Applications
Frame supports
Modular construction
Ceiling supports and ceiling grids
Roof-mounted units
Air conditioning and ventilation systems
Industrial and plant engineering
Prefabricated modules
Combination with SiFramo/Siconnect
Electrical cable routing
4
siMetrix Installation Guidelines
Area of application
This guide enables the user to easily select suitable application solutions with typical Sikla support frames.
Technical advice
Our customer service representatives and application engineers are happy to provide you with further detailed information –
to answer your questions or to work with you to develop specific solutions using Sikla design software.
Disclaimer
This documentation is intended for the use of the recipient only and is the property of Sikla in all its parts. The technical
representations and all information are given to the best of our knowledge. Illustrations and drawings are non-binding.
Liability for printing errors or defects is excluded.
We reserve the right to make changes and improve the design, particularly in the interests of technical progress.
Product overview
The product range of the siMetrix system can be divided into four different blocks depending on the application, which are
explained separately in this installation manual:
Pipe connections 19
Combination of systems 23
09/2024
5
siMetrix Installation Guidelines
Profile PRO 46
Material:
Steel, HCP coating
(Corrosion category ≤ C4
according to DIN EN ISO 12944)
PRO 46
46mm
Hole pattern
(only PRO 46-P)
PRO 46-P
46mm
Ø8 mm
Profil with
internal gearing
50mm
Type Profile Modulus Second Moment of Area Radius of Gyration Area of Section Cut Lengths Z
Wy = 4,12 cm3 Iy = 9,49 cm4 iY = 1,60 cm
PRO 46 3,70 cm2 2m, 6m
Wz = 4,12 cm3 Iz = 9,49 cm4 iz = 1,60 cm Y
Wy = 3,46 cm3 Iy = 7,96 cm4 iY = 1,55 cm
PRO 46 -P 3,33 cm2 2m, 6m
Wz = 4,11 cm3 Iz = 9,45 cm4 iz = 1,68 cm
Precise, continuous
installation can be achieved on
all four sides simultaneously,
without limitation
Quick assembly
system for fastening
pipe clamps and other
components
07/2024
6
siMetrix Installation Guidelines
AF 17 / T50
Click!
Click!
3 Tighten screw
30 Nm
The central spring allows the connector to be pressed onto the profile and locked into place.
1 2 3
09/2024
7
siMetrix Installation Guidelines
Depending on the impact, one or two connectors must be used per connection
07/2024
8
siMetrix Installation Guidelines
Interlocking
Force and form fit guarantee
optimum safety at the
connection points when
installed correctly
Material
PE-LD, yellow
9
siMetrix Installation Guidelines
Profile Coupling PK 46
Self-drilling screws
SKB ST 5,5x16 HCP
200mm
(x8)
35mm
2
Symmetrical installation!
max. 170mm
= =
10
siMetrix Installation Guidelines
ADK 46 Screw
AF 17 / T50
Cantilever Bracket for pipe
or duct mounting on
Profiles PRO 46
CC
Scrope of delivery: installation
fully pre-assembled
Click!
11
siMetrix Installation Guidelines
AK CC 46-P
available lengths
3D constructions
STR 550/350
12
siMetrix Installation Guidelines
min.
50mm
M10
1 2
20 Nm
0 mm !
09/2024
13
siMetrix Installation Guidelines
Arrangement below
steel beams
In all arrangements, the load-bearing capacity of the steel beam must be taken into
account, and torsional stiffness in the case of a cantilevered arrangement.
Connection to
vertical steel beams
SB 46
CN 46
14
siMetrix Installation Guidelines
AK 46
15
siMetrix Installation Guidelines
in combination with:
Universal Joint UG, Blockset PBS
M10x30 and threaded rod GST M10 HCP
or alternatively with Tie Rod STR and
Blockset PBS M10x50
The Lateral Brace can optionally be attached MPK 46 is simply pressed onto
to the concrete wall with two M12 anchors the PRO 46 profile.
to achieve higher load values
07/2024
16
siMetrix Installation Guidelines
Connection to the
structure using Bolt
Scope of delivery:
Anchors AN BZ
pre-assembled
plus or heavy-duty
anchors M12.
