Fire Design Example-1
Fire Design Example-1
1
Example 1 Two storey office building Sheet 2 of 25 Rev
2
A
Figure 1.1
1 2 3 4 5 6 7
7.5 m 7.5 m 7.5 m 7.5 m 7.5 m 7.5 m
533 x 210 x 122 UKB 533 x 210 x 122 UKB 533 x 210 x 122 UKB 533 x 210 x 122 UKB 533 x 210 x 122 UKB 533 x 210 x 122 UKB
A
20
20
20
20
20
20
3
3
3
3
3
3
U
U
UK
UK
UK
UK
KC
C
KC
C6
C6
C6
0
60
0
60
60
0
7.5 m
1.0 m
533 x 210 x 122 UKB
533 x 210 x 122 UKB
533 x 210 x 122 UKB
533 x 210 x 122 UKB
533 x 210 x 122 UKB
Solution A
305 x 165 x 40 305 x 165 x 40 305 x 165 x 40 305 x 165 x 40 305 x 165 x 40
B
20
20
20
20
20
20
3
3
3
3
3
3
U
U
UK
UK
UK
UK
KC
C
KC
C6
C6
C6
0
60
0
60
60
0
Example 1 Two storey office building
7.5 m
Solution B
800
533 x 210 x 122 UKB
533 x 210 x 122 UKB
533 x 210 x 122 UKB
533 x 210 x 122 UKB
533 x 210 x 122 UKB
533 x 210 x 122 UKB
533 x 210 x 122 UKB 533 x 210 x 122 UKB 533 x 210 x 122 UKB 533 x 210 x 122 UKB 533 x 210 x 122 UKB 533 x 210 x 122 UKB
3
Steelwork Layout of the First Floor
C 3m
20
20
20
20
20
20
3
3
3
3
3
3
U
U
UK
UK
UK
UK
KC
C
KC
C6
C6
C6
0
60
0
60
60
0
Figure 1.2
A 3° B C
305 x 165 x 40 305 x 165 x 40
305 x 165 x 40
Section A-A
2.6 m
F.F.L 4.7 m 533 deep
305 x 165 x 40 edge beam
Detail A
Example 1 Two storey office building
4
Detail C
500
7.5 m 7.5 m
2.6
Elevation Gridline C
4.2
Example 1 Two storey office building
5
This drawing to be read in conjuction with drawings
BCF951/01, 03, 04, & 05
Figure 1.4
1 2 3 4 5 6 7
7.5 m 7.5 m 7.5 m 7.5 m 7.5 m 7.5 m
600
A
7.5 m
305 x 165 x 40
305 x 165 x 40
305 x 165 x 40
305 x 165 x 40
305 x 165 x 40
305 x 165 x 40
305 x 165 x 40
305 x 165 x 40
300
Solution A
305 x 165 x 40 305 x 165 x 40 305 x 165 x 40 305 x 165 x 40 305 x 165 x 40
B
300
7.5 m
Solution B
305 x 165 x 40
305 x 165 x 40
305 x 165 x 40
305 x 165 x 40
305 x 165 x 40
305 x 165 x 40
305 x 165 x 40
305 x 165 x 40
305 x 165 x 40
800
C
305 x 165 x 40 305 x 165 x 40 305 x 165 x 40 305 x 165 x 40 305 x 165 x 40 305 x 165 x 40
6
Purlins at 1100 ctrs
Figure 1.5
50 mm
150 mm p.c. unit
Column Column
Steel beam
533 x 210 x 122 UB
100 mm void 100 100
Frame 100 100
Ceiling 20 mm thick light steel Frame
infill light steel
infill
Detail A Detail B Detail C
7
This draw ing to be read in conjuction w ith draw ings
BCF951/01, 02, 03, & 04
8
Example 1 Two storey office building Sheet 9 of 25 Rev
where:
Efi,d is the design effect of actions for the fire design situation (in this case
the reduced bending moment), and
Rfi,d,0 is the corresponding design resistance at time t = 0 (i.e. the design
bending resistance before any heating)
Thus, when considering bending resistance:
M fi,d
o =
M fi,t,Rd
9
Example 1 Two storey office building Sheet 10 of 25 Rev
235 235
Thus 0.85 0.85 0.8 (fy = 265 N/mm2, since 16 < tf < 40)
fy 265
M fi,θ,Rd
Mfi,t,Rd =
1 2
in which:
Mfi,,Rd is the design moment resistance of the cross section for a uniform EN 1993-1-2
temperature 4.2.3.3(1)
= ky, [ M0/ Mfi]MRd
where:
