙Field Test
- Short time delay, instantaneous trip - Simulation of long time, short time,
- l²t On/Off optional (for STD) instantaneous
˙Earth Leakage Protection ˙RS-485 Communication/Modbus-RTU
- Uses ZCT for 5 A output at secondary ˙4a DO (Digital Output)
(used within 3 %) - Contact specification
- GPR setting is calculated based on 5 A at
secondary
Ex) When using 100:5 A, in order for Nominal Switching 5A
Capacity (Resistive Load) 277 VAC
primary to function at 30 A, 30×5/100 =
1.5 A, GPR is set to 2 A Max. Switching Power
1,385 VA
(Resistive Load)
˙Neutral Wire Protection Rating
Max. Switching Voltage 277 VAC
- 3 Pole:No protection
Max. Switching Current 5A
- 4 Pole:Non, 50 %, 100 % (×Ir, Isd, Ii)
Max. Switching Capacity 100 mA
˙Measurement and Display (Reference Value) 5 VDC
- 3 Phase current
˙Realization of Protective Coordination by ˙Protection Features
ZSI (Zone Selective Interlocking)
˙Fault Recording Ir
- Records up to 256 fault information IP
on fault type, fault phase, fault value, tr
occurrence time of fault
Tp
˙Event Recording I2t on
- Records up to 200 events of devices, Isd
Ig I2t on
records changes in protection trip relay tsd
tg
information
I2t off Ii
I2t off

Protection Functions

In = Ict×… 0.5 0.63 0.7 0.8 0.9 1


Current Setting (A)
Ir = In×… 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1 Non
LTD Protection Time Delay (sec) tr @ (1.5×Ir) 10.4 26.1 41.7 52 104 208 312 417 521 626
Accuracy:± 15 % or tr @ (6.0×Ir) 0.5 1.25 2 2.5 5 10 15 20 25 30
Below 100 ms tr @ (7.2×Ir) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
Current Setting (A)
Isd = In×… 1 1.5 2 2.5 3 4 6 8 10 Non
Accuracy:± 15 %
I2t Off 0.05 0.1 0.2 0.3 0.4 0.5
STD Protection tsd
Time Delay (sec) I2t On 0.05 0.1 0.2 0.3 0.4 0.5
@ 10×In Min. Trip Time (ms) 20 80 160 260 360 460
(I2t Off)
Max. Trip Time (ms) 80 140 240 340 440 540
Instantaneous Current Setting (A) Ii = In×… 2 3 4 6 8 10 12 15 Non
Protection Tripping Time Below 50 ms
Current Setting (A)
Ip = In×… 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 Non
Pre-Alarm Accuracy:± 15 %
Time Delay (sec) tp 5 10 15 20 40 60 80 120 160 200
Current Setting (A) I△n 0.5 0.8 1 2 3 5 Non
Leakage Time Delay (ms) Alarm Time (ms) 140 230 350 800 950
Protection Accuracy:± 15 % or △t
Above 40 ms Trip Time (ms) 60 140 230 350 800
Air Circuit Breakers 23

VCB
GPR-LAZ (53, 63)
˙Overload Protection ˙Field Test
- Long time delay - Simulation of long time, short time,
- Thermal operation instantaneous
˙Short Circuit Protection ˙4a DO (Digital Output)
- Short time delay, instantaneous trip - Contact specification
- l²t On/Off optional (for STD)
˙Earth Leakage Protection Nominal Switching 5A

ACB
- Uses our company’s supply of 1,000:1 ZCT Capacity (Resistive Load) 277 VAC
- GPR’s operation setting is set based on Max. Switching Power
1,385 VA
the primary (Resistive Load)
Rating
˙Neutral Wire Protection Max. Switching Voltage 277 VAC
- 3 Pole:No protection Max. Switching Current 5A
- 4 Pole:Non, 50 %, 100 % (×Ir, Isd, Ii) Max. Switching Capacity 100 mA
(Reference Value) 5 VDC
˙Measurement and Display
- 3 Phase current
˙Protection Features
˙Realization of Protective Coordination by
ZSI (Zone Selective Interlocking)
˙Fault Recording
- Records up to 256 fault information Ir
on fault type, fault phase, fault value, IP
tr
occurrence time of fault

MCCB
Tp
˙Event Recording
- Records up to 200 events of devices, I2t on
Isd
records changes in protection trip relay Ig I2t on
tsd
information tg

˙Pre-Trip Alarm I2t off Ii


- Prevent unnecessary overload trip by I2t off
setting according to rated current (In)
˙RS-485 Communication/Modbus-RTU

Protection Functions

In = Ict×… 0.5 0.63 0.7 0.8 0.9 1


Current Setting (A)
Ir = In×… 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1 Non MS
LTD Protection Time Delay (sec) tr @ (1.5×Ir) 10.4 26.1 41.7 52 104 208 312 417 521 626
Accuracy:± 15 % or tr @ (6.0×Ir) 0.5 1.25 2 2.5 5 10 15 20 25 30
Below 100 ms tr @ (7.2×Ir) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
Current Setting (A)
Isd = In×… 1 1.5 2 2.5 3 4 6 8 10 Non
Accuracy:± 15 %
I2t Off 0.05 0.1 0.2 0.3 0.4 0.5
STD Protection tsd
Time Delay (sec) I2t On 0.05 0.1 0.2 0.3 0.4 0.5
@ 10×In Min. Trip Time (ms) 20 80 160 260 360 460
(I2t Off)
Max. Trip Time (ms) 80 140 240 340 440 540
Instantaneous Current Setting (A) Ii = In×… 2 3 4 6 8 10 12 15 Non
Protection Tripping Time Below 50 ms
Current Setting (A)
Ip = In×… 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 Non
Pre-Alarm Accuracy:± 15 %
RELAY

Time Delay (sec) tp 5 10 15 20 40 60 80 120 160 200


Current Setting (A) I△n 0.5 1 2 3 5 10 20 30 Non
Leakage Time Delay (ms) Alarm Time (ms) 140 230 350 800 950
Protection Accuracy:± 15 % or △t
Above 40 ms Trip Time (ms) 60 140 230 350 800
24 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
Appearance and Setting Value

GPR-LP (54, 64) / GPR-LH (55, 65)


˙Overload Protection ˙RS-485 Communication/Modbus-RTU
- Long time delay ˙Need to Connect Voltage Module for
- Thermal operation Voltage Measurement
˙Short Circuit Protection ˙Additional Function in LH Type
- Short time delay, instantaneous trip
˙Voltage/Current Harmonics (1 st ~ 63 th)
- l²t On/Off optional (for STD)
- 3 phase waveform
˙Ground Fault Protection - TDH, TDD
- l²t On/Off optional
˙4a DO (Digital Output)
˙Neutral Wire Protection - Contact specification
- 3 Pole:No protection
- 4 Pole:Non, 50 %, 100 % (×Ir, Isd, Ii)
˙Over-Voltage/Under-Voltage/Imbalance Nominal Switching 5A
Capacity (Resistive Load) 277 VAC
Protection
Max. Switching Power
˙Measurement and Display (Resistive Load)
1,385 VA
- 3 Phase current/voltage/power/power Rating
Max. Switching Voltage 277 VAC
factor/power quantity/phase/demand
Max. Switching Current 5A
˙Realization of Protective Coordination by Max. Switching Capacity 100 mA
ZSI (Zone Selective Interlocking) (Reference Value) 5 VDC

˙Fault Recording
- Records up to 256 fault information ˙Protection Features
on fault type, fault phase, fault value,
occurrence time of fault
Ir
˙Event Recording IP
- Records up to 256 events of devices, records tr
changes in protection trip relay information Tp
˙Pre-Trip Alarm I2t on
Isd
- Prevent unnecessary overload trip by Ig I2t on
tsd
setting according to rated current (In) tg
˙Field Test
I2t off Ii
- Simulation of long time, short time, I2t off
instantaneous
Protection Functions

In = Ict×… 0.5 0.63 0.7 0.8 0.9 1


Current Setting (A)
Ir = In×… 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1 Non
LTD Protection Time Delay (sec) tr @ (1.5×Ir) 10.4 26.1 41.7 52 104 208 312 417 521 626
Accuracy:± 15 % or tr @ (6.0×Ir) 0.5 1.25 2 2.5 5 10 15 20 25 30
Below 100 ms tr @ (7.2×Ir) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
Current Setting (A)
Isd = In×… 1 1.5 2 2.5 3 4 6 8 10 Non
Accuracy:± 15 %
I2t Off 0.05 0.1 0.2 0.3 0.4 0.5
STD Protection tsd
Time Delay (sec) I2t On 0.05 0.1 0.2 0.3 0.4 0.5
@ 10×In Min. Trip Time (ms) 20 80 160 260 360 460
(I2t Off)
Max. Trip Time (ms) 80 140 240 340 440 540
Instantaneous Current Setting (A) Ii = In×… 2 3 4 6 8 10 12 15 Non
Protection Tripping Time Below 50 ms
Ground Pick-Up Setting (A)
Accuracy: ± 15 % (Ig>0.4 In) Ig = Ict×… 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1 Non
± 20 % (Ig≤0.4 In)
Grounding
I2t Off 0.05 0.1 0.2 0.3 0.4 0.5
Protection Time Delay (sec) tg
I2t On 0.05 0.1 0.2 0.3 0.4 0.5
@ 1×Ict
Accuracy:± 20 % Min. Trip Time (ms) 20 80 160 260 360 460
(I t Off)
2
Max. Trip Time (ms) 80 140 240 340 440 540
Current Setting (A)
Ip = In×… 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 Non
Pre-Alarm Accuracy:± 15 %
Time Delay (sec) tp 5 10 15 20 40 60 80 120 160 200
Air Circuit Breakers 25

VCB
GPR-SN (57, 67)
˙Overload Protection ˙Protection Features
- Long time delay
˙Short Circuit Protection
- Short time delay, instantaneous trip Ir
- l²t On/Off optional (for STD)
tr
˙Self-Power
˙Equipped with NFC Functions
I2t on

ACB
- Incident information can be received to Isd
the mobile phone tsd
- Introduction of function and app
installation method:Refer to Page 34 Ii
I2t off
˙1a DO (Digital Output)
- Contact specification

Nominal Switching 5A
Capacity (Resistive Load) 277 VAC
Max. Switching Power
1,385 VA
(Resistive Load)
Rating
Max. Switching Voltage 277 VAC
Max. Switching Current 5A

MCCB
Max. Switching Capacity 100 mA
(Reference Value) 5 VDC

Protection Functions

In = Ict×… (0.5 ~ 1.0) ✽1 % Unit or 1 A Unit


Current Setting (A)
Ir = In×… 0.7 0.8 0.9 1 1.05 1.1 1.15 1.2 1.25 Non MS
LTD Protection Time Delay (sec) tr @ (1.05×Ir) 20 30 40 50 60 70 80 100 120
Accuracy:± 15 % or tr @ (1.2×Ir) 10 15 20 25 30 35 40 50 60
Below 100 ms tr @ (3×Ir) 0.99 1.49 1.99 2.48 2.98 3.48 3.97 4.97 5.96
Current Setting (A)
Isd = In×… 1 1.5 2 2.5 3 3.5 4 4.5 5 Non
Accuracy:± 15 %
I2t Off 0.05 0.1 0.2 0.3 0.4 0.5
STD Protection tsd
Time Delay (sec) I2t On 0.05 0.1 0.2 0.3 0.4 0.5
@ 5×In Min. Trip Time (ms) 20 80 160 260 360 460
(I2t Off)
Max. Trip Time (ms) 80 140 240 340 440 540
Instantaneous Current Setting (A) Ii = In×… 2 3 4 6 8 10 12 15 Non
Protection Tripping Time Below 50 ms
RELAY
26 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
Appearance and Setting Value

GPR-SA (58, 68)


˙Overload Protection ˙3a DO (Digital Output)
- Long time delay - Contact specification
˙Short Circuit Protection
- Short time delay, instantaneous trip
Nominal Switching 5A
- l²t On/Off optional (for STD) Capacity (Resistive Load) 277 VAC
˙In Setting with Minute Adjustment Max. Switching Power
1,385 VA
- Adjusts in 1 A unit within the range of (Resistive Load)
Rating
0.5 ~ 1 lct Max. Switching Voltage 277 VAC
- Adjusted using button in the LCD setting Max. Switching Current 5A
screen Max. Switching Capacity 100 mA
˙Realization of Protective Coordination by (Reference Value) 5 VDC

ZSI (Zone Selective Interlocking)


˙Protection Features
˙Fault Recording
- Records up to 256 fault information
on fault type, fault phase, fault value,
Ir
occurrence time of fault
IP
˙Event Recording tr
- Records up to 200 events of devices,
Tp
records changes in protection trip relay
information I2t on
Isd
˙Pre-Trip Alarm tsd
- Prevent unnecessary overload trip by
setting according to rated current (In) I2t off Ii
˙Field Test
- Simulation of long time, short time,
instantaneous
˙RS-485 Communication/Modbus-RTU

Protection Functions

In = Ict×… (0.5 ~ 1.0) ✽1 % Unit or 1 Unit


Current Setting (A)
Ir = In×… 0.7 0.8 0.9 1 1.05 1.1 1.15 1.2 1.25 Non
LTD Protection Time Delay (sec) tr @ (1.05×Ir) 20 30 40 50 60 70 80 100 120
Accuracy:± 15 % or tr @ (1.2×Ir) 10 15 20 25 30 35 40 50 60
Below 100 ms tr @ (3×Ir) 0.99 1.49 1.99 2.48 2.98 3.48 3.97 4.97 5.96
Current Setting (A)
Isd = In×… 1 1.5 2 2.5 3 3.5 4 4.5 5 Non
Accuracy:± 15 %
I2t Off 0.05 0.1 0.2 0.3 0.4 0.5
STD Protection tsd
Time Delay (sec) I2t On 0.05 0.1 0.2 0.3 0.4 0.5
@ 5×In Min. Trip Time (ms) 20 80 160 260 360 460
(I2t Off)
Max. Trip Time (ms) 80 140 240 340 440 540
Instantaneous Current Setting (A) Ii = In×… 2 3 4 6 8 10 12 15 Non
Protection Tripping Time Below 50 ms
Current Setting (A)
Ip = In×… 0.7 0.75 0.8 0.85 0.9 0.95 1 1.05 1.1 Non
Pre-Alarm Accuracy:± 15 %
Time Delay (sec) tp @ (lp×1.2) 1 5 10 15 20 25 30 35 40
Air Circuit Breakers 27

VCB
GPR-SP (59, 69)
˙Overload Protection ˙RS-485 Communication/Modbus-RTU
- Long time delay ˙Need to Connect Voltage Module for
˙Short Circuit Protection Voltage Measurement
- Short time delay, instantaneous trip ˙3a DO (Digital Output)
- l²t On/Off optional (for STD) - Contact specification
˙Neutral Wire Protection
- 3 Pole:No protection

ACB
- 4 Pole:Non, 50 %, 100 % (× Ir, Isd, Ii) Nominal Switching 5A
Capacity (Resistive Load) 277 VAC
˙Over-Voltage/Under-Voltage/Imbalance
Max. Switching Power
Protection (Resistive Load)
1,385 VA
Rating
˙Measurement and Display Max. Switching Voltage 277 VAC
- 3 Phase current/voltage/power/power Max. Switching Current 5A
factor/power quantity/phase/demand Max. Switching Capacity 100 mA
˙Realization of Protective Coordination by (Reference Value) 5 VDC

ZSI (Zone Selective Interlocking)


˙Protection Features
˙Fault Recording
- Records up to 256 fault information
on fault type, fault phase, fault value,
Ir
occurrence time of fault
IP
˙Event Recording tr

MCCB
- Records up to 200 events of devices,
Tp
records changes in protection trip relay
I2t on
information Isd
˙Pre-Trip Alarm tsd
- Prevent unnecessary overload trip by
setting according to rated current (In) I2t off Ii

˙Field Test
- Simulation of long time, short time,
instantaneous

Protection Functions

In = Ict×… 0.5 0.63 0.7 0.8 0.9 1


Current Setting (A)
Ir = In×… 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1 Non MS
STD Protection Time Delay (sec) tr @ (1.05×Ir) 10.4 26.1 41.7 52 104 208 312 417 521 626
Accuracy:± 15 % or tr @ (1.2×Ir) 0.5 1.25 2 2.5 5 10 15 20 25 30
Below 100 ms tr @ (3×Ir) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
Current Setting (A)
Isd = In×… 1 1.5 2 2.5 3 4 6 8 10 Non
Accuracy:± 15 %
I t Off
2
0.05 0.1 0.2 0.3 0.4 0.5
STD Protection tsd
Time Delay (sec) I2t On 0.05 0.1 0.2 0.3 0.4 0.5
@ 5×In Min. Trip Time (ms) 20 80 160 260 360 460
(I2t Off)
Max. Trip Time (ms) 80 140 240 340 440 540
Instantaneous Current Setting (A) Ii = In×… 2 3 4 6 8 10 12 15 Non
Protection Tripping Time Below 50 ms
Current Setting (A)
Ip = In×… 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 Non
RELAY

Pre-Alarm Accuracy:± 15 %
Time Delay (sec) tp @ (lp×1.2) 5 10 15 20 40 60 80 120 160
28 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
Operation Characteristics

Long Time Delay (LTD)


Standard Current Setting
˙L Type
- The scale marks the magnification of [In].
- The setting range of current is a 10-step method of Non, 0.8, 0.83, 0.85, 0.88, 0.9, 0.93,
0.95, 0.98 and 1.0×[In].
- No protection in case the [Ir] is set as [Non].
- The breaker does not trip below 105 % of [Ir] and trips at 120 % of [Ir] and above.
t ˙S Type t
Ir - The setting range of current is a 10-step method of Non, 0.7, 0.8, 0.9, 1.0, 1.05, 1.1,
tr 1.15, 1.2, 1.25×[In].
- The breaker trips at 100 % of [Ir] setting value and above.
Ig2t on

Time Delay Setting Ig2t off


Ig
˙L Type
Tg
- The scale is the second of operating time based on 600 %×[Ir] with inverse time
I I
operation.
-T
 he setting range of current is a 10-step method of 0.5, 1.25, 2, 2.5, 5, 10, 15, 20, 25, 30 sec.
- The breaker trips at ±15 % of setting time.
t ˙S Type t
- The setting range is a 9-step method of 10, 15, 20, 25, 30, 35, 40, 50, 60 sec.
- The scale is the second of operating time based on 120 %×[Ir] with inverse time
t operation. t
I2t on
Ir
tr I2t off I∆ n
Isd
Short Time Delay T(STD)
sd
Ig2t on
Standard Current Setting ∆T
I Ig2t off I
˙L Type Ig
- The scale marks the magnification of [In].
Tg
- The setting range of current is a 10-step method of Non, 1, 1.5, 2, 2.5, 3, 4, 6, 8, 10×[In].
I I
˙S Type
t - The scale marks thetmagnification of [In].
- The setting range of current is a 10-step method of Non, 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5×[In].
t t
Time delay setting
˙L Type Tp (S type)
I2t on - The marking indicatesIthe
p
relay operation based on the time of 110 % of [lsd] in msec
with definite time operation.
I2i t off I∆
Isd - The setting range is a 6-stepTmethod
p n of 50, 100, 200, 300, 400, 500 msec.
Tsd I I of l²t on setting.
- 1,000 % of inverse time curve is applied in case
˙S Type ∆T
I I
- The marking indicates the relay operation based on the time of 110 % of [lsd] in msec
with definite time operation.
- The setting range is a 6-step method of 50, 100, 200, 300, 400, 500 msec.
- 500 % of inverse time curve is applied in case of l²t on setting.
t t

Tp (S type)
Ip
Ir
tr

Ig2t on
Air Circuit Breakers 29
Ig2t off
Ig

Tg
I I

VCB
t t

I2t on
Instantaneous (INST)
I2t off I∆ n
Isd Standard Current Setting
Tsd - The scale marks the magnification of [In].
- The setting range of current is ∆Ta 9-step method of Non, 2, 3, 4, 6, 8, 10, 12, 15×[In].
I I
- No protection in case [Ii] is set as [Non], the protection does not function.

Time Delay Setting


- Total breaking time is below 50 ms.

ACB
t t

Tp (S type)
Ip

Ii
Tp
I I

MCCB
Ground Fault Trip (GFT)
Standard Current Setting
˙L Type
- The numbers indicate scale for the 1 st currnet of OCR [Ict].
- The setting range of current is a 10-step method of Non, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7,
0.8, 1.0×[Ict].
MS
Time Delay Setting
t ˙L Type
- The marking indicates the relay operation based on the time of 120 % of [Ig] in msec
with definite time operation.
- The setting range is a 6-step method of 50, 100, 200, 300, 400, 500 msec.
Ig2t on
- It functions in case of 100 % lct of inverse time in case of lg²t on setting.
Ig2t off
Ig

Tg
I
RELAY

I∆ n
30 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
t
Operation Characteristics

Earth Leakege Trip (ELT) 2


Ig t on
Standard Current Setting
Ig2t off ˙GPR LAZ
Ig
- The scale marks the magnification of UPR rated primary current [ZCT].
Tg
- The setting range of current is a 9-step method of Non, 0.5, 1, 2, 3, 5, 10, 20, 30×[A].
I
˙GPR LAG
- The scale is based on 5 A ZCT at secondary.
- The setting range of current is a 7-step method of Non, 0.5, 0.8, 1, 2, 3, 5.
t
Time Delay Setting
t ˙L Type
- Once the primary value that has been set flows as much as the delayed time, it is set
as both alarm and trip mode.
I∆ n Ig2t on - The setting range of alarm is a 5-step method of 140, 230, 350, 800, 950 msec.
- The setting range of trip is a 5-step method of 60, 140, 230, 350, 800 msec.
Ig2t off
Ig ∆T
I
Tg
I

t
t

Tp (S type)
Pre-Trip Alram
Ip (PTA)
I∆ n
Standard Current Setting
Tp ˙L Type
∆T I
- The scale marks the magnification of [In] with inverse time operation.
I
- The setting range of current is a 10-step method of Non, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85,
0.9, 0.95, 1.0 of [In].
˙S Type
- The scale marks the magnification with regards to [Io] with inverse time operation.
t - The setting range of current is a 10-step method of Non, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95,
1.0, 1.05, 1.1×[Io].

Time Delay Setting


Tp (S type) ˙L Type
Ip - The marking indicates the relay operation based on the time of 100 % of [lp] in sec.
- The setting range of current is a 10-step method of 5, 10, 15, 20, 40, 60, 80, 120, 160,
Tp
200 sec.
I
˙S Type
- 9-step of 1, 5, 10, 15, 20, 25, 30, 35, 40 sec can be selected in 120 % of [lp] and has
operation characteristics at inverse time operation.
Air Circuit Breakers 31

VCB
Characteristic Curve

General Feeder

❶ Long Time Delay Current 4


Operating Time

3
Setting Range
Hour

1
❷ Short Time Delay Current 50
40
Setting Range 30
20

❸ Instantaneous Tripping 10
Minute

ACB
8
Current Setting Range 6
5
4
3
❹ Ground Fault Trip Current 2

Setting Range 1
50
40
❺ Pre-Trip Alarm Current
30
20
Setting Range
10
8
6
5
4
3
2

1
0.8
Second

0.6
0.5
0.4
500 ms 500 ms
0.3
0.2

0.1
0.08
0.06
0.05 50 ms 50 ms
0.04

MCCB
0.03
0.02

0.01
0.008
0.006
0.005
7
8
9
10

15
20

30
40
50
60
70
80
90
100

60
70
80
90
100
125
150
200
250
300
400
500
600
700
800
900
1,000

1,500
2,000
2,500
3,000

Percent for rated Primary Current of OCR [lct] Percent for rated Current [In]

Generator

❶ Long Time Delay Current 4


Operating Time

3
Setting Range
Hour

❷ Short Time Delay Current


1
50

MS
40
Setting Range 30
20

❸ Instantaneous Tripping 10
8
Minute

Current Setting Range 6


5
4
3
❹ Pre-Trip Alarm Current 2
Setting Range 1
50
40
30
20

10
8
6
5
4
3
2

1
0.8
Second

0.6
0.5 500 ms
0.4
0.3
RELAY

0.2

0.1
0.08
0.06 50 ms
0.05
0.04
0.03
0.02

0.01
0.008
0.006
0.005
7
8
9
10

15
20

30
40
50
60
70
80
90
100
125
150
200
250
300
400
500
600
700
800
900
1,000

1,500
2,000
2,500
3,000

Percent for rated Current [In]


32 Air Circuit Breakers

Accessories
Measurement
Dimension

46.6 Unit:mm
56.4
42

91.4
75
27.6
29.1

Voltage Module
GPR-LP/LH/SP Trip Relay has to be installed with a voltage module to measure the voltage.
Voltage Input Range:AC 69 ~ 690 V

Voltage Connection

Voltage Input Range:69 ~ 690 V


Busbar Connection HGN

※ The length of connecting cable of the voltage


module and ACB’s VR, VS, VT
shall be installed within 150 mm.

Connect with ACB Terminal


3P 3Wire

VR VS VT VN
A B C

VN GPR
VT
VS
VR

ACB Terminal

4P 4Wire / 3P 4Wire

VR VS VT VN
A B C N

VN GPR
VT
VS
VR

ACB Terminal
Air Circuit Breakers 33

VCB
Zone Selective Interlocking
Zone Selective Interlocking System
Zone selective interlocking function involves the breaker in the fault sector detecting malfunction for selective protection coordination.
The circuit breaker in the fault sector sends a lock signal to the back-up protection circuit breaker by force to delay the operation and the
circuit breaker in the fault sector operates instantaneously to enable selective protection coordination of the system.

Examples
˙First Fault Occurrence ˙Fault 2 Occurrence
In case fault 1 occurs in selective zone (Zone 3), ACB 3-2 In case a fault occurs at the lower end of ACB 2-1, the circuit

ACB
functions immediately and ACB 3-2 relay triggers a ZSI signal breaker in zone 3 region is unable to detect. Therefore, the relay
in ACB 2-1 relay to maintain a delay so that the circuit breaker of ACB 2-1 is unable to receive any signal from the lower end so,
does not function, preventing the expansion of fault region. immediately, ACB 2-1 functions, triggering a ZSI signal to ACB 1
to prevent the expansion of fault range.

MCCB
ACB 1
OUT
ZONE 1
IN

ACB 2-1 ACB 2-2


OUT
ZONE 2 Fault 2
IN

ACB 3-1 ACB 3-2 ACB 3-N


MS
ZONE 3 OUT OUT OUT
Fault 1
IN IN IN

ZSI Connection

※ ZSI connection wire’s maximum distance has to be constituted within 3 m.


ZSI function cannot be operated during self-power.
Upon the release of the product, ZSI function is not activated and the 2 terminals (31, 32) at the control power input area are short so please cut the wire before connection when
RELAY

using ZSI.
34 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
System Diagram

R S T N

ACB Trip
ACB

Display
(LCD, LED)
MHT
Trip
Rogowski Relay Operation
CT Measurement
Part Selection

PTA Contact
MCU
LTD Contact

External
Contact STD/INST Contact

GFT Contact
Power
CT Common Contact
Self Power
Trip Relay
ZSI Output +
ZSI Output -
ZSI
ZSI Input +
ZSI Input -

ZCT Eartth RS-485 +


Leakage COMM. RS-485 -

110V ~ SMPS TEST


220V Power Terminal

Communication Function

Modbus-RTU/RS-485 NFC Communication (Near Field Communication) * for Android™


˙Operation Mode:Differential ˙Various information related to the breaker’s faults (cause
˙Distance:Max. 1.2 km of fault, current waveform at fault etc.) can be received
˙Cable:RS-485 Shielded Twist 2-Pair Cable conveniently through smart phones by using NFC wireless
˙Baud Rate:9,600, 19,200, 38,400 bps communication technology’s Android application.
˙Transmission Method:Half-Duplex ˙Execute the application and receive the fault information by
˙Termination:110 Ω placing the smart phone’s NFC antenna at the contact position
indicated in the OCR.
˙You can search the CF Fault Reader in Google Play™ for the
application or download it for free by connecting to the QR
SCADA System
code on the right.
˙Up to 10 past faults worth of information is saved.
(However, as for current’s waveform information, only the
Modbus/RS-485
recent fault is saved.)
˙The information received can be sent to the e-mail through the
application.

※ Android and Google Play are registered


HG-ACB HG-MCCB HGMAP trademarks of Google Inc.
Air Circuit Breakers 35

VCB
Circuit Diagrams

GPR-LN

Over-Current
Main Circuit
Protective Device

NCT
k ℓ

ACB
R S T N 21 29 30

NCT NCT
R S T N L 1 2

Over-Current
Protective Device
GPR-LN
Rn Sn Tn Nn Ac MCR MCR
+ _ TN TP
CT4
CT3 TP

CT2

MCCB
MHT
CT1
TN

1a for MCR

Rn Sn Tn Nn 22

GPR-LA

Over-Current
Main Circuit
Protective Device
AC, DC 100-250 V S0-S2

Power
_
NCT +
k ℓ
MS
R S T N 21 23 29 30 19

R S T N L P NCT NCT
1 2 S2

Over-Current
Protective Device
GPR-LA
Rn Sn Tn Nn Ac S/I G/E ZI1 ZI2 ZO
1
ZO
2 COM COM RR+ RR-
MCR MCR
+ _ TN TP S 0
CT4
RELAY

CT3 TP

CT2 MHT
CT1
TN

1a for MCR

Rn Sn Tn Nn 22 24 26 31 32 33 34 35 36 5 6 20

_ _ _ _
+ + + +
IN OUT Communi- Remote
ZSI cation Reset
36 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
System Diagrams

GPR-LAG/LAZ
Over-Current
Main Circuit
Protective Device
AC, DC 100-250 V S0-S2

Power
External CT / ZCT
(Secondary : 5 A)(1,000 : 1) NCT _
+
k ℓ k ℓ

R S T N 21 23 27 28 29 30 19

R S T N L P ELT ELT NCT NCT


1 1 1 2
S2

Over-Current
Protective Device
GPR-LAG / LAZ
Rn Sn Tn Nn Ac S/I G/E ZI1 ZI2 ZO
1
ZO COM COMRR+ RR-
2
MCR MCR
+ _ TN TP S0
CT4
CT3 TP
CT2 MHT
CT1
TN

1a for MCR

Rn Sn Tn Nn 22 24 26 31 32 33 34 35 36 5 6 20

_ _ _ _
+ + + +
IN OUT Communi- Remote
ZSI cation Reset

GPR-LP/LH
Over-Current
Main Circuit
Protective Device
AC, DC 100-250 V S0-S2
3Ø3W/3Ø4W
Power
VM _
NCT +
k ℓ

R S T N 21 23 29 30 VR VS VT VN 19

NCT NCT S2
R S T N L P 1 2 VR VS VT VN

Over-Current
Protective Device
GPR-LP / LH
ZI ZI ZO ZO MCR MCR
Rn Sn Tn Nn Ac S/I G/E 1 2 1 2 COM COM RR+ RR- + _ TN TP S0
CT4
CT3 TP

CT2 MHT
CT1
TN

1a for MCR

Rn Sn Tn Nn 22 24 26 31 32 33 34 35 36 5 6 20

_ _ _ _
+ + + +
IN OUT Communi- Remote
ZSI cation Reset
Air Circuit Breakers 37

VCB
GPR-SN

Over-Current
Main Circuit
Protective Device

R S T 21

ACB
R S T N L

Over-Current
Protective Device
GPR-SN
Rn Sn Tn Nn Ac MCR MCR
+ _ TN TP

CT3 TP

CT2 MHT
CT1

MCCB
TN

1a for MCR

Rn Sn Tn 22

GPR-SA
Over-Current
Main Circuit
Protective Device
AC, DC 100-250 V S0-S2

Power
_
+

MS
R S T 21 23 19

R S T N L P S2

Over-Current
Protective Device
GPR-SA
ZI ZI ZO ZO MCR MCR TN TP S0
Rn Sn Tn Nn Ac S/I G/E 1 2 1 2 COM COM RR+ RR- + _

CT3 TP
RELAY

CT2 MHT
CT1
TN

1a for MCR

Rn Sn Tn 22 24 26 31 32 33 34 35 36 5 6 20

_ _ _ _
+ + + +
IN OUT Communi- Remote
ZSI cation Reset
38 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
System Diagrams

GPR-SP
Over-Current
Main Circuit
Protective Device
AC, DC 100-250 V S0-S2
3Ø3W/3Ø4W
Power
VM _
+

R S T 21 23 VR VS VT 19

R S T N L P VR VS VT S2

Over-Current
Protective Device
GPR-SP
ZI ZO ZO
Rn Sn Tn Nn Ac S/I G/E 1 ZI2 1 2 COM COM RR+ RR- MCR MCR
+ _ TN TP S0

CT3 TP
CT2 MHT
CT1
TN

1a for MCR

Rn Sn Tn 22 24 26 31 32 33 34 35 36 5 6 20

_ _ _ _
+ + + +
IN OUT Communi- Remote
ZSI cation Reset

※ In case of No. 52 62 (GPR-LAG) 53-63 (GPR-LAZ), CT connecting wire 27, 28 must be within 5 m.
The connecting wire of Remote Reset (RR) No. 5 No. 6 circuit must be within 5 m.
Air Circuit Breakers 39

VCB
Time Chart for LTD Inverse Time (General Feeder)

LTD Time Setting (sec)


Tr
Item
x Ir
0.5 1.25 2 2.5 5 10 15 20 25 30
115 25.05 62.62 100.19 125.23 250.47 500.93 751.40 1,001.87 1,252.34 1,502.80
120 21.04 52.61 84.17 105.22 210.43 420.87 631.30 841.74 1,052.17 1,262.61
125 18.13 45.33 72.53 90.67 181.33 362.66 543.99 725.32 906.66 1,087.99
130 15.90 39.75 63.60 79.50 158.99 317.99 476.98 635.97 794.96 953.96
135 14.12 35.30 56.48 70.61 141.21 282.42 423.64 564.85 706.06 847.27
140 12.67 31.67 50.67 63.34 126.69 253.37 380.06 506.74 633.43 760.11
145 11.46 28.64 45.83 57.29 114.58 229.15 343.73 458.31 572.88 687.46

