38ycc

The 38YCC 50 Hz Outdoor Sections of Split-System Heat Pumps are designed for efficient heating and cooling, with an EER up to 9.2, suitable for residential and light commercial applications. These units feature a range of sizes from 024 to 060, a hermetically sealed compressor for reliability, and built-in components for optimal performance and safety. Additional accessories and controls are available to enhance functionality and adapt to various installation requirements.

Uploaded by

n.faiez60
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6 views

38ycc

The 38YCC 50 Hz Outdoor Sections of Split-System Heat Pumps are designed for efficient heating and cooling, with an EER up to 9.2, suitable for residential and light commercial applications. These units feature a range of sizes from 024 to 060, a hermetically sealed compressor for reliability, and built-in components for optimal performance and safety. Additional accessories and controls are available to enhance functionality and adapt to various installation requirements.

Uploaded by

n.faiez60
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

Product 38YCC 50 Hz

Data Heat Pump

Sizes 024 thru 060

The 38YCC 50 Hertz Outdoor


Sections of Split-System Heat Pumps
are designed for quiet, reliable heating
during the winter and cooling during
the summer. With an EER up to 9.2,
these heat pump systems provide
economy of operation through energy
conservation when used with
components designated by Carrier.
They recover heat for indoor comfort
from outdoor air during the heating
season and, by automatically
reversing the refrigerant system,
remove indoor heat and excess
humidity during the cooling season.

FEATURES/BENEFITS
Electrical Range — Units are offered
in single phase 230v 50 Hz. Three-
phase units are available in sizes 036,
048, and 060 in 400v 50 Hz.
Size Range — The 38YCC is
available in nominal sizes 024, 036,
048 and 060 to meet the needs of
residential and light commercial
applications.
Compressor — Designed
specifically for heat pump duty, with
energy efficiency during heating and
cooling operation. The compressor is
hermetically sealed against
contamination to assure long life and
dependable performance, internally
sprung (units with reciprocating
compressor) and externally mounted
on rubber isolators for quiet operation.
Continuous compressor operation is
approved down to –30°F (–34.4°C)
in the heating mode, and down to
55°F (12.8°C) in the cooling mode.
(See heating and cooling performance
tables.)

Copyright 1997 Carrier Corporation Form 38YCC-C1PD


Downloaded from www.Manualslib.com manuals search engine
Built-in-Reliable Components — control which includes 3 field- optimum heat transfer during heating
Include a suction-tube accumulator selectable time periods of 30, 50, and and cooling. Vertical air discharge
that reduces the amount of liquid 90 minutes. The control includes built- carries sound and air up and away from
refrigerant that reaches the in 5-minute compressor delay for units adjacent patio areas and foliage. Coils
compressor; low-pressure switch to equipped with scroll compressors. can be cleaned with a common garden
stop the compressor if refrigerant Weather-Protective Cabinet — Steel hose.
charge is lost; crankcase heater on is protected with a heavy galvanized External Service Valves — Both
units with reciprocating compressor coating and treated with a layer of zinc service valves are brass, front seating
and all 3-phase units to keep phosphate. A coat of modified type. Valves are externally located
compressor oil warm and free of polyester powder coating is then so refrigerant tube connections can
refrigerant for maximum lubricity; applied and baked-on, providing each be made quickly and easily. Each
internal compressor relief valve for unit with a hard, smooth finish that will valve has a service port for ease of
high-pressure protection. last for many years. checking operating refrigerant
Discharge Silencer — Minimizes low All screws on cabinet exterior are pressures. The 38YCC has sweat-type
frequency sound and pressure coated for a long-lasting rust-resistant, field connections.
pulsation generated by compressor quality appearance. Safety — All units are designed and
discharge gas.
Unit Design — All units are equipped manufactured in accordance with
Defrost Control Board — with totally enclosed fan motors for Underwriters Laboratories (U.L. 1995)
Incorporates a defrost relay, defrost greater reliability under rain and snow standard for safety, heating and
timer, and low-voltage terminations. conditions. The large, wraparound coil cooling equipment.
The defrost control is a time and uses copper tube and enhanced
temperature initiation/termination aluminum fin and is designed for

Quality Assurance

Model number nomenclature


38YCC 024 7 0 3

Electric Heat Pump


Packaging
Series
Nominal Capacity Electrical
024 — 24,000 Btuh (7.0 Kw) 048 — 48,000 Btuh (14.1 Kw) 7 — 230-1-50
036 — 36,000 Btuh (10.6 Kw) 060 — 60,000 Btuh (17.6 Kw) 9 — 400-3-50

2
Downloaded from www.Manualslib.com manuals search engine
Physical data
UNIT SIZE-SERIES 024-70 036-70, 90 048-70, 90, 92 060-90, 92
OPERATING WT (Lb/Kg) 140 / 63.6 216 / 97.8 216, 216, 224 / 97.8, 97.8, 101.8 257, 259 / 116.4, 117.5
COMPRESSOR
Manufacturer Copeland Copeland Millennium, Millennium, Copeland Millennium, Copeland
Type Recip Recip Scroll Scroll
REFRIGERANT R-22
Control Piston
Charge (Lb/Kg) @ 15 ft (4.57m) 4.84 / 2.20 7.93 / 3.60 5.32, 5.32, 7.25 / 2.41, 2.41, 3.29 10.95, 10.75 / 4.97, 4.88
CONDENSER FAN Propeller Type, Direct Drive
Air Discharge Vertical
Air Qty (CFM / L/S) 2160 / 1019 2750 / 1298 2750 / 1298 2750 / 1298
Motor HP 1/10 1/4 1/4 1/4
Motor RPM (50 Hz) 850 900 900 900
CONDENSER COIL
Face Area (Sq ft/m 2) 12.4 / 1.15 22.4 / 2.08 18.7 / 1.74 18.7 / 1.74
Fins per In. / Fins per Cm 20 / 8 20 / 8 20 / 8 20 / 8
Rows 1 1 1 2
Circuits 2 3 4 6
CONNECTION (In./mm ID) Sweat
Vapor 5/8 / 15.875 3/4 / 19.05 7/8 / 22.225 7/8 / 22.225
Liquid 3/8 / 9.525
REFRIG TUBES* (In./mm OD)
Vapor (0–50 Ft (15.24m)
Tube Length) 5/8 / 15.875 3/4 / 19.05 7/8 / 22.225 1-1/8 / 28.575
Vapor (Max Diameter for
Long-Line Applications) 3/4 / 19.05 7/8 / 22.225 1-1/18 / 28.575
Liquid (0–50 Ft (15.24m) Tube
Tube Length) 3/8 / 9.525
Liquid (For Long-Line
Applications) 3/8 / 9.525
* Tube sizes are for lengths up to 50 ft (15.24m). For lengths over 50 ft (15.24m), consult Residential Split System Long-Line Application Guideline.
NOTE: See unit Installation Instructions for proper installation.

METERING DEVICE
UNIT OUTDOOR INDOOR
SIZE-SERIES PISTON PISTON*
024-70 49 63
036-70, 90 61 73
048-70, 90 73 88
048-92 73 90
060-90 76 98
060-92 76 96

*Piston listed is for any approved coil combination.

3
Downloaded from www.Manualslib.com manuals search engine
Accessories
ORDERING NUMBER DESCRIPTION
KAATD0101TDR Time-Delay Relay — All Sizes
P251-0083 (RCD)* Low-Ambient Controller — All Sizes
P504-8083S (RCD) Filter Drier — Bi-Flow — Sizes 024, 036
P504-8163S (RCD) Filter Drier — Bi-Flow — Sizes 048, 060
32LT660004 (RCD) MotorMaster® Control — Sizes 024 (70), 036 (70), 048 (70)
32LT660005 (RCD) MotorMaster® Control — Sizes 036 (90), 048 (90, 92), 060 (90, 92)
KAAFT0101AAA† Evaporator Freeze Thermostat — All Sizes
KAAWS0101AAA Winter Start Control — All Sizes
KHAIR0101AAA† Isolation Relay — All Sizes
KSACY0101AAA Cycle Protector — All Sizes
KSAHS1001AAA Start Assist — Capacitor and Relay — Size 024 (70)
KSAHS1301AAA Start Assist — Capacitor and Relay — Size 036 (70)
KSAHS1601AAA Start Assist — Capacitor and Relay — Size 048 (70)
N/A Start Assist — Capacitor and Relay — Sizes 036 (90), 048 (90, 92), 060 (90, 92)
KAACS0201PTC Start Assist — PTC — Sizes 024 (70), 036 (70), 048 (70)
N/A Start Assist — PTC — Sizes 036 (90), 048 (90, 92), and 060 (90, 92)
KSASH1101COP Sound Hood — Sizes 024, 036
KSASH2001CYL Sound Hood — Sizes 048, 060
KHAOT0301FST Outdoor Thermostat — All Sizes
KHAOT0201SEC Secondary Outdoor Thermostat — All Sizes
KHAIC0101AAA Interface Control (Optimizer II®) — All Sizes
KSATX0601HSO‡ TXV (Hard Shutoff) — Sizes 024, 036
KSATX0701HSO‡ TXV (Hard Shutoff) — Sizes 048, 060
KHATX0301RPB TXV (RPB) — Size 024
KHATX0501RPB TXV (RPB) — Sizes 036
KHATX0601RPB TXV (RPB) — Size 048
KHATX0701RPB TXV (RPB) — Size 060
KHAHI0101HPS High-Pressure Switch — All Sizes
KHALS0101LLS Liquid-Line Solenoid Valve (LSV) — All Sizes
P165-0001 (RCD) Unit Risers — All Sizes (2 Required/Unit)
* Isolation relay required.
† Consult low-ambient controller Installation Instructions for application.
‡ Hard shutoff TXV requires compressor start assist on reciprocating compressors.
N/A — Not applicable in this application.

THERMOSTAT DESCRIPTION
TSTATCCNHP01-A Thermostat, Auto Changeover, Non-Programmable, °F/°C, 2-Stage Heat, 1-Stage Cool
TSTATCCPHP01-A Thermostat, Auto Changeover, 7-Day Programmable, °F/°C, 2-Stage Heat, 1-Stage Cool
Thermostat Auto Changeover, 7-Day Programmable, °F/°C, Dual Fuel Thermostat
TSTATCCPDF01-A
Must be used with Outdoor Sensor (TSTATCCSEN01)
--HH--07AT-215 Thermostat, Manual Changeover, Non-Programmable, °F, 2-Stage Heat, 1-Stage Cool
TSTATCCSEN01 Outdoor Air Temperature Sensor
TSTATXXNBP01 Backplate for Non-Programmable Thermostat
TSTATXXPBP01 Backplate for Programmable Thermostat
TSTATXXCNV10 Thermostat Conversion Kit (4 to 5 wire) — 10 Pack

4
Downloaded from www.Manualslib.com manuals search engine
Accessory usage guideline
REQUIRED FOR REQUIRED FOR REQUIRED FOR
LOW-AMBIENT LONG-LINE BURIED LINE
APPLICATIONS APPLICATIONS* APPLICATIONS†
ACCESSORY (Below 55°F/12.8°C) (Over 50 Ft/15.24m) (Over 3 Ft/0.914m)
Crankcase Heater Yes Yes Yes
Evaporator Freeze Thermostat Yes No No
Winter Start Control Yes‡ No No
Accumulator No No Yes
Compressor Start Assist
Yes Yes Yes
Capacitor and Relay
Low Ambient Controller
or Yes No No
MotorMaster® Control
Wind Baffle See Low-Ambient Instructions No No
Support Feet Recommended No No
Liquid-Line Solenoid Valve See Long-Line
or No Application Yes
Hard Shutoff TXV Guideline
* For tubing line sets between 50 and 175 ft (15.24 and 53.34m), refer to Residential Split-System Long-Line Application Guideline.
† For buried line applications, refer to Residential Split System Buried Line Application Guideline.
‡ Only when low-pressure switch is used.

