0% found this document useful (0 votes)
8 views60 pages

Potterton Promax Combi He Plus Install

The document provides installation and service instructions for the Potterton Promax Combi HE Plus LPG condensing combination boiler, including compliance with building regulations and safety guidelines. It emphasizes the importance of using a competent installer and completing the Benchmark Commissioning Checklist. Additionally, it includes safety handling procedures and a detailed layout of the boiler's components.

Uploaded by

richard.brignull
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views60 pages

Potterton Promax Combi He Plus Install

The document provides installation and service instructions for the Potterton Promax Combi HE Plus LPG condensing combination boiler, including compliance with building regulations and safety guidelines. It emphasizes the importance of using a competent installer and completing the Benchmark Commissioning Checklist. Additionally, it includes safety handling procedures and a detailed layout of the boiler's components.

Uploaded by

richard.brignull
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 60

You can rely on

Installation & Service Instructions Promax Combi


HE Plus LPG
Condensing
Combination Boiler

These instructions include the Benchmark Commissioning


Checklist and should be left with the user for safe keeping.

© Baxi Heating UK Ltd 2008


Propane Building Regulations and the Benchmark Commissioning
Checklist
Potterton Promax Combi 24 HE Plus LPG
G.C.No 47 393 24
Building Regulations (England & Wales) require notification of
the installation of a heating appliance to the relevant Local
Authority Building Control Department. From 1 April 2005 this
can be achieved via a Competent Persons Self Certification
Scheme as an option to notifying the Local Authority directly.
Similar arrangements will follow for Scotland and will apply in
Northern Ireland from 1 January 2006.

CORGI operate a Self Certification Scheme for gas heating


appliances.

These arrangements represent a change from the situation


whereby compliance with Building Regulations was accepted as
being demonstrated by completion of the Benchmark Logbook
(which was then left on site with the customer).

With the introduction of Self Certification Schemes, the


Benchmark Logbook is being withdrawn. However, a similar
document in the form of a commissioning checklist and service
interval record is incorporated at the back of these instructions.

This company is a member of the Benchmark initiative and fully


supports the aims of the programme. Its aim is to improve the
standards of installation and commissioning of central heating
systems in the UK and to encourage the regular servicing of all
central heating systems to ensure safety and efficiency.

Building Regulations require that installations should comply


with manufacturer's instructions. It is therefore important that
the commissioning checklist is completed by the installer. The
relevant section of Building Regulations only relates to
dwellings. Therefore the checklist only applies if the appliance is
being installed in a dwelling or some related structure.
© Baxi Heating UK Ltd 2008 All rights reserved. No part of this publication may
be reproduced or transmitted in any form or by any means, or stored in any The flowchart opposite gives guidance for installers on the
retrieval system of any nature (including in any database), in each case whether process necessary to ensure compliance with Building
electronic, mechanical, recording or otherwise, without the prior written
permission of the copyright owner, except for permitted fair dealing under Regulations.
Copyrights, Designs and Patents Act 1988.

Applications for the copyright owner’s permission to reproduce or make other


use of any part of this publication should be made, giving details of the proposed
use, to the following address:

The Company Secretary, Baxi Heating UK Ltd, The Wyvern Business Park,
Stanier Way, Derby, DE21 6BF.

Full acknowledgement of author and source must be given.

WARNING: Any person who does any unauthorised act in relation to a


copyright work may be liable to criminal prosecution and civil claims for damages.

“Potterton” supports

Baxi Heating UK Ltd is a


BS-EN ISO 9001 Accredited Company
The code of practice for the installation,
This product has an energy rating (A) on a scale of A to G. commissioning & servicing of central
heating systems.
For more information see www.boilers.org.uk. This is a certification mark.

2 © Baxi Heating UK Ltd 2008


Installer Notification Guidelines

Choose Building
Regulations Notification
Route

Competent Person's Building Control


Self Certification Scheme

Install and Commission this Contact your relevant Local


appliance to manufacturer's Authority Building Control
instructions (LABC) who will arrange
an inspection or contact
a government approved
inspector
Complete the
Benchmark Checklist

If you notify via CORGI Scheme,


CORGI will then notify the
relevant Local Authority Install and Commission this
Building Control Scheme appliance to manufacturer's
on member's behalf instructions

Scheme Members only


Complete the
Call CORGI on: 0800 408 1007 Benchmark Checklist
or log onto:
www.corgi-notify.com
within 10 days

You must ensure that the


notification number issued by
CORGI is written onto the
Benchmark Checklist

CORGI will record the data and LABC will record the data
will send a certificate of and will issue a
compliance to the property certificate of compliance

© Baxi Heating UK Ltd 2008 3


Legislation
IMPORTANT - Installation, Commissioning, Service & Repair
This company declare that no substances harmful to health
are contained in the appliance or used during appliance
This appliance must be installed in accordance with the manufacturer’s instructions and
manufacture.
the regulations in force. Read the instructions fully before installing or using the
appliance. The appliance is suitable only for installation in GB and IE and
should be installed in accordance with the rules in force, and
In GB, this must be carried out by a competent person as stated in the Gas Safety only used in a suitably ventilated location.
(Installation & Use) Regulations.
In GB, the installation must be carried out by a CORGI
Registered Installer. It must be carried out in accordance with
Definition of competence: A person who works for a CORGI registered company and the relevant requirements of the:
holding current certificates in the relevant ACS modules, is deemed competent. • Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The Building
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic Regulations, The Building Regulations (Scotland), Building
Regulations (Northern Ireland).
Gas Installations”.
• The Water Fittings Regulations or Water Byelaws in
Scotland.
The addition of anything that may interfere with the normal operation of the appliance • The Current I.E.E. Wiring Regulations.
without express written permission from the manufacturer or his agent could invalidate
the appliance warranty. In GB this could also infringe the Gas Safety (Installation and Where no specific instructions are given, reference should be
made to the relevant British Standard Code of Practice.
Use) Regulations.
In IE, the installation must be carried out by a competent
Warning - Check the information on the data plate is compatible with local supply Person and installed in accordance with the current edition of
conditions. I.S. 813 ‘Domestic Gas Installations’, the current Building
Regulations and reference should be made to the current ETCI
rules for electrical installation.
All CORGI registered installers carry a CORGI identification card and have a
All systems must be thoroughly flushed and treated with
registration number. You can check your installer is registered by telephoning
inhibitor (see section 6.2).
0800 915 0485 or writing to:-
1 Elmwood,
Chineham Park,
Crockford Lane,
Basingstoke. RG24 8WG

Codes of Practice - refer to the most recent version


or check online at www.trustcorgi.com

In GB the following Codes of Practice apply:


Standard Scope
BS 5482 Part 1 Gas Installation.
BS 5546 Installation of hot water supplies for domestic
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency) purposes.
Regulations 1993 No 3083” and is deemed to meet the requirements of Directive BS 5449 Forced circulation hot water systems.
BS 6798 Installation of gas fired hot water boilers.
92/42/EEC on the energy efficiency requirements for new hot water boilers fired with BS 5440 Part 1 Flues.
liquid or gaseous fuels:- BS 5440 Part 2 Ventilation.
BS 7074 Expansion vessels and ancillary equipment for
sealed water systems.
Type test for purpose of Regulation 5 certified by: BS 7593 Treatment of water in domestic hot water
central heating systems.
Notified Body 0085.
In IE the following Codes of Practice apply:
Standard Scope
Product/Production certified by: I.S. 813 Domestic Gas Installations.
Notified Bodies 0086. The following standards give valuable additional information;
BS 5546 Installation of hot water supplies for domestic
purposes.
BS 5449 Forced circulation hot water systems.
BS 7074 Expansion vessels and ancillary equipment for
For GB/IE only. sealed water systems.
BS 7593 Treatment of water in domestic hot water
central heating systems.

4 © Baxi Heating UK Ltd 2008


Safe Manual Handling

General

The following advice should be adhered to, from when first handling the boiler to the final stages of installation, and also during maintenance.

Most injuries as a result of inappropriate handling and lifting are to the back, but all other parts of the body are vulnerable, particularly shoulders, arms and hands.
Health & Safety is the responsibility of EVERYONE.

There is no ‘safe’ limit for one man - each person has different capabilities. The boiler should be handled and lifted by TWO PEOPLE.

Do not handle or lift unless you feel physically able.

Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc.

Preparation

Co-ordinate movements - know where, and when, you are both going.

Minimise the number of times needed to move the boiler - plan ahead.

Always ensure when handling or lifting the route is clear and unobstructed. If possible avoid steps, wet or slippery surfaces, unlit areas etc. and take special care
on ladders/into lofts.

Technique

When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and
sideways and keep the load as close to your body as possible.

Where possible transport the boiler using a sack truck or other suitable trolley.

Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary. See the
‘Installation’ section of these instructions for recommended lift points.

Remember

The circumstances of each installation are different. Always asses the risks associated with handling and lifting according to the individual conditions.

If at any time when installing the boiler you feel that you may have injured yourself STOP !!
DO NOT ‘work through’ the pain - you may cause further injury.

IF IN ANY DOUBT DO NOT HANDLE OR LIFT THE BOILER - OBTAIN ADVICE OR ASSISTANCE BEFORE PROCEEDING !!

© Baxi Heating UK Ltd 2008 5


CONTENTS
Section Page

1.0 Introduction 7

2.0 General Layout 8

3.0 Appliance Operation 9

4.0 Technical Data 10

5.0 Dimensions and Fixings 11

6.0 System Details 12

7.0 Site Requirements 15

8.0 Flue Options 19

9.0 Plume Displacement 24

10.0 Installation 28

11.0 Commissioning 33

12.0 Completion 35

13.0 Servicing 36

14.0 Changing Components 38

15.0 Combustion Check 47

16.0 Electrical 48

17.0 Short Parts List 49

18.0 Fault Finding 50

19.0 Pages for Notes 56

Benchmark Checklist 58

6 © Baxi Heating UK Ltd 2008


1.0 Introduction

1.1 Description

1. The Potterton Promax Combi HE Plus LPG is a fully


automatic gas fired wall mounted condensing combination
boiler. It is room sealed and fan assisted, and will serve central
Case Front Panel heating and mains fed domestic hot water.

2. The boiler is set to give a maximum output of :-

24 models - 24 kW DHW
21 kW CH (Condensing)

3. It is designed for use on Propane (G31).

4. The boiler is suitable for use only on fully pumped sealed


heating systems. Priority is given to domestic hot water.

5. The boiler data badge gives details of the model, serial


number and Gas Council number and is situated on the inner
door panel or the control box. It is visible when the case front
panel is removed (Fig. 1).

6. The boiler model name and serial number are also shown
on the information label on the back of the facia door. This is
for user reference.

7. The boiler is intended to be installed in residential /


commercial / light industrial E.M.C. environments on a
Control Box
governed meter supply only.

Facia Door 8. The boiler must be installed with one of the purpose
designed flues such as the standard horizontal flue kit, part no.
5118489.

Data Badge
Fig. 1 9. All systems must be thoroughly flushed and treated with
inhibitor (see section 6.2).
Information Label

1.2 Contents of Pack

1. Boiler Unit
2. Wall Plate (inc. taps)
3. Set of Pipe (inc. nuts)
4. Template
5. Quick Fit Guide
6. Literature Pack

© Baxi Heating UK Ltd 2008 7


2.0 General Layout

2.1 Layout
23
1. Expansion Vessel
1 15
2. Automatic Air Vent
3. DHW Plate Heat Exchanger
22 4. Circulation Pump
5. Drain Off Point
14 6. Pressure Relief Valve
7. Optional Integral Timer Position
13 8. Central Heating System Pressure Gauge
21 9. PCB
16 10. Control Box
11. 3-Way Valve Assembly
20
12. Condensate Trap
13. Flame Sensing Electrode
14. Spark Electrode
15. Primary Heat Exchanger
16. Fan Assembly
17. On/Off/Reset Selector Switch
18. Central Heating Temperature Control
19. Hot Water Temperature Control

10 20. Venturi

9
21. Air/Gas Collector
8
7 22. Combustion Box Cover & Burner
23. Igniter
24. Burner On Light
25. Central Heating Mode Light
26. Domestic Hot Water Mode Light

12
27. Display

11 2

4 5
6
25 26

2
Reset
1 3

0 4
bar

17 27 24 18 19 8 7
8 © Baxi Heating UK Ltd 2008
3.0 Appliance Operation

1
Central Heating Circuit 3.1 Central Heating Mode (Fig. 2)
27
1. With a demand for heating, the pump circulates water
through the primary circuit.

2 2. Once main burner ignites the fan speed controls the gas
3 4 rate to maintain the heating temperature measured by the
26 7 temperature sensor.
20
5 6 3. When the flow temperature exceeds the setting
temperature, a 3 minute delay occurs before the burner
relights automatically (anti-cycling). The pump continues to
run during this period.
25
8 4. When the demand is satisfied the burner is extinguished
24
18
and the pump continues to run for a period of 3 minutes
22 (Pump Overrun).
9
11
23
21 10
3.2 Domestic Hot Water Mode (Fig. 3)

17 1. Priority is given to the domestic hot water supply. A


demand at a tap or shower will override any central heating
16 19 15 14 13 12 requirement.