ACB
150 10.43 26.08 41.73 52.16 104.33 208.65 312.98 417.30 521.63 625.95
155 9.55 23.88 38.21 47.77 95.53 191.07 286.60 382.13 477.67 573.20
160 8.79 21.98 35.17 43.96 87.91 175.83 263.74 351.65 439.57 527.48
165 8.12 20.31 32.50 40.62 81.25 162.50 243.75 325.00 406.25 487.50
170 7.54 18.84 30.15 37.69 75.38 150.75 226.13 301.50 376.88 452.25
175 7.02 17.54 28.07 35.08 70.16 140.33 210.49 280.65 350.82 420.98
180 6.55 16.38 26.20 32.76 65.51 131.02 196.53 262.04 327.55 393.06
185 6.13 15.33 24.53 30.67 61.33 122.67 184.00 245.34 306.67 368.01
190 5.76 14.39 23.03 28.78 57.57 115.14 172.71 230.28 287.85 345.42
195 5.42 13.54 21.66 27.08 54.16 108.32 162.48 216.64 270.80 324.96
200 5.11 12.77 20.42 25.53 51.06 102.12 153.18 204.24 255.30 306.36
205 4.82 12.06 19.29 24.12 48.23 96.46 144.70 192.93 241.16 289.39
210 4.56 11.41 18.26 22.82 45.64 91.29 136.93 182.57 228.22 273.86

MCCB
215 4.33 10.82 17.31 21.63 43.27 86.53 129.80 173.07 216.33 259.60
220 4.11 10.27 16.43 20.54 41.08 82.16 123.23 164.31 205.39 246.47
225 3.91 9.76 15.62 19.53 39.06 78.12 117.18 156.23 195.29 234.35
230 3.72 9.30 14.88 18.59 37.19 74.38 111.57 148.76 185.95 223.14
235 3.55 8.86 14.18 17.73 35.46 70.91 106.37 141.82 177.28 212.74

Overload 240 3.38 8.46 13.54 16.92 33.85 67.69 101.54 135.38 169.23 203.07
Rate 245 3.23 8.09 12.94 16.17 32.35 64.69 97.04 129.38 161.73 194.07
(%) 250 3.09 7.74 12.38 15.47 30.95 61.89 92.84 123.78 154.73 185.67
255 2.96 7.41 11.86 14.82 29.64 59.28 88.91 118.55 148.19 177.83
260 2.84 7.10 11.37 14.21 28.41 56.83 85.24 113.65 142.07 170.48
265 2.73 6.82 10.91 13.63 27.27 54.53 81.80 109.06 136.33 163.59
270 2.62 6.55 10.47 13.09 26.19 52.37 78.56 104.75 130.94 157.12
275 2.52 6.29 10.07 12.59 25.17 50.35 75.52 100.69 125.87 151.04
280 2.42 6.05 9.69 12.11 24.22 48.44 72.66 96.87 121.09 145.31
285 2.33 5.83 9.33 11.66 23.32 46.64 69.95 93.27 116.59 139.91
MS
290 2.25 5.62 8.99 11.23 22.47 44.94 67.41 89.87 112.34 134.81
295 2.17 5.42 8.67 10.83 21.67 43.33 65.00 86.66 108.33 129.99
300 2.09 5.23 8.36 10.45 20.91 41.81 62.72 83.62 104.53 125.43
305 2.02 5.05 8.07 10.09 20.19 40.37 60.56 80.74 100.93 121.11
310 1.95 4.88 7.80 9.75 19.50 39.00 58.51 78.01 97.51 117.01
315 1.89 4.71 7.54 9.43 18.85 37.71 56.56 75.42 94.27 113.13
320 1.82 4.56 7.30 9.12 18.24 36.48 54.72 72.95 91.19 109.43
325 1.77 4.41 7.06 8.83 17.65 35.31 52.96 70.61 88.27 105.92
330 1.71 4.27 6.84 8.55 17.10 34.19 51.29 68.38 85.48 102.57
335 1.66 4.14 6.63 8.28 16.56 33.13 49.69 66.26 82.82 99.39
340 1.61 4.01 6.42 8.03 16.06 32.12 48.18 64.23 80.29 96.35
RELAY

345 1.56 3.89 6.23 7.79 15.58 31.15 46.73 62.30 77.88 93.45
350 1.51 3.78 6.05 7.56 15.11 30.23 45.34 60.46 75.57 90.69
355 1.47 3.67 5.87 7.34 14.67 29.35 44.02 58.70 73.37 88.04
360 1.43 3.56 5.70 7.13 14.25 28.50 42.76 57.01 71.26 85.51
365 1.38 3.46 5.54 6.92 13.85 27.70 41.55 55.40 69.24 83.09
370 1.35 3.37 5.39 6.73 13.46 26.93 40.39 53.85 67.31 80.78
375 1.31 3.27 5.24 6.55 13.09 26.19 39.28 52.37 65.46 78.56
40 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
Time Chart for LTD Inverse Time (General Feeder)

LTD Time Setting (sec)


Tr
Item
x Ir
0.5 1.25 2 2.5 5 10 15 20 25 30
380 1.27 3.18 5.10 6.37 12.74 25.48 38.21 50.95 63.69 76.43
385 1.24 3.10 4.96 6.20 12.40 24.79 37.19 49.59 61.99 74.38
390 1.21 3.02 4.83 6.04 12.07 24.14 36.21 48.28 60.35 72.42
395 1.18 2.94 4.70 5.88 11.76 23.51 35.27 47.03 58.78 70.54
400 1.15 2.86 4.58 5.73 11.45 22.91 34.36 45.82 57.27 68.73
405 1.12 2.79 4.47 5.58 11.16 22.33 33.49 44.66 55.82 66.99
410 1.09 2.72 4.35 5.44 10.89 21.77 32.66 43.54 54.43 65.31
415 1.06 2.65 4.25 5.31 10.62 21.23 31.85 42.47 53.08 63.70
420 1.04 2.59 4.14 5.18 10.36 20.72 31.07 41.43 51.79 62.15
425 1.01 2.53 4.04 5.05 10.11 20.22 30.33 40.44 50.54 60.65
430 0.99 2.47 3.95 4.93 9.87 19.74 29.61 39.47 49.34 59.21
435 0.96 2.41 3.85 4.82 9.64 19.27 28.91 38.55 48.18 57.82
440 0.94 2.35 3.77 4.71 9.41 18.83 28.24 37.65 47.07 56.48
445 0.92 2.30 3.68 4.60 9.20 18.39 27.59 36.79 45.99 55.18
450 0.90 2.25 3.60 4.49 8.99 17.98 26.97 35.95 44.94 53.93
455 0.88 2.20 3.51 4.39 8.79 17.57 26.36 35.15 43.94 52.72
460 0.86 2.15 3.44 4.30 8.59 17.19 25.78 34.37 42.96 51.56
465 0.84 2.10 3.36 4.20 8.40 16.81 25.21 33.62 42.02 50.43
470 0.82 2.06 3.29 4.11 8.22 16.44 24.67 32.89 41.11 49.33
475 0.80 2.01 3.22 4.02 8.05 16.09 24.14 32.18 40.23 48.28
480 0.79 1.97 3.15 3.94 7.88 15.75 23.63 31.50 39.38 47.25
485 0.77 1.93 3.08 3.86 7.71 15.42 23.13 30.84 38.55 46.26
490 0.76 1.89 3.02 3.78 7.55 15.10 22.65 30.20 37.75 45.30
495 0.74 1.85 2.96 3.70 7.40 14.79 22.19 29.58 36.98 44.37
500 0.72 1.81 2.90 3.62 7.25 14.49 21.74 28.98 36.23 43.47

Overload 505 0.71 1.77 2.84 3.55 7.10 14.20 21.30 28.40 35.50 42.60
Rate 510 0.70 1.74 2.78 3.48 6.96 13.92 20.88 27.83 34.79 41.75
(%) 515 0.68 1.71 2.73 3.41 6.82 13.64 20.46 27.29 34.11 40.93
520 0.67 1.67 2.68 3.34 6.69 13.38 20.07 26.75 33.44 40.13
525 0.66 1.64 2.62 3.28 6.56 13.12 19.68 26.24 32.80 39.36
530 0.64 1.61 2.57 3.22 6.43 12.87 19.30 25.74 32.17 38.60
535 0.63 1.58 2.52 3.16 6.31 12.62 18.94 25.25 31.56 37.87
540 0.62 1.55 2.48 3.10 6.19 12.39 18.58 24.77 30.97 37.16
545 0.61 1.52 2.43 3.04 6.08 12.16 18.24 24.31 30.39 36.47
550 0.60 1.49 2.39 2.98 5.97 11.93 17.90 23.87 29.83 35.80
555 0.59 1.46 2.34 2.93 5.86 11.72 17.57 23.43 29.29 35.15
560 0.58 1.44 2.30 2.88 5.75 11.50 17.26 23.01 28.76 34.51
565 0.56 1.41 2.26 2.82 5.65 11.30 16.95 22.60 28.24 33.89
570 0.55 1.39 2.22 2.77 5.55 11.10 16.65 22.19 27.74 33.29
575 0.55 1.36 2.18 2.73 5.45 10.90 16.35 21.80 27.26 32.71
580 0.54 1.34 2.14 2.68 5.36 10.71 16.07 21.42 26.78 32.14
585 0.53 1.32 2.11 2.63 5.26 10.53 15.79 21.05 26.32 31.58
590 0.52 1.29 2.07 2.59 5.17 10.35 15.52 20.69 25.87 31.04
595 0.51 1.27 2.03 2.54 5.09 10.17 15.26 20.34 25.43 30.51
600 0.50 1.25 2.00 2.50 5.00 10.00 15.00 20.00 25.00 30.00
605 0.49 1.23 1.97 2.46 4.92 9.83 14.75 19.67 24.58 29.50
610 0.48 1.21 1.93 2.42 4.84 9.67 14.51 19.34 24.18 29.01
615 0.48 1.19 1.90 2.38 4.76 9.51 14.27 19.02 23.78 28.53
620 0.47 1.17 1.87 2.34 4.68 9.36 14.04 18.71 23.39 28.07
625 0.46 1.15 1.84 2.30 4.60 9.21 13.81 18.41 23.01 27.62
630 0.45 1.13 1.81 2.26 4.53 9.06 13.59 18.12 22.65 27.17
635 0.45 1.11 1.78 2.23 4.46 8.91 13.37 17.83 22.29 26.74
640 0.44 1.10 1.75 2.19 4.39 8.77 13.16 17.55 21.93 26.32
Air Circuit Breakers 41

VCB
LTD Time Setting (sec)
Tr
Item
x Ir
0.5 1.25 2 2.5 5 10 15 20 25 30
645 0.43 1.08 1.73 2.16 4.32 8.64 12.96 17.27 21.59 25.91
650 0.43 1.06 1.70 2.13 4.25 8.50 12.75 17.01 21.26 25.51
655 0.42 1.05 1.67 2.09 4.19 8.37 12.56 16.74 20.93 25.12
660 0.41 1.03 1.65 2.06 4.12 8.24 12.37 16.49 20.61 24.73
665 0.41 1.01 1.62 2.03 4.06 8.12 12.18 16.24 20.30 24.36
670 0.40 1.00 1.60 2.00 4.00 8.00 12.00 15.99 19.99 23.99
675 0.39 0.98 1.58 1.97 3.94 7.88 11.82 15.76 19.69 23.63

ACB
680 0.39 0.97 1.55 1.94 3.88 7.76 11.64 15.52 19.40 23.28
685 0.38 0.96 1.53 1.91 3.82 7.65 11.47 15.29 19.12 22.94
690 0.38 0.94 1.51 1.88 3.77 7.54 11.30 15.07 18.84 22.61
695 0.37 0.93 1.49 1.86 3.71 7.43 11.14 14.85 18.57 22.28
700 0.37 0.91 1.46 1.83 3.66 7.32 10.98 14.64 18.30 21.96
705 0.36 0.90 1.44 1.80 3.61 7.21 10.82 14.43 18.04 21.64
710 0.36 0.89 1.42 1.78 3.56 7.11 10.67 14.23 17.78 21.34
715 0.35 0.88 1.40 1.75 3.51 7.01 10.52 14.02 17.53 21.04
720 0.35 0.86 1.38 1.73 3.46 6.91 10.37 13.83 17.29 20.74
725 0.34 0.85 1.36 1.70 3.41 6.82 10.23 13.64 17.05 20.46
730 0.34 0.84 1.34 1.68 3.36 6.72 10.09 13.45 16.81 20.17
735 0.33 0.83 1.33 1.66 3.32 6.63 9.95 13.26 16.58 19.90
740 0.33 0.82 1.31 1.64 3.27 6.54 9.81 13.08 16.36 19.63

MCCB
745 0.32 0.81 1.29 1.61 3.23 6.45 9.68 12.91 16.14 19.36
750 0.32 0.80 1.27 1.59 3.18 6.37 9.55 12.73 15.92 19.10
755 0.31 0.79 1.26 1.57 3.14 6.28 9.42 12.57 15.71 18.85
760 0.31 0.77 1.24 1.55 3.10 6.20 9.30 12.40 15.50 18.60
765 0.31 0.76 1.22 1.53 3.06 6.12 9.18 12.24 15.30 18.35

Overload 770 0.30 0.75 1.21 1.51 3.02 6.04 9.06 12.08 15.10 18.11
Rate 775 0.30 0.74 1.19 1.49 2.98 5.96 8.94 11.92 14.90 17.88
(%) 780 0.29 0.74 1.18 1.47 2.94 5.88 8.82 11.77 14.71 17.65
785 0.29 0.73 1.16 1.45 2.90 5.81 8.71 11.62 14.52 17.42
790 0.29 0.72 1.15 1.43 2.87 5.73 8.60 11.47 14.33 17.20
795 0.28 0.71 1.13 1.42 2.83 5.66 8.49 11.32 14.15 16.98
800 0.28 0.70 1.12 1.40 2.80 5.59 8.39 11.18 13.98 16.77
805 0.28 0.69 1.10 1.38 2.76 5.52 8.28 11.04 13.80 16.56
810 0.27 0.68 1.09 1.36 2.73 5.45 8.18 10.90 13.63 16.36
815 0.27 0.67 1.08 1.35 2.69 5.38 8.08 10.77 13.46 16.15
MS
820 0.27 0.66 1.06 1.33 2.66 5.32 7.98 10.64 13.30 15.96
825 0.26 0.66 1.05 1.31 2.63 5.25 7.88 10.51 13.14 15.76
830 0.26 0.65 1.04 1.30 2.60 5.19 7.79 10.38 12.98 15.57
835 0.26 0.64 1.03 1.28 2.56 5.13 7.69 10.26 12.82 15.38
840 0.25 0.63 1.01 1.27 2.53 5.07 7.60 10.13 12.67 15.20
845 0.25 0.63 1.00 1.25 2.50 5.01 7.51 10.01 12.52 15.02
850 0.25 0.62 0.99 1.24 2.47 4.95 7.42 9.89 12.37 14.84
855 0.24 0.61 0.98 1.22 2.44 4.89 7.33 9.78 12.22 14.67
860 0.24 0.60 0.97 1.21 2.42 4.83 7.25 9.66 12.08 14.50
865 0.24 0.60 0.96 1.19 2.39 4.78 7.16 9.55 11.94 14.33
870 0.24 0.59 0.94 1.18 2.36 4.72 7.08 9.44 11.80 14.16
RELAY

875 0.23 0.58 0.93 1.17 2.33 4.67 7.00 9.33 11.67 14.00
880 0.23 0.58 0.92 1.15 2.31 4.61 6.92 9.23 11.53 13.84
885 0.23 0.57 0.91 1.14 2.28 4.56 6.84 9.12 11.40 13.68
890 0.23 0.56 0.90 1.13 2.25 4.51 6.76 9.02 11.27 13.53
895 0.22 0.56 0.89 1.11 2.23 4.46 6.69 8.92 11.15 13.38
900 0.22 0.55 0.88 1.10 2.20 4.41 6.61 8.82 11.02 13.23
905 0.22 0.55 0.87 1.09 2.18 4.36 6.54 8.72 10.90 13.08
42 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
Time Chart for LTD Inverse Time (General Feeder)

LTD Time Setting (sec)


Tr
Item
x Ir
0.5 1.25 2 2.5 5 10 15 20 25 30
910 0.22 0.54 0.86 1.08 2.16 4.31 6.47 8.63 10.78 12.94
915 0.21 0.53 0.85 1.07 2.13 4.27 6.40 8.53 10.66 12.80
920 0.21 0.53 0.84 1.05 2.11 4.22 6.33 8.44 10.55 12.66
925 0.21 0.52 0.83 1.04 2.09 4.17 6.26 8.35 10.43 12.52
930 0.21 0.52 0.83 1.03 2.06 4.13 6.19 8.26 10.32 12.38
935 0.20 0.51 0.82 1.02 2.04 4.08 6.13 8.17 10.21 12.25
940 0.20 0.51 0.81 1.01 2.02 4.04 6.06 8.08 10.10 12.12
945 0.20 0.50 0.80 1.00 2.00 4.00 6.00 7.99 9.99 11.99

Overload 950 0.20 0.49 0.79 0.99 1.98 3.96 5.93 7.91 9.89 11.87
Rate 955 0.20 0.49 0.78 0.98 1.96 3.91 5.87 7.83 9.78 11.74
(%) 960 0.19 0.48 0.77 0.97 1.94 3.87 5.81 7.75 9.68 11.62
965 0.19 0.48 0.77 0.96 1.92 3.83 5.75 7.67 9.58 11.50
970 0.19 0.47 0.76 0.95 1.90 3.79 5.69 7.59 9.48 11.38
975 0.19 0.47 0.75 0.94 1.88 3.75 5.63 7.51 9.38 11.26
980 0.19 0.46 0.74 0.93 1.86 3.72 5.57 7.43 9.29 11.15
985 0.18 0.46 0.74 0.92 1.84 3.68 5.52 7.36 9.19 11.03
990 0.18 0.46 0.73 0.91 1.82 3.64 5.46 7.28 9.10 10.92
995 0.18 0.45 0.72 0.90 1.80 3.60 5.41 7.21 9.01 10.81
1,000 0.18 0.45 0.71 0.89 1.78 3.57 5.35 7.14 8.92 10.70
Air Circuit Breakers 43

VCB
Time Chart for LTD Inverse Time (Generator)

LTD Time Setting (sec)


Tr
Item
x Ir
10 15 20 25 30 35 40 50 60
101 33.12 49.68 66.24 82.80 99.36 115.92 132.49 165.61 198.73
105 20.04 30.05 40.07 50.09 60.11 70.12 80.14 100.18 120.21
110 14.77 22.16 29.54 36.93 44.31 51.70 59.08 73.85 88.63
115 11.90 17.85 23.80 29.76 35.71 41.66 47.61 59.51 71.41
120 10.00 15.00 20.00 25.00 30.00 35.00 40.00 50.00 60.00
125 8.62 12.93 17.23 21.54 25.85 30.16 34.47 43.08 51.70
130 7.56 11.33 15.11 18.89 22.67 26.44 30.22 37.78 45.33

ACB
135 6.71 10.07 13.42 16.78 20.13 23.49 26.84 33.55 40.26
140 6.02 9.03 12.04 15.05 18.06 21.07 24.08 30.10 36.12
145 5.44 8.17 10.89 13.61 16.33 19.06 21.78 27.22 32.67
150 4.96 7.44 9.92 12.39 14.87 17.35 19.83 24.79 29.75
155 4.54 6.81 9.08 11.35 13.62 15.89 18.16 22.70 27.24
160 4.18 6.27 8.36 10.44 12.53 14.62 16.71 20.89 25.07
165 3.86 5.79 7.72 9.65 11.58 13.51 15.44 19.31 23.17
170 3.58 5.37 7.16 8.95 10.75 12.54 14.33 17.91 21.49
175 3.33 5.00 6.67 8.34 10.00 11.67 13.34 16.67 20.01
180 3.11 4.67 6.23 7.78 9.34 10.90 12.45 15.57 18.68
185 2.91 4.37 5.83 7.29 8.74 10.20 11.66 14.57 17.49
190 2.74 4.10 5.47 6.84 8.21 9.58 10.94 13.68 16.41
195 2.57 3.86 5.15 6.43 7.72 9.01 10.29 12.87 15.44

MCCB
200 2.43 3.64 4.85 6.07 7.28 8.49 9.71 12.13 14.56
205 2.29 3.44 4.58 5.73 6.88 8.02 9.17 11.46 13.75
210 2.17 3.25 4.34 5.42 6.51 7.59 8.68 10.85 13.01
215 2.06 3.08 4.11 5.14 6.17 7.20 8.22 10.28 12.34
220 1.95 2.93 3.90 4.88 5.86 6.83 7.81 9.76 11.71

Overload 225 1.86 2.78 3.71 4.64 5.57 6.50 7.42 9.28 11.14
Rate 230 1.77 2.65 3.53 4.42 5.30 6.19 7.07 8.84 10.60
(%) 235 1.68 2.53 3.37 4.21 5.05 5.90 6.74 8.42 10.11
240 1.61 2.41 3.22 4.02 4.83 5.63 6.43 8.04 9.65
245 1.54 2.31 3.07 3.84 4.61 5.38 6.15 7.69 9.22
250 1.47 2.21 2.94 3.68 4.41 5.15 5.88 7.35 8.82
255 1.41 2.11 2.82 3.52 4.23 4.93 5.63 7.04 8.45
260 1.35 2.03 2.70 3.38 4.05 4.73 5.40 6.75 8.10
265 1.30 1.94 2.59 3.24 3.89 4.53 5.18 6.48 7.77
270 1.24 1.87 2.49 3.11 3.73 4.36 4.98 6.22 7.47
MS
275 1.20 1.79 2.39 2.99 3.59 4.19 4.78 5.98 7.18
280 1.15 1.73 2.30 2.88 3.45 4.03 4.60 5.75 6.91
285 1.11 1.66 2.22 2.77 3.32 3.88 4.43 5.54 6.65
290 1.07 1.60 2.14 2.67 3.20 3.74 4.27 5.34 6.41
295 1.03 1.54 2.06 2.57 3.09 3.60 4.12 5.15 6.18
300 0.99 1.49 1.99 2.48 2.98 3.48 3.97 4.97 5.96
305 0.96 1.44 1.92 2.40 2.88 3.36 3.84 4.80 5.76
310 0.93 1.39 1.85 2.32 2.78 3.24 3.71 4.63 5.56
315 0.90 1.34 1.79 2.24 2.69 3.14 3.58 4.48 5.38
320 0.87 1.30 1.73 2.17 2.60 3.03 3.47 4.33 5.20
325 0.84 1.26 1.68 2.10 2.52 2.94 3.36 4.19 5.03
RELAY

330 0.81 1.22 1.62 2.03 2.44 2.84 3.25 4.06 4.87
335 0.79 1.18 1.57 1.97 2.36 2.76 3.15 3.94 4.72
340 0.76 1.14 1.53 1.91 2.29 2.67 3.05 3.82 4.58
345 0.74 1.11 1.48 1.85 2.22 2.59 2.96 3.70 4.44
350 0.72 1.08 1.44 1.80 2.15 2.51 2.87 3.59 4.31
355 0.70 1.05 1.39 1.74 2.09 2.44 2.79 3.49 4.18
360 0.68 1.02 1.35 1.69 2.03 2.37 2.71 3.39 4.06
44 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
Time Chart for LTD Inverse Time (Generator)

LTD Time Setting (sec)


Tr
Item
x Ir
10 15 20 25 30 35 40 50 60
365 0.66 0.99 1.32 1.65 1.97 2.30 2.63 3.29 3.95
370 0.64 0.96 1.28 1.60 1.92 2.24 2.56 3.20 3.84
375 0.62 0.93 1.24 1.56 1.87 2.18 2.49 3.11 3.73
380 0.61 0.91 1.21 1.51 1.82 2.12 2.42 3.03 3.63
385 0.59 0.88 1.18 1.47 1.77 2.06 2.36 2.95 3.53
390 0.57 0.86 1.15 1.43 1.72 2.01 2.29 2.87 3.44
395 0.56 0.84 1.12 1.40 1.68 1.96 2.23 2.79 3.35
400 0.54 0.82 1.09 1.36 1.63 1.91 2.18 2.72 3.27
405 0.53 0.80 1.06 1.33 1.59 1.86 2.12 2.65 3.18
410 0.52 0.78 1.03 1.29 1.55 1.81 2.07 2.59 3.10
415 0.50 0.76 1.01 1.26 1.51 1.77 2.02 2.52 3.03
420 0.49 0.74 0.98 1.23 1.48 1.72 1.97 2.46 2.95
425 0.48 0.72 0.96 1.20 1.44 1.68 1.92 2.40 2.88
430 0.47 0.70 0.94 1.17 1.41 1.64 1.88 2.34 2.81
435 0.46 0.69 0.92 1.14 1.37 1.60 1.83 2.29 2.75
440 0.45 0.67 0.89 1.12 1.34 1.57 1.79 2.24 2.68
445 0.44 0.66 0.87 1.09 1.31 1.53 1.75 2.19 2.62
450 0.43 0.64 0.85 1.07 1.28 1.50 1.71 2.14 2.56
455 0.42 0.63 0.84 1.04 1.25 1.46 1.67 2.09 2.51
460 0.41 0.61 0.82 1.02 1.22 1.43 1.63 2.04 2.45
465 0.40 0.60 0.80 1.00 1.20 1.40 1.60 2.00 2.40
470 0.39 0.59 0.78 0.98 1.17 1.37 1.56 1.95 2.34
475 0.38 0.57 0.76 0.96 1.15 1.34 1.53 1.91 2.29
480 0.37 0.56 0.75 0.94 1.12 1.31 1.50 1.87 2.25
485 0.37 0.55 0.73 0.92 1.10 1.28 1.47 1.83 2.20

Overload 490 0.36 0.54 0.72 0.90 1.08 1.26 1.44 1.79 2.15
Rate 495 0.35 0.53 0.70 0.88 1.05 1.23 1.41 1.76 2.11
(%) 500 0.34 0.52 0.69 0.86 1.03 1.21 1.38 1.72 2.07
505 0.34 0.51 0.67 0.84 1.01 1.18 1.35 1.69 2.02
510 0.33 0.50 0.66 0.83 0.99 1.16 1.32 1.65 1.98
515 0.32 0.49 0.65 0.81 0.97 1.13 1.30 1.62 1.94
520 0.32 0.48 0.64 0.79 0.95 1.11 1.27 1.59 1.91
525 0.31 0.47 0.62 0.78 0.94 1.09 1.25 1.56 1.87
530 0.31 0.46 0.61 0.76 0.92 1.07 1.22 1.53 1.83
535 0.30 0.45 0.60 0.75 0.90 1.05 1.20 1.50 1.80
540 0.29 0.44 0.59 0.74 0.88 1.03 1.18 1.47 1.77
545 0.29 0.43 0.58 0.72 0.87 1.01 1.16 1.44 1.73
550 0.28 0.43 0.57 0.71 0.85 0.99 1.13 1.42 1.70
555 0.28 0.42 0.56 0.70 0.84 0.97 1.11 1.39 1.67
560 0.27 0.41 0.55 0.68 0.82 0.96 1.09 1.37 1.64
565 0.27 0.40 0.54 0.67 0.81 0.94 1.07 1.34 1.61
570 0.26 0.40 0.53 0.66 0.79 0.92 1.05 1.32 1.58
575 0.26 0.39 0.52 0.65 0.78 0.91 1.04 1.30 1.55
580 0.25 0.38 0.51 0.64 0.76 0.89 1.02 1.27 1.53
585 0.25 0.38 0.50 0.63 0.75 0.88 1.00 1.25 1.50
590 0.25 0.37 0.49 0.61 0.74 0.86 0.98 1.23 1.48
595 0.24 0.36 0.48 0.60 0.73 0.85 0.97 1.21 1.45
600 0.24 0.36 0.48 0.59 0.71 0.83 0.95 1.19 1.43
605 0.23 0.35 0.47 0.58 0.70 0.82 0.93 1.17 1.40
610 0.23 0.34 0.46 0.57 0.69 0.80 0.92 1.15 1.38
615 0.23 0.34 0.45 0.56 0.68 0.79 0.90 1.13 1.36
620 0.22 0.33 0.44 0.56 0.67 0.78 0.89 1.11 1.33
625 0.22 0.33 0.44 0.55 0.66 0.77 0.87 1.09 1.31
Air Circuit Breakers 45

VCB
LTD Time Setting (sec)
Tr
Item
x Ir
10 15 20 25 30 35 40 50 60
630 0.22 0.32 0.43 0.54 0.65 0.75 0.86 1.08 1.29
635 0.21 0.32 0.42 0.53 0.64 0.74 0.85 1.06 1.27
640 0.21 0.31 0.42 0.52 0.63 0.73 0.83 1.04 1.25
645 0.21 0.31 0.41 0.51 0.62 0.72 0.82 1.03 1.23
650 0.20 0.30 0.40 0.51 0.61 0.71 0.81 1.01 1.21
655 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.99 1.19
660 0.20 0.29 0.39 0.49 0.59 0.69 0.78 0.98 1.18

ACB
665 0.19 0.29 0.39 0.48 0.58 0.68 0.77 0.96 1.16
670 0.19 0.29 0.38 0.48 0.57 0.67 0.76 0.95 1.14
675 0.19 0.28 0.37 0.47 0.56 0.66 0.75 0.94 1.12
680 0.18 0.28 0.37 0.46 0.55 0.65 0.74 0.92 1.11
685 0.18 0.27 0.36 0.45 0.55 0.64 0.73 0.91 1.09
690 0.18 0.27 0.36 0.45 0.54 0.63 0.72 0.90 1.07
695 0.18 0.26 0.35 0.44 0.53 0.62 0.71 0.88 1.06
700 0.17 0.26 0.35 0.43 0.52 0.61 0.70 0.87 1.04
705 0.17 0.26 0.34 0.43 0.51 0.60 0.69 0.86 1.03
710 0.17 0.25 0.34 0.42 0.51 0.59 0.68 0.84 1.01
715 0.17 0.25 0.33 0.42 0.50 0.58 0.67 0.83 1.00
720 0.16 0.25 0.33 0.41 0.49 0.58 0.66 0.82 0.99
725 0.16 0.24 0.32 0.41 0.49 0.57 0.65 0.81 0.97

MCCB
730 0.16 0.24 0.32 0.40 0.48 0.56 0.64 0.80 0.96
735 0.16 0.24 0.32 0.39 0.47 0.55 0.63 0.79 0.95
740 0.16 0.23 0.31 0.39 0.47 0.54 0.62 0.78 0.93
745 0.15 0.23 0.31 0.38 0.46 0.54 0.61 0.77 0.92
750 0.15 0.23 0.30 0.38 0.45 0.53 0.61 0.76 0.91

Overload 755 0.15 0.22 0.30 0.37 0.45 0.52 0.60 0.75 0.90
Rate 760 0.15 0.22 0.29 0.37 0.44 0.52 0.59 0.74 0.88
(%) 765 0.15 0.22 0.29 0.36 0.44 0.51 0.58 0.73 0.87
770 0.14 0.22 0.29 0.36 0.43 0.50 0.57 0.72 0.86
775 0.14 0.21 0.28 0.35 0.42 0.50 0.57 0.71 0.85
780 0.14 0.21 0.28 0.35 0.42 0.49 0.56 0.70 0.84
785 0.14 0.21 0.28 0.34 0.41 0.48 0.55 0.69 0.83
790 0.14 0.20 0.27 0.34 0.41 0.48 0.54 0.68 0.82
795 0.13 0.20 0.27 0.34 0.40 0.47 0.54 0.67 0.81
800 0.13 0.20 0.27 0.33 0.40 0.46 0.53 0.66 0.80
MS
805 0.13 0.20 0.26 0.33 0.39 0.46 0.52 0.66 0.79
810 0.13 0.19 0.26 0.32 0.39 0.45 0.52 0.65 0.78
815 0.13 0.19 0.26 0.32 0.38 0.45 0.51 0.64 0.77
820 0.13 0.19 0.25 0.32 0.38 0.44 0.51 0.63 0.76
825 0.12 0.19 0.25 0.31 0.37 0.44 0.50 0.62 0.75
830 0.12 0.18 0.25 0.31 0.37 0.43 0.49 0.62 0.74
835 0.12 0.18 0.24 0.30 0.37 0.43 0.49 0.61 0.73
840 0.12 0.18 0.24 0.30 0.36 0.42 0.48 0.60 0.72
845 0.12 0.18 0.24 0.30 0.36 0.42 0.48 0.59 0.71
850 0.12 0.18 0.24 0.29 0.35 0.41 0.47 0.59 0.71
855 0.12 0.17 0.23 0.29 0.35 0.41 0.46 0.58 0.70
RELAY

860 0.11 0.17 0.23 0.29 0.34 0.40 0.46 0.57 0.69
865 0.11 0.17 0.23 0.28 0.34 0.40 0.45 0.57 0.68
870 0.11 0.17 0.22 0.28 0.34 0.39 0.45 0.56 0.67
875 0.11 0.17 0.22 0.28 0.33 0.39 0.44 0.55 0.67
880 0.11 0.16 0.22 0.27 0.33 0.38 0.44 0.55 0.66
885 0.11 0.16 0.22 0.27 0.33 0.38 0.43 0.54 0.65
890 0.11 0.16 0.21 0.27 0.32 0.38 0.43 0.54 0.64
46 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
Time Chart for LTD Inverse Time (Generator)

LTD Time Setting (sec)


Tr
Item
x Ir
10 15 20 25 30 35 40 50 60
895 0.11 0.16 0.21 0.26 0.32 0.37 0.42 0.52 0.64
900 0.10 0.16 0.21 0.26 0.31 0.37 0.42 0.52 0.63
905 0.10 0.16 0.21 0.26 0.31 0.36 0.41 0.52 0.62
910 0.10 0.15 0.20 0.26 0.31 0.36 0.41 0.51 0.61
915 0.10 0.15 0.20 0.25 0.30 0.35 0.41 0.51 0.61
920 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.50 0.60
925 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.50 0.59
930 0.10 0.15 0.20 0.25 0.29 0.34 0.39 0.49 0.59