Accessory description and usage (Listed alphabetically)


1. Compressor Start Assist — Capacitor and Relay
Start capacitor and start relay gives “hard” boost to compressor motor at each start-up.
SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft (15.24m).
Installations where outdoor design temperature exceeds 105°F (40.6°C).
Replacement installations with hard shutoff expansion valve on indoor coil.
Installations where Liquid-Line Solenoid Valve has been added.
Units installed with Low-Ambient Controller.
2. Compressor Start Assist — PTC
Solid-state electrical device which gives a “soft” boost to compressor motor at each start-up.
SUGGESTED USE: Installations with marginal power supply.
Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.
3. Cycle Protector
Solid-state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor
has been interrupted for any reason, including normal room thermostat cycling.
SUGGESTED USE: Installations in areas where power interruptions are frequent.
Where user is likely to “play” with room thermostat.
All commercial installations.
Installations where interconnecting tube length exceeds 50 ft (15.24m).
High-rise applications.
4. Evaporator Freeze Thermostat
An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.
SUGGESTED USE: All units where Winter Start Control has been added.
All units where Low-Ambient Controller has been added.
5. Filter Drier—Bi-Flow
A device for removing contaminants from refrigerant circulating in a heat pump system: 2-direction flow.
SUGGESTED USE: All split-system heat pumps.
6. High-Pressure Switch
Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to about
426 ± 7 psig and resets at 320 ± 20 psig. Provides protection against compressor damage due to loss of outdoor airflow. To prevent rapid compressor
recycling, Cycle Protector can be used with this switch.
SUGGESTED USE: Installations exposed to very “dirty” outdoor air.
Installations where condenser inlet air temperature exceeds 125°F (51.7°C).
7. Interface Control (Optimizer II®)
An electric control for controlling a heat pump and gas or oil furnace system for maximum energy savings. It allows heat pump to operate down to a
predetermined economic balance point temperature, then switches to allow furnace operation only below that temperature. Requires outdoor thermostat
to be adjusted for economic balance point temperature.
SUGGESTED USE: All heat pump and gas- or oil-fired furnace combination systems.
8. Isolation Relay
An SPDT relay which switches the Low-Ambient Controller out of the outdoor fan motor circuit when heat pump switches to heating mode.
SUGGESTED USE: All heat pumps where Low-Ambient Controller has been added.
9. Liquid-Line Solenoid Valve (LSV)
An electrically operated shutoff valve to be installed at the outdoor unit and which stops and starts refrigerant liquid flow in response to compressor
operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.
NOTE: Compressor Start Assist–Capacitor and Relay must also be used.
SUGGESTED USE: In certain long-line applications. Refer to Residential Split System Long-Line Application Guideline.

5
Downloaded from www.Manualslib.com manuals search engine
Accessory description and usage (Listed alphabetically) continued
10. Low-Ambient Controller
Head pressure controller is a cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle
the outdoor fan motor in order to maintain condensing temperature within normal operating limits (approximately 100°F (37.8°C) high and 60°F
(15.6°C) low). The control will maintain working head pressure at low-ambient temperatures down to 0°F (–17.8°C) when property installed.
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).
11. MotorMaster® Control
A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing
temperature during operation in cooling mode only. For outdoor temperatures down to –20°F (–28.9°C), it maintains condensing temperature at
100°F ± 10°F (37.8°C ± 5.5°C).
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).
All commercial installations.
12. Outdoor Air Temperature Sensor
A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat.
SUGGESTED USE: All corporate programmable thermostats.
13. Outdoor Thermostat
An SPDT temperature actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below set point.
SUGGESTED USE: Heat pump installations with multiple-stage supplemental heaters
14. Secondary Outdoor Thermostat
An SPDT temperature actuated switch which turns on a third stage of supplemental electric heaters when outdoor air temperature drops below the
second-stage set point.
SUGGESTED USE: Heat pump installations where 3-stage operation of supplemental heaters is desired.
15. Sound Hood
Wraparound sound attenuation cover for the compressor. Reduces the sound level by about 2 dBA.
SUGGESTED USE: Unit installed closer than 15 ft (4.55m) to quiet areas—bedrooms, etc.
Unit installed between 2 houses less than 10 ft (3.04m) apart.
16. Thermostatic Expansion Valve (TXV) — Bi-Flow
A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving
the evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shutoff and RPB valves are available.
SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
Required for use on all zoning systems.
17. Time-Delay Relay
An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.
SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
18. Unit Risers
Six-in. tall plastic rails that are used to elevate outdoor units above mounting pad. The risers are adjustable from 24- to 34-in. long..
SUGGESTED USE: Heat pump installations in light to moderate snowfall areas.
Coastal installations.
Windy areas where debris can circulate.
Rooftop installations.
19. Winter Start Control
An SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under low-load
conditions.
SUGGESTED USE: All heat pumps where Low-Ambient Controller has been added.

6
Downloaded from www.Manualslib.com manuals search engine
Electrical data
MAX MAX MAX FUSE†
MIN WIRE LENGTH LENGTH OR HACR
OUTDOOR OPER VOLTS* COMPRESSOR FAN SIZE** (Ft)‡ (m)‡ TYPE CKT
UNIT V/PH Max Min LRA RLA FLA MCA 60°C/ 75°C 60°C/ 75°C 60°C/ 75°C BKR AMPS
024-70 68.0 11.5 1.4 15.8 14/14 55/39 16.7/11.9 25
036-70 230-1 253 207 94.0 16.5 1.6 22.2 12/12 65/47 19.8/14.3 35
048-70 140.0 19.2 1.6 25.6 10/10 96/70 29.3/21.3 40
036-90 42.0 6.4 0.7 8.7 14/14 260/247 79.2/75.3 15
048-90 66.5 8.0 0.7 10.7 14/14 165/157 50.3/47.9 15
048-92 400-3 440 360 63.0 7.9 0.7 10.7 14/14 165/157 50.3/47.9 15
060-90 73.0 9.5 0.7 12.6 14/14 165/157 50.3/47.9 20
060-92 74.0 9.0 0.7 11.9 14/14 165/157 50.3/47.9 20
*Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.
†Time-delay fuse.
‡Length shown is as measured 1 way along the wire path between the unit and the service panel for voltage drop not to exceed 2%.
**If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed-
cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-30.
If other than uncoated (non-plated), 60° or 75°C (140° or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for
larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
FLA — Full Load Amps
HACR — Heating, Air Conditioning, Refrigeration
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
RLA — Rated Load Amps
NOTE: Control circuit is 24v on all units and requires external power source. Copper wire must be used from disconnect to unit. All motors/compres-
sors contain internal overload protection.

7
Downloaded from www.Manualslib.com manuals search engine
8
A SQ
AIR DISCHARGE
M AIR IN AIR DISCHARGE

FIELD POWER SUPPLY CONN


22.2mm DIA HOLE WITH
28.6mm DIA KNOCKOUT
AND 34.9mm DIA
N KNOCKOUT
J
K AIR IN FIELD CONTROL SUPPLY
AIR IN L CONN 22.2mm DIA
9.5mm DIA HOLE
B
TIEDOWN
Dimensions (S.I.)

KNOCKOUTS 9.5mm DIA LIQUID

Downloaded from www.Manualslib.com manuals search engine


(2) PLACES LINE CONN

P
AIR DISCHARGE 73.0mm C
E AIR IN

D DIA VAPOR LINE CONN 31.8mm


F
G
H NOTES:
1. Allow 762.0 mm clearance to service side of unit,
1219.2 mm above unit, 152.4 mm on one side,
304.8 mm on remaining side, and
609.6 mm between units for proper airflow.
2. Minimum outdoor operating ambient in cooling mode is 13°C
(unless low ambient control is used) max. 52°C.
3. Maximum outdoor operating ambient in heating mode
is 19°C.
4. Series designation is the 13th position of the unit model number.
5. Center of gravity .
A97281

DIMENSIONS (mm)
UNIT MINIMUM MOUNTING
SIZE SERIES A B C D E F G H J K L M N P PAD DIMENSIONS
024 70 571.5 862.0 81.0 15.9 93.6 460.4 501.7 549.3 365.1 479.4 560.4 317.5 304.8 355.6 571.5 x 571.5
036 70, 90 762.0 1014.4 82.6 19.1 165.1 596.9 692.2 739.8 508.0 669.9 750.9 381.0 400.1 393.7 762.0 x 762.0
048 70, 90 762.0 862.0 82.6 22.2 165.1 596.9 692.2 739.8 508.0 669.9 750.9 381.0 400.1 393.7 762.0 x 762.0
048 92 762.0 862.0 82.6 22.2 165.1 596.9 692.2 739.8 508.0 669.9 750.9 387.4 396.9 393.7 762.0 x 762.0
060 90 762.0 862.0 82.6 22.2 165.1 596.9 692.2 739.8 508.0 669.9 750.9 400.1 396.9 381.0 762.0 x 762.0
060 92 762.0 862.0 82.6 22.2 165.1 596.9 692.2 739.8 508.0 669.9 750.9 396.9 400.1 384.2 762.0 x 762.0
A SQ
AIR DISCHARGE
M AIR IN AIR DISCHARGE

FIELD POWER SUPPLY CONN


7/8 -IN. DIA HOLE WITH
1 1/8 -IN. DIA KNOCKOUT
AND 1 3/8 -IN. DIA
N KNOCKOUT
J
K AIR IN FIELD CONTROL SUPPLY
AIR IN L CONN 7/8 -IN. DIA
3/8 -IN. DIA HOLE
B

Downloaded from www.Manualslib.com manuals search engine


TIEDOWN
KNOCKOUTS 3/8 -IN. DIA LIQUID
(2) PLACES LINE CONN
Dimensions (English)

P
AIR DISCHARGE 2 7/8″ C
E AIR IN

D DIA VAPOR LINE CONN 1 1/4″


F
G
NOTES:
H 1. Allow 30 in. clearance to service side of
unit, 48 in. above unit, 6 in. on one side, 12 in.
on remaining side, and 24 in. between units for proper airflow.
2. Minimum outdoor operating ambient in cooling mode is
55°F (unless low ambient control is used) max. 125°F.
3. Maximum outdoor operating ambient in heating mode
is 66°F.
4. Series designation is the 13th position of the unit
model number.
5. Center of gravity .
A97045

DIMENSIONS (IN.)
UNIT MINIMUM MOUNTING
SIZE SERIES A B C D E F G H J K L M N P PAD DIMENSIONS
024 70 22-1/2 33-15/16 3-3/16 5/8 3-11/16 18-1/8 19-3/4 21-5/8 14-3/8 18-7/8 22-1/16 12-1/2 12 14 22-1/2 x 22-1/2
036 70, 90 30 39-15/16 3-1/4 3/4 6-1/2 23-1/2 27-1/4 29-1/8 20 26-3/8 29-9/16 15 15-3/4 15-1/2 30 x 30
048 70, 90 30 33-15/16 3-1/4 7/8 6-1/2 23-1/2 27-1/4 29-1/8 20 26-3/8 29-9/16 15 15-3/4 15-1/2 30 x 30
048 92 30 33-15/16 3-1/4 7/8 6-1/2 23-1/2 27-1/4 29-1/8 20 26-3/8 29-9/16 15-1/4 15-5/8 15-1/2 30 x 30
060 90 30 33-15/16 3-1/4 7/8 6-1/2 23-1/2 27-1/4 29-1/8 20 26-3/8 29-9/16 15-3/4 15-5/8 15 30 x 30
060 92 30 33-15/16 3-1/4 7/8 6-1/2 23-1/2 27-1/4 29-1/8 20 26-3/8 29-9/16 15-5/8 15-3/4 15-1/8 30 x 30

