Manual_1U_ULTRA_Compact v1.6
Manual_1U_ULTRA_Compact v1.6
Installation Manual
V1.6
Phone +64-3-366-4550
Fax +64-3-366-0884
Email [email protected]
www.enatel.net
Copyright © Enatel Ltd. 2011
Scope ......................................................................................................................................... 4
System Overview ....................................................................................................................... 4
Installation .................................................................................................................................. 6
Unpacking & Installing in 19” Rack.......................................................................................... 6
AC & DC Cabling .................................................................................................................... 6
DC Cabling ............................................................................................................................. 7
Alarm/Ancillary Cabling ........................................................................................................... 7
Alarm Mapping to Volts-free Relays ........................................................................................ 9
Circuit Breaker Fail Monitoring ................................................................................................ 9
LVD Operation ........................................................................................................................... 9
Commissioning ......................................................................................................................... 10
Appendix 1 - Enatel Essential System Set - Up Parameters ..................................................... 15
Appendix 2 - Maintenance ........................................................................................................ 17
Appendix 3 - Rectifier Input Fuse Curves ................................................................................. 18
Appendix 4 - AC Input Transient Protection .............................................................................. 18
Appendix 5 - System Wiring Diagram ....................................................................................... 21
Appendix 6 - Model Specifications ............................................................................................ 23
CAUTION: For your protection, the following information and the product manual should
be read and thoroughly understood before unpacking, installing and using the
equipment.
We present all equipment to the delivering carrier securely packed and in perfect condition.
Upon acceptance of the package from us, the delivering carrier assumes responsibility for its
safe arrival to you. Once you receive the equipment, it is your responsibility to document any
damage the carrier may have inflicted, and to file your claim promptly and accurately.
Package Inspection
Examine the shipping crate or carton for any visible damage: punctures, dents and any
other signs of possible internal damage.
Describe any damage or shortage on the receiving documents and have the carrier sign
their full name.
Equipment Inspection
Within fifteen days, open crate or carton and inspect the contents for damages. While
unpacking, be careful not to discard any equipment, parts or manuals. If any damage is
detected, call the delivering carrier to determine the appropriate action. They may require
an inspection.
Save all the shipping materials for the inspector to see!
After the inspection has been made and you have found damage, call us. We will determine
if the equipment should be returned to our plant for repair or if some other method would be
more expeditious. If it is determined that the equipment should be returned to us, ask the
delivering carrier to send the packages back at the delivering carrier’s expense.
If repair is necessary, we will invoice you for the repair so that you may submit the bill to the
delivering carrier with your claim forms.
It is your responsibility to file a claim with the delivering carrier. Failure to properly file a
claim for shipping damages may void warranty service for any physical damages later
reported for repair.
Handling
Handle the equipment with care. Do not drop or lean on front panel or connectors. Keep away
from moisture.
Identification Labels
Model numbers are clearly marked on all equipment. Please refer to these numbers in all
correspondence with Enatel.
SYSTEM OVERVIEW
The 1U ULTRA Compact DC Power System has a maximum power output of 4.0kW (+24V
rated to 2.0kW), producing a maximum current output of 83A at -48Vdc (74A at -54V) or 83A at
+24Vdc (74A at +27V).
The system is intended to be a complete power system in a box, so no connections need to be
made internally. All the AC, DC (Load and Battery) connections are made at the rear of the unit.
Alarm connections are assessable from the front.
The system is designed to be extremely simple to install and set up.
The following is a summary of the system:
- Overall size is 483mm wide (19” standard mounting) x 44.5mm high (1U) x 350mm deep
- Up to 2 RM18xx series rectifiers or 2 RM20xx rectifiers - may be packaged separately
- SM31 or SM32 supervisory module (fully integrated in the system)
- Battery Low Voltage Disconnect fitted as standard (80A rating).
- 1x 63A Battery Circuit Breaker, this may be specified as different values (from 2A to 63A) at
time of order.
