02 Seismic and Accidental Fire Design Situation NEU
02 Seismic and Accidental Fire Design Situation NEU
buildings and a high number of casualties. Post-installed or transient design situations (fundamental
anchors have to be fit for those extraordinary events as combinations)
they are incorporated in the structural and non-structural
elements of a building, and are used to fix the services For each critical load case, the design values of the
and essential lifelines of a building. effects of actions Ed shall be determined by combining
the values of actions that are considered to occur simul-
Post-installed anchors are assessed based on the valid taneously.
European Assessment Documents (EAD). The different
product behaviour of mechanical, bonded and concrete
screw anchors, is incorporated in their specifically rela-
ted EADs. This relates also to the tests for the assessment
of the product behaviour under accidental loads. In this Effects of actions that cannot exist simultaneously due to
Design Manual, we give information based on the Euro- physical or functional reasons should not be considered
pean guidelines. Information based on American guide- together in combinations of actions. Depending on its
lines would be equivalent. Only post-installed anchors uses and the form and the location of a building, the com-
that are qualified for cracked concrete and seismic appli- binations of actions may be based on not more than two
cations are considered in this chapter. variable actions.
Chapter 9 of the EN 1992-4 provides the requirements The combination factors ψ are given in Annexes of EN
for the design of post-installed fasteners under seismic 1990.
actions. Annex C of the same code provides more
detailed information on the design method and require- Table 1: γG,j & γQ,1 factors for permanent and variable
ments. The design explanations of part 2.5 of this chapter actions
are primarily based on the EN 1992-4 and its annexes. Persistent Permanent Variable
and transient action action
A manufacturer of post-installed anchors is not respon- design
sible for the structural verifications of an anchorage, but situations
should provide information about the relevant and rela-
favourable γG,j = 1.00 γQ,1 = γQ,i = 0
ted topics to design and establish safe anchorage. There-
unfavourable γG,j = 1.35 γQ,1 = γQ,i = 1.50
fore, and as we consider the topic about combination of
actions important, we start here with a short summary.
2.2.2. Combinations of actions for accidental
design situations
2.2. Design values of actions
12
d
AnchorNNintended
eq for seismic application will need to be tested as per the new ETAG 00
eq
qualification in
N anchor seismic performance categories C1 and C2 is the complete asse
Ni i
min N
N eq
Anchors are assessed for their seismic performance and tests under alternating shear load. i
N = 0.375 NNu,m,ref ■
!!
Only anchors, which proved their suitability for the use in eq
±V m
±Vm
both strength (forces) and displacements. Both cases Design Manual 2 (15) !!
take into consideration concrete cracking. In the case of ca
C1, the maximum crack width is taken as △w = 0.5 mm
and in C2 as △w = 0.8 mm. For C2, the performance is
assessed with a test where cracks open and close (see
figure 5) in addition.
eq
Design Manual
V = 0.5 Vu,m,ref
■
2 (15)
Vi = 0.375 Vu,m,ref
The following table provides the reader with the qualifi-
■
Vm = 0.25 Vu,m,ref
cation tests for each performance category:
■
13
SEISMIC AND FIRE CONSIDERATIONS
tests under crack cycling. u,m,ref !!! = 0.4 ∙ !!,!,!"# dings, etc.
-1.0
Vu,m,ref = normalized mean shear capacity !!! = 0.5 ∙ !!,!,!"#
II Ordinary buildings, not belonging in
for C20/25, Δw = 0.8mm Time t
!!,!,!"# = normalized mean shear
the other categories.
Figure 4: Tests under alternating shear load capacity for C20/25, ∆w = 0.8mm
as well as tests under crack cycling. !!! = 0.4 ∙ !!,!,!"#
!!! = 0.5 ∙ !!,!,!"#
III Buildings whose seismic resistance is
of importance in view of the conse-
!!,!,!"# = normalized mean shear
quences associated with a collapse,
capacity for C20/25, ∆w = 0.8mm
!!! = 0.4 ∙ !!,!,!"# e.g. schools, assembly halls, cultural
!!! = 0.5 ∙ !!,!,!"#
Design Manual 3 (15) JoB-130605-001
institutions etc.
