0% found this document useful (0 votes)
15 views12 pages

NF Cal SD 187 Hfc227ea 00 Elv Room 2, Ground Floor, Grid 19 20 e F

The document provides a detailed flow calculation report for the Shield Clean Agent System (HFC-227ea) at the Zanzibar New Airport Terminal 2, designed by NAFFCO. It includes calculations for agent requirements, enclosure reports, and system acceptance metrics, ensuring compliance with UL and FM standards. Key data includes agent concentrations, nozzle specifications, and system discharge times, with all calculations performed on September 5, 2024.

Uploaded by

o.massawe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views12 pages

NF Cal SD 187 Hfc227ea 00 Elv Room 2, Ground Floor, Grid 19 20 e F

The document provides a detailed flow calculation report for the Shield Clean Agent System (HFC-227ea) at the Zanzibar New Airport Terminal 2, designed by NAFFCO. It includes calculations for agent requirements, enclosure reports, and system acceptance metrics, ensuring compliance with UL and FM standards. Key data includes agent concentrations, nozzle specifications, and system discharge times, with all calculations performed on September 5, 2024.

Uploaded by

o.massawe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Shield Clean Agent System Flow Calculation Software (HFC-227ea)

UL: EX27935 / Component of FM Approved System


System calculated within limits of Shield UL Listing and FM Approval

File Name: NF-CAL-SD-187-HFC227ea-00-ELV ROOM 2, GROUND FLOOR, GRID 19-20 E-


F.FC4

Consolidated Report
Customer Information
Company Name: ESTIM CONSTRUCTION
Address: TANZANIA

Phone:
Contact:
Title:

Project Data
Project Name: ZANZIBAR NEW AIRPORT TERMINAL 2
Designer: NAFFCO
Number:
Account:
Location:
Description: FLOW CALCULATION FOR SHIELD 200 SYSTEM

Designer Notes
PROTECTED AREA : ELV ROOM 2, GROUND FLOOR, GRID 19-20 / E-F

ENCLOSURE : ROOM VOID & CEILING VOID

SHOP DRAWING NO : NF--SD-187-HFC227ea-00

PREPARED BY : NPJ

CHECKED BY : RPK

APPROVED BY : Engr.MKS

Calculation Date/Time: Thursday, 5 September 2024, 8:45:11 AM


Copyright (c) Jensen Hughes, Inc.
Key ID: 1250720404

Page: 1 of 12
Consolidated Report
Enclosure Report

Elevation: 0 m (relative to sea level)


Atmospheric Correction Factor: 1 (NFPA 2001)
Enclosure 1 ROOM VOID
Enclosure Temperature: Number of Nozzles: 1
Minimum: 20.0 C Width: 3.05 m
Maximum: 20.0 C Length: 3.94 m
Max. Concentration: 7.28% (At 20.0 C) Height: 2.80 m
Design Concentration: Volume: 33.65 m ³
Adjusted: 7.17 % Non-permeable: 0.00 m ³
Minimum: 7.00 % Total Volume: 33.65 m ³
Min. Agent Required: 18.51 kg
Adjusted Agent Required: 18.99 kg

Calculation Date/Time: Thursday, 5 September 2024, 8:45:11 AM


Copyright (c) Jensen Hughes, Inc.
Key ID: 1250720404

Page: 2 of 12
Consolidated Report

Leakage Area vs Enclosure Pressure


350
Legend

E1-Pos (+)
E1-Neg (-)
300

250
Equivalent Leakage Area (cm²)

200

150

100

50

0
0 100 200 300 400 500 600
Enclosure Pressure (Pa)

Calculation Date/Time: Thursday, 5 September 2024, 8:45:11 AM


Copyright (c) Jensen Hughes, Inc.
Key ID: 1250720404

Page: 3 of 12
Consolidated Report
Enclosure 2 CEILING VOID
Enclosure Temperature: Number of Nozzles: 1
Minimum: 20.0 C Width: 3.05 m
Maximum: 20.0 C Length: 3.94 m
Max. Concentration: 7.07% (At 20.0 C) Height: 2.95 m
Design Concentration: Volume: 35.45 m ³
Adjusted: 7.17 % Non-permeable: 0.00 m ³
Minimum: 7.00 % Total Volume: 35.45 m ³
Min. Agent Required: 19.50 kg
Adjusted Agent Required: 20.01 kg