- 1x 63A Load Circuit Breaker, this may be specified as different values (from 2A to 63A) at
time of order.
- System weight is approximately 5kg without rectifiers, and 7.6kg with two rectifiers fitted.
Note: This system is supplied with the AC and DC earths connected. The standard system
(+ve earth system) output has the DC Common in the positive side of the circuit (-ve
earth system output has the DC Common in the negative side of the circuit).
The earth link can be removed from the system to isolate earths. Please see the
relevant section.
AC & DC Cabling
The AC terminals are clearly marked at the rear of the system (see Fig 1). The terminals can
accept up to 10mm2 cables.
Load (+ve)
Com (+ve)
Com (+ve)
Load (-ve)
Com (-ve)
Com (-ve)
Batt (+ve)
Batt (-ve)
Neutral
Neutral
Line 1
Line 1
Earth
Earth
The AC earth is internally bonded to the system chassis. DC Common (+ve or –ve depending
on specification - see appendix for model numbers) is connected to the AC earth by a
removable cable (green/yellow), but can be removed if DC output is required to be isolated from
AC earth.
DC Earth
Ensure cables are strain relieved by utilising the cable tie slots provided (see Fig 3).
Once cables are connected, ensure cable connector cover is fitted and secured.
Alarm/Ancillary Cabling
Alarm and communication cables terminate directly into the rear of the Supervisory Module,
SM31 or SM32, which terminals are assessable by pulling the monitor forward to expose
connections (see Fig 4 & 5).
When routing the cables, ensure they are kept away from the AC and DC power cables when
possible.
LVD OPERATION
This system is configured with a single Low Voltage Disconnect contactor in the battery side of
the circuit (see wiring diagram at rear of this manual).
The SM31/32 supervisory and monitor unit is powered from both the rectifier side of the LVD
contactor and battery source. Therefore when the low voltage threshold is reached and the LVD
disconnects the battery, the SM3x will loose voltage sense (as voltage sense is measuring
rectifier bus voltage) but still maintains operation for monitoring system. The LVD contactor will
not re-engage until the rectifier power is restored (i.e., until the DC bus voltage is restored).
Note: Prior to leaving the system after it has been commissioned, ensure all AC, DC and
battery circuits are off. If it is required that the system is to be left on (to power load
equipment, ensure rectifiers are left in their powered up state, and batteries are in circuit.
This will prevent anyone leaving the batteries only powering the load (in which case the
batteries would go flat).
Alarms:
1. Adjust the supply/float voltage to 55.7V & observe the “High Float” alarm.
2. Adjust the supply/float voltage to 57.7V & observe the “High Load” alarm.
3. Adjust the supply/float voltage to 52.7V & observe the “Low Float” alarm.
4. Adjust the supply/float voltage to 46.9V & observe the “Low Load” alarm.
Once the test is complete, be sure to rest the High Load Current to its previous value
(or check with the customer for the correct value they require).
Temperature alarm tests are performed by heating up (using a heat gun or other
source) and cooling down (using an aerosol can of freeze, or a tub of ice) the
temperature sensors. Note that when the Battery Condition Monitor is used, there is
one sensor per battery string. The SM3x uses the average of these temperatures as
the “Battery Temperature”. Therefore, all the sensors need to be heated / cooled at
the same time.
When an AC Monitoring PCB is not fitted at system level (as in most cases), the AC
Fail alarm is generated from the rectifiers. The rectifiers sense if AC is present, and
extend an AC fail alarm to the SM3x. Therefore, to test this alarm, simply turn off the
rectifier AC breakers. To allow the monitor to continue to read alarms there must be
DC present on the output of the system.
As this causes the rectifier output to cease, a Rectifier Fail alarm is also generated.
To generate the Urgent Rectifier Fail, turn off the required number to make this occur
(Usually set to 1, but check via the SM3x Config software for the setting (under the
“Rectifier Control” section of the “Power Module Control” tab)).