Fig. 2 2. The flow of water will operate the Hall Effect Sensor
which requests the 3 way valve to change position. This will
Key allow the pump to circulate the primary water through the
1 Primary Heat Exchanger DHW plate heat exchanger.
15 Domestic Hot Water Outlet
2 Burner
16 Heating Flow
3 Ignition Electrodes 3. The burner will light automatically and the temperature of
17 Pressure Gauge
4 Flame Sensing Electrode
5 Gas Valve
18 Water Pressure Sensor the domestic hot water is controlled by the temperature
19 Automatic By-Pass sensor.
6 Pump
20 Fan
7 Automatic Air Vent
21 Diverter Valve Assembly
8 Plate Heat Exchanger 4. When the domestic hot water demand ceases the burner
22 Diverter Valve Motor
9 Flow Sensor with Filter & Regulator
10 Pressure Relief Valve
23 Domestic Hot Water Flow Temperature Sensor will extinguish and the diverter valve will remain in the
24 Safety Thermostat domestic hot water mode, unless there is a demand for
11 Boiler Drain Point
25 Central Heating Temperature Sensor
12 Heating Return central heating.
26 Expansion Vessel
13 Cold Water Inlet On/Off Valve and Filter
27 Heat Exchanger Air Vent
14 Gas Inlet
IMPORTANT: When the selector switch is in the ‘0’
(Off) position the electrical supply to the boiler is isolated.
The boiler will not operate and the integral timer will
1 require resetting once the selector switch is set to either
Domestic Hot Water Circuit Position (i) or Position (ii).
27

3.3 Frost Protection Mode

2 1. The frost protection mode is integral to the appliance and


3 4 functions only with the selector switch (see Section 2.1) in
26 7 the domestic hot water and central heating position. If the
20 system temperature falls below 5° C then the boiler will fire
5 6 on its minimum setting until a flow temperature of 30° C is
reached. Further protection can be incorporated by using a
system frost thermostat.

25
8 3.4 Pump Protection
24
18
1. With the selector switch (see Section 2.1) in either the
22
9 central heating or central heating and domestic hot water
11 position, the pump will automatically operate for 1 minute in
23
21 10 every 24 hours to prevent sticking.

17

16 19 15 14 13 12

Fig. 3

© Baxi Heating UK Ltd 2008 9


4.0 Technical Data

4.1 Promax Combi 24 HE Plus LPG

Appliance Type C13 C33 C53 Electrical Supply 230V~ 50Hz NOx Class 5
(Appliance must be connected to an
Appliance Category CAT I I 2H3P earthed supply) Central Heating Primary Circuit
Pressures
Heat Input CH (Net) Max Min
Power Consumption bar
24 model kW 20.5 7 155W Safety Discharge 3
Max Operating 2.5
Electrical Protection
Heat Input CH (Gross) Max Min Min Operating 0.5
IPX5D
Recommended Operating Range 1-2
24 model kW 22.7 7.8
DHW Circuit bar
External Fuse Rating 3A
Heat Output CH (Non-Condensing) Pressures
Max Min Internal Fuse Rating F2L Max Operating 8
Condensate Drain Min Operating 0.15
24 model kW 20 6.8
To accept 21.5mm (3/4 in) plastic waste pipe Flow Rates 24 model
Heat Output CH (Condensing) Flue Terminal Diameter 100mm l/min
Max Min Dimensions Projection 125mm DHW Flow Rate
24 model kW 21 7.4 @ 30o C Rise 11.43
Connections copper tails DHW Flow Rate
Heat Input DHW (Net) Max Gas Supply - 22mm @ 35o C Rise 9.8
Central Heating Flow - 22mm
24 model kW 24.7 Min Working
Central Heating Return - 22mm
DHW Flow Rate 2
Cold Water Mains Inlet - 15mm
Heat Input DHW (Gross) Max DHW Flow - 15mm Pump
24 model kW 27.4 Pressure Relief Discharge - 15mm Available Head See graph below

Outercase Dimensions Expansion Vessel - (For Central Heating


Heat Output DHW Max
Casing Height - 780mm only. Integral with appliance)
24 model kW 24 Overall Height Inc Flue Elbow - 965mm bar
Casing Width - 450mm Min Pre-charge Pressure 0.5
Max Gas Rate (Propane - G31) Casing Depth - 345mm
(After 10 mins) 24 model
Clearances
24 model kg/h 1.92
Above Casing 200 mm Min Max Capacity of litre
Below Casing 200 mm Min CH System 125
Inlet Pressure (Propane - G31)
Front 450 mm Min (For Servicing) Primary Water Content
mbar 37
Front 5 mm Min (In Operation) of Boiler (unpressurised) 2.5
Injector (Propane - G31) L.H. Side 5 mm Min
7.5mm (24 model) R.H. Side 5 mm Min (In Operation) Temperatures
C.H. Flow Temp (adjustable)
Weights (kg)
25°C to 80°C max (± 5°C)
24 model
Packaged Boiler Carton 44.2
D.H.W. Flow Temp (adjustable)
Installation Lift Weight 39.2
35°C to 60°C max (± 5°C)
dependent upon flow rate

Pump - Available Head


5.5

4.5

SEDBUK Declaration 4

The efficiency is 93.2% 3.5


This value is used in the UK Government’s Standard 3
Assessment Procedure (SAP) for energy rating of
2.5
Metre (wg)

dwellings. The test data from which it has been


2
calculated has been certified by 0085.
1.5

0.5

0
0 200 400 600 800 1000 1200
10 © Baxi Heating UK Ltd 2008 Flow Rate (l/h)
5.0 Dimensions and Fixings

Dimensions

A 780mm
At Least 1.5° G E
B 345mm

C 450mm

D 116mm Ø Min.
A
E 185mm
(207mm for 80/125mm
flue systems)

F 145mm

G 131mm
B
H 180mm
360° Orientation

H
D
C

Flue Ø 100mm

F
Tap Rail

32.5 mm
Condensate
Drain

65 mm 65 mm 65 mm 65 mm 65 mm

Heating Domestic Hot Gas Cold Water Heating Pressure Relief


Flow Water Outlet Inlet Inlet Return Valve
(22mm) (15mm) (22mm) (15mm) (22mm) (15mm)

© Baxi Heating UK Ltd 2008 11


6.0 System Details

6.1 Information

1. The Promax Combi Condensing Combination Boiler is a


‘Water Byelaws Scheme - Approved Product’.
To comply with the Water Byelaws your attention is drawn to
the following installation requirements and notes (IRN).
a) IRN 001 - See text of entry for installation
requirements and notes.
b) IRN 302 - Byelaw 14.
2. Reference to the WRc publications, ‘Water fittings and
materials directory’ and ‘Water supply byelaws guide’ give full
details of byelaws and the IRNs.

6.2 Central Heating Circuit

1. The appliance is suitable for fully pumped SEALED SYSTEMS


ONLY.

Treatment of Water Circulating Systems


• All recirculatory water systems will be subject to
corrosion unless an appropriate water treatment is
applied. This means that the efficiency of the system will
deteriorate as corrosion sludge accumulates within the system,
risking damage to pump and valves, boiler noise and circulation
problems.

• When fitting new systems flux will be evident within the system,
which can lead to damage of system components.

• All systems must be thoroughly drained and flushed out. Using,


for example Betz-Dearborn Sentinel X300 or X400 or Fernox
Superfloc Universal Cleanser. They should be used following the
flushing agent manufacturer’s instructions.

• System additives - corrosion inhibitors and flushing


agents/descalers should comply to BS7593 requirements, e.g.
Betz-Dearborn Sentinel X100 and Fernox-Copal which should be
used following the inhibitor manufacturer’s instructions.

Failure to flush and add inhibitor to the system will


invalidate the appliance warranty.

• It is important to check the inhibitor concentration after


installation, system modification and at every service in
accordance with the manufacturer’s instructions. (Test kits are
available from inhibitor stockists.)

• For information or advice regarding any of the above contact


Technical Enquiries.

6.3 Bypass

1. The boiler is fitted with an automatic integral bypass.

6.4 System Control

1. The boiler is designed for use in a heating system that


incorporates external controls, i.e. a minimum of a timer
device.

2. Suitable timer kits are available as optional extras.

3. For optimum operating conditions and maximum economy


the fitting of a programmable room thermostat is
recommended.

12 © Baxi Heating UK Ltd 2008


6.0 System Details

6.5 System Filling and Pressurising (Fig. 4)

Double 1. A filling point connection on the central heating return


Stop Stop
Check pipework must be provided to facilitate initial filling and
Valve Valve
Valve pressurising and also any subsequent water loss
replacement/refilling.

2. There are connection points on the mains cold water inlet


and central heating return isolating taps (Fig. 5) to which the
DHW Temporary optional filling loop kit (Part No. 248221) can be assembled.
CH
Mains Hose
Return
Inlet
3. The filling method adopted must be in accordance with all
Fig. 4
relevant water supply regulations and use approved
equipment.

4. Your attention is drawn to:


for GB: Guidance G24.2 and recommendation R24.2 of the
Water Regulations Guide.
for IE: the current edition of I.S. 813 “Domestic Gas
Installations”.

Filling Loop 5. The sealed primary circuits may be filled or replenished by


means of a temporary connection between the circuit and a
supply pipe, provided a ‘Listed’ double check valve or some
other no less effective backflow prevention device is
permanently connected at the inlet to the circuit and the
temporary connection is removed after use.

Fig. 5
6.6 Expansion Vessel (Central Heating only)

1. The appliance expansion vessel is pre-charged to 0.5 bar.


The vessel is suitable for correct operation for system
capacities up to 125 litres. For greater system capacities an
additional expansion vessel must be fitted. For GB refer to BS
7074 Pt 1. For IE, the current edition of I.S. 813 “Domestic
Gas Installations”.

6.7 Pressure Relief Valve (Fig. 6)

1. The pressure relief valve is set at 3 bar, therefore all


pipework, fittings, etc. should be suitable for pressures in
excess of 3 bar and temperature in excess of 100°C.

2. The pressure relief discharge pipe should be not less than


15mm dia, run continuously downward, and discharge outside
the building, preferably over a drain. It should be routed in
such a manner that no hazard occurs to occupants or causes
damage to wiring or electrical components. The end of the
pipe should terminate facing down and towards the wall.

3. The discharge must not be above a window, entrance or


other public access. Consideration must be given to the
possibility that boiling water/steam could discharge from the
pipe.

Fig. 6

Pressure Relief Valve


Discharge Pipe

© Baxi Heating UK Ltd 2008 13


6.0 System Details

6.8 Domestic Hot Water Circuit (Fig. 7)

1. All DHW circuits, connections, fittings, etc. should be fully


in accordance with relevant standards and water supply
regulations.
Other Tap
Outlets
2. Your attention is drawn to:
for GB: Guidance G17 to G24 and recommendation R17 to
Expansion Boiler
R24 of the Water Regulations Guide.
Vessel
for IE: the current edition of I.S. 813 “Domestic Gas
Installations”.

3. A single check valve must be fitted as shown in Fig. 7 to


Check
Valve prevent backflow to the supply pipe and to ensure the
efficient operation of the expansion vessel which is required
to accommodate the thermal expansion of the water.

Pressure Reducer
To Hot 4. When the domestic water system includes any device
Valve
Taps which prevents water expanding back towards the supply
(check valve, loose jumpered stopcock, water meter, water
Stop Tap
treatment device) then an expansion vessel must be fitted
(eg. Zilmet 160ml, R1/2 15bar).

5. If the hot water expansion is not provided for, then high


pressures can develop which may result in damage to fittings
and devices on the system.
Fig. 7

6. The boiler’s maximum working mains pressure is 8 bar,


therefore all pipework, connections, fittings, etc. should be
suitable for pressures in excess of 8 bar. A pressure reducing
valve must be fitted for pressures in excess of 8 bar. The
manufacturer of any outlet fittings, such as a shower valve,
may require a lower maximum pressure. The pressure
reduction must take account of all fittings connected to the
DHW system.

6.9 Showers

1. If a shower control is supplied from the appliance it


should be of the thermostatic or pressure balanced type.
Thermostatic type shower valves provide the best comfort
and guard against water at too high a temperature. Existing
controls may not be suitable - refer to the shower valve
manufacturer.

6.10 Hard Water Areas

1. If the area of the installation is recognised as a HARD


WATER AREA then a suitable device should be fitted to
treat the mains water supply to the boiler. Contact your
Water Distribution Company for advice on suitable devices.

14 © Baxi Heating UK Ltd 2008


7.0 Site Requirements
5mm Min 450mm 5mm Min
7.1 Location

200mm Min 1. The boiler may be fitted to any suitable wall with the flue
(300mm Min if passing through an outside wall or roof and discharging to
using 80/125mm atmosphere in a position permitting satisfactory removal of
flueing system) combustion products and providing an adequate air supply.
The boiler should be fitted within the building unless
otherwise protected by a suitable enclosure i.e. garage or
outhouse. (The boiler may be fitted inside a cupboard-see
Section 7.3).

