Hb Ac1 Dp v1 Edd En
Hb Ac1 Dp v1 Edd En
.
Reference documents:
Manual (operation and setting) AUMATIC AC 01.1/ACExC 01.1 with Profibus DP.
Can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA (addresses see page )
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2. Prior to installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1. AUMA scope of delivery 4
2.2. AUMATIC EDD functional overview 4
2.3. Prerequisites for the device integration with AUMATIC EDD 4
7. Appendix A: Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2
Actuator controls AUMATIC AC 01.1/ACExC 01.1
Manual EDD (Electronic Device Description) for Simatic PDM (Process Device Manager)
1. Introduction
Process data DP-V0 The field devices used in the industrial process automation today have,
Extended functions DP-V1 aside from the compulsory main functions, a variety of more detailed appli-
cation functions to adapt their performance optimally to the process require-
ments. In addition to this, most field devices have even more functions and
methods to diagnose their own field device status. When using open, inter-
nationally standardised fieldbus systems such as Profibus DP-V1, access to
these device-specific application and diagnosis functions is made through
the same fieldbus cables which are also used for the process data
exchange between field device and control system. Beside the cyclic
process data exchange via Profibus DP-V0, an additional acyclic communi-
cation via Profibus DP-V1 can hereby be established, without additional
wiring. It serves for adapting parameters of the application functions or read-
ing out status and diagnostic data during operation.
..
By means of the optional acyclic Profibus DP-V1 services, the actuator
controls AUMATIC offers access to
.
User function parameters for adapting to process requirements
Data within the electronic name plate for detailed device identification
Operational data for preventive maintenance
Furthermore, the current device status may be transmitted for diagnosis
purpose.
Access The device access for all connected field devices is thereby made via a
central operation and monitoring station, located e.g. in the control room.
Simatic PDM In Siemens control systems Simatic PDM (Process Device Manager) is
generally used as operation and monitoring software for all connected field
devices. Such tools are also called EDD Interpreter as they interpret and
visualise the EDD.
Device integration with EDD An EDD (Electronic Device Description) is an instrument-specific electronic
description required to integrate a field device of a manufacturer into the
Simatic PDM operation and monitoring software.
The EDD for the actuator controls AUMATIC is available for free download
on the Internet, at www.auma.com.
The EDD frees the user from having to worry about the details regarding the
Profibus DP-V1 communication, but allows to use the device-specific appli-
cation and diagnosis functions immediately after having installed and
assigned the device address.
The present document describes the handling of the EDD on the basis of
the Simatic PDM.
3
Actuator controls AUMATIC AC 01.1/ACExC 01.1
EDD (Electronic Device Description) for Simatic PDM (Process Device Manager) Manual
2. Prior to installation
2.1. AUMA scope of delivery
AUMATIC.bmp BMP graphics for representation of the AUMA actuator within the Simatic
Step7 user interface
AUMA05CD.gsd GSD file for commissioning AUMA actuators with AUMATIC actuator
controls and a Profibus DP class 1 master
ACEDD.devices Devices file for installing AUMA actuators with AUMATIC actuator controls in
Simatic PDM
hb_ac1_dp_v1_edd_de.pdf Manual AUMATIC device description EDD for Simatic PDM in German
hb_ac1_dp_v1_edd_en.pdf Manual AUMATIC device description EDD for Simatic PDM in English
..
The AUMATIC EDD provides the following features:
Reading and writing AUMATIC parameters.
.
Reading and writing the electronic name plate for detailed identification
of the AUMATIC.
..
Reading and clearing the operating data for diagnosis and preventive
maintenance.
Online diagnosis regarding the current AUMATIC status.
Trend functions for current torque, actual position, setpoint, as well as the
current operation status.
Controls AUMATIC
.The following software versions/functions must be installed:
AUMATIC logic software Z031.922/10-xx or later, refer to AUMATIC dis-
play, diagnosis indication D6: LOGIC SW-VERSION.
If the AUMATIC EDD is operated in combination with an AUMATIC
equipped with an older logic software (e.g. Z031.922/05-04 or later, or
.
Z031.922/08-xx), the functionality available is somewhat restricted (no
online transfer of status or diagnosis information, no trend function).
AUMATIC Profibus DP-V1 software Z031.320/02-00 or later, refer to
.
AUMATIC display, diagnosis indication DD:DP1 SW-VERSION (for
Profibus DP redundancy additionally DH: DP2 SW-VERSION).
The Profibus DP-V1 function has to be activated within the AUMATIC,
refer to AUMATIC display, menu indication M0009: MAIN MENU >
CONFIGURATION > SPECIAL FUNCTIONS > VIEW >
DP-V1 SERVICES = FUNCTION ACTIVE.
Computer
..
The following programs/hardware must be installed:
Simatic PDM V6.0 (operation and monitoring software)
Interface card, e.g. Siemens PCMCIA CP5511 or CP5512
4
Actuator controls AUMATIC AC 01.1/ACExC 01.1
Manual EDD (Electronic Device Description) for Simatic PDM (Process Device Manager)
The AUMATIC EDD installation package is just copied on the PC hard disk
and then integrated into the device catalogue of the Simatic manager
(please refer to the description below).
1. Open device catalogue: Options > Simatic PDM > Manage Device
Catalog... menu command.
2. Select the folder containing the AUMATIC EDD file: Click Browse... but-
ton and select ACEDD.devices file.
The selected folder is displayed in the Source: field.
3. Select device(s) by checking the respective box.
Figure 1
5
Actuator controls AUMATIC AC 01.1/ACExC 01.1
EDD (Electronic Device Description) for Simatic PDM (Process Device Manager) Manual
2. Enter the device address of the AUMATIC connected into the Address
field.
