Introduction
This RTU release 12.6 includes several new features and corrections for functional issues in
RTU500 series related to cyber security, fleet management, engineering improvements and
protocol improvements.
More information will be provided by the responsible sales manager link or your local ABB sales
representative and during the offered webinars.
Documentation
Following documentation is available for download:
• Updated Web server user manual
• Updated Security Deployment Guideline
• Updated IEC60870-5-104 protocol description
• Updated Function descriptions
• RTU500 Rel12.6 release notes
—
RTU500 12.6 release (2019-12)
New functions:
Script interface: to support fleet management of installed RTU’s related to file handling of:
• RTU configuration files
• RTU firmware
• RTU HMI files
• PLC project packages
• Password files
• Support of MultiCMU configuration
The up- and download and activation of the files is supported. The scripts are running in Microsoft
PowerShell environment.
IEC 60870-5-104 protocol supports now secure authentication based on IEC62351-5. By configuration the
support of IEC62351-3 (TLS) and IEC62351-5 (secure authentication) can be selected. (contact hotline team
for feature key)→Flyer
PLC parameter management:
It is possible now to change predefined PLC parameters during runtime via web browser.
This simplify the testing and commissioning process of PLC logics based on predefined PLC
functions/libraries (symbolic PLC)
PLC deployment:
PLC programs can be downloaded as PLC project package with web browser and script interface to
RTU500. Multiprog 5 is no more required for the file download to RTU500.
VxWorks vulnerability IPnet URGENT/11 is solved with this release. See separate announcement under link
and further information here
Queue monitoring for IEC60870-5-104 host communication
The filling status if the IEC60870-5-104 host communication is monitored now. If the filling state reaches
75% a system event is generated.
Brute force attack monitoring and protection:
In case of several unsuccessful login attempts to RTU500 (wrong password and/or user name) the login will
be blocked for a time period. Function can be configured (number of attempts, enable/disable) and the
settings will be distributed together with the password file/password policy
Monitoring of SD card:
If SD card is unplugged during operation a system event is created. Based on that system event an alarm
can be initiated.
MODBUS host communication:
Function codes 15 and 16 are now supported for host communication. This function supports industrial
SCADA projects based on MODBUS communication.
DNP3 host communication: A configurable waiting time improves the support of radio net works
New Multimeter 500CVD90: For secondary distribution (SDA) application a new multimeter with detection
functions, power quality monitoring and disturbance recorder function with COMTRADE file support is
available. For details please check the datasheet
ATS function: For secondary distribution automation a PLC library function for automatic transfer switch
function with 5 different modes is available. Function is pretested and works according this description.
Function can be ordered on pricelist (BOL)→ Flyer
PLC issue: With this release the cache function is enabled to provide the full performance for the PLC
function (Process logic control according IEC61131-3). The cache memory of the ARM based CMU’s (RTU540
and RTU560) was temporally disabled in former release to solve a bug in the PLC function.
—
ABB Power Grids Germany AG
P.O. Box 10 01 64
68128 Mannheim, Germany
Phone: +49 621 381-3000
Fax: +49 621 381-7622
Email: [email protected]
www.abb.com/remote-terminal-units