2. If the boiler is sited in an unheated enclosure then it is


recommended to leave the ON/OFF Selector Switch in the
domestic hot water and central heating position to give frost
protection.
780mm
3. If the boiler is fitted in a room containing a bath or shower
reference must be made to the relevant requirements.
In GB this is the current I.E.E. Wiring Regulations and Building
Regulations.
In IE reference should be made to the current edition of I.S.
813 “Domestic Gas Installations” and the current ETCI rules.

4. If the boiler is to be fitted into a building of timber frame


construction then reference must be made to the current
edition of Institute of Gas Engineers Publication IGE/UP/7
200mm Min (Gas Installations in Timber Framed Housing).
Fig. 8

5. In accordance with BS6798 LPG fuelled appliances shall not


be installed in rooms or internal spaces below ground level.

At Least 1.5° 7.2 Clearances (Figs. 8 & 9)

1. A flat vertical area is required for the installation of the


boiler.

2. These dimensions include the necessary clearances around


the boiler for case removal, spanner access and air
movement. Additional clearances may be required for the
passage of pipes around local obstructions such as joists
running parallel to the front face of the boiler.

450mm Min

For Servicing
Purposes

5mm Min

In Operation
Fig. 9

© Baxi Heating UK Ltd 2008 15


7.0 Site Requirement

Gas Service Cock


7.3 Ventilation of Compartments

1. Where the appliance is installed in a cupboard or


compartment, no air vents are required.

2. BS 5440: Part 2 refers to room sealed appliances


installed in compartments. The appliance will run sufficiently
cool without ventilation.

7.4 Gas Supply

1. The gas installation should be in accordance with the


relevant standards. In GB this is BS 5482-1. In IE this is the
current edition of I.S. 813 “Domestic Gas Installations”.
Fig. 10
2. The connection to the appliance is a 22mm copper tail
located at the rear of the gas service cock (Fig. 10).

3. Ensure that the pipework from the meter to the


appliance is of adequate size. Do not use pipes of a smaller
Zone 2 diameter than the boiler gas connection (22mm).

Window
Recess
Zone 1 7.5 Electrical Supply
Zone 2
Zone 3 1. External wiring must be correctly earthed, polarised and
Zone 0 in accordance with relevant regulations/rules. In GB this is
the current I.E.E. Wiring Regulations. In IE reference should
0.6 m
be made to the current edition of ETCI rules.
2.4 m

Window 2. The mains supply is 230V ~ 50Hz fused at 3A.


Recess
Zone 2
NOTE: The method of connection to the electricity
Zone 3 supply must facilitate complete electrical isolation of the
appliance.

Connection may be via a fused double-pole isolator


Fig. 11 with a contact separation of at least 3mm in all poles
In GB Only
and servicing the boiler and system controls only.

Ceiling 7.6 Bath & Shower Rooms

Outside Zones
1. If the boiler is fitted in a room containing a bath or
Zone 2 Zone 3
shower and NOT FITTED with any optional integral timer
Window or thermostat, it can be fitted in zone 2, (Figs. 11 & 12
Recess
Zone 2 shows zone dimensions for a bathtub. For other examples
Outside
Zones
refer to Section 601 of the Current I.E.E. Wiring
3.0 m Zone 3 Regulations) reference must be made to the relevant
Zone 1 2.25 m
Zone 2
requirements.
In GB this is the current I.E.E. Wiring Regulations and
Building Regulations.
Zone 0
In IE reference should be made to the current edition of I.S.
813 “Domestic Gas Installations” and the current ETCI
0.6 m 2.4 m rules.

Fig. 12 In GB Only

16 © Baxi Heating UK Ltd 2008


7.0 Site Requirements

Termination to an internal soil and 7.7 Condensate Drain


Boiler
vent pipe
FAILURE TO INSTALL THE CONDENSATE DISCHARGE
PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE
OPERATION OF THE BOILER
The condensate discharge pipe MUST NOT RISE at any point
50mm along its length. There MUST be a fall of AT LEAST 2.5°
per me
tre of (50mm per metre) along the entire run.
pipe ru
2.5° M n
inimum
fall 1. The condensate outlet will accept 21.5mm (3/4in) plastic
overflow pipe which should generally discharge internally into
Fig. 13 450mm min the household drainage system. If this is not possible, discharge
into an outside drain is acceptable.

2. Ensure the discharge of condensate complies with any


national or local regulations in force.
External termination via internal discharge BS 6798:2000 & Part H1 of the Building Regulations give
Boiler branch further guidance.
e.g sink waste - downstream
3. The discharge pipe should be run in a proprietary drain pipe
material e.g. PVC, PVC-U, ABS, PVC-C or PP.

50mm Pipe must terminate


per me 4. Metal pipework is NOT suitable for use in condensate
Sink tre of above water level but
pipe ru below surrounding discharge systems.
n
2.5° M surface
inimum
fall 5. The pipe should be a minimum of 21.5mm diameter and
must be supported using suitably spaced clips to prevent
sagging.

6. It is advisable to keep the condensate pipe internal.


Fig. 14
7. External runs greater than 3 metres or runs in cold areas
should use 32mm waste pipe.

Termination to a drain or gully 8. If the boiler is fitted in an unheated location the entire
condensate discharge pipe should be treated as an external
Boiler run.
Pipe must terminate above
water level but below
surrounding surface 9. In all cases discharge pipe must be installed to aid disposal
of the condensate. To reduce the risk of condensate being
trapped, as few bends and fittings as possible should be used.
50mm
per me
tre of 10. When discharging condensate into a soil stack or waste
pipe ru
2.5° M n
inimum pipe the effects of existing plumbing must be considered. If soil
fall
pipes or waste pipes are subjected to internal pressure
fluctuations when WC's are flushed or sinks emptied then
Fig. 15 back-pressure may force water out of the boiler trap and
cause appliance lockout.

Termination to a purpose made soak- Examples are shown of the following methods of termination:-
away
i) to an internal soil & vent pipe - Fig. 13
Boiler ii) via an internal discharge branch (e.g. sink waste) - Fig. 14
iii) to a drain or gully - Fig. 15
500mm min
iv) to a purpose made soakaway - Fig. 16

50mm
per me
tre of Holes in the soak-away must
pipe ru
2.5° M n face away from the building
inimum
fall

Fig. 16

© Baxi Heating UK Ltd 2008 17


Terminal Position with Minimum Distance (Fig. 18) (mm)
Aa Directly below an opening, air brick, opening
7.0 Site Requirements
windows, etc. 300
Ba Above an opening, air brick, opening window etc. 300
Ca Horizontally to an opening, air brick, opening window etc. 300 7.8 Flue
D Below gutters, soil pipes or drain pipes. 25
E Below eaves. 25 NOTE: Due to the nature of the boiler a plume of water
F Below balconies or car port roof. 25 vapour will be discharged from the flue. This should be
G From a vertical drain pipe or soil pipe. 25 taken into account when siting the flue terminal.
H From an internal or external corner. 25
I Above ground, roof or balcony level. 300
1. The following guidelines indicate the general requirements
J From a surface or boundary line facing a terminal. 600
K From a terminal facing a terminal (Horizontal flue). 1200 for siting balanced flue terminals. For GB recommendations
From a terminal facing a terminal (Vertical flue). 600 are given in BS 5440 Pt 1. For IE recommendations are given
L From an opening in carport (e.g. door, window) in the current edition of I.S. 813 “Domestic Gas
into the dwelling. 1200 Installations”.
M Vertically from a terminal on the same wall. 1500
N Horizontally from a terminal on the same wall. 300
2. If the terminal discharges onto a pathway or passageway,
R From adjacent wall to flue (vertical only). 300
check that combustion products will not cause a nuisance
S From an adjacent opening window (vertical only). 1000
T Adjacent to windows or openings on pitched and flat roofs 600 and that the terminal will not obstruct the passageway.
U Below windows or openings on pitched roofs 2000
3. If a terminal is less than 2 metres above a balcony, above
a In addition, the terminal should be no nearer than 150 mm to an
ground or above a flat roof to which people have access,
then a suitable terminal guard must be provided.
opening in the building fabric formed for the purpose of accommodating
a built-in element such as a window frame. See BS 5440 Pt. 1.
IMPORTANT:
NOTE: The distance from a fanned draught appliance terminal • Only ONE 25mm clearance is allowed per installation.
installed parallel to a boundary may not be less than 300mm in • Under car ports we recommend the use of the plume
accordance with the diagram below displacement kit.
300 min • The terminal position must ensure the safe and
Terminal
Assembly
* nuisance - free dispersal of combustion products.

Plume
Displacement Kit IMPORTANT: If fitting a Plume
Displacement Flue Kit, the air inlet
must be a minimum of 100mm from
Top View Rear Flue any opening windows or doors (see
Section 9.0).
Fig. 17

Property Boundary Line

T Air Inlet
J,K
U
Opening Window
or Door

100mm Fig. 18a


MIN.

N
R D A
M C E
I I I I
S
F B
F J,K
L A
A
G H H
I

Likely flue positions requiring Fig. 18


a flue terminal guard
18 © Baxi Heating UK Ltd 2008
8.0 Flue Options

8.1 Horizontal Flue Systems

1. The standard flue is suitable only for horizontal termination


applications.

2. All fittings should be fully engaged. The approximate


engagement is 40mm. Apply soap solution to the seal on
Y
each fitting to aid assembly.
X
3. Maximum permissible equivalent flue lengths are:-
(60/100) (80/125)
Horizontal Concentric 10 metres 20 metres

4. Any additional “in line” bends in the flue system must be


taken into consideration.
Their equivalent lengths are:-
Concentric Pipes:
135° bend 0.5 metres
Horizontal 93° bend 1.0 metres
Flues Twin Flue Pipe
135° bend 0.25 metres
91.5° bend 0.50 metres

4. The elbow connected to the boiler adaptor is not included


in any equivalent length calculations.

Plume Displacement Kit 60 /100 Ø


5. The illustrations opposite show examples of permissible
1M Extensions, 45° & 93° bends are
flue systems.
also available - see Section 9.0
NOTE: Flue length is measured from point X to Y as
shown.

NOTE: Horizontal flue pipes should always be installed with a fall of at least 1.5°
from the terminal to allow condensate to run back to the boiler.

This bend is equivalent to


1 metre

C
A
Y
B

This bend is equivalent to


1 metre
X

Total equivalent length =

A+B+C+2x90°Bends

© Baxi Heating UK Ltd 2008 19


8.0 Flue Options

Vertical
Flues 8.2 Twin & Vertical Flue Systems
(Twin Pipe)
1. Maximum permissible equivalent flue lengths are:-

(60/100) (80/125)
Vertical Concentric 10 metres 20 metres
Y Vertical Twin Pipe 15 metres

2. Any additional “in line” bends in the flue system must be


X
taken into consideration.
Their equivalent lengths are:-
Concentric Pipes:
135° bend 0.5 metres
93° bend 1.0 metres
Twin Flue Pipe
135° bend 0.25 metres
91.5° bend 0.50 metres
Vertical
Flues The elbow supplied with the standard horizontal telescopic
flue kit is not included in any equivalent length calculations

NOTE: Flue length is measured from point X to Y as


Y shown.

Total Equivalent Length =


A+B+C+1x90°Bend Roof
Terminal
All vertical and angled runs must be included,
measured from the boiler adaptor (point X) to the
joint with the flue terminal (point Y). One 91.5°
bend or two 135° bends can be included without
reduction of the flue length.

If further elbows are required the flue length must


be reduced by the following amounts:- The total equivalent length for this example is
Y = 6.5 metres.
1 metre for each 91.5° bend
0.5 metre for each 135° bend AIR DUCT
C Equivalent No of Sub total
Length Value fittings/pipes
B
1m extension 1m 5 5.0m
135°bend 0.25m 2 0.5m
91.5°bend 0.5m 2 1.0m
This bend is equivalent to Equivalent Length Air Duct = 6.5m
1 metre
FLUE DUCT
A Equivalent No of Sub total
Length Value fittings/pipes
X
1m extension 1m 5 5.0m
135°bend 0.25m 2 0.5m
91.5°bend 0.5m 2 1.0m
Equivalent Length Flue Duct = 6.5m

20 © Baxi Heating UK Ltd 2008


8.0 Flue Options

8.3 Flue Accessories


A4
Key Accessory Size Code No
FLUE GROUP A
Concentric Flue System 100mm diameter
A2 A Horizontal Flue Terminal (inc. elbow) 5118489
A
A2 Telescopic Flue (inc. elbow) 315-500mm 5118069
A3 Telescopic Internal Flue Kit 315-500mm 5119654
B Flue Extension 1000mm 5111074
C Flue Bend 93° 5111075
D Flue Bend (pair) 135° 5111085
U Pipe Support (painted) 100Ømm 5111080
R Vertical Flue Adaptor 5111070
P Wall Liner 5111067
S Flue Terminal Deflector 5111068
FLUE GROUP N
A3 B Twin Flue System 80mm diameter
E P E Flue Extension (pair) 1000mm 5111087
F Flue Bend (pair) 90° 5111072
G Flue Bend (2 pair) 135° 5111086
K,K1
J Vertical Flue Boiler Adaptor Kit 5111079
H Vertical Flue Adaptor 5111084
W Pipe Support (pair) 80mm 5111081
Y Twin Flue Termination Kit
(horizontal termination) 80mm 5120172

FLUE GROUP G
Concentric Flue System 80/125mm diameter
R
C D A4 Horizontal Flue Kit 5118580
B Straight Extension Kit 1000mm 5118584
D Bend Kit (pair) 135° 5118597
C Bend 91.5° 5118588
U Pipe support 125mm 5118610

FLUE GROUP A, N, G
Vertical Flue Kits
K Vertical Flue Terminal (use with 5111070) 5111078
G F K1 Vertical Flue Terminal 5118576
M
H L Pitched Roof Flashing 25°/50° 5122151
M Roof cover plate 246143
N Flat roof flashing 246144

U,W

N L

S
J

© Baxi Heating UK Ltd 2008 21


8.0 Flue Options

For Twin Flue Systems fit the adaptors as follows:-

8.4 Flue Duct Adaptor

1. Engage the flue duct adaptor on the boiler adaptor, making


sure that it is pushed down as far as possible.
Flue Duct Adaptor
Blanking Plate

8.5 Air duct adaptor

1. Undo the screws securing the blanking plate to the boiler top
panel. Discard the plate.

2. There are three restrictor plates supplied in the kit. One


marked ‘23’, one marked ‘27’ and a third unmarked. The
unmarked one must be used with this 24kW boiler. Discard the
other two. Position the unmarked restrictor as shown below.