Leakage Area vs Enclosure Pressure


350
Legend

E2-Pos (+)
E2-Neg (-)
300

250
Equivalent Leakage Area (cm²)

200

150

100

50

0
0 100 200 300 400 500 600
Enclosure Pressure (Pa)

Calculation Date/Time: Thursday, 5 September 2024, 8:45:11 AM


Copyright (c) Jensen Hughes, Inc.
Key ID: 1250720404

Page: 4 of 12
Consolidated Report
Agent Source Report

Agent: HFC-227ea / Propellant N2


Cylinder Name: 52L DOT Cylinder
Cylinder Part Number: SD-52HFC-02
Agent Per Cylinder: 39.00 kg
Cylinder Pressure: 24.81429 bar
Fill Density: 0.750 kg/l
Number of Main Cylinders: 1
Number of Reserve Cylinders: 0

Cylinder Empty Weight: 52.40 kg


Weight, All Cylinders + Agent: 91.40 kg
Floor Area Per Cylinder: 0.13 m ²
Floor Loading Per Cylinder: 703 kg/m ²

Calculation Date/Time: Thursday, 5 September 2024, 8:45:11 AM


Copyright (c) Jensen Hughes, Inc.
Key ID: 1250720404

Page: 5 of 12
Consolidated Report
Parts Report

Total Agent Required: 39.00 kg


Cylinder Name: 52L DOT Cylinder (Part: SD-52HFC-02)
Number of Cylinders: 1
Nozzle
Nozzle Type Diameter Nozzle Area Part Number
E1-N1 180 Degree 20 mm 160.32 mm ² SD-N180-20
E2-N1 360 Degree 20 mm 150.86 mm ² SD-N360-20

Nozzle Drill Diameter Drill Size


E1-N1 5.4 mm 5.4 mm
E2-N1 4.9 mm 4.9 mm

Pipe &
Fittings Type Diameter Length Elbows (90) Elbows (45) Tees Unions
40T 20 mm 4.85 m 2 0 0 0
40T 32 mm 6.52 m 1 0 1 0
Other
Objects Name Quantity Part Number
50 mm Flex Hose - 90° Bend 1 SD-DH0050

System Acceptance Report

System Discharge Time: 9.4 seconds


Percent Agent In Pipe: 37.4%
Percent Agent Before First Tee: 31.4%
Dead Volume: 0.0% (0.00 kg)

Enclosure Number: 1
Enclosure Name: ROOM VOID
Minimum Design Concentration: 7.00%
Adjusted Design Concentration: 7.17%
Calculation Date/Time: Thursday, 5 September 2024, 8:45:11 AM
Copyright (c) Jensen Hughes, Inc.
Key ID: 1250720404

Page: 6 of 12
Consolidated Report
Adjusted Design Concentration: 7.17%
Predicted Concentration: 7.28%
Maximum Expected Agent Concentration: 7.28% (At 20.0 C)

Minimum Adjusted Predicted Average


Agent Agent Agent Nozzle
Nozzle Required Required Delivered Pressure

E1-N1 18.51 kg 18.99 kg 19.30 kg 9.356 bar

Total 18.51 kg 18.99 kg 19.30 kg

Enclosure Number: 2
Enclosure Name: CEILING VOID
Minimum Design Concentration: 7.00%
Adjusted Design Concentration: 7.17%
Predicted Concentration: 7.07%
Maximum Expected Agent Concentration: 7.07% (At 20.0 C)