9
38YCC BALANCE POINT WORKSHEET
40

A97280
UNIT INTEGRATED HEATING CAPACITY, KW

30
BUILDING HEAT LOSS, KW

38YCC060
FB4AS060
20 38YCC048
FB4AS048
38YCC036
FB4AS036
10

Downloaded from www.Manualslib.com manuals search engine


38YCC024
FB4AS024
BASED ON INDOOR ENT. AIR AT 21°C
AND AT RATED CFM
-20 -10 0 10 20 25
Printed in U.S.A. 11-94
OUTDOOR TEMPERATURE, °C

10
11
38YCC BALANCE POINT WORKSHEET
80 23.4

A97279
UNIT INTEGRATED HEATING CAPACITY, 1000 BTU/HR

38YCC06030/31
70 F(A,B)4AN(F,B)060 20.5
38YCC04830/31
F(A,B)4AN(F,B)048
BUILDING HEAT LOSS, 1000 BTU/HR

60 17.6
38YCC04230/31
F(A,B)4AN(F,B)042
50 38YCC03630/31
14.7
F(A,B)4ANF036
38YCC030/31 11.7
40 F(A,B)4ANF030

KW
38YCC02430/31
30 F(A,B)4ANF024 8.8
38YCC01830/31
F(A,B)4ANF018
20 5.9

Downloaded from www.Manualslib.com manuals search engine


10 2.9
BASED ON INDOOR ENT. AIR AT
70°F AND AT RATED CFM
-10 0 10 20 30 40 50 60 70 80
Printed in U.S.A.
OUTDOOR TEMPERATURE, °F
Performance summary*
HEATING CAPACITY
NOMINAL COOLING CAP @ 95°F (35°C) Hi Temp 47°F (8°C) Lo Temp 17°F (–3°C)
UNIT SIZE- AIRFLOW Rated Capacity Power Rated Rated Capacity Power Rated Capacity Power
SERIES INDOOR MODEL CFM L/ S BTUH KW KW EER BTUH KW KW BTUH KW KW
F(A,B)4ASF024† 800 380 23,000 6.7 2.72 9.00 23,000 6.7 2.40 14,000 4.1 1.72
024-70 F(A,B)4ASF030 800 380 23,600 6.9 2.73 9.00 23,000 6.7 2.38 14,000 4.1 1.70
FG3ASA024 800 380 22,000 6.4 2.77 8.50 23,000 6.7 2.51 13,829 4.1 1.80
F(A,B)4ASF036† 1200 550 35,000 10.3 3.85 9.00 36,000 10.5 3.40 22,100 6.5 2.65
036-70, 90 F(A,B)4AS(F,B)042 1200 550 35,500 10.4 3.80 9.20 37,000 10.8 3.30 22,145 6.5 2.57
FG3ASA036 1200 550 34,000 10.0 3.83 8.80 36,000 10.5 3.43 21,949 6.4 2.67
F(A,B)4AS(F,B)048† 1600 750 46,500 13.6 4.98 9.00 47,000 13.8 4.27 28,000 8.2 3.71
048-70, 90, F(A,B)4AS(F,B)060 1600 750 47,500 13.9 5.03 9.00 47,000 13.8 4.16 28,004 8.2 3.61
92 FG3ASA048 1600 750 45,500 13.3 4.97 8.50 47,000 13.8 4.39 27,909 8.2 3.81
FG3ASA060 1600 750 46,500 13.6 5.01 8.50 47,000 13.8 4.35 28,010 8.2 3.78
F(A,B)4AS(F,B)060† 1900 900 57,000 16.7 6.05 9.00 59,000 17.3 5.20 39,000 11.4 4.44
060-90, 92 FB4ASB070 1900 900 58,000 17.0 6.15 9.00 59,000 17.3 5.01 39,150 11.5 4.28
FG3ASA060 1900 900 56,500 16.6 6.02 9.00 57,500 16.8 5.37 38,793 11.4 4.58
* Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard: 80°F (27°C) db 67°F (19°C) wb indoor entering air temperature and 95°F (35°C) db air entering outdoor unit.
High-Temperature Heating Standard: 70°F (21°C) db indoor entering air temperature and 47°F (8°C) db 43°F (6°C) wb air entering outdoor unit.
Low-Temperature Heating Standard: 70°F (21°C) db indoor entering air temperature and 17°F (–8°C) db 15°F (11°C) wb air entering outdoor unit.
† Outdoor section/indoor section combination tested in accordance with DOE test procedures for heat pumps. Ratings for other combinations are
determined under DOE computer simulation procedures.

Sound power
SOUND
UNIT RATING OCTAVE BAND CENTER FREQUENCY (Hz)
SIZE (dBA) 125 250 500 1000 2000 4000 8000
024 78 42.4 52.9 63.3 64.0 72.2 60.5 59.4
036 78 43.4 52.9 61.3 72.5 63.2 62.5 59.9
048 78 58.5 64.0 68.5 70.0 69.0 63.5 56.0
060 78 55.5 63.5 67.0 67.5 65.5 62.5 57.5

12
Downloaded from www.Manualslib.com manuals search engine
Detailed cooling capacities* (S.I.)
COIL CONDENSER ENTERING AIR TEMPERATURES °C
AIR 28 32 36 40 44 48 52
Capacity Capacity Capacity Capacity Capacity Capacity Capacity
Kw† Sys. Kw† Sys. Kw† Sys. Kw† Sys. Kw† Sys. Kw† Sys. Kw† Sys.
(C) Power Power Power Power Power Power Power
L/S EWB Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw**
38YCC024-70 Outdoor Section With F(A,B)4ASF024 Indoor Section
22 7.83 3.94 2.56 7.50 3.81 2.68 7.17 3.69 2.80 6.84 3.57 2.91 6.50 3.44 3.02 6.16 3.32 3.13 5.81 3.20 3.23
20 7.32 4.64 2.49 7.01 4.51 2.61 6.70 4.39 2.72 6.38 4.26 2.83 6.06 4.14 2.93 5.73 4.01 3.03 5.40 3.88 3.13
340 18 6.84 5.33 2.43 6.55 5.20 2.54 6.25 5.06 2.65 5.96 4.93 2.75 5.66 4.79 2.85 5.36 4.64 2.95 5.05 4.48 3.05
16 6.46 5.89 2.38 6.19 5.74 2.49 5.93 5.58 2.59 5.66 5.42 2.70 5.39 5.25 2.80 5.12 5.06 2.90 4.84 4.84 2.99
14 6.25 6.22 2.35 6.03 6.00 2.46 5.80 5.79 2.57 5.57 5.56 2.68 5.34 5.33 2.79 5.09 5.09 2.89 4.84 4.84 2.99
22 7.96 4.09 2.61 7.62 3.96 2.73 7.28 3.84 2.85 6.93 3.71 2.96 6.58 3.59 3.07 6.23 3.47 3.18 5.88 3.35 3.28
20 7.45 4.86 2.54 7.12 4.74 2.66 6.80 4.61 2.77 6.47 4.48 2.88 6.14 4.35 2.99 5.80 4.23 3.09 5.47 4.10 3.18
380 18 6.97 5.62 2.48 6.67 5.48 2.59 6.36 5.34 2.70 6.06 5.20 2.81 5.76 5.04 2.91 5.46 4.86 3.01 5.17 4.67 3.11
16 6.61 6.20 2.43 6.34 6.03 2.54 6.06 5.87 2.65 5.79 5.69 2.76 5.52 5.49 2.86 5.26 5.26 2.96 5.00 5.00 3.07
14 6.47 6.45 2.41 6.23 6.22 2.53 6.00 5.99 2.64 5.76 5.75 2.75 5.51 5.51 2.86 5.26 5.26 2.96 5.00 5.00 3.07
22 8.06 4.23 2.66 7.72 4.11 2.78 7.37 3.98 2.89 7.01 3.86 3.01 6.65 3.73 3.12 6.29 3.61 3.23 5.93 3.49 3.33
20 7.55 5.08 2.59 7.22 4.95 2.70 6.88 4.82 2.82 6.54 4.70 2.93 6.21 4.57 3.03 5.87 4.44 3.13 5.52 4.31 3.23
420 18 7.08 5.89 2.53 6.77 5.75 2.64 6.46 5.60 2.75 6.16 5.43 2.86 5.86 5.24 2.96 5.56 5.05 3.07 5.26 4.84 3.17
16 6.74 6.48 2.48 6.46 6.30 2.59 6.18 6.11 2.70 5.91 5.90 2.81 5.65 5.65 2.92 5.39 5.39 3.03 5.12 5.12 3.13
14 6.65 6.64 2.47 6.41 6.40 2.59 6.16 6.15 2.70 5.91 5.91 2.81 5.65 5.65 2.92 5.39 5.39 3.03 5.13 5.13 3.13
Multipliers for Determining the Performance With Other Indoor Sections
Cooling Cooling
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4ASF 024 1.00 1.00 FG3ASA 024 0.97 1.02
030 1.02 1.00 — — —
38YCC036-70, 90 Outdoor Section With F(A,B)4ASF036 Indoor Section
22 11.9 6.04 3.60 11.4 5.86 3.77 10.9 5.68 3.94 10.4 5.50 4.11 9.92 5.32 4.27 9.42 5.14 4.42 8.90 4.96 4.58
20 11.1 7.14 3.51 10.6 6.95 3.67 10.2 6.77 3.83 9.69 6.58 3.99 9.21 6.40 4.14 8.73 6.21 4.29 8.25 6.03 4.43
500 18 10.3 8.21 3.42 9.91 8.01 3.58 9.48 7.81 3.74 9.04 7.61 3.89 8.60 7.40 4.04 8.17 7.16 4.18 7.73 6.90 4.32
16 9.78 9.05 3.36 9.39 8.82 3.51 8.99 8.58 3.67 8.60 8.34 3.82 8.21 8.07 3.96 7.82 7.77 4.11 7.43 7.43 4.26
14 9.51 9.47 3.32 9.18 9.15 3.48 8.85 8.83 3.64 8.51 8.49 3.80 8.16 8.15 3.95 7.80 7.80 4.11 7.43 7.43 4.26
22 12.1 6.29 3.68 11.6 6.11 3.85 11.1 5.93 4.02 10.6 5.75 4.18 10.1 5.56 4.35 9.53 5.38 4.50 8.99 5.20 4.65
20 11.3 7.51 3.58 10.8 7.32 3.75 10.3 7.13 3.91 9.83 6.94 4.07 9.33 6.75 4.22 8.84 6.56 4.37 8.34 6.37 4.51
5.60 18 10.5 8.67 3.49 10.1 8.47 3.65 9.65 8.25 3.81 9.21 8.03 3.97 8.77 7.77 4.12 8.33 7.49 4.27 7.90 7.20 4.42
16 10.0 9.53 3.43 9.61 9.28 3.59 9.21 9.02 3.75 8.81 8.74 3.90 8.43 8.40 4.06 8.04 8.04 4.21 7.66 7.66 4.36
14 9.84 9.82 3.41 9.49 9.47 3.58 9.14 9.13 3.74 8.78 8.77 3.90 8.42 8.41 4.06 8.04 8.04 4.21 7.66 7.66 4.36
22 12.3 6.61 3.77 11.8 6.43 3.94 11.3 6.24 4.11 10.7 6.06 4.28 10.2 5.87 4.44 9.65 5.69 4.60 9.10 5.50 4.75
20 11.5 7.98 3.67 11.0 7.78 3.84 10.5 7.59 4.00 9.98 7.40 4.16 9.47 7.20 4.32 8.96 7.01 4.47 8.45 6.81 4.61
640 18 10.8 9.24 3.59 10.3 9.00 3.75 9.85 8.75 3.91 9.41 8.46 4.07 8.98 8.16 4.23 8.53 7.86 4.38 8.08 7.56 4.53
16 10.3 10.1 3.53 9.87 9.79 3.69 9.47 9.47 3.86 9.09 9.09 4.02 8.70 8.70 4.18 8.31 8.31 4.34 7.91 7.91 4.49
14 10.2 10.2 3.52 9.84 9.84 3.69 9.47 9.47 3.86 9.09 9.09 4.02 8.70 8.70 4.18 8.31 8.31 4.34 7.92 7.92 4.49
Multipliers for Determining the Performance With Other Indoor Sections
Cooling Cooling
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4ASF 036 1.00 1.00 FG3ASA 036 0.98 1.00
F(A,B)4AS(F,B) 042 1.02 0.99 — — —
See notes on pg. 14.