AC Fail (urgent) Urgent /
To check Load MCB Open, connect a load, but with no load turned on. Then switch
the breaker to it’s off position and turn on some load (any amount will do). This will
cause the alarm to occur as the load side to the circuit will be taken to system
common voltage. Turn off the load, and then return the breaker to its ON position.
The battery circuit breaker however, uses voltage sense to detect tripping or
whether it is turned off. This is because when a battery breaker is tripped,
there may be very little voltage difference, making electronic fail detection
problematic. Hence, if no battery is connected, the breaker must be “on” to
clear the Battery Breaker Fail alarm.
To check Battery MCB open alarm, turn off the battery circuit breaker.
To check the Surge Protection Failed alarm, simply pull the MOV out. This switches
A Rectifier Off Normal alarm is generated with the rectifier enters a state that may
degrade its performance (e.g., a single fan fail), or a state that is outside of normal
operating conditions (e.g., high temperature, or current limit).
You can observe an Off Normal alarm when the system is placed in current limit, or
you may wish to stop a fan to generate the alarm. The best way to stop a fan is to
use a small cable tie (non-metallic), and push it approximately 1cm through the
rectifier grille.
Connect battery/batteries
Check the correct Battery Capacity (Ahrs) has been entered (SM3x Config.,
“Charge” tab). This is the total capacity, so for 100Ahr string, this should be
100.
Go to SM3x Config, “Control” tab. Set the Battery Charge Current Limit to “Enabled”
(middle right of screen). Also check Battery Current Limit (BCL) is set to desired level
(usually 0.25C10, (25%)). This means that for a single 100Ahr battery, the BCL will be
25A, or if two 100Ahr batteries are connected in parallel, the BCL will be 50A.
Set Vf to 54.0V.
Temperature Compensation
The following items 1 though 5 are system settings that MUST be checked for EACH system
installed, at the time of commissioning.
WARNING: Failure to correctly follow the procedures in items 1 to 5 below may at least cause
incorrect system function, and at worst ruin your battery (without the ability to claim
battery replacement under warranty).
PRIOR to making any changes to settings, ensure that you back up the Configuration settings
that the SM3x is supplied with. To do this, go to the Setup page and click on the “Save
Variable to File” button. The filename is saved with a “.sm3x” extension.
Done:
If you choose not to enable Temperatue Compensation, then set the Rectifier Float Voltage to
that required by the battery manufacturer for the average long-term temperature you anticipate
your system to operate at.
3. Battery Size
For the SM3x to set the correct Battery Current Limit current, it is essential that this is filled out
correctly. These figures are also used for estimating the Battery Time Remaining during a
discharge.
For Telecom applications, the 10 hour rate is usually the name-plate rating of the battery.
However, once again, check the battery manufacturer’s data sheets as some manufacturers
state the 20 hour rate (which is usually a little more “optimistic”).
The second rate is required specifically for the time-remaining algorithm. A 4 hour rate is
usually a good one to use. This information is available from the battery manufacturer’s data
sheet.
SM3x Config Page: Charge
Done:
Note – you need to change both the 10 hour and 4 hour rates at the same time. The rates need
to be reasonably accurate (in terms of the proportion of 4 hour to 10 hour rates), otherwise the
SM3x may not accept the settings.
Done:
Enatel recommends that you set this value at the highest rate possible to ensure the battery is
recharged as fast as possible (this could be as high as 30%, depending on the manufacturer).
However, especially in large systems, this may be more limited by the number of rectifiers
available, rather than this particular setting. For telco settings, this is often set to 10% (or
0.1C10, so for a 100Ahr battery, the current limit is 10A). This is more typical of a design
parameter than the need for the setting to be at this level. So a setting higher than this level
should be considered to enable the fastest recharge possible. However, consult the battery
manufacturer data to find the maximum value.