Minimum Adjusted Predicted Average


Agent Agent Agent Nozzle
Nozzle Required Required Delivered Pressure

E2-N1 19.50 kg 20.01 kg 19.70 kg 10.478 bar

Calculation Date/Time: Thursday, 5 September 2024, 8:45:11 AM


Copyright (c) Jensen Hughes, Inc.
Key ID: 1250720404

Page: 7 of 12
Consolidated Report

Total 19.50 kg 20.01 kg 19.70 kg

Calculation Date/Time: Thursday, 5 September 2024, 8:45:11 AM


Copyright (c) Jensen Hughes, Inc.
Key ID: 1250720404

Page: 8 of 12
Consolidated Report

Pipe Network Report


Total Total
Pipe Start End Pipe Pipe Pipe Elevation Equivalent Nozzle Nozzle Nozzle Nozzle
Description Section Node Node Type Diameter Length Union Change Length Name Size Type Area
Cylinder - On Man. 0 2 50 mm 0.59 m 0 0.59 m 10.67 m
Flex Hose Man. 2 3 50 mm 0.53 m 0 0.27 m 5.36 m
Pipe Man./End 3 4 40T 32 mm 4.78 m 0 4.78 m 4.78 m
Elbow (90) System 4 5 40T 32 mm ------ 0 ------ 1.13 m
Pipe System 5 6 40T 32 mm 1.74 m 0 ------ 1.74 m
Tee System 6 7 40T 20 mm ------ 0 ------ 1.37 m
Pipe System 7 8 40T 20 mm 1.40 m 0 ------ 1.40 m
Elbow (90) System 8 9 40T 20 mm ------ 0 ------ 0.67 m
Pipe&Nozzle System 9 10 40T 20 mm 2.85 m 0 -2.85 m 2.85 m E1-N1 20 mm 180 Degree 160.32 mm ²
Tee System 6 11 40T 20 mm ------ 0 ------ 1.37 m
Pipe System 11 12 40T 20 mm 0.50 m 0 ------ 0.50 m
Elbow (90) System 12 13 40T 20 mm ------ 0 ------ 0.67 m
Pipe&Nozzle System 13 14 40T 20 mm 0.10 m 0 -0.10 m 0.10 m E2-N1 20 mm 360 Degree 150.86 mm ²

Pipe Network Report (Flow and Pressure)


Total Total
Pipe Start End Pipe Pipe Pipe Elevation Equivalent Nozzle Flow Rate Start End
Description Section Node Node Type Diameter Length Change Length Name Pressure Pressure
Cylinder - On Man. 0 2 50 mm 0.59 m 0.59 m 10.67 m 4.14 kg/s 13.490 bar 13.079 bar
Flex Hose Man. 2 3 50 mm 0.53 m 0.27 m 5.36 m 4.14 kg/s 13.079 bar 12.833 bar
Pipe Man./End 3 4 40T 32 mm 4.78 m 4.78 m 4.78 m 4.14 kg/s 12.833 bar 11.621 bar
Elbow (90) System 4 5 40T 32 mm ------ ------ 1.13 m 4.14 kg/s 11.621 bar 11.486 bar
Pipe System 5 6 40T 32 mm 1.74 m ------ 1.74 m 4.14 kg/s 11.486 bar 11.278 bar
Tee System 6 7 40T 20 mm ------ ------ 1.37 m 2.05 kg/s 11.278 bar 10.860 bar
Pipe System 7 8 40T 20 mm 1.40 m ------ 1.40 m 2.05 kg/s 10.860 bar 10.433 bar
Elbow (90) System 8 9 40T 20 mm ------ ------ 0.67 m 2.05 kg/s 10.433 bar 10.229 bar
Pipe&Nozzle System 9 10 40T 20 mm 2.85 m -2.85 m 2.85 m E1-N1 2.05 kg/s 10.229 bar 9.356 bar
Tee System 6 11 40T 20 mm ------ ------ 1.37 m 2.09 kg/s 11.278 bar 10.859 bar
Pipe System 11 12 40T 20 mm 0.50 m ------ 0.50 m 2.09 kg/s 10.859 bar 10.711 bar
Elbow (90) System 12 13 40T 20 mm ------ ------ 0.67 m 2.09 kg/s 10.711 bar 10.506 bar

Key ID: 1250720404


Page: 9 of 12
Consolidated Report
Total Total
Pipe Start End Pipe Pipe Pipe Elevation Equivalent Nozzle Flow Rate Start End
Description Section Node Node Type Diameter Length Change Length Name Pressure Pressure
Pipe&Nozzle System 13 14 40T 20 mm 0.10 m -0.10 m 0.10 m E2-N1 2.09 kg/s 10.506 bar 10.478 bar

Key ID: 1250720404


Page: 10 of 12
Consolidated Report

Key ID: 1250720404


Page: 11 of 12
Consolidated Report

Key ID: 1250720404


Page: 12 of 12