13
Downloaded from www.Manualslib.com manuals search engine
Detailed cooling capacities* (S.I.) continued
COIL CONDENSER ENTERING AIR TEMPERATURES °C
AIR 28 32 36 40 44 48 52
Capacity Capacity Capacity Capacity Capacity Capacity Capacity
Kw† Sys. Kw† Sys. Kw† Sys. Kw† Sys. Kw† Sys. Kw† Sys. Kw† Sys.
(C) Power Power Power Power Power Power Power
L/S EWB Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw**
38YCC048-70, 90, 92 Outdoor Section With F(A,B)4AS(F,B)048 Indoor Section
22 15.4 7.87 4.50 14.9 7.69 4.79 14.4 7.51 5.09 13.9 7.32 5.41 13.3 7.13 5.75 12.8 6.94 6.11 12.3 6.75 6.48
20 14.5 9.38 4.41 14.0 9.19 4.69 13.5 9.00 4.98 13.0 8.81 5.29 12.5 8.62 5.63 12.0 8.42 5.97 11.5 8.23 6.33
650 18 13.6 10.8 4.32 13.2 10.7 4.59 12.7 10.5 4.88 12.3 10.3 5.18 11.8 10.1 5.51 11.3 9.82 5.84 10.8 9.56 6.19
16 12.9 12.0 4.25 12.5 11.8 4.52 12.1 11.5 4.80 11.7 11.3 5.11 11.3 11.0 5.43 10.9 10.7 5.75 10.4 10.4 6.09
14 12.6 12.6 4.21 12.3 12.3 4.49 12.0 11.9 4.78 11.6 11.6 5.09 11.2 11.2 5.41 10.8 10.8 5.75 10.4 10.4 6.09
22 15.6 8.26 4.60 15.1 8.08 4.89 14.6 7.89 5.19 14.1 7.71 5.51 13.5 7.51 5.86 13.0 7.32 6.22 12.4 7.13 6.59
20 14.7 9.96 4.51 14.2 9.78 4.79 13.7 9.59 5.08 13.2 9.39 5.39 12.7 9.19 5.73 12.2 9.00 6.08 11.7 8.80 6.44
750 18 13.9 11.6 4.42 13.4 11.4 4.69 13.0 11.2 4.98 12.5 10.9 5.29 12.0 10.7 5.62 11.6 10.4 5.97 11.1 10.1 6.32
16 13.3 12.8 4.35 12.9 12.5 4.63 12.5 12.2 4.92 12.0 12.0 5.22 11.6 11.6 5.56 11.2 11.2 5.90 10.8 10.8 6.25
14 13.1 13.1 4.34 12.8 12.7 4.62 12.4 12.4 4.91 12.0 12.0 5.22 11.6 11.6 5.56 11.2 11.2 5.90 10.8 10.8 6.25
22 15.8 8.64 4.70 15.3 8.45 4.99 14.8 8.27 5.29 14.2 8.08 5.61 13.7 7.89 5.95 13.1 7.69 6.31 12.5 7.50 6.69
20 14.9 10.5 4.60 14.4 10.3 4.88 13.9 10.2 5.18 13.4 9.96 5.49 12.9 9.75 5.83 12.3 9.55 6.18 11.8 9.35 6.54
850 18 14.1 12.3 4.51 13.6 12.0 4.79 13.2 11.8 5.08 12.7 11.5 5.40 12.3 11.1 5.74 11.8 10.8 6.09 11.3 10.5 6.45
16 13.6 13.4 4.45 13.2 13.1 4.73 12.8 12.8 5.03 12.4 12.4 5.34 11.9 11.9 5.68 11.5 11.5 6.04 11.1 11.1 6.40
14 13.5 13.5 4.45 13.1 13.1 4.73 12.8 12.8 5.03 12.4 12.4 5.34 11.9 11.9 5.68 11.5 11.5 6.04 11.1 11.1 6.40
Multipliers for Determining the Performance With Other Indoor Sections
Cooling Cooling
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4AS(F,B) 048 1.00 1.00 FG3ASA 048 0.98 1.00
060 1.03 1.01 060 1.00 1.01
38YCC060-90, 92 Outdoor Section With F(A,B)4AS(F,B)060 Indoor Section
22 19.1 9.97 5.49 18.5 9.74 5.88 17.9 9.52 6.30 17.2 9.28 6.76 16.5 9.05 7.25 15.8 8.80 7.78 15.1 8.55 8.33
20 18.0 12.0 5.35 17.4 11.7 5.73 16.8 11.5 6.15 16.2 11.3 6.60 15.5 11.0 7.09 14.9 10.8 7.60 14.2 10.5 8.15
850 18 16.9 13.9 5.22 16.4 13.7 5.60 15.8 13.4 6.02 15.2 13.2 6.46 14.7 12.9 6.95 14.1 12.5 7.47 13.5 12.1 8.01
16 16.1 15.4 5.13 15.6 15.1 5.51 15.2 14.8 5.93 14.6 14.4 6.37 14.1 14.0 6.86 13.6 13.6 7.38 13.0 13.0 7.93
14 15.9 15.9 5.10 15.5 15.4 5.49 15.0 15.0 5.91 14.6 14.6 6.36 14.1 14.1 6.86 13.6 13.6 7.38 13.1 13.1 7.93
22 19.2 10.2 5.55 18.6 9.94 5.94 17.9 9.71 6.36 17.3 9.48 6.82 16.6 9.25 7.31 15.9 9.00 7.84 15.2 8.76 8.39
20 18.1 12.3 5.41 17.5 12.0 5.79 16.9 11.8 6.21 16.2 11.6 6.66 15.6 11.3 7.15 14.9 11.1 7.66 14.3 10.8 8.21
900 18 17.0 14.3 5.28 16.5 14.1 5.66 15.9 13.8 6.08 15.4 13.5 6.52 14.8 13.1 7.01 14.2 12.8 7.53 13.6 12.3 8.08
16 16.3 15.8 5.19 15.8 15.5 5.58 15.3 15.1 5.99 14.8 14.7 6.44 14.3 14.3 6.93 13.8 13.8 7.46 13.2 13.2 8.01
14 16.1 16.1 5.17 15.7 15.7 5.56 15.2 15.2 5.98 14.8 14.8 6.44 14.3 14.3 6.94 13.8 13.8 7.46 13.2 13.2 8.01
22 19.3 10.4 5.61 18.7 10.1 6.00 18.1 9.92 6.42 17.4 9.68 6.88 16.7 9.45 7.37 16.0 9.20 7.90 15.2 8.95 8.45
20 18.2 12.6 5.46 17.6 12.3 5.85 17.0 12.1 6.26 16.3 11.9 6.71 15.7 11.6 7.20 15.0 11.4 7.72 14.3 11.1 8.26
950 18 17.1 14.7 5.33 16.6 14.4 5.72 16.0 14.1 6.13 15.5 13.8 6.58 14.9 13.4 7.08 14.3 13.0 7.60 13.7 12.6 8.15
16 16.5 16.1 5.25 16.0 15.8 5.64 15.5 15.4 6.06 15.0 15.0 6.51 14.5 14.5 7.01 13.9 13.9 7.53 13.4 13.4 8.09
14 16.3 16.3 5.24 15.9 15.9 5.63 15.4 15.4 6.05 15.0 15.0 6.51 14.5 14.5 7.01 13.9 13.9 7.53 13.4 13.4 8.09
22 19.4 10.6 5.66 18.8 10.3 6.06 18.1 10.1 6.47 17.4 9.87 6.93 16.7 9.64 7.43 16.0 9.39 7.95 15.3 9.14 8.50
20 18.3 12.9 5.51 17.6 12.6 5.90 17.0 12.4 6.32 16.4 12.2 6.77 15.7 11.9 7.26 15.1 11.7 7.77 14.3 11.4 8.32
1000 18 17.3 15.0 5.39 16.7 14.7 5.78 16.2 14.4 6.19 15.6 14.0 6.65 15.0 13.6 7.14 14.4 13.2 7.66 13.8 12.8 8.21
16 16.6 16.4 5.31 16.1 16.0 5.70 15.6 15.6 6.12 15.1 15.1 6.58 14.6 14.6 7.08 14.1 14.1 7.60 13.5 13.5 8.16
14 16.6 16.5 5.31 16.1 16.1 5.70 15.6 15.6 6.12 15.1 15.1 6.58 14.6 14.6 7.08 14.1 14.1 7.60 13.5 13.5 8.16
Multipliers for Determining the Performance With Other Indoor Sections
Cooling Cooling
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4AS(F,B) 060 1.00 1.00 FG3ASA 060 0.99 1.00
FB4ASB 070 1.02 1.02 — — —
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation and connected by 4.55m of tubing. If other than 4.55m of
tubing is used and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 27°C entering air at the indoor coil. For sensible capacities at other than 27°C, deduct 245 kw per 480
L/S of indoor coil air for each degree below 27°C, or add 245 kw per 480 L/S of indoor coil air per degree above 27°C.
** System kw is total of indoor and outdoor unit kilowatt’s.
EWB — Entering Wet Bulb
L/S — Liters per second