3. Take one of the gaskets supplied in the kit and place on the
boiler top panel.

4. Align the appropriate restrictor as shown. Position the


second gasket over the restrictor.

5. Using the screws previously removed secure the inlet


adaptor to the top panel.
Air Duct Adaptor
6. Continue to fit the twin flue system.

Gasket
Position of Restrictor

Restrictor

Gasket

24 kW models

22 © Baxi Heating UK Ltd 2008


8.0 Flue Options

8.6 For Roof Terminals

1. In the case of a pitched roof 25 - 50 degrees, position the lead


Approx tile to replace/flash over existing roof tiling. Make an aperture in
1425mm the roof suitable for the lower tube of the roof terminal and
ensure the integrity of the roof cover is maintained. The
adjustable plastic collar can either be positioned on the lead tile
or the lower tube of the roof terminal prior to the final
positioning of the vertical flue through the tile. Check the collar is
correctly located to suit required roof pitch (either 25° to 38° or
37° to 50°). From inside the roof adjust the flue to a vertical
position and secure to the roof structure with the clamp supplied.

2. For flat roof installations the aluminium flashing must be


incorporated into the roof covering and the appropriate aperture
made in the roof decking. The vertical flue is lowered onto the
flashing making sure the collar of the flue locates securely with
Cut the same Air Duct
amount off the the flashing. (A mastic seal may be necessary). From inside the
Air Duct & roof, adjust the flue to a vertical position and secure to the roof
Flue Duct Flue Duct structure with the clamp supplied.

Push Fit Adaptor 8.7 Flue Dimensions

The standard horizontal flue kit allows for flue lengths between
100mm and 685mm from elbow to terminal (Fig. 19).

The maximum permissible equivalent flue length is:


10 metres (60/100 system)
20 metres (80/125 system)
m
5m
68
m 8.8 Flue Trim
0m
10
Flue Deflector 1. The rubber flue trim supplied may be fitted to either the
outside wall or on the inner wall of installation.

Fig. 19 8.9 Terminal Guard (Fig. 21)

1. When codes of practice dictate the use of terminal guards,


they can be obtained from most Plumbers’ and Builders’
Merchants.
Fig. 20
2. There must be a clearance of at least 50mm between any part
of the terminal and the guard.

3. When ordering a terminal guard, quote the appliance name


and model number.

4. The flue terminal guard should be positioned centrally over the


terminal and fixed as illustrated.

8.10 Flue Deflector (Fig. 20)

1. If required a flue deflector is available from your Potterton


stockist.

Fig. 21 2. Push the flue deflector over the teminal end and rotate to the
optimum angle for deflecting plume. Secure the deflector to the
terminal with screws provided.

© Baxi Heating UK Ltd 2008 23


93° Elbow/Plume
Outlet Assembly 9.0 Plume Displacement

60Ø Support 9.1 Plume Displacement Kit (Fig. 23)


O Ring Bracket
Kit No 5118638
Content of kit
0.9 metres
1 0.9m 60/100 Concentric Flue
60Ø Exhaust 1 1m 60 Dia Exhaust Flue Pipe
Flue Pipe 1 Adaptor
2 60 Dia Support Brackets
1 93° Elbow/Plume Outlet Assembly
60Ø Support
Bracket 1 Flexible Flue Trim
3 “O” Rings
1 ‘Jubilee Clip
Fig. 22 O Ring 1 Boiler Elbow
Flexible Flue
Trim
Adaptor 1. This kit is recommended for installations where the
‘Jubilee’ Clip condensate plume emitted from the flue may cause a nuisance
O Ring or affect the surroundings.

2. The terminal must be positioned outside the building with


the air inlet facing downward and outlet connection upwards.
Elbow
3. The plume outlet must always be at least 45° to the wall,
with the ‘peak’ uppermost to prevent rain entry (Figs. 24 &
60/100Ø 25), and be at least 2 metres above ground level. It must be
Concentric Flue
Fig. 23 secured as shown in Fig. 19. The plume outlet must also be at
least 500mm from the air inlet in any direction (Fig. 25).
Outlet must be at
45° least 45° from NOTE: The outlet must be positioned so that any
‘Peak’ Uppermost
45° wall face condensate plume is directed away from adjacent surfaces.
There must be a constant fall along the entire length of the
flue system from the outlet back to the boiler.

4. It is possible to reduce or increase (with the addition of


extensions) the length of either or both the 60/100 concentric
and 60Ø exhaust.

5. Standard concentric flue extension kits may be added


between the boiler elbow and the terminal assembly.

6. The minimum length of the concentric flue is 100mm when


500mm Min. measured from the edge of the flue elbow.

IMPORTANT: The maximum equivalent length of


concentric flue is:- 8 metres
Fig. 24 Additional bends may be fitted in the concentric flue, but
the equivalent length must be reduced by 1 metre (93°
bend) or 0.5 metres (45° bend).
Air Inlet at Bottom
7. 60Ø 1 metre extensions (including support bracket), and
additional 93° & 45° elbows are available. Any additional 93°
& 45° elbows must be accounted for when calculating flue
Fig. 25
lengths.

NOTE: Permitted positions of the plume outlet relative to


doors, windows etc. are the same as for conventional
concentric flues as detailed in the main Installation &
Servicing Instructions and BS5440 Pt. 1. It is NOT
necessary to fit a terminal guard over the air inlet or the
plume outlet.

24 © Baxi Heating UK Ltd 2008


16 16

14
9.0 Plume Displacement
14

60 Ø Exhaust (metres) X
60 Ø Exhaust (metres) X

12 12
24 24
10 10

8
9.2 Determining Permissible Lengths
8

6 6

4 4 In the graph the solid line diagonal represents the


2 2 relationship between the concentric flue assembly (and any
0 0 extensions) and the 60Ø exhaust (and any extensions or
0 1 2 3 4 5 6 7 8 9
0 1 2 3 4 5 6 7 8 9 additional bends).
Concentric 60/100 Flue (metres) Y Concentric 60/100 Flue (metres) Y
Example 1 Example 2
Flue Lengths - Not Permissible Flue Lengths - OK Example 1 - Not Permissible
If, for instance, a concentric length of 6 metres was required
and the 60Ø exhaust needed to be 10 metres the graph
16 shows that this combination would NOT be permissible as
the intersection point would be above the solid diagonal line.
14
60 Ø Exhaust (metres) X

12
Example 2 - Flue Lengths OK
24 Where both lengths have been determined they can be
10 applied to the graph to check that the installation is
permissible. For example, if it was known that 2 metres of
8
concentric flue and 6 metres of 60Ø exhaust were required,
6 the values could be applied to the graph as shown in
Example 2.. As the point of intersection of the dotted lines is
4
below the solid diagonal line, the combination of lengths is
2 shown to be acceptable.

0
Example 3 - Flue Lengths OK
0 1 2 3 4 5 6 7 8 9 In the example shown in Fig. 4 assume that the concentric
Concentric 60/100 Flue (metres) Y part of the flue needs to be 8 metres long. Find the position
Example 3 of ‘8’ on the horizontal axis of the graph and then project
Flue Lengths - OK upwards to the solid diagonal line. This is represented by the
vertical thick dotted line. Where this dotted line intersects
with the solid diagonal line on the graph, project across to
the vertical axis. As can be seen this corresponds with 6
metres. Therefore, the total equivalent length of the 60Ø
exhaust can be up to 6 metres. Any bend equivalencies must
be accounted for i.e. 93° bends are equal to 1 metre, each
45° bend to 0.5 metres.

Support
60Ø Exhaust Bracket

X
45° Elbow
Y Flue Length - Worked Example

In Fig. 27 opposite an additional 93° bend and pair of 45°


93° Elbow
elbows have been included in the 60Ø exhaust.
1 metre Extension Also 3 straight extension pieces have been used.
Concentric 60/100 Flue
To calculate total length:-
1 metre supplied in kit Length of 60Ø supplied in kit = 1 metre
3 x 1 metre Extensions = 3 metres
Fig. 26
1 x 93° Elbow = 1 metre
2 x 45° Elbow = 1 metre (0.5 metres each)

Total 60Ø = 6 metres


Concentric Flue

After consulting the table in Example 3 it can be determined


Additional Accessories that the concentric flue could be up to 8 metres long.

A - 93° Elbow 5121369


B - 45° Elbow (Pair) 5121370 Fig. 27
C - 1 metre 60Ø Extension 5121368

© Baxi Heating UK Ltd 2008 25


9.0 Plume Displacement

9.3 General Fitting Notes

1. Cut a hole in the external wall which the concentric flue


assembly will pass through. The hole should allow the flue
to fall back to the boiler at an angle of at least 1.5°.

2. When completed the terminal must be at least 2 metres


Min. 2 metres above ground level (Fig. 28).

3. Measure and cut to size the concentric assembly and any


extensions that are being used.

4. Insert the concentric assembly through the hole from


outside the building.

5. If required, the flexible flue trim should be fitted prior to


this as it cannot be fitted after. Use the large ‘Jubilee’ clip to
Fig. 28 secure the trim to the flue (See Fig. 29, trim shown
dotted), with the screw part of the clip at the bottom.

6. Connect any extensions or elbows that are being used


to the concentric assembly. Engage the extension, elbow
Flue Trim or concentric assembly in the boiler flue elbow. Fit the
boiler flue elbow to the boiler adaptor.

7. Ensure that the concentric assembly and any extensions


fall back to the boiler at an angle of at least1.5° and that
the external air inlet is to the bottom.

8. Use suitable brackets to support the concentric


assembly and any extensions, and make good inside and
Spigot outside.

Position of ‘Jubilee’ Clip 9. The 60Ø exhaust can now be fitted. Slide the adaptor
screw over the plain end of the 60Ø exhaust (Fig. 31) and engage
Fig. 29
the exhaust in the terminal. Slide the adaptor down over
50mm
the spigot. Mark and drill the adaptor, using a 2mm bit, as
shown in Fig. 30. Secure the adaptor to the spigot using
one of the screws supplied.

Adaptor
10. If it is necessary to shorten the 60Ø exhaust or any of
the extensions, the excess material must be cut from the
plain end of the pipe.

11. Determine the position of the 60Ø exhaust and mark


Fig. 31
on the wall a suitable position for the support bracket. If
extensions are being used, a support bracket is supplied in
each kit.
30mm Fig. 30
12. Drill the wall, and fit the bracket(s) using the plug and
screw provided.

13. Mark and drill the 60Ø exhaust, using a 2mm bit, as
shown in Fig. 32. Complete the installation of the 60Ø
30mm exhaust, securing in the brackets.
Fig. 32
14. Fit the 93° elbow/plume outlet and secure with the
two remaining screws supplied. Ensure the plume outlet is
at least 45° to the wall and that the ‘peak’ is uppermost
(Fig. 33).

Fig. 33
26 © Baxi Heating UK Ltd 2008
9.0 Plume Displacement
Plume Outlet
Elbow
9.3 General Fitting Notes (cont.)

15. For aesthetic purposes it is permissible to route the


60Ø exhaust in an enclosed box, but the air inlet and
plume outlet MUST remain in free air.

50 16. It is also possible to separate the plume outlet from the


0m
m 93° elbow to allow the flue to be installed as shown in
Mi
n.
Fig. 34.

17. To do this, first slacken the two screws retaining the


Fig. 34
plume outlet to the elbow, and remove the outlet (Fig. 35).
The elbow can now be used to connect the vertical to
horizontal 60Ø exhaust (Fig. 34). Retighten the screws in
the elbow.

18. The outlet can now be fitted into the female end of an
60Ø extension piece. It must be secured using two of the
screws supplied in the bag with the ‘Jubilee’ clip.