!!,!,!"# = normalized mean shear
IV
capacity for C20/25, ∆w = 0.8mm
Buildings whose integrity during
earthquakes is of vital importance
Design Manual 3 (15) JoB-130605-001
for civil protection, e.g. hospitals, fire
stations, power plants, etc.
Nw1 = 0.4 Nu,m,ref
■
14
2.5. Connections between structural elements of primary and/or secondary seismic members
2.6. Design options and criteria is designed for the maximum load that can be transmitted
to the fastening based either on the development of a
In the design of fastenings one of the following options ductile yield mechanism in the attached steel component
shall be satisfied: (see Figure 6) or in the steel base plate (see Figure 7)
a1) Capacity design taking into account material over-strength effects, or on
a2) Elastic design the capacity of a non-yielding attached component or
b) Design with requirements on the ductility of the structural element (see Figure 8). The assumption of a
anchors plastic hinge in the fixture (Figure 7) requires to take into
account specific aspects including e.g. the redistribution
2.6.1. Design without requirements on the of loads to the individual anchors of a group, the redis-
ductility of the anchors. tribution of the loads in the structure and the low cycle
fatigue behaviour of the fixture.
It shall be assumed that anchors are non-dissipative
elements and they are not able to dissipate energy by
means of ductile hysteretic behaviour and that they do Feq
Mpe
not contribute to the overall ductile behaviour of the
structure.
Figure 6: Yielding in
a1) Capacity design attached element
15
SEISMIC AND FIRE CONSIDERATIONS
The action effects for connections between structural The seismic coefficient may be calculated as follows:
elements of primary and/or secondary seismic members
shall be derived according to EN 1998-1 with a behavi-
our factor q = 1.0. α = ratio of the design ground acceleration on type A
ground, ag, to the acceleration of gravity g,
For attachments of non-structural elements the action S = soil factor,
effects shall be derived with a behaviour factor qa = 1.0 Aa = Amplification factor
for the attached element.
16
Table 5: behaviour factor qa and seismic amplification factor Aa
Type of non-structural element qa Aa
17
SEISMIC AND FIRE CONSIDERATIONS
For the design of the anchors in connections between 2.7.1. General provisions
structural elements of primary and/or secondary seismic
members the vertical component of the seismic action • Limited to the anchor configurations of EN 1992-4
SEISMIC AND FIRE
shall be taken into account according to EN 1998-1, • Stand-off installations (grouted or not) are out of
Section 4.3.3.5.2 (2) to (4) if the vertical design ground scope
acceleration avg is greater than 2.5 m/s2. • If the seismic contribution to the design load
combination is ≤ 20% no explicit seismic design is
The vertical effects of the seismic action Fva for non- needed. However, a seismic approved anchor is still
structural elements may be neglected for the fastener required
when the vertical component of the design ground acce- • Cracked concrete must be considered unless proven
leration avg is less than 2.5 m/s2 and the gravity loads are otherwise
transferred through direct bearing of the fixture on the • The maximum value of each action effect (tension and
structure. The determination of the vertical seismic action shear component of forces for an anchor) shall be
effects of non-structural elements for use in a Country considered to act simultaneously if no other more
may be found in its National Annex to this EN. The accurate model is used for the estimation of the
recommended rule is the application of the formula: probable simultaneous value of each action effect
• An annular gap between an anchor and its fixture
should be avoided in seismic design situations. For
fastenings of non-structural elements in minor non-
critical applications an annular gap (diameter df) of
the clearance hole in the fixture not larger than the
value given in EN 1992-4 is allowed. The effect of
the annular gap on the behaviour of fastenings shall
be taken into account
• Loosening of the nut or screw shall be prevented by
appropriate measures
Key
1 include F Va
2 neglect F Va if aVg ≤ 2.5 m / s2
3 gravity force
4 wall
5 ceiling or floor
18
2.7.2. Required verifications
2.7.3. Design Resistance Note: The forces on the anchors are amplified in
presence an annular gap under shear loading
The seismic design resistance Rd,seis (NRd,seis, VRd,seis) of a due to a hammer effect on the anchor. For
fastening is given by: reasons of simplicity this effect is considered only
in the resistance of the fastening. In absence of
information in the ETA the following values
αgap may be used. These values are based on a
limited number of tests.