14
Downloaded from www.Manualslib.com manuals search engine
Detailed cooling capacities* (English)
COIL CONDENSER ENTERING AIR TEMPERATURES °F
AIR 75 85 95 105 115 125
Capacity Capacity Capacity Capacity Capacity Capacity
MBtuh† Sys. MBtuh† Sys. MBtuh† Sys. MBtuh† Sys. MBtuh† Sys. MBtuh† Sys.
(F) Power Power Power Power Power Power
CFM EWB Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw**
38YCC024-70 Outdoor Section With F(A,B)4ASF024 Indoor Section
72 27.9 13.5 2.43 26.4 12.9 2.60 24.8 12.3 2.76 23.3 11.7 2.92 21.7 11.2 3.08 20.0 10.6 3.22
700 67 25.4 16.7 2.35 24.0 16.1 2.51 22.6 15.5 2.66 21.1 14.9 2.81 19.6 14.3 2.95 18.1 13.7 3.08
62 23.1 19.9 2.27 21.8 19.3 2.42 20.5 18.7 2.56 19.2 18.0 2.70 17.8 17.3 2.84 16.5 16.5 2.97
57 21.9 21.9 2.22 20.8 20.8 2.38 19.8 19.8 2.53 18.7 18.7 2.68 17.6 17.6 2.83 16.5 16.5 2.97
72 28.5 14.1 2.49 26.9 13.5 2.66 25.3 12.9 2.83 23.6 12.3 2.98 22.0 11.7 3.14 20.3 11.1 3.28
800 67 26.0 17.7 2.40 24.5 17.1 2.56 23.0 16.5 2.72 21.5 15.9 2.87 19.9 15.3 3.01 18.3 14.7 3.15
62 23.7 21.3 2.32 22.3 20.6 2.48 21.0 19.9 2.63 19.6 19.2 2.77 18.3 18.3 2.91 17.1 17.1 3.05
57 22.8 22.8 2.29 21.7 21.7 2.45 20.6 20.6 2.61 19.5 19.5 2.76 18.3 18.3 2.91 17.1 17.1 3.06
72 29.0 14.6 2.54 27.3 14.0 2.71 25.7 13.4 2.88 23.9 12.8 3.04 22.2 12.3 3.19 20.5 11.7 3.34
900 67 26.4 18.7 2.46 24.9 18.1 2.62 23.4 17.5 2.77 21.8 16.8 2.93 20.2 16.2 3.07 18.6 15.6 3.20
62 24.2 22.6 2.38 22.8 21.9 2.53 21.4 21.1 2.68 20.1 20.1 2.83 18.9 18.9 2.99 17.6 17.6 3.13
57 23.6 23.6 2.36 22.5 22.5 2.52 21.3 21.3 2.68 20.1 20.1 2.83 18.9 18.9 2.99 17.6 17.6 3.13
Multipliers for Determining the Performance With Other Indoor Sections
Cooling Cooling
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4ASF 024 1.00 1.00 FG3ASA 024 0.97 1.02
030 1.02 1.00 — — —
38YCC036-70, 90 Outdoor Section With F(A,B)4ASF036 Indoor Section
72 42.5 20.8 3.43 40.2 19.9 3.67 37.9 19.1 3.91 35.6 18.2 4.14 33.2 17.4 4.36 30.7 16.5 4.57
1050 67 38.6 25.9 3.31 36.5 25.1 3.54 34.3 24.2 3.76 32.1 23.3 3.98 29.9 22.4 4.18 27.6 21.5 4.38
62 35.0 31.0 3.20 33.1 30.0 3.42 31.2 29.1 3.63 29.2 28.1 3.83 27.3 27.0 4.04 25.4 25.4 4.24
57 33.5 33.5 3.15 31.9 31.9 3.37 30.4 30.4 3.60 28.8 28.8 3.81 27.1 27.1 4.03 25.4 25.4 4.24
72 43.4 21.7 3.52 41.1 20.9 3.76 38.6 20.0 4.00 36.2 19.1 4.23 33.7 18.3 4.45 31.1 17.4 4.67
1200 67 39.4 27.6 3.39 37.2 26.7 3.62 35.0 25.8 3.85 32.6 24.9 4.07 30.3 23.9 4.27 28.0 23.0 4.47
62 35.9 33.1 3.28 33.9 32.1 3.51 31.9 31.0 3.72 30.0 29.8 3.93 28.1 28.1 4.15 26.3 26.3 4.36
57 34.9 34.9 3.25 33.2 33.2 3.48 31.6 31.6 3.71 29.9 29.9 3.93 28.1 28.1 4.15 26.3 26.3 4.36
72 44.1 22.6 3.60 41.7 21.8 3.84 39.2 20.9 4.08 36.7 20.0 4.31 34.0 19.2 4.54 31.4 18.3 4.75
1350 67 40.1 29.1 3.47 37.8 28.2 3.70 35.4 27.3 3.93 33.1 26.4 4.15 30.7 25.4 4.36 28.4 24.5 4.56
62 36.6 35.1 3.37 34.6 33.9 3.59 32.6 32.6 3.81 30.8 30.8 4.04 29.0 29.0 4.26 27.1 27.1 4.48
57 36.0 36.0 3.35 34.3 34.3 3.58 32.6 32.6 3.81 30.8 30.8 4.04 29.0 29.0 4.26 27.1 27.1 4.48
Multipliers for Determining the Performance With Other Indoor Sections
Cooling Cooling
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4ASF 036 1.00 1.00 FG3ASA 036 0.98 1.00
F(A,B)4AS(F,B) 042 1.02 0.99 — — —
See notes on pg. 16.

15
Downloaded from www.Manualslib.com manuals search engine
Detailed cooling capacities* (English) continued
COIL CONDENSER ENTERING AIR TEMPERATURES °F
AIR 75 85 95 105 115 125
Capacity Capacity Capacity Capacity Capacity Capacity
MBtuh† Sys. MBtuh† Sys. MBtuh† Sys. MBtuh† Sys. MBtuh† Sys. MBtuh† Sys.
(F) Power Power Power Power Power Power
CFM EWB Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw**
38YCC048-70, 90, 92 Outdoor Section With F(A,B)4AS(F,B)048 Indoor Section
72 54.5 27.0 4.24 52.3 26.2 4.62 49.9 25.3 5.04 47.5 24.4 5.48 44.9 23.5 5.96 42.4 22.7 6.48
1400 67 50.1 34.3 4.12 48.0 33.4 4.49 45.8 32.5 4.88 43.6 31.6 5.31 41.2 30.7 5.78 38.8 29.8 6.27
62 46.0 41.3 4.00 44.1 40.4 4.36 42.1 39.4 4.75 40.1 38.4 5.17 38.0 37.3 5.61 35.7 35.7 6.08
57 44.4 44.4 3.96 42.8 42.8 4.32 41.2 41.2 4.71 39.5 39.5 5.15 37.8 37.8 5.60 35.8 35.8 6.08
72 55.4 28.2 4.34 53.1 27.4 4.72 50.6 26.5 5.13 48.1 25.6 5.58 45.4 24.7 6.06 42.8 23.8 6.58
1600 67 51.0 36.3 4.21 48.8 35.5 4.58 46.5 34.6 4.98 44.1 33.7 5.41 41.7 32.7 5.88 39.3 31.8 6.37
62 46.9 44.1 4.10 45.0 43.1 4.46 43.0 42.0 4.85 41.0 40.7 5.27 39.0 39.0 5.74 37.0 37.0 6.23
57 46.0 46.0 4.07 44.4 44.4 4.44 42.6 42.6 4.84 40.9 40.9 5.27 39.0 39.0 5.74 37.0 37.0 6.23
72 56.1 29.4 4.43 53.7 28.5 4.81 51.2 27.6 5.22 48.6 26.8 5.67 45.9 25.8 6.15 43.1 24.9 6.67
1800 67 51.6 38.4 4.30 49.4 37.5 4.67 47.1 36.6 5.07 44.6 35.6 5.50 42.1 34.7 5.97 39.7 33.7 6.47
62 47.8 46.6 4.19 45.8 45.4 4.55 43.9 43.9 4.95 41.9 41.9 5.39 40.0 40.0 5.86 38.0 38.0 6.37
57 47.4 47.4 4.18 45.7 45.7 4.55 43.8 43.8 4.95 42.0 42.0 5.39 40.0 40.0 5.86 38.0 38.0 6.37
Multipliers for Determining the Performance With Other Indoor Sections
Cooling Cooling
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4AS(F,B) 048 1.00 1.00 FG3ASA 048 0.98 1.00
060 1.03 1.01 060 1.00 1.01
38YCC060-90, 92 Outdoor Section With F(A,B)4AS(F,B)060 Indoor Section
72 67.5 33.7 5.11 64.7 32.7 5.61 61.8 31.6 6.18 58.6 30.5 6.81 55.5 29.4 7.51 52.0 28.2 8.27
1750 67 61.9 43.0 4.91 59.3 41.9 5.41 56.5 40.8 5.97 53.7 39.7 6.59 50.8 38.6 7.27 47.6 37.3 8.02
62 56.8 52.0 4.74 54.5 50.9 5.24 52.0 49.6 5.79 49.5 48.3 6.41 47.0 46.8 7.09 44.4 44.4 7.84
57 55.2 55.2 4.69 53.3 53.3 5.20 51.3 51.3 5.76 49.1 49.1 6.39 46.9 46.9 7.09 44.4 44.4 7.84
72 68.1 34.6 5.19 65.2 33.6 5.70 62.1 32.5 6.26 59.0 31.4 6.89 55.8 30.3 7.59 52.3 29.1 8.36
1900 67 62.5 44.6 4.99 59.8 43.5 5.49 57.0 42.4 6.05 54.1 41.3 6.67 51.2 40.1 7.36 47.9 38.9 8.11
62 57.6 54.2 4.83 55.2 53.0 5.32 52.8 51.7 5.88 50.2 50.1 6.50 47.9 47.9 7.19 45.2 45.2 7.96
57 56.4 56.4 4.79 54.5 54.5 5.30 52.3 52.3 5.87 50.1 50.1 6.50 47.8 47.8 7.20 45.3 45.3 7.96
72 68.6 35.2 5.24 65.6 34.2 5.75 62.6 33.1 6.32 59.3 32.0 6.95 56.0 30.9 7.65 52.5 29.7 8.41
2000 67 62.8 45.7 5.04 60.1 44.6 5.54 57.3 43.5 6.10 54.4 42.4 6.72 51.3 41.1 7.41 48.0 39.9 8.16
62 58.0 55.6 4.88 55.6 54.3 5.38 53.1 52.8 5.93 50.8 50.8 6.56 48.4 48.4 7.26 45.7 45.7 8.03
57 57.2 57.2 4.86 55.1 55.1 5.36 53.0 53.0 5.93 50.7 50.7 6.57 48.4 48.4 7.26 45.7 45.7 8.03
72 69.0 36.1 5.32 66.0 35.1 5.83 62.9 34.0 6.39 59.6 32.9 7.03 56.2 31.8 7.73 52.7 30.6 8.49
2150 67 63.3 47.2 5.12 60.5 46.1 5.62 57.7 45.0 6.18 54.7 43.9 6.80 51.6 42.7 7.49 48.3 41.4 8.24
62 58.7 57.5 4.96 56.2 55.9 5.46 53.9 53.9 6.03 51.6 51.6 6.66 49.1 49.1 7.36 46.5 46.5 8.13
57 58.2 58.2 4.95 56.1 56.1 5.46 53.9 53.9 6.03 51.5 51.5 6.66 49.1 49.1 7.36 46.5 46.5 8.13
Multipliers for Determining the Performance With Other Indoor Sections
Cooling Cooling
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4AS(F,B) 060 1.00 1.00 FG3ASA 060 0.99 1.00
FB4ASB 070 1.02 1.02 — — —
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation and connected by 25 ft of tubing. If other than 25 ft of
tubing is used and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F entering air at the indoor coil. For sensible capacities at other than 80°F, deduct 835 Btuh per 1000
CFM of indoor coil air for each degree below 80°F, or add 835 Btuh per 1000 CFM of indoor coil air per degree above 80°F.
** System kw is total of indoor and outdoor unit kilowatts.
EWB — Entering Wet Bulb

16
Downloaded from www.Manualslib.com manuals search engine
Heat pump heating performance (S.I.)
OUTDOOR COIL ENTERING AIR TEMPERATURES °C
–16 –8 0 4 8 12 16 20
INDOOR Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total
AIR Kw Power Kw Power Kw Power Kw Power Kw Power Kw Power Kw Power Kw Power
(C)
EDB L/ S Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw*
38YCC024-70 Outdoor Section With F(A,B)4ASF024 Indoor Section
340 3.39 3.12 1.39 4.44 4.04 1.63 5.64 5.08 1.90 6.32 5.90 2.05 7.04 7.01 2.22 7.87 7.87 2.42 8.75 8.75 2.64 9.67 9.67 2.88
12 380 3.44 3.17 1.41 4.51 4.10 1.65 5.73 5.16 1.91 6.42 5.99 2.06 7.15 7.11 2.22 7.98 7.98 2.42 8.88 8.88 2.64 9.82 9.82 2.88
420 3.49 3.21 1.43 4.56 4.15 1.66 5.80 5.21 1.92 6.49 6.05 2.07 7.22 7.18 2.23 8.06 8.06 2.43 8.97 8.97 2.65 9.93 9.93 2.89
340 3.28 3.01 1.41 4.33 3.94 1.66 5.51 4.96 1.94 6.18 5.76 2.10 6.89 6.86 2.27 7.70 7.70 2.47 8.57 8.57 2.70 9.48 9.48 2.95
15 380 3.33 3.06 1.43 4.39 4.00 1.68 5.60 5.04 1.95 6.28 5.85 2.11 6.99 6.96 2.28 7.82 7.82 2.48 8.70 8.70 2.70 9.63 9.63 2.95
420 3.37 3.10 1.45 4.45 4.05 1.69 5.66 5.09 1.96 6.34 5.91 2.12 7.07 7.03 2.28 7.90 7.90 2.48 8.79 8.79 2.71 9.73 9.73 2.95
340 3.16 2.91 1.43 4.21 3.83 1.69 5.38 4.84 1.98 6.04 5.63 2.14 6.74 6.71 2.32 7.54 7.54 2.53 8.39 8.39 2.76 9.28 9.28 3.01
18 380 3.21 2.95 1.45 4.27 3.89 1.71 5.46 4.92 1.99 6.13 5.71 2.15 6.84 6.81 2.33 7.65 7.65 2.54 8.52 8.52 2.77 9.43 9.43 3.01
420 3.26 3.00 1.47 4.33 3.94 1.72 5.53 4.97 2.01 6.20 5.78 2.17 6.92 6.89 2.34 7.74 7.74 2.54 8.61 8.61 2.77 9.54 9.54 3.02
340 3.05 2.80 1.44 4.10 3.73 1.72 5.25 4.73 2.02 5.89 5.49 2.19 6.59 6.56 2.37 7.37 7.37 2.59 8.21 8.21 2.83 9.08 9.08 3.08
21 380 3.10 2.85 1.47 4.16 3.78 1.74 5.33 4.80 2.03 5.98 5.58 2.20 6.69 6.66 2.38 7.49 7.49 2.59 8.34 8.34 2.83 9.23 9.23 3.08
420 3.14 2.89 1.49 4.21 3.83 1.75 5.39 4.85 2.05 6.06 5.65 2.21 6.77 6.74 2.39 7.58 7.58 2.60 8.44 8.44 2.83 9.35 9.35 3.09
340 2.92 2.69 1.46 3.98 3.63 1.75 5.12 4.61 2.06 5.75 5.36 2.23 6.43 6.40 2.42 7.20 7.20 2.64 8.02 8.02 2.89 8.88 8.88 3.14
24 380 2.98 2.74 1.48 4.04 3.68 1.76 5.19 4.68 2.07 5.84 5.44 2.25 6.53 6.50 2.43 7.32 7.32 2.65 8.15 8.15 2.89 9.03 9.03 3.14
420 3.02 2.78 1.50 4.10 3.73 1.78 5.26 4.73 2.09 5.91 5.51 2.26 6.61 6.58 2.44 7.41 7.41 2.66 8.26 8.26 2.89 9.14 9.14 3.15
Multipliers for Determining the Performance With Other Indoor Sections
Heating Heating
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4ASF 024 1.00 1.00 FG3ASA 024 0.99 1.05
030 1.00 0.99 — — —
38YCC036-70, 90 Outdoor Section With F(A,B)4ASF036 Indoor Section
500 5.42 4.98 2.22 7.03 6.40 2.49 8.86 7.98 2.78 9.93 9.26 2.95 11.1 11.0 3.14 12.3 12.3 3.36 13.7 13.7 3.61 15.1 15.1 3.88
2 560 5.49 5.05 2.26 7.13 6.49 2.52 9.00 8.10 2.80 10.1 9.40 2.97 11.2 11.2 3.14 12.5 12.5 3.36 13.9 13.9 3.60 15.3 15.3 3.87
640 5.60 5.15 2.31 7.26 6.60 2.56 9.15 8.23 2.83 10.2 9.54 2.99 11.4 11.4 3.16 12.7 12.7 3.37 14.1 14.1 3.62 15.6 15.6 3.88
500 5.22 4.80 2.25 6.84 6.22 2.54 8.65 7.79 2.84 9.70 9.04 3.02 10.8 10.8 3.21 12.1 12.1 3.44 13.4 13.4 3.69 14.8 14.8 3.97
15 560 5.30 4.87 2.28 6.94 6.32 2.57 8.78 7.90 2.86 9.84 9.17 3.04 11.0 10.9 3.22 12.2 12.2 3.44 13.6 13.6 3.69 15.0 15.0 3.96
640 5.41 4.97 2.34 7.06 6.43 2.61 8.93 8.03 2.90 10.0 9.32 3.06 11.1 11.1 3.24 12.4 12.4 3.46 13.8 13.8 3.70 15.2 15.2 3.97
500 5.02 4.62 2.27 6.65 6.05 2.58 8.44 7.60 2.91 9.46 8.82 3.09 10.6 10.5 3.29 11.8 11.8 3.52 13.1 13.1 3.78 14.4 14.4 4.06
18 560 5.11 4.69 2.31 6.75 6.14 2.61 8.57 7.71 2.93 9.60 8.95 3.11 10.7 10.7 3.30 12.0 12.0 3.52 13.3 13.3 3.78 14.7 14.7 4.05
640 5.21 4.79 2.37 6.87 6.25 2.66 8.71 7.84 2.96 9.76 9.10 3.13 10.9 10.8 3.32 12.2 12.2 3.54 13.5 13.5 3.79 14.9 14.9 4.06
500 4.83 4.44 2.30 6.46 5.88 2.63 8.23 7.40 2.97 9.22 8.60 3.16 10.3 10.2 3.36 11.5 11.5 3.60 12.8 12.8 3.86 14.1 14.1 4.14
21 560 4.91 4.52 2.34 6.56 5.97 2.66 8.35 7.52 2.99 9.37 8.73 3.18 10.5 10.4 3.38 11.7 11.7 3.61 13.0 13.0 3.86 14.3 14.3 4.14
640 5.02 4.61 2.40 6.68 6.08 2.71 8.49 7.64 3.03 9.53 8.88 3.21 10.6 10.6 3.40 11.9 11.9 3.62 13.2 13.2 3.88 14.6 14.6 4.15
500 4.61 4.24 2.33 6.26 5.70 2.67 8.01 7.21 3.03 8.99 8.38 3.22 10.0 9.99 3.44 11.2 11.2 3.68 12.4 12.4 3.95 13.7 13.7 4.23
24 560 4.70 4.32 2.37 6.36 5.79 2.70 8.14 7.32 3.05 9.13 8.51 3.24 10.2 10.1 3.45 11.4 11.4 3.69 12.7 12.7 3.95 14.0 14.0 4.23
640 4.81 4.42 2.42 6.48 5.90 2.75 8.28 7.45 3.09 9.29 8.66 3.28 10.4 10.3 3.48 11.6 11.6 3.71 12.9 12.9 3.96 14.2 14.2 4.24
Multipliers for Determining the Performance With Other Indoor Sections
Heating Heating
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4ASF 036 1.00 1.00 FG3ASA 036 0.99 1.01
F(A,B)4AS(F,B) 042 1.00 0.97 — — —
See notes on pg. 18.