Note You may request the device address at the AUMATIC local controls display
as follows:
Note The device address may be changed at a later date in the Object Proper-
ties dialogue box of the Connection tab.
6
Actuator controls AUMATIC AC 01.1/ACExC 01.1
Manual EDD (Electronic Device Description) for Simatic PDM (Process Device Manager)
3. Select device type from device catalogue using the Assign... button.
7
Actuator controls AUMATIC AC 01.1/ACExC 01.1
EDD (Electronic Device Description) for Simatic PDM (Process Device Manager) Manual
Maintenance engineer A maintenance engineer can only read the information given by the
AUMATIC actuator controls.
Specialist A Specialist can read all data stored in the AUMATIC actuator controls like
the Maintenance engineer and write most data. A password can be
assigned to “specialists” via Simatic PDM.
Note If the device has never been used in combination with Simatic PDM, the
Simatic PDM device catalogue is displayed (see above).
8
Actuator controls AUMATIC AC 01.1/ACExC 01.1
Manual EDD (Electronic Device Description) for Simatic PDM (Process Device Manager)
Before reading data from or writing data into the AUMATIC, you have to
establish a connection to the device.
Note Some information of the AUMATIC actuator controls are connected with
optional functions and features and can only be read via Profibus DP-V1
and displayed in Simatic PDM if these functions are available in the
AUMATIC actuator controls (e.g. parameters of a possibly available redun-
dant Profibus DP or conventional interface).
Since the device description always starts with a minimal representation of
the parameters, we recommend that prior to a writing process, the available
configuration of the AUMATIC is read out using a single reading process via
Profibus DP-V1. Thus the currently available parameter options are taken
over into Simatic PDM.
If the version of the AUMATIC has changed between two reading processes
(e.g. modification or update of the logic software), the AUMATIC data should
be read twice when first establishing communication with Simatic PDM.
9
Actuator controls AUMATIC AC 01.1/ACExC 01.1
EDD (Electronic Device Description) for Simatic PDM (Process Device Manager) Manual
Note Only parameter values which are within the stated minimum and maximum
values are permitted. The permissible minimum and maximum values can
be displayed via the context menu (right mouse button) after a parameter
has been selected. Additionally, the default values are also displayed in this
context menu and a short explanation for each parameter can be found
under “Help”.
10
Actuator controls AUMATIC AC 01.1/ACExC 01.1
Manual EDD (Electronic Device Description) for Simatic PDM (Process Device Manager)
The Device selection in the toolbar enables access to further Simatic PDM
functions.
6.4.1 Trend
Note This function is only available if the connection to the device is active.
This function (Device > Trend) opens the trend view of the dynamic device
values. The following data can be logged as trend:
Further notes Negative torque values correspond to a torque in direction CLOSE, positive
values correspond to a torque in direction OPEN. Only those torque values
are displayed in the Simatic PDM which are higher than a certain actua-
tor-specific basic load (typically approx. 40 – 50 % of the nominal actuator
torque).
The status information contains binary data on the current operation status.
Table 1
Value Signification
1 Actuator runs in direction OPEN
2 Actuator runs in direction CLOSE
3 Actuator is in end position OPEN
4 Actuator is in end position CLOSED
5 Actuator is in desired Setpoint E1
Figure 6
11
Actuator controls AUMATIC AC 01.1/ACExC 01.1
EDD (Electronic Device Description) for Simatic PDM (Process Device Manager) Manual
The resettable operational data can either be deleted individually within the
“Operational data” parameter group or all resettable operational data can
be deleted at once via a menu command in the menu bar (Simatic PDM
menu bar: Device > Reset all operational data)
12
Actuator controls AUMATIC AC 01.1/ACExC 01.1
Manual EDD (Electronic Device Description) for Simatic PDM (Process Device Manager)
6.4.3 General
7. Appendix A: Literature
.
Volume 2: EDDL Specification, Release ½001, Version: 1.1
Order No. 2.152, www.profibus.com
..
EDDL Electronic Device Description Language,
Oldenbourg Verlag [publisher] ISBN 3-486-27034-6
Siemens AG, Simatic PDM https://pcs.khe.siemens.com/pdm_en
Operation instructions actuator controls AUMATIC AC 01.1 Profibus DP,
www.auma.com
13
AUMA worldwide
14
AUMA ACTUATORS (Singapore) Pte Ltd. Al-Arfaj Engineering Co WLL Australia
SG-569551 Singapore KW-22004 Salmiyah
Tel +65 6 4818750 Tel +965 481-7448 BARRON GJM Pty. Ltd.
Fax +65 6 4818269 Fax +965 481-7442 AU-NSW 1570 Artarmon
[email protected] [email protected] Tel +61 294361088
www.auma.com.sg www.arfajengg.com Fax +61 294393413
[email protected]
Al Ayman Industrial. Eqpts Petrogulf W.L.L www.barron.com.au
AE- Dubai QA- Doha
Tel +971 4 3682720 Tel +974 4350 151
Fax +971 4 3682721 Fax +974 4350 140
[email protected] [email protected]
PERFECT CONTROLS Ltd. Sunny Valves and Intertrade Corp. Ltd.
HK- Tsuen Wan, Kowloon TH-10120 Yannawa Bangkok
Tel +852 2493 7726 Tel +66 2 2400656
Fax +852 2416 3763 Fax +66 2 2401095
[email protected] [email protected]
www.sunnyvalves.co.th/
DW Controls Co., Ltd.
KR-153-803 Seoul Korea Top Advance Enterprises Ltd.
Tel +82 2 2113 1100 TW- Jhonghe City Taipei Hsien (235)
Fax +82 2 2113 1088/1089 Tel +886 2 2225 1718
[email protected] Fax +886 2 8228 1975
www.actuatorbank.com [email protected]
www.auma-taiwan.com.tw
2007-02-21
15