Overload 935 0.10 0.15 0.19 0.24 0.29 0.34 0.39 0.49 0.58
Rate 940 0.10 0.14 0.19 0.24 0.29 0.34 0.38 0.48 0.58
(%) 945 0.09 0.14 0.19 0.24 0.28 0.33 0.38 0.47 0.57
950 0.09 0.14 0.19 0.23 0.28 0.33 0.38 0.47 0.56
955 0.09 0.14 0.19 0.23 0.28 0.33 0.37 0.46 0.56
960 0.09 0.14 0.18 0.23 0.28 0.32 0.37 0.46 0.55
965 0.09 0.14 0.18 0.23 0.27 0.32 0.36 0.46 0.55
970 0.09 0.14 0.18 0.23 0.27 0.32 0.36 0.45 0.54
975 0.09 0.13 0.18 0.22 0.27 0.31 0.36 0.45 0.54
980 0.09 0.13 0.18 0.22 0.26 0.31 0.35 0.44 0.53
985 0.09 0.13 0.17 0.22 0.26 0.31 0.35 0.44 0.52
Air Circuit Breakers 47

VCB
Time Chart for STD Inverse Time (General Feeder)

Tsd STD Time Setting (ms) Inland Type Tsd STD Time Setting (ms) Inland Type
Item Item
x In 50 100 200 300 400 500 x In 50 100 200 300 400 500
100 5,000 10,000 20,000 30,000 40,000 50,000 630 126 252 504 756 1,008 12,60
110 4,132 8,264 16,529 24,793 33,058 41,322 640 122 244 488 732 977 1,221
120 3,472 6,944 13,889 20,833 27,778 34,722 650 118 237 473 710 947 1,183
130 2,959 5,917 11,834 17,751 23,669 29,586 660 115 230 459 689 918 1,148
140 2,551 5,102 10,204 15,306 20,408 25,510 670 111 223 446 668 891 1,114
150 2,222 4,444 8,889 13,333 17,778 22,222 680 108 216 433 649 865 1,081
160 1,953 3,906 7,813 11,719 15,625 19,531 690 105 210 420 630 840 1,050

ACB
170 1,730 3,460 6,920 10,381 13,841 17,301 700 102 204 408 612 816 1,020
180 1,543 3,086 6,173 9,259 12,346 15,432 710 99 198 397 595 793 992
190 1,385 2,770 5,540 8,310 11,080 13,850 720 96 193 386 579 772 965
200 1,250 2,500 5,000 7,500 10,000 12,500 730 94 188 375 563 751 938
210 1,134 2,268 4,535 6,803 9,070 11,338 740 91 183 365 548 730 913
220 1,033 2,066 4,132 6,198 8,264 10,331 750 89 178 356 533 711 889
230 945 1,890 3,781 5,671 7,561 9,452 760 87 173 346 519 693 866
240 868 1,736 3,472 5,208 6,944 8,681 770 84 169 337 506 675 843
250 800 1,600 3,200 4,800 6,400 8,000 780 82 164 329 493 657 822
260 740 1,479 2,959 4,438 5,917 7,396 790 80 160 320 481 641 801
270 686 1,372 2,743 4,115 5,487 6,859 800 78 156 313 469 625 781
280 638 1,276 2,551 3,827 5,102 6,378 Overload 810 76 152 305 457 610 762
Rate
290 595 1,189 2,378 3,567 4,756 5,945 820 74 149 297 446 595 744

MCCB
(%)
300 556 1,111 2,222 3,333 4,444 5,556 830 73 145 290 435 581 726
310 520 1,041 2,081 3,122 4,162 5,203 840 71 142 283 425 567 709
320 488 977 1,953 2,930 3,906 4,883 850 69 138 277 415 554 692
330 459 918 1,837 2,755 3,673 4,591 860 68 135 270 406 541 676
340 433 865 1,730 2,595 3,460 4,325 870 66 132 264 396 528 661

Overload 350 408 816 1,633 2,449 3,265 4,082 880 65 129 258 387 517 646
Rate 360 386 772 1,543 2,315 3,086 3,858 890 63 126 252 379 505 631
(%) 370 365 730 1,461 2,191 2,922 3,652 900 62 123 247 370 494 617
380 346 693 1,385 2,078 2,770 3,463 910 60 121 242 362 483 604
390 329 657 1,315 1,972 2,630 3,287 920 59 118 236 354 473 591
400 313 625 1,250 1,875 2,500 3,125 930 58 116 231 347 462 578
410 297 595 1,190 1,785 2,380 2,974 940 57 113 226 340 453 566
420 283 567 1,134 1,701 2,268 2,834 950 55 111 222 332 443 554
960 54 109 217 326 434 543
MS
430 270 541 1,082 1,622 21,63 2,704
440 258 517 1,033 1,550 2,066 2,583 970 53 106 213 319 425 531
450 247 494 988 1,481 1,975 2,469 980 52 104 208 312 416 521
460 236 473 945 1,418 1,890 2,363 990 51 102 204 306 408 510
470 226 453 905 13,58 1,811 2,263 1,000 50 100 200 300 400 500
480 217 434 868 1,302 1,736 2,170
490 208 416 833 1,249 1,666 2,082
500 200 400 800 1,200 1,600 2,000
510 192 384 769 1,153 1,538 1,922
520 185 370 740 1,109 1,479 1,849
530 178 356 712 1,068 1,424 1,780
540 171 343 686 1,029 1,372 1,715
550 165 331 661 992 1,322 1,653
RELAY

560 159 319 638 957 1,276 1,594


570 154 308 616 923 1,231 1,539
580 149 297 595 892 1,189 1,486
590 144 287 575 862 1149 1,436
600 139 278 556 833 11,11 1,389
610 134 269 537 806 1,075 1,344
620 130 260 520 780 1,041 1,301
48 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
Time Chart for STD Inverse Time (Generator)

Tsd STD Time Setting (ms) Marine Type


Item
x In 50 100 200 300 400 500
100 1,250 2,500 5,000 7,500 1,0000 12,500
110 1,033 2,066 4,132 6,198 8,264 10,331
120 868 1,736 3,472 5,208 6,944 8,681
130 740 1,479 2,959 4,438 5,917 7,396
140 638 1,276 2,551 3,827 5,102 6,378
150 556 1,111 2,222 3,333 4,444 5,556
160 488 977 1,953 2,930 3,906 4,883
170 433 865 1,730 2,595 3,460 4,325
180 386 772 1,543 2,315 3,086 3,858
190 346 693 1,385 2,078 2,770 3,463
200 313 625 1,250 1,875 2,500 3,125
210 283 567 1,134 1,701 2,268 2,834
220 258 517 1,033 1,550 2,066 2,583
230 236 473 945 1,418 1,890 2,363
240 217 434 868 1,302 1,736 2,170
250 200 400 800 1,200 1,600 2,000
260 185 370 740 1,109 1,479 1,849
270 171 343 686 1,029 1,372 1,715
280 159 319 638 957 1,276 1,594

Overload 290 149 297 595 892 1,189 1,486


Rate 300 139 278 556 833 1,111 1,389
(%) 310 130 260 520 780 1,041 1,301
320 122 244 488 732 977 1,221
330 115 230 459 689 918 1,148
340 108 216 433 649 865 1,081
350 102 204 408 612 816 1,020
360 96 193 386 579 772 965
370 91 183 365 548 730 913
380 87 173 346 519 693 866
390 82 164 329 493 657 822
400 78 156 313 469 625 781
410 74 149 297 446 595 744
420 71 142 283 425 567 709
430 68 135 270 406 541 676
440 65 129 258 387 517 646
450 62 123 247 370 494 617
460 59 118 236 354 473 591
470 57 113 226 340 453 566
480 54 109 217 326 434 543
490 52 104 208 312 416 521
500 50 100 200 300 400 500
Air Circuit Breakers 49

VCB
Time Chart for GFT Inverse Time (General Feeder)

Tg GFT Time Setting (ms) Tg GFT Time Setting (ms)


Item Item
x Ict 50 100 200 300 400 500 x Ict 50 100 200 300 400 500
10 5,000 10,000 20,000 30,000 40,000 50,000 63 126 252 504 756 1,008 1,260
11 4,132 8,264 16,529 24,793 33,058 41,322 64 122 244 488 732 977 1,221
12 3,472 6,944 13,889 20,833 27,778 34,722 65 118 237 473 710 947 1,183
13 2,959 5,917 11,834 17,751 23,669 29,586 66 115 230 459 689 918 1,148
14 2,551 5,102 10,204 15,306 20,408 25,510 67 111 223 446 668 891 1,114
15 2,222 4,444 8,889 13,333 17,778 22,222 68 108 216 433 649 865 1,081
16 1,953 3,906 7,813 11,719 15,625 19,531 69 105 210 420 630 840 1,050

ACB
17 1,730 3,460 6,920 10,381 13,841 17,301 70 102 204 408 612 816 1,020
18 1,543 3,086 6,173 9,259 12,346 15,432 71 99 198 397 595 793 992
19 1,385 2,770 5,540 8,310 11,080 13,850 72 96 193 386 579 772 965
20 1,250 2,500 5,000 7,500 10,000 12,500 73 94 188 375 563 751 938
21 1,134 2,268 4,535 6,803 9,070 11,338 74 91 183 365 548 730 913
22 1,033 2,066 4,132 6,198 8,264 10,331 75 89 178 356 533 711 889
23 945 1,890 3,781 5,671 7,561 9,452 76 87 173 346 519 693 866
24 868 1,736 3,472 5,208 6,944 8,681 77 84 169 337 506 675 843
25 800 1,600 3,200 4,800 6,400 8,000 78 82 164 329 493 657 822
26 740 1,479 2,959 4,438 5,917 7,396 79 80 160 320 481 641 801
27 686 1,372 2,743 4,115 5,487 6,859 80 78 156 313 469 625 781
Detection
28 638 1,276 2,551 3,827 5,102 6,378 Setting 81 76 152 305 457 610 762
29 595 1,189 2,378 3,567 4,756 5,945 Current 82 74 149 297 446 595 744

MCCB
(%)
30 556 1,111 2,222 3,333 4,444 5,556 83 73 145 290 435 581 726
31 520 1,041 2,081 3,122 4,162 5,203 84 71 142 283 425 567 709
32 488 977 1,953 2,930 3,906 4,883 85 69 138 277 415 554 692
33 459 918 1,837 2,755 3,673 4,591 86 68 135 270 406 541 676
34 433 865 1,730 2,595 3,460 4,325 87 66 132 264 396 528 661
Detection 35 408 816 1,633 2,449 3,265 4,082 88 65 129 258 387 517 646
Setting
36 386 772 1,543 2,315 3,086 3,858 89 63 126 252 379 505 631
Current
(%) 37 365 730 1,461 2,191 2,922 3,652 90 62 123 247 370 494 617
38 346 693 1,385 2,078 2,770 3,463 91 60 121 242 362 483 604
39 329 657 1,315 1,972 2,630 3,287 92 59 118 236 354 473 591
40 313 625 1,250 1,875 2,500 3,125 93 58 116 231 347 462 578
41 297 595 1,190 1,785 2,380 2,974 94 57 113 226 340 453 566
42 283 567 1,134 1,701 2,268 2,834 95 55 111 222 332 443 554
43 270 541 1,082 1,622 2,163 2,704 96 54 109 217 326 434 543
44 258 517 1,033 1,550 2,066 2,583 97 53 106 213 319 425 531
MS
45 247 494 988 1,481 1,975 2,469 98 52 104 208 312 416 521
46 236 473 945 1,418 1,890 2,363 99 51 102 204 306 408 510
47 226 453 905 1,358 1,811 2,263 100 50 100 200 300 400 500
48 217 434 868 1,302 1,736 2,170
49 208 416 833 1,249 1,666 2,082
50 200 400 800 1,200 1,600 2,000
51 192 384 769 1,153 1,538 1,922
52 185 370 740 1,109 1,479 1,849
53 178 356 712 1,068 1,424 1,780
54 171 343 686 1,029 1,372 1715
55 165 331 661 992 1,322 1,653
RELAY

56 159 319 638 957 1,276 1,594


57 154 308 616 923 1,231 1,539
58 149 297 595 892 1,189 1,486
59 144 287 575 862 1,149 1,436
60 139 278 556 833 1,111 1,389
61 134 269 537 806 1,075 1,344
62 130 260 520 780 1,041 1,301
50 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
Time Chart for PTA Inverse Time (Generator)

PTA Time Setting (sec)


Tp
Item
x Ip
1 5 10 15 20 25 30 35 40
49 6.00 29.99 59.98 89.96 119.95 149.94 179.93 209.91 239.90
50 5.76 28.80 57.60 86.40 115.20 144.00 172.80 201.60 230.40
51 5.54 27.68 55.36 83.04 110.73 138.41 166.09 193.77 221.45
52 5.33 26.63 53.25 79.88 106.51 133.14 159.76 186.39 213.02
53 5.13 25.63 51.26 76.90 102.53 128.16 153.79 179.42 205.06
54 4.94 24.69 49.38 74.07 98.77 123.46 148.15 172.84 197.53
55 4.76 23.80 47.60 71.40 95.21 119.01 142.81 166.61 190.41
56 4.59 22.96 45.92 68.88 91.84 114.80 137.76 160.71 183.67
57 4.43 22.16 44.32 66.48 88.64 110.80 132.96 155.12 177.29
58 4.28 21.40 42.81 64.21 85.61 107.02 128.42 149.82 171.22
59 4.14 20.68 41.37 62.05 82.73 103.42 124.10 144.79 165.47
60 4.00 20.00 40.00 60.00 80.00 100.00 120.00 140.00 160.00
61 3.87 19.35 38.70 58.05 77.40 96.75 116.10 135.45 154.80
62 3.75 18.73 37.46 56.19 74.92 93.65 112.38 131.11 149.84
63 3.63 18.14 36.28 54.42 72.56 90.70 108.84 126.98 145.12
64 3.52 17.58 35.16 52.73 70.31 87.89 105.47 123.05 140.63
65 3.41 17.04 34.08 51.12 68.17 85.21 102.25 119.29 136.33
66 3.31 16.53 33.06 49.59 66.12 82.64 99.17 115.70 132.23
67 3.21 16.04 32.08 48.12 64.16 80.20 96.24 112.27 128.31
68 3.11 15.57 31.14 46.71 62.28 77.85 93.43 109.00 124.57
69 3.02 15.12 30.25 45.37 60.49 75.61 90.74 105.86 120.98
70 2.94 14.69 29.39 44.08 58.78 73.47 88.16 102.86 117.55
71 2.86 14.28 28.57 42.85 57.13 71.41 85.70 99.98 114.26
72 2.78 13.89 27.78 41.67 55.56 69.44 83.33 97.22 111.11
73 2.70 13.51 27.02 40.53 54.04 67.55 81.07 94.58 108.09
Detection 74 2.63 13.15 26.30 39.44 52.59 65.74 78.89 92.04 105.19
Setting
75 2.56 12.80 25.60 38.40 51.20 64.00 76.80 89.60 102.40
Current
(%) 76 2.49 12.47 24.93 37.40 49.86 62.33 74.79 87.26 99.72
77 2.43 12.14 24.29 36.43 48.57 60.72 72.86 85.01 97.15
78 2.37 11.83 23.67 35.50 47.34 59.17 71.01 82.84 94.67
79 2.31 11.54 23.07 34.61 46.15 57.68 69.22 80.76 92.29
80 2.25 11.25 22.50 33.75 45.00 56.25 67.50 78.75 90.00
81 2.19 10.97 21.95 32.92 43.90 54.87 65.84 76.82 87.79
82 2.14 10.71 21.42 32.12 42.83 53.54 64.25 74.96 85.66
83 2.09 10.45 20.90 31.35 41.81 52.26 62.71 73.16 83.61
84 2.04 10.20 20.41 30.61 40.82 51.02 61.22 71.43 81.63
85 1.99 9.97 19.93 29.90 39.86 49.83 59.79 69.76 79.72
86 1.95 9.73 19.47 29.20 38.94 48.67 58.41 68.14 77.88
87 1.90 9.51 19.02 28.54 38.05 47.56 57.07 66.59 76.10
88 1.86 9.30 18.60 27.89 37.19 46.49 55.79 65.08 74.38
89 1.82 9.09 18.18 27.27 36.36 45.45 54.54 63.63 72.72
90 1.78 8.89 17.78 26.67 35.56 44.44 53.33 62.22 71.11
91 1.74 8.69 17.39 26.08 34.78 43.47 52.17 60.86 69.56
92 1.70 8.51 17.01 25.52 34.03 42.53 51.04 59.55 68.05
93 1.66 8.32 16.65 24.97 33.30 41.62 49.95 58.27 66.60
94 1.63 8.15 16.30 24.45 32.59 40.74 48.89 57.04 65.19
95 1.60 7.98 15.96 23.93 31.91 39.89 47.87 55.84 63.82
96 1.56 7.81 15.63 23.44 31.25 39.06 46.88 54.69 62.50
97 1.53 7.65 15.30 22.96 30.61 38.26 45.91 53.57 61.22
98 1.50 7.50 14.99 22.49 29.99 37.48 44.98 52.48 59.98
99 1.47 7.35 14.69 22.04 29.38 36.73 44.08 51.42 58.77
100 1.44 7.20 14.40 21.60 28.80 36.00 43.20 50.40 57.60
101 1.41 7.06 14.12 21.17 28.23 35.29 42.35 49.41 56.47
Air Circuit Breakers 51

VCB
PTA Time Setting (sec)
Tp
Item
x Ip
1 5 10 15 20 25 30 35 40
102 1.38 6.92 13.84 20.76 27.68 34.60 41.52 48.44 55.36
103 1.36 6.79 13.57 20.36 27.15 33.93 40.72 47.51 54.29
104 1.33 6.66 13.31 19.97 26.63 33.28 39.94 46.60 53.25
105 1.31 6.53 13.06 19.59 26.12 32.65 39.18 45.71 52.24
106 1.28 6.41 12.82 19.22 25.63 32.04 38.45 44.86 51.26
107 1.26 6.29 12.58 18.87 25.16 31.44 37.73 44.02 50.31
108 1.23 6.17 12.35 18.52 24.69 30.86 37.04 43.21 49.38

ACB
109 1.21 6.06 12.12 18.18 24.24 30.30 36.36 42.42 48.48
110 1.19 5.95 11.90 17.85 23.80 29.75 35.70 41.65 47.60
111 1.17 5.84 11.69 17.53 23.37 29.22 35.06 40.91 46.75
112 1.15 5.74 11.48 17.22 22.96 28.70 34.44 40.18 45.92
113 1.13 5.64 11.28 16.92 22.55 28.19 33.83 39.47 45.11
114 1.11 5.54 11.08 16.62 22.16 27.70 33.24 38.78 44.32
115 1.09 5.44 10.89 16.33 21.78 27.22 32.67 38.11 43.55
116 1.07 5.35 10.70 16.05 21.40 26.75 32.10 37.46 42.81
117 1.05 5.26 10.52 15.78 21.04 26.30 31.56 36.82 42.08
118 1.03 5.17 10.34 15.51 20.68 25.85 31.03 36.20 41.37
119 1.02 5.08 10.17 15.25 20.34 25.42 30.51 35.59 40.68
120 1.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00 40.00
121 0.98 4.92 9.84 14.75 19.67 24.59 29.51 34.42 39.34

MCCB
122 0.97 4.84 9.67 14.51 19.35 24.19 29.02 33.86 38.70
123 0.95 4.76 9.52 14.28 19.04 23.80 28.55 33.31 38.07
124 0.94 4.68 9.37 14.05 18.73 23.41 28.10 32.78 37.46
125 0.92 4.61 9.22 13.82 18.43 23.04 27.65 32.26 36.86
126 0.91 4.54 9.07 13.61 18.14 22.68 27.21 31.75 36.28
Detection 127 0.89 4.46 8.93 13.39 17.86 22.32 26.78 31.25 35.71
Setting
128 0.88 4.39 8.79 13.18 17.58 21.97 26.37 30.76 35.16
Current
(%) 129 0.87 4.33 8.65 12.98 17.31 21.63 25.96 30.29 34.61
130 0.85 4.26 8.52 12.78 17.04 21.30 25.56 29.82 34.08
131 0.84 4.20 8.39 12.59 16.78 20.98 25.17 29.37 33.56
132 0.83 4.13 8.26 12.40 16.53 20.66 24.79 28.93 33.06
133 0.81 4.07 8.14 12.21 16.28 20.35 24.42 28.49 32.56
134 0.80 4.01 8.02 12.03 16.04 20.05 24.06 28.07 32.08
135 0.79 3.95 7.90 11.85 15.80 19.75 23.70 27.65 31.60
136 0.78 3.89 7.79 11.68 15.57 19.46 23.36 27.25 31.14
MS
137 0.77 3.84 7.67 11.51 15.34 19.18 23.02 26.85 30.69
138 0.76 3.78 7.56 11.34 15.12 18.90 22.68 26.47 30.25
139 0.75 3.73 7.45 11.18 14.91 18.63 22.36 26.09 29.81
140 0.73 3.67 7.35 11.02 14.69 18.37 22.04 25.71 29.39
141 0.72 3.62 7.24 10.86 14.49 18.11 21.73 25.35 28.97
142 0.71 3.57 7.14 10.71 14.28 17.85 21.42 25.00 28.57
143 0.70 3.52 7.04 10.56 14.08 17.60 21.13 24.65 28.17
144 0.69 3.47 6.94 10.42 13.89 17.36 20.83 24.31 27.78
145 0.68 3.42 6.85 10.27 13.70 17.12 20.55 23.97 27.40
146 0.68 3.38 6.76 10.13 13.51 16.89 20.27 23.64 27.02
147 0.67 3.33 6.66 10.00 13.33 16.66 19.99 23.32 26.66
RELAY

148 0.66 3.29 6.57 9.86 13.15 16.44 19.72 23.01 26.30
149 0.65 3.24 6.49 9.73 12.97 16.22 19.46 22.70 25.94
150 0.64 3.20 6.40 9.60 12.80 16.00 19.20 22.40 25.60
151 0.63 3.16 6.32 9.47 12.63 15.79 18.95 22.10 25.26
152 0.62 3.12 6.23 9.35 12.47 15.58 18.70 21.81 24.93
153 0.62 3.08 6.15 9.23 12.30 15.38 18.45 21.53 24.61
154 0.61 3.04 6.07 9.11 12.14 15.18 18.22 21.25 24.29
52 Air Circuit Breakers

Accessories
Over Current Relay (OCR)
Time Chart for PTA Inverse Time (Generator)

PTA Time Setting (sec)


Tp
Item
x Ip
1 5 10 15 20 25 30 35 40
155 0.60 3.00 5.99 8.99 11.99 14.98 17.98 20.98 23.98
156 0.59 2.96 5.92 8.88 11.83 14.79 17.75 20.71 23.67
157 0.58 2.92 5.84 8.76 11.68 14.61 17.53 20.45 23.37
158 0.58 2.88 5.77 8.65 11.54 14.42 17.30 20.19 23.07
159 0.57 2.85 5.70 8.54 11.39 14.24 17.09 19.94 22.78
160 0.56 2.81 5.63 8.44 11.25 14.06 16.88 19.69 22.50
161 0.56 2.78 5.56 8.33 11.11 13.89 16.67 19.44 22.22
162 0.55 2.74 5.49 8.23 10.97 13.72 16.46 19.20 21.95
163 0.54 2.71 5.42 8.13 10.84 13.55 16.26 18.97 21.68
164 0.54 2.68 5.35 8.03 10.71 13.38 16.06 18.74 21.42
165 0.53 2.64 5.29 7.93 10.58 13.22 15.87 18.51 21.16
166 0.52 2.61 5.23 7.84 10.45 13.06 15.68 18.29 20.90
167 0.52 2.58 5.16 7.74 10.33 12.91 15.49 18.07 20.65
168 0.51 2.55 5.10 7.65 10.20 12.76 15.31 17.86 20.41
169 0.50 2.52 5.04 7.56 10.08 12.60 15.13 17.65 20.17
170 0.50 2.49 4.98 7.47 9.97 12.46 14.95 17.44 19.93
171 0.49 2.46 4.92 7.39 9.85 12.31 14.77 17.24 19.70
172 0.49 2.43 4.87 7.30 9.73 12.17 14.60 17.04 19.47
173 0.48 2.41 4.81 7.22 9.62 12.03 14.43 16.84 19.25
174 0.48 2.38 4.76 7.13 9.51 11.89 14.27 16.65 19.02
175 0.47 2.35 4.70 7.05 9.40 11.76 14.11 16.46 18.81
176 0.46 2.32 4.65 6.97 9.30 11.62 13.95 16.27 18.60
Detection 177 0.46 2.30 4.60 6.89 9.19 11.49 13.79 16.09 18.39
Setting
178 0.45 2.27 4.54 6.82 9.09 11.36 13.63 15.91 18.18
Current
(%) 179 0.45 2.25 4.49 6.74 8.99 11.24 13.48 15.73 17.98
180 0.44 2.22 4.44 6.67 8.89 11.11 13.33 15.56 17.78
181 0.44 2.20 4.40 6.59 8.79 10.99 13.19 15.38 17.58
182 0.43 2.17 4.35 6.52 8.69 10.87 13.04 15.22 17.39
183 0.43 2.15 4.30 6.45 8.60 10.75 12.90 15.05 17.20
184 0.43 2.13 4.25 6.38 8.51 10.63 12.76 14.89 17.01
185 0.42 2.10 4.21 6.31 8.41 10.52 12.62 14.73 16.83
186 0.42 2.08 4.16 6.24 8.32 10.41 12.49 14.57 16.65
187 0.41 2.06 4.12 6.18 8.24 10.29 12.35 14.41 16.47
188 0.41 2.04 4.07 6.11 8.15 10.19 12.22 14.26 16.30
189 0.40 2.02 4.03 6.05 8.06 10.08 12.09 14.11 16.12
190 0.40 1.99 3.99 5.98 7.98 9.97 11.97 13.96 15.96
191 0.39 1.97 3.95 5.92 7.89 9.87 11.84 13.82 15.79
192 0.39 1.95 3.91 5.86 7.81 9.77 11.72 13.67 15.63
193 0.39 1.93 3.87 5.80 7.73 9.66 11.60 13.53 15.46
194 0.38 1.91 3.83 5.74 7.65 9.57 11.48 13.39 15.30
195 0.38 1.89 3.79 5.68 7.57 9.47 11.36 13.25 15.15
196 0.37 1.87 3.75 5.62 7.50 9.37 11.25 13.12 14.99
197 0.37 1.86 3.71 5.57 7.42 9.28 11.13 12.99 14.84
198 0.37 1.84 3.67 5.51 7.35 9.18 11.02 12.86 14.69
198 0.36 1.82 3.64 5.45 7.27 9.09 10.91 12.73 14.55
198 0.36 1.80 3.60 5.40 7.20 9.00 10.80 12.60 14.40
200 0.36 1.80 3.60 5.40 7.20 9.00 10.80 12.60 14.40
Air Circuit Breakers 53

Accessories

VCB
Spring Charging Geared Motor
˙Manual charging method and geared motor charging method Connection Diagram
using external power source for charging the spring in the
circuit breaker. Power
˙As for the geared motor charging method, if power is applied
to the control power terminal number (1), (2), spring charge is
1
possible at 85 ~ 110 % power of the operating voltage range.
15

˙Add M1 ~ M9 in the order form. Spring


Charge
˙It can be purchased separately. Off SW.

Ordering Method

ACB
Order Name Placed Detailed M
Name of Accessory
upon Outgoing Specification

M1 AC/DC 110 V
M2 AC/DC 220 V

AC 380 V
M3
(Under Development) 2 16

Spring Charging
Geared Motor AC 440 V
M4
(Under Development)

M7 DC 24 V
M8 DC 48 V
M9 DC 125 V

MCCB
Ratings

Item DC 110 DC 220


Rated Current (A) 1.2 0.5
Starting Pick-Up (A) 5 ~ 6 times the rated current
Final Rated rpm 16 ± 3
Charging Time (sec) Within 5 seconds 1)
Rated Torque (kgf) 300 kgf×cm
Rated Watt (W) 100 100
Dielectric Strength (V/min) 2,000
Insulation Resistance (MΩ) 100
Workable Temperature (℃) -15 ~ 60

※ 1) Charging time is within 10 sec of rated, in case of DC 24/48 V.


MS

Wire Ratings Spring Charging


DC 24, 48 DC 110, 220 Geared Motor
Rated Voltage Insulation Insulation
AWG (mm2) AWG (mm2)
Level (V) Level (V)

Specification 18 600 18 600

Spring Charging Switch or Ready to Close Switch


RELAY

˙Spring charging switch delivers (15, 16) the charged status when mechanism spring charge is complete.
˙Read to close switch delivers (15, 16) only when the circuit breaker is open and simultaneously only when the mechanism spring
charge is complete.
˙Order name of spring charging switch:B6, Order name of ready to close switch:BT
˙Two accessories cannot be ordered simultaneously.
54 Air Circuit Breakers

Accessories
Closing Coil (CC)
˙A control device which closes a circuit breaker remotely from Connection Diagram
outside.
˙The circuit breaker is closed by applying power of at least more
Power
than 150 ms within the range of 85 ~ 110 % of the rated control PB
(Close)
voltage to the control power terminal number (3) and (4).
˙Add C1 ~ C9 in the order form when ordering the main unit. 3

˙It can be purchased separately.


˙Use a separate switch externally to apply power to the closing coil.

Ordering Method

Order Name Placed Detailed


Name of Accessory
upon Outgoing Specification
CC
C1 AC/DC 110 V
C2 AC/DC 220 V
C3 AC 380 V
Closing Coil C4 AC 440 V
C7 DC 24 V 4

C8 DC 48 V
C9 DC 125 V

Ratings Wire Ratings

Item DC (V) AC (V) DC 24 AC/DC 110, 220


24 - Rated Voltage Insulation Insulation
AWG (mm2) AWG (mm2)
Rated Voltage (Vn) 100 ~ 130 100 ~ 130 Level (V) Level (V)

200 ~ 250 200 ~ 250 Specification 20 600 20 600


Operating Limits (Vn) 0.85 ~ 1.1
Power Consumption (VA) Inrush (300), Steady-State (10)
Trip Time (ms) 80

Closing Coil
Air Circuit Breakers 55

VCB
Trip Coil (TC)
˙A control device which trips a circuit breaker remotely. Connection Diagram
˙The circuit breaker is tripped by applying power of at least more
than 150 ms within the range of 70 ~ 110 % of the rated control Power
voltage to the control power terminal number (7) and (8).
˙Add S1 ~ S9 in the order form when ordering the main unit.

PB(Open)
˙It can be purchased separately. 7

˙Use a separate switch externally to apply power to the closing coil.

Ordering Method

ACB
Order Name Placed Detailed
Name of Accessory
upon Outgoing Specification
TC
S1 AC/DC 110 V
S2 AC/DC 220 V
S3 AC 380 V
Trip Coil S4 AC 440 V
S7 DC 24 V 8
S8 DC 48 V
S9 DC 125 V

MCCB
Ratings Wire Ratings

Item DC (V) AC (V) DC 24 AC/DC 110, 220


24 - Rated Voltage Insulation Insulation
AWG (mm2) AWG (mm2)
Rated Voltage (Vn) 100 ~ 130 100 ~ 130 Level (V) Level (V)

200 ~ 250 200 ~ 250 Specification 20 600 20 600


Operating Limits (Vn) 0.7 ~ 1.1
Power Consumption (VA) Inrush (300), Steady-State (10)
Trip Time (ms) 40

MS

Trip Coil
RELAY
56 Air Circuit Breakers

Accessories
Secondary Trip Coil
˙It is a control device which trips a circuit breaker remotely from Connection Diagram
outside and dual remote trip is possible with an additional
installation of trip coil. Power Power
˙The circuit breaker is tripped by applying power of at least

PB(Open)

PB(Open)
more than 150 ms within the range of 70 ~ 110 % of the rated
control voltage by applying power to the control power terminal 7 9

number (9) and (10).


˙When dual trip coil is used, it cannot be used together with UVT coil.
˙Add S1 ~ S9 in the order form when ordering the main unit and
under the option, add S1 ~ S9 once again.
˙It can be purchased separately.
˙Use a separate switch externally to apply power to the dual trip coil. TC TC

8 10

Ordering Method Ratings

Order Name Placed Detailed Item DC (V) AC (V)


Name of Accessory
upon Outgoing Specification 24 -
S1 AC/DC 110 V Rated Voltage (Vn) 100 ~ 130 100 ~ 130
S2 AC/DC 220 V 200 ~ 250 200 ~ 250
S3 AC 380 V Operating Limits (Vn) 0.7 ~ 1.1
Secondary Trip Coil S4 AC 440 V Power Consumption (VA) Inrush (300), Steady-State (10)
S7 DC 24 V Trip Time (ms) 40
S8 DC 48 V
S9 DC 125 V

Wire Ratings

DC 24 AC/DC 110, 220


Rated Voltage Insulation Insulation
AWG (mm2) AWG (mm2)
Level (V) Level (V)

Specification 20 600 20 600

Secondary Trip Coil


Air Circuit Breakers 57

VCB
Trip Coil Supervision
˙A control device which trips a circuit breaker remotely from outside. Connection Diagram
˙The circuit breaker is tripped by applying power of at least more
than 150 ms within the range of 70 ~ 110 % of the rated control
Power
voltage by applying power to the control power terminal
number (7) and (8).

PB(Open)
Supervision
˙When using trip coil supervision, auxiliary contact is 4a3b and 7 59

when 1a1b is added, it becomes 5a4b. (AUX S/W 43/44, 53/54


cannot be used.)
˙In order to monitor the permanent normal status when TCS
is closed and tripped, the circuit sequence cannot be created

ACB
by using the additional 1a1b (Order code AA). (Possibility of
contact damage) However, if it is compulsory, select 1a contact
within 4a3b for use. TC

˙The trip coil’s monitoring output contact No. 59.


˙Coil supervision checks not only the circuit’s mechanical
contact but also the condition of the coil.
8
˙Add T1 ~ T9 in the order form when ordering the main unit.
˙It can be purchased separately.

