Chapter4
Chapter4
Outside Radius
Inside Radius
Branch
VP2
VP3
VP1
Main
Duct
Zeta factor = 0.67
Examples of Zeta Factors
Straight Through’
To Branch 1 to 3
1 to 2 Branch
Velocity Velocity
Zeta Zeta
pressure pressure VP2
factor factor
ratio ratio VP3
(z) (z)
VP2/VP1 VP3/VP1
0.6 0.44 0.6 1.60
0.8 0.09 0.8 0.78 VP1
Main Duct
1.0 0.04 1.0 0.55
1.2 0.02 1.2 0.45
Examples of Zeta Factors
3. Tapered Reduction
12 metres Bend –
Air flow rate 1.5 Radiused on
m3/s inside and
outside
Duct Sizing Table
1 2 3 4 5 6 7 8 9 10 11 12
Press Pressure Loss Cumula
ure Total
Leng Flow Fittings tive
drop Duct Velocity Pressu
Sectio th Rate Velocity pressure loss Fitting Straig Pressur
per Size Pressure ht re
n (m3/s (m/s) factor or s e
metre (mm) (Pa) Duct Loss
(m) ) z (zeta) factor (Pa) Loss
(Pa/m (Pa) (Pa)
(Pa)
)
A 12 1.5 1.0 0.51 metres Vel = VP = 0.5 x 1 . 30.6 x 12 x 20.5
dia. vol/CSA 1.2 x 7.142 z factor = 0.67 0.67 1.0 +
CSA = 0.204 = 1.5 / 0.7 x = 30.6 Pa from 12.0
m2 0.3 (EXAMPLES = 20.5
Rectangular = 7.14 m/s OF z zeta = 32.5
Width = 0.204 / FACTORS) = 12.0 = 32.5
0.3
= 0.681 m TOTAL z
say duct size factor = 0.67
is;
700mm x 300
mm high
Pressure Drop Calculation Table
Duct Sizing Table
1 2 3 4 5 6 7 8 9 10 11 12
Pressu Pressure Loss
Velocit Fittings Cumulat
Leng Flow re Total
Duct Velocit y pressure loss ive
th Rate drop Straight Pressu
Section Size y Pressur factor or Fittings Pressure
(m3/s per Duct re Loss
(mm) (m/s) e z (zeta) (Pa) Loss
(m) ) metre (Pa) (Pa)
(Pa) factor (Pa)
(Pa/m)
NOTES ON DUCT PRESSURE DROP CALCULATION
NOTES:
1. Divide the system into sections. A section is from one branch
to another or in parts of the system with a steady volume flow
rate.
2. Size the index circuit first, that is the circuit with the highest
resistance to air flow. Normally the index circuit is the longest
circuit, but not always so check if necessary.
Outlet Diffuser
– Pressure D
loss or
z factor = 3.5
Branch A Sizing as Main Duct
Branch B Sizing as Main Duct
Branch C Sizing as Main Duct
Branch D Sizing as Main Duct
EXAMPLE CAFETERIA OF DUCT PRESSURE DROP CALCULATION
Air Flow
Length
Section Rate
(m)
(m3/s)
A 1.20 10
B 0.90 3
C 0.60 6
D 0.30 8
NOTES:
1. Keep one side 350 mm high.
2. Ductwork to be rectangular galvanised steel.
3. There are no additional pressure losses.
4. Tapered reductions are at 45 degrees.
DUCT PRESSURE DROP CALCULATION
The velocity for the main ducts, section A,B,C do not exceed 9
m/s from the Table.
The velocity for the branch duct, section D also does not
exceed the value of 6 m/s from the Table
The fan should be capable of delivering 1.2 m3/s against a
pressure of 305 Pa.
A percentage addition may be added to these figures for a design
margin
DUCT INTAKE AND DISHARGE LOCATION