Done:
This is usually a customer generated setting. Normally, the longer the discharge, the higher the
end voltage. So, for a discharge of <1hr, this may be 1.75Vpc (42.0V for a “48V” battery), or for
an 8 hour discharge, it may be 1.85Vpc (44.4V for a “48V” battery).
Note that if only one LVD is fitted, then the other thresholds (of LVD2 & LVD3) are normally set
well outside of possible tripping voltages. Although not essential, and those LVDs will not be
enabled anyway, it serves to avoid any confusion over which LVD signal is actually being used.
As ENATEL Power Systems are state of the art electronic systems, very little routine
maintenance is required
System
During normal operation the cable entries to the MCB’s may loosen over time due to movement
in the cable strands.
To avoid damage to the MCB’s and cable entries due to heat build-up and arching, it is
recommended that the retaining torque is periodically checked at least annually.
MCB’s should be maintained at a torque of 2Nm
All other connections should also be checked at this time.
Monitor
The monitor can give a good indication of the condition of the system. Alarm logs can show
issues with the system and rectifiers and should be regularly checked.
As a minimum check ensure the float voltage and load current is as expected.
If the batteries are fully charged, check the battery current is zero or near to zero amps.
Rectifiers
During normal operation some dust will build-up on the front of the rectifiers. This should be kept
to a minimum by regularly wiping the rectifiers to avoid accumulation within the rectifiers and
blocking the airflow to the units. The positioning of the system and surroundings will determine
the regularity of this requirement.
In extremely dusty positions it is recommended that the units are removed and cleaned with
compressed air to prevent airflow blockages.
Batteries
Battery maintenance will depend on the individual manufacturer’s specification, please contact
the battery supplier for recommendations.
RM2048/RM1848
Input Fuse
Fig 6.0
The Type 1 surge arrester, fitted in the installation's main incoming electrical switchboard, is
capable of deviating the energy of a direct lightning strike. This is the first stage of the electrical
network's protection. It is important that upstream Type 1 protection is provided on site.
10/350 wave as shown below is the current waveform which passes through equipment when
subjected to an overvoltage due to a direct lightning strike.
A Type 2 surge arrester should be used in coordination with the incoming surge arrester. This is
the second stage of protection. Type 2 Surge arrester is designed to run-off energy caused by
an overvoltage comparable to that of an indirect lightning strike or an operating overvoltage.
Some of the Enatel Power System models are provided with Type 2 Surge Protection Devices
(SPDs) (as defined by IEC 61643-11). These devices are rated for repeated strikes of 20kA
(8/20μs waveform as shown above), and single shot protection of 40kA.
1. Avoid running input and output cables from AC Surge Protection Devices together:
Incoming Incoming
AC AC