90mm
Screws
AF 17 / T50
Depress both locking sides of the profile intake, insert the The locking
profile and release. mechanism must
engage in the profile 3
grooves. The screws
are then tightened.
20 Nm
2 (4x)
U-support
suspended
Elevated
assembly
Assembly examples
09/2024
17
siMetrix Installation Guidelines
Connection to the
structure using Bolt
Anchors AN BZ plus or
heavy-duty anchors M12.
min.
50mm
Suspended
arrangement of
Vertically mounted pipes on a a pipe traverse.
horizotally attached profile
SQF 350
(max. perm.
pressue load
F = 16kN)
SQF 500
Type t [mm] B [mm]
Suitable for equipment, pipes, t SQF 350 60 350
ventilation ducts or walkways.
SQF 500 90 500
B
07/2024
18
siMetrix Installation Guidelines
Pipe connections
GA 41-46
Material:
PA 6.0
PBS CC 46
M8, M10
PBH 46
M6, M8, M10,
M12, M16, 1/2"
MPK 46
Notice: M8, M10,
The point load capacity of the profile must M12, M16
not be exceeded.
Assembly 4
2 PBS CC 46
und PBH 46
15 Nm
Click!
3
1 Notice:
To disassemble, loosen
Hook/insert part the nut and press on the raised
with fixed claw. side of the upper part. The block
can then be removed from the profile.
3
Assembly
MPK 46 15 Nm
Click!
2
1
Push through
the threaded
rod and nuts. Tighten
MPK 46 is simply pressed onto hex nuts.
the PRO 46 profile.
09/2024
19
siMetrix Installation Guidelines
H3G-PL 46
AF 17
/ T50
H3G2-PL 46
Scope of delivery: fully pre-assembled
Click!
2
Press the Slide Set onto the profile
using the pre-assembled
retaining clips.
15 Nm
(2x)
Slide the Slide Set GS
to the desired position. Then tighten the screw
connection of the Profile
Clips (AF 17 or T50).
07/2024
20
siMetrix Installation Guidelines
Connection to the
structure using Bolt
Anchors AN BZ
plus or heavy-duty
anchors M10.
Notice:
For supported
installations from
DN 100 upwards, a
locking nut must be
mounted on the 3G
triple thread nut for
both Slide Sets.
Notice:
Connecting elements must have
sufficient rigidity. For larger
distances, threaded pipes
must be used.
21
siMetrix Installation Guidelines
(2x) nuts on
each side
22
siMetrix Installation Guidelines
Combination of systems
Screw CC-46
AF 17 CC-46 Screw
AF 17 assembly
/ T50 assembly
/ T50
Scope of
delivery: fully CC-27
pre-assembled assembly
CC-41
assembly
SA PRO 46 - 41 SA PRO 46 - 27
Combination with Assembly System Pressix CC 41 Combination with Assembly System Pressix CC 27
SA PRO assembly
1 Click!
20 Nm (2x)
Click!
SA PRO 46-27: 10 Nm
SA PRO 46-41: 40 Nm (2x)
Slide SA PRO to the Then insert the channel, press it
desired position. firmly and tighten the screws.
09/2024
23
siMetrix Installation Guidelines
Screw
AF 17
MPH PRO
41- 46 1
Click!
(CC-41)
Scope of delivery:
pre-assembled in a
set with 2x Speed Nut
40 Nm (2x)
2
Click!
1 (CC-46)
MPH PRO
46 - 41
pre-assembled
in a set with 2x
Blockset
2 15 Nm (2x)
07/2024
24
siMetrix Installation Guidelines
60 Nm
(4x)
Form-fitting connection to
Beam Section TP F using 4
Self Forming screws FLS F
60 Nm
(4x)
Notice: 20 Nm
The locking parts must be (4x)
pressed open completely.
09/2024
25
siMetrix Installation Guidelines
MPH
F 80 - 46
SA PRO
41 - 46
07/2024
26