The characteristic seismic resistance Rk,seis (NRk,seis, VRk,seis)
of a fastening shall be calculated for each failure mode αgap = 1.0 in case of no hole clearance between anchor
and fixture;
= 0.5 in case of connections with hole clearance
according to the following table
where
αgap = reduction factor to take into account inertia
effects due to an annular gap between anchor
and fixture in case of shear loading; given in the
relevant ETA;
19
SEISMIC AND FIRE CONSIDERATIONS
aseis = reduction factor to take into account the influence of large cracks and scatter of load displacement curves,
see the following table
R0k,seis = basic characteristic seismic resistance for a given failure mode determined as follows:
20
2.7.4. Displacements
If the anchor displacements δN,Seis(DLS) under tension
The anchor displacement under tensile and shear load at loading and/or δV,Seis(DLS) under shear loading provided
damage limitation state (DLS) shall be limited to a value in the relevant ETA (for anchors qualified for seismic
δN,req(DLS) and δV,req(DLS) to meet requirements regarding performance category C2) are higher than the correspon-
e.g. functionality and assumed support conditions. These ding required values δN,req(DLS) and/or δV,req(DLS), the design
values shall be selected based on the requirements of the resistance may be reduced according to Equations (5.11)
If deformations (displacements or rotations) are relevant If fastenings and attached elements shall be operational
for the design of the connection (such as, for example, on after an earthquake the relevant displacements have to
secondary seismic members or façade elements) it shall be taken into account.
be demonstrated that these deformations can be accom-
modated by the anchors.
Table 8: Required verifications for post-installed fasteners without supplementary reinforcement subjected to a combined
tension and shear load
If NEd and VEd are different for the individual fasteners of the group,
the interaction shall be verified for all fasteners.
or
21
SEISMIC AND FIRE CONSIDERATIONS
Injection anchors
Performance Performance
Anchor type Size Anchor type Size
SEISMIC AND FIRE
C1 C2 C1 C2
WIT-VIZ S M8 WIT-PE 1000 M M8 ✓
M10 ✓ ✓ M10 ✓
M12 ✓ ✓ M12 ✓ ✓
M16 ✓ ✓ M16 ✓ ✓
M20 ✓ ✓ M20 ✓ ✓
M24 ✓ ✓ M24 ✓ ✓
WIT-VIZ A4 M8 M27 ✓
M10 ✓ ✓ M30 ✓
M12 ✓ ✓ WIT-PE 1000 R Ø8 ✓
M16 ✓ ✓ Ø10 ✓
M20 ✓ ✓ Ø12 ✓
M24 ✓ ✓ Ø14 ✓
WIT-UH 300 M M8 ✓ Ø16 ✓
M10 ✓ Ø20 ✓
M12 ✓ ✓ Ø24 ✓
M16 ✓ ✓ Ø25 ✓
M20 ✓ ✓ Ø28 ✓
M24 ✓ ✓ Ø32 ✓
M27 ✓ WIT-VM 250 M M8 ✓
M30 ✓ M10 ✓
WIT-UH 300 R Ø8 ✓ M12 ✓
Ø10 ✓ M16 ✓
Ø12 ✓ M20 ✓
Ø14 ✓ M24 ✓
Ø16 ✓ M27 ✓
Ø20 ✓ M30 ✓
Ø24 ✓ WIT-VM 250 R Ø8 ✓
Ø25 ✓ Ø10 ✓
Ø28 ✓ Ø12 ✓
Ø32 ✓ Ø14 ✓
Ø16 ✓
Ø20 ✓
Ø25 ✓
Ø28 ✓
Ø32 ✓
22
Mechanical anchors
23
SEISMIC AND FIRE CONSIDERATIONS
2.8. Structural verifications under fire exposu- fire exposure are not necessary when using the simplified
re and design values of the anchor resistances design concept.