17
Downloaded from www.Manualslib.com manuals search engine
Heat pump heating performance (S.I.) continued
OUTDOOR COIL ENTERING AIR TEMPERATURES °C
–16 –8 0 4 8 12 16 20
INDOOR Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total
AIR Kw Power Kw Power Kw Power Kw Power Kw Power Kw Power Kw Power Kw Power
(C)
EDB L/ S Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw*
38YCC048-70, 90, 92 Outdoor Section With F(A,B)4AS(F,B)048 Indoor Section
650 6.41 5.89 3.05 8.38 7.63 3.25 10.9 9.79 3.48 12.3 11.5 3.61 13.9 13.8 3.75 15.8 15.8 3.92 17.8 17.8 4.12 20.1 20.1 4.34
12 750 6.48 5.96 3.08 8.49 7.72 3.27 11.0 9.92 3.49 12.4 11.6 3.60 13.9 13.9 3.72 15.9 15.9 3.89 18.1 18.1 4.08 20.4 20.4 4.30
850 6.56 6.03 3.13 8.58 7.81 3.31 11.1 9.99 3.50 12.5 11.7 3.61 14.2 14.2 3.74 16.1 16.1 3.88 18.2 18.2 4.05 20.4 20.4 4.25
650 6.35 5.84 3.19 8.33 7.58 3.40 10.8 9.71 3.64 12.2 11.4 3.78 13.8 13.7 3.93 15.6 15.6 4.11 17.7 17.7 4.32 19.9 19.9 4.55
15 750 6.43 5.91 3.23 8.42 7.67 3.42 10.9 9.82 3.64 12.3 11.5 3.77 13.8 13.8 3.89 15.8 15.8 4.07 17.9 17.9 4.27 20.1 20.1 4.49
850 6.50 5.98 3.27 8.52 7.75 3.45 11.0 9.90 3.66 12.4 11.6 3.77 14.1 14.0 3.91 15.9 15.9 4.06 18.0 18.0 4.24 20.2 20.2 4.45
650 6.29 5.79 3.34 8.27 7.52 3.55 10.7 9.62 3.80 12.1 11.3 3.95 13.6 13.6 4.10 15.5 15.5 4.30 17.5 17.5 4.52 19.7 19.7 4.76
18 750 6.37 5.86 3.37 8.36 7.61 3.57 10.8 9.72 3.80 12.2 11.4 3.93 13.7 13.7 4.07 15.6 15.6 4.25 17.7 17.7 4.46 19.9 19.9 4.69
850 6.44 5.92 3.41 8.45 7.69 3.60 10.9 9.81 3.81 12.3 11.5 3.94 13.9 13.8 4.07 15.8 15.8 4.24 17.8 17.8 4.43 20.0 20.0 4.65
650 6.24 5.73 3.48 8.21 7.47 3.70 10.6 9.54 3.96 12.0 11.2 4.11 13.5 13.4 4.28 15.3 15.3 4.48 17.3 17.3 4.72 19.4 19.4 4.96
21 750 6.31 5.80 3.51 8.30 7.55 3.71 10.7 9.63 3.96 12.1 11.3 4.09 13.6 13.6 4.25 15.5 15.5 4.44 17.5 17.5 4.65 19.6 19.6 4.88
850 6.39 5.87 3.54 8.39 7.63 3.74 10.8 9.72 3.97 12.2 11.4 4.10 13.7 13.7 4.24 15.6 15.6 4.42 17.7 17.7 4.62 19.8 19.8 4.84
650 6.20 5.70 3.64 8.18 7.44 3.86 10.5 9.46 4.13 11.9 11.1 4.29 13.4 13.3 4.46 15.1 15.1 4.67 17.1 17.1 4.91 19.2 19.2 5.18
24 750 6.27 5.76 3.66 8.25 7.51 3.87 10.6 9.55 4.12 12.0 11.2 4.27 13.5 13.4 4.43 15.3 15.3 4.63 17.3 17.3 4.85 19.4 19.4 5.09
850 6.34 5.83 3.70 8.31 7.57 3.89 10.7 9.63 4.13 12.1 11.3 4.27 13.6 13.6 4.42 15.5 15.5 4.61 17.5 17.5 4.82 19.6 19.6 5.05
Multipliers for Determining the Performance With Other Indoor Sections
Heating Heating
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4AS(F,B) 048 1.00 1.00 FG3ASA 048 1.00 1.03
060 0.99 0.96 060 1.00 1.02
38YCC060-90, 92 Outdoor Section With F(A,B)4AS(F,B)060 Indoor Section
850 9.46 8.70 3.51 11.7 10.6 3.72 14.3 12.8 4.00 15.7 14.7 4.17 17.4 17.3 4.37 19.4 19.4 4.65 21.6 21.6 4.98 24.0 24.0 5.34
12 900 9.50 8.73 3.53 11.7 10.7 3.73 14.3 12.9 4.00 15.8 14.7 4.17 17.4 17.3 4.36 19.4 19.4 4.64 21.8 21.8 4.97 24.3 24.3 5.33
950 9.54 8.77 3.55 11.7 10.7 3.74 14.4 12.9 4.01 15.9 14.8 4.18 17.5 17.4 4.37 19.5 19.5 4.64 21.7 21.7 4.96 24.0 24.0 5.32
1000 9.59 8.81 3.57 11.8 10.7 3.76 14.4 13.0 4.02 15.9 14.9 4.19 17.6 17.5 4.38 19.6 19.6 4.65 21.7 21.7 4.97 24.0 24.0 5.32
850 9.42 8.66 3.73 11.6 10.6 3.96 14.2 12.8 4.25 15.7 14.6 4.43 17.3 17.2 4.64 19.2 19.2 4.93 21.4 21.4 5.26 23.7 23.7 5.63
15 900 9.46 8.70 3.75 11.7 10.6 3.97 14.3 12.8 4.25 15.7 14.7 4.43 17.3 17.3 4.63 19.3 19.3 4.91 21.5 21.5 5.24 23.9 23.9 5.61
950 9.51 8.74 3.77 11.7 10.6 3.98 14.3 12.9 4.26 15.8 14.7 4.43 17.4 17.3 4.64 19.4 19.4 4.91 21.5 21.5 5.23 23.7 23.7 5.60
1000 9.55 8.78 3.79 11.7 10.7 4.00 14.4 12.9 4.27 15.9 14.8 4.44 17.5 17.4 4.64 19.4 19.4 4.91 21.6 21.6 5.23 23.8 23.8 5.60
850 9.38 8.63 3.95 11.6 10.5 4.20 14.1 12.7 4.51 15.6 14.5 4.69 17.2 17.1 4.91 19.1 19.1 5.20 21.2 21.2 5.54 23.4 23.4 5.91
18 900 9.43 8.67 3.97 11.6 10.6 4.20 14.2 12.8 4.50 15.6 14.6 4.69 17.3 17.2 4.90 19.2 19.2 5.18 21.3 21.3 5.52 23.6 23.6 5.89
950 9.47 8.70 3.99 11.6 10.6 4.21 14.2 12.8 4.51 15.7 14.6 4.69 17.3 17.2 4.90 19.2 19.2 5.18 21.3 21.3 5.51 23.5 23.5 5.88
1000 9.51 8.74 4.01 11.7 10.6 4.23 14.3 12.9 4.52 15.8 14.7 4.69 17.4 17.3 4.90 19.3 19.3 5.18 21.4 21.4 5.50 23.6 23.6 5.87
850 9.34 8.59 4.17 11.5 10.5 4.44 14.1 12.7 4.76 15.5 14.4 4.96 17.1 17.0 5.19 18.9 18.9 5.48 21.0 21.0 5.82 23.1 23.1 6.20
21 900 9.39 8.63 4.19 11.6 10.5 4.44 14.1 12.7 4.76 15.6 14.5 4.95 17.2 17.1 5.17 19.0 19.0 5.46 21.0 21.0 5.79 23.2 23.2 6.17
950 9.43 8.67 4.21 11.6 10.6 4.45 14.2 12.8 4.76 15.6 14.6 4.94 17.2 17.2 5.16 19.1 19.1 5.45 21.1 21.1 5.78 23.3 23.3 6.15
1000 9.47 8.71 4.23 11.6 10.6 4.46 14.2 12.8 4.77 15.7 14.6 4.95 17.3 17.2 5.16 19.2 19.2 5.44 21.2 21.2 5.77 23.4 23.4 6.14
850 9.29 8.54 4.40 11.5 10.5 4.69 14.0 12.6 5.03 15.4 14.4 5.23 16.9 16.9 5.46 18.8 18.8 5.77 20.8 20.8 6.12 22.9 22.9 6.52
24 900 9.34 8.59 4.42 11.5 10.5 4.69 14.1 12.6 5.02 15.5 14.4 5.21 17.0 16.9 5.44 18.9 18.9 5.74 20.9 20.9 6.09 23.0 23.0 6.48
950 9.38 8.62 4.43 11.6 10.5 4.70 14.1 12.7 5.02 15.5 14.5 5.21 17.1 17.0 5.43 18.9 18.9 5.72 21.0 21.0 6.07 23.1 23.1 6.45
1000 9.43 8.67 4.45 11.6 10.6 4.71 14.2 12.7 5.02 15.6 14.5 5.21 17.1 17.1 5.43 19.0 19.0 5.72 21.0 21.0 6.06 23.2 23.2 6.44
Multipliers for Determining the Performance With Other Indoor Sections
Heating Heating
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4AS(F,B) 060 1.00 1.00 FG3ASA 060 0.99 1.03
FB4ASB 070 0.99 0.95 — — —
* The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these
values to obtain total system kilowatts.
† The kw heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The kw heating from supple-
ment heaters should be added to those values to obtain total system capacity.
EDB — Entering Dry Bulb

18
Downloaded from www.Manualslib.com manuals search engine
Heat pump heating performance (English)
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
–3 7 17 27 37 47 57 67
INDOOR Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total
AIR Kw Power Kw Power Kw Power Kw Power Kw Power Kw Power Kw Power Kw Power
(F)
EDB CFM Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw*
38YCC024-70 Outdoor Section With F(A,B)4ASF024 Indoor Section
700 9.25 8.51 1.32 11.6 10.7 1.49 14.1 12.9 1.68 16.7 14.9 1.87 19.7 18.0 2.09 23.0 23.0 2.34 26.8 26.8 2.64 31.0 31.0 2.99
65 800 9.45 8.69 1.34 11.8 10.9 1.51 14.4 13.1 1.70 17.0 15.1 1.89 20.1 18.3 2.10 23.5 23.5 2.35 27.3 27.3 2.64 31.6 31.6 2.99
900 9.62 8.85 1.37 12.0 11.0 1.54 14.6 13.3 1.72 17.3 15.4 1.91 20.4 18.5 2.12 23.8 23.8 2.36 27.7 27.7 2.65 32.1 32.1 2.99
700 8.87 8.16 1.33 11.2 10.3 1.51 13.8 12.5 1.70 16.4 14.5 1.91 19.3 17.6 2.13 22.6 22.6 2.39 26.3 26.3 2.69 30.4 30.4 3.05
70 800 9.07 8.35 1.35 11.5 10.5 1.53 14.0 12.8 1.72 16.7 14.8 1.92 19.6 17.9 2.14 23.0 23.0 2.40 26.8 26.8 2.70 31.0 31.0 3.05
900 9.25 8.51 1.38 11.6 10.7 1.56 14.2 13.0 1.75 16.9 15.0 1.94 19.9 18.1 2.16 23.3 23.3 2.41 27.2 27.2 2.70 31.5 31.5 3.05
700 8.45 7.77 1.34 10.9 9.99 1.52 13.4 12.2 1.73 16.0 14.2 1.94 18.9 17.2 2.17 22.1 22.1 2.44 25.8 25.8 2.75 29.8 29.8 3.11
75 800 8.66 7.96 1.36 11.1 10.2 1.55 13.6 12.4 1.75 16.3 14.4 1.96 19.2 17.5 2.19 22.5 22.5 2.44 26.3 26.3 2.75 30.4 30.4 3.10
900 8.84 8.14 1.39 11.3 10.4 1.57 13.8 12.6 1.77 16.5 14.6 1.98 19.5 17.7 2.20 22.8 22.8 2.46 26.6 26.6 2.76 30.8 30.8 3.11
Multipliers for Determining the Performance With Other Indoor Sections
Heating Heating
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4ASF 024 1.00 1.00 FG3ASA 024 0.99 1.05
030 1.00 0.99 — — —
38YCC036-70, 90 Outdoor Section With F(A,B)4AS(F,B)036 Indoor Section
1050 14.7 13.6 2.15 18.5 17.0 2.35 22.3 20.4 2.57 26.3 23.4 2.79 31.0 28.2 3.03 36.2 36.2 3.31 42.0 42.0 3.64 48.4 48.4 4.03
65 1200 15.1 13.9 2.19 18.8 17.3 2.40 22.7 20.7 2.61 26.8 23.8 2.82 31.6 28.7 3.06 36.8 36.8 3.32 42.8 42.8 3.64 49.3 49.3 4.02
1350 15.4 14.2 2.24 19.1 17.6 2.44 23.1 21.1 2.65 27.2 24.2 2.85 32.0 29.1 3.08 37.3 37.3 3.34 43.4 43.4 3.66 50.0 50.0 4.03
1050 14.0 12.9 2.16 17.9 16.4 2.38 21.7 19.8 2.61 25.7 22.8 2.84 30.3 27.6 3.10 35.3 35.3 3.38 41.0 41.0 3.72 47.3 47.3 4.11
70 1200 14.4 13.2 2.21 18.2 16.7 2.43 22.1 20.2 2.65 26.2 23.2 2.87 30.8 28.1 3.12 36.0 36.0 3.40 41.8 41.8 3.72 48.3 48.3 4.11
1350 14.7 13.5 2.27 18.5 17.0 2.48 22.5 20.5 2.69 26.6 23.6 2.91 31.3 28.5 3.15 36.5 36.5 3.42 42.5 42.5 3.74 49.0 49.0 4.12
1050 13.3 12.2 2.18 17.2 15.8 2.41 21.1 19.3 2.65 25.1 22.3 2.89 29.6 26.9 3.16 34.5 34.5 3.45 40.1 40.1 3.79 46.3 46.3 4.19
75 1200 13.7 12.6 2.23 17.6 16.2 2.45 21.5 19.6 2.69 25.6 22.7 2.92 30.1 27.4 3.18 35.2 35.2 3.47 40.9 40.9 3.80 47.2 47.2 4.19
1350 14.0 12.8 2.28 17.9 16.5 2.50 21.9 20.0 2.73 25.9 23.0 2.96 30.6 27.8 3.21 35.7 35.7 3.49 41.5 41.5 3.81 47.9 47.9 4.20
Multipliers for Determining the Performance With Other Indoor Sections
Heating Heating
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4ASF 036 1.00 1.00 FG3ASA 036 0.99 1.01
F(A,B)4AS(F,B) 042 1.00 0.97 — — —
See notes on pg. 20.