Ordering Method Ratings

MCCB
Order Name Placed Detailed Item DC (V) AC (V)
Name of Accessory
upon Outgoing Specification 24 -
T1 AC/DC 110 V Rated Voltage (Vn) 100 ~ 130 100 ~ 130
T2 AC/DC 220 V 200 ~ 250 200 ~ 250
T3 AC 380 V Operating Limits (Vn) 0.7 ~ 1.1
Trip Coil Supervision T4 AC 440 V Power Consumption (VA) Inrush (300), Steady-State (10)
T7 DC 24 V Trip Time (ms) 40
T8 DC 48 V
T9 DC 125 V

Wire Ratings

DC 24 AC/DC 110, 220 MS


Rated Voltage Insulation Insulation
AWG (mm2) AWG (mm2)
Level (V) Level (V)

Specification 20 600 20 600


RELAY

Trip Coil Supervision


58 Air Circuit Breakers

Accessories
UVT Coil
˙Under-voltage trip device is a device that automatically trips Connection Diagram
the circuit breaker if the load voltage drops to below 70 % of the
standard or to prevent accidents at the load part during a black out. Power

˙Under-voltage trip device is classified into instantaneous and

PB(Open)
time delay type for use. As for instantaneous type, directly 9
connect to control power terminal number (9), (10) for use and
as for time delay type, the Time Delay Controller can be used.
˙The circuit breaker trips when the load voltage at the UVT coil
becomes less than 35 %, becomes an interlocked state that
cannot be closed and when load voltage of 85% is applied,
normal closing is possible. UVT

˙When instantaneous type of UVT is used, dual trip coil cannot


be used.
˙When instantaneous type of UVT is used, add U1 ~ U9 in the
order form when ordering the main unit.
˙It can be purchased separately.
10

Ordering Method Ratings

Order Name Placed Detailed Item DC (V) AC (V)


Name of Accessory
upon Outgoing Specification 24 -
U1 AC/DC 110 V 110 (100 ~ 130) 110 (100 ~ 130)
U2 AC/DC 220 V Rated Voltage (Vn) 220 (200 ~ 250) 220 (200 ~ 250)
U3 AC 380 V - 380
UVT Coil U4 AC 440 V - 440
U7 DC 24 V Pickup Above 0.85 Vn
U8 DC 48 V Drop Below 0.35 Vn
U9 DC 125 V Power Consumption (VA) Inrush (300), Steady-State (10)
Trip Time (ms) 50

Wire Ratings

DC 24 AC/DC 110, 220 AC 380, 440


Rated
Voltage AWG Insulation AWG Insulation AWG Insulation
(mm2) Level (V) (mm2) Level (V) (mm2) Level (V)

Specification 20 600 20 600 20 600

UVT Coil
Air Circuit Breakers 59

VCB
UVT Time Delay Controller
˙Under-voltage trip device is a device that automatically trips Connection Diagram
the circuit breaker if the load voltage drops to below operating
voltage or to prevent accidents at the load part during a black out. COM
U1
Power
˙This device is capable of delaying (0.5, 1.0, 1.5, 3 sec). a
b
U2

˙UVT Time Delay Controller can be mounted at the left side of

PB(Open)
C1
T2

Controller
UVT
C2
the cradle and the external rail and it can also be mounted at T1
9
the position desired by the customer.
˙Add V1 ~ V9 in the order form when ordering the main unit.
Time Delay Controller will be included in the package.
˙When purchasing the UVT time delay controller only, place the

ACB
order for the separate product, HGNS UT1 ~ UT9.
UVT
˙DC 24 V and DC 48 V are only available in instantaneous type.
˙In the event the UVT Time Delay Controller and RCTU are
purchased simultaneously, the front mounting can be installed
in the front for 1 option designated by the customer.
The remaining 1 shall be installed by designating a position in 10

the DIN RAIL inside the panel.

Ordering Method Wiring and Operating Time

Order Name for


Name of Order Name Placed Detailed

MCCB
Separate Sales
Accessory upon Outgoing Specification
(HGNS-)

- HGNS UT1 AC/DC 110 V V Source

- HGNS UT2 AC/DC 220 V 0


UVT Time
Delay - HGNS UT3 AC 380 V
Controller UVT Trip
- HGNS UT4 AC 440 V 0.5 1.0 1.5 3.0
0 Sec
- HGNS UT9 DC 125 V
V1 HGNS V1 AC/DC 110 V
Can be selected from 0.5 – 1.0 – 1.5 – 3 (sec)
UVT Time V2 HGNS V2 AC/DC 220 V
Delay
V3 HGNS V3 AC 380 V
Controller +
UVT Coil V4 HGNS V4 AC 440 V
V9 HGNS V9 DC 125 V

Dimension
MS
UVT Time Delay Controller

Unit:mm

121.4
105
91.4
75

RELAY

2-Ø4.2 (Use M4×25L Screw)

※ 5, 7, 9 switch status is the status when UVT is functioning.


60 Air Circuit Breakers

Accessories
AUX Switch
˙It is an output contact to remotely monitor the On/Off state of Connection
the ACB.
˙As for HGS Type, 3a3b is provided and as for HGN Type, 5a5b is 41 43 45 47 49 51 53 55 57 59
provided as standard without separate indication in the order form.
˙AUX switch can be expanded up to 6a6b maximum.
- How to order HGS 5a5b:Add A5 in the order form.
- How to order HGS/HGN 6a6b:Add AA in the order form.

Used for Short "b" Contact<Option>


Used for TC Supervision<Option>

Used for TC Supervision<Option>


˙When using the monitoring contact for trip coil, 3a3b can be
used for the AUX switch and when using the MCR function of

Used for MCR<Option>


OCR, it can be used as 4a3b.
˙When short “b” is added, it will be attached to ‘b’ contacts 51,
52 for outgoing and upon additional mounting, the short “b”
sealed and released can be mounted additionally depending
on the number of b contacts. 42 44 46 48 50 52 54 56 58 60

˙5a5b can be purchased separately. Place an order separately as


HGNS A5.

AUX Switch Ratings Wire Specification

Applicable Load Resistance Lamp Inductor Motor Wire Specification AWG Insulation Level (V)
AC 125 V 5A 0.7 A 4A 1.3 A Specification 20 300
AC 250 V 5A 0.5 A 4A 0.8 A

AUX Switch
Air Circuit Breakers 61

VCB
Counter OCR Manual/Auto Reset & Alarm Switch Reset
˙It is a device that displays the number of operations, indicating ˙It is a device that interlocks the closing of the circuit breaker
On/Off operation of the circuit breaker in 1 cycle. until the electric line is restored after the user has completely
˙It is a primary component so separate order is unnecessary. removed the fault factor when a circuit breaker tripped by OCR
due to overload or fault current in the electric line. (BR)
˙BR:When the circuit breaker functions due to OCR, it interlocks
to prevent closing of circuit breaker and is reset manually.
˙BA:When the circuit breaker functions due to OCR, the circuit
breaker’s status is indicated as output contact 2a other
than the interlock feature and this output contact is reset
manually.

ACB
˙BH:When the circuit breaker functions due to OCR, the circuit
breaker’s status is indicated as output contact high
capacity switch other than the interlock feature and this
output contact is reset manually.
˙As a product mounted in the main unit, add BR/BA/BH in the
order form when ordering the main unit.

Ordering Method

Order Name Placed Detailed


Name of Accessory
upon Outgoing Specification

MCCB
OCR Manual Reset BR Interlock Manual Reset

OCR Manual Reset + Interlock Manual Reset +


BA
Alarm S/W Reset Alarm S/W Reset

OCR Manual Reset + Interlock Manual Reset +


High Capacity Alarm BH Alarm S/W Reset
S/W Reset (1C) (High Capacity DC 3 A)

MS

OCR Manual/Auto Reset &


Alarm Switch Reset
RELAY

Counter
62 Air Circuit Breakers

Accessories
Position Switch
˙This switch, mounted at the side of the cradle, displays the Position Switch
position of ACB during draw-out.
˙The position of Inserted/Isolated/Test/Connected can be
displayed.
˙Only one switch is applicable and it can only be mounted at the
right side of the cradle.
˙It can be purchased separately.

AUX Switch Ratings

Applicable Load Resistance Lamp Inductor Motor


AC 125 V 10 A 1.5 A 6A 2A
DC 30 V 6A 3A 6A 3A
DC 125 V 0.6 A 0.1 A 0.6 A 0.1 A
DC 250 V 0.3 A 0.05 A 0.3 A 0.05 A

Ordering Method

Specification of Switch Output Mounting


Order Name
Composition Insert Isol Test Connect Position

AQ HGNS AQ Test 1C/Connect 1C × × ● (1C) ● (1C)


AR HGNS AR Connect 2C × × × ● (2C)
AS HGNS AS Test 2C × × ● (2C) ×
AT HGNS AT Isol 1C/Insert 1C ● (1C) ● (1C) × ×
AU HGNS AU Insert 2C ● (2C) × × ×
AV HGNS AV Isol 2C × ● (2C) × × Right Side of
PQ HGNS PQ Isol 1C/Insert 1C/Test 1C/Connect 1C ● (1C) ● (1C) ● (1C) ● (1C) Cradle

PS HGNS PS Isol 1C/Test 1C/Connect 2C × ● (1C) ● (1C) ● (2C)


P4 HGNS P4 Test 2C/Connect 2C × × ● (2C) ● (2C)
PT HGNS PT Test 4C × × ● (4C) ×
PR HGNS PR Insert 1C/Isol 1C/Test 3C/Connect 3C ● (1C) ● (1C) ● (3C) ● (3C)
P8 HGNS P8 Insert 2C/Isol 2C/Test 2C/Connect 2C ● (2C) ● (2C) ● (2C) ● (2C)

Operating Sequence of
Position Switch Operation Circuit Connection Diagram Dimension

Unit:mm
61 64 71 74 81 84
61 64 71 74 81 84 63.5
Insert
Isol TestInsert Connect
Isol Test Connect

Connect
Connect

Test
Test 62 63 65 66 72 73 75 76 82 83 85 86
Test 62 63 65 66 Isolation
Connection 72 73 75 76 82 83 85 86
Isol
Isol Position Position
Test Postion
Connection Isolation
61-62 a Position
71-72 a Position
81-82 a Postion
Insert 61-63 b 71-73 b a
61-62 81-83
71-72 ba 81-82 a
Insert 64-65 a 61-63
74-75 a b 71-73 b
INSERT 81-83 b
64-66 b 74-76 b a
64-65 POSITION
74-75 a INSERT
67-68 a 64-66
77-78 a b 74-76 ab
91-92 POSITION
67-69 b 77-79 b a
67-68 91-93
77-78 ba 91-92 a
67-69 b 77-79 b 91-93 b
Air Circuit Breakers 63

VCB
Lifting Lug Dummy ACB
˙It is a component that is used for transporting the circuit ˙The dummy ACB is applied as emergency in case of a long-
breaker. term black out for repair when a malfunction has occurred in a
˙It can be hung to the handle at the side of the cradle, side of the device when using the ACB. It is a frame used to conduct ACB’s
arc shield and the main unit and the product can be moved by function temporarily.
a crane or a person. ˙As the circuit breaker is closed, the primary power must be
˙When handling all the products, use the crane and in case of removed in the electric line when connecting the Dummy ACB.
transporting independently using only the crane in case of ˙Each frame is provided in the maximum rated current.
products below 3,200 A, the products must be transported in ˙It can be ordered separately. Make a separate inquiry when
accordance with the safety regulations. placing the order.
˙As a product sold separately, place an order for HGNS AL.

ACB
Ordering Method

Name of Accessory Detailed Specification


A Frame, 630 ~ 2,000 A, 3P
A Frame, 630 ~ 2,000 A, 4P
B Frame, 2,000 ~ 4,000 A, 3P
B Frame, 2,000 ~ 4,000 A, 4P
Dummy ACB
C Frame, 4,000 ~ 5,000 A, 3P
C Frame, 4,000 ~ 5,000 A, 4P
D Frame, 4,000 ~ 6,300 A, 3P
D Frame, 4,000 ~ 6,300 A, 4P

MCCB
Lifting Lug

MS
RELAY
64 Air Circuit Breakers

Accessories
Mechanical Interlock
˙MI is a device that mechanically interlocks the closing and
tripping of each circuit breaker by connecting 2 or 3 circuit
breakers.
˙The MI is operated by a combination of the MI unit and the
components of the interlock that is installed inside the main unit.
˙The MI unit is a separate product and it is a device that is mounted
additionally after the ACB has to be installed in the panel.
˙When placing the order for the main unit, add B0 in the order
from and only the component inside the interlock is mounted
inside the main unit for release and as for the external
mounting kit, place an additional order as a separate product.
˙MI wire should be connected under 2 m between ACBs. Mechanical
Interlock
˙In order to install, a square hole of 100×200 (mm) is required.

Ordering Method

Order Name for Order Name for


Name of Name of
Separate Sales Accessory Spec. Separate Sales Accessory Spec.
Accessory Accessory
(HGNS-) (HGNS-)

A & B & C & D Frame Draw-Out (Fixed) Type C Frame 3P Draw-Out 3 Way MI +
HGNS DWB1 HGNS DWB2C3
2 Way MI (External Mounting Kit Only) Interlock Part (B0)

A & B & C & D Frame Draw-Out (Fixed) Type C Frame 4P Draw-Out 3 Way MI +
HGNS DWB2 HGNS DWB2C4
3 Way MI (External Mounting Kit Only) Interlock Part (B0)

A & C Frame Fixed Type 2 Way MI D Frame 3P Draw-Out 2 Way MI +


HGNS FWB1 HGNS DWB1D3
(External Mounting Kit Only) Interlock Part (B0)

A & C Frame Fixed Type 3 Way MI D Frame 4P Draw-Out 2 Way MI +


HGNS FWB2 HGNS DWB1D4
(External Mounting Kit Only) Interlock Part (B0)

HGNS B0DA A Frame Interlock Part (B0) D Frame 3P Draw-Out 3 Way MI +


HGNS DWB2D3
HGNS B0DB B Frame Interlock Part (B0) Interlock Part (B0)

HGNS B0DC3 C Frame 3P Interlock Part (B0) D Frame 4P Draw-Out 3 Way MI +


HGNS DWB2D4
HGNS B0DC4 C Frame 4P Interlock Part (B0) Interlock Part (B0)

HGNS B0DD3 D Frame 3P Interlock Part (B0) HGNS FWB1A A Frame Fixed Type 2 Way MI + Interlock Part (B0)
HGNS B0DD4 D Frame 4P Interlock Part (B0) HGNS FWB2A A Frame Fixed Type 3 Way MI + Interlock Part (B0)

A Frame Interlock Part (B0) + HGNS FWB1B B Frame Fixed Type 2 Way MI + Interlock Part (B0)
Mechanical HGNS B0FA
Fixed Type of Installation Bracket HGNS FWB2B B Frame Fixed Type 3 Way MI + Interlock Part (B0)
Interlock Mechanical
Interlock
B Frame Interlock Part (B0) + C Frame 3P Fixed Type 2 Way MI +
HGNS B0FB HGNS FWB1C3
Fixed Type of Installation Bracket Interlock Part (B0)

C Frame 3P Interlock Part (B0) + C Frame 4P Fixed Type 2 Way MI +


HGNS B0FC3 HGNS FWB1C4
Fixed Type of Installation Bracket Interlock Part (B0)

C Frame 4P Interlock Part (B0) + C Frame 3P Fixed Type 3 Way MI +


HGNS B0FC4 HGNS FWB2C3
Fixed Type of Installation Bracket Interlock Part (B0)

D Frame 3P Interlock Part (B0) + C Frame 4P Fixed Type 3 Way MI +


HGNS B0FD3 HGNS FWB2C4
Fixed Type of Installation Bracket Interlock Part (B0)

D Frame 4P Interlock Part (B0) + D Frame 3P Fixed Type 2 Way MI +


HGNS B0FD4 HGNS FWB1D3
Fixed Type of Installation Bracket Interlock Part (B0)

HGNS DWB1A A Frame Draw-Out Type 2 Way MI + Interlock Part (B0) D Frame 4P Fixed Type 2 Way MI +
HGNS FWB1D4
HGNS DWB2A A Frame Draw-Out Type 3 Way MI + Interlock Part (B0) Interlock Part (B0)

HGNS DWB1B B Frame Draw-Out Type 2 Way MI + Interlock Part (B0) D Frame 3P Fixed Type 3 Way MI +
HGNS FWB2D3
HGNS DWB2B B Frame Draw-Out Type 3 Way MI + Interlock Part (B0) Interlock Part (B0)

HGNS DWB1C3 C Frame 3P Draw-Out 2 Way MI + Interlock Part (B0) D Frame 4P Fixed Type 3 Way MI +
HGNS FWB2D4
HGNS DWB1C4 C Frame 4P Draw-Out 2 Way MI + Interlock Part (B0) Interlock Part (B0)
Air Circuit Breakers 65

VCB
Key Lock Key Lock & Key Interlock
˙It is a device that maintains the interlock condition to prevent ˙3 circuit breakers mounted with the key lock device for
electric/manual closing when the circuit breaker is open. preventing On can be used to make up the system. Only 2
˙When the key has been used to unlock, the electric/manual On/ circuit breakers can be allowed to close using 2 keys and the
Off operation is possible. When the key has been removed from remaining 1 unit can be interlocked to provide stable load.
the circuit breaker, it becomes interlocked. When the key has
been used to lock, the Off button has to be pressed to turn the
key to the lock position.
˙As a product mounted on the main unit, add AB in the order Circuit Breaker 3 cannot be closed
form when placing an order for the main unit. Power 1 Power 2
Circuit Breaker 1 Circuit Breaker 2

ACB
Bus-Tie
Circuit Breaker 3

Load 1 Load 2

Circuit Breaker 2 cannot be closed


Power 1 Power 2
Circuit Breaker 1 Circuit Breaker 2
Key Lock

MCCB
Bus-Tie
Circuit Breaker 3

Load 1 Load 2

Circuit Breaker 1 cannot be closed


Power 1 Power 2
Circuit Breaker 1 Circuit Breaker 2

Bus-Tie
Circuit Breaker 3 MS

Load 1 Load 2

※ Example:Parallel feed at 2 power is prevented in case bus-tie circuit breaker is used


RELAY
66 Air Circuit Breakers

Accessories
On/Off Button Lock DR Device Unit & Position Pad Lock

˙It is a safety device that prevents manual On/Off operation ˙As for the draw-out type of circuit breaker, DR device is mounted
caused by the user’s mistaken. The buttons are covered with a on the main unit.
plastic cover to prevent arbitrary operation of manual close/trip ˙DR device is comprised of a groove for inserting draw-out
button and padlock is used. handle, draw-out push button, position indicator and a padlock
˙As a product mounted on the main unit, add AM in the order device.
form when placing an order for the main unit. ˙As for the padlock device, it is provided as a standard safety
˙Padlock is not provided by our company. (Ø5 ~ Ø8) device that prevents arbitrary draw-out by using a padlock in
the connection/test/isolated position but the padlock is not
provided by our company. (Ø5 ~ Ø8)
˙It can be purchased separately.

On/Off Button Lock DR Device Unit &


Position Pad Lock
Air Circuit Breakers 67

VCB
Auto Connection Type & Manual Control Short “b” Contact
Plug Type
˙As for the method of connecting the control power, auto ˙When the circuit breaker is moved from the Connected
connection type in which the control power is automatically position to the Test position, the auxiliary contact AUX “b” is
connected/isolated when the main unit is drawn out and disconnected to maintain the external control circuit in normal,
manual connection type in which the user directly inserts the ultimately maintaining an accurate sequence operation.
connector with the control power connected to the main unit As for the number of shorting “b” contact, it corresponds to the
are available. number of AUX “b” (5b).
˙Fixed type is provided with manual control plug type as ˙Upon outgoing, only 1b (51, 52) is mounted and as for the
standard so that type of connection terminal of the main power remaining 4b, it is sealed together with the manual pack so it
can be designated without separate indication. can be mounted as much as needed for use.

ACB
˙When completely removing the manual connection type of ˙As a product mounted on the main unit, add AK in the order
product from the cradle, the main unit has to be separated after form when placing an order for the main unit.
removing the connector.
˙As a product mounted on the cradle, select A for automatic Indication of Contact Status
connection type and J for manual connection type. (When AUX “b” and Short “b” are Connected)

ACB Operating
ACB Close ACB Open
(AUX “b” Off) (AUX “b” On)
ACB Position

OFF
OFF ON
ON
Connected Position

MCCB
(Short “b” Off) AUX
AUX "b"
"b" OFF
OFF Short
Short "b"
"b" AUX
AUX "b"
"b" ON
ON Short
Short "b"
"b"

AUX "b" OFF


AUX "b" OFF Short
Short "b"
"b" AUX "b" ON
AUX "b" ON Short
Short "b"
"b"

Manual Control Plug Type AUX


AUX "b"
"b" OFF
OFF Short
Short "b"
"b" AUX
AUX "b"
"b" ON
ON Short
Short "b"
"b"
Test Position
(Short “b” On) AUX
AUX "b"
"b" Short
Short "b"
"b" AUX
AUX "b"
"b" Short
Short "b"
"b"

Auto Control Plug Type Short “b” Contact

MS
RELAY
68 Air Circuit Breakers

Accessories
Miss-Insertion Preventor
˙Although the external size is equivalent, in case the rating does Part’s Mounting Position per Rated Current
not conform when the main unit of the circuit breaker (ACB)
is inserted in the cradle in the composition of another circuit
breaker, this device prevents it from being inserted.
˙It is comprised based on the CT rated current.
˙Each component is mounted on the main unit and cradle
respectively. Add AW in the main unit and cradle’s order form
1
respectively when placing the order. 2
3
4
5
1 A

6
2 B

Ordering Method
3 C

7
4 D
5 E
6 F
7 G

CT Rating Cradle ACB


0 = OCR Non Mounting ADEG 236
I = 80 A AEFG 234
B = 160 A ADFG 235
O = 200 A ADEF 237
V = 320 A ABEF 347
E = 400 A ABDG 356
T = 630 A ABDF 357
H = 800 A ABDE 367
1 A
J = 1,000 A ABCG 456 2 B
3 C
K = 1,250 A ABCF 457 4 D
1 A
5 E
6 F
2 B

L = 1,600 A ABCE 467


3 C

7 G
4 D
5 E
6 F

M = 2,000 A ABCD 567


7 G

N = 2,500 A BCDE 167


P = 3,200 A BCDF 157
Q = 4,000 A BCDG 156
S = 5,000 A BCEF 147
X = 6,300 A ABEG 346

Miss-Insertion Preventer
Air Circuit Breakers 69

VCB
Phase Insulation Barrier Safety Shutter & Shutter Lock
˙Phase insulation barrier is a part installed between phases that ˙It is a safety device that prevents the contact between the
prevents short circuit between phases in advance by closing the conductor part and the front part when the main unit of the
arc which may occur between phases. circuit breaker mounted on the cradle is drawn out.
˙2 ea are mounted for 3P Type and 3 ea are mounted for 4P Type ˙The structure automatically opens and closes when the circuit
and as they are sold individually, select the required quantity breaker is drawn out and it comes with a shutter lock device
when placing the order. that prevents it from opening when the shutter is closed in the
˙As a product sold separately, place an order in HGNS P BAR. event the main unit is drawn out. The padlock is not provided
by our company. (Ø5 ~ Ø8)
˙As for the shutter, the power side and load side operates
separately, each equipped with an operation device and they

ACB
can be locked individually.
˙As a product mounted on the cradle, add AE in the order form
when placing the order for the cradle.

Ordering Method

Order Name Order Name for


Name of
Placed upon Separate Sales Detailed Specification
Accessory
Outgoing (HGNS-)

HGNS AEA3 A Frame, 630 ~ 2,000 A, 3P


Phase Insulation HGNS AEA4 A Frame, 630 ~ 2,000 A, 4P
Barrier

MCCB
HGNS AEB3 B Frame, 2,000 ~ 4,000 A, 3P

Safety HGNS AEB4 B Frame, 2,000 ~ 4,000 A, 4P


AE
Shutter HGNS AEC3 C Frame, 4,000 ~ 5,000 A, 3P
HGNS AEC4 C Frame, 4,000 ~ 5,000 A, 4P
HGNS AED3 D Frame, 4,000 ~ 6,300 A, 3P
HGNS AED4 D Frame, 4,000 ~ 6,300 A, 4P

MS
Safety Shutter &
Shutter Lock
RELAY
70 Air Circuit Breakers

Accessories
Fixing Block Control Terminal Protection Cover
˙It is a safety device for reinforcement in order to prevent ˙It is a safety cover that is placed on the connection terminal to
abnormal operation caused by vibration. prevent contact with external foreign substances or physical
˙It is capable of simultaneously fixing the main unit and the contact after the control power has been connected to the
cradle and reinforcing the cradles and panel supporters. automatic connection type of terminal.
˙Each component is mounted on the main unit and the cradle. ˙It cannot be applied to fixed type ACB and draw-out type ACB
Add AF in the respective order form of the main unit and cradle with manual connection terminal.
when placing the order. ˙As a product mounted on the cradle, add BC when placing an
order for the draw-out type with automatic connection type.

Control Terminal Protection Cover

Fixing Block
Air Circuit Breakers 71

VCB
Terminal Bus Bar (Draw-Out Type)
˙HG-Series ACB is compatible with various type of terminal bus bar such as vertical, horizontal, front and others depending on the type
of bus bar of the customer’s equipment and the terminal can be changed to A frame (630 ~ 1,600 A) and B frame (630 ~ 3,200 A).
˙The front type of terminal bus bar is released separately from the main unit and cradle so it needs to be installed at site. In addition,
the front type of terminal bus bar requires separate order so refer to the following table when placing the order.
˙As for the front type of terminal bus bar that is provided separately for the B frame 2,000/2,500 A, 3,200 A terminal is provided.
˙Front type of terminal bus bar is sold separately.

Mixed Type Standard Type

ACB
(Upper) Vertical Type (Upper) Horizontal Type (Upper) Vertical Type Vertical Type Horizontal Type Front Type
+ + +
(Lower) Horizontal Type (Lower) Vertical Type (Lower) Front Type

MCCB
(Upper) Horizontal Type (Upper) Front Type (Upper) Front Type
+ + +
(Lower) Front Type (Lower) Vertical Type (Lower) Horizontal Type

MS
Ordering Method

Order Name for Separate Sales


Name of Accessory Detailed Specification
(HGNS-)

HGNS HVA3 Up-Down Horizontal Type/Up-Down Vertical Type 6 ea (A Frame, 630 ~ 1,600 A, 3P)
HGNS HVA4 Up-Down Horizontal Type/Up-Down Vertical Type 8 ea (A Frame, 630 ~ 1,600 A, 4P)
HGNS HVB3 Up-Down Horizontal Type/Up-Down Vertical Type 6 ea (B Frame, 2,000 ~ 3,200 A, 3P)
HGNS HVB4 Up-Down Horizontal Type/Up-Down Vertical Type 8 ea (B Frame, 2,000 ~ 3,200 A, 4P)
HGNS FRA3 Up-Down Front Type 6 ea (A Frame, 630 ~ 1,600 A, 3P)

Connection Terminal HGNS FRA4 Up-Down Front Type 8 ea (A Frame, 630 ~ 1,600 A, 4P)
RELAY

(Draw-Out Type) HGNS FRB3 Up-Down Front Type 6 ea (B Frame, 2,000 ~ 3,200 A, 3P)
HGNS FRB4 Up-Down Front Type 8 ea (B Frame, 2,000 ~ 3,200 A, 4P)
HGNS FHVA3 Up-Down Front Type 3 ea + Horizontal Type/Vertical Type 3 ea (A Frame, 630 ~ 1,600 A, 3P)
HGNS FHVA4 Up-Down Front Type 4 ea + Horizontal Type/Vertical Type 4 ea (A Frame, 630 ~ 1,600 A, 4P)
HGNS FHVB3 Up-Down Front Type 3 ea + Horizontal Type/Vertical Type 3 ea (B Frame, 2,000 ~ 3,200 A, 3P)
HGNS FHVB4 Up-Down Front Type 4 ea + Horizontal Type/Vertical Type 4 ea (B Frame, 2,000 ~ 3,200 A, 4P)
72 Air Circuit Breakers

Accessories
Arc Shield
˙Arc which occurs while breaking the circuit breaker is Ordering Method
extinguished through the arc chamber within the main unit or
as the residual arc is discharged to the external upper part, the Order Name Order Name for
Name of
Placed upon Separate Sales Detailed Specification
Accessory
basic distance required for insulation has to be maintained. Outgoing (HGNS-)

˙When mounting the arc shield, the insulation distance can


HGNS AXA3 A Frame, 630 ~ 2,000 A, 3P
be minimized to “0” due to the residual arc discharged to the
HGNS AXA4 A Frame, 630 ~ 2,000 A, 4P
upper part. HGNS AXB3 B Frame, 2,000 ~ 4,000 A, 3P
˙When mounting the arc shield, it can be piled in 4 stories. HGNS AXB4 B Frame, 2,000 ~ 4,000 A, 4P
˙As a product mounted on the cradle, add AX in the order form Arc Shield AX
HGNS AXC3 C Frame, 4,000 ~ 5,000 A, 3P
when placing the order for the cradle. HGNS AXC4 C Frame, 4,000 ~ 5,000 A, 4P
HGNS AXD3 D Frame, 4,000 ~ 6,300 A, 3P
HGNS AXD4 D Frame, 4,000 ~ 6,300 A, 4P

Arc Shield
Air Circuit Breakers 73

VCB
RCTU Temperature Monitoring Device Module
˙This product is a module that closes and prevents the ACB ˙This product detects the bus bar temperature of the ACB
remotely by using communication. through the temperature sensor installed on the temporary
˙This product uses Modbus/RS-485 communication. location of ACB and displays it.
˙Close/Open control of ACB assures its reliability through SBO ˙Up to 3 temperature sensor can be installed and it can trigger
(Select Before Operation) function. the designated temperature alarm through a separate
˙It can be used together with the temperature monitoring device temperature contact.
module and as for the detailed rating, refer to the table in Page 98. ˙It supports Modbus/RS–485 communication and the each
channel’s temperature value and the maximum temperature
value out of the channel are transmitted through
Contact Specification
communication.

ACB
For ACB Control Applicable Range ˙The alarm for operating temperature value can be set through
Contact Ratings 10 A 240 VAC, 30 VDC communication.
Max Switching Power 10 A 240 VAC, 30 VDC ˙The temperature value of each channel can be checked
through the Segment LED mounted at the front and once it
Dimension reaches the temperature alarm set by the user, the temperature
value of the relevant channel is displayed.

105
˙As a product sold separately, it can be installed in the ACB and
7(Panel Protrusion) 70
the internal panel. As a module that can be used together with
the remote breaking module, refer to the table on Page 98.
˙This product is an optional product of remote breaking module
and it is only sold as a combination type with the remote
91.4
75

60

MCCB
breaking module.
121.4
33
2-Ø4.2 (Use M4 X 25L Screw) 77 Contact Specification

Temperature Alarm Applicable Range


Contact Ratings 10 A 120 VAC/5 A 240 VAC, 5 A 30 VDC
Max Switching Power 1,200 VA, 150 W

Remote Control Temperature Unit (RCTU) /


Temperature Monitoring Device Module

MS
RELAY
74 Air Circuit Breakers

Accessories
Temperature Sensor Unit
˙Detailed specification of Remote Control Temperature Unit (RCTU) Contact Specification
- RCTU is equipped with a contact that enables remote
Item Applicable Range
insertion/disconnection of ACB using communication.
Contact Ratings 10 A 240 VAC, 30 VDC
Through the 4 temperature channels, the temperature of ACB ACB Control
Max Switching Power 2,400 VA, 300 W
is measured.
Temperature Contact Ratings 10 A 120 VAC/5 A 240 VAC 5 A 30 VDC
- RCTU supports RS-485/Modbus-RTU communication. Alarm Max Switching Power 1,200 VA, 150 W
- Insertion/disconnection control of ACB assures its reliability
through SBO (Select Before Operation) function.
- If the temperature rises over the value set by the user through
communication, it can be checked through the alarm
contacting point (Additional connection required).
- The temperature of ACB can be checked through the Segment
LED at the front.
- RCTU can be installed in the ACB’s cradle or panel.
- RCU module is equipped with the same function other than
LED
the temperature monitoring function in the RCTU module.