19. Mark the female end of the extension at 30mm as


Fig. 35 shown in two positions, directly opposite each other
(Fig. 36).

30mm 20. Using a suitable bit (e.g. 2mm), drill through the
extension and outlet. Secure using two of the screws
supplied.

21. The remaining screw must be used to secure the


adaptor to the concentric terminal.
Fig. 36

22. When the plume outlet is positioned under a balcony


or other projection (Fig. 37) it must protrude at least
200mm Min. 200mm (it is not necessary to extend it further than this).

23. When under balconies or projections it is permissible to


rotate the concentric flue length up to 70°, clockwise or
anti-clockwise (Fig. 38), if there is insufficient space to
connect vertically.

24.This will allow the connection of the exhaust to the


outlet spigot.

25. All other minimum & maximum dimensions must be


adhered to, and the air inlet positioned such that it will not
be subjetc to rain entry.

Fig. 37

70°

Concentric Flue Length


(shown end-on)
Outlet Spigot

Fig. 38
© Baxi Heating UK Ltd 2008 27
10.0 Installation

10.1 Unpacking & Initial Preparation

The gas supply, gas type and pressure must be checked for
suitability before connection (see Section 7.4).

NOTE: a small amount of water may drain from the


boiler in the upright position.
Fig. 39
1. Remove staples, open flaps and remove the cardboard
sheet. Remove the polystyrene side pieces and literature.
Two people can then lift out the boiler (Figs. 39 & 40)

2. After considering the site requirements


(see Section 7.0) position the fixing template on the wall
Fig. 40 ensuring it is level both horizontally and vertically.

3. Mark the position of the two most suitable fixing slots for
the wall plate and boiler lower fixing holes. It is preferable to
use the vertical fixing slots.

4. Mark the position of the centre of the flue hole (rear


exit). For side flue exit, mark as shown (Fig. 41).

5. If required, mark the position of the gas and water pipes.


Remove the template.

145mm
6. Cut the hole for the flue (minimum diameter 116mm).

7. Drill the wall as previously marked to accept the wall


plugs supplied. Secure the wall plate using the fixing screws.

8. Using a spirit level ensure that the plate is level before


finally tightening the screws.
For Side Flue Exit

Fig. 41 9. Connect the gas and water pipes to the valves on the
wall plate using the copper tails supplied. Ensure that the
Flushing Tube sealing washers are fitted between the connections.

Wall Plate
10.2 Flushing

1. Connect a tube to the central heating flow or return pipe


(Fig. 42).

2. Flush thoroughly (see System Details, Section 6.1).

Fig. 42
Central Heating Return

28 © Baxi Heating UK Ltd 2008


10.0 Installation

Wall Plate 10.3 Fitting The Boiler

1. Lift the boiler using the Lifting Points as shown by the


shaded areas (Fig. 43). The boiler should be lifted by TWO
PEOPLE. Engage the slots at the top rear of the boiler on the
wall plate(see Safe Manual Handling page 5).

2. Pull the lower polystyrene cap off the boiler (where used).
Ease the boiler forwards and remove the sealing caps from the
boiler connections.

NOTE: A small amount of water may drain from the boiler


once the caps are removed.

3. Insert the sealing washers between the valves and pipes on


the wall plate and the boiler connections. THE RUBBER
WASHERS MUST BE USED ON THE GAS CONNECTION.

4. Tighten all the connections.

Suggested Lifting Points Fig. 43


10.4 Fitting the Pressure Relief Discharge Pipe
shown as shaded area
(Fig. 44)

1. Remove the discharge pipe from the kit.

2. Determine the routing of the discharge pipe in the vicinity of


the boiler. Make up as much of the pipework as is practical,
including the discharge pipe supplied.

3. The pipework must be at least 15mm diameter and run


Pressure Relief Valve
continuously downwards to a discharge point outside the
building. See section 6.7 for further details.

4. Utilising one of the sealing washers, connect the discharge


pipe to the adaptor and tighten the nut.

5. Complete the discharge pipework and route it to the


outside discharge point.
Fig. 44
IMPORTANT: Make all soldered joints before connecting
to the pressure relief valve.

Discharge Pipe
10.5 Condensate Drain (see section 7.7)

1. Connect the condensate drain to the trap outlet pipe.

Ensure the discharge of condensate complies with any


national or local regulations in force (see British Gas
“Guidance Notes for the Installation of Domestic Gas
Condensing Boilers”.

2. The connection will accept 21.5mm (3/4in) plastic overflow


pipe which should generally discharge internally into the
household drainage system. If this is not possible, discharge into
an outside drain is acceptable.

© Baxi Heating UK Ltd 2008 29


10.0 Installation
m
5m
68
m 10.6 Fitting The Flue
0m
10
HORIZONTAL FLUE

1. The standard flue is suitable for lengths between 100mm


Fig. 45 minimum and 685mm maximum, as measured from the
edge of the flue elbow outlet to the joint between the
terminal and air duct (Fig. 45).

2. Locate the flue elbow on the adaptor at the top of the


boiler. Set the elbow to the required orientation (Fig. 47).
The elbow is fully engaged when there is a distance of
20mm from the adaptor to the indicator line (Fig. 46).
20mm
NOTE: The flue elbow is angled at 93 degrees to
ensure a fall back to the boiler.
Wall Thickness
Indicator line
3. Measure the distance from the outside wall face to the
Fig. 46
elbow. This dimension will be known as ‘X’ (Fig. 48).

Flue Elbow
(X) 4. To dimension ‘X’ add 50mm. This dimension to be
known as ‘Y’.
Apply Lubricant for
ease of assembly. IMPORTANT: Check all dimensions before cutting.
Ensure Elbow is fully
engaged into Boiler Adaptor
5. Mark dimension ‘Y’ on the flue as shown (Fig. 49).
Adaptor Carefully cut the waste material from the flue, ensuring that
the ducts are square and free from burrs.

Fig. 47

(X) Wall Thickness

Fig. 48

Waste Y

Flue
Fig. 49

30 © Baxi Heating UK Ltd 2008


10.0 Installation
Inner Flue Support Bracket
10.6 Fitting the Flue (Cont)

6. The inner flue duct support bracket may be in the waste


portion of the flue. In this case retrieve the bracket before
discarding the waste.

Fig. 50 7. Take the inner flue support bracket (if not already fitted)
and engage it over the flue duct. This will centralise the flue
and air ducts, and ease assembly (Fig. 50).

8. Insert the flue through the hole in the wall. Fit the elbow
Apply Lubricant for to the boiler adaptor, ensuring that it is pushed fully in.
ease of assembly.
Ensure Flue is fully 9. Draw the flue back through the wall and engage it in the
engaged into Flue elbow. It may be necessary to use soap solution or similar
Elbow to ease assembly of the elbow adaptor and flue (Fig. 51).

10. Ensure that the terminal is positioned with the slots to


the bottom (Fig. 52).

IMPORTANT: It is essential that the flue terminal is fitted


as shown to ensure correct boiler operation and prevent
water entering the flue.

11. Make good between the wall and air duct outside the
building.

12. Fit the flue trim if required, and if necessary fit a terminal
guard (see Section 8.8 & 8.9).
Slots at bottom
Fig. 52

CONCENTRIC VERTICAL FLUE

Fig. 51 13. Once the length of the vertical concentric extension has
been determined mark and carefully cut off the excess
material. The cut end MUST be square and free of burrs to
ensure correct insertion into the boiler adaptor.
25mm
14. Measure 25mm from the end of the flue extension and
apply a length of tape around the outer duct (Fig. 53).

Extension 15. Engage the extension into the adaptor up to this


position (Fig. 54). Once the installation of the flue is
complete and all support brackets are securely in place
Fig. 53
remove the tape.
Cut End Tape

Adaptor

Apply Lubricant for


ease of assembly.
Ensure Extension is
fully engaged into
Boiler Adaptor

Fig. 54

© Baxi Heating UK Ltd 2008 31


10.0 Installation

10.7 Making The Electrical Connections

The boiler is fitted with a 1.3m length of 3 core cable. This


can be connected to the fused 3A 230V 50HZ supply.

NOTE: Both the Live and Neutral connections are fused.

To connect an external control proceed as follows:-


Terminal Block Cover 1. Slacken the facia panel securing screws and lift the
outercase panel so that its securing tabs are clear of the
facia. Remove the panel.

2. Completely undo the screws securing the facia panel and


hinge it down (Fig. 55).

3. Undo the terminal block cover securing screw and


remove the cover (Fig. 55).
Fig. 55
4. Slacken the unused cable clamp on the LH side of the
Fig. 56 boiler chassis (Fig. 56). Insert the external control wiring
Cable Clamp Facia Panel
through the clamp and route it to the terminal block.

5. Refer to the instructions supplied with the control.

IMPORTANT: The room thermostat MUST be suitable


Fused Spur
L N
for 230V switching.

Room ‘Stat
N
NOTE: An external frost thermostat cannot be used
with the optional integral timer.

bk 1 6. Remove the link between terminals 1 & 2. The 230V


supply at terminal 2 must be connected to the thermostat.
230V bk 2 The switched output from the thermostat must be
g/y connected to terminal 1 (Fig. 57). If the room thermostat
being used incorporates an anticipator it MUST be wired as
shown in Fig. 57.
b
N
7. Ensure that the external control input cable(s) have
br
L sufficient slack to allow the control box to drop down.
Tighten the cable clamp on the boiler chassis.
Fig. 57
8. Replace the terminal block cover, routing the external
Frost Thermostat
control input cable(s) through the second cut-out.
Fused Spur
L N

Room ‘Stat
230V 10.8 Preliminary Electrical Checks
N

1. Prior to commissioning the boiler preliminary electrical


bk 1
system checks should be carried out.

230V
bk 2 2. These should be performed using a suitable meter, and
External Clock g/y
include checks for Earth Continuity,
Resistance to Earth, Short Circuit and Polarity.

b
N

br
L

NOTE: The 230V switched signal for external controls


(Frost Stat - Room Stat - Timer) must always be taken
from terminal 2 at the boiler. Live, Neutral and Earth to
power these controls must be taken from the Fused Spur.

32 © Baxi Heating UK Ltd 2008


Heat Exchanger
Automatic Air Vent
11.0 Commissioning
Fig. 58
11.1 Commissioning the Boiler

1. Reference should be made to BS 5449 Section 5 when


commissioning the boiler.

2. Open the mains water supply to the boiler.

IMPORTANT: The heat exchanger air vent on top of


Screw
the boiler (Fig. 58) MUST be opened before filling the
primary system.

3. Open all hot water taps to purge the DHW system.


Pump
Automatic Air
Vent 4. Ensure that the filling loop is connected and open, then
open the heating flow and return valves on the boiler.

5. Open the screw on the automatic air vent on the pump


body (Fig. 59).

6. The system must be flushed in accordance with BS 7593


(see Section 6.2) and the flushing agent manufacturers
instructions.

7. Pressurise the system to 1.5 bar (Fig. 60) then close and
2
Fig. 59 Pump disconnect the filling loop.
1 3

0 4 8. Turn the gas supply on and purge according to in GB


bar
BS 5482-1 and in IE I.S. 813 “Domestic Gas Installations”.
Selector Switch
Fig. 60 Pressure Gauge 9. Test for gas soundness.
Display

10. Hinge the facia panel upwards and refit the case front
panel. Tighten the securing screws.
2
Reset
1 3
11. Turning either of the temperature control knobs will set
0 4
bar
the relevant temperature. When the knob is turned the
display will alter and show the selected temperature. After a
few seconds the display reverts to show the current boiler
temperature (Fig. 61).
Central Heating Domestic Hot Water
Temperature Control Temperature Control
Fig. 61

© Baxi Heating UK Ltd 2008 33


11.0 Commissioning

11.2 Checking

1. The gas valve is factory set and the burner pressure cannot
x2 be measured as it is altered by suction of the fan and
modulates as demand on the boiler alters. The gas supply
pressure should be 37mb.

2. If necessary the gas rate may be checked after running the


boiler for 10 minutes with any other appliances and pilot
lights turned off.

3. Ensure that the integral timer and any external controls are
Central Heating Domestic Hot Water calling for heat, and the selector switch is in the central
Temperature Control Fig. 62 Temperature Control heating and hot water position ( ). The current boiler
temperature is shown on the display.

4. To check the gas rate it is necessary to set the boiler to


‘Calibration Mode’.
Selector Switch Display
5. Turn both temperature control knobs fully anticlockwise,
then quickly turn the DHW temperature knob 1/4 clockwise
twice and back fully anticlockwise (Fig. 62).
2
Reset
1 3

0 4
6. The display will now alternate between ‘SF’ and the
bar

current boiler temperature and both green LEDs will flash


(Figs. 63 & 64).

Central Heating Domestic Hot Water 7. Turn CH temperature control knob fully clockwise. As the
Temperature Control Temperature Control knob is turned the display will change from ‘0’ to ‘00’ (Fig. 65)
indicating maximum rate, then revert to ‘P’ alternating with
the current boiler temperature (Figs 66 & 67).

8. A gas rate measurement may now be made. Approximate


values are:-
24 model 1.92 kg/h

9. The ‘Calibration Function’ is active for 20 minutes unless


the maximum CH temperature is exceeded.

Fig. 63 10. The function can be disabled at any time by turning the
Fig. 64
DHW temperature knob.

Fig. 65

Fig. 66 Fig. 67

34 © Baxi Heating UK Ltd 2008


12.0 Completion

12.1 Completion
Case Front Panel
1. Instruct the user in the operation of the boiler and
system explaining the operational sequence.

2. Set the central heating and hot water temperature


control knobs to the requirements of the user.

3. Carefully read and complete all sections of the


Benchmark Commissioning Checklist at the rear of this
publication that are relevant to the appliance and
installation. These details will be required in the event of
any warranty work. The publication must be handed to the
user for safe keeping and each subsequent regular service
visit recorded.

4. For IE, it is necessary to complete a “Declaration of


Conformity” to indicate compliance with I.S. 813. An
example of this is given in I.S. 813 “Domestic Gas
Installations”. This is in addition to the Benchmark
Commissioning Checklist.

5. Hand over the Users Operating, Installation and


Servicing Instructions giving advice on the necessity of
regular servicing.

Facia Panel
Fig. 68

© Baxi Heating UK Ltd 2008 35


13.0 Servicing

13 .1 Annual Servicing

Case Front Panel 1. For reasons of safety and economy, it is recommended that
the boiler is serviced annually. Servicing must be performed by
a competent person in accordance with B.S. 7967-4:2007.

If a suitably calibrated combustion analyser is available it


may not be necessary to perform a full strip down of the
appliance. Proceed as follows.
Check for/inspect:-
Evidence of leakage of products of combustion
Water leaks
Heat stress
Deterioration such as corrosion
Visible condition of seals and joints
Flue system and ventilation
Condensate drain system
Operation at designed maximum heat input
Fig. 69
If the above are satisfactory perform a combustion check
The CO/CO2 ratio must be less than 0.004 and the CO2
Facia Panel Securing
should be 10% ± 0.2 (max. rate) and 9.5% ± 0.2 (min.
Screws
rate). This can be adjusted - see Section 15.0 - if the
readings are incorrect. When correct combustion
readings cannot be achieved by adjustment a full strip
down must be performed - see below. Carefully check
items such as the burner, injector and heat exchanger
for blockage or damage, rectifying as necessary. Re-
check the combustion. Once satisfactory readings have
been achieved and any other defects corrected complete
the relevant Service Interval Record section of the
Benchmark Commissioning Checklist at the rear of this
publication.

Where no suitable analyser is available a strip down


service must be performed as described below.

2. After servicing, complete the relevant Service Interval


Record section of the Benchmark Commissioning Checklist at
the rear of this publication.

If a full strip-down is to be performed proceed as follows:-

3. Ensure that the boiler is cool.

4. Ensure that both the gas and electrical supplies to the


boiler are isolated.
Inner Door
Fig. 70
Panel
5. Slacken the screws securing the facia panel. Lift the
outercase panel so that its securing tabs are clear of the facia.
Remove the panel, allowing the facia to hinge down (Fig. 69).

6. Remove the screws securing the inner door panel. Lift the
panel slightly to disengage it from the studs on top of the case
(Fig. 70).

7. Unscrew the sump from the bottom of the condensate trap


assembly (Fig. 71).
Sump
8. Remove any deposits from the sump and trap. Clean as
necessary and replace the sump.
Fig. 71
36 © Baxi Heating UK Ltd 2008
13.0 Servicing

13.1 Annual Servicing (Cont)

9. Undo the nut on the gas inlet pipe to the venturi (Fig. 73)
Fan, Collector and Cover
Assembly and pull the sensing pipe off the fan.

10. Disconnect the electrode leads, noting their position,


and the fan electrical plugs.

Electrode 11. Undo the four nuts retaining the combustion box cover
Leads to the heat exchanger.

12. Carefully draw the fan, collector and cover assembly


Fig. 72
forward, being careful to retain the injector in the venturi
(Figs. 72 & 73).

Venturi 13. Clean any debris from the heat exchanger and check
that the gaps between the tubes are clear.
Injector
14. Inspect the burner, electrodes and insulation, cleaning or
replacing if necessary. Clean any dirt or dust from the air
box.

15. Reassemble in reverse order.

NOTE: The sensing pipe must be reconnected to the


fan, not the venturi.
Fig. 73 Gas Inlet Pipe

DHW Filter (Fig. 75)


16. If the flow of domestic hot water is diminished, it may
be necessary to clean the filter.

17. Initially check the cold water inlet tap filter.

18. Turn the tap off and draw off from a hot tap. Undo the
Restricter blanking cap and remove the threaded bush (Fig. 74).
Threaded Fig. 74
19. Extract the filter and rinse thoroughly in clean water.
Bush
Reassemble and check the flow. If required clean the
restricter filter as described below.

20. Pull off the Hall Effect sensor. Undo the restricter from
the inlet/return manifold (Fig. 75).
Filter
21. Rinse the filter thoroughly in clean water and reassemble
in reverse order.
Hall Effect
Sensor 22. Turn the selector switch fully anticlockwise against the
spring pressure to the reset position and hold for 5 seconds
Blanking Cold Water
Inlet Tap to reset the boiler.
Cap
Fig. 75 23. Complete the relevant Service Interval Record section of
the Benchmark Commissioning Checklist at the rear of this
publication and then hand it back to the user.

Hydraulic Inlet
Assembly

© Baxi Heating UK Ltd 2008 37


14.0 Changing Components

Bracket IMPORTANT: When changing components ensure that


both the gas and electrical supplies to the boiler are
isolated before any work is started. When the
Igniter component has been changed turn the selector switch
fully anticlockwise against the spring pressure to the
reset position and hold for 5 seconds to reset the boiler
Igniter Feed before recommissioning.
Plug
See Section 13.1 “Annual Servicing” for removal of case
panel, door etc.

ElectrodeL 14.1 Igniter (Fig. 76)


eads
1. Disconnect the igniter feed plug and the electrode leads,
Fig. 76 noting their positions.

2. Undo the screw securing the bracket to the boiler.

3. Remove the igniter and transfer the bracket to the new


component.

4. Reassemble in reverse order.

14.2 Spark and Sensing Electrodes (Fig. 77)

1. Disconnect the electrode leads, noting their positions.

2. Remove the retaing screws securing each of the


electrodes to the combustion box cover and remove the
electrodes.

3. Check the condition of the sealing gasket and replace if


necessary. Reassemble in reverse order.

Spark
Electrode

ElectrodeL
eads
Sensing
Electrode

Fig. 77

38 © Baxi Heating UK Ltd 2008


14.0 Changing Components

14.3 Fan (Fig. 79)

1. Undo the nut on the gas inlet pipe to the venturi (Fig. 79)
and pull the sensing pipe off the fan.

2. Disconnect the electrode leads, noting their position and


disconnect the fan electrical plugs.

3. Undo the screws securing the collector to the cover (33


models) or extension piece (24 & 28 models).

4. Remove the collector and fan assembly, being careful to


retain the injector in the venturi.

5. Undo the screws securing the fan to the venturi and fit the
new fan, replacing the seal if necessary.

6. Examine the burner gasket and replace if necessary.


Venturi
7. Reassemble in reverse order, ensuring that the injector is
in place and the sensing pipe is connected to the fan.
Injector

14.4 Venturi (Fig. 78)


Cover
1. Remove the collector and fan assembly as described in
section 14.3.

Fig. 79 Gas Inlet Pipe 2. Extract the injector from the venturi.

3. Undo the screws securing the fan to the venturi and the
venturi to the collector.

Burner Important: When fitting the new venturi, ensure the arrows
Gasket
on it’s base point into the collector (Fig. 84).

4. Examine the seals and burner gasket, replace if necessary.


Gas Inlet
5. Reassemble in reverse order, ensuring that the injector is
in place.
Fan

Venturi 14.5 Injector (Fig. 78)

Injector
1. Remove the collector and fan assembly as described in
Collector section 14.3.
Fig. 78
2. Extract and replace the injector and reassemble in reverse
order.

Fig. 80
When fitting the venturi
ensure that the arrow is
pointing forward

© Baxi Heating UK Ltd 2008 39


Cover
14.0 Changing Components

14.6 Burner (Fig. 81)


Burner
1. Undo the screws securing the collector to the venturi and
Gasket extension piece. Remove this extension piece from the
cover.
Extension Piece
2. Withdraw the burner from the cover and replace with
the new one.

3. Examine the gasket, replacing if necessary.

Venturi 4. Reassemble in reverse order.

14.7 Insulation (Fig. 82)

Collector 1. Remove the electrode leads, noting their positions. Also


remove the electrodes as described in section 14.2.
Fig. 81

2. Undo the screws securing the collector to the venturi and


the nuts holding the cover to the heat exchanger. Draw the
collector and cover assembly away.

3. Remove the cover insulation piece.

4. Fit the new insulation carefully over the burner and align
it with the slots for the electrodes.

5. The rear insulation is retained by a screw and large


washer, remove these and draw the insulation out of the
heat exchanger.

6. Examine the cover seal and replace if necessary.

Heat
Exchanger

Rear
Insulation

Spark
Electrode

Venturi
Cover
Insulation
Seal

Fig. 82
Collector

Electrode Sensing
Leads Electrode

40 © Baxi Heating UK Ltd 2008


14.0 Changing Components
Electrical
Plug 14.8 Flue/Heat Exchanger Thermostat Sensor
Flue/Heat Exchanger
Thermostat Sensor (Fig. 83)

1. Ease the retaining tab on the sensor away and disconnect


the electrical plug.

2. Turn the sensor 90° anticlockwise to remove - it is a


bayonet connection.

3. Reassemble in reverse order.

Fig. 83
14.9 Water Pressure Sensor (Fig. 85)

1. Drain the primary circuit.

2. Disconnect the two wires from the sensor.

3. Undo the nut on the flow pipe securing and sealing the
sensor.

4. Remove the sensor, examine the sealing washer, replacing if


necessary.

5. Reassemble in reverse order. The component is not


polarised - either wire will fit each terminal.

14.10 Central Heating Temperature Sensor (NTC)


Flow Pipe (Fig. 84)
Central Heating
Temperature Sensor 1. Ease the retaining tab on the sensor away and disconnect
the electrical plug.

2. Unscrew the sensor from it’s pocket and reassemble in


reverse order. The plug will only fit one way.

14.11 Safety Thermostat (Fig. 85)

1. Pull the plug off the thermostat.

Safety Thermostat
2. Remove the screws securing the thermostat to the
mounting plate on the flow pipe.

3. Reassemble in reverse order, ensuring that the plug is


Fig. 84 pushed fully on.

14.12 DHW Temperature Sensor (NTC) (Fig. 85)

1. Turn off the mains cold water supply tap and draw off the
residual domestic hot water.
Pressure Sensor Plate Heat
Exchanger 2. Ease the retaining tab on the sensor away and disconnect
the electrical plug.

3. Unscrew the sensor from the plate heat exchanger


manifold. Examine the sealing washer,replacing if necessary.

Fig. 85 DHW Temperature 4. Reassemble in reverse order. The plug will only fit one way.
Sensor

© Baxi Heating UK Ltd 2008 41


14.0 Changing Components
Heat Exchanger
Air Vent
14.11 Heat Exchanger Automatic Air Vent (Fig. 86)

1. Drain the boiler primary circuit and unscrew the


automatic air vent from the pump body.

2. Examine the ‘O’ ring seal, replacing if necessary, and fit it


to the new automatic air vent.
Grommet
3. Reassemble in reverse order, transferring the grommet to
the new vent.

Fig. 86 4. Ensure that the grommet is is sealed correctly to the


boiler top panel.

14.12 Pump - Head Only (Fig. 87)

1. Drain the boiler primary circuit and remove the socket


head screws securing the pump head to the body and draw
the head away.

2. Undo the screw on the pump wiring cover and remove


the cover. Using a suitable flat bladed screw driver press the
Pump Wiring Pump Body cable securing levers downwards to release each wire after
Cover noting their position.

3. A standard replacement Grundfos 15-60 head can now


be fitted. Connect the pump wiring to the new head. The
pump speed must be set to 3 (Fig. 88).

Socket Headed 4. Reassemble in reverse order.


Screw

14.13 Pump - Complete (Fig. 88)

1. Drain the boiler primary circuit.


Pump Head
2. Undo the two screws securing the body to the pipe and
Fig. 87 manifold and draw the pump forwards.

3. Undo the screw on the pump wiring cover and remove


the cover. Using a suitable flat bladed screw driver press the
cable securing levers downwards to release each wire after
noting their position.
Pump Setting
4. Unscrew the automatic air vent from the pump body.
Fig. 88
Automatic Air 5. Connect the wiring to the new pump. Examine the ‘O’
Vent ring seals on the return pipe and manifold, replacing if
necessary.
Pump Wiring
Cover
6. Fit the air vent to the pump body and reassemble in
reverse order.

14.14 Automatic Air Vent (Fig. 89)

1. Drain the boiler primary circuit and unscrew the


automatic air vent from the pump body.

