1. GENERAL REQUIREMENTS 1. DUCT MATERIAL AND SIZE: Model: VORTEX LT4 (or equivalent)
· ALL DRYER EXHAUST DUCTS MUST COMPLY WITH THE INTERNATIONAL MECHANICAL · USE RIGID METAL DUCTS WITH A SMOOTH INTERIOR FINISH AND A MINIMUM Material: Powder-coated 24Ga galvanized steel.
CODE (IMC), SECTION 504. THICKNESS OF 0.016 INCHES. Duct Connection: 4-inch round adapters.
· DUCTS MUST BE CONSTRUCTED OF RIGID METAL WITH A SMOOTH INTERIOR FINISH · THE DUCT SHOULD HAVE A NOMINAL DIAMETER OF 4 INCHES. Depth: 5.5 inches.
(MINIMUM THICKNESS: 0.016 INCHES). 2. ROUTING AND INSTALLATION: Lint Monitoring: 4-inch window for monitoring lint accumulation.
· FLEXIBLE DUCTS ARE PROHIBITED IN CONCEALED SPACES SUCH AS CEILINGS AND Compatibility: Suitable for installation with 1/2" and 5/8" drywall.
· PENETRATIONS: WHEN THE EXHAUST DUCT PENETRATES A CEILING MEMBRANE, SEAL
WALLS.
THE ANNULAR SPACE WITH NONCOMBUSTIBLE MATERIAL OR APPROVED FIRE CAULKING.
2. DUCT ROUTING & SUPPORT · FIRE-RESISTANCE RATED ASSEMBLIES: DUCTS MUST NOT PENETRATE OR BE LOCATED ENTRY/ ENTRY/
· ABOVE-CEILING ROUTING: DUCTWORK MUST BE ROUTED IN AN UNOBSTRUCTED PATH WITHIN ANY FIREBLOCKING, DRAFTSTOPPING, OR ASSEMBLIES REQUIRED TO BE EXIT EXIT
Phoenix, AZ 85048
· DUCTS MUST BE SUPPORTED AT INTERVALS NOT EXCEEDING 4 FEET TO PREVENT ALUMINUM AS SPECIFIED IN SECTION 603.4, AND THE FIRE-RESISTANCE RATING IS
SAGGING. MAINTAINED.
602-628-1231
· JOINTS MUST BE ALIGNED IN THE DIRECTION OF AIRFLOW AND SECURED USING · SUPPORT: SECURELY SUPPORT THE DUCT AT INTERVALS NOT EXCEEDING 4 FEET TO
Suite 200
APPROVED FASTENING METHODS (NO SCREWS PENETRATING INTO AIRFLOW SPACE). PREVENT SAGGING.
3. DUCT LENGTH LIMITATIONS · JOINTS: ENSURE THAT JOINTS ARE INSTALLED WITH THE INSERT END OF THE DUCT
· MAXIMUM ALLOWABLE DUCT LENGTH: 35 FEET FROM THE DRYER TO THE TERMINATION EXTENDING INTO THE ADJOINING DUCT OR FITTING IN THE DIRECTION OF AIRFLOW.
POINT. AVOID USING FASTENERS THAT PROTRUDE INTO THE DUCT, SUCH AS SCREWS, TO
· DEDUCT THE FOLLOWING FOR FITTINGS: PREVENT LINT ACCUMULATION. RECEPTION
WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE JOB. THE DESIGNER
ANY DISCREPANCY ON ALL DRAWING & SPECIFICATIONS (ARCHITECTURAL, STRUCTURAL, SANITARY, ELECTRICAL, & MECHANICAL) SHALL BE SUBJECT FOR VERIFICATION AT THE ARCHITECTS OFFICE BEFORE IMPLEMENTATION
26 GAUGE-4"Ø ROUND
METAL DUCT RISER
MUST BE NOTIFIED IMMEDIATELY OF ANY VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN BY THESE DRAWINGS.
4" METAL DUCT CONNECTOR FLANGE
8978 W UNION HILLS DR. SUITE 106-107, PEORIA, AZ 85382 4" Ø SEMI-RIGID METAL DUCT
1 26 GAUGE-4"Ø ROUND
METAL DUCT RISER
WASHER
LEGEND:
LOCKER
AREA
EXIT EXIT
AS SHOWN
DRAWN BY:
MAKE
8978 W UNION HILLS DR. SUITE 106-107, PEORIA, AZ 85382 8978 W UNION HILLS DR. SUITE 106-107, PEORIA, AZ 85382 SHEET: