EPC3000 Controller Data Sheet_HA032952 Issue 11
EPC3000 Controller Data Sheet_HA032952 Issue 11
eurotherm.com/epc3000
Specifications
General
Controller Function • Single loop panel mount PID controller range with autotune, on/off and valve positioning (no slidewire
required).
• Zirconia probe atmosphere control.
• Single loop profile/program.
• AC Mains voltage and 24Vdc power options.
PID Control • 2 PID sets are available as standard, with 8 as an optional extension (Each PID set offers a separate
proportional band for heat and cool operation).
• Enhanced Autotuning control with cutback function to minimize overshoot and oscillation. Fast reacting
precision control to setpoint changes or after process disturbances.
• Enhanced valve positioning (unbounded) algorithm.
• Gain scheduling allows PID selection for a wide range of operating situations, including deviation from
setpoint, absolute temperature, output level and others.
• AC supply voltage monitoring for feedforward function. Process Variable (PV) and Setpoint (SP)
feedforward functions.
Setpoint Programmer/Profiler • Options include 20 profiles of 8 steps (20x8), 10x24, 1x24 and 1x8.
(not available for the FM version) • Holdback (“guaranteed soak”), event outputs, time to target, ramp rate, dwell, step and call segment types.
• Communication addresses are compatible with Eurotherm 2400 Programmable Controller.
• Additional timer functions are available.
Limit Functions • EN ISO 13849-1: Performance Level (PL) “C” for PV input to Alarm function
• EN 14597 TR approved
• Meets Factory Mutual (FM) Approval Standard for Temperature Limit and Supervisory Switches Class
Number 3545 (when FM type selected).
Backup and Configuration Tools • Free Eurotherm iTools software for backup and configuration.
• USB Backup cable available for convenient desktop configuration and back up; powers the instrument
with or without a sleeve.
• iTools also connects using Ethernet Modbus/TCP and serial Modbus RTU.
“OEM Security” Helps protect instrument configurations from unauthorized viewing, cloning or backwards engineering.
Mechanical details
EPC3008 EPC3004
48mm (1.89”)
+ 1mm (0.04”) 96mm (3.78”) 101mm (3.97”)
+ 1mm (0.05”) EPC3016
90mm (3.54”)
90mm (3.54”)
+ 1mm (0.04”)
96mm (3.78”)
96mm (3.78”)
+ 1mm (0.04”)
48mm (1.89”)
I/O Specifications
Universal Process Inputs
Input Types Thermocouples, Pt100/Pt1000 RTD, 4-20mA, 0-20mA, 10V, 2V, 0.8V, 80mV, 40mV, zirconia (oxygen probe),
pyrometers. For other input types, contact your Eurotherm supplier for advice.
Accuracy ±0.1% of reading. When subject to the necessary field calibration, EPC3000 series controllers
manufactured by Eurotherm are suitable for use in Nadcap applications in all furnace classes as defined
in AMS2750F clause 3.3.1. For further information see eurotherm.com/certificates.
Sample Time • Process Inputs 50ms (20Hz)
• Thermocouple 62.5ms (16Hz)
• RTD 100ms (10Hz)
• Automatic cycle time selection
Mains Rejection (48-62Hz) • Series mode rejection >80dB.
• Common mode rejection >150dB
Sensor Break AC sensor break. Break detected within 3 seconds worst case.
Input Filtering OFF to 60 seconds filter time constant.
User Calibration User 2 point input adjust (offset/gradient), transmitter output scaling.
Thermocouple • K, J, N, R, S, B, L, T as standard, plus 2 downloadable custom curves
• Linearization accuracy: refer to User Guide
• Cold Junction (CJ) calibration accuracy: ±1.0ºC at 25ºC (±1.8ºF at 77ºF) ambient
• CJ ambient rejection ratio: better than 40:1 from 25ºC ambient
• External CJ selectable as 0, 45, 50ºC or measurable for EPC3004/EPC3008
Range Min -40mV -80mV -800mV -2V -10V 0Ω (-200ºC; -328ºF) -32mA
400Ω /4000Ω
Range Max +40mV +80mV +800mV +2V +10V +32mA
(850ºC; 1562ºF)
Thermal Stability from ±0.4μV/ºC ±0.4μV/ºC ±0.4μV/ºC ±0.4μV/ºC ±0.8μV/ºC ±0.01ºC/ºC ±0.16μA/ºC
25ºC (77ºF) Ambient ±13ppm/ºC ±13ppm/ºC ±13ppm/ºC ±13ppm/ºC ±70ppm/ºC ±25ppm/ºC ±113ppm/ºC
Resolution 1.0μV unfiltered 1.6μV 16μV 41μV 250μV 0.05 ºC (0.09 ºF) 0.6μA
Electrical Noise (peak to
0.8μV 3.2μV 32μV 82μV 250μV 0.05 ºC (0.09 ºF) 1.3μA
peak with 1.6s input filter)
Linearity Accuracy (best
0.003% 0.003% 0.003% 0.003% 0.007% 0.033% 0.003%
fit straight line)
Calibration Accuracy ±4.6μV ±7.5μV ±75μV ±420μV ±1.5mV ±0.31ºC (0.56ºF) ±3μA
@25ºC (77ºF) ambient ±0.053% ±0.052% ±0.052% ±0.044% ±0.063% ±0.023% ±1.052%
2.49Ω
Input Resistance 100MΩ 100MΩ 100MΩ 100MΩ 57kΩ –
(1% Shunt)
Bulb Current -– -– -– -– -– 190μA/ 180μA -–
TRIAC Module
Rating Min 40mA, 30V RMS, Max 0.75A @ 264V AC resistive.