ky, is the reduction factor for effective yield strength from Table 3.1 of
EN 1993-1-2
1 is an adaption factor for non-uniform temperature across the cross- EN 1993-1-2
section 4.2.3.3(3)
2 is an adaption factor for non-uniform temperature along the beam
At time t = 0 (ambient temperature design): = 20°C, ky, = 1.00 EN 1993-1-2
Table 3.1
The material partial factor at ambient temperature is: UK NA to
EN 1993-1-1
M0 = 1.00 NA.2.15
The UK National Annex to EN 1993-1-2 suggests the use of the value for NA to
partial factors for materials at elevated temperature recommended in EN 1993-1-2
EN 1993-1-2 clause 2.3. Therefore: NA.2.3
10
Example 1 Two storey office building Sheet 11 of 25 Rev
Therefore:
1
a,cr = 39.19 ln 1 + 482
0.9674 0.293.833
a,cr = 669oC
The time taken for the steel beam temperature to reach its critical value is EN 1993-1-2
calculated using an incremental process given in expression 4.25 of 4.2.5.1
EN 1993-1-2
The increase in temperature of the steel beam during a time interval t is
given by:
Expression 4.25
a,t = ksh
Am / V
hnet t
ca a
where: EN 1993-1-2
3.2.2(1)
a is the density of steel = 7850 kg/m3
ca is the specific heat of steel, given by EN 1991-1-2 Clause 3.4.1.2
EN 1993-1-2
ksh is the correction factor for the shadow effect
4.2.5.1
= 0.9[Am/V]b/[Am/V]:
ksh may conservatively be taken as 1 – see NOTE 2 of 4.2.5.1(2)
The design value of net heat flux per unit area, hnet,d , is given by:
hnet, d hnet, c hnet, r EN 1991-1-2 3.1
The net radiative heat flux, hnet, r , is given by:
11
Example 1 Two storey office building Sheet 12 of 25 Rev
where:
= 1.0 (EN 1991-1-2 clause 3.1(7)
m = 0.7 (EN 1993-1-2 clause 2.2)
f = 1.0 (EN 1993-1-2 clause 4.2.5.1(3)
c is the coefficient of heat transfer by convection
g is the gas temperature in the vicinity of the fire exposed member (see
below)
m is the surface temperature of the steel member
is the Stephan Boltzmann constant (= 5.67×10-8 W/m2K4)
(EN 1993-1-2 clause 3.1(6))
The temperature-time curve is given by:
g = 20 + 345 log10 (8t + 1) EN 1991-1-2
3.2.1(1)
where :
t is time (in minutes)
For the beam selected and the exposure considered (3-sided) the value of
[Am/V] is:
Am 1890 211 .9 EN 1993-1-2
= 108 m-1 4.2.5 & P363
V 15 .5
Note that the above calculation assumes the use of precast concrete planks,
which protect the top surface of the beam.
As the radiative heat flux ( hnet, c ) is a function of the surface temperature of the
beam (m), which is dependant on the gas temperature and time, a spreadsheet
may be used to calculate the steel temperature at intervals (t).
According to EN 1993-1-2 clause 4.2.5.1(4) t should not be taken as more than
5 seconds.
A design tool to undertake this verification is available at
www.steelconstruction.info
If ksh is conservatively taken as 1.0, the incremental calculation of the
unprotected steel temperature shows that the beam reaches its critical
temperature of 669°C after 18.8 minutes.
If ksh is calculated (the value is 0.698), the incremental calculation of the
unprotected steel temperature shows that the beam reaches its critical
temperature of 669°C after 22.7 minutes.
Because the critical temperature is reached at 22.7 minutes, earlier than the
required 30 minutes of fire resistance, an unprotected solution is unsatisfactory.
Figure 1.6 shows the variation of the temperature of gas and steel temperature
with time, showing when the critical temperature is reached.
12
Example 1 Two storey office building Sheet 13 of 25 Rev
1200
1000
Gas and Steel temperatures (oC)
800
Gas temperature
600
Steel temperature
Point of failure
Critical temperature
400
200
0
0 10 20 30 40 50 60 70 80 90 100
Minutes
Figure 1.6 Variation of gas and steel temperatures with time – unprotected beam
13
Example 1 Two storey office building Sheet 14 of 25 Rev
M fi,d 352
o = 0.35
M fi, t,Rd 996
14
Example 1 Two storey office building Sheet 15 of 25 Rev
1200
1000
Gas and Steel temperatures (oC)
800
600
Gas temperature
400
Steel temperature
Required fire period
0
0 10 20 30 40 50 60 70 80 90 100
Minutes
Figure 1.7 Variation of gas and steel temperatures with time – protected beam
15
Example 1 Two storey office building Sheet 16 of 25 Rev
Design combination value of actions, using expression 6.10 from EN 1990, is EN 1990
given by: Partial factors
from UK NA to
NEd = 1.35 × 327 + 1.5 × 219 = 770 kN EN 1990
The chosen column section, a 203 203 60 UKC S355 is at least a Class 2 P363
Section at ambient temperature.
This may be verified by inspecting the “n limit” given on page D-204 of P363.
The selected column section is at least Class 2 at all levels of axial load, and
therefore the resistance is based on the gross area.
Design resistance of the cross-section:
Nc,Rd = Npl,Rd = Afy /M0 EN 1993-1-1
6.2.4
= 2710 kN > NEd therefore OK P363
Design buckling resistance of the cross-section: EN 1993-1-1
6.3.1.1
Nb,Rd = A fy /M1
From sheets 4 and 7, the length of the bottom storey column is estimated to be P363
4.2 + 0.5 – 0.15 – 0.05 – (0.5 ×0.533) = 4.23 m, so say 4.25 m. Assuming a
buckling length of 1.0 system length, the buckling resistance (interpolated
from P363) is 1350 kN
Nb,Rd = 1350 kN > NEd therefore OK
16
Example 1 Two storey office building Sheet 17 of 25 Rev
The UK National Annex to EN 1993-1-2 suggests the use of the value for partial NA to
factors for materials at elevated temperature recommended in EN 1993-1-2 EN 1993-1-2
clause 2.3. Therefore: NA.2.3
235 235
Thus 0.85 0.85 0.69 (fy = 355 N/mm2, since tf < 16)
fy 355
17
Example 1 Two storey office building Sheet 18 of 25 Rev
where:
1 93.9 93.9 235 / 355 = 76.4
For this UKC section, the radius of gyration is iz = 52 mm P363
2125 1
= 0.535
52 76.4
The non-dimensional slenderness at an elevated steel temperature, θ is EN 1993-1-2
4.2.3.2(2)
given by:
18
Example 1 Two storey office building Sheet 19 of 25 Rev
Am 1210 P363
158 .4 m–1
V 7 .64
Am
V is the box value of the section factor (the value for a rectangular box
b
that surrounds the profile).