19
Downloaded from www.Manualslib.com manuals search engine
Heat pump heating performance (English) continued
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
–3 7 17 27 37 47 57 67
INDOOR Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total
AIR Kw Power Kw Power Kw Power Kw Power Kw Power Kw Power Kw Power Kw Power
(F)
EDB CFM Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw* Total Integ† Kw*
38YCC048-70, 90, 92 Outdoor Section With F(A,B)4AS(F,B)048 Indoor Section
1400 18.7 17.2 3.27 23.2 21.3 3.41 27.9 25.4 3.56 33.3 29.6 3.72 39.6 36.1 3.92 46.9 46.9 4.13 55.8 55.8 4.41 66.0 66.0 4.74
65 1600 18.9 17.4 3.30 23.5 21.6 3.44 28.2 25.7 3.57 33.7 29.9 3.73 40.0 36.4 3.90 47.3 47.3 4.10 56.3 56.3 4.36 66.7 66.7 4.67
1800 19.1 17.6 3.34 23.7 21.8 3.47 28.5 26.0 3.60 34.0 30.2 3.75 40.3 36.6 3.91 47.8 47.8 4.11 56.7 56.7 4.34 67.3 67.3 4.64
1400 18.5 17.1 3.41 23.0 21.1 3.54 27.7 25.3 3.70 33.1 29.4 3.87 39.3 35.7 4.07 46.4 46.4 4.29 55.3 55.3 4.59 65.3 65.3 4.93
70 1600 18.8 17.3 3.43 23.3 21.4 3.56 28.0 25.5 3.71 33.4 29.7 3.87 39.6 36.0 4.05 47.0 47.0 4.27 55.7 55.7 4.53 65.9 65.9 4.85
1800 19.0 17.4 3.47 23.5 21.6 3.60 28.3 25.8 3.74 33.7 30.0 3.89 39.9 36.3 4.06 47.3 47.3 4.26 56.3 56.3 4.51 66.7 66.7 4.82
1400 18.5 17.0 3.57 22.8 21.0 3.68 27.6 25.2 3.85 32.9 29.2 4.02 38.9 35.4 4.23 46.1 46.1 4.47 54.6 54.6 4.76 64.6 64.6 5.12
75 1600 18.7 17.2 3.59 23.1 21.2 3.70 27.8 25.4 3.85 33.1 29.4 4.02 39.3 35.8 4.21 46.6 46.6 4.44 55.2 55.2 4.71 65.4 65.4 5.05
1800 18.9 17.4 3.62 23.3 21.4 3.73 28.1 25.6 3.88 33.4 29.7 4.03 39.6 36.1 4.22 47.0 47.0 4.43 55.7 55.7 4.69 66.0 66.0 5.01
Multipliers for Determining the Performance With Other Indoor Sections
Heating Heating
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4AS(F,B) 048 1.00 1.00 FG3ASA 048 1.00 1.03
060 0.99 0.96 060 1.00 1.02
38YCC060-90, 92 Outdoor Section With F(A,B)4AS(F,B)060 Indoor Section
1750 28.9 26.6 3.87 33.8 31.1 4.03 39.0 35.5 4.21 44.9 39.8 4.41 51.4 46.7 4.66 58.9 58.9 4.97 68.0 68.0 5.38 78.3 78.3 5.91
65 1900 29.1 26.8 3.90 34.0 31.2 4.05 39.2 35.8 4.22 45.1 40.1 4.41 51.7 47.0 4.65 59.3 59.3 4.95 68.4 68.4 5.35 79.2 79.2 5.87
2000 29.2 26.9 3.92 34.1 31.4 4.07 39.4 35.9 4.23 45.3 40.2 4.42 51.8 47.2 4.65 59.5 59.5 4.95 68.7 68.7 5.34 79.1 79.1 5.86
2150 29.5 27.1 3.95 34.3 31.5 4.10 39.6 36.1 4.25 45.5 40.4 4.44 52.1 47.4 4.66 59.8 59.8 4.95 69.0 69.0 5.34 79.5 79.5 5.85
1750 28.7 26.4 4.06 33.7 31.0 4.25 38.8 35.4 4.43 44.7 39.7 4.65 51.1 46.5 4.90 58.6 58.6 5.22 67.5 67.5 5.64 77.6 77.6 6.17
70 1900 28.9 26.6 4.09 33.9 31.2 4.26 39.1 35.6 4.44 45.0 39.9 4.64 51.4 46.8 4.89 59.0 59.0 5.20 67.9 67.9 5.60 78.1 78.1 6.13
2000 29.0 26.7 4.11 34.1 31.3 4.28 39.2 35.7 4.45 45.1 40.1 4.65 51.6 46.9 4.89 59.2 59.2 5.19 68.2 68.2 5.59 78.4 78.4 6.11
2150 29.3 26.9 4.14 34.3 31.5 4.30 39.4 35.9 4.47 45.4 40.3 4.66 51.8 47.2 4.89 59.5 59.5 5.19 68.5 68.5 5.59 78.8 78.8 6.10
1750 28.4 26.1 4.26 33.6 30.9 4.47 38.8 35.3 4.66 44.5 39.5 4.89 50.8 46.3 5.15 58.2 58.2 5.48 67.0 67.0 5.92 77.0 77.0 6.47
75 1900 28.6 26.3 4.28 33.8 31.1 4.48 39.0 35.6 4.67 44.8 39.8 4.88 51.1 46.5 5.14 58.5 58.5 5.45 67.4 67.4 5.87 77.5 77.5 6.41
2000 28.8 26.5 4.30 34.0 31.2 4.50 39.1 35.7 4.68 44.9 39.9 4.89 51.3 46.7 5.13 58.7 58.7 5.44 67.6 67.6 5.85 77.8 77.8 6.39
2150 29.0 26.7 4.34 34.2 31.4 4.52 39.4 35.9 4.69 45.1 40.1 4.89 51.5 46.9 5.13 59.0 59.0 5.44 68.0 68.0 5.84 78.2 78.2 6.37
Multipliers for Determining the Performance With Other Indoor Sections
Heating Heating
Indoor Indoor
Section Size Capacity Power Section Size Capacity Power
F(A,B)4AS(F,B) 060 1.00 1.00 FG3ASA 060 0.99 1.03
FB4ASB 070 0.99 0.95 — — —
* The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these
values to obtain total system kilowatts.
† The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from sup-
plement heaters should be added to those values to obtain total system capacity.
EDB — Entering Dry Bulb

20
Downloaded from www.Manualslib.com manuals search engine
System Design
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than
0.01-in. wg.
2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).
3. Maximum outdoor operating air temperature for cooling mode is 125°F (51.7°C), except for some 3 phase models it is 115°F
(46.7°C).
4. Minimum outdoor operating air temperature for heating mode is –30°F (–34.4°C).
5. Maximum outdoor operating air temperature for heating mode is 66°F (18.9°C).
6. For reliable operation, unit should be level in all horizontal planes.
7. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft (15.24m), indoor coil below
= 150 ft (45.72m). (See items 8 and 9 following.)
8. For interconnecting refrigerant tube lengths greater than 50 ft (15.24m), consult Residential Split System Long-Line Application
Guideline available from equipment distributor.
9. Not more than 36 in. (912mm) of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk,
provide a minimum 6-in. (152mm) vertical rise to the valve connections at the unit. For buried refrigerant tube lengths, between
3 and 100 ft (0.914 and 30.5m) consult Residential Split System Buried Line Application Guideline.
10. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector
provided.
11. Mixmatches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort.

21
Downloaded from www.Manualslib.com manuals search engine
Guide specifications Air-Cooled, Split-System
Heat Pump
38YCC
2 To 5 Tons Nominal
(7 To 17.5 Kw)
GENERAL Condenser fan motors will be totally enclosed, 1-phase type
with class B insulation and permanently lubricated bearings.
System Description Shafts will be corrosion resistant.
Outdoor-mounted, air-cooled, split-system heat pump unit Fan blades will be statically and dynamically balanced.
suitable for ground or rooftop installation. Unit consists of a Condenser fan openings will be equipped with
hermetic compressor, an air-cooled coil, propeller-type PVC-coated steel wire safety guards.
condenser fan, and a control box. Unit will discharge supply air Compressor
upward as shown on contract drawings. Unit will be used in a Compressor will be hermetically sealed.
refrigeration circuit to match up to a packaged fan coil or coil Compressor will be mounted on rubber vibration isolators.
unit.
Condenser Coil
Quality Assurance Condenser coil will be air cooled.
Unit shall be manufactured in a facility registered to ISO9001/ Coil will be constructed of aluminum fins mechanically
BS5750 Part II, International Standard for Quality Systems. bonded to copper tubes which are then cleaned, dehydrated, and
Unit will be rated in accordance with the latest edition of ARI sealed.
Standard 240. Refrigeration Components
Unit construction will comply with latest edition of ANSI/ Refrigeration circuit components will include liquid line
ASHRAE and with NEC (U.S.A. Standard). shutoff valve with sweat connections, suction shutoff valves with
Unit will be constructed in accordance with UL standards. sweat connections, system charge of refrigerant R-22,
Unit cabinet will be capable of withstanding Federal Test compressor oil, accumulator, and reversing valve.
Method Standard No. 141 (Method 6061) 500-hr salt spray test
(U.S.A. Standard). Operating Characteristics
Air-cooled condenser coils will be leak tested at The capacity of the unit will meet or exceed ____ Btuh
150 psig (1034 KPa) and pressure tested at 300 psig (____ kw) at a suction temperature of ____ F (____ C). The
(2068 KPa). power consumption at full load will not exceed ____ kw.
Delivery, Storage, and Handling Combination of the unit and the evaporator or fan coil unit will
have a total net cooling capacity of ____ Btuh (____ kw) or
Unit will be shipped as single package only and is stored and greater at conditions of ____ CFM (____ L/S) entering air
handled per unit manufacturer’s recommendations. temperature at the evaporator at ____ F (____ C) wet bulb
and ____ F (____ C) dry bulb, and air entering the unit
PRODUCTS at ____ F (____ C).
Equipment Electrical Requirements
Factory-assembled, single piece, air-cooled heat pump unit. Nominal unit electrical characteristics will be ____ v,
Contained within the unit enclosure will be all factory wiring, 1 phase, 50 hertz. The unit will be capable of satisfactory
piping, controls, compressor, refrigerant charge (R-22), and operation within voltage limits of ____ v to ____ v.
special features required prior to field start-up. Unit electrical power will be single point connection.
Unit Cabinet Control circuit will be 24v.
Unit cabinet will be constructed of galvanized steel, Special Features
bonderized, and coated with a powder coat paint. Refer to section of this literature identifying accessories and
Fans descriptions for specific features and available enhancements.
Condenser fan will be direct-drive propeller type, discharging
air upward.

22
Downloaded from www.Manualslib.com manuals search engine
23
Downloaded from www.Manualslib.com manuals search engine
SERVICE TRAINING

Packaged Service Training programs are an excellent way to increase your


knowledge of the equipment discussed in this manual, including:
• Unit Familiarization • Maintenance
• Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs is available, using popular
video-based formats and materials. All include video and/or slides, plus companion
book.

Classroom Service Training plus "hands-on" the products in our labs can mean
increased confidence that really pays dividends in faster troubleshooting, fewer
callbacks. Course descriptions and schedules are in our catalog.

CALL FOR FREE CATALOG 1-800-962-9212

[ ] Packaged Service Training [ ] Classroom Service Training


A94328

Carrier Corporation • Indianapolis, IN 46231 6-97


Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Page 24 Catalog No. 013-819 Printed in U.S.A. PC 101 Form 38YCC-C1PD
Tab 5a 5a Replaces: 38YCB-C2PD