Status Indicating LED Details


Run LED RCTU Operation Status LED

RCTU Com LED Communication LED


Status Temp. Alarm LED Temperature Alarm LED
Alarm DO LED Temperature Alarm Output Contact LED

Universal DI1 Dry Contact (5 V)


Digital Input DI2 Dry Contact (5 V)
CB Close ACB Close Status LED

Temperature CB Open ACB Open Status LED


Alarm
ACB Close/Open Terminal
CB Error
Non Contacted and Control Error Status
Communication Temperature
Setting Indication

Terminal Block

No. Definition No. Definition


1 DI1 + 17 NTC IR Sensor
2 DI1 - 18 NTC IR Sensor
3 DI2 + 19 IR Sensor 3 AOR (Black)
4 DI2 - 20 IR Sensor 3 GND (Green)
5 DI Close + 21 IR Sensor 3 AOT (Yellow)
6 DI Close - 22 IR Sensor 3 Power (Red)
7 DI Open + 23 IR Sensor 2 AOR (Black)
8 DI Open - 25 IR Sensor 2 GND (Green)
Caution
9 DO Temp. Alarm 25 IR Sensor 2 AOT (Yellow)
1. IR sensor differs in value by the reflectivity of metal surface. Measuring
10 DO Temp. Alarm 26 IR Sensor 2 Power (Red)
point should be varnished or painted with matt black paint depending on
11 DO Close 27 IR Sensor 1 AOR (Black) material.
12 DO Close 28 IR Sensor 1 GND (Green) 2. Measuring point and IR distance differ measuring spot size by D:S ratio.
This sensor has 8:1 scale.
13 DO Open 29 IR Sensor 1 AOT (Yellow)
3. IR sensor should be indicated at the point where there is no gloss surface.
14 DO Open 30 IR Sensor 1 Power (Red) 4. IR sensor distance:The ratio of measurement locations is 8:1. The
15 AC Power 31 RS485 (-) diameter measured by the IR sensor is 1 cm when it is 8 cm away from the
measurement position.
16 AC Power 32 RS485 (+)
Air Circuit Breakers 75

VCB
Block Diagram

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

DI 1 DI 2 ACB Close ACB Open VAC


Input Input (110 ~ 220)

Temperatur ACB ACB


e Alarm Closing Open
Relay Relay

ACB
IR Sensor IR Sensor IR Sensor
NTC No 3 No 2 No 1 RS 485
Sensor
B G Y R B G Y R B G Y R - +

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

MCCB
MS
RELAY
76 Air Circuit Breakers

Accessories
Temperature Sensor
˙The temperature sensor is mounted on the designated position Communication Specification
as standard but another location can be designated by the user. ˙RS-485 (Modbus-RTU)
˙It is sold separately. ˙Baud Rate:9,600, 19,200, 38,400 bps (Default:9,600)
˙Data Bits:8 bits
Ordering Method ˙Parity:None
˙Stop Bits:1 bits
Order Name for
Name of Detailed
Separate Sales
Accessory Specification
(HGNS-) Address Setting:1 ~ 240

Temp Sensor HGNS TSN Temperature Sensor On

HGNS RCU Remote Control Trip Module


1 2 3 4 5 6 7 8
Remote Control Trip Module +
HGNS RCTU Temperature Monitoring Device
Remote Control Module
Trip Module

Remote Control Trip Module +


HGNS RCTUN Temperature Monitoring Device
Module + Temperature Sensor

Physical Medium
˙Shielded Twister Pair cable used

Baud Rate Setting


Caution
On Set Description
1. The use of Shielded Twisted Pair cable is recommended.
2. The maximum length for connection can be 1 km but the communication Off Off 9,600
length may become shorter depending on the installation environment 1 2 Off On 19,200
and the number of device connected to the communication line.
On Off 38,400
3. The communication length may differ depending on the communication
speed.
Air Circuit Breakers 77

VCB
IR (Infrared Sensor) Specification (Option)

IR Sensor Example of IR Sensor Application

Mounting Bolt ACB Terminal


Sensor (Important : Black Colored) Mouting Bolt ACB Terminal
Supporter Plate Sensor (Important : Black Colored)
Supporter Plate

ACB
Sense on Bolt or Busbar RCTU Sensor
Busbar
Busbar
RCTU Sensor
Distance = 40 ~ 80 mm

* How to Install
Distance = 40 ~ 80 mm

Pulsed Point Radiation Source Limits


Sensitivity Parameter Unit Conditions
Min Typ Max
100 %

MCCB
Cable Length 3 m
Field of View
50 % at Half Energy Points Optical Axis - 3.5 0 + 3.5 Degree Sensor View Direction
Field of View 6 11 Degree 50 % Energy Points

Angle of Incidence D:S Ratio 8:1 Distance (mm) to Spot Size


Rotated Sensor Module

IR Sensor Measurement
˙IR temperature sensor has to be installed with sufficient insulation distance from the measuring point.
˙The recommended distance between the measuring point and the temperature sensor is 50 ~ 80 mm.
˙The measuring point must be a surface without reflection due to the characteristics of the IR sensor and black matte painting is
recommended at the measuring point.
MS
Caution

1. As for the IR sensor, the measurement value differs depending on the reflection rate of the metal surface. Measuring point with surfaced painted with matte black
or varnish other than metallic varnishing must be measured.
2. As for the surface to be measured and the IR distance, the size of measurement area differs depending on the D:S Ratio. This sensor has a ratio of 8:1.
RELAY
78 Air Circuit Breakers

Accessories
Temperature Sensor
Control Contact Connection

HGN
ACB Information Pin

a Contact b Contact Test Connection


45, 47, 49 55, 57 61 71
46, 48, 50 56, 58 62 72

ACB Open/Close Control Pin

CC TC
3 7
4 8

Example:When DI input is used as ACB position

ACB Close/Open
ACB Information ACB Position
Control

Close Control Open Control Close Open Test Connection

RCTU
Terminal 11 13 5 7 3 1

3 7 45 47 49 55 57 61 71

ACB
Circuit CC TC

4 8 46 48 50 56 58 62 63 72 73

RCTU
Terminal 12 14 6 8 4 2

INTC Thermistor Specification (Option)


˙The electrical resistance value changes depending on the Parameter Content Conditions
ambient temperature and by measuring the change in value, Length of Cable 1,000 mm
the temperature is displayed.
Ambient Temperature
Resistance Value 10 ㏀ ± 1 %
˙The length of the cable is 1,000 mm and it measures the value of 25 ℃
of ambient temperature where in the RCTU has been installed.
˙The range that can be measured is -50 ~ 250 ℃.
Air Circuit Breakers 79

VCB
OCR Portable Checker
˙OCR Portable Checker (Hereinafter referred to as the Checker)
executes the relay test operation of the OCR (Hereinafter
referred to as the OCR) (Long time/short time delay/
instantaneous/ground fault).
˙It is possible to set the current size and phases using button for
the OCR test.
˙The relay test factors can be set through the front LCD and the
operating time can be checked.
˙It is equipped with a battery so it can be used without a
separate external power.

ACB
˙As for the cable connector of the checker, connect when the
control power of OCR is off when inserting the OCR.
˙As a product sold separately, place an order for HGNS OCC.
˙HGNS OCC is a product with a calibration certificate issued by a
specializing institute.

Ratings

Item Detailed Specification

Input:AC/DC 100 ~ 220 V, 50/60 Hz


External Power (Adaptor)
Output:DC 24 V, 2.5 A

MCCB
Battery Alkaline 9 V:3 ea
Trip Time Measurement 0 ~ 999.999 sec
Test Output 0.3 Ict ~ 17 Ict
Output Precision ± 20 % (1 Ict ~ 17 Ict)
Size (mm) 193.40 (H) × 110.60 (W) × 44.60 (D)

Key Pad Externals

❶ ❷ ❸ ❹ ❸ ❹

110.60


MS
193.40


❺ ❻
44.60

No. Button Application No. Content Function


RELAY

❶ UP Move Menu and Increase Setting Value ❶ LCD Indicates Menu, Setting Current, Trip Time
❷ DOWN Move Menu and Decrease Setting Value ❷ Key Pad Move Menu and Setting
❸ FUNC Move to the Previous Menu and Return to the Setup Screen ❸ Signal Output Terminal OCR Connection Terminal

Save the Setting and Move the Number of Digits of ❹ Power Switch Power On/Off
❹ ENTER
Setting Current ❺ Adapter Terminal Control Terminal of Checker
❺ START Generate Waveform
❻ STOP Stop Waveform
80 Air Circuit Breakers

Accessories
OCR Checker
Multi-functional OCR checker is test equipment that can inspect Rating Specification
the OCR operation in unloaded status and the OCR status can be Control Power AC/DC 85 ~ 270 V (50/60 Hz)
inspected through communication.
Output Channel:4 (R, S, T, N)
Output Test Output:0.4 ~ 17 Ict
˙Control Power:AC/DC 85 ~ 270 V (50/60 Hz) Precision:± 3 %

˙Specification
Communication:RS 485
Input
- Dimension:411 (L) × 321 (W) × 165 (H) Touch-Screen of HMI
- Weight:8 kg Size 411×321×165 mm, 8 kg
˙Key Functions
- I nspection of LTD, STD, INST, GFT operation and operating time
- Inspection of PTA operation (Pre Trip Alarm)
- Touch LCD
Air Circuit Breakers 81

VCB
NCT (Neutral CT)
˙It is a separate mounting type of current transform installed Ordering Method
in the N phase in case of protecting the earth fault by using
Name of Order Name for
3-pole air circuit breaker with earth fault protection features in Accessory Separate Sales (HGNS-)
Detailed Specification

a 3 phase 4 line circuit. It clarifies the GFT operation caused by


HGNS NCT_T NCT T = 630 A/Inner Diameter 80
earth fault by detecting currents flowing in the N phase.
HGNS NCT_H NCT H = 800 A/Inner Diameter 80
˙The phase is important for inserting the relay so connect HGNS NCT_J NCT J = 1,000 A/Inner Diameter 80
properly to the designated terminal. HGNS NCT_K NCT K = 1,250 A/Inner Diameter 80
˙As a product sold separately, place the order using the following HGNS NCT_L NCT L = 1,600 A/Inner Diameter 80
form name per rated current. Neutral CT HGNS NCT_M NCT M = 2,000 A/Inner Diameter 135
˙Switch the OCR’s switch from 3P to 4P after connecting the NCT

ACB
HGNS NCT_N NCT N = 2,500 A/Inner Diameter 135
power (k), 30 (ℓ) to the 3-pole circuit breaker. HGNS NCT_P NCT P = 3,200 A/Inner Diameter 135
HGNS NCT_Q NCT Q = 4,000 A/Inner Diameter 200
HGNS NCT_S NCT S = 5,000 A/Inner Diameter 200
HGNS NCT_X NCT×= 6,300 A/Inner Diameter 200
Externals

Unit:mm

630 ~ 1,600 A 2,000 ~ 3,200 A 4,000 ~ 6,300 A

150 W

K 4- 4-
Ø1 Ø1

MCCB
4 4
Ø80
175

Sec. M5
35 00
Ø1 Ø2
300
240

300
300
240

300
97
25

80
107 100
75 SUS 2T
30
30

30 240 40 30 240 40
17.5

300 300

10

MS
RELAY
82 Air Circuit Breakers

Accessories
CTD-Condenser Trip Device
˙In case of using AC/DC power for trip control of the circuit
breaker, it is a device that can electrically trip the circuit breaker
once by using the power charged in the CTD when the supply of
control voltage has been stopped due to black-out and others.
˙It is a product sold separately.

Ordering Method Connection Diagram

Order Name for Power


Name of Detailed
Separate Sales
Accessory Specification
(HGNS-) U V
CTD
HGNS CTD1 AC/DC 110 V P N
CTD
HGNS CTD2 AC/DC 220 V

PB(Open)
7

Ratings

Item Details
YC
Rated Input Voltage AC 110 V AC 220 V
Normal Charging Voltage DC 145 V DC 290 V
Normal Current Capacity DC 2 A
Rated Frequency 50/60 Hz
Delay Circuit Time Within 1.5 sec 8

Applicable Standard IEC 60694/KSC 4611

Operating Sequence of CTD External Operation Circuit

Unit:mm

72 130 1 6

7
R1
6

2

SA RY R2 R3
22
72

SW C1 NL

2
80 5
3 4
90

˙AC Input Power NO. 1, 2 ˙DC Normal Power NO. 6 (+), 5 (-)
˙CTD Trip Power NO. 7 (+), 5 (-) ˙Delay Contact NO. 3, 4
Air Circuit Breakers 83

VCB
Test Jumper
˙It is a device that enables the main unit to be operated
independently by separating the automatic connection type of
main unit from the cradle.
˙As a product sold separately, place an order for HGNS AJ when
ordering.

ACB
190
Draw-In/Out Handle 770

˙The draw-in/out handle for drawing the draw-in type of circuit


breaker is provided basically.

MCCB
˙In case the standard handle is uncomfortable when drawing
the circuit breaker in and out, Long Type Handle and Universal
Joint Handle which are sold separately can be used.
˙As a product sold separately, place an order of HGNS LHANDLE
or HGNS UHANDLE.

190
190

750

770

Type

Long Type Handle Universial Joint Handle T-Type Handle

MS
620
190
190

770 750
400

Ordering Method
RELAY

Order Name Placed Order Name for


Name of Accessory Detailed Specification
upon Outgoing Separate Sales (HGNS-)

HGNS HANDLE Standard Handle (Provided as Standard)


190

620

HGNS LHANDLE Long Type of Draw-In/Out Handle (For ACB)


Draw-In/Out Handle 750 -
HGNS UHANDLE Universal Joint Type of Draw-In/Out Handle

400 HGNS THANDLE T-Type, Long Type Handle


84 Air Circuit Breakers

Accessories
Door Flange Dust Cover
˙It is an auxiliary device mounted on the cutting part of the panel ˙It is a device installed to protect against dust and moisture
door at the front protrusion mounting type of ACB. mounted on the cutting part of the panel door at the front
˙The door flange of our company is IP30. protrusion mounting type of ACB.
˙As for the cutting dimension of the panel, refer to the external ˙The dust cover of our company is IP52.
drawing. ˙The cover can be locked in the test and connected position.
˙As for the panel cutting dimension, it is equivalent for both the ˙The cutting dimension of the panel must be referred to.
draw-out and fixed type and it is the same even if the dust cover ˙As a product sold separately, place an order for HGNS DC.
is installed.
˙As a product sold separately, place an order for HGNS AG.

Panel Door Cutting Dimension Panel Door Cutting Dimension

Unit:mm Unit:mm
Operaing
Panel Center
292
196 196 R5
R5 4-
103.5 100 103.5 4- 292 292
4- 2
Ø5 42.5 103.5 100 103.5 42.5 Ø5. 103.5 100
.2 4-
122.5

20

122.5
15
345
115

290

229
115
345
4

122.5
12

4

7.5

122.5
12

68.6 15
7.5
Bottom
20

7.5 Bottom Bottom


25.6

33.1

7.5 25.6

Operaing
Panel Center
196 196 R5
4- 292
292 103.5 100
4-
Ø5 42.5 103.5 100 103.5 42.5 5 .2
.2 4 -Ø
20

122.5
15
290

229
115
345

Door Flange
4

122.5
12

68.6 15
7.5
20

Bottom
Bottom
Dust Cover
33.1

7.5
25.6
Air Circuit Breakers 85

VCB
ATS & Controller
Features
˙Stable Transfer System
By applying Hyundai air circuit breaker equipped with the
highest rated breaking capacity in Korea, it has outstanding
protective features with regards to electric power system, 4
making it optimal for places in which stable power supply is
compulsory (Communication base station, computer center,
hospital, plant equipment and other important facilities).
˙Unmanned Working System
Unmanned power transfer is possible by applying automatic

ACB
power control device in the ACB equipped with mechanical
interlock device.
˙Various Modes ACB1
Various modes is possible as it is equipped with 4 selection 3

models for user convenience.


˙Multi Protection Device
The multi protection device installed in ACB has self-
monitoring, simple set up and various protecting functions.
Unlike the existing ATS, short circuit and overload protection
are possible for stable use.
˙Compact Size, Lightweight

MCCB
ACB is more compact and lightweight so it can easily be
3 ACB2
installed in the ATS switchgear and occupies less space.
˙ATS Configuration and Interlock
- ACB1:“Normal” power (Power company side)
- ACB2:“Stand-by” power (Power generator side)
- 3:Mechanical interlock device unit
- 4:ATS unit
Each ACB should meet the following specifications.
- Geared charge type of mechanism (Control power of AC 220 V)
- TC (Control power of AC 220 V)
- CC (Control power of AC 220 V)
- Trip device for overload or short protection (2a contact)
MS
Transfer System’s Interlock Conditions

ACB1 ACB2
Open Open
Close Open
Open Close
RELAY

ACB1 ACB2

※ As a product sold separately, place an order for HGNS ATS when placing an order.
However, M1 has to be ordered separately and B0, BA must be added when placing an
order for the product.
86 Air Circuit Breakers

Accessories
ATS & Controller
Characteristics per Mode
There are 4 selection modes.

˙Stop/Manu Mode
220/240 V 50/60 Hz t1
This mode offers On/Off functions using ACB Manual from the 1
2 4
8
N UN = 0
power company side and generator side. N UN R UR 0.5 15
0.1 30

˙Auto Mode
ON/I ON/I
This mode is for automatically controlling the ACB depending 0.5 s 0.5 s

on the sequence of system operation flow chart in the OFF/0 OFF/0


t2 15 30
controller.
8 60
4 120

˙N Mode (Forced Operation of Power Company Power) Fault Fault 0.1 240
UN = I R

This mode turns off the ACB at the generator side and turns on
Reset
the ACB at the power company side by force. Stop Auto
˙R Mode (Forced Operation of Generator Power) Manu

This mode turns off the ACB at the power company side and
turns on the ACB at the generator side by force.
N R

Time Delay Adjustment Indication of the Controller’s Status


t1:0.1 ~ 30 sec On, Off, Fault Indication
t2:0.1 ~ 240 sec (Power Company Side, Generator Side)

Operation Characteristics
T1 (ms) T2 (ms)
Status
0.1-30 500 250 0.1-240 500 250

UN (Normal Power) or I (On)


KT (Forced Operation
Control Signal of
Stand-by Power) ○ (Off)

I (On)

UR (Stand-by Power)

○ (Off)

I (On)

KR (Re-Inspection)

○ (Off)

I (On)
QN (Normal
Power Cut-Off)
○ (Off)

I (On)
QR (Stand-by
Power Cut-Off)
○ (Off)
Air Circuit Breakers 87

VCB
System Operation

Stop Mode Auto Mode N Mode (“Normal Mode” Forced ON)

N R
4-Position Switch
ACB1 and ACB2 “Normal”
Off (N Position, UN Supplied)
Manual Trip Power ON

I O

ACB
ACB2 Trip
Voltage Un Lost (More than setting value of 1 t)
Auto Mode
or when Auto Switching Command is Received

t > 0.5 s
ACB1 Trip
Reset 1s

ACB1 Input
t > 0.5 s
Reset Complete

“Stand-by” ACB1 Closed


ACB2 Input
Power ON
N R

Operation Stopped
ACB2 Input Complete

MCCB
N R I O

4-Position Switch Operation

I O
When Voltage on Exists for t > t2 or
when Auto Switch Command is Stopped
R Mode (“Stand-by” Power Forced ON)
ACB2 Trip

t > 0.5 s 4-Position Switch


(R Position, UR Supplied)

MS
ACB1 Input
ACB1 Trip

ACB1 Input Complete t > 0.5 s

ACB2 Input

ACB2 Input Complete

N R
RELAY

˙ACB1:HGN (S) ACB1 “Normal” Power (Power Company Side)


I O
˙ACB2:HGN (S) ACB2 “Stand-by” Power (Generator Side)
˙UN:“Normal” Power Voltage 4-Position Switch Operation
˙UR:“Stand-by” Power Voltage
88 Air Circuit Breakers

Accessories
ATS & Controller
Circuit Diagram of the System [ HGS/HGN Type ]

Auto Switch System’s Auxiliary Device Circuit Diagram

“Normal” Circuit Breaker’s Auxiliary Device


1)

1
STOP
2 1
Power Company ON 1
Control Circuit Terminal Block

Control Circuit Terminal Block


3 2
Generator ON 2
4 3
AUTO 7
5 4
COMMON 3
6 5
54 53 43 37 7 1 3
7 6
For 37
8 7
communi 53 Spring
9 8
-cation 43 Charge
10 “OFF”SW

B1
A1

A1

AUX.SW.
1
1
Control Circuit Terminal Block

1 2 TC M CC
COMMON 2
Control Circuit Terminal Block

2 3
STOP 7

OCR Alarm SW.


3 4
Power Company ON Aux. Switch per Mode 3
4 5
Generator ON 54
AUX. SW.

5 6
AUTO 37
7
53
8
43
54 44 38 8 2 4

※ 1) The standard model is a SW mounting type on controller. (Control terminal type is not a standard model)

Auto Power Switch System’s Auxiliary Device Circuit Diagram applied with 2 ACBs

Power Company Generator


Side Side 20
1
3 19
18
7
17
19
T 16
20
15
37
14
38
13
ATS Terminal Block

45
R S T R S T
12
MCCB at MCCB at 46
Power Company Generator 11
47
Side Side 10
48
9
55
Controller IVE 56
8
7
N R 57
6
58
5
4
3
2
1

20
1
3 19
18
7
17
19
16
20
15
37
14
38
13
ATS Terminal Block

45
12
46
11
47
10
48
9
Power Company Side ACB 55
56
8
7
57
6
58
5
4
3
2
Generator Side ACB 1
Air Circuit Breakers 89

VCB
“Stand-by” Circuit Breaker’s Auxiliary Device

37 38 OCR DO
53 43 37 7 1 3
43 44 Auxiliary a Switch Terminal

ACB
Spring 53 54 Auxiliary b Switch Terminal
Charge
“OFF”SW TC Voltage Trip
B1
A1

A1

AUX.SW.

7 8 Voltage Trip Power Terminal


1 2 Geared Charge Power Terminal
3 4 Power Terminal for Close
TC M CC

Charging Motor
OCR Alarm SW.

M
Latch Release (Close)
AUX. SW.

CC

54 44 38 8 2 4

MCCB
ATS Panel Remote Circuit Diagram

1
PB (Close) Power is supplied from ATS controller so
3
ATS Controller at Power Company Normal PB (Open) power should not be applied from outside. 1)
7
Control Voltage (AC 220 V) ACB 19
20 OCR Control Power AC/DC 100 ~ 250 S0-S2
N R
ATS Terminal Block

37
38 OCR + OCGR “1a” Contact
45
46
47
48
55
AUX. SW. 2a-2b
MS
56
57
58

1
PB (Close) Power is supplied from ATS controller so
Stand-by 3
PB (Open) power should not be applied from outside. 1)
7
ACB 19
20 OCR Control Power AC/DC 100 ~ 250 S0-S2
ATS Terminal Block

37
38 OCR + OCGR “1a” Contact
45
46
RELAY

47
48 AUX. SW. 2a-2b
55
ATS Controller at Generator Side 56
Control Voltage (AC 220 V) 57
58

※ 1) Upon remote operation, as for the Open/Close power, the power is supplied from the ATS control device so do not input a separate control power supply. (Terminal number “1”, “7”, “16”)
90 Air Circuit Breakers

Accessories
ATS & Controller
Dimensions [ ATS HGN A Frame ]

Unit:mm
HGN06 ~ 16 A [ Front ] [ Vertical Type ] [ Horizontal Type ]

40 470
89 220 89
20.5 128 36 154
27.5
245

46.3
46.3
39.9 79 39.9 79

50 94.1 50

15

159.1
343
20.1

15
1,810

420.9

455.9
1,440
615

50 94.1 50

15

159.1
343
20.1

15
357.05

374.55
250

107 296 50 235 50 235


560 335 335
600 435 435

Unit:mm
HGN20 A [ Front ] [ Vertical Type ]

40 89
128 36 154
20.5
27.5
245

46.3
39.9 79
75 69.1 75
343
20.1
1,810

395.9
1,440

615

75 69.1 75
343
20.1

344.6
250

107 296 50 235


560 335
600 435

※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 91

VCB
Dimensions [ ATS HGN B Frame ]

Unit:mm
HGN20 ~ 25 B [ Front ] [ Vertical Type ] [ Horizontal Type ]

140
40 89 89
128 36 154
27.5
20.5
245

39.9 79 48.3 39.9 79 48.3

ACB
75 68.1 75

20 20
163.1
343
20.1
1,810

396.9

451.9
1,440
615

75 68.1 75

20 20
163.1
343
20.1

345.05

372.55

MCCB
250

154.7 296 50 235 50 235


660 335 335
700 435 435

Unit:mm
HGN32 B [ Front ] [ Vertical Type ] [ Horizontal Type ]
140
40 89 89
128 36 154
27.5

20.5
245

39.9 79 48.3 39.9 79 48.3

MS
20
90 53.1 90

123.1
343

20
20.1
1,810

615
381.9
1,440
615

20
90 53.1 90

163.1
343

20
20.1

RELAY
372.55
337.55
250

154.7 296 50 235 50 235


660 335 335
700 435 435

※ The drawing dimension of this page may be subject to change without prior notice.
92 Air Circuit Breakers

Accessories
ATS & Controller
Dimensions [ ATS HGN B Frame ]

Unit:mm
HGN40 B [ Front ] [ Vertical Type ] [ Horizontal Type ]
140
40
128 36 154 89 89
27.5

20.5
245

39.9 79 90.3 39.9 64.3


79

15
125

40 128 40
15
343

68

15
125
20.1
1,810

15

407
297
1,440

15
615

68 125

40 128 40
15
343

15
125
20.1

15

362.55
295.05
250

154.7 296 50 235 50 235


660 335 335
700 435 435

※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 93

VCB
Dimensions [ ATS HGN C Frame ]

Unit:mm
HGN40 ~ 50 C, [ Front ] [ Vertical Type ] [ Horizontal Type ]

3P
240
40 89 89
128 36 154
20.5
27.5
245

39.9 79 39.9 79 66.3


66.3

ACB
20
110 86.1 110
125 69.1 125

20
343

20
20
20.1
1,810

295.9

308.9
1,440

615

20
110 86.1 110
125 69.1 125

20
343

20
20
20.1

301.1
294.5

MCCB
250

415.2 296 50 235 50 235


760 335 335
800 435 435

Unit:mm
HGN40 ~ 50 C, [ Front ] [ Vertical Type ] [ Horizontal Type ]

4P 440
40 128 36 154 89 89
20.5
27.5
245

39.9 79 66.3 39.9 79 66.3

MS
125 69.1 125

110 86.1 110


20
20
343

20
20
1,810

20.1

295.9

308.9
1,440
615

125 69.1 125

110 86.1 110


20
20
343

20
20
20.1

RELAY
301.1
294.5
250

500.2 296 50 235 50 235


960 335 335
1,000 435 435

※ The drawing dimension of this page may be subject to change without prior notice.
94 Air Circuit Breakers

Accessories
ATS & Controller
Dimensions [ ATS HGN D Frame ]

Unit:mm
HGN40 D, 3P [ Front ] [ Vertical Type ] [ Horizontal Type ]

440
40 128 36 154 89 89
27.5
245 20.5

39.9 79 71.9 39.9 79 71.9

20
110 83.1 110
125 68.1 125

20
343

20
20
1,810

19.1

311.9
295.9
1,440
615

125 69.1 125

20
110 83.1 110
20
343

20
20
19.1

302.5
294.5
250

572.6 270 50 235 50 235


960 335 335
1,000 435 435

Unit:mm
HGN40 D, 4P [ Front ] [ Vertical Type ] [ Horizontal Type ]

40 128 36 154 89 89
20.5
27.5
245

39.9 79 71.9 39.9 79 71.9


20
110 83.1 110
125 68.1 125

20
343

20
1,810

20
19.1

311.9
295.9
1,440
615

20
110 83.1 110
125 69.1 125

20
343

20
20
19.1

294.5

302.5
250

647.6 270 50 235 50 235


1,160 335 335
1,200 435 435

※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 95

VCB
Unit:mm
HGN50 ~ 63 D, [ Front ] [ Vertical Type ] [ Horizontal Type ]

3P 440
40 128 36 154
89 89
20.5

27.5
245

39.9 79 71.9 39.9 79 71.9

ACB
68.1 150

20
110 83.1 110
20
343

20
1,810

20
150
19.1

311.9
246.9
1,440
615

68.1 150

20
110 83.1 110
20
343

20
20
150
19.1

302.5

MCCB
250

270

572.6 270 50 235 50 235


960 335 335
1,000 435 435

Unit:mm
HGN50 ~ 63 D, [ Front ] [ Vertical Type ] [ Horizontal Type ]

4P 40 128 36 154 89 89
20.5
27.5
245

39.9 79 71.9 39.9 79 71.9

MS
68.1 150

20
110 83.1 110
20
343

20
1,810

20
150
19.1

311.9
246.9
1,440
615

150

20
110 83.1 110
20
343

68.1

20
150

20
19.1

RELAY
302.5
250

270

647.6 270 50 235 50 235


1,160 335 335
1,200 435 435

※ The drawing dimension of this page may be subject to change without prior notice.
96 Air Circuit Breakers

Accessories
Order Code
Order Form
Name of Accessory Detailed Specification Release Form Page
Mounted Sold Separately
- HGNS HVA3 Up-Down Horizontal/Up-Down Vertical (A Frame, 06 ~ 16A 3P)
- HGNS HVA4 Up-Down Horizontal/Up-Down Vertical (A Frame, 06 ~ 16A 4P)
- HGNS HVB3 Up-Down Horizontal/Up-Down Vertical (B Frame, 06 ~ 32B 3P)
- HGNS HVB4 Up-Down Horizontal/Up-Down Vertical (B Frame, 06 ~ 32B 4P)
- HGNS FRA3 Up-Down Front 6 ea (A Frame, 06 ~ 16A 3P)

Terminal Bus Bar 1) - HGNS FRA4 Up-Down Front 8 ea (A Frame, 06 ~ 16A 4P)
Sold Separately -
(Draw-Out Type) - HGNS FRB3 Up-Down Front 6 ea (B Frame, 06 ~ 32B 3P)
- HGNS FRB4 Up-Down Front 8 ea (B Frame, 06 ~ 32B 4P)
- HGNS FHVA3 Up-Down Front 3 ea + Horizontal/Vertical 3 ea 06 ~ 16A 3P
- HGNS FHVA4 Up-Down Front 4 ea + Horizontal/Vertical 4 ea 06 ~ 16A 4P
- HGNS FHVB3 Up-Down Front 3 ea + Horizontal/Vertical 3 ea 06 ~ 32B 3P
- HGNS FHVB4 Up-Down Front 4 ea + Horizontal/Vertical 4 ea 06 ~ 32B 4P
- HGNS FRA3F Up-Down Front 6 ea (A Frame, 06 ~ 16A 3P) + Additional Spacer 6
- HGNS FRA4F Up-Down Front 8 ea (A Frame, 06 ~ 16A 4P) + Additional Spacer 8
- HGNS FRB3F Up-Down Front 6 ea (B Frame, 06 ~ 32B 3P) + Additional Spacer 6
Terminal Bus Bar 2) - HGNS FRB4F Up-Down Front 8 ea (B Frame, 06 ~ 32B 4P) + Additional Spacer 8
(Fixed Type) Sold Separately -
- HGNS FHVA3F Up-Down Front 3 ea + Horizontal/Vertical 3 ea 06 ~ 16A 3P + Additional Spacer 3
- HGNS FHVA4F Up-Down Front 4 ea + Horizontal/Vertical 4 ea 06 ~ 16A 4P + Additional Spacer 4
- HGNS FHVB3F Up-Down Front 3 ea + Horizontal/Vertical 3 ea 06 ~ 32B 3P + Additional Spacer 3
- HGNS FHVB4F Up-Down Front 4 ea + Horizontal/Vertical 4 ea 06 ~ 32B 4P + Additional Spacer 4

Mounted upon Release


Auxiliary Switch 3) MC HGNS MOC External Auxiliary Contact 10a10b (Mechanical Opearting Cell Switch) -
and Sold Separately

Automatic
Connection Control Automatic Connection Control Terminal Cover (Cannot be Mounted on Mounted upon Release
BC HGNS BC -
Terminal Protection Fixed Type, Manual Connection Type) and Sold Separately
Cover

Manual Connector J HGNS MCJ Manual Control Plug Sold Separately -

Manual Connector Mounted upon Release


J HGNS MWIRE Manual Connector Lead Wire -
Lead Wire and Sold Separately

Condenser Trip - HGNS CTD1 AC/DC 110 V


Sold Separately -
Device - HGNS CTD2 AC/DC 220 V
- HGNS UT1 AC/DC 110 V & DC 125 V
- HGNS UT2 AC/DC 220 V
UVT Time Delay
- HGNS UT3 AC 380 V Sold Separately -
Module 4)
- HGNS UT4 AC 440 V
- HGNS UT9 AC/DC 110 V & DC 125 V
V1 HGNS V1 AC/DC 110 V

UVT Time Delay V2 HGNS V2 AC/DC 220 V


Module Mounted upon Release
V3 HGNS V3 AC 380 V -
+ and Sold Separately
UVT Coil V4 HGNS V4 AC 440 V
V9 HGNS V9 DC 125 V
- HGNS OC OCR Portable Checker
OCR Acce Sold Separately -
- HGNS VM Voltage Module

※ 1) Only the terminal bus bar (Draw-out type) A frame 630 ~ 1,600A/B frame 2,000 ~ 3,200 A-draw-out type can be ordered.
2) Only the terminal bus bar (Fixed type) A frame 630 ~ 1,600A/B frame 2,000 ~ 3,200 A-fixed type can be ordered.
3) Contact us when placing an order for set order required for installation.
4) UVT time delay type of controller is mounted outside the main unit or the cradle.
Air Circuit Breakers 97

VCB
Order Form
Name of Accessory Detailed Specification Release Form Page
Mounted Sold Separately

Mounted upon Release


Key Lock AB HGNS AB Key Lock -
and Sold Separately

HGNS AEA3 06A3 ~ 20A3


HGNS AEA4 06A4 ~ 20A4
HGNS AEB3 20B3 ~ 40B3
HGNS AEB4 20B4 ~ 40B4 Mounted upon Release
Safety Shutter AE -
HGNS AEC3 32C3 ~ 50C3 and Sold Separately

HGNS AEC4 32C4 ~ 50C4

ACB
HGNS AED3 40D3 ~ 63D3
HGNS AED4 40D4 ~ 63D4

Mounted upon Release


HGNS AF For Main Unit + Cradle -
and Sold Separately
Fixing Block AF
HGNS AFB For Main Unit + Cradle
Sold Separately -
HGNS AFC For Cradle
AQ HGNS AQ Test 1C, Connected 1C
AR HGNS AR Connected 2C
AS HGNS AS Test 2C
AT HGNS AT Isolated 1C, Inserted 1C
AU HGNS AU Inserted 2C

MCCB
AV HGNS AV Isolated 2C Mounted upon Release
Position Switch 5) -
P4 HGNS P4 Test 2C, Connected 2C and Sold Separately

PS HGNS PS Isolated 1C, Test 1C, Connected 2C


PT HGNS PT Test 4C
PQ HGNS PQ Inserted 1C, Isolated 1C, Test 1C, Connected 1C
P8 HGNS P8 Inserted 2C, Isolated 2C, Test 2C, Connected 2C
PR HGNS PR Inserted 1C, Isolated 1C, Test 3C, Connected 3C

Miss Insertion Mounted upon Release


AW HGNS AW Add Order Form in the Main Unit + Cradle, Main Unit/Cradle Respectively -
Preventor and Sold Separately

