Electrical Load Calculation

The document provides a detailed panelboard schedule for the second floor of the Administration Building, listing various air conditioning circuits with their respective loads and cable specifications. It includes information on the total connected load, demand factors, and notes on required components such as MCCBs and RCDs. The overall total demand load is calculated at 31.296 KVA with a balanced load percentage of 9%.

Uploaded by

Zafar Iqbal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views

Electrical Load Calculation

The document provides a detailed panelboard schedule for the second floor of the Administration Building, listing various air conditioning circuits with their respective loads and cable specifications. It includes information on the total connected load, demand factors, and notes on required components such as MCCBs and RCDs. The overall total demand load is calculated at 31.296 KVA with a balanced load percentage of 9%.

Uploaded by

Zafar Iqbal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

DB / Panelboard Schedule

Voltage (V) 400 Main C.B Cable Panel Details


Location SECOND FLOOR Ratings (AT/AF) 25/100 Name/No. Form
Installation WALL MOUNTED
Panel Name PP S.C Rating (Ics)
Size IP 42
Building Name ADMINSTRATION BUILDING Fed From Dimensions W,D,H (mm) 65*30*80 cm

Load Phase Load (VA)


Notes* Circuit No. Circuit Ref. Load Type Wire/Cable mm2 C.B Rating
Designation
R Y B
1 R1 AIR COND 1.9KW 3*6mm2 2375
2 Y1 AIR COND 1.9KW 3*6mm2 2375
3 B1 AIR COND 2.5KW 3*6mm2 3125
4 R2 AIR COND 1.9KW 3*6mm2 2375
5 Y2 AIR COND 1.9KW 3*6mm2 2375
6 B2 AIR COND 2.5KW 3*6mm2 3125
7 R3 AIR COND 1.9KW 3*6mm2 2375
8 Y3 AIR COND 1.915KW 3*6mm2 2393.75
9 B3 AIR COND 2.5KW 3*6mm2 3125
10 R4 AIR COND 2.5KW 3*6mm2 3125
11 Y4 AIR COND 1.915KW 3*6mm2 2393.75
12 B4 AIR COND 1.915KW 3*6mm2 2393.75
13 R5 AIR COND 2.5KW 3*6mm2 3125
14 Y5 AIR COND 2.5KW 3*6mm2 3125
15 B5 AIR COND 1.9KW 3*6mm2 2375
16 R6 AIR COND 2.5KW 3*6mm2 3125
17 Y6 AIR COND 2.5KW 3*6mm2 3125
18 B6 AIR COND 3KW 3*6mm2 3750
19 R7 AIR COND 2.5KW 3*6mm2 3125
20 Y7 AIR COND 2.5KW 3*6mm2 3125
21 B7 AIR COND 3KW 3*6mm2 3750
22 R8 AIR COND 2.5KW 3*6mm2 3125
23 Y8 AIR COND 1.9KW 3*6mm2 2375
24 B8 AIR COND SPACE 3*6mm2 0
25 R9 AIR COND SPACE 3*6mm2 0
26 Y9 AIR COND 1.9KW 3*6mm2 2375
27 B9 SPACE
28 R10 SPACE
29 Y10 SPACE
30 B10 SPACE
31 R11 SPARE
32 11 SPARE
33 B11 SPARE
34 R12 SPARE
35 Y12 SPARE
36 B12 SPARE
TOTAL CONNECTED LOAD (VA) 22750 23662.5 21643.75
*Notes: 5- LCP: Controlled By 1-Ph Contactor Via LCP Lighting Power Heating Air Condition Motor Total
1- MCCB's Rq. 6- RCD 100mA Rq. Connected KVA 0 27160 15000 0 0 42160
2- Push Botton 7- RCD 30mA Rq. Demand Factor 1 0.6 1 0.9 1
3- Indicating Lamps 8- RCD 30mA to 30 A Rq. Demand Load 0 16296 15000 0 0 31296
4- Earth Leakage C.B 9-Selector Switch M-O-A Total Demand Load (KVA) 31.296 KVA

LOAD BALANCE 9% BALANCED