for the respective failure modes When using the Experimental determination for all
load directions and failure modes the required investi-
In general, the duration of the fire resistance of an- gations are given. The duration of fire resistance of the
SEISMIC AND FIRE
chorages depends mainly on the configuration of the anchor can be determined from the results.
structure itself (base materials, anchorage including the A combination of the design concepts is possible. For
fixture). It is not possible to classify an anchor for its fire example: the duration of the fire resistance for individual
resistance. This evaluation concept includes the behavi- failure modes (e.g. steel failure) can be determined by
our of the anchorage in concrete and the parts outside tests and for other failure modes (e.g. pull-out and con-
the concrete. The influence of the fixation is considered crete failure) the limit values can be determined using the
unfavourable. simplified design method.
24
• γM,fi = 1.0 for steel failure and concrete related failure 2.8.2. Resistance
modes under shear loading. For concrete related 2.8.2.1. Fire resistance capacity in tension
failure modes under tension γM,fi = 1.0 γinst and shear
• NRk,p , N0Rk,c , V0Rk,c characteristic resistances of a
single anchor in cracked concrete C20/25 for The following table provides a summary of the resi-
concrete cone failure under normal temperature stances to fire according to the various failure modes of
fasteners. The overview shows values from the simplified
Experimental
Failure mode Simplified Design Concept
Determination
25
SEISMIC AND FIRE CONSIDERATIONS
Table 10: Characteristic tension strength of an unprotected anchor made of C-steel according to EN 10025 in case of fire
exposure
Fastener bolt /
Embedment depth Characteristic tension strength
thread diameter
SEISMIC AND FIRE
hef σRk,s,fi(t)
mm mm N/mm2
30 min 60 min 90 min 120 min
(R15 to R30) (R45 and R60) (R90) (≤ R120)
∅ 6 / M6 ≥ 30 10 9 7 5
∅ 8 / M8 ≥ 30 10 9 7 5
∅ 10 / M10 ≥ 40 15 13 10 8
≥ ∅ 12 / M12 ≥ 50 20 15 13 10
Table 11: Characteristic tension strength of an unprotected anchor made of at least steel grade A4 according to the
EN ISO 3506 series in case of fire exposure
Fastener bolt /
Embedment depth Characteristic tension strength
thread diameter
hef σRk,s,fi
mm mm N/mm2
30 min 60 min 90 min 120 min
(R15 to R30) (R45 and R60) (R90) (≤ R120)
∅ 6 / M6 ≥ 30 10 9 7 5
∅ 8 / M8 ≥ 30 20 16 12 10
∅ 10 / M10 ≥ 40 25 20 16 14
≥ ∅ 12 / M12 ≥ 50 30 25 20 16
26
2.8.2.2. Required verifications for combined tension and shear loads
If NEd and VEd are different for the individual fasteners of the group,
the interaction shall be verified for all fasteners.
or
Failure modes other than steel
2 failure
27
SEISMIC AND FIRE CONSIDERATIONS
depth / No.
(mm) R30 R60 R90 R120
28
Max tensile loading (kN)
Effective for specified fire resistance
anchorage time 1) 2) Authority
Anchor type Size
depth / No.
(mm) R30 R60 R90 R120
1)
All values are for reinforced concrete as base material of strength classes from C20/25 to C50/60
2)
Data valid for steel failure. See approval for other failure modes
3)
Values are for standard effective anchorage depths values in cracked concrete. Check the fire test report for the complete list of values
4)
Values are for non-cracked concrete
29
SEISMIC AND FIRE CONSIDERATIONS
depth / No.
(mm) R30 R60 R90 R120
30
Max tensile loading (kN)
Effective for specified fire resistance
ancho- time 1) 2) Authority
Anchor type Size rage
/ No.
depth
(mm) R30 R60 R90 R120
31