Am 2 b 2 h 2 205.8 2 209.6
V A
= = 108.7 m-1
b 7.64
1400
1000
1200
Gas temperature
Gas and Steel temperatures (0C)
1000
Point of failure
Critical temperature
600 800
Design resistance (kN)
Fire load (kN)
600
400
400
200
200
0 0
0 10 20 30 40 50 60 70 80 90 100
Minutes
Figure 1.8 Variation of gas temperature, steel temperature and design resistance with time
– unprotected column
19
Example 1 Two storey office building Sheet 20 of 25 Rev
20
Example 1 Two storey office building Sheet 21 of 25 Rev
1200 1600
Gas temperature
Steel temperature 1400
1000 Temperature at 30 minutes
Required fire period 1200
Gas and Steel temperatures (oC)
600 800
600
400
400
200
200
0 0
0 10 20 30 40 50 60 70 80 90 100
Minutes
Figure 1.9 Variation of gas temperature, steel temperature and design resistance with time
– protected column
21
Example 1 Two storey office building Sheet 22 of 25 Rev
From page T-11, the vertical shear resistance is given as 752 kN, and the critical
check is identified as check 4. Check 4 covers the resistance of the beam web in
shear.
tp
gv
e2
e1
p1
p1
hp p1
p1
p1
e1
p2
bp
Figure 1.10 The beam to column connection detail at the first floor
Bolt group
From page C-381 of P363, the shear resistance of an M20, 8.8 bolt, is 94.1 kN P363
In P358, check 8, this resistance is factored by 0.8, to allow for the inevitable
tension that the bolts experience, even in a nominally pinned joint.
Thus the design shear resistance per bolt is 0.8 94.1 = 75.3 kN
Because the column flange is 14.2 mm in S355, and the end plate is 12 mm in P363
S275, bearing in the end plate will be critical.
The bolt group has the following geometry:
Edge distance, e2 = 30 mm
End distance, e1 = 40 mm
Pitch, p1 = 70 mm
Gauge, p2 = 140 mm
As all the above dimensions are the same or larger than those in the middle table P363
on page C-381 of P363, the bearing resistance in 12 mm, S275 plate will be at
least 101 kN.
Thus, bolt shear is critical. The resistance of the bolt group is therefore
12 × 75.3 = 903.6 kN
22
Example 1 Two storey office building Sheet 23 of 25 Rev
Beam web
In P358, check 4, the resistance of the beam web, Vpl,Rd is given by:
f y,b1 3
Vpl, Rd Av
M0
fy,b1 = 265 N/mm2, as 16 < tf < 40
Av = 0.9 × 430 × 12.7 = 4915 mm2
265 3
Vpl,Rd 4915 10 3 = 752 kN (as T-11, P358)
1.0
Note that the use of expression 2.5 is associated with the use of expression 6.10
from EN 1990. If expressions 6.10a and 6.10b from EN 1990 had been used, the
calculation of fi should be taken as the smaller value from expressions 2.5a and
2.5b from EN 1993-1-2.
fi is to be taken as 1.1 according to the UK NA to EN 1991-1-2 UK NA to
EN 1991-1-2
The value of 1.1 is taken from the UK NA to EN 1990, for (in this instance), NA.2.7
office areas. UK NA to
EN 1990
fi = 1,1 = 0.5 Table NA.A1.1
5 0 .5 3 .3
fi = = 0.57
1.35 5 1.5 3.3
The reduced design shear force is therefore:
f d L 11.7 7.57.5
Vfi,d = 0.57 × = 188 kN
2 2
23
Example 1 Two storey office building Sheet 24 of 25 Rev
where:
M2 is the partial factor at normal temperature
M,fi is the partial factor for fire conditions
For bolts in shear and for bolts in bearing, M2 = 1.25 UK NA to
EN 1993-1-8
The UK National Annex to EN 1993-1-2 suggests the use of the value for partial NA to
factors for materials at elevated temperature recommended in EN 1993-1-2 EN 1993-1-2
clause 2.3. Therefore: NA.2.3
24
Example 1 Two storey office building Sheet 25 of 25 Rev
Note that this also applies to the resistance of the end plate – no reduction is
required.
More generally, at temperatures greater than 400°C, Table 3.1 indicates a
reduction factor ky, less than 1.0. The verification of connection components
such as the end plate and beam web should follow the checks described in P363,
using a material strength reduced by the factor ky,.
25