2. Examine the ‘O’ ring seal, replacing if necessary, and fit it


to the new automatic air vent.
Fig. 89
3. Reassemble in reverse order.
42 © Baxi Heating UK Ltd 2008
14.0 Changing Components

Gauge Retaining 14.15 Pressure Gauge (Figs. 90 & 91)


Bracket
1. Drain the boiler primary circuit and undo the nut on the
pressure gauge capillary.

2. Undo the screws securing the gauge retaining bracket.

3. Remove the bracket and gauge assembly. Depress the


barbs on the side of the gauge and remove the retaining
Pressure Gauge bracket.

Fig. 90 4. Examine the sealing washer, replace if necessary.

5. Reassemble in reverse order.

14.16 Hall Effect Sensor (Fig. 92)

1. Ease the sensor upwards off the hydraulic inlet manifold


assembly.

2. Disconnect the electrical plug from the sensor.

3. Connect the plug to the new sensor. Carefully fit the new
Fig. 91
Pressure Gauge sensor to the hydraulic assembly, ensuring it is fully down.
Capillary
Hall Effect
Sensor 14.17 Pressure Relief Valve (Fig. 93)

1. Drain the boiler primary circuit.

2. Disconnect the discharge pipe from the valve. Using a


suitable hexagon key undo the grub screw sufficiently to
release the valve.

3. Note the orientation of the valve, rotate it and withdraw


Hydraulic Inlet
Assembly
it from the manifold.

4. Fit the new valve and ‘O’ ring seal and set to the
previously noted orientation. Reassemble in reverse order.
Fig. 92

‘O’ ring seal

Grub Screw
Pressure Relief Valve

Fig. 93

Discharge Pipe

© Baxi Heating UK Ltd 2008 43


14.0 Changing Components

14.18 Plate Heat Exchanger (Fig. 94)

Plate Heat Exchanger 1. Drain the boiler primary circuit and remove the gas valve
as described in section 13.22.

2. While supporting the heat exchanger undo the screws


securing it to the brass manifolds.

3. Withdraw the heat exchanger upwards, taking care not to


damage any wires or controls.

Seals
4. There are four rubber seals between the manifolds and
LH Location Stud
heat exchanger which may need replacement.

Fig. 94 5. Ease the seals out of the manifold. Replace carefully,


Rubber Seal
ensuring that when the seal is inserted into the manifold it is
parallel and pushed fully in.

6. When fitting the new heat exchanger note that the left
hand location stud is offset towards the centre more than the
right hand one.

7. Reassemble in reverse order.

14.19 Diverter Valve - Motor Unit & Assembly


(Figs. 95 & 96)

1. To replace the motor unit, disconnect the multi-pin plug.

2. Pull off the retaining clip and remove the motor unit.
Motor Unit

3. The motor unit can now be replaced, or the valve


assembly removed.
Multi-pin Plug

Retaining Clip 4. Drain the primary circuit and draw off any hot water once
the isolating taps are closed.

5. Remove the spring clip retaining the bypass pipe to the


Valve rear of the assembly and under the flow pipe nut at the left
Assembly hand side.

6. Undo the nuts on the tap rail under the boiler. Remove
the screws securing the valve assembly to the boiler bottom
panel and plate heat exchanger.
Fig. 95
Pressure Sensor 7. Remove the valve assembly. Examine any seals or washers,
replacing if necessary. Transfer the DHW NTC to the new
valve and reassemble in reverse order.
Bypass Pipe

Spring Clip

Fig. 96
Securing Screw

44 © Baxi Heating UK Ltd 2008


14.0 Changing Components

14.20 P.C.B. (Fig. 98)

1. Note the settings of the temperature control knobs,


rotate them fully anticlockwise and carefully pull them off
the drive pins.

2. Completely undo the screws securing the control box


cover and release the cover retaining barbs from their slots.
Disengage the rear of the cover from the control box hinge
pin (Fig. 97).

3. Note the position of all plugs and wires on the P.C.B. and
disconnect them.

4. Undo the securing screws and remove the P.C.B. Transfer


Control Box Cover the control knob drive pins to the new P.C.B. and turn them
Fig. 97 fully anticlockwise.

P.C.B. 5. Reassemble in reverse order, ensuring that the


temperature controllers are reset to their previous positions.

Selector
14.21 Selector Switch (Fig. 98)
Switch
1. Note the setting of the selector switch knob and carefully
pull it off the facia.

Drive Pins 2. Completely undo the screws securing the control box
cover and release the cover retaining barbs from their slots.
Disengage the rear of the cover from the control box hinge
pin (Fig. 97).

3. Note the position of the electrical connections and the


orientation of the switch. Remove the electrical connections.

4. Remove the screws securing the switch to the facia panel.


Facia
5. Fit the new switch, ensuring that it is correctly positioned
and reassemble in reverse order.
Selector Switch Knob
Temperature Control Knobs

Fig. 98

© Baxi Heating UK Ltd 2008 45


Venturi Inlet
Pipe 14.0 Changing Components
Outlet Adaptor
14.22 Gas Valve (Fig. 99)

IMPORTANT: After replacing the valve the CO2 must be


Gas Valve
Sensing Pipe checked and adjusted as detailed in Section 15.0
Combustion Check. Only change the valve if a suitable
calibrated combustion analyser is available

1. Turn the gas cock off and undo the nut on the gas feed
Ignition Lead
elbow under the boiler.

2. Remove the screws securing the inlet pipe flange to the


boiler bottom panel.

3. Pull off the earth lead and sensing pipe.

4. Undo the nut on the gas pipe at the gas/air inlet and the gas
Valve
Inlet Pipe valve. Remove the pipe, taking care not to lose the sealing
washers. Remove the valve.

Gas Feed 5. Remove the outlet adaptor and inlet pipe and transfer them
Elbow to the new valve. Examine the ‘O’ ring seals, replace if
necessary.
Fig. 99
6. Reassemble in reverse order., ensuring that all seals are in
place and the injector is fitted.
Gas/Air
Adjustment Screw
NOTE: To assist the boiler to light prior to final setting,
use a suitable hexagon key to wind out the Gas/Air
adjustment screw until it is flush with the valve body, then
turn the screw 4 full turns clockwise (Fig. 100). If the boiler
will not light, or the correct CO2 cannot be achieved
contact the ‘heateam’ technical helpline.

14.23 Expansion Vessel (Fig. 101)


Fig. 100
1. Drain the boiler primary circuit and undo the nut on the
vessel connection pipe.

Retaining Bracket
2. Remove the screw retaining the air inlet pipe, and swing the
pipe to one side.

Expansion Vessel 3. Undo and remove the locknut securing the vessel spigot to
the boiler lower panel.

4. Remove the bracket and vessel from the boiler.

5. Locate the retaining bracket on the upper flange of the new


vessel and fit to the boiler.

6. Examine the sealing washer, replacing if necessary, and


reassemble in reverse order.

Lock Nut

Boiler Chassis

Fig. 101

46 © Baxi Heating UK Ltd 2008


15.0 Combustion Check

15.1 Checking the CO2


x2
IMPORTANT: The CO2 must only be checked and
adjusted if a suiutable calibrated combustion analyser is
available.

1. The combustion (CO2) may be checked using a suitably


calibrated analyser after running the boiler for several
minutes.

Central Heating Domestic Hot Water 2. To do this it is necessary to set the boiler to ‘Calibration
Temperature Control Fig. 102 Temperature Control Mode’.

Selector Switch Display 3. Ensure that all external controls are calling for heat. The
actual current boiler temperature is shown on the display.

4. Turn both temperature control knobs fully anticlockwise,


Reset
2 then quickly turn the DHW temperature knob 1/4 clockwise
1 3

0
bar
4 twice and back fully anticlockwise (Fig. 102).

5. The display will now alternate between ‘SF’ and the


current boiler temperature and both green LEDs will flash
Central Heating Domestic Hot Water (Figs. 103 & 104).
Temperature Control Temperature Control

6. Turn the CH temperature knob fully clockwise. As the


knob is turned the display will change, indicating the fan
speed.

7. The display will show ‘00’, indicating maximum rate, then


revert to ‘P ‘ alternating with the current boiler temperature
(Figs 105, 106 & 107).
Fig. 103 Fig. 104
8. Remove the plug from the flue adaptor test point. Insert
the analyser probe and allow time for the reading to settle
(Fig. 108).
The CO2 should be 10% ± 0.2

9. It is possible to alter the CO2 by adjustment of the gas


valve. Remove the plastic cover from the ‘Max Rate’
Fig. 105 Fig. 106 Fig. 107
adjustment screw. At maximum rate the ‘Max. Rate’
adjustment screw should be turned, using a suitable
Flue Adaptor Test hexagon key, until the correct reading is obtained (Fig. 109).
Point
Turning clockwise will reduce the CO2. Anticlockwise will
Plug increase the CO2.

Analyser Probe 10. The CO2 must then be checked at minimum rate. Turn
the CH temperature knob fully anticlockwise. As the knob is
Fig. 108 turned the display will change, indicating the fan speed.
When the display reads ‘ 0’ the boiler runs at minimum rate.
Max Rate
The CO2 should be 9.5% ± 0.2.
Adjustment Screw
Min Rate (cover removed)
11. With the boiler on minimum, the ‘Min. Rate’ adjustment
Adjustment Screw
(cap fitted) screw must be altered, using a suitable hexagon key, after
removing the cap (Fig. 109). If the CO2 is reset at either
boiler rate it must be rechecked at the other rate and also
adjusted if required.

12. The ‘Calibration Function’ is maintained for 20 minutes


unless the maximum CH temperature is exceeded. The
Gas Valve function can be disabled at any time by turning the DHW
Fig. 109 knob.

© Baxi Heating UK Ltd 2008 47


16.0 Electrical

16.1 Illustrated Wiring Diagram

Central Heating b
DHW NTC Sensor b
NTC Sensor Overheat Stat

Hall Effect
Sensor
r b
Water Pressure r b
Switch Flue Sensor 1
4
g 2
r br b 5
w
b bk g 3 Fan
g
1
2
b
g/y
b
b br

4
3
X400 2
X401 1
9 87 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1

Optional Timer

bk
4

Control PCB br
3

bk
2

X501
b
1

X9

1 2 1 2 3 4 5 1 2 3 4 5 6 7 8 9
X1 X2 X3

b r bk
br
Flame br
Sensing w Pump
br bk b
Electrode br b
br r
b
b
b br

r
Spark
L
N Generator bk

b a b

Diverter Valve
br

bk
g

w
br
Gas Valve

b
Link
Ignition
g/y b Electrode
br bk

E
N L
Mains Input Cable

br - brown g - green
bk - black g/y - green / yellow
b - blue r - red
w - white

48 © Baxi Heating UK Ltd 2008


17.0 Short Parts List

Short Parts List

Key G.C. Description Manufacturers


306 426 No. No. Part No.

326 Fan 5121447

426 Motor 3 Way Valve 248733

315 Igniter Electrode 5114702

316 Sensing Electrode 5114703


315 316
422 Gas Valve 5114734

311 404 Hall Effect Sensor 5114767

313 Burner 5122149

419 Water Pressure Switch 5114748

400 Plate Heat Exchanger 248048


624 419
415 Pump 248042
422
421 NTC Sensor 5114725

420 Overheat Thermostat 5114729

504 Pressure Gauge 248090

503 PCB 24 5132030

400

415

302 421 420

503
504

© Baxi Heating UK Ltd 2008 49


18.0 Fault Finding

18.1 Initial Fault Finding Checks

NOTE: When instructed to turn the


1. Check that gas, water and electrical supplies are available
selector to the reset position turn the
at the boiler.
selector switch fully anticlockwise against
the spring pressure to the reset position
2. Electrical supply = 230V ~ 50 Hz.
and hold for 5 seconds to reset the
boiler.
3. CH water system pressurised to 0.5 bar minimum when
the boiler is cold.

4. The preferred minimum gas pressure is 37 mbar.

5. Carry out electrical system checks, i.e. Earth Continuity,


Resistance to Earth, Short Circuit and Polarity with a suitable
meter.

NOTE: These checks must be repeated after any


servicing or fault finding.

6. Ensure all external controls are calling for heat and check
all external and internal fuses. Before any servicing or
replacement of parts, ensure the gas and electrical supplies
are isolated.

18.2 Error Codes

1. If a fault occurs on the boiler an error code may be shown


by the facia display.

2. The codes are either two or three digit, preceded by the


Table Of Error Codes letter 'E'. For example, code E133 will be displayed by 'E1'
alternating with '33'. E50 is shown as 'E' then '50'
E20 Central Heating NTC Fault
E28 Flue NTC Fault E20, E28 & E50 indicate faulty or incorrect components.
E50 Hot Water NTC Fault
E110 Safety Thermostat Operated E110 shows overheat of the primary water and E130
E119 Water Pressure Switch Not Operated overheat of the flue system.
E125 Circulation Fault (Primary Circuit)
E119 is displayed when the primary water pressure is less
E130 Flue NTC Operated than 0.5 bar.
E133 Interruption Of Gas Supply or Flame Failure
E160 Fan or Fan Wiring Fault E133 indicates that the gas supply has been interrupted,
E193 Pre-Circulation Fault ignition has failed or the flame has not been detected.