Output Functions Time proportioned heat, time proportioned cool. SSR drive alarm and event outputs, interlock outputs,
other functions available using soft wiring.
Surge Rating Max current surge 30A (<10ms) Max continuous operating voltage 540V peak, 385V RMS.
Max surge voltage 800V peak, 565V RMS (< 10ms).
Communications
Communications
Ethernet • Shielded grounded RJ45 connection supporting 10/100BASE-T auto-sensing
• Certified to Achilles® communications robustness testing level 1
• Modbus/TCP, BACnet and EtherNet/IP Protocols
• Fixed IP address or DHCP
• Bonjour Auto-Discovery
Serial • EIA-485 Half duplex
• EIA-422/EIA-232 Full duplex
• Baud Rates 4800 (EI-Bisynch only), 9600, 19200
• Modbus RTU 8 data bits, odd/even/no parity selectable
• EI-Bisynch 7 data bits even parity fixed
Operator Interface
Display and Operation
Type High visibility LCD with backlight. Flat “washdown” membrane bezel with superior panel sealing, or
sculpted bezel with fully tactile keys.
Keyboard 100,000 operations typical
Main PV • EPC3016 4 digits, 3 decimal places
• EPC3008 4.5 digits, 4 decimal places
• EPC3004 5 digits, 4 decimal places; green/red bicolor (red in alarm)
Second Line 5 character 16 segment text or numeric
(EPC3004/EPC3008 only)
Third Line 16 segment scrolling text or numeric display
Text Character sets Roman, Simplified Cyrillic
• Program status indicator (ramp up, ramp down or dwell)
• Output indicators
Additional Display Functions • Alarm indication
• Units
• Bar graph (EPC3004, EPC3008 Controllers only)
• Communications activity indicator
HMI Functions • Configurable display contents
• Configurable scroll lists for operator/supervisor
• Configurable scrolling event messages
• Passcode level protection with lockout period
• 2 Programmable function keys (EPC3004, EPC3008 Controllers only)
300V ac 300V ac
Double Double
Serial/Ethernet
Comms
Power Rectification
Power
All Logic Inputs and
Supply
Outputs
Circuits
300V ac
Double µP &
System
Secondary PV Circuits Primary PV
Input Input
300V ac
Double
300V ac 300V ac
Double Double
0-20mA/0-10V Transmitter
Isolated Modules Power Supply
EPC3016 isolation
300V ac 300V ac
Double Double
Serial/Ethernet
Comms or
Remote Setpoint
Power Rectification
Power
Supply
Circuits All Logic Inputs and
outputs
µP &
300V ac
system
Double circuits
300V ac
Double
0-20mA/0-10V
CT Measurement
Isolated Modules
{
+ + 1A 3A
IO(1)
- - 1B 3B OP(3) Form C relay
(FM Relay)
+ + 2A Option 3C
IO(2) slot
- - see
2B VI
below
+ + +
AC supply 100-230Vac +/-15%, 48 to 62Hz L V+
2.49Ω
Low voltage supply 24Vac +10/-15%, 48 to 62Hz N V-
24Vdc +20/-15%, max 5% ripple voltage - - -
T/C Pt100 mA mV/V
Pt1000
Digital communications
EIA-232
EIA-485
EIA-422
Remote setpoint Input
Ethernet
CT CT NC HA CT E
C C RX+ HB C C
LA LA RX- HC LA LA
+
Logic Output (SSR drive) Relay Output Contact Input
-
+ 0-10V/0-20mA
TRIAC Output Current Transformer Input
Analog Output
-
Rear terminals
EPC3004 / EPC3008
+ + 1A 3A
IO(1)
- - 1B 3B OP(3) Form C relay
(FM Relay)
+ + 2A 3C
IO(2)
{
- - CMN
2B HD
LB HE A (+) Digital
communications
B (–) EIA-485
LC HF
Options
+ + 4A CT
IO(4)
- -
4B C
5A LA
+
24V
– 5B VI
AC supply + + +
100-230Vac +/-15%, 48 to 62Hz L V+
Low voltage supply 2.49Ω
24Vac +10/-15%, 48 to 62Hz N V-
- - -
24Vdc +20/-15%, T/C Pt100 mA mV/V
max 5% ripple voltage
Pt1000
DIO6 D6 E DIO6 D6 E
DIO7 D7 DIO7 D7
DIO8 D8 DIO8 D8
+ + + + + +
S+ S+
2.49Ω 2.49Ω
S- S-
- - - - - -
mV/V mA Pt100 T/C mV/V mA Pt100 T/C
Pt1000 Pt1000
+
Logic Output (SSR drive) Relay Output Contact Input
-
+ 0-10V/0-20mA
TRIAC Output Current Transformer Input
Analog Output
-
1 2 3 4 5 6 7 8 9 10 11 12
EPC3016
13 14 15
5 Future 13 Labels
X Not Fitted XXXXX None (Default)
Fnnnn Custom Label
6 Future
XX Future 14 Specials
XXXXXX None (Default)
16 17 18 19 20 21 22 23 24 25 26 27 28
27 Warranty
19 Future XX Standard Warranty
X Future
28 Certificate of Conformity
20 Future XX None Required
CERT1 Supplied With Certificate of Conformity
XX Future
EPC
Accessories
Model
EPCACC EPC Accessories
1 Accessories
RES2R9 2.49Ω Resistor
RES250 250Ω Resistor
RES500 500Ω Resistor
SNUBBER RC SNUBBER
USBCONF USB Backup Lead
CTR10A Current Transformer 10A Primary
CTR25A Current Transformer 25A Primary
CTR50A Current Transformer 50A Primary
CTR100A Current Transformer 100A Primary
ITOOLS iTools configuration Software