HGNS AXA3 06A3 ~ 20A3


HGNS AXA4 06A4 ~ 20A4
HGNS AXB3 20B3 ~ 40B3

Arc Shield AX
HGNS AXB4 20B4 ~ 40B4 Mounted upon Release
and Sold Separately
- MS
HGNS AXC3 32C3 ~ 50C3
HGNS AXC4 32C4 ~ 50C4
HGNS AXD3 40D3 ~ 63D3
HGNS AXD4 40D4 ~ 63D4
- HGNS DWB1 Drawout (Fixed)/Wire Type 2 Way MI
- HGNS DWB2 Drawout (Fixed)/Wire Type 3 Way MI
- HGNS FWB1 Fixed/Wire Type 2 Way MI
- HGNS FWB2 Fixed/Wire Type 3 Way MI
Mech Interlock 6) Sold Separately -
- HGNS DWB1A A Frame, Draw-Out Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS DWB2A A Frame, Draw-Out Type, Wire Type 3 Way MI + Interlock Parts (B0)
RELAY

- HGNS DWB1B B Frame, Draw-Out Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS DWB2B B Frame, Draw-Out Type, Wire Type 3 Way MI + Interlock Parts (B0)

※ 5) Position switch cannot be used together and can only be mounted at the right side of the cradle.
6) Mechanical interlock is a wire type. The MI unit is mounted outside the main unit or on the cradle and the interlock part is mounted inside the main unit.
98 Air Circuit Breakers

Accessories
Order Code
Order Form
Name of Accessory Detailed Specification Release Form Page
Mounted Sold Separately
- HGNS DWB1C3 C Frame 3P, Draw-Out Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS DWB1C4 C Frame 4P, Draw-Out Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS DWB2C3 C Frame 3P, Draw-Out Type, Wire Type 3 Way MI + Interlock Parts (B0)
- HGNS DWB2C4 C Frame 4P, Draw-Out Type, Wire Type 3 Way MI + Interlock Parts (B0)
- HGNS FWB1A A Frame, Fixed Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS FWB2A A Frame, Fixed Type, Wire Type 3 Way MI + Interlock Parts (B0)
Sold Separately -
- HGNS FWB1B B Frame, Fixed Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS FWB2B B Frame, Fixed Type, Wire Type 3 Way MI + Interlock Parts (B0)
- HGNS FWB1C3 C Frame, 3P, Fixed Type, Wire Type 2 Way MI + Interlock Parts (B0)
- HGNS FWB1C4 C Frame, 4P, Fixed Type, Wire Type 2 Way MI + Interlock Parts (B0)
Mech Interlock 6)
- HGNS FWB2C3 C Frame, 3P, Fixed Type, Wire Type 3 Way MI + Interlock Parts (B0)
- HGNS FWB2C4 C Frame, 4P, Fixed Type, Wire Type 3 Way MI + Interlock Parts (B0)
HGNS B0DA A Frame, Interlock Parts (B0)
HGNS B0DB B Frame, Interlock Parts (B0)
HGNS B0DC3 C Frame, 3P Interlock Parts (B0)
HGNS B0DC4 C Frame, 4P Interlock Parts (B0) Mounted upon Release
BO -
HGNS B0FA A Frame, Interlock Parts (B0) + Fixed Bracket and Sold Separately

HGNS B0FB B Frame, Interlock Parts (B0) + Fixed Bracket


HGNS B0FC3 C Frame, 3P Interlock Parts (B0) + Fixed Bracket
HGNS B0FC4 C Frame, 4P Interlock Parts (B0) + Fixed Bracket

ATS Controller UNIT (ATS Controller + 2 Way M/I + Wiring Assemble) for Mounted upon Release
ATS Controller B6B7 HGNS ATS -
Draw Out and Sold Separately

- HGNS RCU RCTU


- HGNS RCTU RCTU + Temperature Monitoring Device Module
RCTU Sold Separately -
- HGNS RCTUN RCTU + Temperature Monitoring Device Module + Temperature Sensor
- HGNS TSN Temperature Sensor
- HGNS NCT_T T = 630 A/Inner Diameter 80
- HGNS NCT_H NCT H = 800 A/Inner Diameter 80
- HGNS NCT_J NCT J = 1,000 A/Inner Diameter 80
- HGNS NCT_K NCT K = 1,250 A/Inner Diameter 80
- HGNS NCT_L NCT L = 1,600 A/Inner Diameter 80
Neutral CT - HGNS NCT_M NCT M = 2,000 A/Inner Diameter 135 Sold Separately -
- HGNS NCT_N NCT N = 2,500 A/Inner Diameter 135
- HGNS NCT_P NCT P = 3,200 A/Inner Diameter 135
- HGNS NCT_Q NCT Q = 4,000 A/Inner Diameter 200
- HGNS NCT_S NCT S = 5,000 A/Inner Diameter 200
- HGNS NCT_X NCT×= 6,300 A/Inner Diameter 200

Mounted upon Release


Door Flange AG HGNS AG IP30 -
and Sold Separately

Dust Cover - HGNS DC IP54 Sold Separately -


Test Jumper - HGNS AJ For Automatic Connection Type of Test Sold Separately -

Mounted upon Release


Short “B” Contact AK HGNS AK Short Circuit “B” Contact -
and Sold Separately

Lifting LUG - HGNS AL 2 ea = 1 set, C Frame 5,000 A is Provided as Standard Sold Separately -

※6) Mechanical interlock is a wire type. The MI unit is mounted outside the main unit or on the cradle and the interlock part is mounted inside the main unit.
Air Circuit Breakers 99

VCB
Order Form
Name of Accessory Detailed Specification Release Form Page
Mounted Sold Separately
On/Off Button Lock AM HGNS AM On/Off Button Cover Lock Sold Separately -

Door Lock (On/Off) - HGNS DL_CO Pannel Door Lock for On/Off (In Case of On) In Course of Development Sold Separately -

Door Lock Pannel Door Lock for Position (In Case of Test or Connected)
- HGNS DL_PO Sold Separately -
(Position) > In Course of Development

Insulation Barrier - HGNS PBAR Insulation Barrier Sold Separately -

- HGNS LHANDLE Long Head Type Draw In-Out Handle

ACB
- HGNS UHANDLE Universal Join Head Draw In-Out Handle
Draw In-Out Handle Sold Separately -
- HGNS THANDLE T Grip Long Type Draw In-Out Handle
- HGNS HANDLE Standard Draw In-Out Handle

MCCB
MS
RELAY
100 Air Circuit Breakers

Dimensions
HGS/HGN Fixed Type 630 ~ 2,000 A (HGS06 ~ 16/HGN06 ~ 20 A Frame) Unit:mm

Front

296 381
404.4

404.4

270
270
176.7 261.7
353.4 438.4

3P 4P

Vertical Type
8 313.4 8 398.4
85 85 85 85 85
15 15
40

40
14

14
186.8
152.5

186.8
152.5

4 4
Ø1 Ø1
20

20
109
109

[ HGS/HGN 630 ~ 1,600 A ] [ HGN 2,000 A ]

35 13
35 13 3-Ø
2-Ø
50
75
50
50

15 15
25

144
330
144
330

75
50

132
132

33
33

60 49 186.8 60 49 186.8
295.8 43.6 295.8 43.6

※ The drawing dimension of this page may be subject to change without prior notice.
As for the HGN fixed type A type 2,000 A, only the vertical terminal can be applicable.
Air Circuit Breakers 101

VCB
Unit:mm

Horizontal Type (630 ~ 1,600 A)

8 313.4 8 398.4
85 85 85 85 85
50 50
8 313.4 8 398.4
85 85 85 85 85
50 50
40

40
14

14
40152.5
186.8

152.5
186.8
4
Ø1

40
14

14
152.5
186.8

152.5
186.8
4
Ø1

ACB
20
20
109

109
20
20
109

109

35 13
2-Ø
15

35 13
50
2-Ø
15
50 25
15
129
144
330

15
25
129
15144
330

132
33

MCCB
15

60 49 186.8
132

295.8 43.6
33

60 49 186.8
295.8 43.6

Front Type (630 ~ 1,600 A) 8 313.4 8 398.4


85 85 85 85 85
50 50
8 313.4 8 398.4
85 85 85 85 85
50 50
40

40
14

14
152.5

152.5
109 152.5 186.8

186.8
40

40
14

14
152.5
186.8

186.8
20

20
109

MS
20

20
109

109

11
2-Ø

11
50
25

2-Ø15
446
330

50
25

15
446
330

RELAY
33

60 49 186.8
38

295.8 15
252.4
33

60 49 186.8
38

295.8 15
252.4

※ The drawing dimension of this page may be subject to change without prior notice.
102 Air Circuit Breakers

Dimensions
HGS/HGN Draw-Out Type 630 ~ 2,000 A (HGS06 ~ 16/HGN06 ~ 20 A Frame) Unit:mm

Front

440 525
416 501

440 525
416 501

438(Manual Control Plug Type)


Plug Type)

460(Auto Connection Type)


Type) Type)

Ø1

Ø1
2.1

2.1
438(Manual Control Plug Type)
Plug Type)
Connection

460(Auto Connection Type)


Ø1

Ø1
ControlControl

2.1

2.1
Connection
438(Manual
460(Auto

278.3
438(Manual
460(Auto

278.3
270 270
164 164 164 249
270 270
328 413
164 164 164 249
3P
328 413 4P
3P 4P

Vertical Type
85 85 85 85 85
15 15 85
85 85 85 85
15 15
28.828.8

28.8
28.8
250250

250
368.4

368.4
250
368.4

368.4

Ø1 Ø1
Ø1 4 Ø1 4
4 4

210 59 210 85
210 59 210 85

[[ HGS/HGN 630~~1,600
HGS/HGN 630 1,600AA] ] [ HGN 2,000 A ]
[ HGN 2,000 A ]
(Test) 26.5 60 (Test) 26.5 60
(Test) 26.5 60 Arc Shield Surface (Test) 26.5 60 Arc Shield Surface
Arc Shield Surface
(Option) Arc Shield Surface
(Isol)
(Isol)11.5
11.5 20.4
20.4 (Option) (Isol)
(Isol) 11.5
11.5 20.420.4 (Option)
(Option)

13Ø1
3 3
3535 35 -Ø13 -Ø1
2-Ø2-
35 3
119.3
119.3 66 119.3 6
119.3 6 3
50
25 50
144 50

50
50

465.875

75
50
75

75
465.8
465.8

465.8

FixingBlock
Fixing Block 1515 Fixing
Fixing BlockBlock 15 15
25

(Option)
(Option) (Option)
(Option)
144
330
330

144

144
330
330
50
132 50

75

75

ØØ13 15
15 Ø13 Ø15 15
132

13
132

13
132

50 250 50 250
50 250 50 250
33.1

33.1
15

15

328.8
33.1

328.8
33.1
15

15

328.8 328.8
352.8 352.8
352.8 352.8
39.6 381.6 39.6 381.6
39.6 381.6 39.6 381.6
421.2 421.2
421.2 421.2

※ The drawing dimension of this page may be subject to change without prior notice.
As for the HGN draw-out type A type 2,000 A, only the vertical terminal can be applicable.
Air Circuit Breakers 103

VCB
Unit:mm

Horizontal Type (630 ~ 1,600 A)


85 85 85 85 85
85 85
50 85 50 85 85
50 50

28.8

28.828.8
28.8
250

250 250
368.4

368.4
250

368.4

368.4
Ø1 Ø1
4 4
Ø1 Ø1
4 4
210 59 210 85

ACB
(Test) 26.5 60 210 59 210 85
Arc Shield Surface
(Isol) 11.5 20.4 (Option)
(Test) 26.5 60 Arc Shield Surface
(Isol) 11.5 20.4 (Option)

119.3 6 35 13
2-Ø
15

119.3 6 35 13
2-Ø

50
465.8

Fixing Block
15

15

25
(Option)
129
144

50
330

465.8

Fixing Block
15
(Option) 25
129
144
330

15

Ø13 15
132
15

50 250 15
Ø13
132
33.1

15

328.8

MCCB
352.8
50 250
39.6 381.6
33.1

15

328.8
421.2
352.8
39.6 381.6
421.2

Front Type (630 ~ 1,600 A)


85 85 85 85 85
50 50
28.8

28.8

85 85 85 85 85
50 50
28.8

28.8
250

250
368.4

368.4

Ø1 Ø1
250

250

4 4
368.4

368.4

210 59 210 85
Ø1 Ø1
(Test) 26.5 60
4
20.4 Arc Shield Surface
4
MS
(Isol) 11.5 (Option)
210 59 210 85

(Test) 26.5 60
20.4 Arc Shield Surface 1
(Isol) 11.5 1
119.3 6 (Option) 2-Ø
50
25

Fixing Block
465.8

15 1
446

(Option) 1
2-Ø
330

119.3 6
50
25

328.8
Fixing Block
465.8

15
446

(Option) Ø13 15
330

39.6 50 250
38
33.1

15

328.8
329.6 15
RELAY

15
352.8 Ø13

39.6 50 250
38
33.1

15

329.6 15
352.8

※ The drawing dimension of this page may be subject to change without prior notice.
104 Air Circuit Breakers

Dimensions
HGS/HGN Fixed Type 2,000 (630) ~ 3,200 A (HGS/HGN20 (06) ~ 32 B Frame) Unit:mm

Front

367 482
404.4

404.4

270
270 212.2 327.2
424.4 539.4

3P 4P

Vertical Type

8 384.4 8 499.4
115 115 115 115 115
20 20
40

40
14

14
186.8
152.5

186.8
152.5
20

20
109

109

[ 630 ~ 2,500 A ] [ 3,200 A ]

35 13 35 13
3-Ø 3-Ø
75

50

90

50
75

90

15 15
144

144
330

330
75

90
132

132
33

33

60 49 186.8 60 49 186.8
295.8 43. 6 295.8 43.6

※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 105

VCB
Unit:mm

Horizontal Type
Model Name Detail“A”
8 384.4 8 499.4 HGN20 (06) ~ 25 75
115 115 115 115 115
90 90 HGN32 90
8 384.4 8 499.4
115 115 115 115 115
90 90
40

40
14

14
186.8
152.5

186.8
152.5
40

40
14

14
186.8
152.5

109186.8
152.5
20

20
109

ACB
20

20
109

109

[ 2,000 ~ 2,500 A ] [ 3,200 A ]

35 13 35 13
[ 2,000 ~ 2,500 A ] 3-Ø [ 3,200 A ] 3-Ø

90
50
75

50
35 13 35 13
-Ø 3-Ø
153 15
330

144
330

144

90
50
75

50
15 15
330

144
330

144

20
20

132
132
33

33

60 49 60 49

MCCB
186.8 186.8
20
20

132
132

295.8 43.6 295.8 43.6


33

33

60 49 186.8 60 49 186.8
295.8 43.6 295.8 43.6
8 384.4 8 499.4
Front Type 115 115 115 115 115
75 75
8 384.4 8 499.4
115 115 115 115 115
40
40

75 75
14

14
152.5
152.5

186.8
186.8

40
40

14

14
152.5
152.5

109186.8
109186.8

20
20

MS
20
20

109
109

11
3-Ø
75
50

11
3-Ø
15
484
330

75
50

15
484
330
33

60 49 186.8
38

20
RELAY

295.8
33

257.4
60 49 186.8
38

295.8 20

257.4

※ The drawing dimension of this page may be subject to change without prior notice.
106 Air Circuit Breakers

Dimensions
HGS/HGN Draw-Out Type 2,000 (630) ~ 3,200 A (HGS/HGN20 (06) ~ 32 B Frame) Unit:mm

Front

511 626
487 602

511 626
487 602
438(Manual Control Plug Type)

438(Manual Control Plug Type)


460(Auto Connection Type)
460(Auto Connection Type)

Ø1

Ø1
2.1

2.1
438(Manual Control Plug Type)

438(Manual Control Plug Type)


460(Auto Connection Type)
460(Auto Connection Type)

Ø1

Ø1
2.1

2.1

278.3
278.3

278.3
278.3

270 270
199.5 199.5 199.5 314.5
270 270
199.5 399 199.5 199.5 514
314.5
399 514
3P 4P
3P 4P

Vertical Type 115


115
115
115 115
115
115
115
115
115
20 20
20 20
28.8
28.8

28.8
28.8

250
250

250
250

368.4
368.4
368.4
368.4

ØØ114 Ø1 Ø
4 14
4

210 94.5 210 115


210 94.5 210 115

[ 630 ~ 2,500 A ] [ 3,200 A ]


[ 630 ~ 2,500 A ] [ 3,200 A ]
(Test) 26.5 60 (Test) 26.5 60
Arc Shield Surface (Test) 26.5 60 Arc Shield Surface
(Test) 26.5 60 (Isol) 11.5 20.4 Arc Shield Surface
(Option)
(Isol) 11.5 20.4 Arc Shield Surface
(Option)
(Isol) 11.5 20.4 (Option) (Isol) 11.5 20.4 (Option)

13
35 13
35
3-Ø 119.3 6 3-Ø
119.3 6 3 35 13
119.3 6
35
3-Ø
1
119.3 6 3-Ø
90

90
50
75 75

50 75
50

465.8

Fixing Block
465.8

Fixing Block
90

90
50

(Option) 15
75

(Option) 15
143

465.8
330
330

Fixing Block
143

465.8

Fixing Block
(Option) 15 (Option) 15
143
330
330

143

90
75 75

132.5

Ø13 15
90

Ø13 15
132.5

132.5

Ø13 15 Ø13 15
132.5

50 250 50 250
15
33.1

328.8
15

33.1

328.8
50 352.8
250 50 352.8 250
39.6 383.6328.8
15

39.6 383.6
33.1

15

33.1

328.8
423.2 423.2
352.8 352.8
39.6 383.6 39.6 383.6
423.2 423.2

※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 107

VCB
Unit:mm

Horizontal Type
115 115 115 115 115
Model Name Detail“A”
A A
HGN20 (06) ~ 25 75

28.8
28.8

115 115 115 115 115 HGN32 90


A A

28.8
28.8
250

250
368. 4

368. 4
Ø1 Ø1
4 4
250

250
368. 4

368. 4
210 94.5 210 115
Ø1 Ø1
4 4

ACB
[ 2,000 ~ 2,500 A ] [ 3,200 A ]
(Test) 26.5 60 (Test) 26.5 60
210 Arc Shield Surface 94.5 210 Arc Shield Surface
115
(Isol) 11.5 20.4 (Option) (Isol) 11.5 20.4 (Option)

[ 2,000 ~ 2,500 A ] [ 3,200 A ]


(Test) 26.5 60 (Test) 26.5 60
Arc Shield Surface Arc Shield Surface
(Isol) 11.5 20.4 (Option) 13 (Isol) 11.5 (Option)
35 20.4 35 13
119.3 6 3-Ø 119.3 6 3-Ø

20
20

50
75

50
90
465.8

465.8
Fixing Block Fixing Block
3515 13 35 13
119.3(Option)
6 3-Ø 119.3(Option) 15 3-Ø

143
6

124
330

330
143
124

20
20

50
75

50
90
465.8

465.8
Fixing Block Fixing Block
15
20

20
132.5
Ø13 15
(Option) Ø13 15 15
132.5

(Option)

143
124
330

330
143
124

50 250 50 250
33.1
33.1

15

15

MCCB
328.8 328.8
20

20
132.5
15 15
132.5

352.8 Ø13 352.8 Ø13


39.6 383.6 39.6 383.6
50 423.2 250 50 423.2 250
33.1
33.1

15

328.8 328.8 15
352.8 352.8
39.6 383.6 39.6 383.6

Front Type
423.2 423.2
115 115 115 115 115
75 75
28.8

28.8

115 115 115 115 115


75 75
28.8

28.8
250

250
368.4

368.4

Ø1 Ø1
4 4
250

250
368.4

368.4

210 94.5 210 115

MS
Ø1 Ø1
4 4
(Test) 26.5 60 Arc Shield Surface
20.4 (Option)
(Isol) 11.5
210 94.5 210 115

(Test) 26.5 60 Arc Shield Surface


119.3 20.4 (Option) 11
(Isol) 11.5 6 3-Ø
465.8

Fixing Block
50
75
445.5

(Option) 15 11
330

119.3 6 3-Ø

328.8
465.8

Fixing Block
50
75
445.5

Ø13
(Option) 15
15
330

39.6 50 250
15
33.1

328.8 20
329.6
15
37.5

352.8 Ø13
RELAY

39.6 50 250
15
33.1

329.6 20
37.5

352.8

※ The drawing dimension of this page may be subject to change without prior notice.
108 Air Circuit Breakers

Dimensions
HGN Fixed Type 4,000 A (HGN40 B Frame) Unit:mm

Front

367 482

367 482
404.4 404.4

404.4 404.4

270
270
212.2 327.2
424.4 270 539.4
270
212.2 327.2
3P
424.4 4P
539.4

3P 4P

Vertical Type 384.4 499.4


8 8
152.5 152.5 140 140 140
15 10 15 384.4 15 10 15 499.4
8 8
152.5 152.5 140 140 140
15 10 15 15 10 15
40

40
14

14
109 186.8 186.8
20152.5 152.5
109 109 186.8 186.8
20152.5 152.5
40

40
14

14
20
20

109

[ 4,000 A ]
35 13
[ 4,000 A ] 5-Ø

35 13
5-Ø
25x4=100
125

125
25x4=100
125

15
125
330

169
44

15
330

119.5 119.5 169


125
44
125
57
33

60 49 186.8
295.8 87
57
33

60 49 186.8
295.8 87

※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 109

VCB
Unit:mm

Horizontal Type
405 520
152.5 152.5 140 140 140
100 100
40

40
14

14
186.8
152.5
186.8
152.5
20

20

ACB
109

109
384.4 8 499.4 8

[ 4,000 A ]

3
Ø1
35 3-
25x3=75
100
40

15
330

144
15
10

MCCB
15

132
33

60 49 186.8
295.8 58.6

MS
RELAY

※ The drawing dimension of this page may be subject to change without prior notice.
110 Air Circuit Breakers

Dimensions
HGN Draw-Out Type 4,000 A (HGN40 B Frame) Unit:mm

Front

511 626
487 602

511 626
487 602
Type) Plug Type)

Type) Plug Type)


460(Auto Connection Type)

460(Auto Connection Type)


Ø1

Ø1
2.1

2.1
438(Manual Control Plug Type)

438(Manual Control Plug Type)


ConnectionControl

ConnectionControl
Ø1

Ø1
2.1

2.1
460(Auto438(Manual

460(Auto438(Manual
278.3

278.3
278.3

278.3
270 270
199.5 199.5 199.5 314.5
399 514
270 270

3P
199.5 199.5 199.5
4P 314.5
399 514

3P 4P

152.5 152.5 140 140 140


15 10 15 15 10 15
Vertical Type 152.5 152.5 140 140 140
28.8
28.8

15 10 15 15 10 15
28.8
28.8
250

250

368.4
368.4

Ø1 Ø1
250

250

368.4
368.4

4 4

Ø1
210 94.5 Ø1210 115
4 4

(Test) 26.5 60 [ 4,000210


A] 94.5 210 115
Arc Shield Surface
(Isol) 11.5 20.4 (Option)
(Test) 26.5 60 [ 4,000 A ]
Arc Shield Surface
(Isol) 11.5 20.4 13
(Option) 35 5-Ø

119.3 6 13
35 5-Ø
25x4=100
25x4=100 125
125

119.3 6
Fixing Block 15
465.8

125

(Option)
125
330

193
68

Fixing Block 15
465.8

(Option)
330

193
68
125

Ø13 15
107.5
125

50 250 Ø13 15
107.5
33.1

15

328.8
50 352.8 250
39.6 425.6
33.1

15

328.8
465.2352.8
39.6 425.6
465.2

※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 111

VCB
Unit:mm

Horizontal Type
405 520
152. 5 152. 5 140 140 140
100 100
28.8

28.8
250
250

368.4

368.4
Ø1 Ø1
4 4

ACB
210 94.5 210 115

[ 4,000 A ]
(Test) 26.5 60
Arc Shield Surface
(Isol) 11.5 20.4 (Option)

3
Ø1
35 3-
119.3 6
15

25x3=75
10

100
15

Fixing Block 15
465.8
168

(Option)
330

MCCB
40

Ø13 15
132.5

50 250
33.1

15

328.8
352.8
39.6 399.6
439.2

MS
RELAY

※ The drawing dimension of this page may be subject to change without prior notice.
112 Air Circuit Breakers

Dimensions
HGN Fixed Type 4,000 (3,200) ~ 5,000 A (HGN40 (30) ~ 50 C Frame) Unit:mm

Front

592 762

592 762
404.4

404.4
404.4

404.4

270 270
472.7 176.7 557.7 261.7
649.4 819.4
270 270
472.7 176.7 557.7 261.7
3P 4P
649.4 819.4

3P 4P

Vertical Type
8 609.4 8 779.4
190.5 190.5 190.5 190.5 190.5
20 70 20 148 20 70 20 148
8 609.4 8 779.4
190.5 190.5 190.5 190.5 190.5
20 70 20 148 20 70 20 148
40

40
14

14
186.8
152.5

152.5
186.8

40

40
14

14
186.8
152.5

152.5
186.8
20

20
109

109
20

20
109

109

13
35 5-Ø

13
25x4=100 25x4=100

35 5-Ø
125

125

15
194
69
330

125

125

15
125
107194
69
330
33

125

60 49 186.8
44.5
107

295.8 63.6
33

60 49 186.8
44.5

295.8 63.6

※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 113

VCB
Unit:mm

Horizontal Type

8 609.4 8 779.4
190.5 190.5 190.5 190.5 190.5

148 125 148


40

40

14
14
186.8

152.5
152.5

186.8

ACB
20
20
109

109

13
35 5-Ø
20

25x4=100
110

125
70

15
20
330

196
86
110

MCCB
106
51
33

60 49 186.8
295.8 63.6

MS
RELAY

※ The drawing dimension of this page may be subject to change without prior notice.
114 Air Circuit Breakers

Dimensions
HGN Draw-Out Type 4,000 (3,200) ~ 5,000 A (HGN40 (30) ~ 50 C Frame) Unit:mm

Front

736 906
712 882

736 906
712 882
Type)

Type)
Type) Plug Type)

Type) Plug Type)


Ø1

Ø1
2.1
460(Auto Connection

2.1
460(Auto Connection
Plug Control

Plug Control
Type)

Type)
Ø1

Ø1
438(Manual

2.1

438(Manual
460(Auto Connection

278.3

2.1
278.3
460(Auto Connection
438(Manual Control

438(Manual Control
278.3

278.3
270 270
460 164 545 249
624 794
270 270
460 164 545 249
624 794

190.5 190.5 190.5 190.5 190.5


20 70 20 148 20 70 20 148

Vertical Type
24

190.5 190.5 190.5 190.5 190.5


20 70 20 148 20 70 20 148
103.8
103.8

24

368.4
368.4
175

4
175

4
Ø1 Ø1
175 50 103.8
175 50 103.8

368.4
368.4

4 4
460 Ø1 164 545 Ø1 249
260 260 345 345
50

50

(Test) 26.5 60 Arc Shield Surface


20.4 460 164 545 249
(Option)
(Isol) 11.5 260 260 345 345

13
(Test) 26.5 60 Arc Shield Surface 35 5-Ø
20.4 (Option)
(Isol) 11.5
119.3 6
25x4=100

13
125

125

35 5-Ø
Fixing Block
465.8

119.3 6(Option) 15
194
330

12569

25x4=100

125

Fixing Block
465.8
69125

(Option) 15
194
330

107

Ø13 15
12544.5

50 175
33.1

328.8
15

107

Ø13 15
352.8
44.5

39.6 401.6
50 175
441.2
33.1

328.8
15

352.8
39.6 401.6
441.2

※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 115

VCB
Unit:mm

Horizontal Type

190.5 190.5 190.5 190.5 190.5


148 125 148

103.8
103.8

368.4
368.4

175
175

4
Ø1
14
Ø

ACB
50
50

460 164 545 249


260 345 345
260

(Test) 26.5 60 ARC Shield Surface


(Isol) 11.5 20.4 (Option)

13
35 5-Ø
20

119.3 6
25x4=100
110

125
70

Fixing Block
465.8

(Option) 15
20
196
330

86

MCCB
110

Ø13 15
106
51

50 175
33.1

328.8
15

352.8
39.6 401.6
441.2

MS
RELAY

※ The drawing dimension of this page may be subject to change without prior notice.
116 Air Circuit Breakers

Dimensions
HGN Fixed Type 4,000 ~ 6,300 A (HGN40 ~ 63 D Frame) Unit:mm

Front

734 964

734 964
404.4

404.4
404.4

404.4

270 12 270 12
559.2 192.2 8 674.2 307.2 8
791.4 1,021.4

270 12 270 12
559.2 3P 192.2 8 674.2 4P 307.2 8
791.4 1,021.4

3P 4P

Vertical Type 241 241 241 241 241


20 95 20 183.5 20 95 20 115

241 241 241 241 241


20 95 20 183.5 20 95 20 115
40

40
14
152.5

152.5
186.8

186.8
40

40
14
20

20
152.5

152.5
186.8
109

186.8
109
20

20
109

109

13
35 5-Ø
150

25x5=125
150

13
35 5-Ø
194
69 150 150 69
330

25x5=12515

15
150
107
194
330

15
33

15
60 49 186.8
19.5

295.8 68.6
150
107
33

60 49 186.8
19.5

295.8 68.6

※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 117

VCB
Unit:mm

Horizontal Type

241 241 241 241 241


125 183.5 125
40

40
14

14
152.5

152.5
186.8

186.8

ACB
20
109

109

13
35 5-Ø
20

25x5=125
110
70

150
20
194
84

15
330

110
107
52
33

60 49 186.8

MCCB
295.8 68.6

MS
RELAY

※ The drawing dimension of this page may be subject to change without prior notice.
118 Air Circuit Breakers

Dimensions
HGN Draw-Out Type 4,000 A (HGN40 D Frame) Unit:mm

Front

878.2 1,108.2
854.2 1,084.2

878.2 1,108.2
Type)
Control Plug Type)

Type)
Control Plug Type)
854.2 1,084.2
Ø1

Ø1
460(Auto Connection

460(Auto Connection
2.1

2.1
Type)
Plug Type)

Type)
Plug Type)
Ø1

Ø1
278.3

278.3
438(Manual

438(Manual
460(Auto Connection

460(Auto Connection
2.1

2.1
438(Manual Control

438(Manual Control

270 270
278.3

278.3
566.6 199.6 681.6 314.6
766.2 996.2

270 270
566.6 199.6 681.6 314.6
766.2 996.2

241 241 241 241 241

20 95 20 183.5 115 20 95 20 183.5 115

Vertical Type
241 241 241 241 241
103.8
103.8

20 95 20 183.5 115 20 95 20 183.5 115


368.4
368.4
103.8 175

175 50103.8175

4 4
Ø1 Ø1
175 50

368.4
368.4

566.6 4 199.6 681.6 4 314.6


Ø1 Ø1
330 330 445 445
50

50

566.6 199.6 681.6 314.6


(Test) 26.5 60 Arc Shield Surface
20.4 330 330
(Option) 445 445
(Isol) 11.5

13
(Test) 26.5 60 Arc Shield Surface 35 5-Ø
20.4 (Option)
(Isol) 11.5
119.3 6
25x4=100
125

13
125

35 5-Ø
465.8

Fixing Block 15
193.1

119.3 6
125 45 68.1125 12568.1
330

(Option)
25x4=100
125
465.8

Fixing Block 15
193.1
330

(Option)
107

50 175
Ø1
33.1

328.8 3
15

352.8
107

39.6 406.6
45

50 175 446.2
Ø1
33.1

328.8 3
15

352.8
39.6 406.6
446.2

※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 119

VCB
Unit:mm

Horizontal Type

241 241 241 241 241

183.5 125 183.5 125

103.8
103.8

368.4
368.4
175

175
4 4
Ø1 Ø1
50

50
566.6 199.6

ACB
681.6 314.6
330 330 445 445

(Test) 26.5 60 Arc Shield Surface


20.4 (Option)
(Isol) 11.5

13
35 5-Ø

119.3 6
25x4=100
110

125
70

465.8

Fixing Block 15
20
193.1
83.1
330

(Option)
110

MCCB
106
52.5

50 175
Ø1
33.1

328.8 3
15

352.8
39.6 406.6
446.2

MS
RELAY

※ The drawing dimension of this page may be subject to change without prior notice.
120 Air Circuit Breakers

Dimensions
HGN Draw-Out Type 5,000 ~ 6,300 A (HGN50 ~ 63 D Frame) Unit:mm

Front

878.2 1,108.2
854.2 1,084.2
Control Plug Type)
Connection Type)

878.2 1,108.2

Control Plug Type)


854.2 Connection Type) 1,084.2
Ø1

Ø1
2.1

2.1
Plug Type)
460(AutoType)

Plug Type)
460(AutoType)
278.3

278.3
Ø1
438(Manual

Ø1
438(Manual
460(Auto Connection

460(Auto Connection
2.1

2.1
438(Manual Control

438(Manual Control

270 270
278.3

278.3
566.6 199.6 681.6 314.6
766.2 996.2

270 270
566.6 199.6 681.6 314.6
766.2 996.2

241 241 241 241 241

20 95 20 183.5 115 20 95 20 183.5 115

Vertical Type
241 241 241 241 241
103.8
103.8

20 95 20 183.5 115 20 95 20 183.5 115


368.4
368.4
175

103.8 175

4 4
Ø1 Ø1
103.8
50

50

566.6 199.6 681.6 314.6


368.4
368.4
175

175

4 4
330 Ø1 330 445 Ø1 445
50

50

(Test) 26.5 60 566.6 Arc Shield199.6


Surface 681.6 314.6
20.4 330 (Option)
330
(Isol) 11.5 445 445

13
35 5-Ø
(Test) 26.5 60 Arc Shield Surface
20.4 (Option)
(Isol) 11.5 119.3 6
25x5=125
150

150

13
35 5-Ø
465.8

Fixing Block
193.1
15068.1

119.3 6 15
330

(Option)
25x5=125
150
465.8
68.1150

Fixing Block
193.1

15
330

107

(Option)

