SL Navy
SL Navy
Author
Project: holiday piligrim SL NAVY Katharagama
Variant: New simulation variant
PVsyst V7.3.1
VC0, Simulation date:
29/04/24 22:04
with v7.3.1
Project summary
Geographical Site Situation Project settings
Kataragama Latitude 6.41 °N Albedo 0.20
Sri Lanka Longitude 81.34 °E
Altitude 42 m
Time zone UTC+5.5
Meteo data
Kataragama
Meteonorm 8.1, Sat=100% - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
System information
PV Array Inverters
Nb. of modules 148 units Nb. of units 2 units
Pnom total 84.3 kWp Pnom total 80.0 kWac
Pnom ratio 1.054
Results summary
Produced Energy 114876 kWh/year Specific production 1362 kWh/kWp/year Perf. Ratio PR 78.13 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 5
Loss diagram 6
Predef. graphs 7
Single-line diagram 8
PVsyst V7.3.1
VC0, Simulation date:
29/04/24 22:04
with v7.3.1
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 20 / -160 ° Diffuse Perez, Meteonorm
Circumsolar separate
PV Array Characteristics
Array #1 - PV Array
PV module Inverter
Manufacturer JA Solar Manufacturer Sunways
Model JAM72-S30-550-MR Model STT-30KTL
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 550 Wp Unit Nom. Power 30.0 kWac
Number of PV modules 64 units Number of inverters 4 * MPPT 25% 1 unit
Nominal (STC) 35.2 kWp Total power 30.0 kWac
Modules 4 Strings x 16 In series Operating voltage 180-1000 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.17
Pmpp 32.3 kWp No Power sharing between MPPTs
U mpp 608 V
I mpp 53 A
Array #2 - Sub-array #2
PV module Inverter
Manufacturer Jinkosolar Manufacturer Sunways
Model JKM585M-7RL4-V Model STT-50KTL-P
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 585 Wp Unit Nom. Power 50.0 kWac
Number of PV modules 84 units Number of inverters 1 unit
Nominal (STC) 49.1 kWp Total power 50.0 kWac
Modules 6 Strings x 14 In series Operating voltage 160-1000 V
At operating cond. (50°C) Pnom ratio (DC:AC) 0.98
Pmpp 44.8 kWp Power sharing within this inverter
U mpp 564 V
I mpp 80 A
Array losses
Array Soiling Losses Thermal Loss factor Module Quality Loss
Loss Fraction 6.0 % Module temperature according to irradiance Loss Fraction -0.8 %
Uc (const) 20.0 W/m²K
Uv (wind) 0.0 W/m²K/m/s
PVsyst V7.3.1
VC0, Simulation date:
29/04/24 22:04
with v7.3.1
Array losses
IAM loss factor - Array #1
Incidence effect (IAM): User defined profile
DC wiring losses
Global wiring resistance 10 mΩ
Loss Fraction 1.5 % at STC
System losses
Unavailability of the system Auxiliaries loss
Time fraction 2.0 % constant (fans) 1W
7.3 days, 1.0 kW from Power thresh.
3 periods Night aux. cons. 60 W
PVsyst V7.3.1
VC0, Simulation date:
29/04/24 22:04
with v7.3.1
Main results
System Production
Produced Energy 114876 kWh/year Specific production 1362 kWh/kWp/year
Performance Ratio PR 78.13 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.3.1
VC0, Simulation date:
29/04/24 22:04
with v7.3.1
Loss diagram
1849 kWh/m² Global horizontal irradiation
PVsyst V7.3.1
VC0, Simulation date:
29/04/24 22:04
with v7.3.1
Predef. graphs
Daily Input/Output diagram