Cummins-C100N6_QSJ5.9G
Cummins-C100N6_QSJ5.9G
Spark-ignited
generator set
45–100 kW Standby
EPA emissions
Description
®
Cummins generator sets are fully integrated Cooling system - Standard cooling package
power generation systems providing optimum provides reliable running at up to 50 °C
performance, reliability and versatility for (122 °F) ambient temperature.
stationary Standby applications.
Enclosures - The aesthetically appealing
Features enclosure incorporates special designs that
deliver one of the quietest generators of its kind.
Gas engine - Rugged 4-cycle Cummins Aluminum material plus durable powder coat
QSJ5.9G spark-ignited engine delivers reliable paint provides the best anti-corrosion
power. The electronic air/fuel ratio control performance. The generator set enclosure has
provides optimum engine performance and fast been evaluated to withstand 180 MPH wind
response to load changes. loads in accordance with ASCE7 -10. The
Alternator - Several alternator sizes offer design has hinged doors to provide easy access
for service and maintenance.
selectable motor starting capability with low
reactance 2/3 pitch windings, low waveform NFPA - The generator set accepts full rated load
distortion with non-linear loads and fault clearing in a single step in accordance with NFPA 110 for
short-circuit capability. Level 1 systems.
®
Control system - The PowerCommand 1.1 Warranty and service - Backed by a
electronic control is standard equipment and comprehensive warranty and worldwide
provides total generator set system integration distributor network.
including automatic remote starting/stopping,
precise frequency and voltage regulation, alarm
and status message display, output metering,
auto-shutdown at fault detection and NFPA 110
Level 1 compliance. The PowerCommand 2.3
control is also optional and is UL 508 Listed and
TM
provides AmpSentry protection.
power.cummins.com
©2017 Cummins Inc. | NAS-6092-EN (10/17)
Generator set specifications
Governor regulation class ISO8528 Part 1 Class G3
Voltage regulation, no load to full load ± 1.0%
Random voltage variation ± 1.0%
Frequency regulation Isochronous
Random frequency variation ± 0.25% @ 60 Hz
Radio frequency emissions compliance Meets requirements of most industrial and commercial applications
Engine specifications
Design Naturally aspirated or turbocharged (varies by generator set model)
Bore 102.1 mm (4.02 in.)
Stroke 119.9 mm (4.72 in.)
Displacement 5.9 liters (359 in3)
Cylinder block Cast iron, in-line 6 cylinder
Battery capacity 850 amps at ambient temperature of 0 °F to 32 °F (-18 °C to 0 °C)
Battery charging alternator 52 amps
Starting voltage 12 volt, negative ground
Lube oil filter type(s) Spin-on with relief valve
Standard cooling system 50 °C (122 °F) ambient cooling system
Rated speed 1800 rpm
Alternator specifications
Design Brushless, 4 pole, drip proof, revolving field
Stator 2/3 pitch
Rotor Direct coupled, flexible disc
Insulation system Class H per NEMA MG1-1.65
Standard temperature rise 120 ºC (248 °F) Standby
Exciter type Torque match (shunt) with PMG as option
Alternator cooling Direct drive centrifugal blower
AC waveform Total Harmonic Distortion (THDV) < 5% no load to full linear load, < 3% for any single harmonic
Telephone Influence Factor (TIF) < 50 per NEMA MG1-22.43
Telephone Harmonic Factor (THF) < 3%
Available voltages
1-phase 3-phase
120/240 120/208 120/240 277/480 347/600 127/220
power.cummins.com
©2017 Cummins Inc. | NAS-6092-EN (10/17)
Generator set accessories
Coolant heaters – 1000 W/1500 W Remote monitoring device – Alternator PMG
Battery rack, standard/larger battery PowerCommand 500/550 Alternator heater
Battery heater kit Battery charger – stand-alone, 12 V
Engine oil heater Circuit breakers
Remote control displays Enclosure Sound Level 1 to Sound
Auxiliary output relays (2) Level 2 upgrade kit
Auxiliary configurable signal Base barrier – elevated generator
inputs (8) and relay outputs (8) set
Annunciator – RS485 Mufflers – industrial, residential or
critical
power.cummins.com
©2017 Cummins Inc. | NAS-6092-EN (10/17)
Options Digital governing
Auxiliary output relays (2) AC output analog meters (bargraph)
Remote annunciator with (3) configurable inputs and - Color-coded graphical display of:
(4) configurable outputs - 3-phase AC voltage
PMG alternator excitation - 3-phase current
PowerCommand 500/550 for remote monitoring and - Frequency
alarm notification (accessory) - kVa
Auxiliary, configurable signal inputs (8) and Remote operator panel
configurable relay outputs (8)
PowerCommand 2.3 control with AmpSentry protection
Ratings definitions
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical load
for the duration of power interruption of a reliable utility
source. Emergency Standby Power (ESP) is in
accordance with ISO 8528. Fuel Stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and
BS 5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant electrical
load for limited hours. Limited Time Running Power (LTP)
is in accordance with ISO 8528.