50 175
Ø1
33.1

328.8 3
150
15

20

352.8
107

39.6 406.6
50 175 446.2
Ø1
33.1

328.8 3
15

20

352.8
39.6 406.6
446.2

※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 121

VCB
Unit:mm

Horizontal Type

241 241 241 241 241


183.5 125 183.5 150

103.8
103.8

368.4
368.4
175

175
4 4
Ø1 Ø1
50

50

ACB
566.6 199.6 681.6 314.6
330 330 445 445

(Test) 26.5 60 Arc Shield Surface


20.4 (Option)
(Isol) 11.5

13
35 5-Ø

119.3 6
25x5=125
110
70

150
465.8

Fixing Block
20
193.1
83.1

15
330

(Option)
110

MCCB
106
52.5

50 175
Ø1
33.1

328.8 3
15

352.8
39.6 406.6
446.2

MS
RELAY

※ The drawing dimension of this page may be subject to change without prior notice.
122 Air Circuit Breakers

Dimensions
Panel Cutting Dimension of HGS/HGN Fixed Type Unit:mm

Panel Door Cut-Out (For Dust Cover) Panel Door Cut-Out (For Door Flange)

Operating
Operating Panel Center Operating
Panel Center Operating Panel Center
Panel Center
196 196 - R5 292
196 4 196 R5 5
292 4- 103.5 100 103.5 -R
4292
4- 5.
2 R5
Ø5 42.5 103.5 4 100 292
103.5 42.5 Ø .2
103.5 100 103.5 4-
.2 -Ø 4-103.5 42.5 Ø5
5.2 42.5 103.5 100
4-

122.5
20

122.5

122.5
20

15

122.5
15

144
330
115
345
290

229
115
345

330
115
345
290

229
115
345

75
4

122.5
4

4
12


122.5

132
122.5
4
12

12
7.5

122.5
68.6 15

12
7.5

7.5
68.6 15

Bottom
20

7.5

33
Bottom Bottom
20

33
Bottom 7.5 95 188

25.6
33.1

7.5 7.5 95 188


25.6

25.6
Panel Door Rear Panel (IP
33.1

7.5
25.6

Panel Door

Side View Rear Panel Cutting Size (For IP30)

Operating Operating
Panel Center Panel Center
ACB Center ACB Center
2 5 292
0 103.5 4-
R R5 A A
103.5 100 103.5 4-
122.5

122.5

144
330
115
345

144
330
115
345

B
75

75
4

4


122.5
12

33 122.5
12

132
7.5

132
7.5

ottom Bottom Bottom


33

7.5 95 188 95 188


25.6

7.5
25.6

Rear Panel (IP30)


C

Panel Door Panel Door Rear Panel (IP30)

Detailed Dimensions of Real Panel Cutting

Model Name A B C
HGN 06A3 ~ 20A3, HGS 06A3 ~ 16A3 283 355 25
HGN 06A4 ~ 20A4, HGS 06A4 ~ 16A4 368 355 25
HGN 06B3 ~ 40B3, HGS 20B3 ~ 32B3 354 355 25
HGN 06B4 ~ 40B4, HGS 20B4 ~ 32B4 469 355 25
HGN 32C3 ~ 50C3 579 355 25
HGN 32C4 ~ 50C4 749 355 25

※ The drawing dimension of this page may be subject to change without prior notice.
Air Circuit Breakers 123

VCB
Panel Cutting Dimension of HGS/HGN Draw-Out Type Unit:mm

Panel Door Cut-Out (For Dust Cover) Panel Door Cut-Out (For Door Flange)

Operating Operating Operating Operating


(Test) 26.5 60(Test) 26.5
Panel Center Panel Center 60
Panel Center Panel Center
(Isol) 11.5 20.4
(Isol) 11.5 20.4
196 196 R5 R5
196 4- 196
4-
292 292 292 2925
4-
Ø5 42.5 103.5 4-Ø 10042.5 103.5 .2 .2 -R R5
42.5
100 Ø5
103.5 42.5 Ø5
103.5 100 103.5
103.5 4100 103.5 4-
.2 5.2 4- 4-
20

20

122.5

122.5
122.5

122.5
15

15

ACB
290

229
115
345

115
345

330
290

229
115
345

115
345

330
4

4
4

4



122.5

122.5
122.5

122.5
12

12
12

12
Rear panel R
68.6 15

68.6 15
7.5

7.5
7.5

7.5
(IP30) (
20

20

Bottom Bottom Bottom Bottom Bottom Bottom


33.1

33.1

7.5 7.5

33.1
7.5 7.5
25.6

25.6

33.1
25.6

25.6
Panel Door Panel Door
25 25 323 323

Side View Rear Panel Cutting Size (For IP30)

MCCB
Operating (Test) 26.5 60
Operating Panel Center
(Test) 26.5 60 (Isol) 11.5 20.4
Panel Center
(Isol) 11.5 20.4
292
R5 ACB Center
292 103.5 100 103.5 4-
R5 ACB Center
100 103.5 4- A
A
122.5
122.5

115
330345

330

B
115
345

B
4

122.5
4

12

MS
Rear panel
122.5

7.5
12

Rear panel (IP30)


7.5

Bottom Bottom (IP30) Bottom


31
32

Bottom Bottom
31
32

4
7.5
33.1
25.6

Panel Door 4
7.5
33.1
25.6

Panel Door
25 323
25 323

Detailed Dimensions of Real Panel Cutting

Model Name A B C
HGN 06A3 ~ 20A3, HGS 06A3 ~ 16A3 329 268 70
RELAY

HGN 06A4 ~ 20A4, HGS 06A4 ~ 16A4 414 268 70


HGN 06B3 ~ 40B3, HGS 20B3 ~ 32B3 400 298 55
HGN 06B4 ~ 40B4, HGS 20B4 ~ 32B4 515 298 55
HGN 32C3 ~ 50C3 625 338 35
HGN 32C4 ~ 50C4 795 338 35

※ The drawing dimension of this page may be subject to change without prior notice.
124 Air Circuit Breakers

Circuit Diagrams

Over-Current Spring Charge


Alarm AUX S/W Motor Charge Closing Trip Opening Circuit Condenser Secondary
Main Circuit Protective Device (OCR) Completed
Contact 1a 1b Power Coil Coil Trip Coil Supervision Trip Device Trip Coil
Contact

BA 1a (37/38), 1b (39/40) Power


AC, DC 100-250 V S0 - S2 BH 1a (37/38)
B7 : ATS OCR alarm 1a (37/38) U V
3Ø3W/3Ø4W Power AA 1a 1b : 1a (37/38), 1b (39/40) Power Power Power Power Power
CTD
VM + -
P N
External CT / ZCT
(Secondary : 5 A) (1,000 : 1) NCT PB

PB(Open)

PB(Open)

PB(Open)

PB(Open)
K L K L (Close)
Supervision
R S T N 21 23 27 28 29 30 VR VS VT VN 19 37 39 37 39 1 15 3 7 7 59 7 9

Spring
Charge
Off SW.

R S T N L P ELT ELT NCT NCT


1 2 1 2 VR VS VT VN S2

Over-Current
Protective Device
M CC TC TC TC2

Rn Sn Tn Nn Ac S/I G/E ZI
1
ZI
2
ZO ZO
1 2 COM COM RR+ RR- MCR MCR
+ - TN TP S0 TC
CT4
CT3 TP

CT2 MHT
CT1
TN

1a for MCR
Rn Sn Tn Nn 22 24 26 31 32 33 34 35 36 5 6 20 38 40 38 40 2 16 4 8 8 8 10

+ - + - + - + -
IN OUT Communi- Remote
ZSI cation Reset

Symbol Description Terminal Description

CT Current Transformer 1 2 Charge Motor Power


L LTD Terminal 3 4 Closing Coil Power
PT Pre-Trip Alarm 7 8 Trip Coil Power
G Ground Fault Contact 9 10 UVT Coil Power
S/I STD/INST Contact 15 16 Spring Charge Switch
Ac Common Contact 19 20 OCR Control Power
NCT NCT (Neutral CT) Input 22 21 LTD Contact
ZI Zone Selective Interlock Input 22 23 Pre-Trip Alarm/Temperature Alarm Contact
ZO Zone Selective Interlock Output 22 24 STD/INST Contact
MCR +,- MCR Input Terminal 22 26 GFT/ELT Contact
Tp / Tn MHT Output Terminal 22 30 NCT (Neutral CT) Input Terminal
M Charging Motor 31 ~ 34 ZSI (Zone Selective Interlock)
CC Close Coil 41 ~ 60 Auxiliary Contact
TC Trip Coil 61 ~ 93 Position Switch
UVT Under-Current Voltage Trip Coil
Manufacture’s Wiring
CT Magnetic Hold Trigger
User’s Wiring
SO /S2 OCR Power
Disconnecting Device (Draw-Out Type)
• RR:Remote Reset • VM:Voltage Module • VR ~ VN:Voltage Phase Input
• R ~ N:Current Input • Rn ~ Nn:Current Input

※ This circuit diagram is equipped with the 'GPR-LA' type of OCR and please refer to page 35 to 38 for other types of OCR.
Air Circuit Breakers 125

VCB
UVT Coil + Auxiliary Position External Auxiliary
UVT Time Delay Device Contact Switch Contact (MOC)

U1
COM
a
Power
U2
Power b
Time Delay

C1
T2
UVT
PB(Open)

PB(Open)

C2
T1
9 9 41 43 45 47 49 51 53 55 57 59 61 64 67 101 71 74 77 81 84 91 94 121 123 125 127 129 131 133 135 137 139 141 143 145 147 149 151 153 155 157 159
Used for Short "b" contact (Option)
Used for SHT Supervision (Option)

Used for SHT Supervision (Option)

Used for SHT Supervision (Option)

ACB
Used for MCR (Option)

UVT UVT

10 10 42 44 46 48 50 52 54 56 58 60 62 63 65 66 68 69 102 103 72 73 75 76 78 79 82 83 85 86 92 93 95 96 122 124 126 128 130 132 134 136 138 140 142 144 146 148 150 152 154 156 158 160

MOC1 MOC2

Test Connection Isolation Insert


Position Position Position Position
61-62 ON 71-72 ON 81-82 ON 84-85 ON
61-63 OFF 71-73 OFF 81-83 OFF 84-86 OFF
64-65 ON 74-75 ON 84-85 ON 91-92 ON
64-66 OFF 74-76 OFF 84-86 OFF 91-93 OFF
67-68 ON 77-78 ON 94-95 ON
67-69 OFF 77-79 OFF 94-96 OFF
101-102 ON

MCCB
101-103 OFF

Control Jack Lay-Out

OCR Operating Auxiliary Switch


OCR Contact
POW ELT N-CT ZSI COM Temp V Input M CC TC UVT CHA 1a 2a 3a 4a 5a 1b 2b 3b 4b 5b
COM L S/I P/T G/E
19 21 23 27 29 31 33 35 37 39 VR VT 1 3 7 9 15 41 43 45 47 49 51 53 55 57 59

20 22 24 26 28 30 32 34 36 38 40 VS VN 2 4 8 10 16 42 44 46 48 50 52 54 56 58 60

OCR Protection Relay Operating Circuit Auxiliary Switch

MS
OCR
OCR Contact
POW ELT N-CT ZSI COM Temp V Input
COM L S/I P/T G/E

19 21 23 27 29 31 33 35 37 39 VR VT

20 22 24 26 28 30 32 34 36 38 40 VS VN

- GPR Protection Relay -

Operating Auxiliary Switch


M CC TC UVT CHA 1a 2a 3a 4a 5a 1b 2b 3b 4b 5b

1 3 7 9 15 41 43 45 47 49 51 53 55 57 59
RELAY

2 4 8 10 16 42 44 46 48 50 52 54 56 58 60

- Operating Circuit - - Auxiliary Switch -


126 Air Circuit Breakers

Order Code
HGN Type

HGN 12 A 3 J M2

Frame Category & Charging Motor


Model Name Rated Frame No. of Poles Mounting Method
Neutral Pole Power

Air Circuit 6 630 A 3 3 Pole Independent Release of Draw-Out M0 Manual Type


HGN 630 ~ 2,000 AF 3/4P
Breakers 8 800 A A Standard 4 4 Pole Type (Control Power) of Main Unit M1 AC/DC 110 V
RST (N)
10 1,000 A A Auto Connection M2 AC/DC 220 V
12 1,250 A J Manual Connection M3 AC 380 V 3)
630 ~ 2,000 AF
16 1,600 A W 4P Reverse Phase M4 AC 440 V 3)
NRST
20 2,000 A 1) Fixed Type (Terminal Form) M7 DC 24 V
H Horizontal Type M8 DC 48 V
6 630 A V Vertical Type M9 DC 125 V
8 800 A 630 ~ 4,000 AF 3/4P Upper Side:Horizontal/
Standard T
10 1,000 A B Lower Side:Vertical
RST (N)
12 1,250 A Upper Side:Vertical/
L
16 1,600 A Lower Side:Horizontal

20 2,000 A Front Type and Mounting


630 ~ 4,000 AF P 2)
25 2,500 A Type Selected by Customer
X 4P Reverse Phase
32 3,200 A NRST

40 4,000 A Draw-Out Type


(Combined with Cradle)

32 3,200 A 3,200 ~ 5,000 AF 3/4P Auto Connection +


C B
Standard RST (N) Horizontal Type
40 4,000 A
3,200 ~ 5,000 AF 4P
50 5,000 A Y
Reverse Phase NRST Auto Connection +
C
Vertical Type

40 4,000 A 4,000 ~ 6,300 AF 3/4P Auto Connection +


D D Upper Side:Horizontal /
Standard RST (N)
50 5,000 A Lower Side:Vertical
4,000 ~ 6,300 AF 4P
63 6,300 A Z Auto Connection +
Reverse Phase NRST
E Upper Side:Vertical /
Lower Side:Horizontal
Auto Connection +
G 2) Front Type/Mounting Type
Selected by Customer

Manual Connection +
K
Horizontal Type

Manual Connection +
M
Vertical Type

Manual Connection +
N Upper:Horizontal/
Lower:Vertical
Manual Connection +
Q Upper Side:Vertical/
Lower Side:Horizontal
Manual Connection +
R 2) Front Type/Mounting Type
Selected by Customer

※ 1) A frame, 2,000 A is only available for vertical terminal bus bar arrangement.
2) P, G, R type of fixed terminal bus bar arrangement should be ordered per terminal and mounted personally.
(Refer to the additional components). Applicable frames are A06 ~ 16, B06 ~ 32.
3) Charging motor AC 380 V, AC 440 V are currently under development.
4) CT for Over-Current
- A/W Frame:200 ~ 2,000 A
- B/X Frame:400 ~ 4,000 A
- C/Y Frame:3,200 ~ 5,000 A
- D/Z Frame:4,000 ~ 6,300 A
5) When applying OCR high-end type P, H type, place an order for voltage module (HGNS VM) additionally for mounting.
Air Circuit Breakers 127

VCB
C2 S2 61 K AB

Parts Mounted on Cradle


Closing Coil Trip Coil Over-Current Trip CT 4) Parts for Main Unit (Only Applicable when Placing
an Order for Combination Type)
C0 N/A S0 N/A General Feeder 0 OCR N/A Time Delay Type
INST (UVT Coil)
C1 AC/DC 110 V S1 AC/DC 110 V 00 N/A O 200 A (UVT Coil + UVT Controller)

C2 AC/DC 220 V S2 AC/DC 220 V 50 Hz V 320 A U1 AC/DC 110 V V1 AC/DC 110 V


C3 AC 380 V S3 AC 380 V 50 GPR-LN E 400 A U2 AC/DC 220 V V2 AC/DC 220 V
C4 AC 440 V S4 AC 440 V 51 GPR-LA T 630 A U3 AC 380 V V3 AC 380 V

ACB
C7 DC 24 V S7 DC 24 V 52 GPR-LAG H 800 A U4 AC 440 V V4 AC 440 V
C8 DC 48 V S8 DC 48 V 53 GPR-LAZ J 1,000 A U7 DC 24 V V9 DC 125 V
C9 DC 125 V S9 DC 125 V 54 GPR-LP 5)
K 1,250 A U8 DC 48 V
55 GPR-LH 5) L 1,600 A U9 DC 125 V Position S/W
Trip Supervision Coil 60 Hz M 2,000 A AQ Test 1C, Connected 1C
T1 AC/DC 110 V 60 GPR-LN N 2,500 A Secondary Trip Coil AR Connected 2C
T2 AC/DC 220 V 61 GPR-LA P 3,200 A S1 AC/DC 110 V AS Test 2C
T3 AC 380 V 62 GPR-LAG Q 4,000 A S2 AC/DC 220 V AT Isolated 1C, Inserted 1C
T4 AC 440 V 63 GPR-LAZ S 5,000 A S3 AC 380 V AU Inserted 2C
T7 DC 24 V 64 GPR-LP 5) X 6,300 A S4 AC 440 V AV Isolated 2C
T8 DC 48 V 65 GPR-LH 5) S7 DC 24 V P4 Test 2C, Connected 2C

MCCB
T9 DC 125 V S8 DC 48 V PT Test 4C
Generator S9 DC 125 V Isolated 1C, Test 1C,
PS
50 Hz Connected 2C

57 GPR-SN Inserted 1C,


On/Off Button Lock
AM PQ Isolated 1C, Test 1C,
58 GPR-SA Device
Connected 1C
59 GPR-SP 5) Inserted 2C,
Auxiliary Switch
AA P8 Isolated 2C, Test 2C,
60Hz (Additional 1a 1b)
Connected 2C
67 GPR-SN Inserted 1C,
Key Lock Device
AB PR Isolated 1C, Test 3C,
68 GPR-SA (Prevent ON)
Connected 3C
69 GPR-SP 5) B8 OCR MCR
Auto Connection
OCR Manual Reset
BR BC Control Terminal’s
Function
Safety Cover
- U□ is only applicable when instantaneous type and only the UVT coil is installed. When using time delay
type, place a separate order for the time delay type of controller (HGNS ~ ) and install externally. BA
OCR Manual Reset &
MC
External Auxiliary
Contact (MOC)
MS
Alarm S/W 2a
- V□ is only applicable when time delay type is applied and the UVT coil is installed in the main unit while the 10a10b
time delay type of controller is installed at the side of the cradle. In case of dimension issues, place an order CR Manual Reset + AK Short “b” Contact
for HGNS V□ for separate installation. BH High Capacity Alarm
S/W 1a AE Safety Shutter
- B0:The mechanical interlock device has to be ordered separately and when B0 is marked, only the
components interlocked inside the main unit are assembled for release. Mechanical AX Arc Shield
(Refer to additional components). B0
Interlock Device AF Fixing Block
- When S□ Secondary trip is applied, UVT coil cannot be applied at the same time.
- When using T□ trip coil monitoring contact, it becomes 4a3b and when using MCR function of B8 OCR, it can B6 Spring Charge Switch Miss Insertion
AW
be used as 4a5b. When both functions are applied, 3a3b can be possible. AG Door Flange Preventer
- In the order code for the main unit only (A/J/Fixed type), combination with cradle accessories is not possible
Closing Preparation
and the cradle accessory arrangement is only possible when purchased with cradle arrangement. For the Temperature
BT Contact (B6 and CT TM
independent release of the main unit, place a separate order (HGNS ~ ) (refer to additional components). Sensor Bracket
cannot be Combined)
- Position switch cannot be overlapped for use and can only be attached only at the right side of cradle.
MR Marine Switchgear
In case a combination other than the combination indicate is required, make an inquiry separately.
RELAY

- Mechanical interlock device (B0), external auxiliary contact (MC) and fixing block (AF) cannot be used together. ATS Production
- BC:The control terminal’s safety cover is only available for the auto connection.
Emergency Power
- AK:Short “b” is only available for auto connection and is attached to 51, 52. It can be attached as much as BAB7
Transfer
the number of “B” contact so upon additional mounting, place a separate order (HGNS ~ ).
- AG:O  riginally, it is attached separately but upon release, the front cover is inserted when shipped.
- MR:AE, AG, AF, AM are attached as a standard option, so the relevant accessories are not marked separately.
MR Marine Switchgear
- AA and BA (BH) cannot be attached at the same time.
- UVT and Secondary Trip Coil cannot be attached at the same time.
128 Air Circuit Breakers

Order Code
When Placing an Order for the Cradle

DHN 12 A 3 A H AE

Control
Frame Category & Terminal Bus Bar
Model Name Rated Frame No. of Poles Terminal Accessories
Neutral Pole Arrangement
Connection
Air Circuit 16 DHN06 ~ 16A (W) 630 ~ 1,600 A 3/4P 3 3 Pole H Horizontal Type
Auto Safety
DHN Breakers A Standard RSTN A AE
20 DHN20A (W) 1)
4 4 Pole Connection V Vertical Type Shutter
Cradle Reverse Phase NRST

Manual Upper Side:


J ※ AE:Safety
Connection Horizontal/
25 DHN06 ~ 25B (X) T shutter lock is
630 ~ 4,000 A 3/4P Lower Side:
Vertical supplied with
32 DHN32B (X) B Standard RSTN
Reverse Phase NRST safety shutter.
40 DHN40B (X) Upper Side:
Vertical/
L
Lower Side:
3,200 ~ 5,000 A 3/4P Horizontal
50 DHN32 ~ 50C (Y) C Standard RSTN
Reverse Phase NRST Front Type and
Mounting Type
P 2)
Selected by
40 DHN40D (Z) 4,000 ~ 6,300 A 3/4P Customer
D Standard RSTN
63 DHN50 ~ 63D (Z) Reverse Phase NRST

※ Marking upon Shipping of Cradle


·DHN06/08/10/12/16A (W) > DHN06 ~ 16A (W)
·DHN20A (W) > DHN20A (W)
·DHN06/08/10/12/16/20/25B (X) > DHN06 ~ 25B (X)
·DHN32B (X) > DHN32B (X)
·DHN40B (X) > DHN40B (X)
·DHN32/40/50C (Y) > DHN32 ~ 50C (Y)
·DHN40/50D (Z) > DHN40 ~ 50D (Z)

※ 1) A frame, 2,000 A is only available for vertical terminal bus bar arrangement.
2) P type of fixed terminal bus bar arrangement should be ordered per terminal and mounted personally. (Refer to the additional components).
Applicable frames are A06 ~ 16, B06 ~ 32.
Air Circuit Breakers 129

VCB
ACB
MCCB
MS
RELAY
130 Air Circuit Breakers

Order Code
HGS Type

HGS 12 A 3 J M2

Frame Category &


Model Name Rated Frame No. of Poles Mounting Method Charging Motor Power
Neutral Pole

Air Circuit 6 630 A 3 3 Pole Independent Release of Draw-Out M0 Manual type


HGS 630 ~ 1,600 AF 3/4P
Breakers 8 800 A A 4 4 Pole Type (Control Power) of Main Unit M1 AC/DC 110 V
Standard RST (N)
10 1,000 A A Auto Connection M2 AC/DC 220 V
12 1,250 A 630 ~ 1,600 AF 4P J Manual Connection M3 AC 380 V 2)
W
Reverse Phase NRST
16 1,600 A M4 AC 440 V 2)
Fixed Type (Terminal Form) M5 DC 24 V
20 2,000 A 2,000 ~ 3,200 AF 3/4P H Horizontal Type M6 DC 48 V
B
Standard RST (N)
25 2,500 A V Vertical Type M9 DC 125 V
2,000 ~ 3,200 AF 4P
32 3,200 A X
Reverse Phase NRST Upper Side:Horizontal/
T
Lower Side:Vertical

Upper Side:Vertical/
L
Lower Side:Horizontal

Front Type and


P 1) Mounting Type Selected
by Customer

Draw-Out Type
(Combined with Cradle)

Auto Connection +
B
Horizontal Type

Auto Connection +
C
Vertical Type

Auto Connection +
D Upper Side:Horizontal/
Lower Side:Vertical
Auto Connection +
E Upper Side:Vertical/
Lower Side:Horizontal
Auto Connection +
G 1) Front Type/Mounting Type
Selected by Customer

Manual Connection +
K
Horizontal Type

Manual Connection +
M
Vertical Type

Manual Connection +
N Upper Side:Horizontal/
Lower Side:Vertical
Manual Connection +
Q Upper Side:Vertical/
Lower Side:Horizontal
Manual Connection +
R 1) Front Type/Mounting Type
Selected by Customer

※ 1) P, G, R type of fixed terminal bus bar arrangement should be ordered per terminal
and mounted personally. (Refer to the additional components).
2) Charging motor AC 380 V, AC 440 V are currently under development.
3) O, V can only be applicable to frame A.
- B frame can be applied above 400 A of CT.
4) When applying LP type of OCR, place an order for the voltage module (HGNS VM)
additional for mounting.
Air Circuit Breakers 131

VCB
C2 S2 61 K AB

Parts Mounted on Cradle


Closing Coil Trip Coil Over-Current Trip CT 3) Parts for Main Unit (Only Applicable when Placing
an Order for Combination Type)
C0 N/A S0 N/A General Feeder 0 OCR N/A INST (UVT Coil) Time Delay Type
C1 AC/DC 110 V S1 AC/DC 110 V 00 N/A O 200 A U1 AC/DC 110 V (UVT Coil + UVT Controller)

C2 AC/DC 220 V S2 AC/DC 220 V 50 Hz V 320 A U2 AC/DC 220 V V1 AC/DC 110 V


C3 AC 380 V S3 AC 380 V 50 GPR-LN E 400 A U3 AC 380 V V2 AC/DC 220 V
C4 AC 440 V S4 AC 440 V 51 GPR-LA T 630 A U4 AC 440 V V3 AC 380 V

ACB
C7 DC 24 V S7 DC 24 V 52 GPR-LAG H 800 A U7 DC 24 V V4 AC 440 V
C8 DC 48 V S8 DC 48 V 53 GPR-LAZ J 1,000 A U8 DC 48 V V9 DC 125 V
C9 DC 125 V S9 DC 125 V 54 GPR-LP 4)
K 1,250 A U9 DC 125 V
60 Hz L 1,600 A Position S/W
60 GPR-LN M 2,000 A Secondary Trip Coil Test 1C,
AQ
61 GPR-LA N 2,500 A S1 AC/DC 110 V Connected 1C

62 GPR-LAG P 3,200 A S2 AC/DC 220 V AR Connected 2C


63 GPR-LAZ S3 AC 380 V AS Test 2C
64 GPR-LP 4) S4 AC 440 V Isolated 1C,
AT
S7 DC 24 V Inserted 1C

S8 DC 48 V AU Inserted 2C

MCCB
S9 DC 125 V AV Isolated 2C

Test 2C,
P4
Connected 2C
On/Off Button Lock
AM
Device PT Test 4C

Auxiliary Switch Isolated 1C, Test 1C,


AA PS
(Additional 1a 1b) Connected 2C

Inserted 1C,
Auxiliary Switch
A5 PQ Isolated 1C, Test 1C,
- U□ is only applicable when instantaneous type and only the UVT coil is installed. (Additional 5a 5b)
Connected 1C
When using time delay type, place a separate order for the time delay type of controller
Inserted 2C,
(HGNS ~ ) and install externally. Key Lock Device
AB P8 Isolated 2C, Test 2C,
- V□ is only applicable when time delay type is applied and the UVT coil is installed (Prevent ON)
Connected 2C
in the main unit while the time delay type of controller is installed at the side of Inserted 1C,
B8 OCR MCR
the cradle. In case of dimension issues, place an order for HGNS V□ for separate PR Isolated 1C, Test 3C,
installation. OCR Manual Reset Connected 3C
BR
- B0:The mechanical interlock device has to be ordered separately and when B0 is
marked, only the components interlocked inside the main unit are assembled for
Function
MS
Auto Connection
release. (Refer to additional components). OCR Manual Reset &
BA BC Control Terminal’s
- When S□ Secondary trip is applied, UVT coil cannot be applied at the same time. Alarm S/W 2a
Safety Cover
- When using T□ trip coil monitoring contact, it becomes 4a4b and when using MCR
CR Manual Reset + AE Safety Shutter
function of B8 OCR, it can be used as 4a5b. When both functions are applied, 3a4b can BH High Capacity Alarm
be possible. S/W 1a AX Arc Shield
- In the order code for the main unit only (A/J/Fixed type), combination with cradle Closing Preparation AF Fixing Block
accessories is not possible and the cradle accessory arrangement is only possible Contact (B6 and BT
when purchased with cradle arrangement. For the independent release of the main cannot be Applied
BT
unit, place a separate order (HGNS ~ ) (refer to additional components). Simultaneously
- Position switch cannot be overlapped for use and can only be attached only at the (Overlapping
right side of cradle. In case a combination other than the combination indicate is Mounting)
required, make an inquiry separately. B6 Spring Charge Switch
- Mechanical interlock device (B0), external auxiliary contact (MC) and fixing block (AF)
AG Door Flange
cannot be used together.
RELAY

- BC:The control terminal’s safety cover is only available for the auto connection. Auxiliary Switch
A5
- AK:Short “b” is only available for auto connection and is attached to 51, 52. It can be (5 ~ 5b)
attached as much as the number of “B” contact so upon additional mounting,
place a separate order (HGNS ~ ).
- AG:O  riginally, it is attached separately but upon release, the front cover is inserted
when shipped.
- AA and BA (BH) cannot be attached at the same time.
- UVT and Secondary Trip Coil cannot be attached at the same time.
132 Air Circuit Breakers

Order Code
When Placing an Order for the Cradle

DHS 12 A 3 A H AE

Control
Frame Category & Terminal Bus Bar
Model Name Rated Frame No. of Poles Terminal Accessories
Neutral Pole Arrangement
Connection
Air Circuit 10 DHS06 ~ 10A (W) 630 ~ 1,600 A 3/4P 3 3 Pole H Horizontal Type
Auto Safety
DHS Breakers A Standard RSTN A AE
16 DHS12 ~ 16A (W) 4 4 Pole Connection V Vertical Type Shutter
Cradle Reverse Phase NRST

Manual Upper Side:


J ※ AE:Safety
Connection Horizontal/
20 DHS20B (X) T shutter lock is
2,000 ~ 3,200 A 3/4P Lower Side:
Vertical supplied with
25 DHS25B (X) B Standard RSTN
Reverse Phase NRST safety shutter.
32 DHS32B (X) Upper Side:
Vertical/
L
※M
 arking upon Shipping of Cradle Lower Side:
·DHS06/08/10A (W) > DHS06 ~ 16A (W) Horizontal
·DHS12/16A (W) > DHS12 ~ 16A (W)
Front Type and
·DHS20B (X) > DHS20B (X) Mounting Type
·DHS25B (X) > DHS25B (X) P 1)
Selected by
·DHS32B (X) > DHS32B (X) Customer

※ 1) P type of fixed terminal bus bar arrangement should be ordered per terminal and mounted personally. (Refer to the additional components).
Applicable frames are A06 ~ 16, B06 ~ 32.
Air Circuit Breakers 133

Installation and Environment

VCB
Internal Resistance and Power Consumption

Fixed Type Draw-Out Type Fixed Type Draw-Out Type


Rated Rated
Model Internal Power Internal Power Model Internal Power Internal Power
Current Current
Name Resistance Consumption Resistance Consumption Name Resistance Consumption Resistance Consumption
(A) (A)
(μΩ) (W/3Phase) (μΩ) (W/3Phase) (μΩ) (W/3Phase) (μΩ) (W/3Phase)
630 20 24 40 48 2,000 10 120 20 240
B Frame
800 20 38 40 77 HGS/HGN 2,500 10 188 20 375
A Frame 20 ~ 32
HGS/HGN 1,000 20 60 40 120 3,200 10 307 20 614
06 ~ 16
1,250 20 94 40 188 2,000 10 120 20 240
1,600 20 154 40 307 B Frame 2,500 10 188 20 375
630 15 18 30 36 HGN 40 3,200 10 307 20 614
800 15 29 30 58 4,000 8 384 11 528

ACB
A Frame 1,000 15 45 30 90 C Frame 4,000 8 384 11 528
HGN 20 1,250 15 70 30 141 HGN 40 ~ 50 5,000 8 600 11 825
1,600 15 115 30 230 4,000 6 288 9 432
D Frame
2,000 13 156 27 324 HGN 5,000 6 450 9 675
40 ~ 63
6,300 5 595 7 833
※T
 he abovementioned power consumption is the total power consumption of the
circuit breaker based on 50/60 Hz, 3/4 pole.
The inner resistance value is the resistance value per pole.
Power Factor = 1.0

Tightening Torque

MCCB
Main Circuit
Tightening Torque Control Circuit
M10 : 270 ± 32 kgf-cm Tightening Torque
M12 : 480 ± 57 kgf-cm M3.5 : 8.8 ± 1.1 kgf-cm

Detail
Detail

Insulation Voltage MS
When designing the switchboard, maintain the insulation
distance in accordance with the table below.
A

Insulation Distance from ARC Unit:mm

Item A B
Fixed Type 150 50
Draw-Out Type without Arc Shield 150 50
B B
Draw-Out Type with Arc Shield 0 50
RELAY

e)
anc
Dist
Minimum Insulation Distance at Charging Side tion
n sula
D (I
Insulating Voltage Minimum Insulation Distance(mm)
Below 600 V 8
Above 600 V, below 1,000 V 14
134 Air Circuit Breakers

Installation and Environment


Calibration of Rating Current
Calibration of Rating Current Following Ambient Temperature and Motion Specification

Applicable
Model Rating ACB
Motion
Name Current Terminal
Standard

Horizontal Type Vertical Type


40 ℃ 45 ℃ 50 ℃ 55 ℃ 60 ℃ 40 ℃ 45 ℃ 50 ℃ 55 ℃ 60 ℃
200 A 200 A 200 A 200 A 200 A 200 A 200 A 200 A 200 A 200 A 200 A
5 t×50×1 ea
400 A 400 A 400 A 400 A 400 A 400 A 400 A 400 A 400 A 400 A 400 A
5 t×50×2 ea
630 A 630 A 630 A 630 A 630 A 630 A 630 A 630 A 630 A 630 A 630 A
10 t×60×1 ea
6 t×50×2 ea
800 A 800 A 800 A 800 A 800 A 800 A 800 A 800 A 800 A 800 A 800 A
A Frame 10 t×60×1 ea
HGS/HGN 1,000 A 15 t×50×1 ea 8 t×50×2 ea 1,000 A 1,000 A 1,000 A 1,000 A 1,000 A 1,000 A 1,000 A 1,000 A 1,000 A 1,000 A
06 ~ 16 6 t×75×2 ea - - - - -
1,250 A 8 t×60×2 ea 1,250 A 1,250 A 1,250 A 1,250 A 1,250 A
1,250 A 1,250 A 1,250 A 1,250 A 1,250 A
10 t×50×2 ea
6 t×75×3 ea - - - - -
1,600 A 10 t×60×2 ea 1,600 A 1,600 A 1,580 A 1,550 A 1,500 A
1,600 A 1,600 A 1,520 A 1,480 A 1,420 A
8 t×60×3 ea
A Frame 8 t×75×3 ea
2,000 A 15 t×75×1 ea - - - - - 2,000 A 2,000 A 1,940 A 1,860 A 1,780 A
HGN20 10 t×100×2 ea
5 t×50×2 ea
630 A 630 A 630 A 630 A 630 A 630 A 630 A 630 A 630 A 630 A 630 A
10 t×60×1 ea
6 t×50×2 ea
800 A 800 A 800 A 800 A 800 A 800 A 800 A 800 A 800 A 800 A 800 A
10 t×60×1 ea
1,000 A 8 t×50×2 ea 1,000 A 1,000 A 1,000 A 1,000 A 1,000 A 1,000 A 1,000 A 1,000 A 1,000 A 1,000 A
6 t×75×2 ea - - - - -
B Frame 1,250 A 8 t×60×2 ea 1,250 A 1,250 A 1,250 A 1,250 A 1,250 A
1,250 A 1,250 A 1,250 A 1,250 A 1,250 A
HGS/HGN 20 t×75×1 ea 10 t×50×2 ea
06 ~ 25 6 t×75×3 ea - - - - -
1,600 A 10 t×60×2 ea 1,600 A 1,600 A 1,600 A 1,600 A 1,600 A
1,600 A 1,600 A 1,600 A 1,600 A 1,600 A
8 t×60×3 ea
8 t×75×3 ea 2,000 A 2,000 A 2,000 A 2,000 A 2,000 A
2,000 A 2,000 A 2,000 A 2,000 A 2,000 A 2,000 A
10 t×100×2 ea - - - - -
10 t×75×3 ea
2,500 A 2,500 A 2,500 A 2,500 A 2,400 A 2,300 A 2,500 A 2,500 A 2,500 A 2,500 A 2,500 A
8 t×75×4 ea
B Frame 10 t×100×3 ea - - - - -
3,200 A 20 t×90×1 ea 3,200 A 3,200 A 3,120 A 3,050 A 2,950 A
HGN32 10 t×75×4 ea 3,200 A 3,200 A 3,100 A 3,000 A 2,900 A
4,000 A 10 t×100×4 ea
15 t×100×2 ea 4,000 A 4,000 A 3,900 A 3,800 A 3,640 A - - - - -
B Frame Horizontal 10 t×125×3 ea
HGN40 4,000 A 10 t×100×4 ea
15 t×125×2 ea - - - - - 4,000 A 4,000 A 3,950 A 3,800 A 3,680 A
Vertical 10 t×125×3 ea
3,200 A 10 t×100×3 ea 3,200 A 3,200 A 3,100 A 3,000 A 2,900 A 3,200 A 3,200 A 3,100 A 3,000 A 2,900 A
C Frame
4,000 A 20 t×125×2 ea 10 t×100×4 ea 4,000 A 4,000 A 3,920 A 3,860 A 3,800 A 4,000 A 4,000 A 3,960 A 3,900 A 3,880 A
HGN32 ~ 50
5,000 A 10 t×125×4 ea 5,000 A 5,000 A 4,900 A 4,800 A 4,700 A 5,000 A 5,000 A 4,950 A 4,900 A 4,850 A
4,000 A 10 t×100×4 ea 4,000 A 4,000 A 4,000 A 4,000 A 4,000 A 4,000 A 4,000 A 4,000 A 4,000 A 4,000 A
D Frame
5,000 A 20 t×125×2 ea 10 t×125×4 ea 5,000 A 5,000 A 4,900 A 4,820 A 4,750 A 5,000 A 5,000 A 4,950 A 4,870 A 4,850 A
HGN40 ~ 63
6,300 A 10 t×150×4 ea 6,300 A 6,300 A 6,170 A 6,040 A 5,900 A 6,300 A 6,300 A 6,220 A 6,160 A 6,100 A

※ The ambient temperature is based on the external temperature of the circuit breaker and the motion that can be applicable to the circuit breaker is applied.
The motion is based on copper material with no separate painting.
The maximum allowable temperature of the motion is below 100 ℃.