E125 is displayed in either of two situations:-


i) If within 15 seconds of the burner lighting the boiler
temperature has not changed by 1°.
ii) If within 10 minutes of the burner lighting the boiler
temperature twice exceeds the selected temperature by 30°.
In these instances poor primary circulation is indicated.

3. By turning the selector switch to the 'Reset' position for a


minimum of 5 seconds when E110, E130 & E133 are
displayed it is possible to relight the boiler.

4. If this does not have any effect, or the codes are displayed
regularly further investigation is required.

50 © Baxi Heating UK Ltd 2008


18.0 Fault Finding
Refer to Section 16.0 “Illustrated Wiring Diagram” for position of terminals and components
Central Heating - Follow operational sequence

Turn selector switch to NO


Go to section ‘A’
The display illuminates

YES

Error 110 flashing


Error 130 flashing YES Turn the selector switch to YES If the error 110 is still flashing.
Error 133 flashing reset position for 5 seconds Go to section ‘J’

NO

YES
Error 20, 28 or 50 flashing Go to section ‘E’

NO

YES
Error 119 flashing Go to section ‘C’
Ensure controls are set to
demand and verify the
NO NO contacts are closed

Turn Central Heating Ensure all controls (and


thermostat to Maximum. NO YES
integral clock if fitted) are Go to section ‘B’
Pump runs calling for heat
YES
Ensure that primary
YES
Error 125 or 193 flashing circulation is OK & that
there is no blockage
NO

3-way valve is open to Central NO


Go to section ‘K’
Heating circuit

YES

NO Error 160 flashing


Fan runs
Go to section ‘D’

YES

NO Error 160 flashing


Fan runs at correct speed
Go to section ‘L’

YES

Spark at ignition electrodes for Go to section ‘H’


NO YES
up to 5 seconds and for 3 Error 133 flashing Turn the selector switch to
attempts reset

Go to section ‘F’
YES
NO

YES Burner does not stay alights YES Error 133 flashing
Burner lights
after 5 seconds Go to section ‘I’

Check the Central Heating


YES NTC sensor
NO Go to section ‘E’

Burner output modulates to Error 130 flashing


maintain the temperature set Go to section ‘M’

YES
YES YES Pump continues to run for 3
YES Operation sequence
Burner goes out Fan stops after 10 seconds minutes
successful
(room thermostat open)
© Baxi Heating UK Ltd 2008 51
18.0 Fault Finding

Domestic Hot Water - Follow operational sequence

Turn selector switch to NO


Go to section ‘A’
The display illuminates

YES

Error 110 flashing YES Turn the selector switch to YES If the error 110 is still flashing.
Error 133 flashing reset position for 5 seconds Go to section ‘J’

NO

YES
Error 20, 28 or 50 flashing Go to section ‘E’

NO
YES
Error 119 flashing Go to section ‘C’

NO Go to section ‘B’
Turn Domestic Hot Water YES
thermostat to Maximum.
Open DHW tap fully. Is mains water filter and
DHW Hall Effect sensor NO YES assembly clean?
DHW flow rate more than 2
operated (red neon on the Is the magnetic detector free
l/min
sensor illuminated to move in the Hall Effect
YES sensor

3-way valve is open to NO


Go to section ‘K’
Domestic Hot Water circuit

YES
NO Error 125 flashing
Pump runs Go to section ‘B’
YES
NO Error 160 flashing
Fan runs
Go to section ‘D’

YES

NO Error 160 flashing


Fan runs at correct speed
Go to section ‘L’

YES

Spark at ignition electrodes for Go to section ‘H’


NO YES
up to 5 seconds and for 3 Error 133 flashing Turn the selector switch to the
attempts reset position for 5 seconds

Go to section ‘F’
YES
NO

YES Burner does not stay alights YES Error 133 flashing
Burner lights
after 5 seconds Go to section ‘I’
YES
NO Reduce DHW flow rate NO Clean DHW NTC sensor
Burner output modulates to
maintain the temperature set Burner modulates and DHW heat exchanger

YES NO Error 130 flashing


Go to section ‘M’
Close DHW tap

YES

DHW flow sensor senses no YES YES YES Operation sequence


Fan stops after 10 seconds Pump runs for 30 seconds
flow. Burner goes out successful

52 © Baxi Heating UK Ltd 2008


18.0 Fault Finding

Fault Finding Solutions Sections

A Is there 230V at:

NO
1. Main terminals L and N Check electrical supply
NO
2. Main terminal fuse Replace fuse NO
Display
Replace PCB
NO illuminated
3. Check wiring
PCB - X1 connector
terminals 1,2

B Is there 230V at:

YES NO
1. Pump If pump jammed, release Replace pump

2. PCB - X3 connector terminals 3 & 4 NO Replace PCB


YES
Change pump supply cable

C 1. CH system pressure less than 0.5 bar


YES
Re-pressurise system

NO Check connection water pressure


switch terminal YES Replace water
COM - NO and PCB connector pressure switch
X400 terminals 3,4

2. Check the tap of the automatic air NO


Open the automatic air vent
vent is opened

D 1.
Fan connections correct at fan. PCB -
X2 connector, is 230V AC across
YES
Fan jammed or faulty winding
YES
Replace fan
terminals 5 & 7

NO
Replace PCB

© Baxi Heating UK Ltd 2008 53


18.0 Fault Finding

E E20 or E50 - Temperature sensors faulty.


Cold resistance approximately
10kΩ @ 25° C (DHW and CH sensors) NO
20kΩ @ 25° C (Flue sensor) Replace sensor or PCB (E28)
(resistance reduces with increase in temp.)
E28 - Incorrect PCB fitted

F 1.
Check and correct the connection of the
tube between the venturi and gas valve

NO
2. Gas at burner Ensure gas is on and purged

PCB - X3 connector is 230V AC across YES


Replace gas valve
terminals 1 & 2
NO
Replace PCB

G 1.
Ensure that the Hall Effect Sensor is in position. YES Check the voltage between red wire and blue
Check the connection between the PCB - X400 wire is more than 5V DC
connector terminals 3,6,7 and the electronic sensor
NO YES

Replace PCB Replace Hall


Effect Sensor

H Check and correct if necessary


1. Ignition electrode and lead YES
Voltage at PCB - X2 connector is at
least 100V DC across terminals 2 & 5
NO
Replace PCB

2. Electrode connection (Note: from multimeter connect


YES
3. Spark gap and position ‘common’ to 2 & ‘volts’ to 5). Replace igniter
Check wiring

54 © Baxi Heating UK Ltd 2008


18.0 Fault Finding

I 1. Check the gas supply pressure:


Propane LPG should be 37 mbar

2. Check and correct if necessary


1. The mechanical set of the gas valve
(CO2 values - see instruction)
2. Flame sensing electrode and lead connections
3. Flame sensing electrode position
YES
Replace PCB
Flame current should be more than 0.5 μA
NO
Replace flame sensing electrode

J 1. Overheat thermostat operated or


faulty, i.e. continuity across
NO Allow to cool. Continuity
across thermostat terminals
YES
Replace safety thermostat
thermostat terminals more than 1.5 ohm

YES

Replace PCB

K Is there 230V at:

YES
1. Motor 3-way valve Replace motor 3-way valve

2. PCB - X3 connector terminals NO


Replace PCB
5 & 6 central heating mode
5 & 7 domestic hot water mode
YES
Change pump supply cable

L 1.
Fan connections correct at fan. YES
Replace fan
PCB - X401 connector terminals 5,6,7 & 8

M 1. Temperature sensors faulty.


Cold resistance approximately NO
10kΩ @ 25° C (CH sensor) Replace sensor
20kΩ @ 25° C (Flue sensor)
(resistance reduces with increase in temp.)

YES
2. Replace heat exchanger
If pump is running the heat exchanger could be
obstructed

© Baxi Heating UK Ltd 2008 55


19.0 Notes

56 © Baxi Heating UK Ltd 2008


19.0 Notes

© Baxi Heating UK Ltd 2008 57


BENCHMARK No. 5 1 3 1 7 8 9
1.0 Introduction

COLLECTIVE MARK GAS BOILER COMMISSIONING CHECKLIST


BOILER SERIAL No. NOTIFICATION No.
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROL TO HEATING ROOM T/STAT & PROGRAMMER/TIMER PROGRAMMABLE ROOMSTAT
TIME & TEMPERATURE CONTROL TO HOT WATER CYLINDER T/STAT & PROGRAMMER/TIMER COMBI BOILER
HEATING ZONE VALVES FITTED NOT REQUIRED
HOT WATER ZONE VALVES FITTED NOT REQUIRED
THERMOSTATIC RADIATOR VALVES FITTED
AUTOMATIC BYPASS TO SYSTEM FITTED NOT REQUIRED

FOR ALL BOILERS CONFIRM THE FOLLOWING


THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE BOILER MANUFACTURER’S INSTRUCTIONS?
THE SYSTEM CLEANER USED
THE INHIBITOR USED

FOR THE CENTRAL HEATING MODE, MEASURE & RECORD


GAS RATE m3/hr ft3/hr
BURNER OPERATING PRESSURE (IF APPLICABLE) N/A mbar
CENTRAL HEATING FLOW TEMPERATURE °C
CENTRAL HEATING RETURN TEMPERATURE °C

FOR COMBINATION BOILERS ONLY


HAS A WATER SCALE REDUCER BEEN FITTED? YES NO
WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED?

FOR THE DOMESTIC HOT WATER MODE, MEASURE & RECORD


GAS RATE m3/hr ft3/hr
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE) N/A mbar
COLD WATER INLET TEMPERATURE °C
HOT WATER OUTLET TEMPERATURE °C
WATER FLOW RATE lts/min

FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING


THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH
THE MANUFACTURER’S INSTRUCTIONS? YES

FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING


THE HEATING AND HOT WATER SYSTEM COMPLIES
WITH CURRENT BUILDING REGULATIONS
THE APPLIANCE AND ASSOCIATED EQUIPMENT HAS BEEN INSTALLED AND COMMISSIONED
IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS
IF REQUIRED BY THE MANUFACTURER, HAVE YOU RECORDED A CO/CO2 RATIO READING? N/A YES CO/CO2 RATIO
THE OPERATION OF THE APPLIANCE AND SYSTEM
CONTROLS HAVE BEEN DEMONSTRATED TO THE CUSTOMER
THE MANUFACTURER’S LITERATURE HAS BEEN LEFT WITH THE CUSTOMER

COMMISSIONING ENG’S NAME PRINT CORGI ID No.


1 © Baxi Heating UK Ltd 2008 SIGN DATE 1
58
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly
and that you complete the appropriate Service Interval Record Below.

Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service
as described in the boiler manufacturer’s instructions. Always use the manufacturer’s specified spare part when replacing all controls

SERVICE 1 DATE SERVICE 2 DATE


ENGINEER NAME ENGINEER NAME
COMPANY NAME COMPANY NAME
TEL No. TEL No.
CORGI ID CARD SERIAL No. CORGI ID CARD SERIAL No.
COMMENTS COMMENTS

SIGNATURE SIGNATURE

SERVICE 3 DATE SERVICE 4 DATE


ENGINEER NAME ENGINEER NAME
COMPANY NAME COMPANY NAME
TEL No. TEL No.
CORGI ID CARD SERIAL No. CORGI ID CARD SERIAL No.
COMMENTS COMMENTS

SIGNATURE SIGNATURE

SERVICE 5 DATE SERVICE 6 DATE


ENGINEER NAME ENGINEER NAME
COMPANY NAME COMPANY NAME
TEL No. TEL No.
CORGI ID CARD SERIAL No. CORGI ID CARD SERIAL No.
COMMENTS COMMENTS

SIGNATURE SIGNATURE

SERVICE 7 DATE SERVICE 8 DATE


ENGINEER NAME ENGINEER NAME
COMPANY NAME COMPANY NAME
TEL No. TEL No.
CORGI ID CARD SERIAL No. CORGI ID CARD SERIAL No.
COMMENTS COMMENTS

SIGNATURE SIGNATURE

SERVICE 9 DATE SERVICE 10 DATE


ENGINEER NAME ENGINEER NAME
COMPANY NAME COMPANY NAME
TEL No. TEL No.
CORGI ID CARD SERIAL No. CORGI ID CARD SERIAL No.
COMMENTS COMMENTS

SIGNATURE SIGNATURE

59
All descriptions and illustrations provided in this leaflet have been carefully prepared
but we reserve the right to make changes and improvements in our products which
may affect the accuracy of the information contained in this leaflet. All goods are
sold subject to our standard Conditions of Sale which are available on request.

P O T T E RTON
A Tr a din g D i v i s i o n of B a x i Heat i ng U K Lt d ( 3879156)
A D ivis io n o f B a x i Gro u p
Brooks House, Coventry Road, Warwick. CV34 4LL
After Sales Service 08706 017 017 Technical Enquiries 08706 049 049
Website www.potterton.co.uk
e&oe

IT Comp No 925.737.1

© Baxi Heating UK Ltd 2008 UK Comp No 5131789 - Iss 1 - 4/08

You might also like