AC to DC Power
System
AC to DC Power
System
SPD SPD
(Type 1) (Type 1)
Significant coupling
between unprotected and
protected AC line negates Minimal coupling
the effectiveness of SPD between Protected and
Unprotected AC lines
CHNT
6000A
GB14048.2
IEC60947-2
230/400V
C32
NB1-63
eNaTeL Supervisory Module
Load eNaTeL
SM32
CHNT
6000A
GB14048.2
IEC60947-2
230/400V
C32
NB1-63
Battery
ENP
COMPACT
SYSTEM Supervisory Module
SM31 Supervisory
SM3X
SM32
Module O
K
Supervis
ory
Module
eNaTeL
RECTIFIER 1 RECTIFIER 2
J101
J107
Rectifier
Comm's Temp 1 +ve
Backplane J10 Temp 2 +ve
PCB 0V
*see note
below
J113
Aux Power + Ambient Battery
Green
Aux Power - Temp Temp
Sensor Sensor
J111
(Optional)
I3-
I3+
+
-
Brown
I2-
4k7
4k7
I2+
White
I1-
I1+
Sm3x
Control
PLYSW
J110
Loom
Red VS2 -
+ Battery 4k7
VS2 +
LVD 0V
- 4k7
0V
VS1 -
VS1 +
4k7
Load
J109
Circuit Black
LVD -ve Supply
Breaker Battery LVD 2 Control
Circuit Red
LVD Com (or LVD3^)
Breaker LVD +ve Supply
Violet
LVD Com
LVD 1 Control
Orange
J108
J107
GPIP6 (Spare)
GPIP5 (Spare) Relay 3
Customer Alarms
GPIP4 (Spare)
LVD -ve Power (from -ve bus)
GPIP3 (Spare)
Pink
GPIP2 (LVD Open)
Relay 2
GPIP1 (Load MCB Open)
Blue
J106
4k7
4k7
*see note
below
Comm’s (Optional)
Comm’s
J4
DI1
DI2
DI3
DI4
DI5
DI6
“Commons” (-ve)
J3
(System Live)
Relay 8
Monitor
Relay 7
J2
+ Relay 6
AI6 (± 50mV)
-
Customer Alarms
J1
Relay 5
AI5 (0-10V)
AI4
System Ratings: AI3 Relay 4
(0-75V)
AI2
Nominal Output Voltage: -48Vdc -60Vdc AI1
Relay 3
Max. Output Current (RM1848): 66.7A/-48V & -54V -
Max. Output Current (RM1860/48): 60A/-48V & -54V 60A/-48V, 53A/-67.5V
Relay 2
Max. Output Current (RM2048): 83A/-48V, 74A/-54V -
AC Input (total): 19A** @ 230Vin 17A @ 230Vin Relay 1
CHNT
6000A
GB14048.2
IEC60947-2
230/400V
C32
NB1-63
Battery
ENP
COMPACT
SYSTEM Supervisory Module
SM31 Supervisory
SM3x
SM32
Module O
K
Supervis
ory
Module
eNaTeL
RECTIFIER 1 RECTIFIER 2
J107
Rectifier
Comm's Temp 1 +ve
Backplane J10 Temp 2 +ve
PCB 0V
*see note
below
J113
Green
Aux Power + Ambient Battery
High Side Shunt PCB Aux Power - Temp Temp
(PS-SHNTH1-xx) Sensor Sensor
J111
(Optional)
A I3-
B I3+
Brown
0V I2-
I2+
White
PLYSW
Sm3x I1-
I1+
Control
Loom
J110
Red 4k7 Grey
VS2 -
+ Battery LVD 1 Control (to LVD 1 coil “+”)
VS2 +
Red
0V 1 Common (to LVD 1 coil “-”)
LVD
- LVD 4k7 0V
LVD +ve Power (from +ve bus)
VS1 -
LVD + Common (to LVD 2 coil “-”)
VS1 2
4k7
LVD 2 Control (to LVD 2 coil “+”)
J109
Load PLYSW Black
LVD -ve Power (from -ve bus)
LVD -ve Supply
Circuit LVD 2 Control
Breaker Battery LVD Com (or LVD3^)
Red
LVD +ve Supply
Circuit LVD Com
Violet
Breaker LVD 1 Control
Orange
J108
J107
GPIP6 (Spare)
GPIP5 (Spare)
GPIP4 (Spare) Relay 3
Customer Alarms
Pink
GPIP3 (LVD Open)
GPIP2 (Load MCB Fail)
Blue
GPIP1 (Spare)
Relay 2
SM3x Fail
J106
4k7
4k7
*see note
below
Comm’s (Optional)
Comm’s
J4
DI1
DI2
DI3
DI4
DI5
DI6
“Commons” (-ve)
J3
(System Live)
Relay 8
Monitor
Relay 7
J2
+ Relay 6
AI6 (± 50mV)
-
Customer Alarms
J1
Relay 5
AI5 (0-10V)
AI4
System Ratings**: AI3 Relay 4
(0-75V)
AI2
Nominal Output Voltage: +24Vdc AI1
Relay 3
Output Current: 83.4A /+24V & 74A/+27V
Relay 2
AC Input (total): 9.5A @ 230Vin
12.5Amax @ 175Vin Relay 1