Prime Power (PRP):
Applicable for supplying power to varying electrical load
for unlimited hours. Prime Power (PRP) is in accordance
with ISO 8528. Ten percent overload capability is
available in accordance with ISO 3046, AS 2789,
DIN 6271 and BS 5514.
Base Load (Continuous) Power (COP):
Applicable for supplying power continuously to a constant This outline drawing is for reference only. See respective
electrical load for unlimited hours. Continuous Power model data sheet for specific model outline drawing
(COP) in accordance with ISO 8528, ISO 3046, AS 2789, number.
DIN 6271 and BS 5514.
Do not use for installation design
power.cummins.com
©2017 Cummins Inc. | NAS-6092-EN (10/17)
Dim “A” Dim “B” Dim “C” Set weight*wet
Model mm (in.) mm (in.) mm (in.) kg (lbs.)
Open set
C45 N6 2489 (98) 1016 (40) 1473 (58) 989 (2180)
C50 N6 2489 (98) 1016 (40) 1473 (58) 989 (2180)
C60 N6 2489 (98) 1016 (40) 1473 (58) 1103 (2431)
C70 N6 2489 (98) 1016 (40) 1473 (58) 1111 (2449)
C80 N6 2489 (98) 1016 (40) 1473 (58) 1173 (2587)
C100 N6 2489 (98) 1016 (40) 1473 (58) 1233 (2719)
Weather protective enclosure
C45 N6 2489 (98) 1016 (40) 1473 (58) 1070 (2359)
C50 N6 2489 (98) 1016 (40) 1473 (58) 1070 (2359)
C60 N6 2489 (98) 1016 (40) 1473 (58) 1184 (2610)
C70 N6 2489 (98) 1016 (40) 1473 (58) 1192 (2628)
C80 N6 2489 (98) 1016 (40) 1473 (58) 1255 (2766)
C100 N6 2489 (98) 1016 (40) 1473 (58) 1315 (2898)
Sound attenuated enclosure Level 1
C45 N6 3023 (119) 1016 (40) 1473 (58) 1114 (2455)
C50 N6 3023 (119) 1016 (40) 1473 (58) 1114 (2455)
C60 N6 3023 (119) 1016 (40) 1473 (58) 1227 (2706)
C70 N6 3023 (119) 1016 (40) 1473 (58) 1236 (2724)
C80 N6 3023 (119) 1016 (40) 1473 (58) 1298 (2862)
C100 N6 3023 (119) 1016 (40) 1473 (58) 1358 (2994)
Sound attenuated enclosure Level 2
C45 N6 3454 (136) 1016 (40) 1473 (58) 1127 (2485)
C50 N6 3454 (136) 1016 (40) 1473 (58) 1127 (2485)
C60 N6 3454 (136) 1016 (40) 1473 (58) 1241 (2736)
C70 N6 3454 (136) 1016 (40) 1473 (58) 1249 (2754)
C80 N6 3454 (136) 1016 (40) 1473 (58) 1312 (2892)
C100 N6 3454 (136) 1016 (40) 1473 (58) 1372 (3024)
* Weights above are average. Actual weight varies with product configuration.
power.cummins.com
©2017 Cummins Inc. | NAS-6092-EN (10/17)
Codes and standards
Codes or standards compliance may not be available with all model configurations – consult factory for availability.
The Prototype Test Support
(PTS) program verifies the
performance integrity of the
The generator set is available
generator set design. Cummins
Listed to UL 2200, Stationary
products bearing the PTS
Engine Generator Assemblies.
symbol meet the prototype test
requirements of NFPA 110 for
Level 1 systems.
The generator set is certified to All low voltage models are CSA
International
International Building Code certified to product class
Building Code
(IBC) 2012. 4215-01.
This generator set is designed
in facilities certified to ISO 9001 Engine certified to U.S. EPA SI
and manufactured in facilities U.S. EPA Stationary Emission Regulation
certified to ISO 9001 or 40 CFR, Part 60.
ISO 9002.
Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s
electrical system except through an approved device or after building main switch is open.
©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
NAS-6092-EN (10/17)