Calibration of Rating Current Following Altitude Item Altitude 2,000 m 3,000 m 4,000 m 5,000 m
ACB is designed to be used at altitudes below 2,000 m. Withstand Voltage (V) 3,500 3,150 2,500 2,100
Average Insulating Voltage (V) 1,000 900 700 600
When used at above 2,000 m, change the ratings depending on
Max. Operation Voltage (V) 690 590 520 460
the surrounding environment condition for use. Current Calibration Coefficient 1×In 0.99×In 0.96×In 0.94×In
Air Circuit Breakers 135

VCB
Derating Table (HGN)

4
3
2
Switchboard Composition
1
Connection Type

Model Name HGN 06 ~ 08 HGN 10

Rated Current 2)
~ 800 A 1,000 A

Busbar Dimensions (mm) 2 ea×50×6 2 ea×50×8

ACB
Ventilated Switchboard Board 4 800↓
(IP31) 3)
3 800↓ 800↓ 1,000
Ta 1) = 30 ~ 40 ℃
H 2 800↓ 800↓ 800↓ 1,000 1,000

1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000

4 800↓
H
3 800↓ 800↓ 1,000
Ta = 40 ~ 50 ℃
D 2 800↓ 800↓ 800↓ 1,000 1,000
W
1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000

4 800↓

MCCB
D 3 800↓ 800↓ 1,000
W
Ta = 50 ~ 60 ℃
Area of Intake Ventilator:350 cm2 2 800↓ 800↓ 800↓ 1,000 1,000
Area of Exhaust Ventilator:350 cm2
1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000

Non-Ventilated Switchboard 4 800↓


(IP41/54) 4)
3 800↓ 800↓ 1,000
Ta 1) = 30 ~ 40 ℃
2 800↓ 800↓ 800↓ 1,000 1,000

1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000

4 800↓

3 800↓ 800↓ 1,000


H Ta = 40 ~ 50 ℃
2 800↓ 800↓ 800↓ 1,000 1,000

1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000


MS
H 4 800↓

3 800↓ 800↓ 1,000


D
W
Ta = 50 ~ 60 ℃
2 800↓ 800↓ 800↓ 1,000 1,000

1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1000

Panel Dimensions
D
(mm):W×H×D 800×2,300×900
W
Area of Outlet Vents (IP31) 350 cm2

Area of Inlet Vents (IP31) 350 cm2

※ 1) The ambient temperature, Ta refers to the external temperature of the panel (IEC 60439-1).
2) The rated current satisfies the temperature condition in accordance with the temperature test regulation of IEC 60947-1, 2. When installed within the panel, the derating of
RELAY

additional current and recommended motion specification must be used.


3) The ventilation structure has to been designed to reduce the temperature of the product installed in the panel.
4) Forced ventilation device must be added in order to reduce the temperature inside the panel in an enclosed structure.
The load rate under the derating table above must be used below 70 % of the rated current. In case it is smaller than the designated bus bar size, it causes an increase in
temperature due to the reduced area of the bus bar. In order to protect the load, the current load rate must be reduced to a safe range.
136 Air Circuit Breakers

Installation and Environment


Derating Table (HGN)

4
3
2
Switchboard Composition
1
Connection Type

Model Name HGN 12A HGN 16A HGN 20A

Rated Current 2)
1,250 A 1,600 A 2,000 A

Busbar Dimensions (mm) 2 ea×75×8 3 ea×75×8 2 ea×100×10

Ventilated Switchboard (IP31) 3) 4

3 1,250 2,000
Ta 1) = 30 ~ 40 ℃
H 2 1,250 1,250 1,600 2,000 2,000

1 1,250 1,250 1,250 1,250 1,600 1,600 1,600

4
H
3 1,250 1,900
Ta = 40 ~ 50 ℃
D 2 1,250 1,250 1,600 2,000 2,000
W
1 1,250 1,250 1,250 1,250 1,600 1,600 1,600

4
D
W 3 1,250 1,800
Ta = 50 ~ 60 ℃
Area of Intake Ventilator:350 cm2 2 1,250 1,250 1,470 1,900 1,900
Area of Exhaust Ventilator:350 cm2
1 1,250 1,250 1,250 1,250 1,520 1,600 1,600

Non-Ventilated Switchboard 4
(IP41/54) 4)
3 1,250 1,750
Ta 1) = 30 ~ 40 ℃
2 1,250 1,250 1,600 1,850 1,850

1 1,250 1,250 1,250 1,250 1,600 1,600 1,600

3 1,250 1,650
H Ta = 40 ~ 50 ℃
2 1,250 1,250 1,500 1,750 1,750

1 1,250 1,250 1,250 1,250 1,500 1,600 1,600

H 4

3 1,250 1,550
D
W
Ta = 50 ~ 60 ℃
2 1,250 1,250 1,400 1,650 1,650

1 1,250 1,250 1,250 1,250 1,400 1,520 1,520

Panel Dimensions
D (mm):W×H×D 800×2,300×900
W
Area of Outlet Vents (IP31) 350 cm2

Area of Inlet Vents (IP31) 350 cm2

※ 1) The ambient temperature, Ta refers to the external temperature of the panel (IEC 60439-1).
2) The rated current satisfies the temperature condition in accordance with the temperature test regulation of IEC 60947-1, 2. When installed within the panel, the derating of
additional current and recommended motion specification must be used.
3) The ventilation structure has to been designed to reduce the temperature of the product installed in the panel.
4) Forced ventilation device must be added in order to reduce the temperature inside the panel in an enclosed structure.
The load rate under the derating table above must be used below 70 % of the rated current. In case it is smaller than the designated bus bar size, it causes an increase in
temperature due to the reduced area of the bus bar. In order to protect the load, the current load rate must be reduced to a safe range.
Air Circuit Breakers 137

VCB
4
3
2
Switchboard Composition
1
Connection Type

Model Name HGN 06 ~ 20B HGN 25B HGN 32B HGN 40B

Rated Current 2)
2,000 A 2,500 A 3,200 A 4,000 A

Busbar Dimensions (mm) 2 ea×100×10 3 ea×100×10 3 ea×125×10 4 ea×125×10

ACB
Ventilated Switchboard (IP31) 3) 4

3 2,000↓
Ta 1) = 30 ~ 40 ℃
H 2 2,000↓ 2,000↓ 2,000↓ 2,375 2,500 3,040 3,200 3,320 3,700

4
H
3 2,000↓
Ta = 40 ~ 50 ℃
D 2 2,000↓ 2,000↓ 2,000↓ 2,250 2,380 2,880 3,100 3,160 3,500
W
1

MCCB
D
W 3 2,000↓
Ta = 50 ~ 60 ℃
Area of Intake Ventilator:350 cm2 2 2,000↓ 2,000↓ 2,000↓ 2,100 2,250 2,690 2,900 2,960 3,280
Area of Exhaust Ventilator:350 cm2
1

Non-Ventilated Switchboard 4
(IP41/54) 4)
3 2,000↓
Ta 1) = 30 ~ 40 ℃
2 2,000↓ 2,000↓ 2,000↓ 2,125 2,275 2,650 2,850 3,040 3,320

3 1,900↓
H Ta = 40 ~ 50 ℃
2 1,900↓ 1,960↓ 1,960↓ 2,000 2,150 2,550 2,700 2,880 3,120

1
MS
H 4

3 1,780↓
D
W
Ta = 50 ~ 60 ℃
2 1,800↓ 1,920↓ 1,920↓ 1,900 2,020 2,370 2,530 2,720 2,960

Panel Dimensions
D (mm):W×H×D 800×2,300×900
W
Area of Outlet Vents (IP31) 350 cm2

Area of Inlet Vents (IP31) 350 cm2


RELAY
138 Air Circuit Breakers

Installation and Environment


Derating Table (HGN)

4
3
2
Switchboard Composition
1
Connection Type

Model Name HGN 40C HGN 50C HGN 40D HGN 50D HGN 63D

Rated Current 2)
4,000 A 5,000 A 4,000 A 5,000 A 6,300 A

Busbar Dimensions (mm) 4 ea×125×10 5 ea×140×10 4 ea×125×10 5 ea×140×10 5 ea×160×10

Ventilated Switchboard (IP31) 3) 4

3
Ta 1) = 30 ~ 40 ℃
H 2 3,900 4,000 4,550 4,850 4,000 4,000 4,700 5,000 5,550 5,850

4
H
3
Ta = 40 ~ 50 ℃
D 2 3,850 3,900 4,350 4,650 4,000 4,000 4,450 4,850 5,380 5,670
W
1

4
D
W 3
Ta = 50 ~ 60 ℃
Area of Intake Ventilator:350 cm2 2 3,800 3,850 4,100 4,400 4,000 4,000 4,200 4,600 5,080 5,350
Area of Exhaust Ventilator:350 cm2
1

Non-Ventilated Switchboard 4
(IP41/54) 4)
3
Ta 1) = 30 ~ 40 ℃
2 3,800 3,900 4,200 4,500 4,000 4,000 4,350 4,650 5,050 5,290

3
H Ta = 40 ~ 50 ℃
2 3,650 3,800 3,950 4,250 4,000 4,000 4,100 4,400 4,780 5,040

H 4

3
D
W
Ta = 50 ~ 60 ℃
2 3,550 3,650 3,750 4,050 3,840 3,950 3,850 4,150 4,490 4,730

Panel Dimensions
D (mm):W×H×D 1,000×2,300×900 1,400×2,300×1,500
W
Area of Outlet Vents (IP31) 500 cm 2
500 cm2

Area of Inlet Vents (IP31) 500 cm2 500 cm2

※ 1) The ambient temperature, Ta refers to the external temperature of the panel (IEC 60439-1).
2) The rated current satisfies the temperature condition in accordance with the temperature test regulation of IEC 60947-1, 2. When installed within the panel, the derating of
additional current and recommended motion specification must be used.
3) The ventilation structure has to been designed to reduce the temperature of the product installed in the panel.
4) Forced ventilation device must be added in order to reduce the temperature inside the panel in an enclosed structure.
The load rate under the derating table above must be used below 70% of the rated current. In case it is smaller than the designated bus bar size, it causes an increase in
temperature due to the reduced area of the bus bar. In order to protect the load, the current load rate must be reduced to a safe range.
Air Circuit Breakers 139

VCB
Derating Table (HGS)

4
3
2
Switchboard Composition
1
Connection Type

Model Name HGS 06 ~ 08A HGS 10A HGS 12A

Rated Current 2)
~ 800 A 1,000 A 1,250 A

Busbar Dimensions (mm) 2 ea×50×6 2 ea×50×8 2 ea×75×8

ACB
Ventilated Switchboard (IP31) 3) 4 800↓

3 800↓ 800↓ 1,000 1,250


Ta 1) = 30 ~ 40 ℃
H 2 800↓ 800↓ 800↓ 1,000 1,000 1,250 1,250

1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000 1,250 1,250 1,250 1,250

4 800↓
H
3 800↓ 800↓ 1,000 1,250
Ta = 40 ~ 50 ℃
D 2 800↓ 800↓ 800↓ 1,000 1,000 1,250 1,250
W
1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000 1,250 1,250 1,250 1,250

4 800↓

MCCB
D
W 3 800↓ 800↓ 1,000 1,050
Ta = 50 ~ 60 ℃
Area of Intake Ventilator:350 cm2 2 800↓ 800↓ 800↓ 1,000 1,000 1,200 1,150
Area of Exhaust Ventilator:350 cm2
1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000 1,250 1,250 1,250 1,250

Non-Ventilated Switchboard 4 800↓


(IP41/54) 4)
3 800↓ 800↓ 1,000 1,050
Ta 1) = 30 ~ 40 ℃
2 800↓ 800↓ 800↓ 1,000 1,000 1,200 1,150

1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000 1,250 1,250 1,250 1,250

4 800↓

3 800↓ 800↓ 900 1,000


H Ta = 40 ~ 50 ℃
2 800↓ 800↓ 800↓ 975 950 1,100 1,050

1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 1,000 1,000 1,250 1,250 1,150 1,150
MS
H 4 800↓

3 800↓ 800↓ 850 975


D
W
Ta = 50 ~ 60 ℃
2 800↓ 800↓ 800↓ 950 900 1,050 1,000

1 800↓ 800↓ 800↓ 800↓ 800↓ 1,000 1,000 975 950 1,250 1,250 1,150 1,050

Panel Dimensions
D (mm):W×H×D 800×2,300×900
W
Area of Outlet Vents (IP31) 350 cm2

Area of Inlet Vents (IP31) 350 cm2


RELAY
140 Air Circuit Breakers

Installation and Environment


Derating Table (HGS)

4
3
2
Switchboard Composition
1
Connection Type

Model Name HGS 16A HGS 20B HGS 25B HGS 32B

Rated Current 2)
1,600 A 2,000 A 2,500 A 3,200 A

Busbar Dimensions (mm) 3 ea×75×8 2 ea×100×10 3 ea×100×10 3 ea×25×10

Ventilated Switchboard (IP31) 3) 4

3 2,000
Ta 1) = 30 ~ 40 ℃
H 2 1,600 2,000 2,000 2,000 2,375 2,500 2,880 3,100

1 1,600 1,600 1,600

4
H
3 1,900
Ta = 40 ~ 50 ℃
D 2 1,520 1,900 2,000 2,000 2,250 2,380 2,690 2,900
W
1 1,600 1,600 1,600

4
D
W 3 1,800
Ta = 50 ~ 60 ℃
Area of Intake Ventilator:350 cm2 2 1,450 1,800 1,950 1,900 2,100 2,250 2,500 2,700
Area of Exhaust Ventilator:350 cm2
1 1,520 1,600 1,520

Non-Ventilated Switchboard 4
(IP41/54) 4)
3 1,750
Ta 1) = 30 ~ 40 ℃
2 1,520 1,750 1,850 1,850 2,125 2,275 2,550 2,700

1 1,600 1,600 1,600

3 1,650
H Ta = 40 ~ 50 ℃
2 1,450 1,650 1,750 1,750 2,000 2,150 2,370 2,530

1 1,520 1,600 1,520

H 4

3 1,550
D
W
Ta = 50 ~ 60 ℃
2 1,370 1,550 1,650 1,650 1,900 2,020 2,200 2,370

1 1,370 1,450 1,450

Panel Dimensions
D (mm):W×H×D 800×2,300×900 800×2,300×900
W
Area of Outlet Vents (IP31) 350 cm 2
350 cm2

Area of Inlet Vents (IP31) 350 cm2 350 cm2

※ 1) The ambient temperature, Ta refers to the external temperature of the panel (IEC 60439-1).
2) The rated current satisfies the temperature condition in accordance with the temperature test regulation of IEC 60947-1, 2. When installed within the panel, the derating of
additional current and recommended motion specification must be used.
3) The ventilation structure has to been designed to reduce the temperature of the product installed in the panel.
4) Forced ventilation device must be added in order to reduce the temperature inside the panel in an enclosed structure.
The load rate under the derating table above must be used below 70 % of the rated current. In case it is smaller than the designated bus bar size, it causes an increase in
temperature due to the reduced area of the bus bar. In order to protect the load, the current load rate must be reduced to a safe range.
Air Circuit Breakers 141

VCB
Standard Operation Conditions
The following regulated value has been set in accordance with IEC 62271-100 (IEC 62271-1).

| Ambient Temperature | -5 ~ +40 °C The surrounding environment may affect the insulation
(Daily average temperature of below 35 °C) performance and durability of the circuit break so the
| Altitude | Below 2,000 m above sea level operation conditions must be checked clearly before
| Relative Humidity | Below 85 % (Below daily average of 85 %) application.

ACB
In case of operating in high ambient temperature In case of operating in places with high
exceeding 40 °C, use according to the derating humidity and frequent rain, the insulation or
calibrated depending on the ambient electrical performance may drop.
temperature indicated in the catalogue.

In case of storing and using in places with a lot When storing circuit breaker without
of dust and humidity, the use of a dust cover electric circuit:-25 °C ~ 85 °C
or dehumidifier is recommended. Excessive When storing circuit breaker with

MCCB
impact and vibration may cause damage in the electric circuit:-15 °C ~ 70 °C
operation mechanism. After storing in low temperature, store for more
than 8 hours in room temperature then store in an
open location for the type with charging motor.

In case there is a lot of corrosive gas, it must be In case of highland with high altitude, the
stored in an enclosed protective structure to insulation performance drops so please apply
minimize damage. the highest rating product after checking the
insulation performance calibration coefficient.

MS

Special Operating Conditions

The HG-Series air circuit breaker has been designed/manufactured to operate in a standard operating environment designated by the
IEC standard and in case of operating the circuit breaker in the following special environment, contact our company.

˙In case the altitude above sea level and the ambient ˙In case the relative humidity exceeds the standard operating
temperature exceeds the standard operating environment environment
˙In case of a region with a lot of sea wind or salinity ˙In case of a region with a lot of humidity and frequent rainfall
RELAY

˙In case of a region with snow and freezing ˙In case of a region with a lot of dust, vapor, corrosive and
˙In case of a region of frequent shock and vibration combustible gas, wet steam
˙In other special environment that exceeds the standard
environment

※ Special operating environment and condition may cause damage in the product (Increase in resistance at main circuit, rust, change in coating).
142 Air Circuit Breakers

Installation and Environment


Standard Operating Conditions
Load Rate (I/In) Altitude
˙ACB cannot be used in outdoor panel in principle. In case ˙Below 2,000 m
of inevitable installation, the ambient temperature must be
Altitude
below 40 °C and the load rate must be below 50 % of the rated Item
2,000 m (6,600 ft) 2,600 m (8,500 ft) 3,900 m (13,000 ft)
current. In case it is not complied with, it may cause heating
Isolation Voltage
and burning in the ACB. (V)
1,000 950 800

˙As for the total harmonic distortion (THD) rate, it must be


Operating Voltage
managed below 5 % in the distribution system phase. In case it (V)
690 655.5 552

is not complied with, it may cause heating in the product.


Allowed Current
In 0.99×In 0.96×In
(V)

Load Rate Hours of Use Effect Installation

Normal Condition
I/In ≤ 80 % 24/24 Hours -
(Recommended)

Periodic
80 < I/In ≤ 90 % 24/24 Hours -
Inspection

Change in Plastic
Additional
I/In = 100 % 24/24 Hours Insulation
Exhaust
Material Color

Protection Degree Provided by Enclosures (IP Code)


˙Standard:IP30 (When the ACB front cover part of the switchboard door is cut out)
˙With Dust Cover:IP52

Classification of Protection Degree Provided by Enclosures (IP code) IEC 60529


Indication: I P
Second Characteristic Numeral:Level of preventing liquid
from permeating into the external box (0 ~ 8)
First Characteristic Numeral:Level of preventing particulate
materials from permeating into the external box (0 ~ 6)

※ In the event indicating the characteristic number is not required, mark the said area with ‘X’.

Classification Table Following the Degree

Protection Degree
Numeral
First Characteristic Numeral (Particulate) Second Characteristic Numeral (Liquid)

0 No protection (Open) No protection (Open)


1 Protected against external objects with a diameter of 50 mm and above Protected against vertical fall
2 Protected against external objects with a diameter of 12.5 mm and above Protected against falling with a gradient of 15 °
3 Protected against external objects with a diameter of 2.5 mm and above Protected against falling with a gradient of 60 °
4 Protected against external objects with a diameter of 1.0 mm and above Protected against spraying water from up, down, left, right (Splash proof)
5 Protected against deposition risk of dust and others Protected against spraying water from up, down, left, right (Hose proof)
6 Complete protection without deposition of dust and others Protected against heavy rainfall and tsunami (Deckwater proof)

Protected against submersion under certain pressure and


7 -
certain time (Immersible)

8 - Protected against complete submersion (Submersible)


Air Circuit Breakers 143

VCB
Product Installation Condition
˙In order to prevent burning of products caused by electrical fault and to enhance structural safety of the panel when installing the
product in areas with concerns of vibration, mount the fixing block and install the terminal supporting position like the figure.
˙In particular, when executing short-time/short-circuit panel testing, it must be installed for structural safety.
˙For the support dimension of the product, refer to the drawing.
˙In the event of switchboard (Panel) development test (Short-time, short-circuit), the bus bar inside the panel must be supported firmly
according to the following conditions.

Unit:mm

B
A

ACB
Ø12.1

150 150
119.3 6 119.3 6
278.3

Fixing Fixing
Block Block
278.3

278.3
Front

Horizontal Type Vertical Type

MCCB
70

250

119.3 6 119.3 6 119.3 6 119.3 6

Fixing Fixing Fixing Fixing


Block Block Block Block
278.3

278.3

278.3

278.3
250

Front Type Wrong Installation


70

MS

Model Name A B
HGS 06 ~ 16A 3P, HGN 06 ~ 20A 3P 416 440
HGS 06 ~ 16A 4P, HGN 06 ~ 20A 4P 501 525
RELAY

HGS 20 ~ 32A 3P, HGN 20 ~ 40A 3P 487 511


HGS 20 ~ 32A 4P, HGN 20 ~ 40A 4P 602 626
HGN 40 ~ 50C 3P 712 736
HGN 40 ~ 50C 4P 906 982
HGN 40 ~ 63C 3P 854 878
HGN 40 ~ 63C 4P 1,084 1,108
144 Air Circuit Breakers

Maintenance Inspection List


Regular Inspection and Part Replacement
Regular Inspection

Inspection Item
Inspection Form Inspection Period
Main Review Item Details and Countermeasures

Visual examination must be executed and there must be no foreign substance inside.
Foreign Substance Every 6 months
Blow away the foreign substance using compressed air.

Gap Execute visual examination and there must be no cracks or gaps. Replace, repair

Circuit breaker must be closed manually to inspect the operation area during normal
Operation Once a year
status.

General Regular Apply an adequate amount of grease on each pin, axle and bearing.
Inspection Excessive greasing may cause dust and stain from building up.
Greasing Every 6 months
Electrical grease:HITALWBE 28G
Lubiricant grease:Kamro Chemical/CHEMAX HHI 5000#1.

Spring Type The status of the spring must be checked to inspect the damaged area. Replace, repair
Screw/Bolt Type Tighten loose areas using screw or bolt. Every 6 months

Stain on the There must be no dust or stain at the fastening area. Wipe the area well using clean
All the time
Fastening Bolt Area cloth dipped in alcohol.

Total operation frequency:3,000 times Non-current 2,500 time, current 500 time
Paid inspection is
required (Precision
Open/close within the range of rated inspection)
Open/closing frequency:500 times
Below 2,500 AF current
Inspection period:
Open/close in over-load (Around 6 times At least 6 months
Open/closing frequency:25 times after exceeding the
the rated current) area
Mechanical Durability opening/closing
Warranty Lifespan Immediately upon breaking Prevent short-circuit/earth fault frequency
Inspection Precision inspection
Open/close frequency: 2,000 times Non-current 1,500 time, current 500 time
once a year is
recommended
Open/close within the range of rated
Open/close cycle:500 times
current
Contact our company
Above 3,200 AF
to determine is
Open/close in over-load (Around 6 times replacement is
Open/close cycle:25 times
the rated current) area required
Immediately upon breaking Prevent short-circuit/earth fault

Contact with Foreign In case foreign substance has melted onto the grid’s side plate, replace the ionized Replace,
Arc Chamber (Grid)
Substance pieces inside the arc chamber and others. contact our company

Remove foreign substance, dust and oil.


Melting stains on the contact tip surface is caused by open/closing arc.
Visual inspection,
In case the extent of melting caused by arc reduces to 1/3, replace the entire operation no problem
Arc Contact Contact Tip Surface
and fixing moving contact unit. Replace,
contact our company
However, in case there is foreign substance on the contact, precision diagnosis is
required to determine if replacement is necessary through our company’s paid service.

In case the main contact has been worn off and is rough, the surface must be
managed neatly.
Damage of
Main Contact At all times
Main Contact
However, in case there is foreign substance on the contact, precision diagnosis is
required to determine if replacement is necessary through our company’s paid service.

Caution

1. In the event the contact or part is replaced, turn the circuit breaker off and replace after drawing out the disconnected position to isolated.
2. Execute the inspection work after checking whether the remaining heat in the conduction part has been dissipated. It may cause burns.
3. When rubbing the contact tip, ensure that the sludge does not enter the circuit breaker’s mechanical device. After rubbing, wipe the contact tip neatly.
Air Circuit Breakers 145

VCB
Assembly & Disassembly
Loosen the screw for arc chamber assembly. Then, remove the arc chamber. (Level the circuit breaker).
In order to assemble the arc chamber, check the square nut, place the arc chamber in the original position and tighten the fixing screw
(M6).

ACB
Square Nut
(M6)

MCCB
Caution

When replacing the contact or part, turn the circuit breaker off and exchange after drawing out from isolated position.
In addition, execute the inspection work after checking whether the remaining heat in the conduction part has been dissipated.
It may cause burns.

When removing the arc chamber, the square nut for bolt fastening must be removed together.
In the event of on-off operation without removing the square nut, the nut may flow into the pole due to impact.
It may cause malfunction.

When rubbing the contact tip, ensure that the sludge does not enter the circuit breaker’s mechanical device.
After rubbing, wipe the contact tip neatly.

MS
RELAY
146 Air Circuit Breakers

Maintenance Inspection List


Regular Inspection and Part Replacement
Operation Tool

⓳ ⓲

❺ ❹ ❸ ❷ ❶




❻ ⓴

❽ ⓰

❿ ⓯

❶ Arc Chamber ❾ CO Latch ⓱ Arc Fix Contact Tip


❷ Move Contact Fix Base ❿ Closing Cam ⓲ Arc Move Contact Tip
❸ Crossbar Unit ⓫ Mechanism Frame ⓳ Arc Move Contact
❹ Open Lever ⓬ Current Transformer ⓴ Main Move Contact
❺ Close Lever ⓭ Arc Runner Main Move Contact Tip
❻ Charged/Discharged Indicator ⓮ Up Terminal Low Terminal
❼ Open Latch ⓯ In/Out Terminal Body
❽ Close Latch ⓰ Main Fix Contact Tip
Air Circuit Breakers 147

Current Status of Acquired Standards

VCB
Approvals & Certificates
●:Acquired
ACB ◎:In Progress (Expected)

Type of Certification Approvals


Type of Standard KS IEC IEC IEC ANSI

Mark

Testing Institute KS CE DEKRA Nuclear KERI


Certification Country Korea Europe Netherlands Korea Korea
HGS06 A Frame ● ● ●

ACB
HGS08 A Frame ● ● ●
HGS10 A Frame ● ● ●
HGS12 A Frame ● ● ●
HGS16 A Frame ● ● ●
HGS20 B Frame ● ● ●
HGS25 B Frame ● ● ●
HGS32 B Frame ● ● ●
HGN06 A Frame ● ● ● ●
HGN08 A Frame ● ● ● ●
HGN10 A Frame ● ● ● ●
HGN12 A Frame ● ● ● ●

MCCB
HGN16 A Frame ● ● ● ◎ ●
HGN20 A Frame ● ● ● ●
HGN06 B Frame ● ● ● ●
HGN08 B Frame ● ● ● ●
HGN10 B Frame ● ● ● ●
HGN12 B Frame ● ● ● ●
HGN16 B Frame ● ● ● ●
HGN20 B Frame ● ● ● ◎ ●
HGN25 B Frame ● ● ● ●
HGN32 B Frame ● ● ● ◎ ●
HGN40 B Frame ● ● ● ●
HGN32 C Frame ● ● ● ●
HGN40 C Frame ● ● ● ●
HGN50 C Frame ● ● ● ● MS
HGN40 D Frame ● ●
HGN50 D Frame ● ●
HGN63 D Frame ● ●
RELAY
148 Air Circuit Breakers

Current Status of Acquired Standards


Approvals & Certificates
●:Acquired
ACB ◎:In Progress (Expected)

Type of Certification Vessel


Type of Standard Korea U.K U.S.A France Japan Germany Germany Italy Russia

Mark

Testing Institute KR LR ABS BV NK GL DNV RINA RMRS


Certification Country Korea U.K. USA France Japan Germany Germany Italy Russia
HGS06 A Frame ● ● ● ● ● ● ● ● ●
HGS08 A Frame ● ● ● ● ● ● ● ● ●
HGS10 A Frame ● ● ● ● ● ● ● ● ●
HGS12 A Frame ● ● ● ● ● ● ● ● ●
HGS16 A Frame ● ● ● ● ● ● ● ● ●
HGS20 B Frame ● ● ● ● ● ● ● ● ●
HGS25 B Frame ● ● ● ● ● ● ● ● ●
HGS32 B Frame ● ● ● ● ● ● ● ● ●
HGN06 A Frame ● ● ● ● ● ● ● ● ●
HGN08 A Frame ● ● ● ● ● ● ● ● ●
HGN10 A Frame ● ● ● ● ● ● ● ● ●
HGN12 A Frame ● ● ● ● ● ● ● ● ●
HGN16 A Frame ● ● ● ● ● ● ● ● ●
HGN20 A Frame ● ● ● ● ● ● ● ● ●
HGN08 B Frame ● ● ● ● ● ● ● ● ●
HGN10 B Frame ● ● ● ● ● ● ● ● ●
HGN12 B Frame ● ● ● ● ● ● ● ● ●
HGN16 B Frame ● ● ● ● ● ● ● ● ●
HGN20 B Frame ● ● ● ● ● ● ● ● ●
HGN32 B Frame ● ● ● ● ● ● ● ● ●
HGN40 B Frame ● ● ● ● ● ● ● ● ●
HGN32 C Frame ● ● ● ● ● ● ● ● ●
HGN40 C Frame ● ● ● ● ● ● ● ● ●
HGN50 C Frame ● ● ● ● ● ● ● ● ●
HGN40 D Frame ● ● ● ● ● ● ● ● ●
HGN50 D Frame ● ● ● ● ● ● ● ● ●
HGN63 D Frame ● ● ● ● ● ● ● ● ●